NYC Administrative Code Title 29, Chapter 2 New York City Fire Code, part 10 of 15
Section FC 5004 to Section FC 5506: 30 sections.
Section FC 5004. Storage
5004.1 General.
Hazardous materials in amounts exceeding the maximum allowable quantity per control area as set forth in FC 5003.1 shall be stored in accordance with FC 5001, 5003 and 5004. Hazardous materials in amounts not exceeding the maximum allowable quantity per control area as set forth in FC 5003.1 shall be stored in accordance with FC 5001 and 5003. Nonflammable solid and nonflammable and noncombustible liquid hazardous materials in Group M retail occupancies and Group S wholesale storage shall be stored and displayed in accordance with FC 5003.11.
5004.2 Spill control and secondary containment for liquid and solid hazardous materials.
Buildings, structures, rooms or areas used for the storage of liquid or solid hazardous materials shall be provided with spill control and secondary containment in accordance with FC 5004.2.1 through 5004.2.3.
Exception: Outdoor storage of containers on approved containment pallets in accordance with FC 5004.2.3.
5004.2.1 Spill control for hazardous material liquids.
Buildings, structures, rooms or areas used for the storage of hazardous material liquids in individual vessels having a capacity of more than 55 gallons (208 L), or in which the aggregate capacity of multiple vessels exceeds 1,000 gallons (3785 L), shall be provided with spill control to prevent the flow of liquids to adjoining areas. Floors in indoor locations, and similar surfaces in outdoor locations, shall be designed to contain a spill from the largest single vessel by one of the following methods:
1. Liquid-tight sloped or recessed floors in indoor locations or similar protection in outdoor locations.
2. Liquid-tight floors and raised or recessed sills or dikes in indoor locations or similar protection in outdoor locations.
3. Sumps and collection systems.
4. Other approved engineered systems.
5004.2.1.1 Containment system construction.
Except for surfacing, the floors, sills, dikes, sumps and collection systems shall be constructed of noncombustible material, and the liquid-tight seal shall be compatible with the material stored. When liquid-tight sills or dikes are provided, they are not required at perimeter openings having an open-grate trench across the opening that connects to an approved collection system.
5004.2.2 Secondary containment for hazardous material liquids and solids.
Where required by FC Table 5004.2.2, buildings, structures, rooms or areas used for the storage of hazardous materials liquids or solids shall be provided with secondary containment in accordance with this section when the capacity of an individual vessel or the aggregate capacity of multiple vessels exceeds the following quantities:
1. Liquids: Capacity of an individual vessel exceeds 55 gallons (208 L) or the aggregate capacity of multiple vessels exceeds 1,000 gallons (3785 L).
2. Solids: Capacity of an individual vessel exceeds 550 pounds (250 kg) or the aggregate capacity of multiple vessels exceeds 10,000 pounds (4540 kg).
FC Table 5004.2.2 Required Secondary Containment – Hazardous Material Solids and Liquids Storage
Material Indoor Storage Outdoor Storage Solids Liquids Solids Liquids Physical-hazard materials Combustible liquids Class II Not Applicable See FC Chapter 57 Not Applicable See FC Chapter 57 Class IIIA See FC Chapter 57 See FC Chapter 57 Class IIIB See FC Chapter 57 See FC Chapter 57 Cryogenic fluids See FC Chapter 55 See FC Chapter 55 Explosives a See FC Chapter 56 See FC Chapter 56 Flammable liquids Class IA Not Applicable See FC Chapter 57 Not Applicable See FC Chapter 57 Class IB See FC Chapter 57 See FC Chapter 57 Class IC See FC Chapter 57 See FC Chapter 57 Flammable solids Not Required Not Applicable Not Required Not Applicable Organic peroxides, nondetonable Class I Required Required Not Required Required Class II Required Required Not Required Not Required Class III Class IV Class V Not Required Not Required Not Required Not Required Oxidizers Class 4 Required Required Not Required Required Class 3 Not Required Class 2 Not Required Class 1 Not Required Not Required Not Required Not Required Pyrophorics, nondetonable Not Required Required Not Required Required Unstable (reactives), nondetonable Class 4 Required Required Required Required Class 3 Class 2 Class 1 Not Required Not Required Not Required Not Required Water-reactives, nondetonable Class 3 Required Required Required Required Class 2 Class 1 Not Required Not Required Not Required Not Required Health-hazard materials Corrosives Not Required Required Not Required Required Highly toxics Required Required Required Required Toxics
a. Unclassified detonable organic peroxides (see FC Chapter 62), detonable pyrophoric materials (see FC Chapter 64), detonable unstable (reactive) materials (see FC Chapter 66) and detonable water-reactive materials (see FC Chapter 67) shall be treated as explosives for purposes of storage, handling and use (see FC Chapter 56).
5004.2.2.1 Containment and drainage methods.
The building, structure, room or area shall contain or drain the hazardous materials and fire protection water through the use of one of the following methods:
1. Liquid-tight sloped or recessed floors in indoor locations or similar protection in outdoor locations.
2. Liquid-tight floors and raised or recessed sills or dikes in indoor locations or similar protection in outdoor locations.
3. Sumps and collection systems.
4. Drainage systems leading to an approved location.
5. Other approved engineered systems.
5004.2.2.2 Incompatible materials.
Incompatible materials used in open systems shall be separated from each other in the secondary containment system.
5004.2.2.3 Indoor design.
Secondary containment for indoor storage areas shall be designed to contain a spill from the largest vessel plus the design flow volume of fire protection water calculated to discharge from the fire extinguishing system over the minimum required system design area or area of the room or area in which the storage is located, whichever is smaller. The containment capacity shall be designed to contain the flow for a minimum period of 20 minutes.
5004.2.2.4 Outdoor design.
Secondary containment for outdoor storage areas shall be designed to contain a spill from the largest individual vessel. If the area is open to rainfall, secondary containment shall be designed to include the volume of a 24-hour rainfall as determined by a 25-year storm but in no case less than 110 percent of the largest individual vessel and provisions shall be made to drain accumulations of ground water and rainwater.
5004.2.2.5 Monitoring.
Monitoring shall be provided to detect hazardous materials in the secondary containment system. The method of monitoring may be visual inspection of the primary or secondary containment, or other approved means. Where secondary containment is subject to the intrusion of water, a monitoring method for detecting water shall be provided. Where monitoring devices are provided, they shall be connected to approved audible or visible alarms.
5004.2.2.6 Drainage system design.
Drainage systems shall be in accordance with the Plumbing Code and the following requirements:
1. The slope of floors to drains in indoor locations, or similar protection in outdoor locations, shall not be less than 1 percent.
2. Drains from indoor storage areas shall be sized to carry the volume of the fire protection water as determined by the design density discharged from the fire extinguishing system over the minimum required system design area or area of the room or area in which the storage is located, whichever is smaller.
3. Drains from outdoor storage areas shall be sized to carry the volume of the fire flow and the volume of a 24-hour rainfall as determined by a 25-year storm.
4. Materials of construction for drainage systems shall be compatible with the materials stored.
5. Incompatible materials used in open systems shall be separated from each other in the drainage system.
6. Drains shall terminate in an approved location away from buildings, structures, valves, means of egress, fire access roadways, adjoining property and storm drains.
5004.2.3 Containment pallets.
When used as an alternative to spill control and secondary containment for outdoor storage in accordance with the exception set forth in FC 5004.2, containment pallets shall be in compliance with the following requirements:
1. A liquid-tight sump accessible for visual inspection shall be provided.
2. The sump shall be designed to contain not less than 66 gallons (250 L).
3. Exposed surfaces shall be compatible with material stored.
4. The containment pallet shall be protected to prevent collection of rainwater within the sump.
5004.3 Ventilation.
Indoor storage areas and storage buildings shall be provided with mechanical exhaust ventilation or natural ventilation where natural ventilation can be shown to be acceptable for the materials as stored.
Exception: Storage areas for flammable solids complying with the requirements of FC Chapter 59.
5004.3.1 System requirements.
Exhaust ventilation systems shall comply with the following requirements:
1. Installation shall be in accordance with the Mechanical Code.
2. Mechanical ventilation shall be at a rate of not less than 1 cubic foot per minute per square foot (0.00508 m 3 /s/m 2 ) of floor area over the storage area.
3. Systems shall operate continuously unless alternative designs are approved.
4. A manual shutoff control shall be provided outside of the room in a position adjacent to the access door to the room or in an approved location. The switch shall be a break-glass or other approved type and shall be labeled: VENTILATION SYSTEM EMERGENCY SHUTOFF.
5. Exhaust ventilation shall be designed based on the density of the potential fumes or vapors released. For fumes or vapors that are heavier than air, exhaust shall be taken from a point within 12 inches (305 mm) of the floor. For fumes or vapors that are lighter than air, exhaust shall be taken from a point within 12 inches (305 mm) of the highest point of the room.
6. The design and location of exhaust and inlet air openings shall serve to provide air movement across all portions of the floor and room to prevent the accumulation of vapors.
5004.4 Separation of incompatible hazardous materials.
Incompatible materials shall be separated in accordance with FC 5003.9.8.
5004.5 Sprinkler systems.
Indoor storage areas and storage buildings shall be protected throughout by a sprinkler system. The design of the sprinkler system shall not be less than that required for Ordinary Hazard Group 2 with a minimum design area of 3,000 square feet (279 m 2 ). Where the materials or storage arrangement are required by other regulations to be provided with a higher level of sprinkler system protection, the higher level of sprinkler system protection shall be provided.
5004.6 Explosion control.
Buildings, structures and indoor rooms and other areas shall be provided with explosion control in accordance with FC 911.
5004.7 Emergency power.
Where mechanical ventilation, treatment systems, temperature control, alarm, detection or other electrically operated systems are required, such systems shall be provided with an emergency power system in accordance with the Electrical Code, and the construction codes, including the Building Code, and FC 604.
Exceptions:
1. Mechanical ventilation for storage of Class IB and Class IC flammable liquids and combustible liquids in closed containers not exceeding 6 1/2 gallons (25 L) capacity.
2. Storage areas for Class 1 and 2 oxidizers.
3. Storage areas for Class III, IV and V organic peroxides.
4. Storage areas for highly toxic or toxic materials, in accordance with FC 6004.2.2.8 and 6004.3.2.6.
5. Storage areas for which an approved fail-safe engineered system has been installed for mechanical ventilation, treatment systems or temperature control systems.
5004.8 Limit controls.
Limit controls shall be provided in accordance with FC 5004.8.1 and 5004.8.2.
5004.8.1 Temperature control.
Materials that must be kept at temperatures other than normal ambient temperatures shall be provided with an approved means to maintain the temperature within a safe range. Redundant temperature control equipment that will operate on failure of the primary temperature control system, or other approved means to maintain the required temperature range, shall be provided.
5004.8.2 Pressure control.
Stationary tanks and equipment containing hazardous material liquids that can generate pressures exceeding design limits because of exposure fires or internal reaction, shall have some form of construction or other approved means that will relieve excessive internal pressure. The means of pressure relief shall vent to an approved location outdoors or to an exhaust scrubber or treatment system in accordance with FC Chapter 60.
5004.9 Emergency alarm.
An approved manual emergency alarm system shall be provided in buildings, rooms or areas used for storage of hazardous materials. Emergency alarm-initiating devices shall be installed outside of each interior exit or exit access door of storage buildings, rooms or areas. Activation of an emergency alarm-initiating device shall sound a local alarm to alert occupants of an emergency situation involving hazardous materials.
5004.10 Supervision.
Emergency alarm, detection and fire extinguishing systems required by FC 5004 shall be supervised by an approved central, proprietary or remote station service or shall initiate an audible and visual signal at a constantly attended on-site location.
5004.11 Clearance from combustibles.
The area surrounding an outdoor storage area or tank shall be kept clear of vegetation, rubbish and other combustible waste, and storage of combustible materials, for a minimum distance of 25 feet (7620 mm).
5004.12 Noncombustible floor.
Except for surfacing, floors of storage areas shall be of noncombustible construction.
5004.13 Weather protection.
Outdoor hazardous material storage areas sheltered by overhead noncombustible construction shall not be considered indoor storage when the area is constructed in accordance with the requirements for weather protection as required by the construction codes, including the Building Code.
Exception: Storage of explosives shall be considered as indoor storage.
Section FC 5005. Handling and Use
5005.1 General.
Hazardous materials in amounts exceeding the maximum allowable quantity per control area set forth in FC 5003.1 shall be handled and used, including dispensed, in accordance with FC 5001, 5003 and 5005. Hazardous materials in amounts not exceeding the maximum allowable quantity per control area set forth in FC 5003.1 shall be handled and used, including dispensed, in accordance with FC 5001 and 5003.
5005.1.1 Separation of incompatible materials.
Separation of incompatible materials shall be in accordance with FC 5003.9.8.
5005.1.2 Noncombustible floor.
Except for floor finishing operations, floors of areas where liquid or solid hazardous materials are used in open systems shall be of noncombustible, liquid-tight construction.
5005.1.3 Spill control and secondary containment for hazardous material liquids.
Where required by other provisions of FC 5005, spill control and secondary containment shall be provided for hazardous material liquids in accordance with FC 5004.2.
5005.1.4 Limit controls.
Limit controls shall be provided in accordance with FC 5005.1.4.1 through 5005.1.4.4.
5005.1.4.1 High-liquid-level control.
Open tanks in which liquid hazardous materials are used shall be equipped with a liquid-level limit control or other means to prevent overfilling of the tank.
5005.1.4.2 Low-liquid-level control.
Approved safeguards shall be provided to prevent a low-liquid level in a tank from creating a hazardous condition, including overheating of a tank or its contents.
5005.1.4.3 Temperature control.
Temperature control shall be provided in accordance with FC 5004.8.1.
5005.1.4.4 Pressure control.
Pressure control shall be provided in accordance with FC 5004.8.2.
5005.1.5 Emergency power.
Where mechanical ventilation, treatment systems, temperature control, alarm, detection or other electrically operated systems are required, such systems shall be provided with an emergency power system in accordance with the Electrical Code, the construction codes, including the Building Code, and FC 604.
Exception: Systems for highly toxic or toxic gases provided with emergency power in accordance with FC 6004.2.2.8 and 6004.3.2.6.
5005.1.6 Supervision.
Alarm, detection and fire extinguishing systems required by other provisions of FC 5005 shall be supervised by an approved central station or shall initiate an audible and visible signal at a continuously attended on-site location.
5005.1.7 Lighting.
Adequate lighting by natural or artificial means shall be provided.
5005.1.8 Fire extinguishing systems.
Indoor rooms or areas in which hazardous materials are handled or used shall be protected by a fire extinguishing system in accordance with FC Chapter 9 and the construction codes, including the Building Code. The design of any sprinkler system shall not be less than that required for Ordinary Hazard, Group 2, with a minimum design area of 3,000 square feet (279 m 2 ). Where the materials or storage arrangement are required by other regulations to be provided with a higher level of sprinkler system protection, the higher level of sprinkler system protection shall be provided.
5005.1.9 Ventilation.
Indoor use areas, including dispensing areas, shall be provided with exhaust ventilation in accordance with Section 502.8 of the Mechanical Code.
Exception: Ventilation is not required for flammable solids, unless they are in the form of finely divided particles or generate finely divided particles during use.
5005.1.10 Liquid transfer.
Liquids having a hazard ranking of 3 or 4 pursuant to NFPA 704 shall be transferred by one of the following methods:
1. From safety cans complying with the requirements of UL 30.
2. Through an approved closed piping system.
3. From containers or tanks by an approved pump taking suction through an opening in the top of the container or tank.
4. From containers or tanks by gravity through an approved self-closing or automatic-closing valve when the container or tank and dispensing operations are provided with spill control and secondary containment in accordance with FC 5004.2. Highly toxic liquids shall not be dispensed by gravity from tanks.
5. Approved engineered liquid transfer systems.
Exceptions:
1. Liquids having a hazard ranking of 4 when dispensed from approved containers not exceeding 1.3 gallons (5 L).
2. Liquids having a hazard ranking of 3 when dispensed from approved containers not exceeding 5.3 gallons (20 L).
5005.2 Indoor use.
Indoor use, including dispensing, of hazardous materials shall be in buildings complying with the requirements of the construction codes, including the Building Code, and in accordance with FC 5005.1 and FC 5005.2.1 through 5005.2.2.5.
