NYC Administrative Code Title 29, Chapter 2 New York City Fire Code, part 13 of 15
Section FC 5706 to Section FC 6108: 31 sections.
Section FC 5706. Special Operations
5706.1 Scope.
Flammable and combustible liquids shall be stored, handled and used in connection with special operations, including the following operations, in compliance with the requirements of this section:
1. Storage and dispensing of flammable and combustible liquids at construction sites.
2. Bulk plants or terminals.
3. Bulk transfer and process transfer operations utilizing cargo tanks and tank cars.
4. Cargo tanks and cargo tank operation.
5. Vapor recovery and vapor-processing systems.
5706.1.1 General.
Special operations involving the storage, handling and use of flammable and combustible liquids shall be conducted in accordance with FC 5701, 5703, 5704 and 5705, except as otherwise provided in this section.
5706.1.2 Prohibition.
It shall be unlawful to dispense any flammable or combustible liquid from a cargo tank or tank car into the fuel tanks of motor vehicles, except for the transfer of liquids from a cargo tank to construction equipment at a construction site in accordance with FC 5706.2.8.
5706.2 Storage and dispensing of flammable and combustible liquids at construction sites.
Temporary storage and dispensing of flammable and combustible liquids at construction sites shall be in accordance with FC 5706.2.1 through 5706.2.8.
Exception: Storage and use of fuel oil connected with nonportable oil-burning equipment regulated by the Mechanical Code.
5706.2.1 Combustibles and open flames near tanks.
Storage areas shall be kept free from weeds and other combustible waste. It shall be unlawful to smoke, or light or maintain an open flame in a flammable or combustible liquid storage area.
5706.2.2 Marking of tanks and containers.
Tanks and containers for aboveground storage of liquids shall be conspicuously marked with the name of the product which they contain and the words: FLAMMABLE – KEEP FIRE AND FLAME AWAY. Tanks shall bear the additional marking: KEEP 50 FEET FROM BUILDINGS.
5706.2.3 Containers for storage and use.
Flammable and combustible liquid shall only be stored in metal containers of a type meeting the requirements of the regulations of the United States Department of Transportation, as set forth in 49 CFR Part 178, or in containers of an approved design.
5706.2.3.1 Liquid handling devices.
Discharge devices shall be of a type that do not develop an internal pressure on the container. Pumping devices or approved self-closing faucets used for dispensing liquids shall not leak and shall be well-maintained. Individual containers shall not be interconnected and shall be kept closed when not in use.
5706.2.3.2 Outdoor storage.
Containers stored outdoors shall be in accordance with FC 5704 and the construction codes, including the Building Code.
5706.2.4 Temporary tanks.
The capacity of a storage tank temporarily installed aboveground containing flammable or combustible liquids shall not exceed 660 gallons (2498 L). Tanks shall be of the single-compartment design, shall be constructed of steel, and shall meet the requirements of the New York State Department of Environmental Conservation regulations, as set forth in 6 NYCRR Part 613.
5706.2.4.1 Fill-opening security.
Fill openings shall be equipped with a locking closure device. Fill openings shall be separate from vent openings.
5706.2.4.2 Vents.
Tanks shall be provided with a method of normal and emergency venting. Normal vents shall also be in accordance with FC 5704.2.7.3. Emergency vents shall be in accordance with FC 5704.2.7.4. Emergency vents shall be arranged to discharge in a manner which prevents localized overheating or flame impingement on any part of the tank in the event that vapors from such vents are ignited.
5706.2.4.3 Location.
Tanks containing flammable or combustible liquids shall be kept outdoors and at least 50 feet (15 240 mm) from buildings, combustible material and combustible waste. Additional distance shall be provided when necessary to ensure that vehicles, equipment and containers being filled directly from such tanks will not be less than 50 feet (15 240 mm) from structures or combustible storage.
5706.2.5 Type of tank.
Tanks shall be provided with top openings only.
Exception: Aerial crane refueling operations when conducted in accordance with FC 5706.2.5.2.
5706.2.5.1 Tanks with top openings only.
Tanks with top openings shall be mounted as follows:
1. On well-constructed metal legs connected to shoes or runners designed so that the tank is stabilized and the entire tank and its supports can be moved as a unit; or
2. For stationary tanks, on a stable base of timbers or blocks approximately 6 inches (152 mm) in height which prevents the tank from contacting the ground.
5706.2.5.1.1 Pumps and fittings.
Tanks with top openings only shall be equipped with a tightly and permanently attached, approved pumping device having an approved hose of sufficient length for filling construction equipment or containers to be served from the tank. Either the pump or the hose shall be equipped with a padlock to its hanger to prevent tampering. An antisiphoning device shall be provided in the pump discharge unless a self-closing nozzle is used. Siphons or internal pressure discharge devices shall not be used.
5706.2.5.2 Tanks for gravity discharge.
Tanks with a connection in the bottom or the end for gravity-dispensing liquids for aerial crane refueling operations shall be mounted and equipped as follows:
1. Support lugs used to elevate the tank for gravity discharge shall be designed to carry all required loads and provide stability.
2. Bottom or end openings for gravity discharge shall be equipped with a valve located adjacent to the tank shell which will close automatically in the event of fire through the operation of a heat-activated releasing device. Where this valve cannot be operated manually, it shall be supplemented by a second, manually operated valve.
3. The gravity discharge outlet shall be provided with an approved hose equipped with a self-closing valve at the discharge end of a type that can be padlocked to its hanger.
5706.2.6 Spill control drainage control and diking.
Indoor storage and dispensing areas shall be provided with spill control and drainage control as set forth in FC 5703.4. Outdoor storage areas shall be provided with drainage control or diking as set forth in FC 5704.2.10.
5706.2.7 Portable fire extinguishers.
Portable fire extinguishers with a minimum rating of 20-B:C and complying with the requirements of FC 906 shall be provided where required by this code.
5706.2.8 Dispensing from cargo tanks.
Where approved, liquids used as fuels are allowed to be transferred from cargo tanks into the fuel tanks of construction equipment at a construction site, subject to the following requirements:
1. The cargo tank is used solely for the purpose of supplying fuel to construction equipment at a construction site.
2. The dispensing hose does not exceed 100 feet (30 480 mm) in length.
3. The dispensing nozzle is an approved type.
4. The dispensing hose is properly placed on the approved reel or in a compartment provided before the cargo tank is moved.
5. Signs prohibiting smoking and open flames within 25 feet (7620 mm) of the cargo tank and construction equipment being refueled are prominently posted on the cargo tank.
6. Electrical devices and wiring in areas where fuel dispensing is conducted are in accordance with the Electrical Code.
7. Cargo tank-dispensing equipment is operated only by a person holding a certificate of fitness.
8. Provision has been made to control and mitigate the accidental or unauthorized release of flammable and combustible liquid.
9. The cargo tank has a capacity of not more than 1,920 gallons (7267 L), and contains no Class IA liquid and not more than 640 gallons (2422 L) of any other Class I liquid.
10. Dispensing is conducted at least 50 feet (15 240 mm) from buildings, structures, combustible material or combustible waste.
11. A portable fire extinguisher with a minimum rating of 40-B:C shall be provided on the cargo tank with signage clearly indicating its location.
12. Absorbent materials, nonwater-absorbent pads, a 10-foot-long (3048 mm) containment boom, an approved container with lid and a nonmetallic shovel shall be provided to mitigate a minimum 5-gallon (19 L) fuel spill.
13. Operators of tank vehicles used for mobile fueling operations shall have in their possession at all times an approved means of notifying the department of a fire or other emergency.
14. Fuel dispensing shall be prohibited within 25 feet (7620 mm) of any source of ignition.
15. The engines of vehicles being fueled shall be shut off during dispensing operations.
16. Nighttime fueling operations shall only be conducted in adequately lighted areas.
17. The cargo tank shall be positioned with respect to the construction equipment being fueled so as to prevent vehicular traffic from driving over the delivery hose.
18. During fueling operations, a cargo tank shall be secured from movement by setting the cargo tank's brakes and chocking the wheels, and the cargo tank's warning lights shall be activated.
5706.3 Reserved.
5706.4 Bulk plants and terminals.
Any premises in or upon which flammable and combustible liquids are received by marine vessels, watercraft, pipelines, tank cars or cargo tanks and which are stored or blended in bulk for the purpose of distributing such liquids by marine vessels, watercraft, pipelines, tanks cars, cargo tanks or containers shall be designed, installed, operated and maintained in accordance with FC 5706.4.1 through 5706.4.10.4.
5706.4.1 Building construction.
Buildings and structures housing bulk plant or terminal materials, operations and facilities shall be constructed in accordance with the construction codes, including the Building Code.
5706.4.1.1 Design and installation documents.
A site plan of the bulk plant or terminal, indicating the location and dimensions of all buildings and structures housing bulk plan or terminal materials, operations and facilities, and all flammable and combustible liquid installations, shall be filed with the department, together with such other design and installation documents as the department may require.
5706.4.2 Means of egress.
Rooms in which flammable and combustible liquids are stored, handled or used shall be arranged such that occupants engaging in such handling and use have readily available access to a means of egress in the event of fire.
5706.4.3 Heating.
Rooms in which Class I liquids are stored, handled or used shall be heated only by means not constituting a source of ignition, such as steam or hot water.
5706.4.4 Ventilation.
Ventilation shall be provided for rooms, enclosures and other areas in buildings or structures in which Class I liquids are handled or used, including any pumping or transfer. Ventilation systems shall be designed in a manner that takes into consideration the relatively high specific gravity of the vapors. When natural ventilation is approved, adequate openings in outside walls at floor level, unobstructed except by louvers or coarse screens, shall be provided. When natural ventilation is not approved, mechanical ventilation shall be provided in accordance with the construction codes, including the Mechanical Code.
5706.4.4.1 Basements and other areas below grade.
Class I liquids shall not be stored, handled or used within a building or structure having a basement, cellar or other area below grade into which flammable vapors can travel, unless such area is provided with ventilation designed to prevent the accumulation of flammable vapors therein.
5706.4.4.2 Dispensing of Class I liquids.
Containers of Class I liquids shall not be drawn from or filled indoors unless a provision is made to prevent the accumulation of flammable vapors in hazardous concentrations. Where mechanical ventilation is required, it shall be kept in operation while flammable vapors could be present.
5706.4.5 Storage.
Except as otherwise provided in FC 5706.4, storage of flammable and combustible liquids in bulk plants and terminals shall be in compliance with the applicable requirements of FC 5704.
5706.4.5.1 Distance to lot line.
The distance between any part of an aboveground flammable or combustible liquid storage tank and the nearest lot line shall be as provided in FC Table 5706.4.5.1, except where FC 5706.4.5.1.1 through 5706.4.5.1.5 require a greater distance.
FC Table 5706.4.5.1 Distance Between an Aboveground Storage Tank and Lot Lines
Tank Capacity Minimum Distance (feet) 30,000 gallons 20 Over 30,000 to 50,000 gallons 30 Over 50,000 to 100,000 50 Over 100,000 to 500,000 80 Over 500,000 to 1,000,000 100 Over 1,000,000 to 2,000,000 135 Over 2,000,000 to 3,000,000 165 Over 3,000,000 to 6,000,000 175
5706.4.5.1.1 Vertical cylindrical tanks over 50,000 gallons (189 250 L) storing a flammable liquid.
For vertical cylindrical tanks over 50,000 gallons (189 250 L) storing a flammable liquid, the distance shall not be less than the greater dimension of height or diameter of the tank, up to a maximum distance of 175 feet (53 340 mm).
5706.4.5.1.2 Rectangular tanks over 50,000 gallons (189 250 L) storing a flammable liquid.
For rectangular tanks over 50,000 gallons (189 250 L) storing a flammable liquid, the distance shall not be less than the total of the length and the width of the tank divided by two, up to a maximum distance of 175 feet (53 340 mm).
5706.4.5.1.3 Vertical cylindrical tanks over 50,000 gallons (189 250 L) storing a combustible liquid.
For vertical cylindrical tanks over 50,000 gallons (189 250 L) storing a combustible liquid, the distance shall not be less than 1/2 the greater dimension of height or diameter of the tank, up to a maximum distance of 175 feet (53 340 mm).
5706.4.5.1.4 Rectangular tanks over 50,000 gallons (189 250 L) storing a combustible liquid.
For rectangular tanks over 50,000 gallons (189 250 L) storing a combustible liquid, the distance shall not be less than the total of the length and the width of the tank divided by 4, up to a maximum distance of 175 feet (53 340 mm).
5706.4.5.1.5 Tank construction.
Newly constructed tanks shall be in accordance with API 650. Repairs and alterations to existing tanks shall be in accordance with API 653.
5706.4.5.2 Distance between aboveground tanks.
The distance between any part of an aboveground storage tank and adjacent tanks shall be in accordance with FC Table 5706.4.5.2.
FC Table 5706.4.5.2 Distance Between Aboveground Storage Tanks
Adjacent Tank Capacity Minimum Distance (feet) 50,000 gallons 3 Over 50,000 to 100,000 gallons 6 Over 100,000 to 200,000 gallons 12 Over 200,000 gallons 25
5706.4.5.3 Height of aboveground storage tanks.
The maximum height of aboveground flammable and combustible liquid storage tanks shall not exceed 40 feet (12 192 mm).
Exception: Aboveground vertical cylindrical tanks storing combustible liquids shall not exceed 48 feet (14 630 mm) in height.
5706.4.5.4 Distance from aboveground tanks to buildings.
The distance between any part of an aboveground storage tank and buildings or structures used for housing of fire extinguishing equipment, central heating plant or electrical distribution equipment shall not be less than 50 feet (15 240 mm).
5706.4.5.5 Maximum capacity for aboveground tanks.
The maximum capacity of any aboveground tank used for storage of a flammable liquid shall not exceed 500,000 gallons (1892 500 L). The maximum capacity of any aboveground tank used for storage of combustible liquid shall not exceed 6,000,000 gallons (22 710 000 L).
5706.4.5.6 Distance from aboveground tanks to exposures.
No aboveground tank shall be installed within:
1. 1,000 feet (304 800 mm) of the nearest wall of a building occupied as a school or hospital, or an entrance to or exit from a tunnel for motor vehicles, subway or railroad trains, or the ventilating buildings or shafts of such tunnels.
2. 250 feet (76 200 mm) of any point under a bridge for pedestrians, motor vehicles, subway or railroad trains, a public park or a land zoned for residential purposes.
5706.4.5.7 Depth of underground storage tanks.
The maximum distance between the top and bottom plates of an underground flammable and combustible liquid storage tank shall not exceed 40 feet (12 192 mm).
5706.4.5.8 Underground tank location.
Underground tanks shall be located such that the top plate thereof shall be at least 2 feet (610 mm) below the established grade. No such tank shall be buried within 10 feet (3048 mm) of any building or adjoining property line. Individual underground tanks shall be covered with 2 feet (610 mm) of earth or 4 inches (102 mm) of reinforced concrete extending 10 feet (3048 mm) beyond all the vertical walls of the tank, and the excavation made to receive the tank shall be backfilled with well-compacted clean sand or earth, free of any ash or other corrosive substance, and free from stones larger than will pass through a 1-inch (25-mm) mesh. Underground tanks may be erected in groups of 2 or more, when such tanks are separated by a space of 1 foot (305 mm), and provided the reinforced concrete top cover extends unbroken over the open space between the tanks.
