NYC Administrative Code Title 29, Chapter 2 New York City Fire Code, part 14 of 15

Section FC 6109 to Section FC A05: 44 sections.

Section FC 6109. Storage of Portable LPG Containers

Open this section

6109.1 General.

Storage of portable LPG containers shall comply with the requirements of FC 6109.2 through 6109.14, and shall be approved by the commissioner.

Exceptions:

1. Containers that have not previously contained LPG.

2. Containers stored for use at construction sites.

6109.2 Exposure hazards.

Containers in storage shall be stored in locations that minimize exposure to physical damage, tampering or excessive temperature rise.

6109.3 Position.

Containers in storage having individual capacity greater than 1 pound (0.454 kg) of LPG shall be positioned with the pressure relief valve in direct communication with the vapor space of the container.

6109.4 Separation from means of egress.

Containers shall not be stored or left unattended near exit access doors, exits, stairways, exit discharge areas, or other areas designed or used as a means of egress.

6109.5 Quantity.

Empty containers that have been in LPG service shall be considered as full containers for the purpose of determining the maximum quantities of LPG allowed in FC 6109.9 and 6109.11.

6109.6 Storage on roofs.

Containers shall not be stored, or connected for use in a stationary LPG installation, on the roof of any building or structure.

6109.7 Storage in basement, pit or other area below grade.

LPG containers shall not be stored in a cellar, basement, pit or other area below grade.

6109.8 Protection of valves on containers in storage.

Container valves shall be protected by screw-on-type caps or collars which shall be securely in place on all containers stored regardless of whether they are full, partially full or empty. Container outlet valves shall be closed.

6109.9 Storage within buildings accessible to the public.

LPG containers constructed in accordance with the United States Department of Transportation (DOTn) specifications with a maximum capacity of 16.4 ounces (0.465 kg) of LPG used in completely self-contained hand torches and similar devices are allowed to be stored for sale or displayed in a building accessible to the public. Buildings shall be protected by a sprinkler system in storage and display areas when quantities exceed permit amounts. The quantity of LPG shall not exceed 200 pounds (91 kg).

6109.10 Storage within buildings not accessible to the public.

The quantity of LPG containers allowed in one storage location in a building not accessible to the public, such as an industrial building, shall not exceed a maximum capacity of 300 pounds (136 kg) of LPG. Where LPG containers are stored in more than one location on the same floor of a building, the storage areas shall be separated by a minimum of 300 feet (91 440 mm).

Exception: Storage of LPG at construction sites shall be in accordance with the rules.

6109.11 Reserved.

6109.12 Location of outdoor storage.

Outdoor storage, including storage of containers for sale and containers connected for use, shall be located not less than 20 feet (6096 mm) from building openings, 20 feet (6096 mm) from any motor vehicle fuel dispenser and 10 feet (3048 mm) from any combustible material and, as applicable, in accordance with FC Table 6109.12. Outdoor storage of LPG shall be limited to not more than 400 pounds (181.6 kg) of LPG and shall be located at or above grade level.

Exception: Storage of LPG at construction sites shall be in accordance with the rules.

FC Table 6109.12 Distances from Outdoor Lpg Storage Area to Exposures

Type of Outdoor Exposure LPG Storage Area More than 100 Pounds LPG up to Maximum 400 Pounds LPG Minimum Distance to Exposure (feet) Building or structure of combustible construction 10 Subway entrance, exit or other opening 25 Flammable and combustible liquids Aboveground – 1,000 gallons or less 10 a Flammable and combustible liquids Aboveground – in excess of 1,000 gallons 20 a Flammable and combustible liquids Below ground tank – 1,000 gallons or less 10 a Flammable and combustible liquids Below ground tank – 1,000 gallons or less Vent or fill opening of tank 15 a Flammable and combustible liquids Below ground tank – in excess of 1,000 gallons 15 a Flammable and combustible liquids Below ground tank – in excess of 1,000 gallons Vent or fill opening of tank 15 a Flammable gas storage area, 1,500 SCF or less 10 a Flammable gas storage area, More than 1,500 SCF up to maximum 3,500 SCF 20 a Oxygen storage – 20,000 SCF or less In accordance with NFPA 51 a Oxygen storage – in excess of 20,000 SCF In accordance with NFPA 55 a Fast-burning solids, such as ordinary lumber, excelsior or paper 10 a Slow-burning solids, such as heavy timber or coal 10 a Air compressor intakes or inlets to heating, ventilating or air-conditioning equipment 5 Group A occupancies and public gathering places 25 Public sidewalks and parked motor vehicles 10 Public streets, private roads and lot lines 10 a

