NYC Administrative Code RS 10-1B MASONRY

ACI 530–92/ASCE 5–92—Building Code Requirements for Masonry Structures, as modified.

ACI 530.1–92/ASCE 6–92—Specifications for Masonry Structures, as modified.

MODIFICATIONS—The provisions of ACI 530–92/ASCE 5–92 shall be subject to the following modifications. The chapter and section numbers are from that standard.

Chapter 1—General Requirements.

Section 1.3—Approval of special systems of design or construction.

Delete this section.

Section 1.4—Standards cited in this code.

Section 1.4.1—Delete the words "ANSI A 58.1–82—Minimum Design Loads for Buildings and other structures".

Chapter 5—General Analysis and Design Requirements.

Section 5.2.2—Delete this section and substitute the following:

"5.2.2—Service loads shall be in accordance with the building code of the city of New York of which this standard forms a part, with such live load reductions as are permitted in the building code of the city of New York. The load provisions of the reference standard RS 9 shall be used."

Chapter 6—Design Allowing Tensile Stresses in Masonry.

Section 6.1.1—Delete this section and substitute the following:

"6.1.1—The provisions of this chapter are to be applied in conjunction with the provisions of Chapter 5—General Analysis and Design Requirements and Appendix A."

Section 6.4—Axial tension.

Add the following sentence at the end of section 6.4:

"Axial tension stress shall be resisted entirely by steel reinforcement in accordance with Chapter 7."

Chapter 7—Design Neglecting Tensile Strength of Masonry.

Section 7.1.2—Delete this section and substitute the following:

"7.1.2—The provisions of this chapter are to be applied in conjunction with the provisions of Chapter 5—General Analysis and Design Requirements and Appendix A."

Chapter 9—Empirical Design of Masonry.

Section 9.1.1.1—Seismic—Delete this section and substitute the following:

"9.1.1.1—Seismic—Empirical requirements may apply to the design or construction of masonry for buildings, parts of buildings or other structures located in New York City."

Section 9.1.1.2—Wind.

Delete this section and substitute the following:

"9.1.1.2—Wind—Empirical requirements shall not apply to the design or construction of masonry for buildings, parts of buildings, or other structures to be located in areas where the basic wind speed will result in a wind pressure that exceeds 20 psf."

Section 9.2—Height.

Add the following sentence at the end of section 9.2:

"However, members which are not part of the lateral force resisting system of the building are permitted to be designed in accordance with the provisions of Chapter 9 of reference standard RS 10–1B in buildings greater than 35 feet in height."

Section 9.9—Miscellaneous requirements.

Delete this section and add the following new Chapter 10:

"Chapter 10—Miscellaneous Requirements.

10.1—Chases and recesses—Masonry directly above chases or recesses wider than 12 inches shall be supported on lintels.

10.1.1—Where permitted—Chases and recesses shall be prohibited in any wall less than 12 inches thick and in the required area of piers and buttresses; except that where permitted in 8-inch walls, in residential buildings and in the apron under window openings, the maximum depth of chases shall be 4 inches.

10.1.2—Maximum size—The maximum permitted depth of a chase in any wall shall not be more than one-third of the wall thickness, and the maximum length of a horizontal chase or the maximum horizontal projection of a diagonal chase shall not exceed 4 feet except as provided for in Section 10.1.6; and except further that the maximum length of the apron below window sills in all walls shall not exceed the width of the window opening. Waterproofed chases in such aprons in 8-inch walls shall not exceed 4 inches in depth. The aggregate area of recesses and chases shall be not more than one-fourth of the area of the face of the wall in any one story.

10.1.3—Waterproofing chases—The backs and sides of all chases in exterior walls with less than 8 inches of masonry to the exterior surface shall be insulated and waterproofed.

10.1.4—Fire resistive limitations—Chases or recesses shall not reduce the thickness of masonry material below the minimum equivalent thickness required for firewalls, fire separation assemblies or required fire resistive coverings of structural members.