5706.4.5.9 Mounded-over tanks.
Mounded-over tanks shall be considered underground tanks. A mounded-over tank may be erected with its base at any desired elevation not higher than the grade plane of the premises. It shall be enclosed with a steel, reinforced-concrete, or closed-face-concrete cribbing wall extending from the established grade to the top of the top cover, with the exterior face of the wall at least 10 feet (3048 mm) from the exterior face of the wall of the tank, and backfilled between the tank and the enclosing wall with compacted clean earth or sand containing no ash or other corrosive substance. The wall and backfill may be replaced with compacted similar fill, extending from the established grade to the level of the top cover on the tank, at the normal angle of repose of the material so used, with the provision that the width of the sloped material at the level of the top of the top cover shall be at least 10 feet (3048 mm) wide. When two or more mounded-over tanks, either rectangular or vertical-cylindrical, are grouped together, the tanks shall be at least 1 foot (305 mm) apart from each other, and the group of tanks shall be enclosed around the periphery with the same type of wall and backfill described above for one mounded-over tank.
5706.4.5.10 Maximum capacity of flammable liquid underground tanks.
Underground storage tanks used for storage of a flammable liquid shall not exceed 500,000 gallons (1892 500 L), except that the commissioner may approve the installation of underground tanks with a capacity not to exceed 6,000,000 gallons (22710 000 L) where such greater capacity is determined to be necessary because of the capacity of the marine vessel, watercraft, pipeline or tank car delivering such liquid and where such increased capacity does not endanger the public safety.
5706.4.5.11 Maximum capacity of combustible liquid underground tanks.
Underground storage tanks used for storage of a combustible liquid shall not exceed 6,000,000 gallons (22 710 000 L). Such tanks may be compartmented; however, in no case shall any compartment exceed 4,000,000 gallons (15 140 000 L).
5706.4.6 Overfill protection.
To prevent an overfill during the transfer of flammable or combustible liquid from a marine vessel, watercraft, pipeline, tank car, cargo tank or storage tank, each tank shall be equipped with an approved electrically operated overfill protection system. Such system shall be in accordance with API 2350.
5706.4.6.1 Alarms.
Audible and visible alarms shall be activated automatically when the liquid level in the tank approaches 95 percent of tank capacity and again when it attains a level of 98 percent of tank capacity. This alarm shall be connected to both the marine vessel, watercraft, pipeline, tank car or cargo tank receiving point, as applicable, and to the facility dispatcher's office.
5706.4.6.2 Tanks filled from pipelines.
Tanks filled by pipelines shall be provided with a shutoff valve in the fill line that will automatically shut off the flow to the tank when the liquid level in the tank approaches 95 percent.
5706.4.7 Wharves.
This section shall apply to all wharves, piers, bulkheads and other structures over or contiguous to navigable water having a primary function of transferring liquid cargo in bulk between shore installations and marine vessels and watercraft including barges, lighter boats or similar watercraft.
Exception: Marine liquid motor fuel-dispensing facilities designed, installed, operated and maintained in accordance with FC Chapter 23.
5706.4.7.1 Transferring approvals.
Handling packaged cargo of liquids, including full and empty drums, bulk fuel and stores, over a wharf during cargo transfer shall be subject to the approval and under the personal supervision of the bulk plant or terminal certificate of fitness holder and the senior deck officer on duty.
5706.4.7.2 Transferring location.
Wharves at which liquid cargoes are to be transferred in bulk quantities to or from marine vessels and watercraft shall be at least 100 feet (30 480 mm) from any bridge over a navigable waterway; or from any entrance to, or superstructure of, any vehicular or railroad tunnel under a waterway. The termination of the fixed piping used for loading or unloading at a wharf shall be at least 200 feet (60 960 mm) from a bridge or from an entrance to, or superstructures of, a tunnel.
5706.4.7.3 Superstructure and decking material.
Superstructure and decking shall be designed for the intended use. Decking shall be constructed of materials that will afford the desired combination of flexibility, resistance to shock, durability, strength and fire resistance.
5706.4.7.4 Wharf tanks prohibited.
It shall be unlawful to install, operate or maintain on wharfs any tanks containing flammable and combustible liquids.
5706.4.7.5 Transferring equipment.
Loading pumps capable of building up pressures in excess of the safe working pressure of cargo hose or loading arms shall be provided with bypasses, relief valves or other arrangements to protect the loading facilities against excessive pressure. Relief devices shall be tested at least annually to determine that they function satisfactorily at their set pressure.
5706.4.7.6 Piping, valves, fittings and ancillary equipment.
Piping systems shall be in accordance with FC 5703.6 except as otherwise provided as follows:
1. Piping systems shall be designed to protect against physical damage resulting from the motion of the wharf from wave action, currents, tides or the mooring of marine vessels and watercraft.
2. Pipe joints that depend on the friction characteristics of combustible materials or on the grooving of pipe ends for mechanical continuity of piping shall not be used.
3. Swivel joints may be used in piping to which hoses are connected and for articulated, swivel-joint transfer systems, provided that the design of the swivel joints is such that the mechanical strength of the joint will not be impaired if the packing materials fail such as by exposure to fire.
4. Each pipe used to convey Class I or II liquids leading to a wharf shall be provided with a readily accessible block valve located on shore near the approach to the wharf and outside of any diked area. Where more than one line is used to convey liquid, the valves shall be grouped in one location.
5. Means shall be provided for ready access to cargo line valves located below the wharf deck.
6. Piping systems shall contain a sufficient number of valves to operate the system properly and to control the flow of liquid both during normal operation and in the event of physical damage.
7. Piping on wharves shall be bonded and grounded where Class I and II liquids are transported. If excessive stray current conditions exist, insulating joints shall be installed. Bonding and grounding connections on piping shall be located on the wharf side of hose riser insulating flanges, where used, and shall be accessible for inspection.
8. Hose or articulated swivel-joint pipe connections used for cargo transfer shall be capable of accommodating the combined effects of change in draft and maximum tidal range, and mooring lines shall be kept adjusted to prevent surge of the marine vessel or watercraft from placing stress on the cargo transfer system.
9. Hoses shall be supported to avoid kinking and physical damage, including damage from chafing.
10. Piping, hoses, valves and fittings shall be constructed of steel. Valves shall be rated for not less than 150 pounds per square inch (psig) (1034 kPa).
5706.4.7.7 Loading and unloading.
Loading or unloading shall not commence until the bulk plant or terminal certificate of fitness holder and officer in charge of the marine vessel or watercraft agree that the marine vessel or watercraft has been properly moored and connections have been properly made.
5706.4.7.8 Construction work.
Construction work shall not be performed on the wharf except as approved by the commissioner upon a determination that such work can be safely performed, and subject to such terms and conditions as the commissioner may prescribe in the interest of public safety.
5706.4.8 Sources of ignition.
Class I, II or IIIA liquids shall not be used, drawn or dispensed where flammable vapors can reach a source of ignition.
5706.4.9 Drainage control.
Loading and unloading areas shall be provided with drainage control in accordance with FC 5704.2.10.
5706.4.10 Fire protection.
Fire protection shall be in accordance with FC Chapter 9 and FC 5706.4.10.1 through 5706.4.10.8.
5706.4.10.1 Portable fire extinguishers.
Portable fire extinguishers with a rating of not less than 20-B and complying with the requirements of FC 906 shall be located within 75 feet (22 860 mm) of hose connections, pumps and separator tanks.
5706.4.10.2 Fire hoses.
Fire hose connected to a water supply in a size appropriate for the water supply shall be provided in accordance with FC 905 and the construction codes, including the Building Code, so that manifolds where connections are made and broken can be reached by at least one hose stream.
5706.4.10.3 Obstruction of equipment.
Material shall not be placed on wharves in such a manner that would obstruct access to firefighting apparatus or equipment or important pipeline or other delivery control valves.
5706.4.10.4 Fire apparatus access.
An unobstructed fire apparatus access road to the shore end of the wharf shall be maintained in accordance with FC Chapter 5.
5706.4.10.5 Fire protection systems.
Aboveground tanks, mounded-over tanks, underground tanks, tank car loading and unloading racks, cargo tank loading racks, cargo tank unloading areas, marine vessel and watercraft loading and unloading areas and all other portions of a bulk plant or terminal shall be provided with fire extinguishing systems that are approved by the commissioner, inspected by a representative of the department and tested at the owner's risk by his or her representative before a representative of the department. Such systems shall include an approved yard hydrant system and tank monitor nozzles.
5706.4.10.5.1 Cargo tank loading racks.
A fire extinguishing system shall be provided over and under each cargo tank loading position. At least one remote control valve shall be provided to control the extinguishing agent for each three loading positions. Piping systems shall be installed so they can be thoroughly drained. The fire extinguishing system shall be sized to provide protection for the three largest adjacent loading positions.
5706.4.10.6 Emergency alarm transmission.
Manual pull stations shall be provided at one or more approved locations that will automatically transmit a signal to the department via an approved central station.
5706.4.10.7 Periodic tests.
Fire extinguishing systems, fire protection systems and tank overfill protection shall be tested once every 2 years at the owner's risk by his or her representative before a representative of the department. Tests of foam extinguishing systems shall produce foam at the most remote tank and produce water flow at each tank. In the event that the discharge of foam to the most remote tank would result in a reportable hazardous material release in accordance with federal, state or local laws, rules or regulations, such other test acceptable to the commissioner may be conducted.
5706.4.10.8 Color coding and labeling.
Fire protection systems shall be color-coded and labeled in accordance with FC 5706.4.10.8.1 through 5706.4.10.8.2. Copies of the color code shall be posted in all central locations for fire extinguishing media, such as the foam house location.
5706.4.10.8.1 Color coding.
Fire protection systems shall be color-coded as follows:
1. Standpipe and/or yard hydrant systems:
1.1. Piping, valve bodies and handles, hydrants and hydrant or hose houses: Red with contrasting white bands.
1.2. Fire department connections: Red.
2. Sprinkler systems (wet or dry):
2.1. Piping and valve bodies and handles: Red with contrasting bright green bands.
2.2. Fire department connections: Red with green caps.
3. Nonautomatic sprinkler systems (including fog spray systems):
3.1. Piping and valve bodies and handles: Red with contrasting aluminum bands.
3.2. Fire department connections: Aluminum.
4. Carbon dioxide extinguishing systems – piping, valve bodies and handles: Red with contrasting brown bands.
5. Steam extinguishing systems – piping, valve bodies and handles: Red with contrasting black bands.
6. Foam extinguishing systems:
6.1. Piping, valve bodies and handles, hydrants and hydrant or hose houses: Red with contrasting bright orange bands.
6.2. Department water connections: Red. A durable sign that reads "WATER FOR FOAM SYSTEM", shall be conspicuously posted immediately adjacent to such connections.
6.3. Department foam connection: Red with contrasting bright orange band or caps. A durable sign that reads "CHEMICAL FOAM DIRECT TO TANKS" or "...% MECHANICAL FOAM SOLUTION DIRECT TO TANKS", shall be conspicuously posted immediately adjacent to such connections.
5706.4.10.8.2 Labeling.
Bands, or piping immediately adjacent to bands, shall be labeled to indicate the names of the extinguishing media. The letters shall be in a contrasting color of a suitable size in proportion to the pipe diameters. The width of each band shall be not less than the pipe diameter and shall be spaced not more than 30 feet (9144 mm) apart. Bands, lettering and piping shall be painted in sun- and weather-resistant colors and paint; but bands and lettering may be applied by means of pressure sensitive tape that is sun- and weather-resistant.
5706.4.11 Interconnected piping.
All tanks shall be connected by a system of steel pipes in a manner that the contents of each tank may be transferred to another tank without resulting in product contamination, or flash point reduction of the stored liquid.
5706.4.12 Supervision.
Bulk plants and terminals, including transfer operations, shall be continuously under the personal supervision of a person holding a certificate of fitness for such facility. Such supervision shall satisfy the certificate of fitness supervision requirements of this code for all fire protection systems at the facility, including standpipe systems, sprinkler systems, yard hydrant systems and foam systems.
5706.4.13 Oil spills.
Bulk plants and terminals storing petroleum products and petroleum product pipelines operating within the city shall provide oil-absorbent material, oil-dispersant material, booms and other such material and equipment for the control and remediation of oil spills in such quantity and at such locations as set forth in FC 5706.4.13.1 through 5706.4.13.4.
Exceptions:
1. Bulk plants and terminals storing petroleum products when such facility has in place a spill prevention control and countermeasure plan meeting the requirements of United States Environmental Protection Agency regulations, as set forth in 40 CFR Part 112.
2. Petroleum product pipelines when such pipeline operator has in place for its New York City operations a response plan for onshore oil pipelines meeting the requirements of United States Department of Transportation regulations, as set forth in 49 CFR Part 194.
5706.4.13.1 Quantities of clean-up materials and equipment.
Oil spill clean-up materials and equipment shall be stored for use at each bulk plant and terminal and locations designated for pipeline operations in accordance with FC Table 5706.4.13.1, the rules or as a condition of the permit for the facility.
FC Table 5706.4.13.1 Oil Spill Materials and Equipment to Be Stored at Each Bulk Plant and Terminal or Pipeline
Material or Equipment Total Petroleum Product Storage 1,000,000 Gallons or Less 5,000,000 Gallons or Less 10,000,000 Gallons or Less or Pipeline Operation Over 10,000,000 Gallons Absorbent material to recover 3,000 gallons 5,000 gallons 10,000 gallons 20,000 gallons Boom 300 feet 300 feet plus enough to encircle marine vessel or watercraft, including barges which may be loading or unloading at the premises
5706.4.13.2 Availability.
Adequate storage facilities, materials-handling equipment and personnel shall be provided by the bulk plant and terminal or pipeline operator. Such materials-handling equipment and personnel shall be continuously available to properly deploy and apply the materials and equipment specified in FC 5706.4.13.1.
5706.4.13.3 Use of clean-up service.
The commissioner may approve the utilization of an oil spill clean-up service as a "back-up" spill mitigation measure, authorizing the material quantities to be reduced by 2/3 of those specified in FC Table 5706.4.13.1, but to a quantity not less than 3,000 gallons (11 356 L) of absorbent material and 300 feet (91 440 mm) of boom, and subject to the following conditions:
1. A responsible officer of the bulk plant and terminal or pipeline operation shall submit a sworn affidavit identifying the oil spill clean-up service with which it has contracted to perform such services, averring that such oil spill clean-up service meets the standards set forth in FC 5706.4.13.4 and setting forth the nature of the services to be rendered.
2. The department shall be notified, in writing, within 10 business days of the date when the utilization of the clean-up service is cancelled or the service goes out of business.
3. Such approval may be rescinded by the commissioner for good cause for failure of the spill clean-up service to timely respond to an oil spill, to have adequate equipment, materials or personnel, or to obey or cooperate with the department representatives in charge of the scene of the oil spill.
5706.4.13.4 Oil spill clean-up service standards.
An oil spill clean-up service may be retained by a bulk plant, bulk terminal or pipeline operation pursuant to FC 5706.4.13.3 provided it is capable of meeting the following standards:
1. It maintains the stockpile of material and equipment required by FC 5706.4.13.1 for storage of over 10,000,000 gallons (37 850 000 L) of petroleum products, regardless of the amount of petroleum products actually stored at the contracting bulk plants, bulk terminals or pipelines.
2. A supervisor will respond to the spill site within 1 hour from time of notification.
3. It is capable of delivering, on a 24-hour, 7-day-a-week basis, sufficient materials, equipment and personnel to the contracting bulk plant, bulk terminal or pipeline within 2 hours from time of notification.
4. Such service is licensed and operated in accordance with all applicable federal, state and local laws.
5706.4.14 Valves.
All inlet and outlet nozzles of tanks shall be provided with a valve of steel construction of a 150 pounds per square inch (psig) (1034 kPa) rating located as close as practicable to the tank.
5706.4.15 Dike construction.
All dike walls shall be of steel or reinforced concrete, designed to be liquid-tight and to withstand a full hydraulic head, and constructed so as to afford ready access. Where stairways or other similar means are required to afford such access, they shall be constructed of steel or other approved noncombustible material.