For SI: 1 foot = 304.8 mm, 1 cubic foot = 0.02832 m 3 , 1 gallon = 3.785 L.

a. The minimum required distances may be reduced to 5 feet when protective structures having a minimum fire-resistance rating of 2 hours interrupt the line of sight between the container and the exposure. The protective structure shall be at least 5 feet from the exposure. The configuration of the protective structure shall be designed to allow natural ventilation to prevent the accumulation of hazardous gas concentrations.

6109.12.1 Proximity to hazards.

Storage shall not be located where the stored LPG would be exposed to the following hazards in the event of the failure of their structure or containment systems:

1. Electric power lines.

2. Piping containing flammable or combustible liquids.

3. Piping containing flammable gases.

4. Piping containing oxidizing materials.

6109.13 Protection of containers.

Containers shall be stored within a suitable enclosure or otherwise protected against tampering. Vehicular protection shall be provided as required by the commissioner.

6109.14 Electrical equipment.

Except as otherwise provided in NFPA 58, electrical equipment within 3 feet (914 mm) in any direction of an outdoor LPG facility shall comply with the Class I, Division 2 wiring requirements of the Electrical Code for hazardous locations, unless electrical equipment is separated from such area by a wall or other solid partition having no openings.

6109.15 LPG container storage for sale.

Outdoor storage of LPG for sale at mercantile establishments, including LPG container exchange stations, in areas accessible to the public, shall comply with the following requirements:

1. Each storage facility shall store no more than 400 pounds (181.6 kg) of propane, with individual container capacity of no more than 20 pounds (9.1 kg).

2. Containers shall be secured in a locked, fenced enclosure, ventilated listed cabinet or other approved location in accordance with the rules, or an automated container exchange system pursuant to FC 6109.15.1.

3. Containers shall be accessible only by certificate of fitness holders or by use of an automated exchange system in accordance with FC 6109.15.1.

4. A sign shall be posted at or near each entrance to the mercantile establishment stating "DO NOT BRING LPG CONTAINERS INTO THE BUILDING" or similar approved wording.

5. A durable sign shall be conspicuously posted at or near the cylinder storage enclosure or cabinet identifying the vendor/supplier of the LPG containers and providing emergency contact information for the vendor/supplier.

6109.15.1 Automated container exchange systems.

An automated container exchange system shall comply with the following additional requirements:

1. The system shall operate only during regular business hours under the general supervision of authorized personnel holding a certificate of fitness.

2. The system shall be designed and located with a full, unobstructed view of the system from within the mercantile establishment, either directly or with the use of mirrors or an approved closed-circuit television installation. The owner of the mercantile establishment shall take reasonable steps to ensure that system is monitored to prevent tampering or misuse.

3. The system shall only allow access to a single container per transaction.

4. The systems shall be designed such that containers can be placed inside only when they are oriented in the upright position.

5. The system's electrical components and all other electrical equipment within 3 feet (914 mm) of the system shall comply with the requirements for Class I, Division 2 equipment set forth in the Electrical Code.

6. The system shall be equipped with a manual override control that enables authorized personnel to access the stored containers and/or disable the system from automated container exchange. The system shall not be capable of returning to automated operation after a manual override until the system has been inspected and reset by a trained and knowledgeable person employed by the company supplying and servicing the system.

7. The system shall be inspected by a trained and knowledgeable person on a regular basis, but at least once a day, to confirm that there is no odor or other evidence of a gas leak, all compartments are closed and locked, and the system appears to be in good working order. If the system is not in good working order, the certificate of fitness holder and the company supplying and servicing the system shall be immediately notified and prompt corrective action shall be taken. Gas leaks shall be reported to the department by calling 911.