10.1.5—Hollow walls—Where chases and recesses are permitted in hollow walls and walls constructed of hollow blocks or tile, the chases and recesses shall be built in with the wall. Chases shall not be cut in hollow walls after erection.

10.1.6—Continuous chases—Where horizontal chases for the bearing of reinforced concrete floors and roof slabs are continuous, anchors shall be installed above and below the floor construction to resist bending and uplift in the wall due to flexure of the slab.

10.2—Lintels—The design for lintels shall be in accordance with the provisions of Sections 5.6 and 7.3.3. Minimum end bearing shall be 4 inches.

10.3—Support on wood—No masonry shall be supported on wood girders or other forms of wood construction.

10.4—Corbelling.

10.4.1—Solid masonry units shall be used for corbelling. The maximum corbelled projection beyond the face of the wall shall be not more than one half of the wall thickness or one half the wythe thickness for hollow walls; the maximum projection of one unit shall neither exceed one half the height of the unit nor one third its thickness at right angles to the face which is offset. Corbelling of hollow walls or walls built of hollow units shall be supported on at least one full course of solid masonry.

10.4.2—Molded cornices—Unless structural support and anchorage are provided to resist the overturning moment, the center of gravity of all projecting masonry or molded cornices shall lie within the middle one-third of the supporting wall. Terra cotta and metal cornices shall be provided with a structural frame of non-combustible anchored material.

10.5—Arches and lintels—The masonry above openings shall be supported by properly buttressed arches or by lintels that bear on the wall at each end for at least 4 inches.

10.6—Parapet walls—All cells in the hollow masonry units and all joints in solid, cavity, or masonry bonded hollow wall construction shall be filled solid with mortar. All corners of masonry parapet walls shall be reinforced with joint reinforcement or its equivalent at vertical intervals not greater than 12 inches. Such reinforcement shall extend around the corner for at least 4 feet in both directions and splices shall be lapped at least 6 inches. Parapet walls shall be properly coped and flashed with noncombustible, weatherproof material of a width not less than the width of the parapet wall plus sufficient overage for overlaps. Masonry parapet walls shall be not less than 8 inches in thickness and their height shall not exceed three times their thickness. Parapet walls shall be designed in accordance with the provisions of Appendix A.

10.7—Isolated piers—Isolated masonry piers shall be bonded as required for solid walls of the same thickness and shall be provided with adequate means for distributing the load at the top of the pier.

10.8—Bearing details—Concentrated loads shall be supported upon construction of solid masonry, concrete, or masonry of hollow units with cells filled with mortar, grout, or concrete and of sufficient height to distribute safely the loads to the wall or column, or other adequate provisions shall be made to distribute the loads.

10.8.1—Joists—Solid construction for support under joists shall be at least 2 1/4 inches in height, and joists supported on such construction shall extend into the masonry at least 3 inches.

10.8.2—Beams—Solid construction for support under beams, girders, or other concentrated loads shall be at least 4 inches in height and the bearing of beams shall extend into the masonry at least 4 inches.

10.9—Use of existing walls—An existing masonry wall may be used in the alteration or extension of a building provided that it meets the requirements of this standard.

10.9.1—Walls of insufficient thickness—Existing walls of masonry units that are structurally sound, but that are of insufficient thickness when increased in height, may be strengthened by an addition of similar masonry units laid in type M or S mortar. The foundations and lateral support shall be equivalent to those required for newly constructed walls under similar conditions. All such linings shall be thoroughly bonded into existing masonry by toothings to assure combined action of wall and lining. Toothings shall be distributed uniformly throughout the wall, and shall aggregate in vertical cross-sectional area at least 15 percent of the total surface area of the lining. Stresses in the masonry under the new conditions shall not exceed the allowable stresses.

10.10—Precautions during erection—Temporary bracing shall be used wherever necessary to take care of any loads to which the walls may be subjected during erection. Such bracing shall remain in place as long as may be required for safety.

10.11—Horizontal compression joints—All concrete framed buildings to be constructed over 35 feet in height (as measured from adjoining grade to the main roof level), whose exterior wythe are of cavity wall construction with steel lintels, shall have horizontal compression joints in the exterior wythe to prevent masonry distress induced by vertical shortening of the structural frame.

