NYC Administrative Code Title 29, Chapter 2 New York City Fire Code, part 4 of 15

Section FC 408 to Section FC 607: 28 sections.

Section FC 408. Assisted Living Facilities and Similar Occupancies

Open this section

408.1 General.

Assisted living facilities, adult homes, community residences, congregate care facilities, enriched housing, halfway houses, intermediate care facilities, residential care facilities, social rehabilitation facilities, substance abuse rehabilitation centers and other Group I-1 buildings and occupancies in which building occupants are capable of self-preservation and capable of responding to a fire or other emergency without assistance from others shall comply with the emergency preparedness requirements set forth in FC 401, 416 and this section.

408.2 Emergency preparedness in assisted living facilities and similar occupancies with fire and emergency preparedness plans (Level 2).

A fire and emergency preparedness plan in accordance with FC 401.5 shall be prepared for a Group I-1 building or occupancy with more than twenty-five persons above or below street level.

408.3 Fire and emergency preparedness staff.

The commissioner may prescribe by rule that in Group I-1 buildings or occupancies provided with voice communication capability there shall be present during regular business hours one or more members of the FEP staff required pursuant to FC 401.5.5 who hold a certificate of fitness for emergency announcements and other fire safety duties.

408.4 Special drill requirements.

In addition to the requirements of FC 401.7, persons residing in Group I-1 occupancies shall:

1. participate in a full building evacuation on an annual basis.

2. if capable of participating in an evacuation or in-building relocation without assistance, be trained to provide assistance to other such residents to the extent that their physical and mental abilities permit them to do so without additional personal risk.

408.5 Fire and emergency notice.

A fire and emergency notice in accordance with FC 405.5 shall be posted within each dwelling unit in the building or occupancy, on or immediately adjacent to the main entrance door to the dwelling unit.

Section FC 409. Correctional Facilities and Other Secured Facilities

Open this section

409.1 General.

Correctional facilities, secure psychiatric hospitals and other Group I-3 buildings and occupancies (including prisons, detention centers and pre-release centers) regulated by New York State Department of Correctional Services or the New York State Education Department, shall maintain the emergency preparedness staff and conduct the drills required by the regulations of the New York State Department of Correctional Services, and otherwise comply with the requirements of such regulations.

409.2 Staffing and staff training.

The following staffing and staff training shall be provided in Group I-3 buildings and occupancies:

409.2.1 Staffing.

In Group I-3 occupancies, staff trained in emergency preparedness procedures shall be in the building at all times, and within three floors or 300 feet (91440 mm) horizontal distance of the access door of each resident housing area. Keys necessary for unlocking doors installed in a means of egress shall be individually identifiable by both touch and sight. When movement of occupants from one smoke compartment to another or egress from the building is impeded by staff-controlled manual releases, the staff responsible for controlling such movement or egress must be continuously available to initiate emergency procedures within 2 minutes of an alarm.

Exception: Staff shall not be required to be located within three floors or 300 feet (91440 mm) of areas in which all locks may be unlocked automatically in accordance with Section 408.4 of the Building Code.

409.2.2 Staff training.

The staff responsible for emergency preparedness procedures in Group I-3 occupancies shall be trained in the use of portable fire extinguishers and other manual fire extinguishing equipment.

409.2.3 Notification.

Provision shall be made to promptly notify emergency preparedness staff of a fire or non-fire emergency.

Section FC 410. Educational Occupancies

Open this section

410.1 General.

Schools, colleges, universities and other Group B and Group E educational buildings and occupancies; Group R-1 dormitories operated by or on behalf of educational institutions; and Group E day care facilities shall comply with the emergency preparedness requirements set forth in FC 401, 416 and this section.

410.2 Day care plans.

Group E educational buildings and occupancies regulated by the New York City Department of Health and Mental Hygiene shall prepare and maintain a written safety plan addressing fire safety, medical emergencies and evacuation procedures, in compliance with the rules or other requirements of that agency.

410.3 Emergency preparedness in Group B educational occupancies with comprehensive fire safety/emergency action plans.

Group B educational buildings and occupancies required by FC 410.3.1 to have a comprehensive fire safety and emergency action plan shall comply with the emergency preparedness requirements of this section.

410.3.1 Comprehensive fire safety/emergency action plan (Level 1).

A comprehensive fire safety and emergency action plan in accordance with FC 401.4 shall be prepared for:

1. a high-rise Group B educational building with staged evacuation.

2. a high-rise Group R-1 dormitory, or high-rise Group R-2 student apartment building, with staged evacuation.

410.3.2 Fire and life safety staff.

The comprehensive fire and life safety plan required pursuant to FC 410.3.1 shall designate an FLS director and such other FLS staff as the commissioner may prescribe by rule as appropriate for the manner in which the building or occupancy, or floors thereof, is used or staffed.

410.4 Emergency preparedness in educational occupancies and dormitories with fire and emergency preparedness plans.

Educational and dormitory buildings and occupancies required by FC 410.4.1 to have a fire and emergency preparedness plan shall comply with the emergency preparedness requirements of this section.

410.4.1 Fire and emergency preparedness plan (Level 2).

A fire and emergency preparedness plan in accordance with FC 401.5 shall be prepared for the following buildings and occupancies (other than buildings subject to FC 410.3):

1. a high-rise and large-area Group B educational building.

2. a low-rise and high-rise Group E educational building.

3. a Group B educational occupancy occupied or designed to be occupied by a total of more than one hundred persons on one or more high-rise floors.

4. a Group E educational occupancy occupied or designed to be occupied by a total of more than one hundred persons on one or more high-rise floors.

5. a high-rise Group R-1 dormitory, or high-rise Group R-2 student apartment building, without staged evacuation.

6. a low-rise Group R-1 dormitory building or occupancy, or low-rise Group R-2 student apartment building or occupancy, with a total of more than fifty sleeping rooms above street level, or communal sleeping facilities above street level occupied or designed to be occupied by a total of more than fifty lodgers.

410.4.2 Fire and emergency preparedness staff.

The commissioner may prescribe by rule that in a Group B, E, Group R-1 dormitory building or occupancy and/or Group R-2 student apartment building subject to FC 410.4.1 that is provided with voice communication capability there shall be present during regular business hours one or more members of the FEP staff required pursuant to FC 401.5.5 who hold a certificate of fitness for emergency announcements and other fire safety duties.

410.4.3 Fire and emergency notice.

In Group R-1 dormitory buildings or occupancies subject to FC 410.4.1, a fire and emergency notice in accordance with FC 405.5 shall be posted within each dwelling unit in the building or occupancy, on or immediately adjacent to the main entrance door to the dwelling unit.

410.5 Emergency preparedness in dormitories without fire and emergency preparedness plans.

Group R-1 dormitory buildings and occupancies, and Group R-2 buildings and occupancies, other than buildings and occupancies subject to FC 410.4, shall comply with the following emergency preparedness requirements:

410.5.1 Fire and emergency preparedness guide and notices (Level 3).

Fire and emergency preparedness guide and notices in accordance with FC 401.6 and the rules shall be prepared, and periodically reviewed and amended, for a Group R-1 dormitory.

410.6 Special drill requirements.

Fire and non-fire emergency drills shall be conducted in all educational buildings and occupancies and dormitories in accordance with FC 401.7 and the rules. The frequency and timing of drills in educational occupancies shall be in accordance with the New York State Educational Law. Group E occupancies shall establish procedures for accounting for students after they have been relocated or evacuated during a drill.

Section FC 411. Factories

Open this section

411.1 General.

Group F buildings and occupancies shall comply with the emergency preparedness requirements set forth in FC 401, 416 and this section, except that Group F buildings and occupancies regulated by New York State Labor Law § 279 shall maintain the emergency preparedness staff and conduct the drills required by the rules of the New York City Board of Standards and Appeals, as set forth in 2 RCNY § 3-05, and otherwise comply with the requirements of such rules, and, if located in a mixed-occupancy building, shall additionally comply with the requirements of FC 416.

411.2 Emergency preparedness in factories with fire and emergency preparedness plans (Level 2).

A fire and emergency preparedness plan in accordance with FC 401.5 shall be prepared for a Group F building and occupancy with more than twenty-five persons above or below street level during regular business hours.

Section FC 412. High Hazard Occupancies

Open this section

412.1 General.

Group H buildings and occupancies shall comply with the emergency preparedness requirements set forth in FC 401, 416 and this section, except that such requirements shall not apply to Group H buildings and occupancies that have prepared one or more of the following plans in compliance with applicable requirements:

1. An emergency action plan in accordance with the regulations of the United States Department of Labor, as set forth in 29 CFR Section 1910.119.

2. A contingency plan and emergency procedures in accordance with the regulations of the New York State Department of Environmental Conservation, as set forth in 6 NYCRR Part 373.

3. A risk management plan in accordance with the rules of the New York City Department of Environmental Protection, as set forth in 15 RCNY § 41-08.

412.2 Emergency preparedness in high-hazard buildings and occupancies with fire and emergency preparedness plans (Level 2).

A fire and emergency preparedness plan in accordance with FC 401.5 shall be prepared for a Group H building and occupancy with more than twenty-five persons above or below street level during regular business hours, excluding Group H buildings and occupancies required to comply with FC 412.1(1), (2) or (3).

412.3 Group H-5 occupancies.

Group H-5 occupancies shall additionally comply with the requirements of Sections 412.3.1 through 412.3.4.

412.3.1 Plans and diagrams.

Plans and diagrams shall be maintained in an approved location on the premises indicating the plan for each area, the amount and type of HPM stored, handled and used, locations of shutoff valves for HPM supply piping, emergency telephone locations and locations of exits.

412.3.2 Periodic review and revision.

The plans and diagrams required by FC 412.3.1 shall be maintained up to date and the department shall be notified of all changes in use or occupancy, and design and arrangement of the premises.

412.3.3 Emergency response team.

On-site emergency response personnel shall be familiar with the HPM stored, handled or used on the premises. Responsible persons shall be designated to an on-site emergency response team. An emergency response team shall be staffed for each workshift to coordinate their emergency response activities with emergency response personnel, and shall cooperate with the department in planning emergency responses.

412.3.4 Emergency response drills.

Emergency drills of the on-site emergency response team shall be conducted on a regular basis but not less than once every 3 months. Records of emergency drills conducted shall be maintained in the same manner as records of fire and non-fire emergency drills.

Section FC 413. Hospitals, Nursing Homes and Other Patient and Residential Care Facilities

Open this section

413.1 General.

Hospitals, nursing homes, adult homes, ambulatory care facilities, community residences, enriched housing, intermediate care facilities and other Group I-2 buildings and occupancies and ambulatory care facilities classified as Group B occupancies, caring for or housing more than three persons not capable of self-preservation and not capable of responding to a fire or other emergency without assistance from others shall comply with the emergency preparedness requirements set forth in FC 401, 416 and this section.

413.2 Emergency preparedness in patient and residential care facilities with fire and emergency preparedness plans (Level 2).

A fire and emergency preparedness plan in accordance with FC 401.5 shall be prepared for a hospital, nursing home or other Group I-2 building or occupancy, and any ambulatory care facility.

413.3 Fire and emergency preparedness staff.

The commissioner may prescribe by rule that in all Group I-2 buildings or occupancies, and Group B ambulatory care facilities, provided with voice communication capability there shall be present during regular business hours one or more members of the FEP staff required pursuant to FC 401.5.5 who hold a certificate of fitness for emergency announcements and other fire safety duties.

413.4 Drills.

Fire and non-fire emergency drills in Group I-2 buildings and occupancies and Group B ambulatory care facilities may be conducted in accordance with the provisions of FC 413.4.1 and 413.4.2.

413.4.1 Coded alarm signal.

During drills, coded announcements may be made in lieu of an audible alarm to alert medical and other fire and emergency preparedness staff of such drill.

413.4.2 Relocation of patients.

During drills, the in-building relocation of patients to safe areas or to the exterior of the building is not required.

413.5 FEP staff training.

FEP staff training may be conducted throughout the entire building or occupancy or in specific areas thereof, but training shall be conducted in all areas of the building or occupancy within each 1 year period. Such training shall be conducted at least once each month for a total of not less than twelve training drills per year, as follows: at least three drills during the day shift; at least six drills during the evening shift, and at least three drills during the night shift.

Section FC 414. Mercantile Occupancies and Covered Malls

Open this section

414.1 General.

Department stores, retail and wholesale stores and other Group M buildings and occupancies, including covered malls, shall comply with the emergency preparedness requirements set forth in FC 401, 416 and this section.

414.2 Emergency preparedness in mercantile occupancies with comprehensive fire safety/emergency action plans.

Group M occupancies that are required by FC 414.2.1 to have a comprehensive fire safety and emergency action plan shall comply with the emergency preparedness requirements of this section.

414.2.1 Comprehensive fire safety/emergency action plan (Level 1).

A comprehensive fire safety and emergency action plan in accordance with FC 401.4 shall be prepared for:

1. a high-rise Group M building.

2. a building with one or more Group M occupancies with an aggregate area of more than 300,000 square feet (27 870 m 2 ) on high-rise floors.

3. a covered mall of more than 300,000 square feet (27 870 m 2 ).

414.2.2 Fire and life safety staff.

The comprehensive fire safety and emergency action plan required by FC 414.2.1 shall designate FLS staff consisting of an FLS director and such other FLS staff as the commissioner may prescribe by rule as appropriate for such building or occupancy, including building occupants designated by lessees of tenant spaces and similar occupancies. FLS staff shall be provided with initial and refresher FLS staff training in accordance with FC 401.4.5.2.