5706.4.16 Dike capacity.
Each single dike wall enclosure shall have a capacity equal to 110 percent of the tank's capacity. Tanks arranged in groups with a total capacity not exceeding 500,000 gallons (1 892 500 L) may be enclosed in a single dike wall enclosure. Each group tank dike area shall have a net capacity not less than that of the largest tank plus 10 percent of the aggregate capacity of all other tanks served by the dike enclosure. That portion of the surface occupied by tank or tanks shall be included when computing the diked area.
5706.4.17 Tank and piping test.
Tank and piping shall be tested at the time of installation at the owner's risk by his or her representative before a representative of the department as follows:
1. Aboveground, underground and mounded-over tanks shall be filled to capacity with water and maintained for not less than 24 hours.
2. Piping shall be hydrostatically tested to a pressure of 100 pounds per square inch (psig) (689.5 kPa) or 150 percent of the maximum operating pressure, whichever is greater, for 30 minutes.
5706.4.17.1 Periodic test.
Underground piping shall be tested once every 10 years at the owner's risk by his or her representative before a representative of the department. Such test shall be made at 100 pounds per square inch (psig) (689.5 kPa) or 150 percent of the maximum operating pressure, whichever is greater, for 30 minutes.
5706.5 Bulk transfer and process transfer operations.
Bulk transfer and process transfer operations shall be subject to the approval of the commissioner and be conducted in compliance with the requirements of FC 5706.5.1 through 5706.5.18.3, except that liquid motor fuel-dispensing facilities shall comply with the requirements of FC Chapter 23.
5706.5.1 Location.
Bulk transfer and process transfer operations shall be conducted in approved locations. Tank cars shall be unloaded only on private sidings or railroad-siding facilities equipped for transferring flammable or combustible liquids. Cargo tank and tank car transfer facilities shall be separated from buildings, aboveground tanks, combustible materials, lot lines, public streets and private roads by a distance of 25 feet (7620 mm) for flammable liquids and 15 feet (4572 mm) for combustible liquids measured from the nearest position of any loading or unloading valve or connection. Buildings for pumps or shelters for personnel shall be considered part of the transfer facility.
5706.5.2 Weather protection canopies.
Where weather protection canopies are provided, they shall be constructed in accordance with FC 5004.13. Weather protection canopies shall not be located within 15 feet (4572 mm) of a building or combustible material or within 25 feet (7620 mm) of building openings, lot lines, public streets or private roads.
5706.5.3 Ventilation.
Ventilation shall be provided to prevent accumulation of vapors in accordance with FC 5705.3.7.5.1.
5706.5.4 Sources of ignition.
Sources of ignition shall be controlled or eliminated in accordance with FC 5003.7.
5706.5.5 Spill control and secondary containment.
Areas where transfer operations are located shall be provided with spill control and secondary containment in accordance with FC 5703.4. The spill control and secondary containment system shall have a design capacity capable of containing the capacity of the largest tank compartment located in the area where transfer operations are conducted. Containment of the rainfall volume specified in FC 5004.2.2.6 is not required.
5706.5.6 Fire protection.
Fire protection shall be in accordance with FC 5706.4.10.5.
5706.5.7 Static protection.
Static protection shall be provided to prevent the accumulation of static charges during transfer operations. Bonding facilities shall be provided during the transfer through open domes where flammable liquids are transferred, or where combustible liquids are transferred into cargo tanks or tank cars which could contain vapors from previous cargoes of flammable liquids. Protection shall consist of a metallic bond wire permanently electrically connected to the fill stem. The fill pipe assembly shall form a continuous electrically conductive path downstream from the point of bonding. The free end of such bond wire shall be provided with a clamp or equivalent device for convenient attachment to a metallic part in electrical contact with the cargo tank or tank car. For cargo tanks, protection shall consist of a flexible bond wire of adequate strength for the intended service and the electrical resistance shall not exceed 1 megohm. For tank cars, bonding shall be provided where the resistance of a tank car to ground through the rails is 25 ohms or greater. Such bonding connection shall be fastened to the cargo tank or tank car before dome covers are raised and shall remain in place until filling is complete and all dome covers have been closed and secured.
Exceptions:
1. Where cargo tanks or tank cars are loaded exclusively with products not having a static-accumulating tendency, such as asphalt, cutback asphalt, most crude oils, residual oils and water-miscible liquids.
2. When flammable liquids are not handled at the transfer facility and the cargo tanks are used exclusively for combustible liquids.
3. Where cargo tanks or tank cars are loaded or unloaded through closed top or bottom connections when the hose is conductive.
5706.5.7.1 Filling through open domes.
Filling through open domes into the tanks of cargo tanks or tank cars that contain vapor-air mixtures within the flammable range, or where the liquid being filled can form such a mixture, shall be by means of a downspout which extends to near the bottom of the tank. It shall be unlawful to fill a cargo tank or tank car with gasoline through an open dome.
5706.5.8 Stray current protection.
Tank car loading facilities where Class I, II or IIIA liquids are transferred through open domes shall be protected against stray currents by permanently bonding the pipe to at least one rail and to the transfer apparatus. Multiple pipes entering the transfer areas shall be permanently electrically bonded together. In areas where excessive stray currents are known to exist, all pipes entering the transfer area shall be provided with insulating sections to isolate electrically the transfer apparatus from the pipelines.
5706.5.9 Top loading.
When top loading a cargo tank with Class I and II liquids without vapor control, valves used for the final control of flow shall be of the self-closing type and shall be manually held open except where automatic means are provided for shutting off the flow when the tank is full. When used, automatic shutoff systems shall be provided with a manual shutoff valve located at a safe distance from the loading nozzle to stop the flow if the automatic system fails. When top loading a cargo tank with vapor control, flow control shall be in accordance with FC 5706.5.10. Self-closing valves shall not be tied or locked in the open position.
5706.5.10 Bottom loading.
When bottom loading a cargo tank or tank car with or without vapor control, a positive means shall be provided for loading a predetermined quantity of liquid, together with an automatic secondary shutoff control to prevent overfill. The connecting components between the transfer equipment and the cargo tank or tank car required to operate the secondary control shall be functionally compatible.
5706.5.10.1 Dry disconnect coupling.
When bottom loading a cargo tank, the coupling between the liquid loading hose or pipe and the cargo tank piping shall be a dry disconnect coupling.
5706.5.10.2 Venting.
When bottom loading a cargo tank or tank car that is equipped for vapor control and vapor control is not required or used for the product being loaded, the tank shall be vented to the atmosphere to prevent pressurization of the tank. Such venting shall be at a height equal to or greater than the top of the cargo tank or tank car.
5706.5.10.3 Vapor-tight connection.
Connections to the plant vapor control system shall be designed to prevent the escape of vapor to the atmosphere when not connected to a cargo tank or tank car.
5706.5.10.4 Vapor recovery and processing equipment.
Vapor recovery and processing equipment at bulk plants and terminals shall comply with the requirements of FC 5706.8.
5706.5.11 Switch loading.
Cargo tanks or tank cars which have previously contained flammable liquids shall not be loaded with combustible liquids until such tanks or cars and all piping, pumps, hoses and meters connected thereto have been completely drained and flushed.
5706.5.12 Loading racks.
Where provided, loading racks, stairs or platforms shall be constructed of noncombustible materials. Buildings for pumps or for shelter of loading personnel are allowed to be part of the loading rack. Wiring and electrical equipment located within 25 feet (7620 mm) of any portion of the loading rack shall be in accordance with FC 5703.1.1.
5706.5.13 Transfer apparatus.
Bulk and process transfer apparatus shall be of an approved type.
5706.5.14 Indoor transfers.
Cargo tanks and tank cars shall not be located indoors while transferring flammable or combustible liquids.
Exception: Cargo tanks are allowed under weather protection canopies and canopies of automotive liquid motor fuel-dispensing facilities.
5706.5.15 Cargo tank and tank car.
Cargo tanks and tank cars shall be certified and permitted in accordance with this section.
5706.5.15.1 DOTn certification.
Certification shall be maintained for cargo tanks and tank cars in accordance with the regulations of the United States Department of Transportation, as set forth in Parts 100 - 180.
5706.5.15.2 Department permit.
It shall be unlawful for any person to load a cargo tank with any flammable liquid or Class II or IIIA combustible liquid or to receive or accept delivery of such products in or from a cargo tank, except in or from a cargo tank for which a department permit has been issued and is displayed pursuant to the provisions of FC Chapter 50. The provisions of this section shall not prohibit the loading of a cargo tank with any liquid products with a flash point over 200°F (93°C) nor the receiving or acceptance of delivery from a cargo tank of any liquid products with a flash point over 200°F (93°C), provided that such cargo tank is designed, constructed, and equipped in accordance with the regulations of the United States Department of Transportation governing the transportation of dangerous articles by common, contract, private and proprietary carriers engaged in interstate commerce.
5706.5.16 Securing cargo tanks and tank cars from movement.
Cargo tanks and tank cars shall be secured from movement during loading and unloading operations by setting the cargo tank's or tank car's brakes and by chocking or blocking the wheels. At least two wheel chocks not less than 5 inches by 5 inches by 12 inches (127 mm by 127 mm by 305 mm) in size and dished to fit the contour of the tires shall be used for cargo tanks.
5706.5.17 Vehicle motor.
Motors of cargo tanks or tank cars shall be shut off during the making and breaking of hose connections and during the unloading operation except when unloading is performed with a pump deriving its power from the cargo tank motor.
5706.5.18 Piping, valves, hoses and fittings.
During process transfers, piping, valves, hoses and fittings which are not a part of the cargo tank or tank car shall be designed and installed in accordance with FC 5703.6. Caps or plugs which prevent leakage or spillage shall be provided at all points of connection to transfer piping.
5706.5.18.1 Shutoff valves.
Approved automatically or manually activated shutoff valves shall be provided where the transfer hose connects to the process piping, and on both sides of any exterior fire-resistance-rated wall through which the piping passes. Manual shutoff valves shall be arranged such that they are readily accessible from grade. Valves shall not be locked in the open position.
5706.5.18.2 Hydrostatic relief.
Hydrostatic pressure-limiting or relief devices shall be provided where pressure buildup in trapped sections of the system could exceed the design pressure of the components of the system. Devices shall relieve to other portions of the system or to another approved location.
5706.5.18.3 Antisiphon valves.
Antisiphon valves shall be provided when the system design would allow siphonage.
5706.6 Reserved.
5706.7 Reserved.
5706.8 Vapor recovery and processing systems for use in bulk plants and terminals.
Vapor recovery and processing systems installed at bulk plants and terminals, including systems associated with piping, loading racks, dikes, fire detection and fire protection equipment, shall be designed, installed, operated and maintained in accordance with FC 5706.8.1 through 5706.8.3. Such compliance shall be required for all vapor recovery processing systems, whether installed voluntarily or pursuant to the requirements of the United States Environmental Protection Agency, United States Coast Guard or New York State Department of Environmental Conservation. The requirements of FC 5706.8 through 5706.8.3 apply to both new and existing facilities.
5706.8.1 General.
Vapor recovery and processing systems shall comply with the requirements of NFPA 30, except as otherwise provided in this section, the regulations of the United States Environmental Protection Agency, United States Coast Guard and New York State Department of Environmental Conservation, as applicable, and the following general requirements:
1. Electrical equipment shall comply with the requirements of the Electrical Code. Upon request, proof of compliance with the Electrical Code shall be filed with the department.
2. The installation of any refrigerating system shall comply with the requirements of FC Chapter 6 and the Mechanical Code.
3. All tanks and piping shall be grounded. Static bonding connections shall be made between loading arm, vehicle and vapor recovery unit. An interlock shall be provided to prevent pumping operations until properly grounded.
4. All product pumps and compressors shall be of a type approved for such use.
5. Pressure vessels shall conform to the ASME Boiler and Pressure Vessel Code. The manufacturer data sheet for the pressure vessel shall be maintained on the premises and made available for inspection to any representative of the department.
6. Knock-out vessels shall be provided with a high liquid level sensor that will initiate shutdown of the liquid transfer into the vessel and the vapor recovery or processing system.
7. A flame arrestor and mist eliminator element shall be provided at final emission vent.
8. A fire detection system shall be provided that will initiate shutdown of the vapor recovery and processing system in the event of fire.
9. An annunciator panel with audible and visible alarms shall be provided in the dispatcher's office. The annunciator panel shall monitor and shut down the vapor recovery and processing system upon any equipment malfunction, including a malfunction of the fire detection system.
10. Insulation material shall be noncombustible.
11. Lightning protection shall be provided in accordance with NFPA 780.
12. Pressure relief valves shall be provided on all pressure vessels and wherever else required by the system design, and shall be sized in accordance with the ASME Boiler and Pressure Vessel Code. Pressure relief valves shall discharge to a safe location. No shutoff valve shall be installed in the line of relief. Tanks and equipment shall have independent venting for over-pressure or vacuum conditions that might occur from malfunction of the vapor recovery or recovery unit.
13. A reinforced concrete base shall be provided and approved by the agency having jurisdiction.
14. Vapor recovery and processing systems shall be placed in an unpierced dike of such construction and capacity as the commissioner may prescribe. No drains shall be allowed, and any drain pump used shall be manually activated.
15. Vapor recovery and processing systems shall be installed at least 25 feet (7620 mm) from bulk storage tanks, warehouses, loading racks, dispatchers' offices, transfer facilities, buildings housing fire protection systems, central heating plants or electrical distribution systems, other plant buildings, building lines and adjoining lot lines. When vessels in the vapor recovery and processing system operate in excess of 50 pounds per square inch gauge (psig) (345 kPa), but less than 150 pounds per square inch gauge (psig) (1034 kPa), the minimum distance shall be 50 feet (15 240 mm), unless a protective structure, such as masonry or concrete fire wall, is installed in the line of sight between such vessel and the exposure, in which case the minimum distance of 25 feet (7620 mm) shall be applicable.
16. Vents on vapor-processing equipment shall be not less than 15 feet (4572 mm) from ground level, with outlets located and directed so that flammable vapors will disperse to below the lower flammable limit (LFL) before reaching a potential ignition source.
17. The vapor recovery and processing system shall be protected from physical damage, including damage by motor vehicles utilizing dikes, posts, or other approved means.
18. The entire vapor recovery and processing system shall be inspected for proper operation on a periodic basis, but not less than once every 6 months, by a qualified person. Such inspection shall be documented in a log book maintained at the facility for such purpose.
19. Durable signs reading "DANGER – NO SMOKING, MATCHES, OPEN LIGHTS OR SPARKING DEVICES AT THIS EQUIPMENT" shall be conspicuously posted at or near the vapor recovery and processing system in addition to the "No Smoking" signs required throughout the facility.
20. One or more foam hydrants, yard hydrants, monitor nozzles and portable fire extinguishers having a minimum 40-B:C rating, shall be provided within 50 feet (15240 mm) of the vapor recovery and processing system and shall be readily available for use.
21. All piping associated with a vapor recovery and processing system, including piping connecting such system to storage tanks, shall be hydrostatically tested to a pressure of 100 pounds per square inch gauge (psig) (690 kPa) or one and one-half (1.5) times the maximum working pressure, whichever is greater, for a period of 2 hours, and shall show no leaks. Such hydrostatic testing shall be conducted at the owner's risk by his or her representative before a representative of the department. In lieu of such hydrostatic testing, the commissioner may accept an affidavit from the manufacturer attesting to the integrity of piping integral to the vapor recovery and processing system.
22. Where a storage tank is connected to a vapor recovery and processing system, a mist eliminator shall be provided in the vapor line at or adjacent to the tank to remove entrained liquid and return same to the tank or an approved collection system.
23. The vapor recovery and processing system shall be designed to minimize and dissipate static electricity in accordance with NFPA 77.