(a) Unless substantiated as indicated by (b) below, horizontal compression joints shall be 1/4 inch minimum thickness, with neoprene, polyethylene, or urethane gasket or equivalent joint filler filling the entire joint, except for a recess from the toe of the lintel angle to the exterior of the facing brick, to provide space for caulking. These joints shall be spaced at each floor.

(b) The applicant of record shall submit an engineering analysis establishing that proposed building compression joints spaced further apart than in (a) above are sufficient to provide for the effects of vertical shortening of the structural frame.

10.12—Dry-stacked, surface-bonded masonry walls.

10.12.1—General—Dry-stacked, surface-bonded masonry walls may be used for only one and two family dwellings and shall comply with the requirements of this code for masonry wall construction.

10.12.2—Materials—Surface-bonding mortar shall comply with ASTM C 476. Concrete masonry units shall comply with ASTM C 55, C 90 or C 145.

10.12.3—Design—Dry-stacked, surface-bonded masonry walls shall be of adequate strength and proportions to support all superimposed loads without exceeding the allowable stresses listed in Table 10.12.3. Allowable stresses not specified in Table 10.12.3 shall comply with the requirements in this standard.

Table 10.12.3 Allowable Stress Gross Cross-Sectional Area

Description Maximum allowable stress (psi) Compression • Standard block 45 • Shear 10 Flexural tension • Vertical span 18 • Horizontal span 30

10.12.4—Construction—Construction of dry-stacked, surface-bonded masonry walls, including stacking and leveling of units, mixing and application of mortar, curing and protection, shall comply with ASTM C 946.

10.13—Glass-block walls.

10.13.1—Exterior wall panels—The maximum dimensions of glass-block wall panels in exterior walls, where used singly or in multiples to form continuous bands of glass blocks between structural supports, shall be 25 feet in length and 20 feet in height between structural supports and expansion joints; and the area of each individual panel shall not be more than 250 square feet. Intermediate structural supports shall be provided to support the dead load of the wall and all other superimposed loads. Where individual panels are more than 144 square feet in area, a supplementary stiffener shall be provided to anchor the panels to the structural supports.

10.13.2—Joint materials—Glass blocks shall be laid up in Type S or N mortar with approved galvanized metal panel anchors in the horizontal mortar joints of exterior panels. The sills of glass-block panels shall be coated with approved water-based asphaltic emulsion, or other elastic waterproofing material, prior to laying the first mortar course, and the perimeter of the panels shall be caulked to a depth of not less than 1/2 inch with nonhardening caulking compound on both faces, or expansion joints shall be provided. Where placed in joint materials other than mortars herein defined, a single panel shall not be more than 100 square feet in area, nor more than 10 feet in either length or height.

10.13.3—Wind and seismic loads—Exterior wall panels held in place in the wall openings shall be designed to resist both the internal and external loads due to wind and seismic loads.

10.13.4—Interior wall panels—Solid or hollow glass blocks shall not be used in fire walls, party walls, fire separation assemblies or fire partitions, or for loadbearing construction. Such blocks shall be erected with mortar and reinforcement in metal frames, structural channels or embedded panel anchors as provided for exterior walls or other joint materials. All mortar-bearing surfaces of the glass block shall be precoated or prepared to insure adhesion between mortar and glass. Wood strip framing shall not be used in fire separation assemblies that are required to be fire resistance rated.

Exceptions: Glass-block assemblies with a material and equipment acceptance number or Board of Standards and Appeals number having a fire-resistance rating of not less than 3/4 hour shall be permitted in fire separations which have a required fire resistance rating of one hour or less and do not enclose exit stairways or exit passageways.

10.14—Veneer.

10.14.1—General—Veneer, as used in this section, refers to an exposed facing wythe of brick, tile, ceramic veneer, terra cotta, concrete masonry units, cast stone, natural stone, or similar weather-resistant noncombustible masonry units laid in mortar and securely attached to a surface for the purpose of providing ornamentation, protection or insulation, but not intentionally so bonded as to exert common action under load. In lieu of the provisions of Section 10.14, veneers may be designed according to Chapters 5, 6 and 9 of reference standard RS 10–1B.