414.3 Emergency preparedness in mercantile buildings and occupancies with fire and emergency preparedness plans.

Group M buildings and occupancies required by FC 414.3.1 to have a fire and emergency preparedness plan shall comply with the emergency preparedness requirements of this section.

414.3.1 Fire and emergency preparedness plan (Level 2).

A fire and emergency preparedness plan in accordance with FC 401.5 shall be prepared for the following buildings and occupancies (other than buildings and occupancies subject to FC 414.2):

1. a Group M occupancy of more than 30,000 square feet (2787 m 2 ), in which more than twenty-five persons are employed during regular business hours.

2. a building with one or more Group M occupancies with an aggregate area of more than 30,000 square feet (2787 m 2 ) in which more than twenty-five persons are employed during regular business hours.

3. a covered mall of more than 30,000 square feet (2787 m 2 ).

414.3.2 Fire and emergency preparedness staff.

The commissioner may prescribe by rule that in a Group M building or occupancy provided with voice communication capability, other than buildings and occupancies subject to FC 414.2, there shall be present during regular business hours one or more members of the FEP staff required pursuant to FC 401.5.5 who hold a certificate of fitness for emergency announcements and other fire safety duties .

414.4 Special circumstances.

The commissioner shall, under circumstances prescribed by rule, modify the emergency preparedness requirements for any Group M building or covered mall where the configuration of such building or covered mall, including its pedestrian areas and means of egress, is such that the purposes of this section would be better served by requiring a different type of emergency preparedness plan or reducing the level of the emergency preparedness plan and/or staffing. The owner may request guidance from the department as to the appropriate emergency preparedness plan to be prepared for such a building or covered mall prior to preparation of the emergency preparedness plan required by this section. Such request shall be accompanied by a floor plan and other appropriate documentation of the configuration of the building or covered mall.

Section FC 415. Warehouses and Other Storage Occupancies

Open this section

415.1 General.

Warehouses and other Group S buildings shall comply with the emergency preparedness requirements set forth in FC 401, FC 416, and this section.

415.1.1 Emergency preparedness in buildings and occupancies with fire and emergency preparedness plans (Level 2).

A fire and emergency preparedness plan in accordance with FC 401.5 shall be prepared for:

1. a high-rise or large-area Group S building in which more than twenty-five persons are employed during regular business hours.

2. a non-high-rise Group S building with an aggregate of more than 20,000 square feet (1858 m 2 ) of high-piled combustible storage.

415.1.2 Fire and emergency preparedness staff.

The commissioner may prescribe by rule that in a Group S building or occupancy provided with voice communication capability there shall be present during regular business hours one or more members of the FEP staff required pursuant to FC 401.5.5 who hold a certificate of fitness for emergency announcements and other fire safety duties .

Section FC 416. Mixed Occupancy Buildings

Open this section

416.1 General.

The owners of a mixed-occupancy building and each occupancy within such building required to have an emergency preparedness plan pursuant to this chapter shall comply with the emergency preparedness requirements of this section with respect to such building and occupancies.

416.2 Single plan.

In lieu of a separate Level 1 or 2 emergency preparedness plan for each occupancy, a single emergency preparedness plan may be developed for the entire building or multiple occupancies within a single building, provided that it meets or exceeds the level of emergency preparedness required for each occupancy.

416.3 Coordination of plans.

The owner preparing an emergency preparedness plan for an occupancy in a mixed-occupancy building shall consult the owner responsible for preparing the emergency preparedness plan for each other occupancy within such building with respect to evacuation and in-building relocation procedures, including use of stairwells and elevators and designation of in-building relocation areas and assembly areas.

416.4 Coordination of drills.

The owner of a mixed-occupancy building and the owner of each occupancy within such a building required to conduct emergency preparedness drills pursuant to this chapter shall conduct a coordinated drill at least once every 2 years.

416.5 Communications.

The owner of a mixed-occupancy building and the owner of each occupancy within such a building required to have emergency preparedness plan pursuant to this chapter shall arrange for a means of communication between their respective FLS directors, FEP coordinators and/or designated FEP staff, in the event of a fire or other emergency. Such communications may be by telephone (other than a telephone requiring a coin to operate), text message, e-mail, walkie-talkie, or other approved means.

416.6 Notification of fires and non-fire emergencies and coordination of responses.

In the event of a fire or other emergency in a mixed-occupancy, notification shall be made to the other occupancies and, if necessary, the emergency preparedness staffs of the respective occupancies shall coordinate their responses to the emergency, as follows:

416.6.1 Fires.

An FLS director, FEP coordinator and/or a designated emergency preparedness staff member who becomes aware of fire on the premises shall promptly notify the FLS director, FEP coordinator and/or designated staff in the other occupancies in the mixed-occupancy building. The staffs shall coordinate the evacuation, in-building relocation and/or sheltering in place of their respective building occupants, and other matters requiring coordination pursuant to their emergency preparedness plans.

416.6.2 Non-fire emergencies.

An FLS director, FEP coordinator and/or a designated emergency preparedness staff member who becomes aware of a non-fire emergency shall promptly notify the FLS director, FEP coordinator and/or designated emergency preparedness staff for any other occupancy that could be affected by such emergency, or who is situated in the building's entrance lobby and who would be first encountered by firefighters or other emergency personnel responding to the emergency.

Section FC 501. General

Open this section

501.1 Scope.

This chapter shall govern the design, installation, operation and maintenance of buildings, structures and premises with respect to requirements designed to ensure safe and effective firefighting operations.

501.2 Permits.

Permits shall be required as set forth in FC 105.6.

501.3 Reserved.

501.4 General.

Buildings, structures and premises shall be designed, installed, operated and maintained in accordance with this chapter.

501.4.1 Newly-constructed buildings and structures.

When fire apparatus access roads, frontage spaces, private hydrants or yard hydrants are required to be installed in connection with a newly constructed building or structure, such roads, frontage spaces and hydrants shall be installed and made serviceable prior to and during the time of construction, except that, in connection with a phased development, the provision of fire apparatus access and water supply shall be as set forth in design and installation documents approved by the department. Interim access and water supply arrangements will be considered pending completion of heavy construction that would damage the roads or piping, provided that such arrangements would not unduly impair firefighting operations. Temporary signs shall be installed at each street intersection when construction of new roadways allows passage by motor vehicles in accordance with FC 505.2.

501.4.2 Lawfully existing fire department access.

Fire department access to buildings, structures and premises not fronting on a public street may be continued in compliance with the provisions of FC 102.3, 102.4, and 102.5, when such fire department access was lawfully existing as of June 30, 2008 or the date of an amendment to this code relating to fire department access. The private roads providing such lawfully existing fire department access shall be deemed to constitute fire apparatus access roads pursuant to this chapter.

501.4.3 Alterations and change of occupancy.

A building or structure undergoing alteration or a change of occupancy under the circumstances set forth in FC 501.4.3.1 and 501.4.3.2 shall comply with the requirements set forth in said sections.

501.4.3.1 Provision of sprinkler protection in altered buildings on substandard width public streets and fire apparatus access roads.

An existing building or structure that undergoes alteration or a change in use or occupancy and which is located on a public street or fire apparatus access road that has a substandard road width as set forth in FC 503.2.10 or 503.3.2 shall install a sprinkler system throughout such building, when:

1. The cost of making alterations to the building (other than alterations made to Group R-3 occupancies) in any 12-month period exceeds 60 percent of the value of the building, as set forth in New York City Administrative Code § 27-115; or

2. By reason of alteration or otherwise, there is a change in the "main use or dominant occupancy" of the building, as determined by the New York City Department of Buildings for purposes of assigning a single occupancy classification to the building, including any change from a Group R-3 occupancy to a Group R-2 occupancy, but excluding a change in use or occupancy that is limited to restoring a building that was originally constructed as a one-family or two-family dwelling to its original one-family or two-family use and occupancy; or

3. There is an increase of more than 125 percent in the square footage of the floor area of a building (excluding attic, basement and cellar space, as those terms are defined in Section 202 of the Building Code); or

4. There is a change constituting an alteration under the Building Code (excluding rooftop equipment installations) to a building of combustible (non-fireproof) construction with a height of 35 feet (10 668 mm) or less above the grade plane, that increases the height of such building to more than 35 feet (10 668 mm) above the grade plane (with the terms "grade plane" and "building height" having the meanings set forth in Section 502.1 of the Building Code); or

5. A one-family Group R-3 occupancy is being altered to a two-family Group R-3 occupancy, except where:

5.1. the alteration involves converting a basement space to a separate dwelling unit, and the new basement dwelling unit is protected throughout by a sprinkler system; or

5.2. the alteration does not involve converting a basement space to a separate dwelling unit, and either at least two lawful accessory off-street parking spaces are provided on the premises, or sufficient space exists to park two motor vehicles on a common driveway shared exclusively with an adjoining Group R-3 occupancy.

501.4.3.2 Compliance with rooftop access requirements on altered rooftops.

The rooftop of an existing building or structure that undergoes alteration shall comply with the requirements of FC 504.4.

Section FC 502. Definitions

Open this section

502.1 Definitions.

The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.

CITYWIDE STANDARD KEY.

FIRE APPARATUS ACCESS ROAD.

FIRE DEPARTMENT STANDARD KEY.

FIRE LANE.

FRONTAGE SPACE.

HIGH-RISE MEGASTRUCTURE.

KEY BOX.

MULTI-FLOOR DWELLING UNIT.

PRIVATE ROAD.

PUBLIC STREET.

TRAFFIC CALMING DEVICES.

Section FC 503. Fire Apparatus Access

Open this section

This section has 3 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read Section FC 503 at American Legal Publishing.

503.1 General.

Buildings shall be accessible to department fire apparatus by way of a public street or approved fire apparatus access road. The public street or fire apparatus access road shall provide access to the frontage space of the building.

503.2 Fire apparatus access roads.

Fire apparatus access roads shall be provided, designed, installed and maintained in accordance with this section.

503.2.1 Where required.

Where the frontage space to a building does not directly front on a public street, a fire apparatus access road shall be provided from the public street to the frontage space of such building.

503.2.2 Design and construction.

Except as otherwise provided in FC 503.2.4, a fire apparatus access road shall be designed and constructed in accordance with the standards of the New York City Department of Transportation and in compliance with the following requirements:

503.2.2.1 Surface.

Fire apparatus access roads shall have an all-weather driving surface constructed of asphalt, concrete or other approved permeable or impermeable material.

503.2.2.2 Load-bearing capacity.

Fire apparatus access roads shall be capable of supporting the imposed load of department apparatus weighing at least 80,000 pounds (36 320 kg) and the operational load of department apparatus outrigger of 52,000 pounds (23 608 kg) over a 2 foot (610 mm) by 2 foot (610 mm) area.

503.2.2.3 Grade.

The grade of the fire apparatus access road shall not exceed 10 percent unless approved by the commissioner.

503.2.2.4 Turning radius.

The required turning radius of a fire apparatus access road shall be determined by the commissioner.

503.2.2.5 Bridges and elevated surfaces.

Any bridge or elevated surface on a fire apparatus access road shall be designed for a live load sufficient to carry the imposed loads of fire apparatus. Signs shall be posted at both entrances to any bridge or elevated surfaces not capable of carrying such a load. Roadways or surfaces not capable of carrying such load that adjoin fire apparatus roads shall be separated by approved barriers and/or marked by approved signs.

503.2.2.6 Angles of approach.

The angles of approach and departure for fire apparatus access roads shall be within the limits established by the department based on the department's fire apparatus.

503.2.3 Roadway width and vertical clearance.

Fire apparatus access roads shall have an unobstructed width of not less than 34 feet (10 363 mm) excluding shoulders, except as provided in FC 503.2.3.1 through 503.2.3.4, and an unobstructed vertical clearance of not less than 14 feet (4267 mm).

503.2.3.1 Special zoning districts.

In Special Hillside Preservation Districts complying with the requirements of Section 119-214 of the Zoning Resolution, or other special zoning district regulation restricting the width of streets or private roads to less than 34 feet (10 363 mm), a fire apparatus access road shall have an unobstructed width of not less than 30 feet (9144 mm), excluding shoulders.

503.2.3.2 Small residential developments.

Where access is being provided to residential developments of not more than five dwelling units, and all buildings to which the road provides access are protected throughout by a sprinkler system, a fire apparatus access road shall have an unobstructed width of not less than 30 feet (9144 mm), excluding shoulders.

503.2.3.3 Buildings set back from street.

Where the main front entrance to a building is set back more than 40 feet (12 192 mm) from the curb line, a fire apparatus access road shall have the unobstructed width and comply with the other requirements set forth in FC 503.2.4.

503.2.3.4 Special conditions.

Where the commissioner determines that the nature and location of the building served by the fire apparatus road or other site conditions render such roadway width or vertical clearance inadequate for firefighting or other emergency response operations, the commissioner may require that the roadway width or vertical clearance be increased.

503.2.4 Buildings set back from street.

Where the main front entrance to a building is set back more than 40 feet (12 192 mm) from the curb line, a fire apparatus access road with the unobstructed roadway width required by FC 503.2.3 shall be provided to the frontage space of the building, except as otherwise provided in FC 503.2.4.1 through 503.2.4.3.