5005.2.1 Open systems.
Use of hazardous materials in open containers or systems shall be in accordance with FC 5005.2.1.1 through 5005.2.1.4.
5005.2.1.1 Ventilation.
Where gases, liquids or solids having a hazard ranking of 3 or 4, as defined in NFPA 704 are used, mechanical exhaust ventilation shall be provided to capture gases, fumes, mists or vapors at the point of generation.
Exception: Gases, liquids or solids that do not generate harmful fumes, mists or vapors.
5005.2.1.2 Explosion control.
Explosion control shall be provided in accordance with FC 5004.6 when an explosive environment can occur because of the characteristics or nature of the hazardous materials or the manner in which they are used.
5005.2.1.3 Spill control for hazardous material liquids.
Buildings, rooms or areas where hazardous material liquids are dispensed into vessels exceeding a 1.3-gallon (5 L) capacity or used in open systems exceeding a 5.3-gallon (20 L) capacity shall be provided with spill control in accordance with FC 5004.2.1.
5005.2.1.4 Secondary containment for hazardous material liquids.
Where required by FC Table 5005.2.1.4, buildings, structures, rooms or areas where hazardous material liquids are used in open systems shall be provided with secondary containment in accordance with FC 5004.2.2 when the capacity of an individual vessel or system or the capacity of multiple vessels or systems exceeds the following quantities:
1. Individual vessel or system: greater than 1.3 gallons (5 L).
2. Multiple vessels or systems: greater than 5.3 gallons (20 L).
FC Table 5005.2.1.4 Required Secondary Containment – Hazardous Material Solids and Liquids Use
Material Indoor Use Outdoor Use Solids Liquids Solids Liquids Physical-hazard materials Combustible liquids Class II Not Applicable See FC Chapter 57 Not Applicable See FC Chapter 57 Class IIIA See FC Chapter 57 See FC Chapter 57 Class IIIB See FC Chapter 57 See FC Chapter 57 Cryogenic fluids Not Applicable See FC Chapter 55 Not Applicable See FC Chapter 55 Explosives a See FC Chapter 56 See FC Chapter 56 Flammable liquids Class IA Not Applicable See FC Chapter 57 Not Applicable See FC Chapter 57 Class IB See FC Chapter 57 See FC Chapter 57 Class IC See FC Chapter 57 See FC Chapter 57 Flammable solids Not Required Not Applicable Not Required Not Applicable Organic peroxides nondetonable Class I Not Required Required Not Required Required Class II Class III Class IV Class V Not Required Not Required Not Required Oxidizers Class 4 Not Required Required Not Required Required Class 3 Class 2 Class 1 Pyrophorics nondetonable Not Required Required Not Required Required Unstable (reactives) nondetonable Class 4 Not Required Required Required Required Class 3 Class 2 Class 1 Not Required Not Required Required Required Water-reactives, nondetonable Class 3 Not Required Required Required Required Class 2 Class 1 Not Required Not Required Required Required Health-hazard materials Corrosives Not Required Required Not Required Required Highly toxics Required Toxics Not Required
a. Unclassified detonable organic peroxides (see FC Chapter 62), detonable pyrophoric materials (see FC Chapter 64), detonable unstable (reactive) materials (see FC Chapter 66) and detonable water-reactive materials (see FC Chapter 67) shall be treated as explosives for purposes of storage, handling and use (see FC Chapter 56).
5005.2.2 Closed systems.
Use of hazardous materials in closed containers or systems shall be in accordance with FC 5005.2.2.1 through 5005.2.2.5.
5005.2.2.1 Design.
Systems shall be suitable for the use intended and shall be designed by a qualified person. Controls shall be designed to prevent materials from entering or leaving the process or reaction systems at other than the intended time, rate or path. Where automatic controls are provided, they shall be designed to be fail safe.
5005.2.2.2 Ventilation.
Where closed systems are designed to be opened as part of normal operations, ventilation shall be provided in accordance with FC 5005.2.1.1.
5005.2.2.3 Explosion control.
Explosion control shall be provided in accordance with FC 5004.6 where an explosive environment exists because of the hazardous materials or the manner in which they are used.
Exception: Where process vessels are designed to contain fully the worst-case explosion anticipated within the vessel under process conditions based on the most likely failure.
5005.2.2.4 Spill control for hazardous material liquids.
Buildings, rooms or areas where hazardous material liquids are used in individual vessels exceeding a 55-gallon (208 L) capacity shall be provided with spill control in accordance with FC 5004.2.1.
5005.2.2.5 Secondary containment for hazardous material liquids.
Where required by FC Table 5005.2.1.4, buildings, rooms or areas where hazardous material liquids are used in vessels or systems shall be provided with secondary containment in accordance with FC 5004.2.2 when the capacity of an individual vessel or system or the capacity of multiple vessels or systems exceeds the following quantities:
1. Individual vessel or system: greater than 55 gallons (208 L).
2. Multiple vessels or systems: greater than 1,000 gallons (3785 L).
5005.3 Outdoor use.
Outdoor use, including dispensing, of hazardous materials shall be in accordance with FC 5005.3.1 through 5005.3.9.
5005.3.1 Quantities exceeding the maximum allowable quantity per control area.
Outdoor use of hazardous materials, in either closed or open containers or systems, in amounts exceeding the maximum allowable quantity per control area indicated in FC Tables 5003.1.1(3) and 5003.1.1(4) shall be in accordance with FC 5001, 5003, 5005.1 and 5005.3.
5005.3.2 Quantities not exceeding the maximum allowable quantity per control area.
Outdoor use of hazardous materials, in either closed or open containers or systems, in amounts not exceeding the maximum allowable quantity per control area indicated in FC Tables 5003.1.1(3) and 5003.1.1(4) shall be in accordance with FC 5001 and 5003.
5005.3.3 Location.
Outdoor use areas for hazardous materials shall be located as required for outdoor storage in accordance with FC 5004.
5005.3.4 Spill control for hazardous material liquids in open systems.
Outdoor areas where hazardous material liquids are dispensed in vessels exceeding a 1.3-gallon (5 L) capacity or used in open systems exceeding a 5.3-gallon (20 L) capacity shall be provided with spill control in accordance with FC 5004.2.1.
5005.3.5 Secondary containment for hazardous material liquids in open systems.
Where required by FC Table 5005.2.1.4, outdoor areas where hazardous material liquids are used in open systems shall be provided with secondary containment in accordance with FC 5004.2.2 when the capacity of an individual vessel or system or the capacity of multiple vessels or systems exceeds the following quantities:
1. Individual vessel or system: greater than 1.3 gallons (5 L).
2. Multiple vessels or systems: greater than 5.3 gallons (20 L).
5005.3.6 Spill control for hazardous material liquids in closed systems.
Outdoor areas where hazardous material liquids are used in closed systems exceeding 55 gallons (208 L) shall be provided with spill control in accordance with FC 5004.2.1.
5005.3.7 Secondary containment for hazardous material liquids in closed systems.
Where required by FC Table 5005.2.1.4, outdoor areas where hazardous material liquids are used in closed systems shall be provided with secondary containment in accordance with FC 5004.2.2 when the capacity of an individual vessel or system or the capacity of multiple vessels or systems exceeds the following quantities:
1. Individual vessel or system: greater than 55 gallons (208 L).
2. Multiple vessels or systems: greater than 1,000 gallons (3785 L).
5005.3.8 Clearance from combustibles.
The area surrounding an outdoor use area, including an area used for dispensing, shall be kept clear of vegetation, rubbish and other combustible waste, and combustible materials, for a minimum distance of 30 feet (9144 mm).
5005.3.9 Weather protection.
Outdoor hazardous material use areas sheltered by overhead noncombustible construction shall not be considered indoor use when the area is constructed in accordance with the requirements for weather protection as required in the construction codes, including the Building Code.
Exception: Use of explosives shall be considered as indoor use.
5005.4 Handling.
Handling of hazardous materials shall be in accordance with FC 5005.4.1 through 5005.4.4.
5005.4.1 Quantities exceeding the maximum allowable quantity per control area.
Handling of hazardous materials in indoor and outdoor locations in amounts exceeding the maximum allowable quantity per control area indicated in FC Tables 5003.1.1(1) through 5003.1.1(4) shall be in accordance with FC 5001, 5003, 5005.1 and 5005.4.
5005.4.2 Quantities not exceeding the maximum allowable quantity per control area.
Handling of hazardous materials in indoor locations in amounts not exceeding the maximum allowable quantity per control area indicated in FC Tables 5003.1.1(1) and 5003.1.1(2) shall be in accordance with FC 5001 and 5003. Handling of hazardous materials in outdoor locations in amounts not exceeding the maximum allowable quantity per control area indicated in FC Tables 5003.1.1(3) and 5003.1.1(4) shall be in accordance with FC 5001 and 5003.
5005.4.3 Location.
Outdoor handling areas for hazardous materials shall be located as required for outdoor storage in accordance with FC 5004.
5005.4.4 Emergency alarm.
Where hazardous materials in quantities exceeding the maximum allowable quantity per control area having a hazard ranking of 3 or 4 pursuant to NFPA 704 are moved through corridors or exit enclosures, there shall be an emergency telephone system, a local manual alarm station or an approved alarm-initiating device at not more than 150-foot (45 720-mm) intervals throughout the handling route, and at each exit doorway throughout the handling route. The signal shall be relayed to an approved central station or remote supervising station or a constantly attended on-site location and shall also initiate a local audible alarm.
Section FC 5006. Non-Production Chemical Laboratories
5006.1 Scope.
This section shall govern the storage, handling and use of laboratory chemicals in a non-production laboratory and accessory storage of laboratory chemicals in a storage room. The design and construction of non-production laboratories and accessory storage rooms for laboratory chemicals shall comply with the requirements of the construction codes, including the Building Code and the Mechanical Code.
5006.2 General.
Laboratory chemicals within a laboratory unit, including an educational or instructional laboratory unit, shall be stored, handled and used in accordance with this section and, except as otherwise provided in this section, NFPA 45, as modified by FC Appendix B with respect to laboratory unit fire hazard class D requirements. The ceiling, floor and walls of a laboratory unit shall be separated from all adjoining areas by a minimum 1-hour fire-rated construction.
5006.3 Permits.
Permits shall be required as set forth in FC 105.6.
5006.4 Supervision.
Non-production laboratory operations requiring a permit shall be under the personal supervision of a certificate of fitness holder. At least one certificate of fitness holder shall be present on each floor of the laboratory unit on which laboratory operations are being conducted while the laboratory is in operation. Additional certificate of fitness holders shall be provided as the commissioner may require as a condition of the permit. Accessory laboratory chemical storage rooms shall be under the general supervision of a certificate of fitness holder.
5006.5 Prohibitions.
It shall be unlawful in any non-production laboratory or any accessory storage of laboratory chemicals in a storage room to:
1. Store, handle or use any explosive.
2. Store, handle or use any unclassified detonable organic peroxide, detonable pyrophoric material, detonable unstable (reactive) material or detonable water-reactive material.
3. Store, handle or use any Class 4 unstable (reactive) material.
4. Store, handle or use any Class 4 oxidizing material.
5. Store, handle or use below grade any flammable gas.
6. Use an open flame for heating or distilling any flammable solid, flammable liquid or flammable gas.
7. Store flammable liquids in basements, cellars or other areas below grade.
8. Store combustible liquids in basements, cellars or other areas below grade in a manner contrary to FC 5704.3.5.1.
9. Store, handle or use LPG in Group E and I occupancies in a manner contrary to FC 6103.2.1.4.
10. Store, handle or use in an educational laboratory gases classified as a Class 3 or 4 health hazard.
5006.6 Quantity limitations.
The quantities of laboratory chemicals stored, handled or used within a laboratory unit, excluding storage rooms, shall be in accordance with FC 5006.6.1 through 5006.6.10. Unless designated as a control area, FC 5003.8.3 shall not apply to a laboratory unit.
5006.6.1 Flammable and combustible liquids.
The density and total quantity of flammable and combustible liquids allowed within a laboratory unit, excluding storage rooms, shall be in accordance with Table 9.1.1(b) of NFPA 45, as modified by FC Appendix B, for laboratory unit fire hazard Class D.
Exceptions: For laboratory units other than educational or instructional laboratories pursuant to NFPA 45, as modified by FC Appendix B:
1. The density of flammable and combustible liquids allowed within a Class D laboratory unit may be increased to those set forth in Table 9.1.1(b) of NFPA 45, as modified by FC Appendix B, for laboratory unit fire hazard Class B provided the total quantity of flammable and combustible liquid, including any in storage cabinets or safety cans, does not exceed 25 gallons (95 L).
2. The density of flammable and combustible liquids allowed within a Class D laboratory unit may be increased to those set forth in Table 9.1.1(b) of NFPA 45, as modified by FC Appendix B, for laboratory unit fire hazard Class B provided the total quantity of flammable and combustible liquid, including any in storage cabinets or safety cans, does not exceed 30 gallons (114 L) and the walls, floors and ceilings of the laboratory unit are separated from all adjoining areas by 2-hour fire-rated construction.
3. The quantity of flammable and combustible liquids allowed within a Class D laboratory unit, excluding quantities in storage cabinets or safety cans, may be increased from 75 gallons (284 L) to 100 gallons (379 L), provided the walls, floors and ceilings of the laboratory unit are separated from all adjoining areas by 2-hour fire-rated construction. Total quantities of flammable and combustible liquids, including quantities in storage cabinets and safety cans, may be increased from 150 gallons (568 L) to 200 gallons (757 L), provided the walls, floors and ceilings of the laboratory unit are separated from all adjoining areas by 2-hour fire-rated construction.
5006.6.2 Flammable solids.
The storage, handling and use of flammable solids within a laboratory unit shall be in accordance with FC Chapters 50 and 59. The total quantity of flammable solids stored, handled and used, excluding any quantities in a storage room, shall not exceed 10 pounds (4.54 kg).
Exception: The total quantity of flammable solids allowed within a laboratory unit that is provided with walls, floors and ceilings that separate the laboratory unit from all adjoining areas by 2-hour fire-rated construction shall not exceed 15 pounds (6.81 kg).
5006.6.3 Oxidizers and organic peroxides.
The storage, handling and use of solid and liquid oxidizers and organic peroxides within a laboratory unit shall be in accordance with FC Chapters 50, 62 and 63 and the total quantity of all such material, excluding any quantities in a storage room, shall not exceed 40 pounds (18.14 kg), provided that not more than 2 pounds (0.907 kg) of such oxidizers are Class 3 oxidizers and not more than 1 pound (0.454 kg) of such peroxides are Class I organic peroxides.
Exception: The total aggregate quantity of solid and liquid oxidizers and organic peroxides allowed within a laboratory unit that is provided with walls, floors and ceilings that separate the laboratory unit from all adjoining areas by 2-hour fire-rated construction shall not exceed 50 pounds (22.7 kg), provided that not more than 2 pounds (0.907 kg) of such oxidizers are Class 3 oxidizers and not more than 1 pound (0.454 kg) of such peroxides are Class I organic peroxides.
5006.6.4 Unstable (reactive) material.
The storage, handling and use of unstable (reactive) material within a laboratory unit shall be in accordance with FC Chapters 50 and 66 and the total quantity, excluding any quantities in a storage room, shall not exceed 6 pounds (2.722 kg), provided not more than 1 pound (0.454 kg) of such reactive material is Class 3 unstable (reactive).
Exception: The total quantity of unstable (reactive) material allowed within a laboratory unit that is provided with walls, floors and ceilings that separate the laboratory unit from all adjoining areas by 2-hour fire-rated construction shall not exceed 12 pounds (5.44 kg), provided not more than 1 pound (0.454 kg) of such reactive material is Class 3 unstable (reactive).
5006.6.5 Water-reactive material.
The storage, handling and use of water-reactive material within a laboratory unit shall be in accordance with FC Chapters 50 and 67 and the total quantity, excluding any quantities in a storage room, shall not exceed 2 1/2 pounds (1.134 kg).