10.14.1.1—Limitations—Veneer shall not be assumed to add to the strength of any wall, nor shall it be assumed to support any load other than its own weight. No veneer shall be less than the thickness specified in Table 10.14.1.1. The height and length of veneer areas shall be unlimited, except as required to control expansion and contraction, and except as provided in Section 10.14.2.

Table 10.14.1.1 Minimum Thickness of Masonry Veneer

Type of Veneer Minimum Thickness Actual (in.) Anchored Type: • Solid masonry units 1 5/8 • Hollow masonry units 1 5/8 • Ceramic veneer 1 5/8 Adhesion Type: • Solid masonry units 1 3/8 • Ceramic veneer 1 3/8

10.14.1.2—Design—All anchor attachments shall be designed to resist a minimum positive or negative horizontal force as required for wind or seismic effects, and adhesion type veneer shall be designed to have a bond sufficient to withstand a shearing stress of 50 psi. At a minimum, the veneer shall also meet the attachment requirements of Sections 10.14.2.1 and 10.14.3.1.

10.14.1.3—Support of veneer—The weight of all anchored type veneer shall be supported upon footings, noncombustible foundation walls, or other approved supports. Veneer above openings shall be supported upon noncombustible, non-corrosive lintels.

10.14.2—Veneer on wood—Anchored masonry veneer attached to wood frame structures shall be supported on noncombustible footings or foundation walls. The height of the veneer shall not exceed 35 feet measured from the top of the supporting footings or foundation walls. Where anchored veneer exceeding 20 feet in height is applied, it shall be supported in a manner that will provide for movement between the veneer and its backing.

10.14.2.1—Attachment—At a minimum, veneer of unit masonry shall be attached directly to wood studs, by one of the following means:

(a) With at least 22 gauge corrosion-resistance corrugated steel ties at least one inch wide, at vertical intervals of not more than 24 inches and horizontal intervals of not more than 32 inches, but in no case less than one tie for 3 1/2 square feet of wall area;

(b) Directly to a 1 inch reinforced cement mortar base.

10.14.3—Veneer on masonry—Veneer attached to masonry or concrete backing shall not be limited in height other than by compressive stresses.

10.14.3.1—Attachment—At a minimum, veneer shall be securely attached to the masonry or concrete backing by one of the following means or by a means that is equivalent in strength:

(a) Metal ties conforming to Section 5.8 except that ties shall be spaced not more than 24 inches apart either horizontally or vertically;

(b) Corrosion-resistant dovetail slot anchors where the backing and the veneer has been designed for this type of attachment. Such anchors shall be formed from at least 16 gauge steel at least 1 inch wide;

(c) Adhesion type masonry veneer shall be installed in accordance with the manufacturer's recommendations and setting plans;

(d) Where anchored veneer is not grouted to the back, it shall be supported in a manner that will provide for movement between the veneer and its backing.

10.15 Miscellaneous structures and systems.

10.15.1—Flat or segmental masonry floor or roof arches—The provisions of this section do not apply when masonry floor or roof arches are proportioned on the basis of structural analysis.

10.15.1.1—Span—The maximum clear span between supporting beams shall be 8 feet.

10.15.1.2—Tie rods—All masonry flat arches or segmental arches shall be provided with tie rods in both the exterior and interior spans. The minimum size and spacing of tie rods shall be:

For exterior spans—1 1/4 inches round rods spaced 4 feet 6 inches apart.

For interior spans—7/8 inches round rods spaced 4 feet 6 inches apart.

Washers shall be used with all tie rods. All tie rods shall have a minimum specified yield point of 36,000 psi.

10.15.1.3—Flat arches—The depth of flat arches of burnt clay or shale hollow blocks shall be at least 1 1/2 inches for each foot of span, inclusive of the portion of the block extending below the under side of the beam, and such arches shall be at least 6 inches thick. Brick shall not be used for flat arches.