503.2.4.1 Group R-3 occupancies set back 100 feet or less.

The fire apparatus access road to a Group R-3 building with any main front entrance located more than 40 feet (12192 mm) but not more than 100 feet (30 480 mm) from the street line (as measured along the route of the fire apparatus access road) may be designed and constructed in compliance with the requirements of the Building Code for driveways where:

1. The driveway is designed and is used exclusively to provide access only to a single Group R-3 building and no more than 1 ancillary dwelling unit, as defined in Section U102 of the Building Code, and to no other buildings; and

2. The height of the Group R-3 building or an ancillary dwelling unit does not exceed 35 feet (10 668 mm) above the grade plane (with the terms "building height" and "grade plane" having the meanings set forth in Section BC 502.1 of the Building Code); and

3. The driveway provides access to the frontage space of each occupancy, except as otherwise provided in FC 504.1.2; and

4. The dwelling units are equipped with interconnected smoke alarms, in accordance with Section 907.2.11 of the Building Code.

(Am. L.L. 2024/127, 12/18/2024, eff. 6/16/2025)

503.2.4.2 Group R-3 occupancies set back more than 100-150 feet.

The fire apparatus access road to a Group R-3 building with any main front entrance located more than 100 feet (30 480 mm) but not more than 150 feet (45 720 mm) from the street line (as measured along the route of the fire apparatus access road) shall be designed and constructed with an unobstructed width of not less than 20 feet (6096 mm) in accordance with FC 503.2.2 where:

1. The fire apparatus access road is designed and is used exclusively to provide access only to a single Group R-3 building, and to no other buildings; and

2. The height of the Group R-3 building does not exceed 35 feet (10 668 mm) above the grade plane (with the terms "building height" and "grade plane" having the meanings set forth in Section 502.1 of the Building Code); and

3. The fire apparatus access road provides access to the frontage space of each occupancy, except as otherwise provided in FC 504.1.2; and

4. The dwelling units are equipped with interconnected smoke alarms, in accordance with Section 907.2.10* of the Building Code; and

* Editor's note: correct reference should be Section 907.2.11 of the Building Code.

5. The dwelling units are protected throughout by a sprinkler system; and

6. At least two off-street parking spaces for a one-family dwelling, and at least three such spaces for a two-family dwelling are provided on the premises separate from the fire apparatus access road; and

7. Parking is prohibited on the fire apparatus access road, and a "No Parking" sign conforming to the requirements of FC 503.2.7.2 is conspicuously posted at the entrance to the access road.

503.2.4.3 Group R-3 occupancies set back more than 150 feet.

The fire apparatus access road to a Group R-3 building with any main front entrance located more than 150 feet (45720 mm) from the street line (as measured along the route of the fire apparatus access road) shall be designed and constructed in compliance with FC 503.2.2, except as approved by the commissioner and subject to such conditions as the commissioner may require.

503.2.5 Obstruction.

Fire apparatus access roads shall not be obstructed in any manner that impedes vehicular access, except for lawful parking and approved traffic calming devices. The minimum widths and clearances required by FC 503.2.3 shall be maintained at all times, except with prior department approval.

503.2.5.1. Traffic calming device signage.

Traffic calming devices shall be identified by approved signage or roadway markings.

503.2.6 Secondary fire apparatus access.

The commissioner may require more than one fire apparatus access road to one or more buildings where fire apparatus access is impeded to or on the primary access road as a result of substandard width public streets, substandard width fire apparatus access roads, traffic patterns, traffic calming devices, railroad crossings, and other conditions that would significantly delay an emergency response.

503.2.7 Parking.

Motor vehicles shall not be parked on fire apparatus access roads except in lawful parking spaces that do not obstruct fire apparatus access. Curbside street parking that is lawfully established in accordance with the Zoning Resolution, Building Code and/or other applicable laws, rules and regulations is allowed on any fire apparatus access road if such curbside street parking does not reduce the usable roadway width to less than 18 feet (5486 mm). This requirement shall not be applicable to fire apparatus access roads whose design and use for parking was lawfully existing prior to the effective date of this section. For purposes of this usable roadway width determination, the dimensions of each parking space shall not be less than established by the department, consistent with the regulations of the New York City Department of Transportation for vehicles intended to be parked in such spaces, or, in the absence of such standard, as approved by the department.

503.2.7.1 Parking regulations necessitated by roadway configuration.

The commissioner may restrict parking on fire apparatus roads where the angle of approach, curvature of the road, or other roadway configuration or site conditions impede the ability of fire apparatus to make turns or otherwise navigate the fire apparatus access road. Such restrictions shall constitute an operational requirement of this code.

503.2.7.2 Signage and roadway markings.

On any fire apparatus access road upon which parking is prohibited, or upon which there are both lawful curbside street parking and parking restrictions, appropriate signage and/or roadway markings shall be provided in accordance with this section.

503.2.7.2.1 Signage.

Fire apparatus access roads subject to parking restrictions shall be marked with permanent NO PARKING – FIRE APPARATUS ACCESS ROAD signs complying with FC Figure 503.2.7.2.1. Signs shall have a minimum dimension of 12 inches (305 mm) wide by 18 inches (457 mm) high and have red letters on a white reflective background. Signs shall be posted on the sides of the fire apparatus access road upon which parking is prohibited.

NO PARKING FIRE APPARATUS ACCESS ROAD BY ORDER OF THE FIRE COMMISSIONER

FC Figure 503.2.7.2.1 No Parking Sign Fire Apparatus Access Road

503.2.7.2.2 Roadway markings.

Where required by the commissioner, approved roadway markings that include the words NO PARKING – FIRE APPARATUS ACCESS ROAD shall be provided for fire apparatus access roads to identify them as fire apparatus access roads.

503.2.8 Gates.

The design of gates across a fire apparatus access road shall be in accordance with this section.

503.2.8.1 Design requirements.

Gates across a fire apparatus access road shall comply with the following requirements:

1. The gates shall not encroach upon or otherwise reduce the required or approved width of a fire apparatus access road.

2. Gates shall be of the swinging or sliding type.

3. Manually-operated gates shall be designed to allow for operation by one person.

4. Only approved locking devices shall be used.

5. Manually-operated gates shall not be locked with a padlock or chain and padlock unless the padlock and chain are capable of being cut with standard bolt cutters.

6. Automatically-operated gates shall be designed and installed in accordance with ASTM F 2200 and UL 325, as applicable, and shall have an approved means of manual operation for emergency access by firefighters and other emergency response personnel.

503.2.8.2 Use to restrict access.

The commissioner may require the installation of locked gates where access to a road is to be restricted for fire apparatus use. It shall be unlawful to operate or park a motor vehicle on a fire apparatus access road restricted in this manner unless authorized by the commissioner.

503.2.9 Dead-end roads.

Dead-end fire apparatus access roads more than 150 feet (45 720 mm) in length, as measured from the curb line of the nearest public street which is not itself a dead-end, shall be provided with an approved means by which fire apparatus can turn around or otherwise exit the area in accordance with FC 503.2.9.1 or 503.2.9.2. Dead-end fire apparatus roads shall not exceed 400 feet (121 920 mm) in length unless approved by the commissioner.

503.2.9.1 Dead-end turnarounds.

Dead-end fire apparatus access roads shall be provided with a turnaround, as set forth in FC Table 503.2.9.1, unless the department accepts an alternative means for fire apparatus egress, as set forth in FC 503.2.9.2.

FC Table 503.2.9.1 Requirements for Dead-end Fire Apparatus Access Roads

Length (feet) Width (feet) a Turnaround Required 0 – 150 34 None required, > 150 and £ 400 34 90-foot hammerhead, or 76-foot-diameter unobstructed turnaround, 90-foot-diameter turnaround with a 15-foot-diameter island, or other approved means. b > 400 As approved As approved by the department.

For SI: 1 foot = 304.8 mm.

a. Except as otherwise provided in FC 503.2.3.

b. See FC Figure 503.2.9.

503.2.9.2 Alternative dead-end solutions.

Where the configuration of the site makes provision of a turnaround complying with FC 503.2.9.1 impracticable, the department may allow alternative means of fire apparatus egress, including use of a building entrance driveway; garage or loading dock entrance driveway; open plaza; planted open space utilizing vehicle load-bearing permeable paving materials; parking lot lane; or other driveway or lane leading to a separate through road. Any such alternative means of fire apparatus egress shall be capable of accommodating fire apparatus operation, including load-bearing construction, grades, clearances, and, if required, provision of mountable curbs.

1. 76-Foot-Diameter Turnaround

2. 90-Foot-Diameter Turnaround with up to 15-Foot-Diameter Island

3. 90-Foot Hammerhead

a. 34 feet (10 363 mm) except as otherwise provided in FC 503.2.3.

FC Figure 503.2.9 Dead-end Fire Apparatus Access Road Turnaround

503.2.10 Substandard width roads.

Buildings on fire apparatus access roads that have an unobstructed roadway width of less than 34 feet (10 363 mm) shall be protected throughout by a sprinkler system. Buildings served by a substandard width fire apparatus access road that is a lawfully existing condition pursuant to FC 102.3, 102.4 and 102.5 shall comply with this requirement when undergoing alteration or a change of occupancy in accordance with FC 501.4.3. This requirement shall not apply to any detached, unheated carport, garden shed, greenhouse, private parking garage for not more than three motor vehicles, tower or other accessory building, that is:

1. Classified by the Building Code as a Group U occupancy;

2. Not occupied or designed to be occupied for residential, commercial or office purposes; and

3. Accessory to a Group R-2 or Group R-3 occupancy.

503.3 Public streets.

Buildings fronting on public streets shall comply with the requirements of FC 503.3.1 and 503.3.2.

503.3.1 Dead-end turnarounds.

Dead-end public streets in excess of 150 feet (45 720 mm) in length, as measured from the curb line of the nearest public street that is not a dead-end, shall be provided with an approved means by which fire apparatus can turn around or otherwise exit the street, in accordance with FC 503.2.9.

503.3.2 Substandard width.

Buildings on public streets that have an unobstructed width of less than 34 feet (10 363 mm) shall be protected throughout by a sprinkler system. Buildings on substandard width public streets that were not required prior to the effective date of this section to be protected throughout by a sprinkler system shall comply with this requirement when undergoing alteration or a change of occupancy subject to FC 501.4.3. This requirement shall not apply to any Group U occupancy complying with the requirements of FC 503.2.10.

503.4 Fire lanes.

It shall be unlawful to park on a fire lane. Where other vehicular traffic is allowed on a fire lane, such traffic shall yield to fire apparatus or other department emergency response vehicles.

503.4.1 Signage.

Fire lanes subject to parking restriction shall be marked with permanent NO PARKING-FIRE LANE signs complying with FC Figure 503.4.1, and/or approved roadway markings. Signs shall have a minimum dimension of 12 inches (305 mm) wide by 18 inches (457 mm) high and have red letters on a white reflective background. Signs shall be posted on the sides of the fire lane upon which parking is prohibited.

NO PARKING FIRE LANE BY ORDER OF THE FIRE COMMISSIONER

FC Figure 503.4.1 Fire Lane Sign

503.5 Outdoor parking lots.

Outdoor parking lot lanes between rows of parking spaces and aisle space between motor vehicles shall comply with the requirements of the Building Code and Zoning Resolution, except that parking lot lanes that serve as the fire apparatus access road to the main front entrances of buildings situated in parking lots shall comply with the fire apparatus access requirements set forth in this code or such other roadway width requirements established by the Fire Department by rule.

Section FC 504. Building and Rooftop Access

Open this section

504.1 Frontage space.

Buildings shall be provided with a frontage space in compliance with the requirements of this chapter and the Building Code. The term "frontage space" shall have the meaning set forth in FC 202 for purposes of this code. For purposes of the Building Code, "frontage space" shall have the meaning set forth in Section 502 thereof.

Exception: Accessory buildings or structures classified by the Building Code as a Group U occupancy.

504.1.1 Main front entrance.

The main front entrance of a building is the entrance that is designed to serve as the primary means of ingress and egress to the building, and which is located on a side of the building that contains windows, emergency escape and rescue openings, outdoor building corridors or other building openings that serve to afford firefighters access to the upper floors of the building. Where a building has more than one entrance that is so designed and situated, the owner may designate one such entrance as the main front entrance of the building, provided, however, that if such entrance does not provide an appropriate location for firefighting operations, the commissioner may require that another entrance be designated the main front entrance.

504.1.2 Occupancies with separate entrances.

When a building contains more than one occupancy or is primary to a semi-attached or detached ancillary dwelling unit, as defined by Section U102 of the Building Code, and separate entrances are provided for individual occupancies, there shall be a main front entrance for each such occupancy, and a separate frontage space shall be provided for each main front entrance, except that a second frontage space is not required for a two-family Group R-3 occupancy or a dwelling unit ancillary to a one-family or two-family Group R-3 occupancy if unobstructed access, 5 feet (1524 mm) in width, is provided to the rear yard and to the main front entrance of any dwelling unit from either side of the building that is not directly accessible from the public street, fire apparatus access road, or driveway. An open accessory parking area not less than 5 feet (1524 mm) in width shall be sufficient to constitute unobstructed access to the rear yard, regardless of the presence of parked vehicles in such parking area.

(Am. L.L. 2024/127, 12/18/2024, eff. 6/16/2025)

504.1.2.1 Detached ancillary dwelling units.

A detached ancillary dwelling unit is not required to provide frontage space if access to the main front entrance of the detached ancillary dwelling unit is provided in accordance with the requirements for unobstructed access set forth in FC 504.1.2 and Table U103.8 of Appendix U of the Building Code.

(L.L. 2024/127, 12/18/2024, eff. 6/16/2025)

504.1.3 Building access.

An approved access walkway leading from the fire apparatus access road or driveway to the main front entrance of each occupancy or other exterior openings shall be provided when required by the commissioner.

504.1.4 Frontage space obstructions.

Obstructions, such as planters, fences and bollards, shall not be placed in the required frontage space unless they have been approved by the Commissioner of Buildings, the Commissioner of Transportation, or the commissioner, as applicable.