Exception: The total quantity of water-reactive material allowed within a laboratory unit that is provided with walls, floors and ceilings that separate the laboratory unit from all adjoining areas by 2-hour fire-rated construction shall not exceed 5 pounds (2.27 kg).
5006.6.6 Pyrophoric material.
The storage, handling and use of solid or liquid pyrophoric material within a laboratory unit shall be in accordance with FC Chapters 50 and 64 and the total quantity, excluding any quantities in a storage room, shall not exceed 1/2 pound (0.227 kg).
Exception: The total quantity of solid or liquid pyrophoric material allowed within a laboratory unit that is provided with walls, floors and ceilings that separate the laboratory unit from all adjoining areas by 2-hour fire-rated construction shall not exceed 1 pound (0.454 kg).
5006.6.7 Highly toxic material.
The storage, handling and use of solid or liquid highly toxic material within a laboratory unit shall be in accordance with FC Chapters 50 and 60 and the total quantity, excluding any quantities in a storage room, shall not exceed 5 pounds (2.27 kg).
5006.6.8 Toxic material.
The storage, handling and use of solid or liquid toxic material within a laboratory unit shall be in accordance with FC Chapters 50 and 60 and the total quantity, excluding any quantities in a storage room, shall not exceed 250 pounds (113.4 kg).
5006.6.9 Corrosive material.
The storage, handling or use of solid or liquid corrosive material within a laboratory shall be in accordance with FC Chapters 50 and 54 and the total quantity, excluding any quantity in a storage room, shall not exceed 250 gallons (946 L).
5006.6.10 Hazardous gases.
The storage, handling and use of hazardous gases within a laboratory unit shall be in accordance with this section, FC Chapters 50, 53 through 55, 58, 60, 63, 64 and 66, as applicable, and NFPA 45, as modified by FC Appendix B. The total quantity of hazardous gases, excluding any quantity stored in a storage room, shall be in accordance with NFPA 45, as modified by FC Appendix B.
5006.6.10.1 Highly toxic toxic, and corrosive gases.
It shall be unlawful to store, handle or use in any instructional laboratory unit any combination of highly toxic, toxic, and corrosive gases in quantities that exceed 20 SCF (0.566 m 3 ).
5006.6.10.2 Asphyxiant gases.
When the quantity of cryogenic inert gases or refrigerated carbon dioxide stored, handled or used within a laboratory unit exceeds 60 gallons (227 L), an oxygen sensor shall be installed and maintained at one or more locations within the laboratory unit in accordance with FC 5505.4.1.1.1, provided that at least one oxygen sensor is installed in the laboratory unit.
5006.7 Storage room classification.
Storage rooms for laboratory chemicals accessory to a laboratory unit shall be classified as set forth in the Building Code.
5006.8 Storage rooms.
In addition to the quantities that may be stored, handled and used in a laboratory unit pursuant to FC 5006.6, chemicals for use in a laboratory unit may be stored in a dedicated storage room complying with Chapter 4 of the Building Code and the following requirements:
1. Storage room capacity shall not exceed a maximum of 300 gallons (1136 L) of chemicals, not to exceed 5 gallons per square foot (204 L/m 2 ) of floor area.
2. Flammable gas storage rooms shall not contain more than 2,500 SCF (70.8 m 3 ) of flammable gas.
3. Chemicals that are incompatible with each other shall not be stored in the same storage room, unless in compliance with the requirements of this chapter.
4 . Chemicals shall not be used within the storage room.
5006.9 Safety showers.
Where more than 5 gallons (19 L) of corrosive liquid or flammable liquid are stored, handled or used, suitable facilities with fixed overhead or flexible hand-held showers shall be provided. Such shower shall be within 25 feet (7620 mm) of the laboratory unit and storage room door and shall be maintained in good working order, and readily accessible at all times.
5006.10 Neutralizing or absorbing agents.
Where more than 5 gallons (19 L) of corrosive liquids are stored, handled or used, a sufficient quantity of suitable neutralizing or absorbing agents shall be provided.
5006.11 Curtains and drapes.
Curtains and drapes installed in a laboratory unit shall comply with the flame resistance requirements of FC Chapter 8.
Section FC 5007. Transportation of Hazardous Materials
5007.1 Scope.
This section shall govern the transportation of hazardous materials, as defined in the regulations of the United States Department of Transportation, as set forth in 49 CFR Part 173.
5007.2 General.
Transportation of hazardous materials shall be in accordance with the regulations of the United States Department of Transportation and this section.
5007.3 Prohibitions.
It shall be unlawful to:
1. Transport hazardous materials in or through the city where such transport is prohibited or restricted by federal or state law, rule or regulation, including restrictions on transportation of hazardous materials over bridges and through tunnels.
2. Transport in or through the city hazardous materials of such type, in such quantities, or in such manner as is prohibited by this code or the rules, except where such transport is in accordance with approved routes and times or other approved procedures or safety measures.
3. Transport hazardous materials in quantities requiring a permit pursuant to this code or the rules without such permit.
4. Deliver hazardous materials in quantities requiring a permit pursuant to this code or the rules to any location unless the owner or other person taking delivery thereof is in possession of a permit for the storage, handling and/or use of such hazardous material at such location.
5. Transport LPG containers that are or have ever been filled with LPG in the trunk of a passenger motor vehicle, or other area of such vehicle not readily visible to emergency responders.
5007.4 Reserved.
5007.5 Transportation of hazardous materials by vehicle.
Transportation of hazardous materials by vehicle shall be in accordance with this section, the rules, and the requirements contained in the regulations of the United States Department of Transportation, as set forth in 49 CFR, Parts 171, 172, 173, 177, 178, 180, 383, 387, 390, 392, 393, 396 and 397 and their appendices, and any amendments thereto, with respect to:
1. The design, construction, maintenance and equipment of cargo tanks and other vehicles.
2. The marking and placarding of vehicles.
3. The preparation, execution and use of shipping documents.
4. The handling, loading and unloading of hazardous materials.
5. The qualifications and commercial driver's license requirements of vehicle operators.
6. Insurance and other financial requirements.
5007.6 Transportation of explosives by vehicle.
Transportation of explosives by vehicle for storage, handling and use in the city shall additionally comply with the requirements of FC 5007.6.1 through 5007.6.6.
5007.6.1 Approved vehicles.
Except as otherwise authorized by the department, it shall be unlawful to transport, including delivering, any blasting materials or Division 1.1 or 1.5 explosives for storage, handling or use in the city, except in a vehicle designed and constructed in accordance with the rules, and for which a permit has been issued.
5007.6.2 Nitroglycerine.
It shall be unlawful to transport any nitroglycerine-containing material, except nitroglycerine in the form of tablets, pills or granules, in quantities not exceeding ten thousand, containing not more than 1/50 of a grain each, or to transport frozen nitroglycerine.
5007.6.3 Packing and marking.
Other than as prescribed or approved by the commissioner, it shall be unlawful to sell or deliver for use any explosive except in original and unopened packages, packed in accordance with FC 5007.6.3.1 through 5007.6.3.3.
5007.6.3.1 Explosives containing liquids.
Dynamite and other explosives containing a liquid which may exude a liquid shall be transported in DOTn approved cases, lined with a liquidproof plastic lining sufficient to prevent the exudation of the liquid. Such cases shall contain not more than 50 pounds (22.7 kg) of net explosive weight.
5007.6.3.2 Other explosives.
Other blasting materials (except black powder, blasting powder and smokeless propellant) that do not contain a substance subject to deterioration or instability by exposure to moisture shall be transported in DOTn approved cases each containing not more than 50 pounds (22.7 kg) of net explosive weight.
5007.6.3.3 Sticks or cartridges.
All explosives in the form of sticks or cartridges shall be packed so as to lie on their sides; and, when the boxes are loaded in or upon a motor vehicle, marine vessel or watercraft they shall be so arranged that the sticks or cartridges rest on their sides.
5007.6.4 Detonators.
Transportation of blasting caps and other detonators shall additionally comply with the requirements of FC 5007.6.4.1 and 5007.6.4.2.
5007.6.4.1 Packaging.
It shall be unlawful to bring into, transport, or deliver within the city any blasting caps and other detonators, unless packaged in original, unopened boxes.
5007.6.4.2 Delivery vehicles.
It shall be unlawful to transport any detonators in quantities exceeding five thousand, or to transport or cause to be transported, detonators together with any other explosives, except in an approved container in accordance with the regulations of the United States Department of Transportation, as set forth in 49 CFR Part 177.
5007.6.5 Black powder, blasting powder or smokeless propellants.
Black powder, blasting powder or smokeless propellant shall be transported in containers of not more than 25 pounds (11.34 kg).
5007.6.6 Restrictions.
Vehicles transporting explosives shall comply with the following requirements:
1. Explosives shall be delivered only during daylight hours.
2. No unnecessary stops shall be made in transit.
3. Vehicles shall be escorted in accordance with FC 5007.12, as applicable.
4. If explosives are being transported in more than one vehicle, the vehicles shall maintain a safe distance from each other of not less than 250 feet (76 200 mm).
5. It shall be unlawful to transport or deliver any explosives in a subway or other underground tunnel or conveyance, except as approved for blasting operations.
5007.7 Transportation of explosives by marine vessel.
Transportation of explosives by marine vessel and watercraft shall be in accordance with the regulations of the United States Department of Transportation, as set forth in CFR Part 176, and any amendments thereto, and shall additionally comply with the requirements of FC 5007.7.1 through 5007.7.5.
5007.7.1 Temporary storage on marine vessel.
It shall be unlawful to store for more than 48 hours on board of any marine vessel or watercraft lying to at a wharf, pier, bulkhead or other structure over or contiguous to navigable waters within the city, any explosives in excess of the amount required for the vessel's own use for signaling or lifesaving purposes.
5007.7.2 Supervision.
Any powder-boat or other marine vessel or watercraft used to transport explosives upon the navigable waters within the city for delivery at a wharf, pier, bulkhead or other structure over or contiguous to navigable waters, or to a marine vessel or watercraft lying thereto, shall, while transporting explosives, have on board at all times two persons, each holding a certificate of fitness for explosives handling. Only such certificate holders, the permit holder and the marine vessel or watercraft's crew shall be allowed in or upon such vessel or watercraft. Whenever practicable, all explosives shall be stowed on deck under a waterproof cover or otherwise kept dry.
5007.7.3 Detonators.
Except for marine vessels and watercraft engaged in export trade, it shall be unlawful to carry in or upon a marine vessel or watercraft transporting explosives within the city, detonators together with any other explosives, except in approved containers in accordance with the regulations of the United States Department of Transportation, as set forth in 49 CFR Part 176.
5007.7.4 Unloading.
It shall be unlawful to unload explosives onto a wharf, pier, bulkhead or other structure over or contiguous to navigable waters. Explosives intended for storage, handling or use within the city shall be transferred from the marine vessel or watercraft making the delivery directly to a vehicle at a wharf, pier, bulkhead or other structure over or contiguous to navigable waters approved by the commissioner. Explosives intended for shipment to points outside the city may be transferred from a marine vessel or watercraft directly to another marine vessel or watercraft lying at a wharf, pier, bulkhead or other structure within the city over or contiguous to navigable waters approved by the commissioner, provided the amount so transferred does not exceed 2,500 pounds (1134 kg). All such shipments in quantities exceeding 2,500 pounds (1134 kg) but not more than 5,000 pounds (2268 kg), may be transferred from marine vessel or watercraft to a marine vessel or watercraft at a distance of not less than 1,000 feet (304 800 mm) from any pier line.
5007.7.5 Smoking and intoxicated persons.
It shall be unlawful to smoke or maintain any flame while in or upon any marine vessel or watercraft carrying explosives, or allow in or upon such vessel or watercraft, any intoxicated person.
5007.8 Transportation of fireworks by vehicle.
Transportation of fireworks by vehicle for firework displays in the city shall additionally comply with the requirements of FC 5007.8.1 and 5007.8.2.
5007.8.1 Delivery to display site.
It shall be unlawful to transport fireworks through the city unless such fireworks are being transported to or from a display site for which a permit has been issued and such vehicle is escorted by department firefighting apparatus in accordance with FC 5007.12.
5007.8.2 Restrictions.
Vehicles transporting fireworks shall comply with the requirements of FC 5007.6.6.
5007.9 Transportation of flammable and combustible liquids by vehicle.
Transportation of flammable and combustible liquids by vehicle shall additionally comply with the requirements of FC 5007.9.1 through 5007.9.6.
5007.9.1 Operation of cargo tanks.
Cargo tanks shall be maintained and operated in accordance with FC 5007.9.1.1 through 5007.9.1.13.
5007.9.1.1 Vehicle maintenance.
Cargo tanks shall not be used unless they are in good working order and free from accumulation of grease, oil or other flammable or combustible waste.
5007.9.1.2 Monitoring of loading and unloading.
The operator of a cargo tank shall not remain in the vehicle during loading or unloading of the cargo and shall personally supervise such operation from a location at which the operator may observe the vehicle, the delivery and vapor recovery hoses, the fill connection and any overfilling of the tank.
5007.9.1.3 Vehicle shutdown.
The cargo tank motor shall be shut down during the making and breaking of hose connections. If loading or unloading is performed without the use of a power pump, the cargo tank motor shall be shut down throughout such operations.
5007.9.1.4 Secured from movement.
All appropriate actions shall be taken to prevent vehicle movement during the loading and unloading of the cargo, including setting the parking brake and chocking of tires.
5007.9.1.5 Outage.
A cargo tank or compartment thereof shall not be loaded to absolute capacity. The vacant space in a cargo tank or compartment thereof shall not be less than 1 percent to prevent leakage from or distortion of such tank or compartment by expansion of the contents caused by a rise in temperature.
5007.9.1.6 Overfill prevention.
The operator of a cargo tank shall, before making delivery to a tank, determine the unfilled capacity of the tank by use of a suitable gauging device, and shall not deliver cargo in excess of that amount.
5007.9.1.7 Securing hatches.
During the loading of cargo tanks with openable domes, the domes shall be secured on all but the receiving compartment, except that during loading of gasoline, all domes shall be secured.
5007.9.1.8 Cargo temperature.
Flammable and combustible liquids shall not be loaded into or transported in a cargo tank or delivered at a temperature above the material's ignition temperature.
5007.9.1.9 Bonding to underground tanks.
An external bond-wire connection or bond-wire integral to the delivery hose shall be provided when transferring flammable liquids into underground tanks.
5007.9.1.10 Smoking.
It shall be unlawful for the operator of a cargo tank to smoke in and within 25 feet (7620 mm) of the vehicle while transporting, loading or unloading cargo or to allow others to do so.
5007.9.1.11 Hose connections.
Flammable and combustible liquids shall be transferred to tanks by means of approved liquid- and vapor-tight connections between the delivery hose and fill tank connection. Where underground tanks are equipped with a vapor recovery system, all connections required for the safe and proper functioning of the vapor recovery system shall be made and maintained liquid- and vapor-tight throughout the unloading process. Vapors shall not be discharged at grade level during delivery.
5007.9.1.12 Hose protection.
In making any delivery of flammable or combustible liquid the operator of the cargo tank shall ensure, prior to unloading, that all hoses utilized for liquid delivery and vapor recovery are protected from physical damage, including damage by motor vehicles. Such protection shall be provided by positioning the cargo tank to prevent motor vehicles from passing through the area or areas occupied by hoses, or by other approved equivalent means.
5007.9.1.13 Method of discharge.
Gasoline that is transferred to underground tanks shall be discharged by gravity only.
5007.9.2 Parking restrictions.
Parking of cargo tanks shall be in accordance with FC 5007.9.2.1 and 5007.9.2.2, except that in the event of an accident, mechanical breakdown or other emergency, a cargo tank may be parked and left unattended at any safe location while the operator is obtaining assistance.
5007.9.2.1 Restricted areas.
It shall be unlawful to:
1. Leave a cargo tank unattended at any time on a public street, or any off-street location within 250 feet (76 200 mm) of an occupied building, or any other restricted location designated by the commissioner by rule or as a condition of a permit.
2. Park cargo tanks indoors.
5007.9.2.2 Approved parking.
Cargo tanks temporarily parked during working hours shall be parked at an approved off-street location not less than 250 feet (76 200 mm) from an occupied building. Cargo tanks shall be parked during nonworking hours on the grounds of a bulk plant or terminal, not less than 25 feet (7620 mm) from the nearest lot line; or at other approved location, not less than 50 feet (15 240 mm) from any building.