5706.8.2 Atmospheric condensation and refrigeration vapor recovery and processing systems.
A vapor condenser system shall be placed in an unpierced dike or within a concrete trench of adequate width and depth to hold at least 1 hour's vapor recovery.
5706.8.3 Absorption vapor recovery and processing systems.
Absorption vapor recovery and processing systems shall comply with the following requirements:
1. A lean oil storage tank shall be protected by a foam fire extinguishing system.
2. The entire vapor recovery and processing system, including the lean oil storage tank, shall be placed in an unpierced dike. The height of the dike shall be based upon the size of the lean oil storage tank and shall have a capacity of at least 110 percent of such tank, but in any event not less than the maximum pumping capacity of the system for 20 minutes of operation.
3. Heaters used shall be of a type approved for such use and shall be equipped with an automatic shutoff device that activates upon reaching the high temperature limit for the absorption vapor recovery and processing system.
4. All absorbers, saturators, heat exchangers and condensers shall conform to ASME Boiler and Pressure Vessel Code and the provisions of FC Chapter 53.
5. A relief valve shall be provided for compressors, stripper columns and other pressure vessels.
6. Lean oil tanks and vapor vessels shall be constructed and installed in accordance with this chapter and API 650.
7. Upon installation, a vapor vessel bladder shall be pneumatically tested at one and one quarter times the maximum operating pressure for 4 hours without leakage. A retest shall be performed annually. All such tests shall be conducted at the owner's risk by his or her representative before a representative of the department.
5706.9 Cargo tank loading rack systems.
Loading rack systems shall be designed, installed, operated and maintained in accordance with the following requirements:
1. Any vapor recovery and processing system used in connection with a loading rack system shall comply with the requirements of FC 5706.8.1 through 5706.8.3.
2. Loading racks shall be protected throughout by a fire extinguishing system as set forth in FC 5706.4.10.5.1.
3. Cargo tanks loaded at bulk plants or terminals shall be compatible with all safety features incorporated into the loading rack.
4. Dry-break adapters conforming to API standards shall be provided on the fill and vapor recovery lines. During loading, each cargo tank compartment shall be sealed except for the dry-break fill coupling and vapor recovery line.
5. An interlock shall be provided to prevent loading when the cargo tank vehicle motor is running and to prevent start up of the cargo tank vehicle motor during loading. Such interlock device shall further prevent the vehicle motor from starting before the product fill line and vapor return line have been disconnected.
6. An interlock device shall be provided so that no loading may take place unless the vapor recovery line is properly connected to the cargo tank.
7. Except when loading, protective caps shall cover all dry-break adapters as protection against the elements and physical damage from impact.
8. No more than three compartments shall be loaded at a time.
9. A two-stage preset meter shall be provided for each loading arm. Loading arms shall be equipped with manual or electronic dead-man control valves.
10. All electrical equipment shall be suitable for use in hazardous locations. The design of the electronic sending device shall be such that a source of higher voltage or current cannot be connected to same.
11. An approved overfill prevention system shall be provided at the loading rack and shall be designed to ensure at least 1 percent vapor space per compartment. In no event shall the vapor space in a compartment be less than 40 gallons (151 L) in capacity.
12. A liquid detector shall be provided in the vapor return line, to automatically shut off the loading system if liquid reaches the vapor line.
13. All components of the fill and vapor recovery loading arm assemblies making contact with the cargo tank, including the loading head, shall be constructed of sparkproof material.
14. The fill line and the vapor recovery line in loading arm assemblies shall be of the same diameter. The maximum velocity in any liquid line shall not exceed 15 feet per second (4572 mm per second).
15. The fill line and vapor recovery line in loading arm assemblies shall be constructed of rigid steel, except that flexible hose may be used for fill or vapor recovery loading assemblies provided that such hose is no longer in length than necessary, has an inner diameter no greater than 4 inches (102 mm), is of steel construction and is rated for not less than 800 pounds per square inch gauge (psig) (5617 kPa).
16. Cargo tanks shall not be filled with flammable or combustible liquids unless one or more devices, equipment or systems are provided to immediately shut down the flow of such liquid in the event of cargo tank overfilling, faulty dome seal, cargo tank pressure exceeding 3 pounds per square inch gauge (psig) (21.7 kPa) and electrical grounding fault.
17. The loading arm assembly shall be grounded.
18. The loading arm assembly shall be designed to break away from the cargo tank without rupture should the cargo tank move with the loading arm still in place.
19. All liquid and vapor piping at the loading arm assembly shall be hydrostatically tested to a pressure of 100 pounds per square inch gauge (psig) (690 kPa) or one and one-half (1.5) times the maximum working pressure, whichever is greater, for a period of 2 hours. Such test shall be conducted at the owner's risk by his or her representative before a representative of the department.
20. The loading head unit seal against the cargo tank shall not exceed a force of 200 pounds (90.8 kg) or a pressure of 5 pounds per square inch gauge (psig) (34.5 kPa).
21. A mist eliminator shall be provided in the vapor line at or adjacent to the loading arm to remove entrained liquid and return same to the cargo tank, or to an approved collection system.
22. Cargo tanks containing flammable liquids in any compartment shall not be loaded with combustible liquids unless the loading rack is protected by a fire extinguishing system in accordance with this chapter.
23. The loading rate of combustible liquids into cargo tanks shall be such that the initial velocity in the liquid line is 3 feet per second (914 mm per second) and the final rate does not exceed 15 feet per second (4572 mm per second).
Section FC 5707. Fleet Fueling Operations*
* Editor's note: "FC" prefix added at the discretion of the editor.
5707.1 General.
Fleet fueling operations shall be conducted in accordance with this section.
5707.2 Site plan.
A site plan shall be prepared and maintained at each fleet fueling location or other approved location identifying all buildings, structures and property lines; adjoining property uses; proposed fueling locations; and slope, drainage, storm drains and other relevant site conditions. The site plan shall be made available for inspection by any department representative.
5707.3 Scope and duration of fleet fueling operations.
Cargo tanks used to conduct fleet fueling operations shall be used solely for that purpose. Fleet fueling operations shall be conducted during approved hours and the cargo tank shall leave the fleet facility after completing such operations.
5707.4 Location of dispensing at fleet facility.
Fleet fueling may be conducted at a designated location at the fleet facility and/or by proceeding from vehicle to vehicle, as approved by the department. Fleet fueling shall not be conducted at the following locations:
1. On public streets;
2. On fire apparatus access roads;
3. Inside buildings;
4. On the roof level of parking structures or other buildings;
5. Less than 10 feet (3048 mm) from buildings or property lines;
6. Less than 15 feet (4572 mm) from combustible material or waste;
7. Less than 25 feet (7620 mm) from any flammable gas storage area; and
8. Less than 25 feet (7620 mm) from any smoking, open flames or other source of ignition.
9. Less than 10 feet (3048 mm) from overhead powerlines or other aboveground electrical installation, measured from the boundary of the utility easement, or, if there is no easement, from the vertical plane of the installation at its widest point; or
10. Less than 10 feet (3048 mm) from the boundary of any transportation easement, including bridges and tunnels, as measured from the vertical plane of the easement at its widest point.
5707.5 Cargo tank and dispensing equipment.
Fleet fueling shall be conducted from a cargo tank complying with DOTn regulations or other approved vehicle, subject to the following requirements:
1. The capacity of the cargo tank shall not exceed 5,500 gallons (20 818 L), except as otherwise approved by the department.
2. The cargo tank shall be designed for fleet fueling operations, including a fuel limit switch set to a maximum of 50 gallons (189 L).
3. The dispensing hose does not exceed 100 feet (30 480 mm) in length and shall be mounted on a reel.
4. Dispensing hoses and nozzles shall be listed. The dispensing hose shall be provided with a breakaway device designed to prevent release of the combustible liquid on both sides of the breakaway point.
5707.6 Fleet fueling procedures.
Fleet fueling operations shall be conducted in accordance with the following procedures:
1. The cargo tank shall be positioned so as to prevent vehicular traffic from driving over the dispensing hose.
2. The cargo tank shall be secured from movement by setting the cargo tank's brakes and chocking the wheels, and the cargo tank's warning lights shall be activated.
3. The engines of the motor vehicles being fueled shall be shut off.
4. The dispensing nozzle shall be maintained in contact with the motor vehicle fuel tank at all times.
5. The dispensing hose and nozzle shall be placed back on the reel before moving the cargo tank.
6. Signs prohibiting smoking and open flames within 25 feet (7620 mm) of the cargo tank and the motor vehicle being fueled shall be prominently posted on the cargo tank.
7. Nighttime fueling operations shall only be conducted in adequately lighted areas.
8. Cargo tank operators shall have in their possession at all times an approved means of notifying the department of a fire or other emergency.
5707.7 Emergency procedures.
The fleet owner and the provider of fleet fueling services shall comply with the requirements of FC 5707.7.1 through 5707.7.2.
5707.7.1 Emergency response plan.
A written fire safety and emergency response plan that sets forth policies and procedures for compliance with the requirements of this section and other fire safety measures, including spill prevention and control, shall be prepared and maintained by the fleet facility and the provider of fleet fueling services and made available for inspection to any department representative.
5707.7.2 Spill Control.
A catchment basin with a capacity of not less than 5 gallons (19 L) shall be provided under the cargo tank hose nozzle/motor vehicle fuel tank connection during fuel dispensing. Spill absorbing materials, such as absorbent socks, pads or powders, in quantities sufficient to handle at least 200 gallon (757 L) spill, shall be available for immediate use. Where dispensing operations occur within 15 feet (4572 mm) of a storm drain, an approved storm drain cover or approved equivalent method shall be used to prevent any fuel spill from reaching the drain. Non-water-absorbent pads, a 10-foot-long (3048 mm) containment boom, an approved container with lid and a nonmetallic shovel shall be provided to mitigate a minimum 5 gallon (19 L) fuel spill.
5707.8 Portable fire extinguisher.
A portable fire extinguisher complying with FC 906 with a minimum rating of 40-B:C shall be provided on the cargo tank with signage clearly indicating its location.
Section FC 5801. General
5801.1 Scope.
This chapter shall govern the storage, handling and use of flammable gases.
Exceptions:
1. Flammable gases used as refrigerants in refrigerating systems, as set forth in FC 606.
2. Liquefied petroleum gases, as set forth in FC Chapter 61.
3. Fuel-gas systems, as set forth in the construction codes, including the Fuel Gas Code, other than gaseous hydrogen systems.
4. Compressed natural gas motor fuel-dispensing facilities as set forth in FC 2308.
5. Pyrophoric gases, as set forth in FC Chapter 64.
6. Liquefied natural gas (LNG) as set forth in FC Chapter 55.
5801.2 Permits.
Permits shall be required as set forth in FC 105.6.
5801.3 General.
Flammable gases shall be stored, handled and used in accordance with this chapter, FC Chapter 53 and NFPA 55. Cryogenic fluids shall additionally comply with the requirements of FC Chapter 55.
5801.4 Supervision.
Except as otherwise provided for ethylene oxide, compressed natural gas and methane recovery, the handling and use of flammable gases in quantities requiring a permit shall be under the personal supervision of a certificate of fitness holder. The storage of flammable gases in quantities requiring a permit shall be under the general supervision of a certificate of fitness holder.
5801.4.1 Ethylene oxide.
The handling and use of flammable compositions of ethylene oxide in any amount, including the cleaning and maintenance of the sterilizer, shall be under the personal supervision of a person holding a certificate of fitness.
5801.4.2 Compressed natural gas.
The connecting and disconnecting of CNG containers shall be performed by a person holding a certificate of fitness. The handling and use of CNG containers in quantities requiring a permit, or for purposes of operating a tar kettle, conducting torch operations, curing concrete, drying plaster and similar applications, or conducting hot air balloon operations, shall be under the personal supervision of a person holding a certificate of fitness applicable to such operation. In addition, a pilot's license issued by the United States Federal Aviation Administration shall be required for hot air balloon operations involving the handling and use of CNG.
5801.4.3 Methane recovery.
Methane recovery facilities shall be operated under the personal supervision of a person holding a certificate of fitness to recover methane gas from landfills.
5801.5 Prohibitions.
It shall be unlawful to:
1. fill a container with a flammable gas, except as authorized by this code or the rules, including FC 309.5.4, 2308, 2309, 5807 and 5808;
2. manufacture, generate or compress acetylene;
3. use an acetylene generator; or
4. fill balloons with hydrogen or any other flammable gas, or to possess, store, handle, use, transport, or sell any such balloon.
5801.6 Flood hazard.
Stationary flammable gas containers located in areas of special flood hazard or on the premises of Group I-2 occupancies that are hospitals located in shaded X-Zones (as defined in Section G201.2 of Appendix G of the Building Code) shall comply with Section G307.5 of the Building Code.
Section FC 5802. Definitions
5802.1 Definitions.
The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.
FLAMMABLE GAS.
FLAMMABLE LIQUEFIED GAS.
GASEOUS HYDROGEN.
HYDROGEN FUEL GAS ROOM.
METAL HYDRIDE.
METAL HYDRIDE HYDROGEN STORAGE SYSTEM.
MICROTURBINE.
Section FC 5803. General Requirements
5803.1 Quantities not exceeding the maximum allowable quantity per control area.
Flammable gases in amounts not exceeding the maximum allowable quantity per control area set forth in FC 5003.1 shall be stored, handled and used in accordance with FC 5001, 5003, 5801, 5803, 5806, 5807, 5808 and 5811.
5803.1.1 Special limitations for indoor storage, handling and use.
Flammable gases shall not be stored, handled or used in Group A, B office, E, I or R occupancies.
Exceptions:
1. Containers not exceeding a capacity of 250 SCF (7.08 m 3 ) used for maintenance purposes or operation of equipment.
2. Food service operations conducted in accordance with FC 6103.2.1.7.
5803.1.1.1 Medical gases.
It shall be unlawful to store, handle or use flammable gas as an anesthetizing agent. Medical gas systems using flammable gas for other approved purposes shall be located in medical gas storage rooms or gas cabinets as set forth in FC 5306.*
* Editor's note: "FC" prefix added at the discretion of the editor.
5803.1.1.2 Aggregate quantity.
The aggregate quantities of flammable gases used for maintenance purposes and operation of portable equipment shall not exceed the maximum allowable quantity per control area set forth in FC Table 5003.1.1(1).
5803.1.2 Storage containers.
Containers for flammable gases shall be designed, constructed, installed, operated and maintained in accordance with FC Chapter 53.
5803.1.3 Emergency shutoff.
Flammable gas piping systems shall be provided with approved manual or automatic emergency shutoff valves that can be activated at each point of use and at each source of supply.
5803.1.3.1 Shutoff at source.
A manual or automatic fail-safe emergency shutoff valve shall be installed on supply piping at the container or other source of supply. Manual or automatic valves on the containers supplying the flammable gas may serve as the emergency shutoff valve when the containers are the sole source of supply and are not manifolded.
5803.1.3.2 Shutoff at point of use.
A manual or automatic emergency shutoff valve shall be installed on the supply piping at the point of use or at a point where the equipment using the gas is connected to the supply system.
5803.1.4 Sources of ignition.
Protection against sources of ignition in areas in which flammable gases are being stored or used shall be provided in accordance with FC 5003.7* and in compliance with the following requirements:
* Editor's note: "FC" prefix added at the discretion of the editor.
5803.1.4.1 Static-producing equipment.
Static-producing equipment located in flammable gas storage areas shall be grounded.
5803.1.4.2 Signs.
"No Smoking" signs shall be posted at entrances to and in areas containing flammable gas containers, piping and equipment in accordance with FC 5003.7.1.
5803.1.5 Electrical.
Electrical wiring and equipment shall be installed and maintained in accordance with the Electrical Code.