504.2 Maintenance of exterior doors and openings.

Exterior doors and openings required by this code or the construction codes, including the Building Code, shall be maintained in a manner that affords access by firefighting personnel in accordance with the requirements of this section, FC Chapter 10, and the Building Code. Exterior doors and their function shall not be eliminated without prior approval of the Department of Buildings. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. Required department access doors shall not be obstructed or eliminated. Exit and exit access doors shall comply with the requirements of FC Chapter 10 and the construction codes, including the Building Code. Access doors for high-piled combustible storage shall comply with the requirements of FC 3206.6.1.

504.3 Stairway access to roof.

Stairway access to the roof shall be in accordance with FC Chapter 10 and the construction codes, including the Building Code. Such stairway shall be marked at street and floor levels with a sign indicating that the stairway continues to the roof. Where roofs are used for rooftop gardens or for other lawful purposes, stairways shall be provided as required for such occupancy classification.

504.4 Rooftop access and obstructions.

The rooftops of buildings 100 feet (30 480 mm) or less in height, except rooftops with a slope exceeding 20 degrees (0.35 rad) from the horizontal, shall be designed, installed, operated and maintained in accordance with this section and in a manner that avoids or minimizes obstructions that impede firefighting operations such as vertical ventilation of heat and smoke, surveillance of rear yards and courtyards, and rooftop-aided rescues. For purposes of this section only, "rooftop" shall include rooftops of building setbacks, and "obstruction" shall mean any fixture or other item that is not readily movable by one person without the use of tools or equipment, including air conditioning systems, billboards and other signs, cellular antenna equipment, columns and girders, cooling towers, fuel oil storage tanks, generators, heating systems, planters, solar panels, ventilation system ducts, intakes and exhausts, and window cleaning equipment, but shall not include nonmetallic decking that is readily cut by standard power tools.

504.4.1 Rooftop access.

Access to building rooftops shall be provided for fire operations by providing unobstructed access to the rooftop, including unobstructed passage across the building parapet, perimeter fence or other obstructions, and a safe landing. Such rooftop access shall be provided in compliance with the following required clearances:

1. For each 12 linear feet (3658 mm) of building perimeter accessible from the frontage space of the building and from any other exposure accessible to fire apparatus, a minimum clearance of 6 feet (1829 mm) in width and 6 feet (1829 mm) in depth from any obstruction shall be provided at the parapet wall or other perimeter of the rooftop.

2. Where such building perimeter is 24 linear feet (7315 mm) or greater, but less than 36 linear feet (10 973 mm), the required clearance openings shall be separated by a distance of not less than 12 linear feet (3658 mm).

3. Where such building perimeter is 36 linear feet (10 973 mm) or greater, the required clearance openings may be contiguous, provided, however, that such contiguous openings shall not exceed 12 linear feet (3658 mm) and shall be separated from other required clearance openings by a distance of not less than 12 linear feet (3658 mm).

4. Each exposure accessible by fire apparatus shall be treated separately for purposes of locating clearance openings and otherwise complying with the requirements of this provision.

5. Awnings, sun control devices, solar panels or other structures affixed to an exterior building wall below the roof line shall not obstruct fire apparatus aerial ladder access to the rooftop perimeter access locations.

6. Scaffolding obstructing rooftop access locations shall be designed to provide secure landings at such locations in an approved manner.

7. The rooftop parapet or other perimeter railing or barrier shall be designed to facilitate the safe dismounting of a firefighter from an aerial ladder. Any such parapet, railing or barrier on a building constructed after the effective date of this section, or installed pursuant to a work permit issued by the Department of Buildings after such date, shall be of substantial construction capable of supporting a minimum of 350 pounds (159 kg) and shall be designed with a level surface at least 5 inches in width (127 mm) so as to allow a firefighter to safely step on it, as prescribed by the department, or other approved design. Where the height of the rooftop parapet, railing or other enclosure is more than 48 inches (1219 mm), an approved landing platform and steps or ladder shall be provided to allow a firefighter to safely dismount and descend to the rooftop. Design and installation documents shall be submitted to the department for approval.

8. To the maximum extent practicable, wind turbines or other equipment with moving components shall be installed at rooftop location where they do not impede access or encroach up rooftop access landings, clear path, or required clearances, but in no case shall fan blades or other moving component operate within 3 feet (914 mm) of the rooftop access required by this section, including the 9-foot (2743 mm) height above the parapet or other rooftop perimeter railing or barrier and rooftop access landings. The tips of the fan blades and the edges of other moving components shall bear reflective markings and identified by caution warning signs or other means, to ensure that persons on the rooftop are aware of the presence of such equipment.

504.4.2 Rooftop access signs and markings.

Where required by the department, a sign, decal or approved marking shall be provided on the exterior wall of a building, at an approved location on a lower story, directly below the rooftop perimeter access landings, to identify the location of such rooftop access. The department may require such signs or markings when rooftop conditions not apparent from the street make rooftop access unsafe at locations other than the approved building perimeter access landings, or do not allow for access to the roof.

504.4.3 Rooftop access landings.

At each rooftop perimeter access location, there shall be a safe landing area not less than 6 feet (1829 mm) in any dimension, and 9 feet (2743 mm) in height above the parapet or other rooftop perimeter railing or barrier. The access landing shall be connected to the clear path required by FC 504.4.4. The landing shall not be obstructed by a fence, except as approved. If approved, such fence shall be provided with a standard 3-foot-wide (914 mm) gate that swings inward. Such gate may be secured by a padlock and chain capable of being cut by standard bolt cutters from either side of the gate, or secured by other approved device.

504.4.4 Rooftop clear path.

A clear path of not less than 6 feet (1829 mm) horizontal width and 9 feet (2743 mm) in height shall be provided from the front of the building to the rear of the building; from one side of the building to the other for each 100 linear feet (30 480 mm) of rooftop width and depth such that the maximum distance between clear paths is 100 feet (30 480) mm. Such path shall comply with the following requirements:

1. Such clear path shall be accessible from each rooftop perimeter access landing required pursuant to FC 504.4.3.

2. Such clear path shall afford reasonable access to bulkhead doors, fire escapes, access ladders, cockloft vents, skylights, scuttles, shafts and rooftop stationary energy storage systems. Such access shall include, to the maximum extent practicable, 3-feet (914 mm) clearance on three sides of the skylight or scuttle. On buildings constructed after the effective date of this section, the clear path shall afford reasonable access, to the maximum extent practicable, to windowed areas on any side of the building that is not fire apparatus accessible.

3. A conduit or pipe may cross such clear path in accordance with FC 504.4.7.

4. Any lawful fence obstructing such clear path shall be provided with a standard 3-foot-wide (914 mm) gate, which may be secured by padlock or chain capable of being cut by standard bolt cutters, or secured by other approved device.

5. When the main building rooftop has more than one level, a fixed ladder or other approved means shall be provided to afford access along the clear path from one roof level to the next, excluding any height differential between levels exceeding one story or 16 feet (4077 mm), and any level with a rooftop area that is less than 6 feet (1829 mm) in any dimension.

6. On an "H"-shaped building or other building whose irregular configuration renders a single clear path inadequate to provide access to each wing of the building or other rooftop area, the commissioner may require one or more additional clear paths to provide adequate access to such rooftop areas.

7. The rooftop surface serving as the clear path shall not be constructed of glass or other transparent or translucent material, nor shall it require a firefighter to walk upon any flush-mounted solar panels or other energized equipment.

8. Rooftop stationary energy storage systems shall be designed and installed in accordance with FC 608 and the rules, including ensuring that the deflagration zone is not in the clear path and the exhaust system does not vent into the clear path.

9. The requirements for wind turbines and other equipment with moving components set forth in FC 504.4.1(8) shall be applicable to the rooftop clear path.

504.4.5 Rooftop clear path protection.

Adequate protection, in the form of a securely affixed protective railing or barrier that is at least 42 inches (1067 mm) above the roof surface in height along the clear path, shall be provided for any shaft, building perimeter or elevation adjoining the clear path or rooftop perimeter access landing (except the rooftop access landing itself).

Exception: Height differentials of 6 feet (1829 mm) or less.

504.4.6 Required rooftop clearances.

A minimum clearance of 6 feet (1829 mm) in all directions shall be provided from each door opening onto a rooftop from a dwelling unit, stairway, bulkhead, or other occupied space or means of egress, as measured from the door hinge. A minimum clearance of 3 feet (914 mm) in all directions shall be provided from any fire escape or rooftop access ladder, as measured from each side of the ladder or landing.

504.4.7 Rooftop conduits and piping.

To the maximum extent practicable, conduits, including cable trays, and piping, shall be installed at rooftop locations where they do not obstruct rooftop access landings, clear path or required clearances. If it is impracticable to avoid these areas, conduits and piping shall be designed and installed to facilitate access and minimize tripping hazards. Steps or ramps (or platforms with steps, ramps or ladders) shall be provided that are constructed of noncombustible material, equipped with railings, and designed to allow any conduit or piping installations that exceed 1 foot (305 mm) in height above the roof surface, or more than 24 inches (610 mm) in width, to be readily traversed. Steps, ramps, platforms and ladders shall not be placed in areas or in a manner that would obstruct any door or means of egress. All conduits and piping installations shall be color-coded with continuous, durable and weatherproof reflective or luminescent markings as follows, and for conduit and piping installed after July 1, 2014, shall be continuously labeled in an approved manner to indicate its contents:

1. High voltage wiring – Red.

2. Low voltage wiring – Orange.

3. Natural gas piping – Yellow.

4. Other compressed gas piping – Yellow, labeled at regular intervals with the type of gas.

5. Fuel oil piping – Yellow with black stripes.

504.4.8 Rooftop access underneath cantilevered or overhead buildings.

Where a building is constructed directly above another building, including a building cantilevered over another building, a vertical clearance from the rooftop of the building below shall be provided for firefighting operations in accordance with the following requirements. Design and installation documents documenting compliance with this section, including the fire analysis filed with the Department of Buildings, shall be submitted for Fire Department review and approval. Such vertical clearance:

1. shall be at least 12 feet (3658 mm); and

2. shall be at least 9 feet (2743 mm) above the highest building feature on the rooftop when the building feature is 25 feet (7620 mm) or less from the closest exterior surface of the building constructed above; but

3. shall not apply to rooftop areas above which a noncombustible screen wall or other similar structure has been constructed for purposes of zoning compliance, provided that such structure extends below the cantilever from the side wall of the new building facing a street for a width not to exceed 8 feet (2438 mm) and a depth not to exceed 12 feet (3658 mm).

504.4.9 Group R-3 occupancies with shallow-pitched roofs.

A Group R-3 occupancy that is primarily a building with a roof pitch of less than 9.5 degrees shall comply with FC 504.4, notwithstanding the presence of a pitched roof element such as a mansard or a penthouse with a pitched roof. A Group R-3 occupancy with a roof pitch of 9.5 degrees or more shall comply with FC 512.3, not FC 504.4.

504.4.10 Rooftop telecommunications installations.

Telecommunications installations on building rooftops, including cellular antenna installations, shall additionally comply with the following requirements:

1. Transmitting antennas shall be identified by affixing to the antenna, the antenna mounting, or a conspicuous location near the antenna, continuous, durable and weatherproof reflective or luminescent markings and not less than 3-inch (76-mm) lettering that reads, "TRANSMITTER." If the antenna is enclosed or screened, such marking shall be placed on the exterior of the enclosure or screening.

2. A durable sign shall be conspicuously posted near the main building electrical panel, on the side of the bulkhead or rooftop hatch, and on or near any equipment closet, roof base station or similar telecommunications antenna installation, identifying the owner of the installation, providing a 24-hour/7-day per week telephone number by which such owner can be contacted, and identifying the installation, including antennas and other powered equipment associated with the installation, by number or other unique designation.

3. Transmitting antennas and other rooftop installations subject to radio frequency exposure limits, as set forth in the regulations of the Federal Communications Commission, shall be installed in a manner that complies with the applicable exposure limits, including those applicable to rooftop access, landing, clear path and clearance areas and other rooftop areas to which the general population has uncontrolled access. Certification of compliance, in an approved format, by a qualified person trained and knowledgeable in the measurement of Federal Communications Commission radio frequency exposure limits shall be submitted to the department with rooftop access applications and upon request in connection with rooftop access inspections.

504.4.11 Rooftop gardens.

Rooftop gardens and landscaping, including living walls, shall be designed, installed, operated and maintained in compliance with the requirements of the construction codes, including the Building Code and this section.

504.4.11.1 Perimeter and clear path access.

Rooftop gardens and landscaping shall not obstruct any rooftop area access to which is required pursuant to this section, including rooftop perimeter access and landings, clear path and clearances.

504.4.11.2 Landscaped rooftops.

Rooftop access landings, clear paths and other areas access to which is required pursuant to FC 504.3 and 504.4.4 may be landscaped in compliance with the following requirements:

1. The earth or other landscaping material in such areas shall be securely contained and compacted in such a manner as to ensure a stable, continuous surface with a slope not exceeding the slope of the rooftop.

2. Vegetation in such areas shall be limited to grass or other plants that do not exceed 12 inches (305 mm) in height and do not constitute a tripping hazard or pitfall.

504.4.11.3 Maintenance and water supply.

Rooftop gardens and landscaping shall be maintained and provided with a water supply in accordance with FC 318. Equipment used for the maintenance of rooftop gardens and landscaping shall be stored in accordance with FC 318.

504.4.12 Rooftop solar installations.

Rooftop solar installations shall be designed, installed, operated and maintained in accordance with FC 512.