10.15.1.4—Segmental arches—Segmental arches shall have a rise of at least 1 inch per foot of span, and the minimum thickness shall be 6 inches for hollow tile arches, 4 inches for brick arches with a span of 5 feet or less, and 8 inches for brick arches with a span exceeding 5 feet.

10.15.1.5—Structural clay tile arches—The blocks shall be at least two cells deep, shall be laid in type M or S mortar, and shall be properly keyed.

10.15.1.6—Brick arches—Brick arches shall be laid in a full bed of type M or S mortar and shall be solidly bonded.

10.15.1.7—Openings in floors and roofs—Suitable metal framing or reinforcement shall be provided in masonry arch and roof construction around any opening more than 1 foot 6 inches on a side."

Appendix A—Special Provisions for Seismic Design.

Section A.1.1.1—Delete this section and substitute the following:

"A.1.1.1—Appendix A sets special requirements for masonry and construction of masonry building elements for seismic design as defined in reference standard RS 9–6."

Section A.2—Delete this section.

Section A.3—Delete the words "for Seismic Zone 2."

Section A.3.3—Delete this section and substitute the following:

"A.3.3—Distribution of seismic loads or forces shall be in accordance with the provisions of reference standard RS 9–6."

Section A.3.6—Delete the first two sentences and substitute the following:

"Masonry walls which require lateral forces shown in Table 23-P of reference standard RS 9–6 shall be anchored to all floors and roofs which provide lateral support for the walls. The anchorage of such walls or partitions shall provide direct connection capable of resisting the forces derived from Table No. 23-P or a minimum of 200 pounds per lineal foot of wall, whichever is greater."

Section A.3.8—Delete this section and substitute the following:

"A.3.8—Vertical reinforcement of at least 0.20 square inches in cross sectional area shall be provided continuously from support to support at each corner, at each side of each opening, at the ends of walls and at a maximum spacing of 10 feet apart throughout the wall. Horizontal reinforcement not less than 0.20 square inches in cross sectional area shall be provided: (1) at the bottom and top of wall openings and shall extend not less than 24 inches nor less than 40 bar diameters past the opening; (2) continuously at structurally connected roof and floor levels and at the top of walls; (3) at the bottom of the wall or in the top of the foundations when dowelled to the wall; (4) at maximum spacing of 10 feet unless uniformly distributed joint reinforcement is provided. Reinforcement at the top and bottom of openings when used in determining the maximum spacing specified in item (4) above shall be continuous in the wall."

Add the following sections:

"A.3.10—Non-bearing back-up or infill walls and non-bearing partitions need not comply with the vertical and horizontal (2 way) reinforcing requirements of section A.3.8 if the requirements set forth in A.3.10.1 through A.3.10.4 are met.

A.3.10.1—The cross sectional area of uniformly spaced steel reinforcement in either the horizontal or the vertical direction shall equal or exceed 0.0005 times the gross cross sectional area of the masonry.

A.3.10.2—Reinforcement shall be continuous between supports.

A.3.10.3—Spacing of prescribed horizontal reinforcement shall not exceed 16 inches for joint reinforcement and 4 feet for reinforcement bars in grouted bond beams. When vertical reinforcement is used, bars shall not exceed placement at 10 feet on center and at the ends of walls.

A.3.10.4—Lateral support anchorage shall be provided between the non-loadbearing back-up, infill or partition wall and its structural support. Spacing of anchors shall conform to the provisions of Sections 4.2 and 5.11 and shall not exceed the spacing of prescribed reinforcement. Anchorage shall be designed to transfer lateral (out-of-plane) forces to the adjacent structural support."

Section A.4—Delete this section.

MODIFICATIONS—The provisions of ACI 530.1–92/ASCE 6–92 shall be subject to the following modifications. The chapter and section numbers are from that standard.

2.3.1—Inspection and testing.

Delete the opening sentence and substitute the following:

"Inspection shall conform to the requirements of Articles 1.5 and 1.6, the inspection and testing provisions of the building code of the city of New York, and the following:"

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1995/017.