5007.9.3 Portable fire extinguishers.
Cargo tanks shall be equipped with a portable fire extinguisher complying with the requirements of FC 906 and having a minimum rating of 2-A:20-B:C. During unloading of the cargo tank, the portable fire extinguisher shall be outside of the motor vehicle and shall be readily available, but at a distance of at least 15 feet (4572 mm) from the unloading valves.
5007.9.4 Delivery and unloading of cargo.
Except as otherwise provided in FC 5706.2.8, cargo tanks shall deliver flammable or combustible liquids only to approved stationary storage systems. Flammable liquids being transported by a motor vehicle other than a cargo tank shall not be dispensed from a container prior to removal of the container from the vehicle.
5007.9.5 Emergency transfers between vehicles.
Department representatives may authorize a transfer from one cargo tank directly into a permitted or other approved cargo tank in the interest of public safety, such as when a cargo tank has been involved in a vehicular accident or has otherwise been damaged.
5007.9.6 Compartmental markings.
The maximum capacity of each compartment of a cargo tank shall be marked, in gallons, on the driver and passenger sides of the cargo tank in 3-inch (76-mm) white letters.
5007.10 Transportation of compressed gases by cargo tank.
Transportation of compressed gases by cargo tank shall additionally comply with the requirements of FC 5007.10.1.
5007.10.1 Prohibited compressed gases.
It shall be unlawful to transport the following compressed gases in a cargo tank:
1. Acetylene.
2. Liquefied carbon monoxide.
3. Liquefied chlorine.
4. Cyanogen.
5. Cyclopropane.
6. Diborane.
7. Di-, mono-, and tri-methylamines.
8. Dimethyl ether.
9. Ethylene.
10. Fluorine.
11. Liquefied hydrogen.
12. Hydrogen cyanide.
13. Hydrogen sulfide.
14. Liquefied petroleum gases (LPG).
15. Liquefied natural gas (LNG).
16. Methylacetylene propadiene mixture-stabilized, including propyns, mapp gas or apache gas.
17. Methyl chloride.
18. Methyl mercaptan.
19. Phosgene.
20. Phosphine.
21. Vinyl chloride.
22. Vinyl fluoride.
23. Vinyl methyl ether.
24. Any gas mixtures of the foregoing.
25. Any gas that contains:
25.1. Bromacetone.
25.2. Cyanogen chloride containing less than 0.9 percent water.
25.3. Diphosgene.
25.4. Ethyldichlorarsine.
25.5. Methyldichlorarsine.
25.6. Nitrogen peroxide (tetroxide).
25.7. Nitrogen tetroxide-nitric oxide mixtures containing up to 33.2 percent weight nitric oxide.
5007.11 Route and time requirements.
Vehicles transporting hazardous materials shall comply with such route and time requirements as the commissioner may promulgate by rule, to the maximum extent possible, to minimize their travel on local, non-arterial roads.
5007.12 Escort requirements for vehicles transporting explosives and fireworks.
Vehicles transporting explosives and fireworks shall additionally comply with the requirements of FC 5007.12.1 and 5007.12.2.
5007.12.1 Vehicles transporting explosives.
Vehicles transporting in or through the city Division 1.1, 1.2, 1.3 or 1.5 explosives requiring the vehicle to be placarded pursuant to DOTn regulations, including vehicles in continuous transit or transporting such explosives on approved routes at approved times, shall be escorted by department firefighting apparatus unless such explosives are transported in a vehicle for which a transportation permit has been issued.
5007.12.2 Vehicles transporting fireworks.
Vehicles transporting fireworks in amounts requiring the vehicle to be placarded pursuant to DOTn regulations, whether in continuous transit through the city or to or from a fireworks display in the city or surrounding waters, shall be escorted by department firefighting apparatus, in accordance with approved routes and times.
Section FC 5101. General
5101.1 Scope.
This chapter shall govern the manufacture, storage, handling and use of combustible Level 1, 2 and 3 aerosol products, including the display of such products in any building, structure or premises.
5101.2 Permits.
Permits shall be required as set forth in FC 105.6.
5101.3 Supervision.
The handling and use of aerosols in quantities requiring a permit shall be performed under the personal supervision of a person holding a certificate of fitness. The storage of aerosols in quantities requiring a permit shall be under the general supervision of a person holding a certificate of fitness.
5101.4 General.
Combustible Level 1, 2 and 3 aerosol products shall be manufactured, stored, handled and used in accordance with this chapter, the construction codes, including the Building Code, and NFPA 30B.
5101.5 Manufacturing prohibited.
It shall be unlawful to manufacture Level 1, 2 or 3 aerosol products.
5101.6 Aerosol container size limitations.
It shall be unlawful to store, handle or use Level 1 or 2 aerosol products in metal cans exceeding 33.8 fluid ounces (1000 ml), or in glass or plastic bottles exceeding 4 fluid ounces (118 ml). Level 3 aerosol products shall be stored, handled and used in containers with a maximum capacity of 24 fluid ounces (708 ml).
Exceptions:
1. Pressurized ether shall be stored, handled or used only in metal containers with a maximum capacity of 8 fluid ounces (236 ml).
2. Level 1, 2 and 3 oven-cleaning aerosol products shall be stored, handled or used in containers with a maximum capacity of 16 fluid ounces (472 ml).
3. Level 1 or 2 aerosol products in plastic containers exceeding 4 fluid ounces (118 ml) but not exceeding 33.8 fluid ounces (1000 ml), and Level 3 aerosol products in plastic containers exceeding 4 fluid ounces (118 ml) but not exceeding 24 fluid ounces (708 ml), that meet one or more of the following conditions:
3.1. Base product has no fire point when tested in accordance with ASTM D 92, and nonflammable propellant.
3.2. Base product has no sustained combustion as tested in accordance with Appendix H, "Method of Testing for Sustained Combustibility in DOTn 49 CFR Part 173."
3.3. Base product contains up to 20 percent by volume (15.8 percent by weight) of ethanol and/or isopropyl alcohol in an aqueous mix, and nonflammable propellant.
3.4. Base product contains 4 percent by weight or less of an emulsified flammable liquefied gas propellant within an aqueous base. The propellant shall remain emulsified for the life of the product. Where such propellant is not permanently emulsified, the propellant shall be nonflammable.
Section FC 5102. Definitions
5102.1 Definitions.
The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.
AEROSOL.
AEROSOL CONTAINER.
AEROSOL WAREHOUSE.
PROPELLANT.
RETAIL DISPLAY AREA.
Section FC 5103. Classification of Aerosol Products
5103.1 Classification levels.
Aerosol products shall be classified as Level 1, 2 or 3 in accordance with FC 5102.1. Aerosol products in cartons which are not identified shall be classified as Level 3.
5103.2 Identification.
Cartons shall be identified on at least one side with the classification level of the aerosol products contained within the carton as follows: LEVEL ________ AEROSOLS.
Section FC 5104. Indoor Storage of Aerosol Products
5104.1 General.
Indoor storage of Level 2 and 3 aerosol products shall comply with the requirements of FC 5104.2 through 5104.7 and NFPA 30B. Level I aerosol products, and Level 1, 2 and 3 aerosol products in plastic containers covered by FC 5101.6 Exception 3, shall be deemed a Class III commodity and shall comply with the requirements for palletized or rack storage set forth in NFPA 13, as modified by FC Appendix B.
5104.2 Storage in buildings with Group A, B, E, F, I and R occupancies.
Except as otherwise provided in FC 5104.2.1, it shall be unlawful to store Level 2 and 3 aerosol products in excess of the following amounts in buildings that house Group A, B, E, F, I and R occupancies:
1. A net weight of 1,000 pounds (454 kg) of Level 2 aerosol products.
2. A net weight of 500 pounds (227 kg) of Level 3 aerosol products.
3. A combined net weight of 1,000 pounds (454 kg) of Level 2 and 3 aerosol products.
5104.2.1 Excess storage.
Level 2 and 3 aerosol products exceeding the maximum quantities set forth in FC 5104.2 may be lawfully stored in accordance with FC 5104.2.1.1 and 5104.2.1.2.
5104.2.1.1 Storage cabinets.
Aerosol products in a quantity not to exceed 100 percent of the maximum storage limitation may be stored in storage cabinets in accordance with FC 5704.3.2.
5104.2.1.2 Storage rooms.
Level 2 and 3 aerosol products in a quantity exceeding that set forth in FC 5104.2 may be lawfully stored indoors in a flammable liquid storage room in accordance with FC 5104.5.
5104.3 Storage in general purpose warehouses.
Storage of aerosol products in general purpose warehouses, as defined in NFPA 30B, utilized only for warehousing-type operations involving mixed commodities shall comply with the requirements of FC 5104.3.1 or 5104.3.2.
5104.3.1 Nonsegregated storage.
Storage consisting of solid pile, palletized or rack storage of Level 2 and 3 aerosol products not segregated into areas utilized exclusively for the storage of aerosols shall comply with the requirements of FC Table 5104.3.1.
FC Table 5104.3.1 Nonsegregated Storage of Level 2 and 3 Aerosol Products in General Purpose Warehouses b
Aerosol Level Maximum Net Weight per Floor (pounds) b Palletized or solid-pile storage Rack storage Unprotected Protected a Unprotected Protected a 2 2,500 12,000 2,500 24,000 3 1,000 12,000 1,000 24,000 Combination 2 and 3 2,500 12,000 2,500 24,000
For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg, 1 square foot = 0.0929 m 2 .
a. Sprinkler system protection and storage arrangements shall comply with the requirements of NFPA 30B. Sprinkler system protection shall extend 20 feet beyond the storage area containing the aerosol products.
b. Storage quantities indicated are the maximum allowed in any 50,000-square-foot area.
5104.3.2 Segregated storage.
Storage of Level 2 and 3 aerosol products segregated into areas utilized exclusively for the storage of aerosols shall be in accordance with FC Table 5104.3.2 and FC 5104.3.2.1 and 5104.3.2.2.
FC Table 5104.3.2 Segregated Storage of Level 2 and 3 Aerosol Products in General Purpose Warehouses
Storage Separation Maximum Segregated Storage Area a Sprinkler Requirements Percentage of building area (percent) Area limitation (square feet) Separation area e, f 15 20,000 Notes b, c Chain-link fence enclosure d 20 20,000 Notes b, c 1-hour fire-resistance-rated interior walls 20 30,000 Note b 2-hour fire-resistance-rated interior walls 25 40,000 Note b 3-hour fire-resistance-rated interior walls 30 50,000 Note b
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m 2 .
a. The maximum segregated storage area shall be limited to the smaller of the two areas resulting from the percentage of building area limitation and the area limitation.
b. Sprinkler system protection in aerosol product storage areas shall comply with the requirements of NFPA 30B and be approved. Other building areas not containing aerosol product storage shall be protected throughout by a sprinkler system in accordance with the construction codes, including the Building Code.
c. Sprinkler system protection in aerosol product storage areas shall comply with the requirements of NFPA 30B and be approved. Sprinkler system protection shall extend a minimum 20 feet beyond the aerosol storage area.
d. Chain-link fence enclosures shall comply with the requirements of FC 5104.3.2.1.
e. A separation area shall be defined as an area extending outward from the periphery of the segregated aerosol product storage area as follows.
1. The limits of the aerosol product storage shall be clearly marked on the floor.
2. The separation distance shall be a minimum of 25 feet and maintained clear of all materials with a commodity classification greater than Class Ill in accordance with NFPA 13, as modified by FC Appendix B.
f. Separation areas shall be allowed when approved.
5104.3.2.1 Chain-link fence enclosures.
Chain-link fence enclosures required by FC Table 5104.3.2 shall comply with the following requirements:
1. The fence shall not be less than No. 9 gauge steel wire, woven into a maximum 2-inch (51-mm) diamond mesh.
2. The fence shall be installed from the floor to the underside of the roof or ceiling above.
3. Class IV and high-hazard commodities shall be stored outside of the aerosol storage area and a minimum of 8 feet (2438 mm) from the fence.
4. Access openings in the fence shall be provided with either self-closing or automatic-closing devices or a labyrinth opening arrangement preventing aerosol containers from rocketing through the access openings.
5. Not less than two means of egress shall be provided from the fenced enclosure.
5104.3.2.2 Aisles.
The minimum aisle requirements for segregated storage in general purpose warehouses shall be in accordance with FC Table 5104.3.2.2.
FC Table 5104.3.2.2 Segregated Storage Aisle Widths and Distance to Aisles in General Purpose Warehouses
Storage Condition Minimum Aisle Width (feet) Maximum Distance from Storage to Aisle (feet) Solid pile or palletized a 4 feet between piles 25 Racks with ESFR sprinklers a 4 feet between racks and adjacent Level 2 and 3 aerosol product storage 25 Racks without ESFR sprinklers a 8 feet between racks and adjacent Level 2 and 3 aerosol product storage 25
For SI: 1 foot = 304.8 mm.
a. Sprinklers shall comply with the requirements of NFPA 30B.
5104.4 Storage in aerosol warehouses.
The total quantity of Level 2 and 3 aerosol products stored in an aerosol warehouse shall not be restricted provided such warehouse complies with the requirements of FC 5104.4.1 through 5104.4.4.
5104.4.1 Sprinkler system.
Aerosol warehouses shall be protected throughout by a wet-pipe sprinkler system in accordance with NFPA 30B. Sprinkler protection shall be designed based on the highest classification level of aerosol product present.
5104.4.2 Pile and palletized storage aisles.
Solid pile and palletized storage shall be arranged so the maximum travel distance to an aisle is 25 feet (7620 mm). Aisles shall have a minimum width of 4 feet (1219 mm).
5104.4.3 Rack storage aisles.
Rack storage shall be arranged with a minimum aisle width of 8 feet (2438 mm) between rows of racks and 8 feet (2438 mm) between racks and adjacent solid pile or palletized storage. Where early suppression fast-response (ESFR) sprinklers provide sprinkler protection, the minimum aisle width shall be 4 feet (1219 mm).
5104.4.4 Combustible commodities.
Combustible commodities, other than flammable and combustible liquids, may be stored in an aerosol warehouse.
Exception: Flammable and combustible liquids in 1-quart (0.95 L) metal containers and smaller may be stored in an aerosol warehouse.
5104.5 Storage in indoor flammable liquid storage rooms.
Indoor flammable liquid storage rooms shall comply with the requirements of FC 5704.3.7. The maximum quantities of aerosol products shall comply with the requirements of FC 5104.5.1 or 5104.5.2.
5104.5.1 Storage rooms of 500 square feet or less.
The storage of aerosol products in flammable liquid storage rooms less than or equal to 500 square feet (46 m 2 ) in area shall not exceed the following quantities:
1. A net weight of 1,000 pounds (454 kg) of Level 2 aerosol products.
2. A net weight of 500 pounds (227 kg) of Level 3 aerosol products.
3. A combined net weight of 1,000 pounds (454 kg) of Level 2 and 3 aerosol products.
5104.5.2 Storage rooms greater than 500 square feet.
The storage of aerosol products in flammable liquid storage rooms greater than 500 square feet (46 m 2 ) in area shall not exceed the following quantities:
1. A net weight of 2,500 pounds (1135 kg) of Level 2 aerosol products.
2. A net weight of 1,000 pounds (454 kg) of Level 3 aerosol products.
3. A combined net weight of 2,500 pounds (1135 kg) of Level 2 and 3 aerosol products. The maximum aggregate storage quantity of Level 2 and 3 aerosol products allowed in separate indoor storage rooms protected by a sprinkler system in accordance with NFPA 30B shall be 5,000 pounds (2270 kg).
5104.6 Storage in liquid warehouses.
The storage of Level 2 and 3 aerosol products in liquid warehouses, as defined in NFPA 30B, shall comply with the requirements of NFPA 30B. The storage shall be located within segregated storage areas in accordance with FC 5104.3.2 and FC 5104.6.1 through 5104.6.3.
5104.6.1 Containment.
Spill control or drainage shall be provided to prevent the flow of liquid to within 8 feet (2438 mm) of the segregated storage area.