5803.1.5.1 Bonding of electrically conductive components.
Exposed noncurrent-carrying metal components, including metal gas piping, that are part of a flammable gas supply system located in a hazardous location shall be bonded to a grounded conductor in accordance with the provisions of the Electrical Code.
5803.1.5.2 Static-producing equipment.
Static-producing equipment located in flammable gas storage or use areas shall be grounded.
5803.1.6 Liquefied flammable gases and flammable gases in solution.
Containers of liquefied flammable gases and flammable gases in solution shall be positioned in the upright position or positioned so that the pressure relief valve is in direct contact with the vapor space of the container.
Exceptions:
1. Containers of flammable gases in solution with a capacity of 1.3 gallons (5 L) or less.
2. Containers of flammable liquefied gases, with a capacity not exceeding 1.3 gallons (5 L), designed to preclude the discharge of liquid from safety relief devices.
5803.2 Quantities exceeding the maximum allowable quantity per control area.
The storage, handling and use of flammable gases in amounts exceeding the maximum allowable quantity per control area set forth in FC 5003.1 shall be in accordance with FC Chapter 50 and this chapter.
Section FC 5804. Storage
5804.1 Indoor storage.
Indoor storage of flammable gases in amounts exceeding the maximum allowable quantity per control area set forth in FC Table 5003.1.1(1), is not allowed where outdoor storage is available on the premises. Indoor storage shall be in accordance with FC 5001, 5003 and 5004, and this chapter.
5804.1.1 Explosion control.
Buildings or portions thereof containing flammable gases shall be provided with explosion control in accordance with FC 911.
5804.1.2 Maximum storage quantity.
Storage of flammable gases shall not exceed 15,000 SCF (424.8 m 3 ) in any building or structure, except at construction sites where larger quantities of CNG are authorized by rule.
5804.1.3 Flammable gas storage of 3,500 SCF ( 99.11 m3) or less.
Indoor storage shall be protected against damage or injury from falling objects or surrounding activity, and be located not less than:
1. 20 feet (6096 mm) from all classes of flammable and combustible liquids, oxidizing gases and readily combustible materials, such as paper and combustible fibers.
2. 25 feet (7620 mm) from open flames, ordinary electrical equipment or other sources of ignition.
3. 50 feet (15 240 mm) from air-conditioning equipment, air compressors and intakes of ventilation.
4. 50 feet (15 240 mm) from other flammable gas storage.
5804.1.4 Flammable gas storage of more than 3,500 SCF ( 99.11 m3).
Except as otherwise provided in the rules with respect to construction sites, a storage room may contain more than one storage area, provided that each storage area does not exceed 3,500 SCF ( 99.11 m 3 ) and storage areas are separated from each other by at least 50 feet (15 240 mm) or an approved masonry barrier having a minimum fire resistance rating of 2 hours. Each such storage area shall additionally comply with the requirements of FC 5804.1.2 and 5804.1.3.
5804.2 Outdoor storage.
Outdoor storage of flammable gases in amounts exceeding the maximum allowable quantity per control area set forth in FC Table 5003.1.1(3) shall be limited to a maximum storage of 3,500 SCF (99.12 m 3 ) except where the provisions of this code or the rules authorize storage in larger quantities at construction sites. Outdoor storage of flammable gases shall be in accordance with FC 5001, 5003 and 5004, and this chapter.
5804.2.1 Location of outdoor storage areas.
Outdoor storage areas for flammable gases shall be located at or above grade level, and in accordance with FC 5804.2.1.1 and FC Table 5804.2.1, as applicable.
FC Table 5804.2.1 Flammable Gases Distance from Outdoor Storage Areas to Exposures
Type of Outdoor Exposure Flammable Gas Storage Area More Than 1,500 SCF up to Maximum 3,500 SCF Minimum Distance to Outdoor Exposure (feet) Building or structure of combustible construction 10 a Building or structure of noncombustible construction 5 a Building openings 10 Flammable and combustible liquids Aboveground – 1,000 gallons or less 10 a Flammable and combustible liquids Aboveground – in excess of 1,000 gallons 20 a Flammable and combustible liquids Underground tank – 1,000 gallons or less 10 a Flammable and combustible liquids Underground tank – 1,000 gallons or less Vent or fill opening of tank 15 a Flammable and combustible liquids Underground tank – in excess of 1,000 gallons 15 a Flammable and combustible liquids Underground tank – in excess of 1,000 gallons Vent or fill opening of tank 15 a Flammable gas storage area, any pressure 1,500 SCF or less 10 a Flammable gas storage area, any pressure More than 1,500 SCF up to maximum 3,500 SCF 20 a Oxygen storage – 20,000 SCF or less In accordance with NFPA 51 a Oxygen storage – in excess of 20,000 SCF In accordance with NFPA 55 a Combustible material or combustible waste 10 a Air compressor intakes or inlets to ventilating or air-conditioning equipment 5 Group A occupancies and public gathering places 25 Public sidewalks and parked motor vehicles 10 Public streets, private roads and lot lines 10 a
For SI: 1 foot = 304.8 mm, 1 cubic foot = 0.02832 m 3 , 1 gallon = 3.785 L.
a. The minimum required distances shall be reduced to 5 feet when protective structures having a minimum fire-resistance rating of 2 hours interrupt the line of sight between the container and the exposure. The protective structure shall be at least 5 feet from the exposure. The configuration of the protective structure shall be designed to allow natural ventilation to prevent the accumulation of hazardous gas concentrations.
5804.2.1.1 Proximity to hazards.
Storage shall not be located where the stored flammable gases would be exposed to the following hazards in the event of the failure of their structure or containment systems:
1. Electric power lines.
2. Piping containing flammable or combustible liquids.
3. Piping containing flammable gases.
4. Piping containing oxidizing materials.
5804.2.2 Proximity to flammable and combustible liquid storage.
Storage within 50 feet (15 240 mm) of aboveground storage of flammable and combustible liquids shall be located on ground higher than such storage, except where dikes, diversion curbs, grading or walls are used to prevent these liquids from accumulating under the flammable gas storage.
5804.2.3 Electrical equipment.
Electrical equipment within 3 feet (914 mm) in any direction of an outdoor flammable gas storage area shall comply with the Class I, Division 2 wiring requirements of the Electrical Code for hazardous locations, unless such electrical equipment is separated from such area by a wall or other solid partition having no openings.
Section FC 5805. Use
5805.1 General.
Flammable gases in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1) or 5003.1.1(3) shall be used in accordance with FC 5001, 5003 and 5005, and this chapter.
Section FC 5806. Ethylene Oxide
5806.1 Scope.
This section shall govern the storage, handling and use of flammable gas containing ethylene oxide used for sterilization purposes.
5806.2 General.
Flammable gases containing ethylene oxide used for sterilization purposes shall be stored, handled and used in compliance with the requirements of this chapter and FC Chapter 53. Ethylene oxide shall additionally be stored, handled and used in compliance with the requirements of NFPA 55.
5806.3 Design and installation requirements.
The design and installation of sterilization systems shall comply with the requirements of FC 5806.3.1 through 5806.3.7.
5806.3.1 Sterilizer design.
The sterilization equipment shall be of a type listed by an approved testing laboratory, and approved by the department, and having a chamber volume of not more than 10 cubic feet (0.2832 m 3 ).
5806.3.2 Sprinkler protection.
Sterilization systems shall be located in a room or other area protected by a sprinkler system.
5806.3.3 Proximity to hazard.
Sterilization systems shall be installed away from sources of heat and ignition, means of egress and areas of activity, and shall not be installed in any room or other area in which flammable liquids or flammable gases, other than sterilizer gases, are stored, handled or used.
5806.3.4 Sterilization system room and local area ventilation.
Room ventilation and local area ventilation shall comply with the requirements of FC 5806.3.4.1 and 5806.3.4.2.
5806.3.4.1 Room ventilation.
Rooms in which sterilization systems are installed shall be equipped with ventilation systems that provide not less than 10 air changes per hour.
5806.3.4.2 Local area ventilation.
When a local ventilation system is required by the regulations of the United States Department of Labor, such ventilation system shall comply with the following requirements:
1. The discharge point of the ventilation system shall be at least 25 feet (7620 mm) from pedestrian traffic, building openings or sources of ignition. Prevailing wind direction and location of adjacent buildings shall be considered in selecting the discharge point.
2. At each discharge location there shall be a durable sign, conspicuously posted, that reads "DANGER – FLAMMABLE GAS".
3. Signage shall appear on the duct at intervals of not more than 20 feet (6090 mm) and at least once in each room and each story traversed by the duct. Such signage shall be by means of metal tags, stenciling, stamping or adhesive markers, which shall be attached or imprinted in a manner that is not readily removable.
4. A sparkproof centrifugal fan with backward curved blades designed for continuous operation shall be used, and the impeller and the ring around the impeller drive shaft shall be nonferrous.
5806.3.5 Vent lines.
Sterilization system vent lines shall be designed and installed in accordance with the following requirements:
1. The discharge point of vent lines shall be at least 25 feet (7620 mm) from pedestrian traffic, building openings and sources of ignition. Prevailing wind direction and location of adjacent buildings shall be considered in selecting the discharge point.
2. At each discharge location there shall be a durable sign, conspicuously posted, that reads "Danger – Flammable Gas".
3. Signage shall appear on the vent line at intervals of not more than 20 feet (6096 mm) and shall be present in at least one place in each room and in each story traversed by the duct.
4. A sparkproof centrifugal fan with backward curved blades designed for continuous operation shall be used, and the impeller and the ring around the impeller drive shaft shall be nonferrous.
5. Vent terminals shall be provided with a flash arrester, provided that the manufacturer of the sterilizer or the testing laboratory does not prohibit same. The flash arrester, when used, shall be constructed of material compatible with ethylene oxide and installed in such a manner as not to restrict gas flow.
5806.3.6 Storage.
Flammable gases containing ethylene oxide shall be stored in compliance with the following requirements:
1. Only containers of the type, composition and size approved by the manufacturer for the particular model of sterilization system shall be stored or used.
2. A one-day supply of flammable gases that contains ethylene oxide, but not more than 12 containers, may be stored in its original packaging in the room or other area in which the sterilizer is installed, provided that:
2.1. Such room or other area is above grade.
2.2. The containers are stored at room temperature, away from sources of heat and ignition.
2.3. The containers are stored not less than 5 feet (1524 mm) from the sterilizer, on open shelving protected by a sprinkler system or in an approved flammable liquid storage cabinet.
2.4. In addition to the amounts specified in FC 5806.3.6(2), a maximum of 3 gallons (11.4 L) liquid volume (9908 grams, or 21.8 pounds) of flammable gases that contain ethylene oxide may be stored in their original packaging in a flammable gas storage room, provided that such storage room meets the requirements of the construction codes, including the Building Code, is located above grade, is away from sources of heat and ignition, and is protected by a sprinkler system. Storage of flammable gases that contain ethylene oxide, in excess of 3 gallons (11.4 L) liquid volume, shall be in a detached above grade building designed for the storage of flammable gas in accordance with this chapter and the construction codes. For purposes of complying with the foregoing, 3-gallon (11.4 L) storage limitation, FC Table 5806.3.6 shall be used to determine the quantity of ethylene oxide being stored.
FC Table 5806.3.6 Maximum Number of Ethylene Oxide Containers Not Exceeding 3 Gallon Limit
Quantity of gas per container (grams) Maximum number of containers not exceeding 3 gallon limit 100 99 134 73 150 66 170 58 200 49
For SI: 1 gallon = 3.785 L.
5806.3.7 Certification of installation.
The owner of the facility in which the sterilization system is installed shall maintain on the premises and make available for inspection by any representative of the department a written certification from the manufacturer of the sterilizer, the certificate of fitness holder responsible for the supervision of the sterilization system and/or a New York State licensed professional engineer, that the installation conforms to the requirements of the manufacturer, the approved testing laboratory that listed the sterilizer and this section.
5806.4 Operation and maintenance.
Sterilization systems shall be operated and maintained in compliance with the following requirements:
1. The quantity of flammable gases that contain ethylene oxide connected to the sterilizer at any one time shall be no more than required for a single sterilization cycle and in no circumstance more than 200 grams (7 ounces) net weight. Containers shall be opened only while connected to the sterilizer in the manner specified by the manufacturer of the sterilizer.
2. Empty or underweight containers, containers with past expiration dates, and containers which fail to open in the sterilizer shall be kept separate from other containers and promptly removed from the premises and lawfully disposed of. Containers shall not be incinerated.
5806.5 Portable fire extinguishers.
At least one portable fire extinguisher having a minimum 40 B:C rating shall be provided in the area where flammable gases containing ethylene oxide are stored or used. The maximum travel distance to such extinguisher shall not exceed 30 feet (9144 mm).
Section FC 5807. Metal Hydride Hydrogen Storage Systems*
* Editor's note: "FC" prefix added at the discretion of the editor.
5807.1 General.
Metal hydride hydrogen storage systems shall be designed, installed, operated and maintained in accordance with this section. Metal hydride hydrogen storage systems may only be used to provide motive power on powered industrial trucks.
5807.2 Hazard classification.
Metal hydride hydrogen storage systems shall be classified pursuant to FC 5001.2 based on the hazard presented by the hydrogen it absorbs and/or stores, without regard for the metal hydride content.
5807.3 Design requirements.
Metal hydride hydrogen storage systems shall be designed and installed in compliance with the requirements of this section.
5807.3.1 Listing or approval for intended use.
Metal hydride hydrogen storage systems shall either be listed for the purpose for which they are used or be of the type for which a certificate of approval has been issued.
5807.3.2 Containers.
Containers designed for use in metal hydride hydrogen storage systems shall be designed to be filled, refilled or emptied of metal hydride only by the original equipment manufacturer or a trained and knowledgeable supplier, constructed in accordance with FC 5303.1, and marked in accordance with FC 5807.3.3.
5807.3.3 Marking and labeling.
Metal hydride hydrogen storage systems shall be marked and labeled in accordance with FC 5303.2, and FC 5807.3.3.1 through 5807.3.3.4.
5807.3.3.1 System markings.
Metal hydride hydrogen storage systems shall be marked with the following:
1. Manufacturer's name;
2. Manufacturer's emergency contact information;
3. A unique code or serial number specific to the system;
4. System name or product code that identifies the system by the type of chemistry used in the system;
5. Limitations on refilling of containers that include rated charging pressure and capacity; and
6. Service life indicating the last date the metal hydride hydrogen storage system can be used.
5807.3.3.2 Valve markings.
Metal hydride hydrogen storage system valves shall be marked with the following information:
1. Manufacturer's name;
2. The type of metal hydride hydrogen storage system with which the valve is compatible; and
3. Service life indicating the last date the valve can be used.
5807.3.3.3 Pressure relief device markings.
Metal hydride hydrogen storage system pressure relief devices shall be marked with the following information (markings for pressure relief devices integral to a valve may be made on the valve):
1. Manufacturer's name;
2. The type of metal hydride hydrogen storage system with which the device is compatible; and
3. Activation parameters that include temperature and/or pressure.
5807.3.3.4 Container markings.
Containers used in metal hydride hydrogen storage systems shall be marked with the following information:
1. Manufacturer's name;
2. Standard to which the container was designed and constructed;
3. Date of manufacturer's initial inspection and testing;
4. Individual serial number;
5. The type of metal hydride hydrogen storage system; and
6. Service life identifying the last date the container can be used.
5807.3.4 Physical protection.
Metal hydride hydrogen storage systems installed on powered industrial trucks shall be designed and installed in compliance with the requirements of this section.
5807.3.4.1 Securing containers.
The installation shall be designed to secure containers from movement when the truck is in motion.
5807.3.4.2 Impact protection.
The installation shall be designed to minimize the risk of release of metal hydride or hydrogen gas in the event of a physical impact. System components shall not extend beyond the truck platform or chassis.
