NYC Administrative Code RS 5-18 STANDARDS FOR THE PRESSURIZATION OF STAIRS

1. Each stair shall be provided with air in such amount as to satisfy the following requirements:

a. The air shall be mechanically supplied at one or more levels.

b. Each fan shall supply 100 per cent outdoor air.

c. Any opening shall be provided with an intake closure complying with the requirements for opening protectives of Title 27, Chapter 1 of the administrative code with an approved smoke detector located between the outside air intake and the supply fan. Upon the activation of this detector, only the system serviced by such detector shall shut down.

d. The maximum velocity of air supplied at the openings into the stair shall not exceed 3,000 fom at its point of discharge within the stair enclosure.

e. Intake closures shall open and the supply fan or fans shall start upon the activation of any detector in the building except that called for in paragraph c above. However, only the fan system associated with the activation of the detector shall shut down.

2. An approved, automatically controlled louver and weather closure open to the exterior at the highest floor served by the stair shall be installed in the case of a fan or fans producing an upward flow of air, or at the furthest point or points from the fan or fans when more than one fan is used, or at the lower end of the stair venting to outside if a single fan is located at the upper end of the shaft. The size shall be not less than 2 sq. in. per 100 cu. ft. of total shaft volume. Any existing fixed ventilating opening may be included in meeting this requirement. The louver shall be normally closed and shall open automatically by fusible link or other approved device when subjected to a temperature of 135°F. or to a rapid rise in temperature at a rate of 15 to 20°F. per minute, and the louver shall also be remotely operable from the fire command center. Such louver shall also satisfy the requirements of subdivision d of section 27-344.

3. The total supply of air introduced into each stair shall be equal to and not less than the algebraic sum of 24,000 cfm plus 200 cfm per story of stair.

4. Other operating requirements.

a. All weather closures may normally be in closed position.

b. The air supply fans shall provide positive pressure differential between the stair shaft and each floor at a maximum of 0.4 inches of water column whether doors are open or closed. Minimum positive pressure differentials between the stair shafts and each floor of 0.10 inches of water column when all doors are closed, and no less than 0.050 inches of water column when any three doors are open, shall be maintained. As an alternative to the maintenance of 0.050 inches of water column, a minimum average velocity of 400 feet per minute, measured in the plane of any open door, with any three doors open, shall be maintained.

c. Excess positive pressure within the stair closure may be relieved at one or more levels through protected openings in the stair enclosure in the following manner:

(1) Each opening shall be provided with an approved adjustable barometric back-draft damper so arranged as to permit air flow out of the stair enclosure only and shall be adjusted to close if the pressure differential is less than 0.05 inches of water column, and to remain open if the pressure differential is greater than 0.4 inches of water column.

(2) Each opening shall be protected with two 1 1/2-hour fire dampers arranged in series, each with fusible links rated to melt at 125°F.

(3) Acceptable alternative systems for the relief of excessive positive pressure other than through the protective openings in the stair enclosure may be installed, subject to the approval of the commissioner.

(4) Spill ducts located entirely within the stair enclosure and utilizing barometric dampers may be installed as an acceptable alternative system referred to in sub-paragraph 3 above.

d. Air supply fans shall also be controlled from a local start-stop station at the fans and from the fire command station. In addition, fan controls may also be located at the mechanical control center. These controls shall over-ride the automatic detection shut-down.

e. The fans shall be operated from circuits that are separate from the general lighting and power circuits taken off ahead of the main switch and connected to an emergency power source when such source is provided.

5. Full system testing shall be required for each installation and shall be subject to controlled inspection. Pressure or velocity measurements shall be taken for the purpose of determining whether the desired control of smoke will be established and reports of such measurements shall be made and copies thereof filed with the department as provided in Section 27-132 for controlled inspection. A full system test shall be performed after any construction and/or modifications to the stair enclosures altering the volume of such enclosures.

6. Operational tests of the stair pressurization systems shall be conducted every twelve months by building maintenance personnel and witnessed by the Fire Safety Director or by a Registered Architect or Professional Engineer to ensure that each system functions. The owner or his authorized representative shall retain at the premises a record of each test performed for Building and Fire Departments' use.

7. Operational tests shall determine that initiating devices such as fire alarms, sprinkler alarms, elevator recall, manual switches, and smoke detectors other than those designed to cause the shutdown of outside air intake systems, will cause the stair pressurization systems' intake dampers to open and fans to start.