BetaNYCLaw Reader
Contents
  1. Home
  2. NYC Administrative Code
  3. Title 29
  4. Chapter 2
  5. Part 10 of 15
  6. Section FC 5105

NYC Administrative Code Section FC 5105 Outdoor Storage

5105.1 General.

The outdoor storage of Level 2 and 3 aerosol products, including storage in temporary storage trailers, shall be separated from exposures in accordance with FC Table 5105.1.

FC Table 5105.1 Distance to Exposures for Outdoor Storage of Level 2 and 3 Aerosol Products

Exposure Minimum Distance from Aerosol Storage (feet) a Public streets or private roads 20 Buildings 50 Exit discharge to a public street or private road 50 Lot lines 20 Other outdoor hazardous material storage 50

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

a. The minimum separation distance indicated is not required where exterior walls having a 2-hour fire-resistance rating without penetrations separate the storage from the exposure. The walls shall extend not less than 30 inches above and to the sides of Level 2 and 3 aerosol products.