5807.4 Operational and maintenance requirements.
Metal hydride hydrogen storage systems shall be operated and maintained in compliance with the requirements of this section.
5807.4.1 Valves.
Container valves shall remain closed except when containers are connected for use and the hydrogen-powered equipment is in use.
5807.4.2 Protection from temperature extremes and falling objects.
Metal hydride hydrogen storage systems shall comply with the requirements of FC 5303.5.4 and 5303.5.5.
5807.4.3 Refilling of containers.
The refilling of metal hydride hydrogen storage system containers with metal hydride shall be in accordance with the listing or approval requirements and manufacturers' instructions. The refilling of metal hydride hydrogen storage systems with hydrogen shall be in accordance with FC 309 and 2309.
5807.4.4 Periodic inspection and testing of containers.
Metal hydride hydrogen storage system containers shall be inspected, tested and requalified for service at least once every 5 years in accordance with the requirements of the United States Department of Transportation.
5807.4.5 Hydrogen purity.
The purity of the hydrogen generated by a metal hydride hydrogen storage system shall meet or exceed the listing or approval requirements, and the design specifications of the truck to be powered by the hydrogen supplied.
Section FC 5808. Hydrogen Fuel Gas Rooms*
* Editor's note: "FC" prefix added at the discretion of the editor.
5808.1 Scope.
This section shall govern the generation, storage, handling and use of gaseous hydrogen.
5808.2 General.
Devices, equipment and systems designed or used to generate gaseous hydrogen shall be installed and operated in hydrogen fuel gas rooms, except as otherwise provided in this code or approved by the department.
5808.3 Prohibition.
It shall be unlawful to:
1. install or operate devices, equipment or systems that generate gaseous hydrogen in any location other than a hydrogen fuel gas room, except as otherwise provided by this code or approved by the department.
2. install or operate devices, equipment or systems that generate gaseous hydrogen for purposes other than immediate use and incidental storage, except as otherwise provided in this code or approved by the department.
3. install or operate a hydrogen fuel gas room below grade.
5808.4 Design and installation.
Hydrogen fuel gas rooms shall be designed and installed in accordance with the Building Code and NFPA 2. Design and installation documents shall be submitted for review and approval to the Department of Buildings and the department.
Section FC 5809. Methane Recovery from Landfills
5809.1 Recovery operations.
The commissioner shall promulgate rules relating to the recovery of methane gas from landfills, to ensure the safe recovery and processing thereof.
Section FC 5810. Microturbines
5810.1 Scope.
This section shall govern the design, installation, operation and maintenance of microturbines when the aggregate electrical energy produced by all microturbines on or within a single building, including building roofs and setbacks, does not exceed 2,000 kW.
5810.2 Permits.
Permits shall be required as set forth in FC 105.6.
5810.3 Supervision.
The operation of a microturbine during regular business hours shall be under the personal supervision of a certificate of fitness holder. At all other times, a microturbine shall be under the general supervision of a certificate of fitness holder. Certificate of fitness holders shall be trained by the manufacturer or other qualified and knowledgeable person in the safe operation of the equipment, including how to safely shut down the equipment in the event of an emergency.
5810.3.1 Alarm monitoring.
The alarms initiated from the operation of a microturbine shall be annunciated both locally and remotely as required by the construction codes, including the Building Code and Mechanical Code, and the Electrical Code. The remote panel shall be located in a continuously supervised location on the premises.
5810.4 Design and installation.
Microturbines shall be designed and installed in accordance with the construction codes, including the Building Code and the Mechanical Code, and the Electrical Code. A copy of the design and installation documents for microturbine installations approved by the Department of Buildings shall be submitted to the department prior to installation.
5810.5 Operation and maintenance.
Facilities housing microturbines shall be operated and maintained in compliance with the requirements of FC 5810.5.1 through 5810.5.4.
5810.5.1 Signage and diagrams.
Signage and diagrams shall be provided in compliance with the requirements of FC 5810.5.1.1 through 5810.5.1.3.
5810.5.1.1 Emergency gas shutoff valve.
The fail safe emergency natural gas shutoff valve shall have a durable sign conspicuously posted near such valve that reads: "MICROTURBINE EMERGENCY GAS SHUTOFF".
5810.5.1.2 Fuel shutoff valve diagram.
A durable diagram shall be conspicuously posted on all doors and other entrances to a microturbine room or area indicating the location of all manual and automatic natural gas shutoff valves.
5810.5.1.3 Gas piping.
A durable sign shall be conspicuously posted on or near each door or other entrance to a room or outdoor area in which a microturbine is located, and on or adjacent to the microturbine itself, that reads: "HIGH PRESSURE NATURAL GAS".
5810.5.2 Secured location.
The microturbine shall be located in an area protected from unauthorized entry. Doors to rooms containing a microturbine shall be kept locked, but a key to such locks shall be readily available on the premises to certificate of fitness holders, maintenance personnel, and emergency responders.
5810.5.3 Combustible materials.
Combustible material shall not be stored and combustible waste shall not be allowed to accumulate in rooms or within 10 feet (3048 mm) of outdoor areas in which microturbines are located.
5810.5.4 Service contract.
The owner of any microturbine installation shall maintain a service contract with the microturbine manufacturer or other qualified service company as long as the installation exists on the premises. A copy of the service contract shall be maintained on the premises and made available for inspection by any department representative.
Section FC 5811. Compressed Natural Gas
5811.1 Scope.
This section shall govern the storage, handling and use of compressed natural gas (CNG).
Exceptions:
1. Storage, handling and use of CNG, including dispensing, for use as a fuel in motor vehicles, as set forth in FC Chapter 23.
2. The storage, handling and use of CNG in connection with special effects.
5811.2 General.
Compressed natural gas shall be stored, handled and used in accordance with this chapter, including this section, and the rules.
5811.3 General prohibitions.
It shall be unlawful to:
1. fill a CNG container with CNG or transfer CNG from one container to another, except as authorized by FC 2308.
2. store, handle or use CNG in any container with a capacity greater than 381 SCF.
3. store, handle or use CNG in a basement, cellar or other area below grade, except as authorized by the commissioner.
4. store, handle or use CNG without a permit when such storage, handling or use exceeds the quantities set forth in FC 105.6.
5. store CNG in any outdoor or indoor storage facility, or store, handle or use CNG for a stationary CNG installation, that has not been approved.
6. store, handle or use in, or bring or allow into any residential occupancy, or on any lot containing a building used for a residential occupancy, any CNG container with a capacity greater than 8.7 SCF, except as authorized by the commissioner.
7. store, handle or use in, or bring or allow into any nonresidential building, any CNG container with a capacity greater than 8.7 SCF, except as authorized by the commissioner.
8. store CNG containers on the roof of any building.
9. handle or use on the roof of any building CNG containers with a capacity greater than 8.7 SCF of gas, except as authorized by the commissioner.
10. store, handle or use CNG in or on motor vehicles, except as temporary storage incidental to transportation, or as a fuel for generating motive power for a motor vehicle, or otherwise authorized by the commissioner.
11. store, handle or use CNG for a stationary installation in any area where access to piped natural gas from a public utility is available, except as authorized by the commissioner.
12. store, handle or use CNG in any equipment used or previously used for LPG, except as may be authorized by the commissioner on an emergency basis.
13. store, handle or use CNG for space heating or water heating, except as authorized by the commissioner.
14. use nonmetallic pipe, tubing and components for any installation, appliance or equipment using CNG, except as authorized by the commissioner.
15. store, handle or use CNG at bazaars, carnivals, street fairs and similar outdoor events, including public gathering places.
16. store, handle, use or sell any CNG that has not been satisfactorily odorized with mercaptans or other approved chemical.
Section FC 5901. General
5901.1 Scope.
This chapter shall govern the storage, handling and use of flammable solids.
5901.2 Permits.
Permits shall be required as set forth in FC 105.6.
5901.3 General.
Flammable solids shall be stored, handled and used in accordance with this chapter.
5901.4 Supervision.
The handling and use of flammable solids in quantities requiring a permit shall be performed under the personal supervision of a person holding a certificate of fitness. The storage of flammable solids in quantities requiring a permit shall be under the general supervision of a person holding a certificate of fitness.
Section FC 5902. Definitions
5902.1 Definition.
The following term shall, for the purposes of this chapter and as used elsewhere in this code, have the meaning set forth in FC 202.
FLAMMABLE SOLID.
Section FC 5903. General Requirements
5903.1 Quantities not exceeding the maximum allowable quantity per control area.
The storage, handling and use of flammable solids in amounts not exceeding the maximum allowable quantity per control area as indicated in FC 5003.1* shall be in accordance with FC 5001, 5003, 5901 and this section.
* Editor's note: "FC" prefix added at the discretion of the editor.
5903.2 Quantities exceeding the maximum allowable quantity per control area.
The storage, handling and use of flammable solids exceeding the maximum allowable quantity per control area as indicated in FC 5003.1* shall be in accordance with FC Chapter 50, this chapter, and NFPA 484.
* Editor's note: "FC" prefix added at the discretion of the editor.
Section FC 5904. Storage
5904.1 Indoor storage.
Indoor storage of flammable solids in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1) shall be in accordance with FC 5001, 5003, 5004, this chapter, and NFPA 484.
5904.1.1 Pile size limits and location.
Flammable solids stored in quantities greater than 1,000 cubic feet (28 m 3 ) shall be separated into piles each not larger than 1,000 cubic feet (28 m 3 ).
5904.1.2 Aisles.
Aisle widths between piles shall not be less than the height of the piles or 10 feet (3048 mm), whichever is greater.
5904.1.3 Basement storage.
Flammable solids shall not be stored in basements or other areas below grade.
5904.2 Outdoor storage.
Outdoor storage of flammable solids in amounts exceeding the maximum allowable quantities per control area indicated in FC Table 5003.1.1(3) shall be in accordance with FC 5001, 5003, 5004, this chapter, and NFPA 484.
5904.2.1 Distance from storage to exposures.
Outdoor storage of flammable solids shall not be located within 20 feet (6096 mm) of a building, lot line, public street, private road or means of egress. A 2-hour fire barrier without openings or penetrations and extending 30 inches (762 mm) above and to the sides of the storage area is allowed in lieu of such distance. The fire barrier shall either be an independent structure, or the exterior wall of the building adjacent to the storage area.
5904.2.2 Pile size limits.
Outdoor storage of flammable solids shall be separated into piles not larger than 5,000 cubic feet (141 m 3 ) each. Piles shall be separated by aisles with a minimum width of not less than one-half the pile height or 10 feet (3048 mm), whichever is greater.
5904.3 Combustible material and combustible waste.
Combustible material and combustible waste, including packing materials and oily rags, shall not be stored in the same area as that where solid combustible metal scraps or powders are stored.
Section FC 5905. Handling and Use
5905.1 General.
The handling and use of flammable solids in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1) or 5003.1.1(3) shall be in accordance with FC 5001, 5003, 5005, this chapter, and NFPA 484.
Section FC 6001. General
6001.1 Scope.
This chapter shall govern the storage, handling and use of highly toxic and toxic materials and ozone gas generators.
Exceptions:
1. Storage and display in Group M and storage in Group S occupancies complying with the requirements of FC 5003.11.
2. Storage, handling or use for agricultural purposes, including as a pesticide, herbicide, fertilizer or similar application, when approved for such use by the federal, state or city regulatory agency having jurisdiction and when such storage, handling or use is in accordance with the manufacturer's instructions.
3. Storage, handling or personal or domestic use as a pesticide, herbicide, fertilizer in and around a residential dwelling, when approved for such use by the federal, state or city regulatory agency having jurisdiction and when such storage, handling or use is in accordance with the manufacturer's instructions.
6001.2 Permits.
Permits shall be required as set forth in FC 105.6.
6001.3 General.
Highly toxic and toxic materials and ozone gas generators shall be stored, handled and used in accordance with this chapter. Highly toxic and toxic materials that are compressed gases shall additionally comply with the requirements of FC Chapter 53.
6001.4 Highly toxic and toxic material mixtures.
The level of toxicity of highly toxic and toxic materials may be reduced by diluting such materials with other materials, such as water, to a degree that the resulting mixture may no longer be highly toxic or toxic. A mixture containing any amount of highly toxic and/or toxic material is presumed to be a highly toxic or toxic material, as applicable, unless it is otherwise certified and labeled by the manufacturer.
6001.5 Supervision.
The handling and use of highly toxic and toxic materials in quantities requiring a permit shall be under the personal supervision of a certificate of fitness holder. The storage of highly toxic and toxic materials in quantities requiring a permit shall be under the general supervision of a certificate of fitness holder.
6001.6 Prohibition.
It shall be unlawful to compress highly toxic and toxic materials.
Section FC 6002. Definitions
6002.1 Definitions.
The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.
CONTAINMENT SYSTEM.
CONTAINMENT VESSEL.
EXCESS FLOW VALVE.
HIGHLY TOXIC MATERIAL.
OZONE GAS GENERATOR.
REDUCED FLOW VALVE.
TOXIC MATERIAL.
Section FC 6003. Highly Toxic and Toxic Solids and Liquids
6003.1 Indoor storage, handling and use.
The indoor storage, handling and use of highly toxic and toxic materials shall comply with the requirements of FC 6003.1.1 through 6003.1.5.3.
6003.1.1 Quantities not exceeding the maximum allowable quantity per control area.
The indoor storage, handling or use of highly toxic and toxic solids or liquids in amounts not exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(2) shall be in accordance with FC 5001, 5003 and 6001.
6003.1.2 Quantities exceeding the maximum allowable quantity per control area.
The indoor storage, handling or use of highly toxic and toxic solids or liquids in amounts exceeding the maximum allowable quantity per control area set forth in FC Table 5003.1.1(2) shall be in accordance with FC 6001, FC 6003.1.3 through 6003.1.5.3 and FC Chapter 50.
6003.1.3 Treatment system – highly toxic liquids.
Exhaust scrubbers or other systems for processing vapors of highly toxic liquids shall be provided where a spill or accidental release of such liquids can be expected to release highly toxic vapors at normal temperature and pressure. Treatment systems and other processing systems shall be installed in accordance with the construction codes, including the Mechanical Code.
6003.1.4 Indoor storage.
Indoor storage of highly toxic and toxic solids and liquids shall comply with the requirements of FC 6003.1.4.1 and 6003.1.4.2.
6003.1.4.1 Floors.
In addition to the requirements set forth in FC 5004.12, floors of storage areas shall be of liquid-tight construction.
6003.1.4.2 Separation – highly toxic solids and liquids.
In addition to the requirements set forth in FC 5003.9.8, highly toxic solids and liquids in storage shall be located in approved hazardous material storage cabinets or isolated from other hazardous material storage by construction in accordance with the construction codes, including the Building Code.
6003.1.5 Indoor handling and use.
Indoor handling and use of highly toxic and toxic solids and liquids shall be in accordance with FC 6003.1.5.1 through 6003.1.5.3.
6003.1.5.1 Liquid transfer.
Highly toxic and toxic liquids shall be transferred in accordance with FC 5005.1.10.
6003.1.5.2 Exhaust ventilation for open systems.
Mechanical exhaust ventilation shall be provided for highly toxic and toxic liquids used in open systems in accordance with FC 5005.2.1.1.*
Exception: Liquids or solids that do not generate highly toxic or toxic fumes, mists or vapors.
* Editor's note: "FC" prefix added at the discretion of the editor.
6003.1.5.3 Exhaust ventilation for closed systems.
Mechanical exhaust ventilation shall be provided for highly toxic and toxic liquids used in closed systems in accordance with FC 5005.2.2.2.
Exception: Liquids or solids that do not generate highly toxic or toxic fumes, mists or vapors.
6003.2 Outdoor storage, handling and use.
Outdoor storage, handling and use of highly toxic and toxic materials shall be in accordance with FC 6003.2.1 through 6003.2.6.