Section FC 6201. General

Open this section

6201.1 Scope.

This chapter shall govern the manufacture, storage, handling and use of organic peroxides.

6201.2 Permits.

Permits shall be required for organic peroxides as set forth in FC 105.6.

6201.3 General.

Organic peroxides shall be manufactured, stored, handled and used in accordance with this chapter and FC Chapter 50.

6201.4 Prohibited manufacture, storage, handling and use.

It shall be unlawful to manufacture, store, handle and/or use unclassified detonable organic peroxides except as specifically authorized by FC Chapter 56.

6201.5 Supervision.

The handling and use of organic peroxides in quantities requiring a permit shall be under the personal supervision of a certificate of fitness holder. The storage of organic peroxides in quantities requiring a permit shall be under the general supervision of a certificate of fitness holder.

Section FC 6202. Definitions

Open this section

6202.1 Definition.

The following term shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.

ORGANIC PEROXIDE.

Section FC 6203. General Requirements

Open this section

6203.1 Quantities not exceeding the maximum allowable quantity per control area.

The storage, handling and use of organic peroxides in amounts not exceeding the maximum allowable quantity per control area indicated in FC 5003.1 shall be in accordance with FC 5001, 5003, 6201, 6203 and 6206.

6203.1.1 Prohibited indoor storage, handling and use by occupancy.

It shall be unlawful to store, handle or use Class I organic peroxides:

1. in Group A, E, I, R or U occupancies.

2. in offices in Group B, F, M or S occupancies, and any areas of such occupancies that are accessible to the public.

6203.2 Quantities exceeding the maximum allowable quantity per control area.

The storage, handling and use of organic peroxides in amounts exceeding the maximum allowable quantity per control area indicated in FC 5003.1 shall be in accordance with FC Chapter 50 and this chapter.

6203.3 Multiple hazard sign.

Where more than one class of organic peroxide formulations is stored in immediate proximity to one another, such area shall be provided with hazard identification signs pursuant to FC Chapter 50 for the most severe class present.

6203.4 Multiple class storage.

Except as otherwise specifically provided in this code, where more than one class of organic peroxide is stored in the same control area, the maximum quantity allowed of each organic peroxide shall be limited as follows: the maximum quantity shall be reduced by multiplying the maximum allowable quantity for each such material by the proportional amount that such material bears to the total quantity of organic peroxide stored in the control area. The total of the proportional amounts shall not exceed 100 percent.

6203.5 Temperature-sensitive material.

Where the required storage temperature range, as specified by the manufacturer, extends beyond normal ambient temperatures, high or low temperature limit switches, as applicable, shall be provided in addition to normal temperature controls. These limit switches shall actuate an alarm in a supervised area to ensure reporting to the fire department.

Section FC 6204. Storage

Open this section

6204.1 Indoor storage.

Indoor storage of organic peroxides in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1) shall be in accordance with FC 5001, 5003, 5004 and this chapter.

6204.1.1 Detached storage.

Storage of organic peroxides shall be in a detached building when required by FC 5003.8.2.

6204.1.2 Distance from detached storage buildings to exposures.

In addition to the requirements of the Building Code, detached storage buildings shall be located in accordance with FC Table 6204.1.2.

FC Table 6204.1.2 Organic Peroxides – Distance from Detached Storage Buildings or Outdoor Storage Areas to Exposures

Organic Peroxide Class Maximum Storage Quantity (pounds) at Minimum Separation Distance Distance to buildings, lot lines, public streets, private roads or means of egress Distance between individual detached storage buildings or individual outdoor storage areas 50 feet 100 feet 150 feet 20 feet 75 feet 100 feet I 2,000 20,000 175,000 2,000 20,000 175,000 II 100,000 200,000 No Limit 100,000 a No Limit No Limit III 200,000 No Limit No Limit 200,000 a No Limit No Limit IV No Limit No Limit No Limit No Limit No Limit No Limit V No Limit No Limit No Limit No Limit No Limit No Limit

For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg.

a. When the amount of organic peroxide stored exceeds this amount, the minimum separation shall be 50 feet.

