NYC Administrative Code RS 14-17
Minimum Equipment Foundation Mountings Requirements
Noncombustible Construction Equipment Classification Fuels Fire Resistance Rating Extension Beyond Equipment Low Temperature All fuels 2 hr. 18 in. on all sides Medium Gas and liquid fuels 3 hr. 3 ft. on all sides Temperature Solid fuels 3 hr. 3 ft. on all sides and 8 ft. on firing side and ash removal side High Temperature All fuels 4 hr. 10 ft. on all sides and 30 ft. at front or side where hot products are removed
Combustible Construction Exceptions Base (in.) Open Clearance Under Applying To: Type of Protection Mounted on Combustible Surface Ext. of Protection Beyond Eqt. All Sides (in.) Solid Fuel-Firing Side at Ash Removal Side (in.) Low temperature equipment 18 1.4 in. asbestos millboard 0 18 8 1/2 in. asbestos millbd. covered with no less than 0.24 Mfg's Standard Gauge Sheet 6 18 4 4 in. of hollow clay or concrete tile 0 18 0 2 courses of 4 in. hollow clay or concrete tile covered with 3/16 in. steel plate 0 18 Medium temperature equipment 24 4 in. of hollow clay or concrete tile 0 18 Boilers, furnaces, and warm air furnaces for heating one-family dwellings; and to floor mounted unit heaters 4 1/4 in. asbestos millboard covered with not less than 0.24 Mfg's Standard Gauge Sheet 6 18 0 4 in. of hollow clay or concrete tile 0 18 Commercial or restaurant type cooking equipment 18 A metal baffle between burner and floor 0 18 8 3/8 in. asbestos millbd. 6 18 4 4 in. of hollow clay or concrete tile 0 18 0 2 courses of 4 in. hollow clay or concrete tile covered with 3/16 in. steel plate 0 0 18 18 Domestic type floor mounted cooking and rm. heating eqpt., such as, stoves, ranges, space heaters, fuel fired steam or hot water radiators and hot water 18 4 A metal baffle between burner and floor 1/2 in. asbestos millbd. covered with not less than No. 24 Mfg's Standard Gauge Sheet 0 0 — 18
Notes for Combustible Construction:
Hollow tile shall be set with ends unsealed and joints matched so as to provide for the circulation of air through the tile. Where two courses of hollow tile are required, the tiles courses shall be laid at right angles to each other with the ends unsealed and joints matched so as to provide for the circulation of air through each course.
Low temperature equipment with a water cooled base and a grate area of less than 3 sq. ft., or low temperature equipment in which the combustion chamber is located at least 12 in. above the floor, may rest directly on a sheet metal base of not less than no. 14 manufacturer's standard gauge sheet steel without heat insulation on combustible construction.
Where the floor protection used does not provide a monolithic surface of steel, concrete, or cement, the side or surface where ashes are removed or where traffic or other usage would wear the protection away shall be covered with no. 24 manufacturer's standard gauge sheet steel or equivalent material.