5104.6.2 Sprinkler design.
Sprinkler protection shall be designed based on the highest level of aerosol product present.
5104.6.3 Opening protection into segregated storage areas.
Fire doors or gates opening into the segregated storage area shall either be self-closing or provided with automatic-closing devices activated by sprinkler water flow or an approved fire detection system.
5104.7 Storage in Group M occupancies.
Storage of Level 2 and 3 aerosol products in occupancies in Group M shall comply with the requirements of FC Table 5104.7. Retail display shall comply with the requirements of FC 5106.
FC Table 5104.7 Maximum Quantities of Level 2 and 3 Aerosol Products in Retail Storage Areas
Maximum Net Weight Per Floor (pounds) Floor Nonsegregated storage a, b Segregated storage Storage cabinets b Separated from retail area c Basement, cellar or other area below grade Not permitted Not permitted Not permitted Ground floor 2,500 5,000 Note d Upper floors 500 1,000 Note d
For SI: 1 pound = 0.454 kg, 1 square foot = 0.0929 m 2 .
a. The total aggregate quantity on display and in storage shall not exceed the maximum retail display quantity indicated in FC 5106.3.
b. Storage quantities indicated are the maximum allowed in any 50,000-square-foot area.
c. The storage area shall be separated from the retail area with a 1-hour fire-resistance-rated assembly.
d. See FC Table 5104.3.2.
Section FC 5105. Outdoor Storage
5105.1 General.
The outdoor storage of Level 2 and 3 aerosol products, including storage in temporary storage trailers, shall be separated from exposures in accordance with FC Table 5105.1.
FC Table 5105.1 Distance to Exposures for Outdoor Storage of Level 2 and 3 Aerosol Products
Exposure Minimum Distance from Aerosol Storage (feet) a Public streets or private roads 20 Buildings 50 Exit discharge to a public street or private road 50 Lot lines 20 Other outdoor hazardous material storage 50
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. The minimum separation distance indicated is not required where exterior walls having a 2-hour fire-resistance rating without penetrations separate the storage from the exposure. The walls shall extend not less than 30 inches above and to the sides of Level 2 and 3 aerosol products.
Section FC 5106. Retail Display
5106.1 General.
This section shall apply to the retail display of Level 2 and 3 aerosol products.
5106.2 Retail aerosol product displays not exceeding 8 feet high.
Aerosol product displays for retail sale not exceeding 8 feet (2438 mm) in height shall comply with the requirements of FC 5106.2.1 through 5106.2.4.
5106.2.1 Maximum quantity.
Only aerosol products being used for display purposes shall be stored for sale in retail display areas and the total quantity of such aerosol products shall not exceed the amounts set forth in FC Table 5106.2.1.
FC Table 5106.2.1 Maximum Quantities of Level 2 and 3 Aerosol Products in Retail Display Areas
Maximum Net Weight Per Floor (pounds) b Floor Unprotected a Protected in accordance with FC 5106.2 a, c Protected in accordance with FC 5106.3 c Basement, cellar or other area below grade Not allowed 500 500 Ground 2,500 10,000 10,000 Upper 500 2,000 Not allowed
For SI: 1 pound = 0.454 kg, 1 square foot = 0.0929 m 2 .
a. The total quantity shall not exceed 1,000 pounds net weight in any one 100-square-foot retail display area.
b. Per 25,000-square-foot retail display area.
c. Minimum Ordinary Hazard Group 2 wet-pipe sprinkler system throughout the retail sales occupancy.
5106.2.2 Display of containers.
Aerosol containers shall not be stacked more than 6 feet (1829 mm) high from the base of the aerosol array to the top of the aerosol array unless the containers are placed on fixed shelving or otherwise secured in an approved manner. When storage or retail display is on shelves, the height of such storage or retail display to the top of aerosol containers shall not exceed 8 feet (2438 mm) from the floor.
Exception: Storage or display protected in accordance with FC 5106.3.
5106.2.3 Combustible cartons.
Aerosol products located in retail display areas shall be removed from combustible cartons.
Exceptions:
1. Display areas that use a portion of combustible cartons, which consist of only the bottom panel and not more than 2 inches (51 mm) of side panel are allowed.
2. When the display area is protected in accordance with Tables 6.3.2.7(a) through 6.3.2.7(l) of NFPA 30B, storage of aerosol products in combustible cartons is allowed.
5106.2.4 Retail display sprinkler system.
When a sprinkler system is required for the protected retail display of aerosol products, the wet-pipe sprinkler system shall be in accordance with this code, and the construction codes, including the Building Code. The minimum system design shall be for an Ordinary Hazard Group 2 occupancy. The system shall be provided throughout the retail display area.
5106.3 Retail aerosol displays exceeding 8 feet high.
Aerosol product displays for retail sale exceeding 8 feet (2438 mm) in height shall comply with the requirements of FC 5106.3.1 through 5106.3.3.
5106.3.1 Maximum quantity.
Only aerosol products being used for display purposes shall be stored for sale in retail display areas and the total quantity of such aerosol products shall not exceed the amounts set forth in FC Table 5106.2.1.
5106.3.2 Fire protection.
Aerosol displays shall be protected by a sprinkler system in accordance with NFPA 30B and the following requirements:
1. The fire protection required for a retail display of aerosol products shall be determined based on the height of the aerosol products in the display and the type of packaging in which aerosol products displayed more than 6 feet (1829 mm) above the finished floor are stored.
2. Uncartoned Level 2 and 3 aerosols and Level 2 and 3 aerosols in display-cut cartons may be displayed not more than 6 feet (1829 mm) above the finished floor when applying the cartoned aerosol display tables set forth in NFPA 30B.
3. Where sprinkler protection is provided for a Level 2 or 3 aerosol retail display area, such sprinkler system shall be designed to extend coverage to an area not less than 20 feet (6096 mm) in all directions beyond the display area.
4. Where ordinary and high-temperature ceiling sprinkler systems are adjacent to each other, noncombustible draft curtains shall be installed between the areas protected by the respective sprinkler systems.
5106.3.3 Fire separation.
Retail displays of Level 2 and 3 aerosol products shall comply with the following separation distance requirements:
1. Level 2 and 3 aerosol display areas shall be separated from each other by not less than 25 feet (7620 mm).
2. Level 2 and 3 aerosol displays shall be separated from flammable and combustible liquids storage and display areas by one or more of the following measures:
2.1. A horizontal distance of not less than 25 feet (7620 mm).
2.2. A noncombustible partition extending not less than 18 inches (457 mm) above the merchandise. When the aerosol products are located within 25 feet (7620 mm) of flammable or combustible liquids, the noncombustible partition shall be liquid tight at the floor level.
2.3. Special fire protection for double-row racks in accordance with FC 5106.5.
5106.4 Maximum quantities in storage areas.
Aerosol products in storage areas adjacent to retail display areas shall not exceed the quantities in FC Table 5106.4.
FC Table 5106.4 Maximum Storage Quantities for Storage Areas Adjacent to Retail Display of Level 2 and Level 3 Aerosols
Maximum Net Weight Per Floor (pounds) Floor Unseparated a, b Separated Storage cabinets b 1-hour occupancy separation Basement, cellar or other area below grade Not allowed Not allowed Not allowed Ground 2,500 5,000 In accordance with NFPA 30B, Sections 6.3.4.3 and 6.3.4.4 Upper 500 1,000 In accordance with NFPA 30B, Sections 6.3.4.3 and 6.3.4.4
For SI: 1 pound = 0.454 kg, 1 square foot = 0.0929 m 2 .
a. The aggregate quantity in storage and retail display shall not exceed the quantity limits for retail display.
b. In any 50,000-square-foot area.
5106.5 Special protection design for Level 2 and 3 aerosols adjacent to flammable and combustible liquids in double-row racks.
The display of Level 2 and 3 aerosols adjacent to flammable and combustible liquids in double-row racks shall be in accordance with FC 5106.5.1 through 5106.5.8 or FC 5106.3.3.
5106.5.1 Fire protection.
Fire protection for the display of Level 2 and 3 aerosols in double-row racks shall be in accordance with Table 7.4.1 and Figure 7.4.1 of NFPA 30B.
5106.5.2 Cartoned products.
Level 2 and 3 aerosols displayed more than 8 feet (2438 mm) above the finished floor shall be in cartons.
5106.5.3 Shelving.
Shelving in racks shall be limited to wire mesh shelving having uniform openings not more than 6 inches (152 mm) apart, with the openings comprising at least 50 percent of the overall shelf area.
5106.5.4 Aisles.
Racks shall be arranged so that aisles not less than 7 1/2 feet (2286 mm) wide are maintained between rows of racks and adjacent solid-piled or palletized merchandise.
5106.5.5 Flue spaces.
Flue spaces in racks shall comply with the following:
1. Transverse flue spaces – nominal 3-inch (76-mm) transverse flue spaces shall be maintained between merchandise and rack uprights.
2. Longitudinal flue spaces – nominal 6-inch (152-mm) longitudinal flue spaces shall be maintained.
5106.5.6 Horizontal barriers.
Horizontal barriers constructed of minimum 3/8-inch-thick (10-mm-thick) plywood or minimum 0.034-inch (0.086-mm) (No. 22 gauge) sheet metal shall be provided and located in accordance with NFPA 30B when in-rack sprinklers are installed.
5106.5.7 Class I, II, III, IV and plastic commodities.
Class I, II, III, IV and plastic commodities located adjacent to retail Level 2 and 3 aerosol product displays shall be protected in accordance with NFPA 13, as modified by FC Appendix B.
5106.5.8 Flammable and combustible liquids.
Class I, II, IIIA and IIIB Liquids shall be allowed to be located adjacent to Level 2 and 3 aerosol products when the following conditions are met:
1. Class I, II, IIIA and IIIB liquid containers: Containers for Class I, II, IIIA and IIIB liquids shall be limited to 1.06-gallon (4-L) metal-relieving and nonrelieving style containers and 5.3-gallon (20-L) metal-relieving style containers.
2. Fire protection for Class I, II, IIIA and IIIB liquids: Automatic sprinkler protection for Class I, II, IIIA and IIIB liquids shall be in accordance with FC Chapter 57.
Section FC 5301. General
5301.1 Scope.
This chapter shall govern the storage, handling and use of compressed gases in compressed gas containers and systems, including those gases regulated elsewhere in this code.
Exceptions:
1. Compressed gases used as refrigerants in refrigerating systems in accordance with FC Chapter 6.
2. Compressed natural gas (CNG) stored and used on a motor vehicle for motive power in accordance with FC Chapter 23, NFPA 52 and the Fuel Gas Code.
3. Compressed gases connected for use in a fire extinguishing system.
5301.2 Permits.
Permits shall be required as set forth in FC 105.6.
5301.3 General.
Compressed gases shall be stored, handled and used in accordance with this chapter.
5301.3.1 Cutting and welding gases.
Cutting and welding gases shall additionally comply with the requirements of FC Chapter 35.
5301.3.2 Cryogenic fluids.
Cryogenic fluids shall additionally comply with the requirements of FC Chapter 55.
5301.3.3 Hazardous materials.
Compressed gases classified as hazardous materials shall additionally comply with the requirements of FC Chapter 50 and any other applicable chapters of this code, including FC Chapters 58 (Flammable Gases), 60 (Highly Toxic and Toxic Materials), 63 (Oxidizers, Oxidizing Gases and Oxidizing Cryogenic Fluids) and 64 (Pyrophoric Materials), as applicable.
5301.3.4 Liquefied petroleum gas (LPG).
LPG shall additionally comply with the requirements of FC Chapter 61 and the Fuel Gas Code.
5301.4 Supervision.
The storage, handling, use and compression of compressed gases shall be supervised as set forth in FC 5301.4.1 through 5301.4.5.
5301.4.1 Handling and use.
The handling and use of compressed gases in quantities requiring a permit, including piped medical gas systems and the removal of leaking, damaged or corroded compressed gas cylinders from service, shall be under the personal supervision of a person holding a certificate of fitness.
5301.4.2 Storage.
The storage of compressed gases in quantities requiring a permit, including medical gases that are not piped, shall be under the general supervision of a person holding a certificate of fitness.
5301.4.3 Compressing.
The compressing of gases requiring a permit shall be performed by or under the personal supervision of a person holding a certificate of fitness.
Exception: Compressing atmospheric air may be under the general supervision of a person holding a certificate of fitness.
5301.4.4 Filling of containers.
The transfer of nonflammable compressed gases between containers shall be performed by a person holding a certificate of fitness.
5301.4.5 Installation.
The installation of carbon dioxide beverage dispensing systems, including the maintenance and repair of such systems, shall be conducted by or under personal supervision of a person holding a certificate of fitness.
Section FC 5302. Definitions
5302.1 Definitions.
The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.
COMPRESSED GAS.
Nonliquefied compressed gases.
Liquefied compressed gases.
Compressed gases in solution.
Compressed gas mixtures.
COMPRESSED GAS CONTAINER.
COMPRESSED GAS SYSTEM.
HYPERBARIC FACILITY.
NESTING.
TUBE TRAILER.
Section FC 5303. General Requirements
5303.1 Containers.
Compressed gas containers shall comply with the requirements of this section. Compressed gas containers that are not designed for refillable use shall not be refilled after use of the original contents. Compressed gas containers that are partially full or contain residual fumes or vapors shall be considered as full for the purposes of complying with the requirements of this chapter.
5303.1.1 Design and construction.
Compressed gas containers shall be designed, fabricated, tested, marked with the specifications of manufacture and maintained in accordance with Section VIII of the ASME Boiler and Pressure Vessel Code, or the regulations of the United States Department of Transportation, as set forth in 49 CFR Parts 100-180.
5303.1.2 Pressure relief devices.
Pressure relief devices shall be designed in compliance with the requirements of FC 5303.1.2.1 through 5303.1.2.4.
5303.1.2.1 Where required.
Containers and tanks for compressed gas storage shall be provided with pressure relief devices designed in accordance with CGA S-1.1, CGA S-1.2, CGA S-1.3, or Section VIII of the ASME Boiler and Pressure Vessel Code, as applicable, to protect such containers and tanks from rupture in the event of overpressure.
5303.1.2.2 Size.
Pressure relief devices shall be sized in accordance with the specifications to which the container was fabricated and to material-specific requirements, as applicable.
5303.1.2.3 Arrangement.
Pressure relief devices shall be arranged to discharge upward and unobstructed to the open air in such a manner as to prevent any impingement of escaping gas upon the container, adjacent structures or personnel.
Exception: DOTn specification containers having an internal volume of 30 SCF (0.855 m 3 ) or less.
5303.1.2.4 Protection against freezing.
Pressure relief devices shall be designed and installed to prevent moisture from collecting and freezing in a manner that would impair the operation of the device.
5303.2 Marking.
Stationary and portable compressed gas containers and systems shall be marked in compliance with the requirements of FC 5303.2.1 through 5303.2.4.
5303.2.1 Stationary compressed gas containers.
Stationary compressed gas containers shall be marked with the name of the gas in accordance with FC 5003.5 and 5003.6. Markings shall be visible from any direction of approach. All uninsulated stationary outdoor compressed gas containers shall be of light-reflective design or painted with a light-reflecting color.
5303.2.2 Portable containers.
Portable compressed gas containers shall be marked in accordance with CGA C-7 and DOTn regulations.
5303.2.3 Piping systems.
Piping systems shall be marked in accordance with ASME A13.1. Markings used for piping systems shall consist of the name of the contents and include an arrow indicating direction of flow. Markings shall be provided at each valve; at wall, floor or ceiling penetrations; at each change of direction; and at a minimum of every 20 feet (6096 mm) or fraction thereof throughout the piping run.
Exceptions:
1. Piping that is designed or intended to carry more than one compressed gas at various times shall have appropriate signs or markings posted at the manifold, along the piping and at each point of use to provide clear identification and warning.
2. Piping within gas-manufacturing plants, gas-processing plants and similar occupancies shall be marked in an approved manner.
5303.2.4 Out-of-service containers.
Out-of-service compressed gas containers shall be marked to indicate that they are no longer available for service.
5303.3 Container protection.
Compressed gas containers and systems shall be secured and protected against physical damage and tampering in compliance with the requirements of FC 5003.9.2, 5303.3.2 and 5303.3.3.