504.4.13 Maintenance of rooftop building features.

Rooftop installations shall not obstruct the function, use or accessibility of any rooftop building features, including those listed in FC 504.4.4(2). Such rooftop building features shall be maintained in good working order to facilitate firefighting operations.

504.5 Rooftop access on buildings more than 100 feet in height.

To the maximum extent practicable, a clear path complying with FC 504.4.4 shall be provided on all buildings more than 100 feet (30 480 mm) in height constructed after the effective date of this section from the bulkhead or other point of rooftop access to the rooftop perimeter on any side of the building that has windows.

Section FC 505. Premises Identification

Open this section

505.1 Address numbers.

Buildings and structures shall have their lawful address numbers, building numbers and/or other approved building identification placed at a location on or near a building that allows such building identification to be plainly discernible from the public street or frontage space. These numbers shall contrast with their background. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 1/2 inch (12.7 mm). Address numbers shall additionally comply with the requirements of the Building Code, New York City Housing Maintenance Code and the borough president of the borough in which such building is located.

505.1.1 Identification of buildings in developments.

Buildings located within outdoor shopping malls, office parks, housing complexes or other developments shall be identified in compliance with the requirements of FC 505.1. Where required by the commissioner, approved signage identifying the street address of each building in the development and, in outdoor shopping malls, each tenant space or similar occupancy, and the direction to such building or tenant space, shall be provided. Such signage shall be clearly visible at the intersection of the public street and any fire apparatus access road that provides access to buildings in the development. In any development in which one or more buildings does not have a separate street address, or in any outdoor shopping mall in which one or more tenant spaces or similar occupancies does not have a separate street address, the commissioner may require approved signage indicating the location and direction to each such building or tenant space upon a determination that such signage is necessary to enable firefighting or other emergency response personnel to expeditiously locate such buildings or tenant spaces within the development.

505.2 Street or road signs.

Streets and roads within developments shall be identified with approved signs in accordance with the requirements of the New York City Department of Transportation. Temporary signs shall be installed at each street intersection when construction of new roadways allows passage by motor vehicles. Signs shall be of an approved size, weather resistant and be maintained until replaced by permanent signs.

505.3 Identification of apartment and guest rooms.

The location of, and entrance to, each dwelling unit (guest room or sleeping room) in a Group R-1 building or occupancy, and each dwelling unit in a Group R-2 building or occupancy, shall be identified in accordance with this section and the rules to assist emergency response personnel responding to fires, medical emergencies and other emergencies at the premises.

505.3.1 Apartment and guest room numbers.

Each dwelling unit shall be identified on the public corridor side of the door by a room number and/or letter marking or sign conspicuously and durably printed or posted on or adjacent to at least one entrance door.

505.3.2 Public entry and corridor signage.

In a Group R-1 or R-2 building or occupancy with more than eight dwelling units on a floor, a sign shall be conspicuously posted in the elevator lobby or other public entry on each floor, and in the public corridor opposite each stairwell entrance, identifying by directional arrows and dwelling unit numbers and/or letters, the direction to each dwelling unit. Such signage need not be provided in the public entry or opposite any stairwell entrance in any building or on any floor where the entrances to dwelling units are located in a single direction from such entry or stairwell entrance.

505.3.3 Existing installations.

Existing buildings and occupancies shall comply with the operational requirements for marking and signage set forth in FC 505.3.1 and 505.3.2 within 2 years of the effective date of this section.

505.4 Apartment, guest room and stairwell fire emergency markings.

Dwelling units (apartments, guest rooms and sleeping rooms) and stairwell entrances in Group R-1 and Group R-2 buildings and occupancies shall be marked in accordance with this section and the rules to facilitate firefighting and emergency rescue operations at the premises.

505.4.1 Multi-floor dwelling units.

The entrance door to a multi-floor dwelling unit in a Group R-1 or Group R-2 building or occupancy shall be identified on the door jamb on the public corridor side of the door by an approved fire emergency marking, not more than 12 inches (305 mm) from the bottom of the door, indicating the dwelling unit number and/or letter. In addition, every door of each such multi-floor dwelling unit that opens to a public corridor or other means of egress shall be identified on the public corridor side of the door by one or more upward or downward-pointing arrows indicating the direction(s) of the other floor(s) to which the multi-floor dwelling unit is connected.

505.4.2 Apartment and sleeping rooms.

Except as otherwise provided in FC 505.4.1, and except in buildings protected throughout by a sprinkler system, in a Group R-1 or R-2 building or occupancy with more than eight dwelling units on a floor, each dwelling unit shall be identified on the door jamb on the public corridor side of the door by an approved fire emergency marking, not more than 12 inches (305 mm) from the bottom of the door, indicating the dwelling unit number and/or letter.

505.4.3 Stairwell signage.

Except in buildings protected throughout by a sprinkler system, each stairwell door in a building or occupancy subject to compliance with the requirements of FC 505.4.1 or FC 505.4.2 shall be identified as a stairwell door on the door jamb on the public corridor side of the door with an approved marking or sign not more than 12 inches (305 mm) from the bottom of the door, unless such stairwell entrance has been marked in compliance with Section 1024* of the Building Code.

* Editor's note: correct reference should be Section 1031 of the Building Code.

505.4.4 Design and materials.

The fire emergency markings for dwelling unit entrance doors shall be of photoluminescent, retroreflective or other approved material, durable, water-resistant and securely affixed and shall use Arabic numerals and/or English alphabet letters. The fire emergency marking on multi-floor dwelling units shall be a minimum of 3 inches (76 mm) high and 1 1/2 inches (38 mm) wide with a stroke width of 1/2 inch (12.7 mm) and the fire emergency markings required by FC 505.4.2 and 505.4.3 shall be in accordance with the rules. Any approved fire emergency marking may be used provided that the same type of marking is consistently used throughout the building. Photoluminescent markings and signs shall comply with the Building Code requirements for photoluminescent exit path markings.

505.4.5 Existing installations.

Existing buildings and occupancies shall comply with the operational requirements for marking and signage set forth in FC 505.4.1 within 2 years of the effective date of this section, and with the operational requirements for marking and signage as set forth in FC 505.4.2 and 505.4.3 within 3 years of the effective date of this section.

505.5 Covered mall exterior door signage.

Each exterior door that provides access directly to a tenant space in a covered mall or to a corridor serving as an exit passageway from one or more such tenant spaces shall be provided with signage or markings identifying the business occupying such space or spaces. Such identification shall be durably and conspicuously posted or marked on or adjacent to the outdoor side of the exterior door such that the business name is readily discernible from nearby parking lot lanes.

Section FC 506. Keys and Key Access

Open this section

506.1 General.

This section shall govern the use and possession of keys required for firefighter service elevator operation, key boxes, gates and barriers, and other locked areas, boxes or cabinets to which the department requires access for firefighting operations.

506.2 Citywide-standard keys.

Citywide-standard keys shall be used to operate firefighter service elevators, and to provide access to key boxes, gates and barriers, and other locked areas, boxes or cabinets to which the department requires access for firefighting operations, in accordance with this section. All locks required to be operable by the citywide-standard key shall also be operable by the fire department standard key. Access to a fire department standard key shall be in accordance with FC 506.4.

506.2.1 Elevator keys.

Firefighter service elevator key switches shall be operable by a citywide standard key.

506.2.2 Key boxes.

Where access to or within a building, structure or premises is restricted because of locked doors or other building openings, or where immediate access would be needed for lifesaving or firefighting purposes in the event of a fire or other emergency, the department may require that keys be kept in a key box installed in an approved location. The owner shall ensure that the key kept in the lock box is replaced whenever a lock securing the area, box or cabinet is changed or rekeyed.

506.2.3 Gates and barriers.

Wherever a gate or similar barrier obstructs fire department access or fire apparatus access to a premises, and a lock is installed on such gate or barrier, the lock shall be of an approved type and operable by a citywide standard key.

506.2.4 First responder box.

The department may require that a locked box operable by a citywide standard key be provided in a designated area in a building, structure or premises to store plans, building information cards or other materials that will assist firefighting personnel responding to a fire or other emergency at the premises.

506.3 Access to citywide standard keys.

It shall be unlawful to possess a citywide standard key except for persons authorized to possess such key in connection with the following purposes:

1. Owners of buildings equipped with firefighter service elevators, or their authorized representatives, including FLS directors and FEP coordinators.

2. Elevator contractors.

3. Elevator inspectors of the Department of Buildings.

4. Persons authorized to conduct testing and other maintenance or servicing of fire alarm systems.

5. Authorized department personnel.

6. New York City police officers and other approved law enforcement personnel.

7. Building owners required to have key boxes, locked boxes or locked gates or barriers pursuant to this code, or their authorized representatives.

8. Building owners with locked gates and barriers that block required fire department and fire apparatus access.

9. Building owners, impairment coordinators, and persons authorized to install or maintain in-building auxiliary radio communication systems.

10. Locksmiths or other authorized key suppliers when in connection with their lawful business operations.

506.4 Access to fire department standard keys.

It shall be unlawful to possess a fire department standard key, except for authorized department personnel and other approved persons. The right to possess and use a citywide-standard key pursuant to FC 506.2 does not confer the right to possess or use a fire department standard key. Licensed locksmiths are authorized to use the fire department standard key to verify the operability by such key as required by FC 506.2 of locks and devices required to be operable by a citywide-standard key, but are not authorized to provide a fire department standard key to any unauthorized person for the purpose of complying with FC 506.2.

Section FC 507. Fire Protection Water Supplies

Open this section

507.1 Required water supply.

For premises requiring the installation of private fire hydrant systems or yard hydrant systems, an approved water supply capable of supplying the required design capacity for fire protection shall be provided.

507.2 Type of water supply.

A water supply shall consist of pressure tanks, gravity tanks, water mains or other approved fixed systems capable of providing the required design capacity.

507.2.1 Private fire service mains.

Private fire service mains and appurtenances shall be installed in accordance with NFPA 24 and the requirements of the New York City Department of Environmental Protection.

507.2.2 Water tanks.

Water tanks for private hydrant systems and yard hydrant systems shall be installed in accordance with NFPA 22.

507.2.3 Yard hydrant systems.

Outdoor amusement parks, bulk plants or terminals, lumber yards, trailer camps, industrial parks, and similar occupancies shall be provided with a yard hydrant system installed in compliance with the requirements of the construction codes, including the Building Code, this section and FC 914. Yard hydrants shall be installed such that the entire area may be reached by 250 feet (76.2 m) of hose from a yard hydrant or a street hydrant supplied from a direct connection to a city water main or other approved water supply.

507.3 Design capacity.

The design capacity of the water supply shall be determined by an approved method.

507.4 Water supply test.

Upon completion of the installation of a private fire hydrant system and yard hydrant system, a flow test shall be conducted to verify that the system provides the minimum design capacity required by FC 507.3. Certification of the water supply test shall be submitted to the commissioner by a registered design professional.

507.5 Private fire hydrant systems.

Private fire hydrant systems shall comply with the requirements of FC 507.5.1 through 507.5.6.

507.5.1 Where required.

Where the front entrance of a building is more than 250 feet (76.2 m) from a hydrant on a public street, as measured by an approved route, private fire hydrants and mains shall be provided as required by the commissioner.

507.5.2 Inspection, testing and maintenance.

Private fire hydrant systems shall be subject to periodic tests as required by the commissioner. Private fire hydrant systems shall be maintained in good working order at all times and shall be repaired when defective. Additions, repairs, alterations and servicing shall comply with approved standards.

507.5.2.1 Department flow tests.

The department may periodically inspect and test private fire hydrant systems, at the risk of the owner, for proper operation and unobstructed flow of such hydrant system.

507.5.3 Private fire service mains and water tanks.

Private fire service mains and water tanks shall be periodically inspected, tested and maintained in accordance with NFPA 25 at the following intervals:

1. Private fire hydrants (all types): Inspection annually and after each operation; flow test and maintenance annually.

2. Fire service main piping: Inspection of exposed, annually; flow test every 5 years.

3. Fire service main piping strainers: Inspection and maintenance after each use.

507.5.4 Obstructions.

Posts, fences, vegetation, rubbish containers, vehicles and other items shall not be installed, planted, placed, parked or stored near fire hydrants, fire department connections or fire protection system control valves in a manner that would obscure the location of such fire hydrants, connections or valves, or that would hinder immediate access thereto by firefighting personnel.

507.5.5 Clear space around hydrants.

A 3-foot (914 mm) radius clear space shall be maintained around the circumference of fire hydrants to allow unobstructed operation of the hydrant operating nut, except as otherwise required or approved.

507.5.6 Physical protection.

Where fire hydrants are subject to impact by motor vehicles, posts that comply with the requirements of the New York City Department of Environmental Protection shall be installed. Notwithstanding the requirements of FC 507.5.5, these posts may be installed no less than 2 feet (610 mm) from the hydrant if they do not obstruct the use of a 24-inch (610-mm) wrench on the hydrant operating nut.

Section FC 508. Reserved

Open this section

BetaNYC's copy has no text for this section. Read Section FC 508 at American Legal Publishing.

Section FC 509. Fire Protection and Utility Equipment Identification and Access

Open this section

509.1 Identification.

Fire protection equipment shall be identified in an approved manner. Rooms containing controls for ventilation systems, sprinkler risers and valves, or other fire detection, extinguishing or control elements shall be identified for the use of the department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and conspicuously posted.

509.2 Safe access.

Fire protection devices, equipment and systems, including fire detection systems and fire extinguishing systems, shall be readily accessible for inspection, operation and maintenance. Combustible materials, combustible waste and other items shall not be placed or stored in a manner that would obstruct or impede access to such equipment. Sprinkler and standpipe system control valves located at a height of 7 feet (2134 mm) or more above the floor shall be provided with fixed ladders, chains and wheels, or other approved means to provide ready access.