6003.2.1 Quantities not exceeding the maximum allowable quantity per control area.
The outdoor storage, handling or use of highly toxic and toxic solids or liquids in amounts not exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(4) shall be in accordance with FC 5001, 5003 and 6001.
6003.2.2 Quantities exceeding the maximum allowable quantity per control area.
The outdoor storage, handling or use of highly toxic and toxic solids or liquids in amounts exceeding the maximum allowable quantity per control area set forth in FC Table 5003.1.1(4) shall be in accordance with FC 6001 and 6003.2 and FC Chapter 50.
6003.2.3 General outdoor requirements.
The general requirements applicable to the outdoor storage of highly toxic or toxic solids and liquids shall be in accordance with FC 6003.2.3.1 and 6003.2.3.2.
6003.2.3.1 Location.
Outdoor storage, handling or use of highly toxic or toxic solids and liquids shall not be located within 20 feet (6096 mm) of lot lines, public streets, private roads, exit discharges or exterior wall openings. A 2-hour fire barrier wall without openings or penetrations extending not less than 30 inches (762 mm) above and to the sides of the storage is allowed in lieu of such distance. The fire barrier wall shall be either an independent structure or the exterior wall of the building adjacent to the storage area.
6003.2.3.2 Treatment system – highly toxic liquids.
Exhaust scrubbers or other systems for processing vapors of highly toxic liquid shall be installed where a spill or accidental release of such liquids can be expected to release highly toxic vapors at normal temperature and pressure (NTP). Treatment systems and other processing systems shall be installed in accordance with the construction codes, including the Mechanical Code.
6003.2.4 Outdoor storage piles.
Outdoor storage piles of highly toxic and toxic solids and liquids shall be separated into piles not larger than 2,500 cubic feet (71 m 3 ). Aisle widths between piles shall not be less than one-half the height of the pile or 10 feet (3048 mm), whichever is greater.
6003.2.5 Weather protection – outdoor storage or use.
Where overhead weather protection is provided for outdoor storage or use of highly toxic and toxic liquids or solids, and the weather protection is attached to a building or structure, the storage or use area shall either be protected throughout by a sprinkler system, or storage or use vessels shall be fire-resistance rated. Weather protection shall be provided in accordance with FC 5004.13 for storage and FC 5005.3.9 for use.
6003.2.6 Outdoor liquid transfer.
Highly toxic and toxic liquids shall be transferred in accordance with FC 5005.1.10.
Section FC 6004. Highly Toxic and Toxic Compressed Gases
6004.1 General.
The storage, handling and use of highly toxic and toxic compressed gases shall comply with the requirements of this section.
6004.1.1 Prohibited indoor storage, handling and use by occupancy.
It shall be unlawful to store, handle or use highly toxic and toxic compressed gases in:
1. Group A, E, I, R or U occupancies.
2. Group B office occupancies, F, M or S occupancies, or any other areas of such occupancies that are accessible to the public.
6004.1.2 Gas cabinets.
Gas cabinets containing highly toxic or toxic compressed gases shall comply with the requirements of FC 5003.8.6 and shall be ventilated in accordance with the Mechanical Code.
6004.1.2.1 Capacity limits.
The maximum number of containers located in a single gas cabinet shall not exceed three, except that cabinets containing containers not over 1 pound (0.454 kg) net contents are allowed to contain up to 100 containers.
6004.1.2.2 Fire protection.
Gas cabinets required by FC 6004.2 or 6004.3 shall be protected by a sprinkler system. Alternative fire extinguishing systems shall not be used in lieu of a sprinkler system.
6004.1.3 Exhausted enclosures.
Exhausted enclosures containing highly toxic or toxic compressed gases shall be ventilated in accordance with the Mechanical Code.
6004.1.3.1 Fire protection.
Exhausted enclosures required by FC 6004.2 or 6004.3 shall be protected by a sprinkler system. Alternative fire extinguishing systems shall not be used in lieu of a sprinkler system.
6004.2 Indoor storage, handling and use.
The indoor storage, handling and use of highly toxic or toxic compressed gases shall be in accordance with FC 6004.2.1 through 6004.2.2.10.3.
6004.2.1 Applicability.
The applicability of regulations governing the indoor storage, handling and use of highly toxic and toxic compressed gases shall be as set forth in FC 6004.2.1.1 through 6004.2.1.3.
6004.2.1.1 Quantities not exceeding the maximum allowable quantity per control area.
The indoor storage, handling or use of highly toxic and toxic gases in amounts not exceeding the maximum allowable quantity per control area set forth in FC Table 5003.1.1(2) shall be in accordance with FC 5001, 5003, 6001 and 6004.1.
6004.2.1.2 Quantities exceeding the maximum allowable quantity per control area.
The indoor storage, handling or use of highly toxic and toxic gases in amounts exceeding the maximum allowable quantity per control area set forth in FC Table 5003.1.1(2) shall be in accordance with FC 6001, 6004.1, 6004.2 and FC Chapter 50.
6004.2.1.3 Ozone gas generators.
The indoor use of ozone gas-generating equipment shall be in accordance with FC 6005.
6004.2.2 General indoor requirements.
The general requirements applicable to the indoor storage, handling and use of highly toxic and toxic compressed gases shall be in accordance with FC 6004.2.2.1 through 6004.2.2.10.3.
6004.2.2.1 Container location.
Portable containers shall be located within gas cabinets, exhausted enclosures or gas rooms. All other containers shall be located within gas rooms or exhausted enclosures.
6004.2.2.2 Ventilated areas.
The room or other area in which gas cabinets or exhausted enclosures are located shall be provided with exhaust ventilation. Gas cabinets or exhausted enclosures shall not be used as the sole means of exhaust for any room or area.
6004.2.2.3 Leaking containers.
One or more gas cabinets or exhausted enclosures shall be available on the premises to capture the gas from the containers until such time as the leaking container can be removed from the premises and disposed of lawfully.
Exceptions:
1. Where containers are located within gas cabinets or exhausted enclosures.
2. Where approved containment vessels or containment systems are provided in accordance with the following requirements:
2.1. Containment vessels or containment systems shall be capable of fully containing or terminating a release.
2.2. Trained personnel shall be available at an approved location.
2.3. Containment vessels or containment systems shall be capable of being transported to the leaking container.
6004.2.2.3.1 Location.
Gas cabinets and exhausted enclosures shall be located in gas rooms and connected to an exhaust system.
6004.2.2.4 Local exhaust for portable containers.
A means of local exhaust shall be provided to capture leaks from portable containers. The local exhaust shall consist of portable ducts or collection systems designed to be applied to the site of a leak in a valve or fitting on the container. The local exhaust system shall be located in a gas room. Exhaust shall be directed to a treatment system in accordance with FC 6004.2.2.7.
6004.2.2.5 Piping and controls – stationary containers.
In addition to the requirements of FC 5003.2.2, piping and controls on stationary containers shall comply with the following requirements:
1. Pressure relief devices shall be vented to a treatment system designed in accordance with FC 6004.2.2.7.
Exception: Pressure relief devices on outdoor containers provided exclusively for relieving pressure due to fire exposure are not required to be vented to a treatment system provided that:
1. The material in the container is not flammable.
2. The container is not located in a diked area with other containers containing combustible materials.
3. The container is located not less than 30 feet (9144 mm) from combustible materials or structures or is shielded by a fire barrier complying with the requirements of FC 6004.3.2.1.1.
2. Filling or dispensing connections shall be provided with a means of local exhaust. Such exhaust shall be designed to capture fumes and vapors. The exhaust shall be directed to a treatment system in accordance with FC 6004.2.2.7.
3. Stationary containers shall be provided with a means of excess flow control on all container inlet or outlet connections.
Exceptions:
1. Inlet connections designed to prevent backflow.
2. Pressure relief devices.
6004.2.2.6 Gas rooms.
Gas rooms shall comply with the requirements of FC 2703.8.4 and both of the following requirements:
1. The exhaust ventilation from gas rooms shall be directed to an exhaust system.
2. Gas rooms shall be protected throughout by a sprinkler system. Alternative fire extinguishing systems shall not be used in lieu of a sprinkler system.
6004.2.2.7 Treatment systems.
The exhaust ventilation from gas cabinets, exhausted enclosures and gas rooms, and local exhaust systems required by FC 6004.2.2.4 and 6004.2.2.5 shall be directed to a treatment system. The treatment system shall be utilized to handle the accidental release of gas and to process exhaust ventilation. The treatment system shall be designed in accordance with FC 6004.2.2.7.1 through 6004.2.2.7.5 and Chapter 5 of the Mechanical Code.
Exceptions:
1. Highly toxic and toxic gases – storage. A treatment system is not required for containers in storage when the following controls are provided:
1.1. Valve outlets are equipped with gas-tight outlet plugs or caps.
1.2. Handwheel-operated valves have handles secured to prevent movement.
1.3. Approved containment vessels or containment systems are provided in accordance with FC 6004.2.2.3.
2. Toxic gases – use. Treatment systems are not required for toxic gases supplied by portable containers not exceeding 1,700 pounds (771 kg) water capacity when the following controls are provided:
2.1. A listed or approved gas detection system with a sensing interval not exceeding 5 minutes.
2.2. A listed or approved automatic-closing fail-safe valve located immediately adjacent to container valves. The fail-safe valve shall close when gas is detected at the permissible exposure limit (PEL) by a gas detection system monitoring the exhaust system at the point of discharge from the gas cabinet, exhausted enclosure, ventilated enclosure or gas room. The gas detection shall comply with the requirements of FC 6004.2.2.10.
6004.2.2.7.1 Design.
Treatment systems shall be capable of diluting, adsorbing, absorbing, containing, neutralizing, burning or otherwise processing the contents of the largest compressed gas container. Where a total containment system is used, the system shall be designed to handle the maximum anticipated pressure of release to the system when it reaches equilibrium.
6004.2.2.7.2 Performance.
Treatment systems shall be designed to reduce the maximum allowable discharge concentrations of the gas to one-half immediate dangerous to life and health (IDLH) at the point of discharge to the atmosphere. Where more than one gas is emitted to the treatment system, the treatment system shall be designed to handle the worst-case release based on the release rate, the quantity and the IDLH for all compressed gases stored or used.
6004.2.2.7.3 Sizing.
Treatment systems shall be sized to process the maximum worst-case release of gas based on the maximum flow rate of release and the entire contents from the largest container utilized.
6004.2.2.7.4 Stationary containers.
Stationary containers shall be labeled with the maximum rate of release for the compressed gas contained based on valves or fittings that are inserted directly into the container. Where multiple valves or fittings are provided, the maximum flow rate of release for valves or fittings with the highest flow rate shall be indicated. Where liquefied compressed gases are in contact with valves or fittings, the liquid flow rate shall be utilized for computation purposes. Flow rates indicated on the label shall be converted to SCF.
6004.2.2.7.5 Portable containers.
The maximum flow rate of release for portable containers shall be calculated based on the total release from the container within 5 minutes for containers with nonliquefied content and 30 minutes for containers with liquefied content. When portable containers are equipped with approved excess flow or reduced flow valves, the worst-case release shall be determined by the maximum achievable flow from the valve as determined by the valve manufacturer or compressed gas supplier. Reduced flow and excess flow valves shall be permanently marked by the valve manufacturer to indicate the maximum design flow rate. Such markings shall indicate the flow rate for air under normal temperature and pressure.
6004.2.2.8 Emergency power.
Emergency power shall be provided in accordance with the Electrical Code and the Building Code where any of the following systems are required:
1. Exhaust ventilation system.
2. Treatment system.
3. Gas detection system.
4. Smoke detection system.
5. Temperature control system.
6. Fire alarm system.
7. Emergency alarm system.
Exception: Emergency power is not required for mechanical exhaust ventilation, treatment systems and temperature control systems where approved fail-safe engineered systems are installed.
6004.2.2.9 Automatic fire detection system – highly toxic compressed gases.
An approved automatic fire detection system shall be installed in rooms or areas where highly toxic compressed gases are stored or used. Activation of the detection system shall sound a local alarm. The fire detection system shall comply with the requirements of the Building Code.
6004.2.2.10 Gas detection system.
A gas detection system shall be provided to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided. The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit.
Exception: A gas detection system is not required for toxic gases when the physiological warning properties for the gas are at a level below the accepted PEL for the gas.
6004.2.2.10.1 Alarms.
The gas detection system shall initiate a local alarm and transmit a signal to a continuously attended control station on the premises whenever it detects the presence of the gas in the atmosphere. The alarm shall be both visual and audible and shall provide warning both inside and outside the area where gas is detected.
Exception: Signal transmission to a continuously attended control station is not required where not more than one container of highly toxic or toxic gas is stored.
6004.2.2.10.2 Shutoff of gas supply.
The gas-detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected.
Exception: Automatic shutdown is not required for reactors utilized for the production of highly toxic or toxic compressed gases where such reactors are:
1. Operated at pressures less than 15 pounds per square inch gauge (psig) (103.4 kPa).
2. Continuously attended.
3. Provided with readily accessible emergency shutoff valves.
6004.2.2.10.3 Valve closure.
When the gas-detection sampling point initiating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downstream of a piping distribution manifold, the shutoff valve in the gas valve enclosure for the branch line located in the piping distribution manifold enclosure shall automatically close. Under all other circumstances, shutoff valves shall comply with the following automatic closure requirements:
1. When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure, the shutoff valve in the gas cabinet or exhausted enclosure for the specific gas detected shall automatically close.
2. Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures, the shutoff valves on all gas lines for the specific gas detected shall automatically close.
3. Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribution manifold enclosure, the shutoff valve for the container of specific gas detected supplying the manifold shall automatically close.
6004.3 Outdoor storage, handling and use.
The outdoor storage, handling and use of highly toxic and toxic compressed gases shall be in accordance with FC 6004.3.1 through 6004.3.4.
6004.3.1 Applicability.
The outdoor storage, handling and use of highly toxic and toxic compressed gases shall be in accordance with FC 6004.3.1.1 through 6004.3.1.3.
6004.3.1.1 Quantities not exceeding the maximum allowable quantity per control area.
The outdoor storage, handling or use of highly toxic and toxic gases in amounts not exceeding the maximum allowable quantity per control area set forth in FC Table 5003.1.1(4) shall be in accordance with FC 5001, 5003 and 6001.
6004.3.1.2 Quantities exceeding the maximum allowable quantity per control area.
The outdoor storage, handling or use of highly toxic and toxic gases in amounts exceeding the maximum allowable quantity per control area set forth in FC Table 5003.1.1(4) shall be in accordance with FC 6001 and 6004.3 and FC Chapter 50.
6004.3.1.3 Ozone gas generators.
The outdoor use of ozone gas-generating equipment shall be in accordance with FC 6005.
6004.3.2 General outdoor requirements.
The outdoor storage, handling and use of highly toxic and toxic compressed gases shall be in accordance with FC 6004.3.2.1 through 6004.3.2.7.
6004.3.2.1 Location.
Outdoor storage, handling or use of highly toxic or toxic compressed gases shall be located in accordance with FC 6004.3.2.1.1 through 6004.3.2.1.3.
Exception: Compressed gases located in gas cabinets complying with the requirements of FC 5003.8.6 and 6004.1.2 and located 5 feet (1524 mm) or more from buildings and 25 feet (7620 mm) or more from an exit discharge.
6004.3.2.1.1 Distance limitation to exposures.
Outdoor storage, handling or use of highly toxic or toxic compressed gases shall not be located within 75 feet (22 860 mm) of a lot line, public street, private road, exit discharge or building not associated with the manufacture or distribution of such gases, unless all of the following conditions are met:
1. Storage is shielded by a 2-hour fire-resistant barrier which interrupts the line of sight between the storage and the exposure.