5303.3.1 Flood hazard.
Stationary compressed gas containers located in areas of special flood hazard or on the premises of Group I-2 occupancies that are hospitals located in shaded X-Zones (as defined in Section G201.2 of Appendix G of the Building Code) shall comply with Section G307.5 of the Building Code.
5303.3.2 Physical protection.
Compressed gas containers and systems that could be exposed to physical damage shall be protected. Posts or other approved means shall be provided to protect compressed gas containers and systems indoors and outdoors from vehicular damage and shall comply with the requirements of FC 312.
5303.3.3 Securing compressed gas containers.
Compressed gas containers shall be secured to prevent movement from contact, vibration or seismic activity, utilizing one or more of the following methods:
1. Securing containers to a fixed object with one or more noncombustible restraints. Containers shall not be secured to plumbing systems or electrical conduits.
2. Securing containers on a cart or other mobile device designed for the movement of compressed gas containers.
3. Nesting of compressed gas containers at container filling or servicing facilities or in seller's warehouses not accessible to the public. Nesting may be used provided the nested containers, if dislodged, do not obstruct any required means of egress.
4. Securing of compressed gas containers to or within a rack, framework, cabinet or similar assembly designed for such use, except when the containers are being inspected, serviced, filled or transported.
5. Securing stationary compressed gas containers to a foundation designed for such use in accordance with the construction codes, including the Building Code.
5303.4 Valve protection.
Compressed gas container valves shall be protected from physical damage by means of protective caps, collars or similar devices, in compliance with the requirements of FC 5303.4.1 and 5303.4.2.
5303.4.1 Compressed gas container protective caps or collars.
Compressed gas containers designed to be fitted with protective caps, collars or other protective devices shall have such caps or devices in place except when the containers are in use or are being serviced or filled.
5303.4.2 Caps and plugs.
Valves of compressed gas containers designed to accept protection caps or other protective devices shall have such caps or devices attached. Outlet caps or plugs shall be in place except when the compressed gas containers are in use or are being serviced or filled.
5303.5 Separation from hazardous conditions.
Compressed gas containers and systems in storage or use shall be separated from materials and conditions that present potential hazards to them, or to which they present potential hazards. Compressed gas containers and systems in storage or use shall be separated in accordance with FC 5303.5.1 through 5303.5.11.
5303.5.1 Incompatible materials.
Compressed gas containers shall be separated from each other based on the hazard class of their contents. Compressed gas containers shall be separated from incompatible materials in accordance with FC 5003.9.8.
5303.5.2 Combustible waste and vegetation.
Combustible waste and vegetation shall be kept a minimum of 10 feet (3048 mm) from compressed gas containers and systems. A noncombustible partition, without openings or penetrations extending not less than 18 inches (457 mm) above the height of the tallest container or system piping and not less than 18 inches (457 mm) to the sides of the storage area is allowed in lieu of such distance. The wall shall either be an independent structure, or the exterior wall of the building adjacent to the storage area.
5303.5.3 Ledges, platforms and elevators.
Compressed gas containers shall not be placed near elevators, unprotected platform ledges or other areas where the container could drop a distance exceeding one-half the height of the container.
5303.5.4 Extreme temperature.
Compressed gas containers, regardless of contents, shall not be exposed to temperatures exceeding 125°F (52°C) or less than mean low atmospheric temperatures unless designed for use under such conditions.
5303.5.5 Falling objects.
Compressed gas containers and systems shall not be placed in areas where they are exposed to damage from falling objects.
5303.5.6 Heating.
Compressed gas containers shall not be heated by devices that could raise the surface temperature of the container to above 125°F (52°C). Heating devices shall comply with the requirements of the Mechanical Code and the Electrical Code. Approved heating methods not capable of producing surface temperatures above 125 ° F (52 ° C) are allowed to be used by trained personnel. Devices designed to maintain individual compressed gas containers at constant temperature shall be approved and shall be designed to be fail-safe.
5303.5.7 Sources of ignition.
Compressed gas containers and tanks shall not be exposed to open flames or high-temperature devices in a manner that could create a hazardous condition.
5303.5.8 Exposure to chemicals.
Compressed gas containers and systems shall not be exposed to corrosive chemicals or fumes that could damage containers, valves or valve-protective caps.
5303.5.9 Exhausted enclosures.
When exhausted enclosures are provided as a means to segregate compressed gas containers from exposure hazards, such enclosures shall comply with the requirements of FC 5003.8.5.
5303.5.10 Gas cabinets.
When gas cabinets are provided as a means to separate compressed gas containers from exposure hazards, such gas cabinets shall comply with the requirements of FC 5003.8.6.
5303.5.11 Tube trailers.
A tube trailer may be used to deliver compressed gas to a stationary compressed gas storage system, or, when approved, may serve as a temporary storage system to supply compressed gas for on-site equipment or operations. Except for the tube trailer's piping system connections, a minimum separation distance of 3 feet (914 mm) shall be maintained in all directions around tube trailers to allow for access, inspection and maintenance. The separation distance between individual tube trailers containing incompatible gases shall be in accordance with FC 5303.5.1.
5303.6 Wiring and equipment.
Electrical wiring and equipment shall comply with the requirements of the Electrical Code. Compressed gas containers and systems shall not be located where they could become part of an electrical circuit. Compressed gas containers and systems shall not be used for electrical grounding.
5303.7 Maintenance and alteration.
Servicing, repairs and other maintenance work or alteration to a valve, pressure-relief device or other compressed gas container or system component shall be performed by competent personnel.
5303.8 Unauthorized use.
Compressed gas containers and systems shall not be used for any purpose other than as a vessel for the materials that they are designed to contain.
5303.9 Exposure to fire.
Compressed gas containers that have been exposed to fire shall be removed from service. Containers so removed shall be handled by qualified persons under the personal supervision of a certificate of fitness holder. Containers exposed to fire shall not be used unless they have been requalified in accordance with the standards set forth in ASME or DOTn regulations, or otherwise approved by the commissioner.
5303.10 Leaks, damage or corrosion.
Leaking, damaged or corroded compressed gas containers shall be removed from service under the personal supervision of a certificate of fitness holder, and properly repaired or disposed.
5303.11 Protection against corrosion.
Except as otherwise provided in this section, compressed gas containers may be stored or used without being placed under overhead cover. Containers shall be protected from direct contact with soil or unimproved surfaces to prevent bottom corrosion. The surface of the area upon which the containers are placed shall be graded to prevent accumulation of water.
5303.12 Overhead cover.
Compressed gas containers in quantities requiring a permit are allowed to be stored or used in the sun except in locations where extreme temperatures prevail. When extreme temperatures prevail, overhead covers shall be provided. Overhead covers shall also be provided to prevent accumulations of ice and snow on the valves of containers connected for use.
5303.13 Lighting.
Areas used for the storage, handling and use of compressed gas containers and systems shall be provided with approved lighting by natural or artificial means.
Section FC 5304. Storage of Compressed Gases
5304.1 Upright storage.
Compressed gas containers, except those designed for use in a horizontal position, and all compressed gas containers containing nonliquefied gases, shall be stored in an upright position with the valve end up. The axis of the container stored in the upright position may be inclined as much as 45 degrees (0.80 rad) from the vertical provided that it is properly secured.
Exception: Compressed gas containers with an internal volume less than 0.174 ft 3 (0.005 m 3 ) may be stored in a horizontal position.
5304.2 Material-specific regulations.
In addition to the requirements of this section, indoor and outdoor storage of compressed gases shall comply with the material-specific requirements of FC Chapters 54, 58 and 60 through 67.
Section FC 5305. Handling and Use of Compressed Gases
5305.1 Compressed gas systems.
Compressed gas systems shall be suitable for the use intended and shall be designed and installed by persons competent in such design and installation. Compressed gas devices and systems shall be listed or approved.
5305.2 Controls.
Compressed gas system controls shall be designed to prevent materials from entering or leaving process or reaction systems at other than the intended time, rate or path. Automatic controls shall be designed to be fail-safe.
5305.3 Piping systems.
Piping, including tubing, valves, fittings and pressure regulators, shall comply with the requirements of this section and FC Chapter 50. Piping, tubing, pressure regulators, valves and other apparatus shall be kept gas tight to prevent leakage. Adequate pressure-relief devices shall be provided where refrigerated liquefied gas can become trapped in the piping.
5305.4 Valves.
Valves utilized on compressed gas systems shall be suitable for the use intended and shall be accessible. Valve handles or operators for required shutoff valves shall not be removed or otherwise altered to prevent access or hinder operation.
5305.5 Venting.
Venting of gases shall be directed to an approved location. Venting shall comply with the requirements of the Mechanical Code.
5305.6 Upright use.
Compressed gas containers, except those designed for use in a horizontal position, and all compressed gas containers containing nonliquefied gases, shall be used in an upright position with the valve end up. The axis of a container being used in an upright position may be inclined as much as 45 degrees (0.80 rad) from the vertical provided that it is properly secured. Use of nonflammable liquefied gases in the inverted position when the compressed gas is in the liquid state shall be allowed provided that the container is properly secured and the dispensing apparatus is designed for such liquefied gas use.
Exception: Compressed gas containers with an internal volume less than 0.174 ft 3 (0.005 m 3 ) may be used in a horizontal position.
5305.7 Transfer.
Transfer of nonflammable compressed gases between containers shall be performed using equipment and operating procedures specified in CGA P-1 and NFPA 99.
5305.8 Use of compressed gas for inflation.
Inflatable equipment, devices or balloons shall be pressurized or filled only with nonflammable gases.
5305.9 Material-specific regulations.
In addition to the requirements of this section, indoor and outdoor use of compressed gases shall comply with the material-specific requirements of FC Chapters 54, 58 and 60 through 67.
5305.10 Handling.
The handling of compressed gas containers shall comply with the requirements of FC 5305.10.1 and 5305.10.2.
5305.10.1 Carts and hand trucks.
Containers shall be moved using an approved method. Where containers are moved by cart, hand truck or other mobile device, such carts, hand trucks or devices shall be designed for the secure movement of containers. Carts and hand trucks utilized for moving compressed gas containers indoors shall comply with the requirements of FC 5003.10. Carts and hand trucks utilized for moving compressed gas containers outdoors shall be designed so that the containers will be secured against dropping or otherwise striking against each other or other surfaces.
5305.10.2 Lifting of containers.
Ropes, chains or slings shall not be used to suspend compressed gas containers unless such containers have been designed for such handling. Valves of compressed gas containers shall not be used for lifting.
Section FC 5306. Medical Gas Storage
5306.1 General.
The storage of compressed gases intended for inhalation or sedation including, but not limited to, analgesics for dentistry, podiatry, veterinary and similar uses at hospitals and other medical facilities shall comply with the requirements of this section in addition to other requirements of this chapter and the Plumbing Code.
5306.2 Storage locations within buildings.
Medical gases shall be stored in areas dedicated to the storage of such gases without other storage or uses. Where containers of medical gases in quantities greater than 1,500 SCF (42.5 m 3 ) per control area are located indoors, they shall be stored in a gas room in accordance with FC 5306.2.1 or a gas cabinet in accordance with FC 5306.2.3. Where gas rooms are located above or below grade, the fire-resistance rating and maximum number of gas rooms shall be in accordance with FC Table 5003.8.3.3. Rooms or areas where medical gases are stored or used in quantities exceeding 6,000 SCF (169.9 m 3 ) shall be designed and constructed in compliance with Building Code requirements for high-hazard occupancies.
5306.2.1 Gas rooms.
A gas room shall be a room separated from the remainder of the building or structure by fire barriers with a fire-resistance rating of not less than 1 hour. Openings between the room and interior spaces shall be protected by self-closing smoke and draft-control assemblies having a fire protection rating of not less than 1 hour. Rooms having an exterior wall shall be provided with at least two vents in such wall, each having not less than 36 square inches (0.023 m 2 ) free area. One vent shall be within 6 inches (152 mm) of the floor and one shall be within 6 inches (152 mm) of the ceiling. Rooms with no exterior wall shall be exhausted through a duct to the outdoors. Supply and exhaust ducts shall be enclosed in a 1-hour-rated shaft enclosure from the room to the outdoors. Approved mechanical ventilation shall comply with the requirements of the Mechanical Code and be provided at a minimum rate of 1 cubic foot per minute per square foot (0.00508 m 3 /s/m 2 ) of the area of the room. Rooms shall be protected by a sprinkler system.
5306.2.2 Reserved.
5306.2.3 Gas cabinets.
Gas cabinets shall be constructed in accordance with FC 5003.8.6 and the following:
1. The average velocity of ventilation at the face of access ports or windows shall not be less than 200 feet per minute (1.02 m/s) with a minimum of 150 feet per minute ( 0.76 m/s) at any point of the access port or window.
2. Connected to an exhaust system.
3. Internally protected by a sprinkler system.
5306.3 Outdoor storage locations.
The storage of oxidizing medical gases located outdoors in quantities greater than the amount requiring a permit shall be located in accordance with FC 6304.2.
5306.4 Medical gas system.
Medical gas system, including containers, distribution piping, supply manifolds, connections, pressure regulators, relief devices, valves, and monitoring and alarm systems shall comply with the requirements of NFPA 99 and this chapter.
5306.5 Hyperbaric facilities.
Hyperbaric facilities shall be designed, installed, operated and maintained in accordance with the construction codes and this section.
5306.5.1 Maintenance.
Hyperbaric chambers and associated medical gas systems shall be inspected, tested and otherwise maintained in accordance with NFPA 99.
5306.5.2 Precaution against electronic devices.
Mobile telephones and other transmitting electronic devices shall not be brought into the hyperbaric facility when the hyperbaric system is in operation, unless the device has been approved or listed for use in a hyperbaric atmosphere.
5306.6 Signage.
A durable sign shall be conspicuously posted at each entrance to any indoor medical gas storage room and any hyperbaric facility, indicating that medical gas is in storage and/or use in the room or facility, and clearly stating all applicable prohibitions and hazards, in accordance with FC 5003.5 and 5003.6.
5306.7 Portable fire extinguishers.
Portable fire extinguishers shall be provided outside of the entrance to any indoor medical gas storage room, including any room in which medical gas containers are manifolded.
Section FC 5307. Carbon Dioxide Beverage Dispensing Systems
5307.1 Scope.
The storage, handling and use in beverage dispensing systems of more than 100 pounds (874 SCF) of carbon dioxide, in low-pressure, liquefied form, shall be in accordance with this section. The storage, handling and use of carbon dioxide in other forms and for other purposes shall be regulated by other applicable provisions of this code and the rules.
5307.2 Permits.
Permits shall be required as set forth in FC 105.6.
5307.3 General.
Carbon dioxide beverage dispensing systems shall be designed, installed, operated and maintained in accordance with this section, the construction codes, the rules, Chapter 13 of NFPA 55, and the equipment manufacturer's instructions.
5307.4 Supervision.
The storage, handling and use of carbon dioxide in carbon beverage dispensing systems shall be supervised as set forth in FC 5307.4.1 and 5307.4.2:
5307.4.1 Installation.
Carbon dioxide beverage dispensing systems shall be installed by a person holding a certificate of fitness.
5307.4.2. Filling of containers.
The filling of a carbon dioxide container from any source shall be performed by a person holding a certificate of fitness.
5307.5 Carbon dioxide detection and alarm systems.
All carbon dioxide beverage dispensing systems shall be equipped with a carbon dioxide detection and alarm system in accordance with the rules. Such a system shall be installed in the room or other area in which the carbon dioxide storage containers are installed and any other room or area in which carbon dioxide could accumulate, and shall activate an alarm in such room or area, outside the entrance to such room or area and such other locations that the department may prescribe by rule.
Exceptions:
1. Any aboveground room or area provided with continuous mechanical ventilation system designed to exhaust carbon dioxide to a safe outdoor location. Such mechanical ventilation shall be designed to operate at a negative pressure in relation to the surrounding area; provide ventilation at a rate of not less than 1 cubic foot per minute per square foot (0.00508 m 3 /(s.m 2 )); and take exhaust from a point within 12 inches (305 mm) of the floor.