509.3 Natural gas shutoff tools.

Natural gas utilities shall provide the department with suitable tools for the operation of outdoor gas service line valves for a building or structure or other outdoor emergency shutoff device or equipment. The number of such tools required to supply the department's needs shall be determined by the commissioner.

509.4 Utility identification.

Where required by the department, water, natural gas, electric or other utility service shutoff valves and disconnect switches to a building, structure, premises, device, equipment or system shall be provided with a durable and conspicuous marking that identifies the building, structure, premises, device, equipment or system such shutoff valve or disconnect switch serves.

Section FC 510. In-Building Auxiliary Radio Communication Systems

Open this section

510.1 General.

The design, installation, operation and maintenance of in-building auxiliary radio communication systems dedicated for fire department use, whether required by the Building Code or installed voluntarily, shall comply with this section and the rules.

510.2 Design and installation.

In-building auxiliary radio communication systems for fire department use shall be designed and installed in accordance with the construction codes, including the Building Code, and the Electrical Code.

510.2.1 Installer qualifications.

In-building auxiliary radio communication systems for fire department use shall be installed by a master electrician licensed by the Department of Buildings and such other qualifications as may be prescribed by rule.

510.2.2 Installation acceptance.

In-building auxiliary radio communication systems for fire department use shall be tested for department acceptance in compliance with the requirements of this section and the rules.

510.2.2.1 Commissioning test.

Upon completion of installation of an in-building auxiliary radio communication system for fire department use, a commissioning test shall be conducted in accordance with the rules by a person holding a Federal Communications Commission general radiotelephone operator license and such other qualifications as may be prescribed by rule.

510.2.2.2 Department acceptance test.

Upon successful completion of the commissioning test, the owner shall submit to the department a detailed report of the results of the commissioning test and request a department acceptance test. The department acceptance test shall serve to demonstrate the system is functioning satisfactorily and is ready for department use. The in-building auxiliary radio communication system shall be demonstrated in the presence of a department representative by a representative of the owner. Upon satisfactory completion of the department acceptance test, the department shall issue a permit for such system.

510.3 Operation and maintenance.

The operation and maintenance of in-building auxiliary radio communication systems for fire department use shall be in accordance with this section and the rules.

510.3.1 General.

In-building auxiliary radio communication systems for fire department use shall be maintained in good working order.

510.3.2 Out-of-service systems.

The department shall be notified immediately if an in-building auxiliary radio communication system for fire department use, or part thereof, is out of service. A tag identifying the system as out of service shall be placed on the fire command center or other approved location when the system is out of service.

Section FC 511. High-Rise Megastructure Fire Operations

Open this section

511.1 General.

High-rise megastructures shall be designed, installed, operated and maintained in accordance with this section to facilitate firefighting operations.

511.2 Supervision.

A person holding a certificate of fitness for emergency announcements shall be present on the premises at all times when the building is occupied except in a high-rise megastructure required to be staffed by an FLS director. In a mixed-occupancy high-rise megastructure, each occupancy with its own voice communication capability shall be staffed with such a certificate of fitness holder or FLS director.

511.3 Building information card.

A building information card complying with FC 401.3.4 shall be prepared and maintained at the fire command center or other approved location in all high-rise megastructures, including apartment buildings and other Group R-2 occupancies.

511.4 Emergency preparedness.

Emergency preparedness plans shall be prepared when required by FC Chapter 4, provided, however, that a fire and emergency preparedness (Level 2) plan shall be prepared for Group R-2 occupancies in a high-rise megastructure. All emergency preparedness plans in a mixed-occupancy high-rise megastructure shall be coordinated in accordance with FC 416.

511.5 Fire command center.

The fire alarm system control panel shall be installed in accordance with fire command center requirements, as set forth in FC 907.4.

511.6 Standpipe elevation markings.

The elevation above grade of each floor level shall be conspicuously marked in accordance with FC 905 on or adjacent to the standpipe hose outlets on each floor of a high-rise megastructure.

511.7 Storage space for pre-positioned department equipment.*

Space shall be provided in a storage room, mechanical room or other approved, enclosed, secure storage location in a high-rise megastructure for the sole purpose of storing department equipment, in accordance with the following requirements:

1. A storage space shall be provided for every 150 feet (45 720 mm) in elevation more than 420 feet (128 016 mm) above the lowest level of fire apparatus access, at a location near the fire service access elevator or a stairwell.

2. Each such storage space shall be not less than 8 feet (2438 mm) in length, 8 feet (2438 mm) in width, and 8 feet (2438 mm) in height, and openable only by fire department standard key or as otherwise approved by the department. Upon reasonable notice to the department, the owner shall be afforded access to such storage spaces for inspection, building maintenance or other legitimate business purpose.

3. Each such storage space shall be protected by a sprinkler system, except as otherwise approved by the department.

4. Each storage space shall be identified by a sign or marking in accordance with the rules identifying it as a department equipment room.

5. This constitutes an operational requirement of this code; however, in a building constructed prior to the effective date of this section that lacks storage spaces in compliance with this section, suitable storage spaces (including spaces not protected by a sprinkler system) may be provided at alternative locations, as approved by the department.

* Editor's note: Section 8 of L.L. 2022/047 provides, in part, that FC 511.7 shall take effect one year from the date of adoption of a zoning amendment exempting from the calculation of the building floor area ratio storage spaces for pre-positioned department equipment.

511.8 Access to elevator shafts.

The department, in coordination with the Department of Buildings, may adopt rules requiring additional access to elevator cabs, installation of elevator location technology, or other design, installation or operational measures designed to facilitate rescue operations in blind hoistways 36 feet (10 973 mm) or more in height in high-rise megastructures.

Section FC 512. Rooftop Solar Panel Installations

Open this section

512.1 General.

The design, installation, operation and maintenance of solar panel systems, including photovoltaic and thermal systems, on the rooftops of buildings and structures, shall be in accordance with this section, the Electrical Code and the construction codes, including the Building Code, Mechanical Code and Plumbing Code.

512.2 Flat-roofed buildings and structures 100 feet or less in height.

Solar panel installations shall not obstruct any rooftop area access to which is required pursuant to FC 504.4, except that solar panel installations may obstruct the clear path required by FC 504.4.4 as follows:

1. if the installation is provided with a hinged mechanism or other device for which a certificate of approval has been issued that enables the installation to be safely swung, slid, lifted, collapsed or otherwise moved out of the clear path, and that is designed to allow for operation by one person, without the use of a tool; or

2. on any building with a rooftop width or depth of 25 feet (7620 mm) or less, where the design of a solar panel installation necessitates coverage of all or substantially all of the rooftop across the full width or length thereof, the commissioner may authorize permanent obstructions that encroach upon and thereby reduce the clear path width within such area when necessary to accommodate the presence of building features and building service equipment that constitute permanent obstructions, including attic ventilators, bulkheads, chimneys, hatches, plumbing ventilations pipes, scuttles, skylights, and roof-mounted heating, ventilation and air conditioning equipment. Such permanent obstructions may encroach upon and, for the distance of the obstruction, reduce the clear path width up to 2 feet (610 mm). Such permanent obstructions shall not reduce the width of clear path at any point to less than 4 feet (1219 mm) and shall not encroach upon the rooftop landing areas required by FC 504.4.3.

512.3 Pitched-roofed buildings and structures 100 feet or less in height.

Solar panel installations shall be designed, installed, operated and maintained in accordance with this section on rooftops of buildings and structures 100 feet (30 480 mm) or less in height with a slope exceeding 20 degrees, except detached Group U buildings and structures.

512.3.1 Hip roofs.

Solar panel installations shall provide a 3 foot (914 mm) wide clear access area along the ridge on each roof slope upon which solar panels are installed.

512.3.2 Ventilation.

Solar panels shall not be installed closer than 3 feet (914 mm) to the ridge line.

512.4 Photovoltaic solar panel installations.

Photovoltaic solar panel installations shall be designed, installed, operated and maintained in compliance with the requirements of this section.

512.4.1 Location of photovoltaic solar panel installations on pitched roofs.

Direct current conduit, wiring systems, and raceways for photovoltaic circuits installed on pitched roofs subject to the requirements of FC 512.3 shall be located along hips and valleys, away from the ridge, and on outside walls, to maximize ventilation opportunities. Conduit runs between sub-arrays and to direct current combiner boxes shall be installed in a manner that minimizes the total amount of conduit on the roof by taking the shortest path from the array to the direct current combiner box, except as necessary to minimize the tripping hazard. The direct current combiner boxes shall be located such that conduit runs are minimized in the pathways between arrays.

512.4.2 Photovoltaic solar panel installation markings.

Indoor and outdoor direct current conduit, enclosures, raceways, cable assemblies, junction boxes, combiner boxes, and main service and other disconnects shall have durable, retroreflective and, if outdoors, weatherproof, markings, in white capital letters with a height of not less than 3/8 inch (9.5 mm) on a red background, reading "WARNING: PHOTOVOLTAIC POWER SOURCE." Continuous installations, including conduit, raceways, enclosures and cable assemblies, shall be marked every 10 feet (3048 mm), within 1 foot (305 mm) of all turns or bends, and within 1 foot (305 mm) above and below all penetrations of roof or ceiling assemblies and all walls.

Section FC 601. General

Open this section

601.1 Scope.

This chapter shall govern the design, installation, operation and maintenance of selected devices, equipment and systems used or designed to be used to provide building services, including battery, commercial cooking, elevator recall, emergency power, heating and refrigerating systems.

601.2 Permits.

Permits shall be required as set forth in FC 105.6.

601.3 General.

Fuel-fired appliances, devices, equipment and systems, emergency power systems, electrical systems and equipment, refrigerating systems, elevator recall, stationary energy storage systems and commercial cooking systems shall be designed, installed, operated and maintained in accordance with this chapter.

601.4 Supervision.

Fuel oil storage systems, refrigerating systems and stationary energy storage systems shall be supervised in accordance with FC 601.4.1 through 601.4.4.

601.4.1 Fuel oil storage and transfer.

A stationary fuel oil storage tank, and related piping, that is installed on the lowest floor of a building and that transfers fuel oil through piping to another stationary fuel oil storage tank, or to fuel-oil burning equipment, installed above such floor, shall be under the general supervision of a certificate of fitness holder. The periodic inspection and testing of such tanks and piping pursuant to FC 603.1.9 shall be conducted under the personal supervision of such certificate of fitness holder.

601.4.2 Refrigerating systems.

Refrigerating systems shall be supervised by a person holding a certificate of qualification in accordance with FC 606.1.1 and FC Table 606.1.1.

601.4.3 Stationary energy storage systems.

Stationary energy storage systems subject to compliance with the requirements of FC 608 shall be supervised by a person holding a certificate of fitness in accordance with FC 608.7.

601.4.4 Commercial cooking systems.

Commercial cooking systems subject to compliance with requirements of FC 609 shall be supervised by a person holding a certificate of fitness in accordance with FC 609.3.

Section FC 602. Definitions

Open this section

602.1 Definitions.

The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.

APPROVED TESTING LABORATORY.

CERTIFICATE OF QUALIFICATION.

CITYWIDE STANDARD KEY.

COMMERCIAL COOKING APPLIANCES.

COMMERCIAL COOKING SYSTEM.

COMMERCIAL KITCHEN.

COOKING OIL.

DEDICATED USE BUILDING

DUCTLESS HOOD.

ENERGY STORAGE SYSTEM, STATIONARY.

Indoor System.

Mobile system.

Outdoor System

HOOD.

Type I.

KILOWATT HOURS (kWh).

MEGAWATT HOURS (MWh).

PROOF OF COMPLIANCE.

REFRIGERANT.

REFRIGERATING SYSTEM.

STORAGE BATTERY.

Types of storage batteries include:

Flow Battery.

Lead-Acid battery.

Lithium-Ion battery.

Lithium Metal Polymer Battery.

Nickel-Cadmium (Ni-Cd) Battery.

Nickel Metal Hydride (NiMH) Battery.

Nonrecombinant Battery.

Recombinant Battery.

Valve-Regulated Lead-Acid (VRLA) Battery.

Vented (flooded) Lead-Acid Battery.

STORAGE BATTERY UNIT.

Section FC 603. Fuel-Fired Appliances and Equipment

Open this section

603.1 Installation.

Nonportable fuel-fired appliances, devices, equipment and systems shall be designed, installed, operated and maintained in accordance with the construction codes, including the Fuel Gas Code and the Mechanical Code.

603.1.1 Manufacturer's instructions.

In addition to the requirements of this code and other applicable laws, rules and regulations, the installation shall be made in accordance with the manufacturer's instructions. Where it becomes necessary to change, modify, or alter a manufacturer's instructions in any way, written approval shall first be obtained from the manufacturer.

603.1.2 Approval.

The design, construction and installation of fuel-fired appliances, devices, equipment and systems shall be in accordance with the construction codes, including the Fuel Gas Code and the Mechanical Code.

603.1.3 Electrical wiring and equipment.

Electrical wiring and equipment used in connection with oil-burning equipment shall be installed and maintained in accordance with FC 605 and the Electrical Code.

603.1.4 Fuel oil.

The grade of fuel oil used in a burner shall be that for which the burner is approved and as stipulated by the burner manufacturer and approved by the Department of Buildings. Oil containing gasoline shall not be used. Waste crankcase oil shall not be used, except when such waste oil is mixed with number six fuel oil in bulk or waste oil recovery plants, the resultant mixture meets the minimum specifications for number six fuel oil set forth in the Building Code, and the use of such waste oil complies with all laws, rules and regulations relating to smoke and other emissions and is approved by the Department of Environmental Protection.