2. The 2-hour fire-resistant barrier shall be located at least 5 feet (1524 mm) from any exposure.
3. The 2-hour fire-resistant barrier shall not have more than two sides at approximately 90-degree (1.57 rad) directions, or three sides with connecting angles of approximately 135 degrees (2.36 rad).
6004.3.2.1.2 Openings in exposed buildings.
Where the storage, handling or use area is located within 75 feet (22 860 mm) of a building not associated with the manufacture or distribution of highly toxic or toxic compressed gases, openings into such building other than for piping are not allowed above the height of the top of the 2-hour fire-resistant barrier or within 50 feet (15 240 mm) horizontally from the storage area whether or not shielded by a fire barrier.
6004.3.2.1.3 Air intakes.
Any area used for storage, handling or use shall not be located within 75 feet (22 860 mm) of air intakes.
6004.3.2.2 Leaking containers.
The requirements of FC 6004.2.2.3 shall apply to outdoor containers. Gas cabinets and exhausted enclosures shall be located within or immediately adjacent to outdoor storage, handling or use areas.
6004.3.2.3 Local exhaust for portable containers.
Local exhaust for outdoor portable containers shall be provided in accordance with FC 6004.2.2.4.
6004.3.2.4 Piping and controls – stationary containers.
Piping and controls for outdoor stationary containers shall be in accordance with FC 6004.2.2.5.
6004.3.2.5 Treatment systems.
The treatment system requirements set forth in FC 6004.2.2.7 shall apply to highly toxic or toxic gases located outdoors.
6004.3.2.6 Emergency power.
The requirements for emergency power set forth in FC 6004.2.2.8 shall apply to highly toxic or toxic gases located outdoors.
6004.3.2.7 Gas detection system.
The gas detection system requirements set forth in FC 6004.2.2.10 shall apply to highly toxic or toxic gases located outdoors.
6004.3.3 Outdoor storage weather protection for portable containers.
Weather protection in accordance with FC 5004.13 shall be provided for portable containers located outdoors and not within gas cabinets or exhausted enclosures. The storage area shall be protected throughout by a sprinkler system.
Exception: A sprinkler system is not required when:
1. all materials under the weather protection structure, including hazardous materials and the containers in which they are stored, are noncombustible.
2. the weather protection structure is located not less than 30 feet (9144 mm) from combustible materials or structures or is separated from such materials or structures using a fire barrier complying with the requirements of FC 6004.3.2.1.1.
6004.3.4 Outdoor use of portable containers.
Portable containers in outdoor use shall be located in gas cabinets or exhausted enclosures.
Section FC 6005. Ozone Gas Generators
6005.1 Scope.
This section shall govern the design, installation, operation and maintenance of ozone gas generators with a maximum ozone-generating capacity of 1/2 pound (0.23 kg) or more over a 24-hour period.
Exceptions:
1. Ozone-generating equipment used in Group R-3 occupancies.
2. Ozone-generating equipment used in Group H-5 occupancies in compliance with FC Chapters 27 and 50 and the provisions of FC Chapter 60 governing highly toxic gases.
6005.2 Design.
Ozone gas generators shall be designed, manufactured and tested in accordance with NEMA 250.
6005.3 Location.
Ozone gas generators shall be located in approved cabinets or ozone generator rooms in accordance with FC 6005.3.1 or 6005.3.2.
6005.3.1 Cabinets.
Ozone cabinets shall be constructed of approved materials and compatible with ozone. Cabinets shall display an approved sign that reads: OZONE GAS GENERATOR – HIGHLY TOXIC – OXIDIZER.
6005.3.1.1 Seismic design.
Cabinets shall be braced for seismic activity in accordance with the Building Code.
6005.3.1.2 Ventilation.
Cabinets shall be mechanically ventilated in accordance with the Mechanical Code.
6005.3.2 Ozone gas generator rooms.
Ozone gas-generator rooms shall be mechanically ventilated in accordance with the Mechanical Code. Ozone gas generator rooms shall be equipped with a continuous gas detection system which will shut off the generator and sound a local audible and visible alarm when concentrations above the permissible exposure limit occur.
6005.3.2.1 Signage.
Ozone gas-generator rooms shall not be normally occupied, and such rooms shall be kept free of combustible and hazardous material storage. An approved sign that reads, "OZONE GAS GENERATOR – HIGHLY TOXIC – OXIDIZER", shall be posted on or near each entrance door to an ozone gas-generator room.
6005.4 Piping, valves and fittings.
Piping, valves, fittings and related components used to convey ozone shall be in accordance with FC 6005.4.1 through 6005.4.3.
6005.4.1 Piping.
Only welded stainless steel piping or tubing shall be used.
Exceptions:
1. Double-walled piping.
2. Piping, valves, fittings and related components located in exhausted enclosures.
6005.4.2 Materials.
Materials shall be compatible with ozone and shall be rated for the design operating pressures.
6005.4.3 Signage or marking.
Piping shall be marked, or identified by a durable sign posted on or near the piping that reads, as follows: "OZONE GAS – HIGHLY TOXIC – OXIDIZER".
6005.5 Automatic shutdown.
Ozone gas generators shall be designed to shut down automatically under the following conditions:
1. When the dissolved ozone concentration in the water being treated is above saturation when measured at the point where the water is exposed to the atmosphere.
2. When the process using generated ozone is shut down.
3. When the gas detection system detects ozone.
4. Failure of the ventilation system for the cabinet or ozone-generator room.
5. Failure of the gas-detection system.
6005.6 Manual shutdown.
Manual shutdown controls shall be provided at the ozone gas generator and, when the generator is in a room, within 10 feet (3048 mm) of the main exit or exit access door.
Section FC 6101. General
6101.1 Scope.
This chapter shall govern the manufacture, storage, handling and use of LPG and the installation and operation of LPG equipment relating to such systems.
Exceptions:
1. Use of LPG or LPG mixtures as a refrigerant in a refrigerating system regulated by the construction codes, including the Mechanical Code, and FC 606.
2. Storage and use of LPG in connection with special effects.
3. Outdoor storage and use for private, noncommercial barbecues within the lot line of a Group R-3 occupancy, as set forth in FC 307.
6101.2 Permits.
Permits shall be required as set forth in FC 105.6.
6101.2.1 Deliveries.
Distributors shall not deliver LPG containers to any location in quantities requiring a permit unless a permit for such installation, storage or use has been issued for that location.
6101.3 Design and installation documents.
Design and installation documents for LPG storage facilities and stationary installations shall be submitted to and approved by the department in accordance with FC 105.4.
6101.4 General.
LPG shall be stored, handled and used, and devices, equipment and systems utilizing LPG shall be designed, installed, operated and maintained, in accordance with this chapter, the rules and NFPA 58.
6101.5 Supervision.
The storage, handling and use of LPG shall be supervised in accordance with FC 6101.5.1 through 6101.5.9.
6101.5.1 Connecting and disconnecting of LPG containers.
The connecting and disconnecting of LPG containers with a capacity greater than 16.4 ounces (0.465 kg) shall be conducted by a person holding a certificate of fitness.
6101.5.2 Tar kettles.
The storage, handling and use of a tar kettle that requires a permit shall be under the personal supervision of a person holding a certificate of fitness.
6101.5.3 Torch operations.
Torch operations using LPG containers with a capacity greater than 16.4 ounces (0.465 kg) LPG shall be performed by a person holding a certificate of fitness.
6101.5.4 Curing concrete, drying plaster and similar applications.
The use of LPG for curing concrete, drying plaster and similar applications shall be under the personal supervision of a person holding a certificate of fitness.
6101.5.5 Manhole operations.
The storage, handling and use of LPG at manhole operations shall be under the personal supervision of a person holding a certificate of fitness.
6101.5.6 Street fairs and similar outdoor gatherings.
The storage, handling and use of LPG at street fairs and similar outdoor gatherings shall be under the personal supervision of a person holding a certificate of fitness.
6101.5.7 Hot air balloon tethering operation.
The storage, handling and use of LPG for hot air balloon tethering operations shall be under the personal supervision of a person holding a certificate of fitness and a United States Federal Aviation Administration license, except as may otherwise be provided in the rules.
6101.5.8 Outdoor storage for sale.
Except for automated container exchange systems subject to FC 6109.15.1, outdoor storage of LPG for sale at mercantile establishments shall be under the personal supervision of a person holding a certificate of fitness.
6101.5.9 General supervision.
Except as otherwise provided in FC 6101.5.1 through 6101.5.8, the storage and use of LPG in quantities requiring a permit shall be under the general supervision of a person holding a certificate of fitness.
Section FC 6102. Definitions
6102.1 Definitions.
The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.
AUTOMATED CONTAINER EXCHANGE SYSTEM.
LIQUEFIED PETROLEUM GAS (LPG).
Section FC 6103. Installation of Equipment
6103.1 General.
LPG equipment shall be installed in accordance with the construction codes, including the Fuel Gas Code, the rules and NFPA 58, except as otherwise provided in this chapter.
6103.2 Indoor storage, handling and use of LPG containers.
The storage, handling and use of LPG containers indoors shall be in accordance with FC 6103.2.1 and 6103.2.2.
6103.2.1 Portable containers.
Portable LPG containers, as defined in NFPA 58, shall not be stored, handled or used indoors except as authorized by the commissioner, NFPA 58 and FC 6103.2.1.1 through 6103.2.1.8.
6103.2.1.1 Use in basement, pit or other area below grade.
LPG containers shall not be used in a cellar, basement, pit or other area below grade where heavier-than-air gas might collect. LPG containers shall not be used in an above-grade underfloor space or basement unless such location is provided with an approved means of ventilation.
Exceptions:
1. Use with self-contained torch assemblies in accordance with FC 6103.2.1.6 and the rules.
2. Manhole operations in accordance with the rules.
6103.2.1.2 Construction site heating.
Portable containers may be used in buildings, or parts thereof, undergoing construction, in accordance with NFPA 58, FC 313.5 and 3303, and the rules.
6103.2.1.3 Group F occupancies.
Portable LPG containers shall not be stored, handled or used indoors in Group F occupancies, except as the commissioner may authorize by rule.
6103.2.1.4 Group E and I occupancies.
Portable LPG containers shall not be allowed in Group E and I occupancies, except as set forth in this section and the rules. In Group E and I occupancies, portable LPG containers are allowed to be used for research purposes. Such containers shall not be used in classrooms. Such containers shall not exceed 16.4 ounces (0.465 kg) of LPG. Where more than one such container is present in the same room, each container shall be separated from other containers by a distance of not less than 20 feet (6096 mm).
6103.2.1.5 Group A occupancies.
Portable LPG containers may be brought into a building on a temporary basis for use in conducting a demonstration, or in connection with a trade show or other public exhibition. Such use, and incidental storage and handling, shall be in accordance with the rules, and the containers shall be promptly removed from the premises upon completion of the demonstration or exhibition. Where more than one LPG container is in use in the same room, and are fueling different devices or equipment, the containers shall be separated from each other by a distance of not less than 20 feet (6096 mm).
6103.2.1.6 Use with self-contained torch assemblies.
Portable LPG containers are allowed to be used to supply approved self-contained torch assemblies. Such containers shall not exceed 16.4 ounces (0.465 kg) of LPG.
6103.2.1.7 Use for food preparation.
Use of LPG for commercial cooking is allowed only when authorized by this code or the rules.
6103.2.1.8 Residential storage.
LPG container storage in Group R-2 and R-3 occupancies shall not exceed four containers per dwelling unit, each container having a capacity not exceeding 16.4 ounces (0.465 kg) of LPG. Storage of such LPG containers in a basement, cellar or other area below grade is prohibited.
6103.2.2 Industrial vehicles.
Containers on industrial vehicles shall comply with the requirements of FC 309, NFPA 58, and the rules.
6103.3 Location of equipment and piping.
Equipment and piping shall not be installed in locations where such equipment and piping is prohibited by the construction codes, including the Fuel Gas Code, or the rules.
Section FC 6104. Reserved
BetaNYC's copy has no text for this section. Read Section FC 6104 at American Legal Publishing.
Section FC 6105. Prohibited Storage, Handling and Use of LPG
6105.1 Unapproved equipment.
LPG shall not be used for the purpose of operating any device, equipment or system unless such device, equipment or system is approved for use with LPG.
6105.2 Release to the atmosphere.
LPG shall not be released to the atmosphere except as authorized by the commissioner.
6105.3 General prohibitions.
It shall be unlawful to:
1. store, handle or use LPG in any container with a capacity greater than 100 pounds (45.4 kg) of LPG.
2. store, handle or use LPG in a basement, cellar or other area below grade, except as authorized by the commissioner.
3. store LPG in any outdoor or indoor storage facility, or store, handle or use LPG for a stationary LPG installation that has not been approved.
4. store, handle or use LPG without a permit when such storage, handling or use exceeds the quantities set forth in FC 105.6.
5. store, handle or use in, or bring or allow into, any residential occupancy, or on any lot containing a building used for a residential occupancy, any LPG container with a capacity greater than 16.4 ounces (0.465 kg), except as authorized by the commissioner.
6. store, handle or use in, or bring or allow into, any nonresidential building, any LPG container with a capacity greater than 16.4 ounces (0.465 kg) LPG, except as authorized by the commissioner.
7. store LPG containers on the roof of any building.
8. handle or use on the roof of any building LPG containers with a capacity greater than 16.4 ounces (0.465 kg), except as authorized by the commissioner.
9. store, handle or use LPG in or on motor vehicles, except as temporary storage incidental to transportation, or as a fuel for generating motive power for a motor vehicle, or as otherwise authorized by the commissioner.
10. store, handle or use LPG for a stationary LPG installation in any area where access to piped natural gas from a public utility is available, except as authorized by the commissioner.
11. store, handle or use LPG in any equipment used or previously used for natural gas, except as may be authorized by the commissioner on an emergency basis.
12. store, handle or use LPG for space heating or water heating, except as authorized by the commissioner.
13. store, handle or use LPG in or for any appliance that withdraws or utilizes LPG in a liquid form except as authorized by the commissioner.
14. use nonmetallic pipe, tubing and components for any installation, appliance or equipment using LPG, except as authorized by the commissioner.
15. store LPG containers with a capacity greater than 16.4 ounces (0.465 kg) LPG indoors in any residential occupancy and in any building where an outdoor location for such LPG container storage is available.
16. store or operate a floor maintenance machine utilizing LPG indoors.
17. manufacture LPG.
18. dispense LPG and fill LPG containers as set forth in FC 6106.
Section FC 6106. Dispensing and Filling
6106.1 Dispensing and filling.
It shall be unlawful to dispense LPG, fill a container with LPG, or transfer LPG in any state from one container to another.
Section FC 6107. Safety Precautions and Devices
6107.1 Safety devices.
Safety devices on LPG containers, equipment and systems shall not be tampered with or otherwise rendered inoperable and the service unsafe.
6107.2 Smoking and other sources of ignition.
"No Smoking" signs complying with the requirements of FC 310 shall be posted when required by the commissioner. Smoking is prohibited in accordance with FC Chapter 3. Control of other sources of ignition shall comply with the requirements of FC Chapter 3 and NFPA 58.
6107.3 Clearance to combustibles.
LPG containers shall be kept a minimum of 10 feet (3048 mm) from vegetation, rubbish and other combustible waste and combustible materials.
6107.4 Protecting containers from vehicles.
Where exposed to vehicular damage due to proximity to alleys, driveways or parking areas or when required by the commissioner, LPG containers, regulators and piping shall be protected in accordance with FC 312.
Section FC 6108. Portable Fire Extinguishers
6108.1 Reserved.
6108.2 Portable fire extinguishers.
Portable fire extinguishers complying with the requirements of FC 906 shall be provided as specified in NFPA 58 and the rules.