2. Any room or area provided with a gas detection system in accordance with FC 908.
5307.6 Operational and Maintenance Requirements.
Carbon dioxide beverage dispensing systems shall be operated and maintained in accordance with the standards set forth in FC 5307.3 and such other requirements as the department may prescribe by rule, including:
1. Warning signs.
2. Periodic inspections of the system.
3. User safety training.
4. Required notifications in the event of a carbon dioxide leak.
5. Filing of affidavit of carbon dioxide beverage dispensing system installation, alteration and repair, and carbon dioxide release.
6. Protected from physical damage.
Section FC 5308. Ethylene Oxide
5308.1 Scope.
This section shall govern the storage, handling and use of gases containing ethylene oxide used for sterilization purposes. The storage, handling and use of gases containing ethylene oxide for purposes other than sterilization shall comply with the other applicable requirements of this chapter. The storage, handling and use of flammable gases containing ethylene oxide shall additionally comply with the requirements of FC Chapter 58.
5308.2 General.
The storage, handling and use of gases containing ethylene oxide used for sterilization purposes shall comply with the other requirements of this chapter, as applicable, and shall additionally be in accordance with this section.
5308.3 Prohibitions.
It shall be unlawful to sterilize pressurized oxygen equipment with gases containing ethylene oxide.
5308.4 Application.
Prior to storing or using gases containing ethylene oxide, or modifying an existing installation or system, the owner shall file with the department an application for the approval of the design and installation of the sterilization system which contains such information and documentation as the commissioner may prescribe.
5308.5 Design and installation requirements.
The design and installation of sterilization systems shall comply with the requirements of FC 5308.5.1 through 5308.5.3.
5308.5.1 Compliance with other codes and standards.
The design and installation of sterilization systems and the storage of gases containing ethylene oxide shall be in accordance with the construction codes, including the Building Code, the Electrical Code, the manufacturer's specifications and the approved testing laboratory that listed the sterilizer.
5308.5.2 Sterilization system room and local area ventilation.
Sterilization systems shall be installed in rooms that are ventilated as follows:
5308.5.2.1 Room ventilation.
Sterilizers shall be installed in a well-ventilated room or other area provided with an independent, nonrecirculating mechanical ventilation system that discharges outdoors. Ventilation supply and exhaust registers shall be located such that there are no stagnant air spaces in the immediate area of the sterilizer and that the direction of air movement is away from the operator.
5308.5.2.2 Local area ventilation.
Where a local ventilation system is required by the regulations of the United States Department of Labor, such ventilation system shall be an independent, dedicated and nonrecirculating system that discharges directly outdoors or to an emission control system and only metallic ductwork impervious to ethylene oxide shall be used. The amount of flexible ducting and the number of elbows in the duct shall be kept to a minimum.
5308.5.3 Vent lines.
Sterilizer vent lines shall be designed and installed in compliance with the following requirements:
1. Each sterilizer shall be equipped with an independent, dedicated and gas-tight vent line for the discharge of gases containing ethylene oxide.
2. Vent lines shall discharge directly outdoors or to an emission control system. Such vent lines shall not discharge into any other ventilation or exhaust system.
3. The piping and the point of discharge for all vent lines discharging outdoors shall be designed and installed to prevent moisture from entering the vent line.
4. Vent lines, including piping, fittings and other components, shall be in accordance with the specifications of the sterilizer manufacturer. Pipe lengths shall not exceed the maximum lengths specified by the manufacturer. Vertical travel distances, elbows, sharp bends and any reduction in vent line size shall be kept to a minimum.
5308.6 Operation and maintenance.
Sterilization systems shall be operated and maintained in compliance with the following requirements:
1. Sterilization systems shall be operated and maintained in compliance with the manufacturer's specifications and the approved testing laboratory listing requirements.
2. Air compressors and their air intakes shall be located such that any gas that may leak from the sterilization system or stored containers will not enter the compressor.
3. Sterilizers shall not be operated if the room ventilation system, local area ventilation system or vent pipe is not operational.
5308.7 Emergency plan.
Where required by the regulations of the United States Department of Labor, a written emergency plan to be implemented in the event of an ethylene oxide spill or leak shall be prepared, shall be maintained on the premises and made available for inspection by any representative of the department.
5308.8 Recordkeeping.
A copy of the manufacturer's instructions for the installation, operation and maintenance of the sterilizer shall be maintained in the room or other area in which the sterilization system is located.
Section FC 5309. Compressed Gases Not Otherwise Regulated
5309.1 General.
Compressed gases in storage or use not regulated by the material-specific provisions of FC Chapters 6, 54, 58 and 60 through 67, including asphyxiant, irritant and radioactive gases, shall comply with the requirements of this section in addition to other applicable requirements of this chapter.
5309.2 Ventilation.
Indoor storage and use areas and storage buildings shall be provided with mechanical exhaust ventilation or natural ventilation in accordance with FC 5004.3 or 5005.1.9. Mechanical exhaust ventilation shall be provided where required by FC 5005.2.1.1 or 5005.2.2.2. When mechanical ventilation is provided, the systems shall be operational during such time as the building or space is occupied.
Section FC 5401. General
5401.1 Scope.
This chapter shall govern the storage, handling and use of corrosive materials.
Exceptions:
1. Display and storage in Group M and storage in Group S occupancies complying with the requirements of FC 5003.11.
2. Stationary energy storage systems in accordance with FC 608.
3. Ammonia (R-717) when used as a refrigerant in a refrigerating system in accordance with FC 606.
5401.2 Permits.
Permits shall be required as set forth in FC 105.6.
5401.3 General.
Corrosive materials shall be stored, handled and used in accordance with this chapter. Corrosive materials that are compressed gases shall additionally comply with the requirements of FC Chapter 53.
5401.4 Supervision.
The handling and use of corrosive materials in quantities requiring a permit shall be under the personal supervision of a certificate of fitness holder. The storage of corrosive materials in quantities requiring a permit shall be under the general supervision of a certificate of fitness holder.
Section FC 5402. Definitions
5402.1 Definition.
The following term shall, for the purposes of this chapter and as used elsewhere in this code, have the meaning set forth in FC 202.
CORROSIVE MATERIAL.
Section FC 5403. General Requirements
5403.1 Quantities not exceeding the maximum allowable quantity per control area.
The storage, handling and use of corrosive materials in amounts not exceeding the maximum allowable quantity per control area indicated in FC 5003.1 shall be in accordance with FC 5001, 5003 and 5401.
5403.2 Quantities exceeding the maximum allowable quantity per control area.
The storage, handling and use of corrosive materials in amounts exceeding the maximum allowable quantity per control area indicated in FC 5003.1 shall be in accordance with this chapter and FC Chapter 50.
Section FC 5404. Storage
5404.1 Indoor storage.
Indoor storage of corrosive materials in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(2), shall be in accordance with FC 5001, 5003, 5004 and this chapter.
5404.1.1 Liquid-tight floor.
In addition to the provisions of FC 5004.12, floors in storage areas for corrosive liquids shall be of liquid-tight construction.
5404.2 Outdoor storage.
Outdoor storage of corrosive materials in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(4) shall be in accordance with FC 5001, 5003, 5004 and this chapter.
5404.2.1 Aboveground outdoor storage tanks.
Aboveground outdoor storage tanks exceeding an aggregate quantity of 1,000 gallons (3785 L) of corrosive liquids shall be provided with secondary containment in accordance with FC 5004.2.2.
5404.2.2 Distance from storage to exposures.
Outdoor storage of corrosive materials shall not be within 20 feet (6096 mm) of buildings not associated with the manufacturing or distribution of such materials, lot lines, public streets, private roads or means of egress. A 2-hour fire barrier wall without openings or penetrations, and extending not less than 30 inches (762 mm) above and to the sides of the storage area, is allowed in lieu of such distance. The wall shall either be an independent structure, or the exterior wall of the building adjacent to the storage area.
Section FC 5405. Handling and Use
5405.1 Indoor use.
The indoor handling and use of corrosive materials in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(2) shall be in accordance with FC 5001, 5003, 5005 and this chapter.
5405.1.1 Liquid transfer.
Corrosive liquids shall be transferred in accordance with FC 5005.1.10.
5405.1.2 Ventilation.
When corrosive materials are dispensed or used, mechanical exhaust ventilation in accordance with FC 5005.2.1.1 shall be provided.
5405.2 Outdoor use.
The outdoor handling and use of corrosive materials in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(4) shall be in accordance with FC 5001, 5003, 5005 and this chapter.
5405.2.1 Distance from use to exposures.
Outdoor handling and use of corrosive materials shall be located in accordance with FC 5404.2.2.
Section FC 5501. General
5501.1 Scope.
This chapter shall govern the storage, handling and use of cryogenic fluids.
Exception: Fluids used as refrigerants in refrigerating systems (see FC 606).
5501.2 Permits.
Permits shall be required as set forth in FC 105.6.
5501.3 General.
Cryogenic fluids shall be stored, handled and used in accordance with this chapter, except that liquefied natural gas (LNG) shall comply with the requirements of FC 5506 only. Containers that contain any amount of cryogenic fluid, including containers that are partially full or have residual gas, shall be considered as full for the purposes of the requirements of this chapter.
5501.3.1 Oxidizing cryogenic fluids.
Oxidizing cryogenic fluids, including oxygen, shall additionally comply with the requirements of NFPA 55 and FC Chapter 63, as applicable.
5501.3.2 Flammable cryogenic fluids.
Flammable cryogenic fluids, including hydrogen, methane and carbon monoxide, shall additionally comply with the requirements of NFPA 55 and FC Chapter 58, as applicable.
5501.3.3 Inert cryogenic fluids.
Inert cryogenic fluids, including argon, helium and nitrogen, shall additionally comply with the requirements of CGA P-18.
5501.4 Supervision.
The storage, handling and use of cryogenic fluids shall be supervised as set forth in FC 5501.4.1 through 5501.4.3.
5501.4.1 Handling and use.
Handling and use of cryogenic fluid in quantities requiring a permit shall be performed under the personal supervision of a person holding a certificate of fitness.
5501.4.2 Installation and maintenance.
The installation and maintenance of cryogenic containers and of systems containing cryogenic fluids, including the repair of such systems, shall be conducted under the personal supervision of a person holding a certificate of fitness.
5501.4.3 Storage.
Storage of cryogenic fluids in quantities requiring a permit shall be under the general supervision of a person holding a certificate of fitness.
5501.5 Prohibition.
It shall be unlawful to fill a container with a flammable cryogenic fluid except for containers mounted on a hydrogen-powered motor vehicle and used for motive power as authorized by FC 2309.1.1(1).
Section FC 5502. Definitions
5502.1 Definitions.
The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.
CRYOGENIC CONTAINER.
CRYOGENIC FLUID.
FLAMMABLE CRYOGENIC FLUID.
LOW-PRESSURE CONTAINER.
MAXIMUM ALLOWABLE WORKING PRESSURE (MAWP).
Section FC 5503. General Requirements
5503.1 Cryogenic container.
Cryogenic containers shall comply with the requirements of FC 5503.1.1 through 5503.1.3.3 and FC Chapter 50.
5503.1.1 Cryogenic container standards.
Cryogenic containers shall be designed, constructed, operated and maintained in accordance with the ASME Boiler and Pressure Vessel Code or United States Department of Transportation regulations, or as otherwise approved.
5503.1.1.1 Pressure gauges.
Cryogenic containers shall be provided with pressure gauges. The maximum face reading for dial-type gauges shall not be less than 133 percent nor more than 250 percent of the MAWP of the cryogenic container.
5503.1.1.2 Liquid level-indicating devices.
Cryogenic containers shall be provided with a liquid level-indicating device. It shall be unlawful to use cryogenic containers with glass liquid level gauges in direct contact with the contents of such containers.
5503.1.2 Flood hazard.
Stationary cryogenic containers located in areas of special flood hazard or on the premises of Group I-2 occupancies that are hospitals in shaded X-Zones (as defined in Section G201.2 of Appendix G of the Building Code) shall comply with Section G307.5 of the Building Code.
5503.1.3 Foundations and supports.
Cryogenic containers shall be installed upon substantial concrete or masonry foundations or structural steel supports on firm concrete or masonry foundations. Cryogenic containers shall be supported to prevent the concentration of excessive loads on the supporting portion of the shell. Foundations for horizontal cryogenic containers shall be constructed to accommodate expansion and contraction of the cryogenic container. Foundations shall be provided to support the weight of vaporizers and heat exchangers.
5503.1.3.1 Temperature effects.
When cryogenic container foundations or supports are subject to exposure to temperatures below -130°F (-89.9°C), the foundations or supports shall be constructed of materials to withstand the low-temperature effects of cryogenic fluid spillage.
5503.1.3.2 Corrosion protection.
Portions of cryogenic containers in contact with foundations or saddles shall be painted to protect against corrosion. Precautions shall be taken to avoid or minimize corrosion due to galvanic action.
5503.1.3.3 Fill connection supports.
Fill connection supports shall be designed and maintained to withstand the repeated application of force required to connect and disconnect hoses of cargo tanks.
5503.2 Pressure relief devices.
Pressure relief devices shall be provided in accordance with FC 5503.2.1 through 5503.2.6 to protect cryogenic containers and systems containing cryogenic fluids from rupture in the event of overpressure. Pressure relief devices shall be designed in accordance with CGA S-1.1, CGA S-1.2 and CGA S-1.3.
5503.2.1 Cryogenic containers.
Cryogenic containers shall be provided with pressure relief devices. Precautions shall be taken to prevent overpressurization of atmospheric tanks. Such pressure relief devices shall communicate with the vapor space of the container, not the cryogenic fluid.
5503.2.2 Equipment other than cryogenic containers.
Heat exchangers, vaporizers, insulation casings surrounding cryogenic containers, and sections of coaxial or single wall piping systems in which liquefied cryogenic fluids could be trapped because of leakage from cryogenic containers or isolation by valves shall be provided with pressure relief devices.
5503.2.3 Sizing.
Pressure relief devices shall be sized in accordance with the specifications to which the cryogenic container was fabricated. The relief devices shall have sufficient capacity to prevent the MAWP of the cryogenic container or system from being exceeded. It shall be unlawful to use pressure relief devices that are not clearly marked by the manufacturer with their set pressure.
5503.2.4 Accessibility.
Pressure relief devices shall be located such that they are readily accessible for inspection, repair and other maintenance.
5503.2.5 Arrangement.
Pressure relief devices shall be arranged to discharge unobstructed, at rated capacity, to the outdoors in such a manner as to prevent escaping gas from impinging on personnel, cryogenic containers, equipment and adjacent structures or from entering enclosed spaces.
Exception: United States Department of Transportation specification cryogenic containers with an internal volume of 2 cubic feet (0.057 m 3 ) or less.
5503.2.6 Shutoffs between pressure relief devices and cryogenic containers.
Shutoff valves shall not be installed between pressure relief devices and cryogenic containers.
Exception: A shutoff valve is allowed on cryogenic containers equipped with multiple pressure-relief device installations where the design and arrangement of the valves provide sufficient relief capacity for the pressure relief devices to prevent the MAWP of the cryogenic container or system from being exceeded at all times.
5503.3 Pressure-relief vent piping.
Pressure-relief vent-piping systems shall be constructed and arranged so as to remain functional and direct the flow of gas to a safe location in accordance with FC 5503.3.1 and 5503.3.2.
5503.3.1 Sizing.
Pressure-relief-device vent piping shall have a cross-sectional area not less than that of the pressure-relief-device vent opening and shall be arranged so as not to restrict the flow of escaping gas.
5503.3.2 Arrangement.
Pressure-relief-device vent piping and drains in vent lines shall be arranged so that escaping gas will discharge unobstructed to the outdoors and not impinge on personnel, containers, equipment, foundations and adjacent structures or enter enclosed spaces. Pressure-relief-device vent lines shall be installed in such a manner to exclude or remove moisture and condensation and prevent malfunction of the pressure relief device because of freezing or ice accumulation or other types of obstruction.
5503.4 Marking.
Cryogenic containers and systems shall be marked in accordance with FC 5503.4.1 through 5503.4.6.
5503.4.1 Identification signs.
Visible hazard identification signs in accordance with NFPA 704 shall be provided at entrances to areas in which cryogenic fluids are stored, handled or used.