603.1.5 Access.

The installation shall be readily accessible for cleaning hot surfaces; removing burners; replacing motors, controls, air filters, chimney connectors, draft regulators, and other working parts; and for adjusting, cleaning and lubricating parts.

603.1.6 Testing, diagrams and instructions.

After installation of the oil-burning equipment, operation and combustion performance tests shall be conducted to determine that the burner is in proper operating condition and that all accessory equipment, controls, and safety devices function properly in accordance with the requirements of the Department of Buildings and the Department of Environmental Protection.

603.1.6.1 Diagrams.

Contractors installing industrial oil-burning systems shall furnish not less than two copies of diagrams showing the main oil lines and controlling valves, one copy of which shall be posted at the oil-burning equipment and another at an approved location that will be accessible in case of emergency.

603.1.6.2 Instructions.

After completing the installation, the installer shall instruct the owner or operator in the proper operation of the equipment. The installer shall also furnish the owner or operator with the name and telephone number of persons to contact for technical information or assistance and routine or emergency services.

603.1.7 Clearances.

Working clearances between oil-fired appliances and electrical panelboards and equipment shall be in accordance with the Electrical Code. Clearances between oil-fired equipment and oil supply tanks shall be in accordance with the construction codes, including the Building Code and the Mechanical Code.

603.1.8 Supervision of operation.

Every stationary oil-fired device, equipment or system that is not fully automatic or requires preheating of the oil shall be operated by or under the personal supervision of a person holding a certificate of fitness or a person holding a high-pressure boiler operating engineer's license issued by the Department of Buildings. In addition to providing personal supervision, such person shall be present at the device, equipment or system during startup. A stationary oil-fired device, equipment or system that is subject to annual inspection pursuant to Article 303 of Title 28 of the Administrative Code may be operated under the general supervision of a certificate of fitness holder or a high-pressure boiler operating engineer license holder.

603.1.9 Fuel oil transfer maintenance.

The fuel oil storage tanks and piping systems in which fuel oil is transferred from a stationary fuel oil storage tank installed on the lowest floor of a building to another stationary fuel oil storage tank, or to fuel-oil burning equipment, installed above such floor, shall be inspected for evidence of leaks, and stationary tank float switches shall be tested to ensure that they are in good working order, on not less than a weekly basis.

603.2 Chimneys.

Masonry chimneys shall be constructed in accordance with the construction codes, including the Building Code. Factory-built chimneys shall be installed in accordance with the construction codes, including the Mechanical Code. Metal chimneys shall be constructed and installed in accordance with the construction code, including the Building Code and the Mechanical Code.

603.3 Fuel oil storage systems.

Fuel oil storage and piping systems shall be installed in accordance with the construction codes, including the Mechanical Code. Fuel oil storage shall be subject to the permit requirements set forth in FC 105.6.

603.3.1 Portable fire extinguisher.

In all occupancies other than Group R-3 occupancies, stationary fuel oil-burning equipment, including boilers, emergency generators, furnaces, hot water heaters and space heaters, shall be provided with a dry chemical type portable fire extinguisher with at least a 20-B:C rating, or a carbon dioxide type portable fire extinguisher with at least a 2-B:C rating. Such portable fire extinguisher shall be located not more than 30 feet (9144 mm) from the fuel oil fired equipment, except that such travel distance may be increased to a maximum of 50 feet (15 240 mm) if a dry chemical portable fire extinguisher with at least a 40-B:C rating, or a carbon dioxide portable fire extinguisher with at least a 4-B:C rating, is provided.

603.4 Reserved.

603.5 Heating appliances and equipment.

Heating appliances and equipment shall be listed and shall comply with the requirements of this section.

603.5.1 Protection of heating element.

The heating element or combustion chamber shall have a permanent device to prevent accidental contact by persons or material.

603.5.2 Heating appliance and equipment installation.

Heating appliances and equipment shall be installed in accordance with the manufacturer's instructions, the Electrical Code, and the construction codes, including the Building Code, the Mechanical Code and the Fuel Gas Code.

603.6 Chimney installation.

Chimneys, smokestacks or similar devices for conveying smoke or hot gases to the outer air and the incinerators, stoves, furnaces, fireboxes or boilers to which such devices are connected, shall be maintained so as not to create a fire hazard.

603.6.1 Masonry chimneys.

Masonry chimneys that, upon inspection, are found to have open mortar joints which will permit smoke or gases to be discharged into the building or structure, or which are cracked as to be dangerous, shall be repaired or relined with a listed chimney liner system installed in accordance with the manufacturer's installation instructions or a flue lining system installed in accordance with the construction codes, including the Building Code and the Mechanical Code, and appropriate for the intended class of chimney service.

603.6.2 Metal chimneys.

Metal chimneys which are corroded or improperly supported shall be repaired or replaced.

603.6.3 Decorative shrouds.

Decorative shrouds installed at the termination of factory-built chimneys shall be removed except where such shrouds are listed and labeled for use with the specific factory-built chimney system and are installed in accordance with the chimney manufacturer's installation instructions.

603.6.4 Factory-built chimneys.

Existing factory-built chimneys that are damaged, corroded or improperly supported shall be repaired or replaced.

603.6.5 Connectors.

Existing chimney and vent connectors that are damaged, corroded or improperly supported shall be repaired or replaced.

603.6.6 Incinerator requirements.

Incinerators shall be maintained and operated in accordance with FC 603.6.6.1 and 603.6.6.2.

603.6.6.1 Spark arrestor.

Incinerators shall be equipped with an effective means for arresting sparks.

603.6.6.2 Time of burning.

Burning shall take place only during approved hours.

603.6.7 Discontinuance.

The commissioner may require the operation of an incinerator or other device connected to a chimney to be discontinued immediately upon a determination that the use of the incinerator or other device constitutes an undue fire hazard because of conditions in the surrounding environment.

603.7 Discontinuing operation of unsafe heating appliances and equipment.

The commissioner may order that measures be taken to prevent the operation of any existing stove, oven, furnace, incinerator, boiler or any other heat-producing appliance, device, equipment or system found to be defective or in violation of code requirements for existing appliances, devices, equipment or systems after giving notice to this effect to any person, owner, firm or agent or operator in charge of the same. The commissioner may take measures to prevent the operation of any appliance, device, equipment or system without notice upon a determination of the existence of an immediate fire hazard or imminent peril to public safety. The defective appliance, device, equipment or system shall remain out of service until all necessary repairs or alterations have been made.

603.7.1 Unauthorized operation.

It shall be a violation of this code for any person, user, firm or agent to continue the utilization of any appliance, device, equipment or system (the operation of which has been discontinued or ordered discontinued in accordance with FC 603.7), unless written authority to resume operation is given by the department. Removing or breaking the means by which operation of the appliance, device, equipment or system is prevented shall be a violation of this code.

603.8 Reserved.

603.9 Gas meters.

Gas meters shall be installed in accordance with FC 603.9.1 and 603.9.2.

603.9.1 Protection of outdoor aboveground installations.

Aboveground gas meters, regulators and piping subject to damage shall be protected by a barrier complying with the requirements of FC 312 or otherwise protected in an approved manner.

603.9.2 Gas meter identification.

Where more than one gas meter is installed at a single indoor or outdoor location, each gas meter shall be identified by a durable sign or marking identifying the dwelling unit or other occupancy or area that such meter serves. Where more than 12 gas meters are installed at a single location in a non-sequential manner, each meter shall be numbered for identification in a sequential manner (starting with number 1) and a durable sign shall be posted at a conspicuous location in the form of a table listing in sequential order the apartment/room numbers served by the meter with a cross-reference to the sequential meter identification number.

Section FC 604. Emergency Power Systems

Open this section

604.1 Installation.

Emergency power systems shall be designed, installed, operated and maintained in accordance with the Electrical Code and the construction codes, including the Building Code.

604.2 Where required.

Emergency power systems shall be maintained in accordance with NFPA 110, as modified by FC Appendix B, and NFPA 111, such that the system is capable of supplying service within the time specified for the type and duration of emergency power required by the Electrical Code and the construction codes, including the Building Code.

604.3 Maintenance.

Emergency power systems shall be maintained such that the system is capable of supplying service within the time specified for the type and duration of emergency power required by the Electrical Code and the construction codes, including the Building Code.

604.3.1 Schedule.

Inspection, testing and other maintenance of emergency power systems shall be conducted in accordance with an approved schedule established upon completion and approval of the system installation.

604.3.2 Written record.

Written records of the inspection, testing and other maintenance of emergency power systems shall include the date of service, name of the servicing technician, a summary of conditions noted and a detailed description of any conditions requiring correction and what corrective action was taken.

604.3.3 Switch maintenance.

Emergency power system transfer switches shall be included in the maintenance schedule required by FC 604.3.1. Transfer switches shall be maintained free from accumulated dust and dirt. Inspection shall include examination of the transfer switch contacts for evidence of deterioration. When evidence of contact deterioration is detected, the contacts shall be replaced in accordance with the transfer switch manufacturer's instructions.

604.4 Inspection and testing.

Emergency power systems, including all appurtenant components, shall be periodically inspected and tested under load in accordance with NFPA 110, as modified by FC Appendix B, and NFPA 111.

Exception: Where the emergency power system is used for standby power or peak load shaving, such use shall be recorded and may substitute for scheduled testing of the emergency power system, provided that appropriate records are maintained of such use.

604.4.1 Transfer switch test.

The test of the transfer switch shall consist of electrically operating the transfer switch from the normal position to the alternate position and then returning back to the normal position.

604.5 Supervision.

Inspection, testing and other maintenance shall be conducted under the personal supervision of a person who possesses the required knowledge and training to conduct such maintenance, and who has at least one of the following qualifications:

1. An electrician licensed by the Department of Buildings.

2. An electrician holding a special license issued by the Department of Buildings.

3. A person holding a stationary engineer license, or high-pressure boiler operating engineer's license, issued by the Department of Buildings.

4. A person holding a certificate of qualification.

5. A person holding a certificate of fitness as an FLS director.

6. A person holding a certificate of fitness as an FEP coordinator.

7. A registered design professional.

Section FC 605. Electrical Equipment, Wiring and Hazards

Open this section

605.1 Abatement of electrical hazards.

Defective devices, equipment or systems shall not be used and the hazardous conditions shall be corrected or the device, equipment or system shall be removed from the premises. Electrical wiring, devices and other equipment that is damaged or otherwise constitutes an electrical or fire hazard shall not be used, and the hazardous condition shall be corrected or the equipment removed from the premises.

605.2 Illumination.

Illumination shall be provided for service equipment areas, motor control centers and electrical panelboards.

605.3 Working space and clearance.

A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.

Exceptions:

1. Where other dimensions are required or allowed by the Electrical Code.

2. Access openings into attics or under-floor areas which provide a minimum clear opening of 22 inches (559 mm) by 30 inches (762 mm).

605.3.1 Labeling.

Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident.

605.4 Multiplug adapters.

Multiplug adaptors, such as cube adaptors, unfused plug strips or any other device not complying with the requirements of the Electrical Code shall be prohibited.

605.4.1 Power tap design.

Portable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363.

605.4.2 Power supply.

Portable power taps shall be directly connected to a permanently installed receptacle.

605.4.3 Installation.

Portable power tap cords shall not extend through walls, ceilings, floors, under doors or floor coverings, or be subject to environmental or physical damage.

605.5 Extension cords.

Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to buildings or structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable devices.

605.5.1 Power supply.

Extension cords shall be plugged directly into an approved receptacle, power tap or multiplug adapter and, except for approved multiplug extension cords, shall serve only one portable device.

605.5.2 Ampacity.

The ampacity of the extension cords shall not be less than the rated capacity of the portable appliance supplied by the cord.

605.5.3 Maintenance.

Extension cords shall be maintained in good condition without splices, deterioration or damage.

605.5.4 Grounding.

Extension cords shall be grounded when serving grounded portable devices.

605.6 Unapproved conditions.

Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

605.7 Electrical devices and equipment.

Electrical devices and equipment shall be listed or labeled and installed in accordance with the construction codes and the Electrical Code.

605.8 Electrical motors.

Electrical motors shall be maintained free from excessive accumulations of oil, dirt, waste and debris.

605.9 Temporary wiring.

Temporary wiring for electrical power and lighting installations is allowed for a period not to exceed 90 calendar days. Temporary wiring methods shall meet the applicable provisions of the Electrical Code.

Exception: Temporary wiring for electrical power and lighting installations is allowed during periods of construction, remodeling, repair or demolition of buildings, structures, equipment or similar activities.

605.9.1 Attachment to structures.

Temporary wiring attached to a building or structure shall be attached in an approved manner.

605.10 Portable electric space heaters.

The use of portable electric space heaters shall be in accordance with this section.

605.10.1 Listed and labeled.

Portable electric space heaters shall be listed and labeled. Portable electric space heaters shall be operated only in locations for which they are listed.

605.10.2 Power supply.

Portable electric space heaters shall be plugged directly into a receptacle. Extension cords shall not be used for electrical connections for portable electric space heaters.

605.10.3 Prohibited use.

It shall be unlawful to use portable electric space heaters in the following locations:

1. In any building or occupancy, where the power requirements for the portable electric space heater exceed the rating of the electrical circuit or receptacle from which the heater will draw current.

2. In any occupancy, within 3 feet (914 mm) of any combustible material.

3. In Group I-2 occupancies, except that a portable electric space heater with a heating element designed not to exceed a temperature of 212°F (100°C) may be used in nonsleeping staff and employee areas.