5503.4.2 Identification of contents.
Stationary and portable cryogenic containers shall be clearly marked with the name of the cryogenic fluid contained therein. Stationary aboveground cryogenic containers shall be placarded in accordance with FC 5003.5 and 5003.6. Portable cryogenic containers shall be identified in accordance with CGA C-7.
5503.4.3 Identification of cryogenic containers.
Stationary cryogenic containers shall be identified with a permanent nameplate indicating the manufacturing specification and MAWP. The nameplate shall be installed on the cryogenic container in an accessible location. The nameplate shall be marked in accordance with the ASME Boiler and Pressure Vessel Code or the regulations of the United States Department of Transportation, as set forth in 49 CFR Parts 100-180.
5503.4.4 Identification of cryogenic container connections.
Cryogenic container inlet and outlet connections, liquid level indicating devices, liquid level limit controls, valves, pressure gauges, regulators, and safety devices shall be marked with a permanent tag or label identifying their function or identified by a schematic drawing designating their function and whether they are connected to the vapor or liquid space of the cryogenic container. Where a schematic drawing is provided, it shall be permanently attached to the cryogenic container and maintained in a legible condition.
5503.4.5 Identification of piping systems.
Piping systems shall be identified in accordance with FC 5303.2.3.
5503.4.6 Identification of emergency shutoff valves.
Emergency shutoff valves shall be identified by posting a durable sign at a conspicuous location at or near the valve.
5503.5 Container protection.
Cryogenic containers and systems shall be secured and protected against physical damage and tampering in accordance with FC 5003.9.2, and FC 5503.5.2 through 5503.5.4.
5503.5.1 Reserved.
5503.5.2 Securing of cryogenic containers.
Stationary containers shall be secured to foundations in accordance with the Building Code. Portable cryogenic containers shall be secured to prevent movement from contact, vibration or seismic activity. Nesting shall be an acceptable means of securing cryogenic containers. Cryogenic containers shall not be secured to plumbing pipes or electrical conduits.
5503.5.3 Securing of vaporizers.
Vaporizers, heat exchangers and similar equipment shall be anchored to a suitable foundation. Connecting piping shall be sufficiently flexible to provide for the effects of expansion and contraction due to temperature changes.
5503.5.4 Physical protection.
Cryogenic containers, piping, valves, pressure relief devices, regulating equipment and other appurtenances which could be exposed to physical damage and tampering shall be protected by posts or other approved means.
5503.6 Electrical wiring and equipment.
Electrical wiring and equipment shall comply with the requirements of the Electrical Code and FC 5503.6.1 and 5503.6.2.
5503.6.1 Location.
Cryogenic containers and systems shall not be located where they could become part of an electrical circuit.
5503.6.2 Electrical grounding and bonding.
Cryogenic containers and systems shall not be used for electrical grounding. When electrical grounding and bonding is required, the grounding and bonding system shall comply with the requirements of the Electrical Code. The grounding system shall be protected against corrosion, including corrosion caused by stray electric currents or galvanic action.
5503.7 Service and repair.
Service, repair, modification or removal of valves, pressure relief devices or other cryogenic container appurtenances, shall comply with the requirements of FC 5503.7.1 and 5503.7.2 and the ASME Boiler and Pressure Vessel Code, Section VIII or the regulations of the United States Department of Transportation, as set forth in 49 CFR Parts 100-180, as applicable.
5503.7.1 Cryogenic containers.
Cryogenic containers that have been removed from service shall be repaired or disposed of lawfully.
5503.7.2 System inspection.
Cryogenic containers and systems shall be inspected by competent personnel at least once a month.
5503.8 Unauthorized use.
Cryogenic containers shall not be used for any purpose other than as a container for the product that it is designed to contain.
5503.9 Leaks, damage and corrosion.
Leaking, damaged or corroded cryogenic containers shall be immediately removed from service. Leaking, damaged or corroded systems shall be replaced, repaired or disposed of lawfully in accordance with FC 5503.7.
5503.10 Lighting.
Lighting shall be provided for equipment such as control valves, gauges, regulators, vaporizers and heat exchangers and operating facilities such as walkways and gates ancillary to stationary cryogenic container installations.
Section FC 5504. Storage
5504.1 General.
Storage of cryogenic containers shall be in accordance with this section.
5504.2 Indoor storage.
Indoor storage of cryogenic containers shall be in accordance with FC 5504.2.1 through 5504.2.1.3.
5504.2.1 Cryogenic containers.
Cryogenic containers shall be installed in accordance with the provisions applicable to the type of cryogenic fluid stored and this section.
5504.2.1.1 Cryogenic containers.
Cryogenic containers shall be in accordance with FC 5503.1.
5504.2.1.2 Construction of indoor areas.
Cryogenic containers stored indoors shall be located in buildings, rooms or areas constructed in accordance with the Building Code.
5504.2.1.3 Ventilation.
Storage areas for cryogenic containers shall be ventilated in accordance with the Mechanical Code.
5504.3 Outdoor cryogenic storage.
Outdoor storage of cryogenic containers shall be in accordance with FC 5504.3.1 through 5504.3.1.2.5.
5504.3.1 Separation from hazardous conditions.
Cryogenic containers and systems in storage or use shall be separated from materials and conditions which pose exposure hazards to or from each other in accordance with FC 5504.3.1.1 through 5504.3.1.1.5.
5504.3.1.1 Stationary cryogenic containers.
Stationary cryogenic containers shall be separated from exposure hazards in accordance with the minimum separation distances set forth in FC Table 5504.3.1.1.
FC Table 5504.3.1.1 Separation of Stationary Cryogenic Containers from Exposure Hazards
Exposure Minimum Distance (feet) Buildings, regardless of construction type 1, or minimum required for service access Building exit 10 Building openings other than building exits 1 Air intakes 10 Lot lines 5 Group A occupancies and other public gathering places 50 Nonambulatory patient areas 50 Combustible waste or vegetation 15 Other hazardous materials In accordance with FC Chapter 50
For SI: 1 foot = 304.8 mm.
5504.3.1.1.1 Point-of-fill connections.
Fill connections for stationary cryogenic containers shall not be positioned closer to exposure hazards than the minimum distances required for stationary cryogenic containers. Fill connections for stationary cryogenic containers shall be located and maintained to afford cargo tank operator access to valves and indicators on the cryogenic containers and cargo tank.
5504.3.1.1.2 Surfaces beneath cryogenic containers.
The surface of the area on which stationary cryogenic containers are placed, including the surface of the area located below the point where connections are made for the purpose of filling such cryogenic containers, shall be compatible with the cryogenic fluid in the cryogenic container. The surface shall be capable of withstanding temperatures of cryogenic fluid that may be released during normal filling operations, without cracking, shifting or other impact upon the stability of the installation.
5504.3.1.1.3 Location.
Containers of cryogenic fluids shall not be stored or used within diked areas containing other hazardous materials.
5504.3.1.1.3.1 Prohibited locations.
It shall be unlawful to install stationary cryogenic containers on the roof of any building or structure.
5504.3.1.1.4 Areas subject to flooding.
Stationary cryogenic containers, vaporizers, heat exchangers and connecting piping located in areas subject to flooding shall be securely anchored or elevated to prevent separation of the cryogenic containers and related equipment from foundations or supports.
5504.3.1.1.5 Drainage.
The area surrounding stationary cryogenic containers shall be provided with a means to prevent accidental discharge of cryogenic fluid from endangering personnel, cryogenic containers, equipment and adjacent structures or to enter enclosed spaces. The stationary cryogenic container shall not be placed where spilled or discharged fluid will be retained around the cryogenic container.
Exception: These drainage requirements shall not apply when it is determined by the commissioner that the cryogenic container does not constitute a hazard, upon consideration of special features such as crushed rock utilized as a heat sink, topographical conditions, nature of occupancy, proximity to structures on the same or adjacent property, and the capacity and construction of cryogenic containers and character of cryogenic fluid to be stored.
5504.3.1.2 Portable cryogenic containers.
Outdoor storage of portable cryogenic containers shall comply with the requirements of FC 5503 and this section.
5504.3.1.2.1 Exposure hazard separation.
Portable cryogenic containers shall be separated from exposure hazards in accordance with FC Table 5504.3.1.2.1.
FC Table 5504.3.1.2.1 Separation of Portable Cryogenic Containers from Exposure Hazards
Exposure Minimum Distance (feet) Building exits 10 Building openings other than building exits 1 Air intakes 10 Lot lines 5 Combustible waste or vegetation 15 Other hazardous materials In accordance with FC Chapter 50
For SI: 1 foot = 304.8 mm.
5504.3.1.2.2 Surfaces beneath cryogenic containers.
Cryogenic containers shall be placed on surfaces that are compatible with the cryogenic fluid in the cryogenic container.
5504.3.1.2.3 Drainage.
The area surrounding portable cryogenic containers shall be provided with a means to prevent accidental discharge of fluids from endangering adjacent containers, buildings, equipment or adjoining property.
Exception: These requirements shall not apply when it is determined by the commissioner that the cryogenic container does not constitute a hazard.
5504.3.1.2.4 Areas subject to flooding.
Portable cryogenic containers located in areas subject to flooding shall be properly secured to prevent movement.
5504.3.1.2.5 Pressure relief valve discharge.
Cryogenic containers shall be positioned such that the pressure relief valve discharge is directed away from any building exit.
Section FC 5505. Handling and Use
5505.1 Applicability.
Handling and use of cryogenic containers and systems shall be in accordance with this section.
5505.1.1 Cryogenic fluid systems.
Cryogenic systems shall be suitable for the use intended and designed by persons competent in such design. Equipment and processes shall be listed or approved.
5505.1.2 Piping systems.
Piping, tubing, valves, joints and fittings used in cryogenic systems shall be designed and installed in accordance with the material-specific provisions of FC 5501.3.1, 5501.3.2, 5501.3.3 and 5505.1.2.1 through 5505.1.2.6.
5505.1.2.1 Design and construction.
Piping systems shall be suitable for the use intended through the full range of pressure and temperature to which they will be subjected. Piping systems shall be designed and constructed to provide adequate allowance for expansion, contraction, vibration, settlement and fire exposure.
5505.1.2.2 Joints.
Joints on cryogenic container piping and tubing shall be threaded, welded, silver brazed or flanged.
5505.1.2.3 Valves and piping components.
Valves and piping components shall be suitable for the intended use at the temperatures of the application and shall be designed and constructed to withstand the maximum pressure at the minimum temperature to which they will be subjected. Valves shall be oriented so that the stem is above the horizontal plane and discharge is directed away from supporting elements.
5505.1.2.3.1 Shutoff valves on cryogenic containers.
Shutoff valves shall be provided on all cryogenic container connections except for pressure relief devices. Shutoff valves shall be readily accessible and located as close as practical to the cryogenic container. Manually-operated shutoff valves shall be designed and installed to minimize accidental opening and closing.
Exception: Valves before pressure relief devices shall be installed in accordance with FC 5503.2.6.
5505.1.2.3.2 Shutoff valves on piping.
Shutoff valves shall be installed in piping containing cryogenic fluids where needed to limit the volume of liquid discharged in the event of piping or equipment failure. Pressure relief valves shall be installed on all sections of piping systems where liquid is capable of being trapped (see FC 5503.2). Shutoff valves shall be installed so that piping components can be isolated for maintenance. Check valves shall be installed on discharge lines where pumps or other pressure-increasing equipment operate in parallel.
5505.1.2.4 Physical protection and support.
Piping systems shall be supported and protected from physical damage. Piping passing through floors or walls shall be protected from damage caused by movement of the floors or walls.
5505.1.2.5 Corrosion protection.
Aboveground piping that is subject to corrosion because of exposure to corrosive atmospheres, shall be constructed of materials to resist the corrosive environment or otherwise protected against corrosion. Underground piping shall be protected against corrosion.
5505.1.2.6 Testing.
Piping systems shall be tested and proven free of leaks after installation as required by the standards to which they were designed and constructed. Test pressures shall not be less than 150 percent of the MAWP when hydraulic testing is conducted or 110 percent when testing is conducted pneumatically.
5505.2 Indoor use.
Indoor use of cryogenic fluids shall comply with the material-specific requirements of FC 5501.3.1 through 5501.3.3.
5505.3 Outdoor use.
Outdoor use of cryogenic fluids shall comply with the material specific requirements of FC 5501.3.1, 5501.3.2, 5501.3.3, 5505.3.1 and 5505.3.2.
5505.3.1 Separation.
Distances from property lines, buildings and exposure hazards shall comply with the requirements of FC 5504.3 and the material specific requirements of FC 5501.3.1 through 5501.3.3.
5505.3.2 Emergency shutoff valves.
Approved manual or automatic emergency shutoff valves shall be provided to shut off the cryogenic fluid supply in case of emergency. An emergency shutoff valve shall be located at the source of supply and at the point where the system enters the building.
5505.4 Filling and dispensing.
Filling and dispensing of cryogenic fluids shall comply with the requirements of FC 5505.4.1 through 5505.4.4.
5505.4.1 Dispensing areas.
Dispensing of cryogenic fluids shall be conducted in approved locations. Dispensing indoors shall be conducted in areas constructed in accordance with the construction codes, including the Building Code.
5505.4.1.1 Ventilation.
Indoor areas where cryogenic fluids are dispensed shall be ventilated in accordance with the Mechanical Code in a manner that captures any vapor at the point of generation.
5505.4.1.1.1 Alarms.
Oxygen sensors equipped with an audible alarm shall be provided in dispensing areas to continuously monitor the level of oxygen in the area. The alarm shall actuate when oxygen concentration drops below 19.5 percent.
5505.4.1.2 Piping systems.
Piping systems utilized for filling or dispensing of cryogenic fluids shall be designed and constructed in accordance with FC 5505.1.2.
5505.4.2 Vehicle loading and unloading areas.
Loading or unloading areas shall be designed and maintained in accordance with the standards referenced in FC 5501.3.1 through 5501.3.3. Loading and unloading areas shall additionally comply with the requirements of FC 5504.3.1 through 5504.3.1.2.5 and shall be capable of withstanding the weight of the fully loaded cargo tank.
5505.4.2.1 Vehicle loading and unloading operations.
Vehicle loading and unloading operations shall be conducted in an approved manner in accordance with the standards referenced in FC 5501.3.1 through 5501.3.3.
5505.4.3 Limit procedures.
Limit procedures shall be established to prevent overfilling of stationary cryogenic containers during filling operations.
5505.4.4 Prohibited filling of flammable cryogenic fluid.
It shall be unlawful to fill cryogenic containers with flammable cryogenic fluid.
5505.5 Handling.
Handling of cryogenic containers shall be in accordance with this section.
5505.5.1 Carts and hand trucks.
Cryogenic containers shall be moved using an approved method. Where cryogenic containers are moved by cart, hand truck or other mobile device, such carts, hand trucks or devices shall be designed for the secure movement of containers, including a means of restraining the containers.
5505.5.2 Closed cryogenic containers.
Pressurized portable cryogenic containers shall be moved with all operable valves in a closed position. Cryogenic containers designed for use at atmospheric conditions shall be moved with appropriate loose fitting covers in place to prevent spillage.
5505.5.3 Stationary cryogenic containers.
Stationary cryogenic containers shall not be moved while containing cryogenic fluid. Handling of cryogenic containers shall be in accordance with the manufacturer's instructions.
Section FC 5506. LNG Installations and Facilities
5506.1 New LNG installations and facilities.
It shall be unlawful to construct any new LNG installation or facility. It shall be unlawful to operate any LNG installation or facility that was not lawfully existing on the effective date of this code.
5506.2 Existing LNG installations and facilities.
LNG installations and facilities lawfully existing on the effective date of this code shall be designed, installed, operated and maintained in accordance with this code, the rules and the regulations of the United States Department of Transportation, as set forth in 49 CFR Part 193, except as otherwise provided in FC 102.3, 102.4 and 102.5.
5506.2.1 Out-of-service LNG storage tanks.
Notwithstanding any other provision of law, rule or regulation, any storage tank erected prior to the effective date of this code which has not been used for the storage of liquefied natural gas for a period in excess of 2 years from the date of completion of the construction of the tank structure shall be recertified by the various city agencies in the same manner as if filing design and installation documents of a new tank before a certificate of occupancy be issued if the tank is to be placed in service.