4. In Group R-1 college and university dormitories.

5. In any location considered to be a hazardous location in accordance with the Electrical Code, unless listed for such use.

605.11 Portable halogen floor lamps.

Portable halogen floor lamps shall be designed, operated and maintained in compliance with the requirements of this section.

605.11.1 Prohibitions.

It shall be unlawful to:

1. store or use portable halogen floor lamps in Group I-2 occupancies and Group R-1 college and university dormitories.

2. use portable halogen floor lamps for any purpose other than lighting.

3. store or use portable halogen floor lamps that are not designed with an approved glass or wire bulb guard or when such guard is not in place.

605.11.2 Manufacturer instructions.

Portable halogen floor lamps shall be used in accordance with the manufacturer's instructions.

605.11.3 Placement.

Portable halogen floor lamps shall be placed in locations where the risk of the lamp being tipped over by occupant traffic or activities, or of igniting curtains, furnishings or other combustible materials, is minimized.

605.11.4 Bulb replacement and disposal.

Portable halogen floor lamp bulbs shall be replaced and discarded only when the bulb is cool to the touch.

Section FC 606. Refrigerating Systems

Open this section

606.1 General.

Refrigerating systems shall be designed, installed, operated and maintained in accordance with this code and the construction codes, including the Mechanical Code, and ASHRAE 15. Refrigerating systems using ammonia refrigerant shall comply with the applicable IIAR standards for system design, installation, operation and maintenance, except as modified by the Mechanical Code.

606.1.1 Supervision.

It shall be unlawful to operate any refrigerating system for which a permit is required and which is a system described in FC Table 606.1.1, unless such operation is under either the personal supervision or general supervision, as set forth in FC Table 606.1.1, of a person who has obtained a certificate of qualification for refrigerating system operating engineer. For purposes of this section, personal supervision shall mean that such person is present in the building at all times while the system is in operation and that the operation of such system is under his or her personal direction and control, and general supervision shall mean that such person is responsible at all times for the safe operation of such system when such system is in operation and that such system is operated under his or her general direction and control. Persons providing general or personal supervision as required by this section shall register their work location with the department.

606.1.2 Operator inspection after repairs.

After any repairs are made to a refrigerating system the operation of which requires supervision by a certificate of qualification holder, the certificate of qualification holder shall check the repairs, together with the functioning of all control devices and the positioning of all valves. Such certificate of qualification holder shall also be present when the system is restarted after repairs.

606.1.3 Operator logbook.

A logbook or other form of approved recordkeeping shall be maintained for all refrigerating systems whose operation requires either personal or general supervision by a certificate of qualification holder. For systems requiring personal supervision the logbook shall, at a minimum, contain an entry for each shift the system is in operation. For systems requiring general supervision the logbook shall, at a minimum, contain an entry for each day during which the system is in operation.

606.1.3.1 Logbook entries.

The logbook shall provide information relevant to the operation of the system, including any operating problems or deficiencies and required periodic tests. The signature of the certificate of qualification holder shall appear next to each entry.

606.2 Refrigerants.

The use and purity of new, recovered, and reclaimed refrigerants shall be in accordance with the construction codes, including the Mechanical Code.

606.3 Refrigerant classification.

Refrigerants shall be classified in accordance with the construction codes, including the Mechanical Code.

606.4 Change in refrigerant type.

Any change in the type of refrigerant in a refrigerating system shall be made in accordance with the construction codes, including the Mechanical Code.

606.5 Access.

Refrigerating systems having a refrigerant circuit containing more than 200 pounds (91 kg) of Group A1 or 30 pounds (14 kg) of any other group refrigerant shall be accessible to the department at all times as required by the commissioner. Refrigerating systems requiring a permit shall be accessible at all times, and shall, where practicable, be made accessible for department inspection without the use of portable ladders or other portable equipment.

606.6 Testing of equipment.

Refrigerating equipment and systems having a refrigerant circuit containing more than 200 pounds (91 kg) of Group A1 or 30 pounds (14 kg) of any other group refrigerant shall be subject to periodic testing in accordance with FC 606.6.1. Tests of emergency devices or systems required by this chapter shall be conducted by a person holding a certificate of qualification.

606.6.1 Periodic testing.

The following emergency devices or systems shall be tested at least monthly in accordance with the manufacturer's instructions.

1. Treatment and flaring systems.

2. Valves and appurtenances necessary to the operation of emergency refrigerating system control boxes.

3. Fans and associated equipment intended to operate emergency ventilation systems.

4. Detection and alarm systems.

FC Table 606.1.1 Refrigerating System Operating Engineer

Installation Date Refrigerant Group or Name a Occupancy Type b Application Pounds of Refrigerant in System System Horsepower System Design c Supervision Required Prior to June 1, 1957 A1 Industrial Human comfort More than 50 NA Not fully automatic Personal A1 Industrial Human comfort More than 200 NA Fully automatic Personal A1 Industrial Human comfort More than 50 up to 200 NA Fully automatic General A1 All except Industrial All More than 50 NA Not fully automatic Personal A1 All except Industrial All More than 200 NA Fully automatic Personal A1 All except Industrial All More than 50 up to 200 NA Fully automatic General On or after June 1, 1957 A1 Industrial Human comfort NA More than 50 (or kilowatt equivalency) NA Personal A1 All except Industrial All NA More than 50 (or kilowatt equivalency) NA Personal Regardless of when installed A2, A3, B1, B2, B3 and carbon dioxide All All More than 50 NA Not fully automatic Personal A2, A3, B1, B2, B3 and carbon dioxide All All More than 200 NA Fully automatic Personal A1 Industrial All except human comfort More than 50 NA Not fully automatic Personal A1 Industrial All except human comfort More than 200 NA Fully automatic Personal A1 and carbon dioxide Industrial All except human comfort More than 50 up to 200 NA Fully automatic General A1 All Human comfort NA Aggregate exceeds 100 d NA Personal

a. For purposes of this table, refrigerant R-123 shall be treated as a group A1 refrigerant, and carbon dioxide shall not be treated as a group A1 refrigerant.

b. For purposes of this table, "industrial" occupancy refers to occupancy groups F, H and S. For installations constructed under the 1968 Building Code, "industrial" occupancy refers to occupancy groups A, B and D. For installations constructed prior to such 1968 code, "industrial" occupancy refers to that portion of a building used for manufacturing, processing, or storage of materials or products, including, among others, chemical, food, candy, and ice cream factories, ice making plants, meat packing plants, refineries, perishable food warehouses, and similar occupancies.

c. A fully automatic refrigerating system is one whose regulating and safety devices are automatically activated once the system is in operation.

d. This aggregate provision applies only to systems within a single building which are under the sole direct control of a single occupant, lessee or owner. Systems with a rating of 15 horsepower or less or the kilowatt equivalency thereof are excluded from the aggregate.

606.7 Emergency signs.

Emergency signs shall be provided in accordance with the construction codes, including the Mechanical Code.

606.8 Refrigerant detector.

Machinery rooms shall contain a refrigerant detector with an audible and visual alarm as required by the construction codes, including the Mechanical Code for the refrigerant classification.

606.9 Remote controls.

Remote control of the mechanical equipment and appliances located in the machinery room and the emergency ventilation system shall be provided in accordance with the construction codes, including the Mechanical Code.

606.10 Storage, handling and use.

Flammable liquids, combustible liquids, combustible materials and combustible waste, except for quantities of combustible liquids below permit amounts, spare parts, tools, and incidental materials necessary for the safe and proper operation and maintenance of the system, shall not be stored in machinery rooms for refrigerating systems. Storage, use or handling of extra refrigerant or refrigerant oils shall be as required by FC Chapters 50, 53, 55 and 57 and the Mechanical Code.

606.11 Discharge and termination of pressure relief devices.

Pressure relief devices, fusible plugs and purge systems for refrigerating systems containing flammable, toxic or highly toxic refrigerants or ammonia shall comply with FC 606.11.1 through 606.11.3. Discharge piping and devices connected to the discharge side of a fusible plug or rupture member shall have provisions to prevent plugging the pipe in the event of the fusible plug or rupture member functions. Discharge from systems containing Group A3 or B3 refrigerants shall be approved by the department and the Department of Buildings.

606.11.1 Flammable refrigerants.

Systems containing more than 6.6 pounds (3 kg) of flammable refrigerants having a density equal to or greater than the density of air shall discharge vapor to the atmosphere only through an approved treatment system in accordance with FC 606.11.4 or a flaring system in accordance with FC 606.11.5. Systems containing more than 6.6 pounds (3 kg) of flammable refrigerants having a density less than the density of air shall be allowed to discharge vapor to the atmosphere provided that the point of discharge is located outdoors and not less than 15 feet (4572 mm) above the adjoining grade level and not less than 20 feet (6096 mm) from any window, ventilation opening or exit.

606.11.2 Toxic and highly toxic refrigerants.

Systems containing more than 6.6 pounds (3 kg) of toxic or highly toxic refrigerants shall discharge vapor to the atmosphere in accordance with FC 606.11.4 or a flaring system in accordance with FC 606.11.5.

606.11.3 Ammonia refrigerant.

Systems containing more than 6.6 pounds (3 kg) of ammonia refrigerant shall discharge vapor to the atmosphere in accordance with one of the following methods:

1. Through an approved treatment system in accordance with FC 606.11.4;

2. Through a flaring system in accordance with FC 606.11.5;

3. Through an approved ammonia diffusion system in accordance with FC 606.11.6;

4. Directly to the atmosphere, when the commissioner determines, on review of an engineering analysis prepared in accordance with FC 104.7.2, that a fire, health or environmental hazard would not result from the atmospheric discharge of ammonia; or

5. By other approved means.

Exception: Ammonia/water absorption systems containing less than 22 pounds (10 kg) of ammonia and for which the ammonia circuit is located entirely outdoors.

606.11.4 Treatment systems.

Treatment systems shall be designed to reduce the allowable discharge concentration of the refrigerant gas to not more than 50 percent of the IDLH at the point of exhaust. Treatment systems shall be in accordance with FC Chapter 60.

606.11.5 Flaring systems.

Flaring systems for incineration of flammable refrigerants shall be designed to incinerate the entire discharge. The products of refrigerant incineration shall not pose health or environmental hazards. Incineration shall be automatic upon initiation of discharge, shall be designed to prevent blowback, and shall not expose structures or materials to threat of fire. Emergency power shall have the capacity to operate for one and one-half the required time for complete incineration of refrigerant in the system.

606.11.6 Ammonia diffusion systems.

Ammonia diffusion systems shall include a tank containing 1 gallon of water for each pound of ammonia (8.3 L of water for each 1 kg of ammonia) that will be released in 1 hour from the largest relief device connected to the discharge pipe. The water shall be prevented from freezing. The discharge pipe from the pressure relief device shall distribute ammonia in the bottom of the tank, but no lower than 33 feet (10 058 mm) below the maximum liquid level. The tank shall contain the volume of water and ammonia without overflowing.

606.12 Discharge location for refrigerating system machinery room ventilation.

Exhaust from mechanical ventilation systems serving refrigerating machinery rooms capable of exceeding 25 percent of the LFL or 50 percent of the IDLH shall be equipped with approved treatment systems to reduce the discharge concentrations of flammable, toxic or highly toxic refrigerants to those values or lower.

606.13 Notification of refrigerant discharges.

The commissioner shall be notified immediately when a discharge becomes reportable under state, federal or local regulations in accordance with FC 5003.3.1.

606.14 Records.

A written record shall be kept of refrigerant quantities brought into and removed from the premises.

606.15 Electrical equipment.

Where refrigerants of Groups A2, A3, B2 and B3, as defined in the Mechanical Code, are used, refrigerating system machinery rooms shall conform to the Class I, Division 2 hazardous location classification requirements of the Electrical Code.

Exception: Ammonia machinery rooms that are provided with ventilation in accordance with Chapter 11 of the Mechanical Code.

606.16 Use of Group A3 and B3 refrigerants.

Nothing contained in this section shall be construed to authorize the use of Group A3 or B3 refrigerants, as classified in the Mechanical Code, if otherwise prohibited by the construction codes, including the Mechanical Code.

Section FC 607. Elevators in Readiness

Open this section

607.1 Phase I emergency recall operation and Phase II emergency in-car operation.

Elevators intended to serve the needs of emergency personnel for firefighting or rescue purposes shall be provided with Phase I emergency recall operation and Phase II emergency in-car operation in accordance with the Building Code. Such elevators shall be operable with a citywide standard key in accordance with FC 506.2.1.

607.2 Emergency signs.

All required signage for elevators shall be provided in accordance with the construction codes, including the Building Code.

607.3 Elevators in readiness.

Elevators in every building 75 feet (22 860 mm) or more in height shall be kept ready for immediate use by the department during all hours of the night and day including holidays and weekends. There shall be a competent building attendant available to operate such elevators, except that no attendant shall be required for buildings between 75 and 150 feet (22 860 and 45 720 mm) in height having elevators with Phase I emergency recall operation and Phase II emergency in-car operation.

607.4 Emergency elevator operation and maintenance.

All elevators equipped with Phase I emergency recall operation and Phase II emergency in-car operation shall be maintained in proper working order such that the emergency elevator operations are operable at all times. All elevators with Phase I emergency recall operation shall be subjected, at least monthly, to a Phase I recall test. All elevators with Phase II emergency in-car operation shall be subjected, at least monthly, to a minimum of a one-floor operation II test.

607.5 Water protection of hoistway enclosures.

Methods to prevent water from infiltrating into the hoistway enclosures of fire service access elevators and occupant evacuation elevators, as approved by the Department of Buildings, shall be maintained.