6204.1.3 Liquid-tight floor.

In addition to the requirements of FC 5004.12, floors of storage areas shall be of liquid-tight construction.

6204.1.4 Electrical wiring and equipment.

In addition to the requirements of FC 5003.9.4, electrical wiring and equipment in storage areas for Class I or II organic peroxides shall comply with the requirements of the Electrical Code for electrical Class I, Division 2 locations.

6204.1.5 Smoke detection.

An approved supervised smoke detection system in accordance with the construction codes, including the Building Code, shall be provided in rooms or areas where Class I, II or III organic peroxides are stored. Activation of the smoke detection system shall sound a local alarm.

Exception: A smoke detection system shall not be required in detached storage buildings equipped throughout with a fire extinguishing system.

6204.1.6 Maximum quantities.

Maximum allowable quantities per building in a mixed occupancy building shall not exceed the amounts set forth in FC Table 5003.8.2. Maximum allowable quantities per building in a detached storage building shall not exceed the amounts specified in FC Table 6204.1.2.

6204.1.7 Storage arrangement.

Storage arrangements for organic peroxides shall be in accordance with FC Table 6204.2.4 and shall comply with the following requirements:

1. Containers and packages in storage areas shall be closed.

2. Bulk storage shall not be in piles or bins.

3. A minimum 2-foot (610 mm) clear space shall be maintained between storage and uninsulated metal walls.

4. Fifty-five-gallon (208 L) drums shall not be stored more than one drum high.

6204.1.8 Location in building.

Class I or II organic peroxides shall be stored on the ground floor. Class III organic peroxides shall not be stored in basements or other areas below grade.

6204.1.9 Contamination.

Organic peroxides shall be stored in their original DOTn shipping containers. Organic peroxides shall be stored in a manner to prevent contamination.

6204.1.10 Explosion control.

Indoor storage rooms, areas and buildings containing Class I organic peroxides shall be provided with explosion control in accordance with FC 911 and the construction codes, including the Building Code.

6204.1.11 Emergency power.

Emergency power in accordance with the construction codes, including the Building Code and Electrical Code, shall be provided for storage areas of Class I organic peroxides.

6204.1.12 Smoke and heat venting.

Storage areas for Class I organic peroxides shall be provided with smoke and heat venting in accordance with FC 910 and the construction codes, including the Building Code.

6204.2 Outdoor storage.

Outdoor storage of organic peroxides in amounts exceeding the maximum allowable quantities per control area indicated in FC Table 5003.1.1(3) shall be in accordance with FC 5001, 5003, 5004 and this chapter.

6204.2.1 Distance from storage to exposures.

Outdoor storage areas for organic peroxides shall be located in accordance with FC Table 6204.1.2.

6204.2.2 Electrical wiring and equipment.

In addition to the requirements of FC 5003.9.4, electrical wiring and equipment in outdoor storage areas containing Class I or II organic peroxides shall comply with the requirements of the Electrical Code for electrical Class I, Division 2 locations.

6204.2.3 Maximum quantities.

Maximum allowable quantities of organic peroxides in outdoor storage shall be in accordance with FC Table 6204.1.2.

6204.2.4 Storage arrangement.

Storage arrangements shall be in accordance with FC Table 6204.2.4.

FC Table 6204.2.4 Storage Requirements for Organic Peroxides

Organic Peroxide Class Pile Configuration Maximum Quantity Per Building Maximum width (feet) Maximum height (feet) Minimum distance to next pile (feet) Minimum distance to walls (feet) I 6 8 4 a 4 b Note c II 10 8 4 a 4 b Note c III 10 8 4 a 4 b Note c IV 16 10 3 a, d 4 b No Requirement V No Requirement No Requirement No Requirement No Requirement No Requirement

For SI: 1 foot = 304.8 mm.

a. At least one main aisle with a minimum width of 8 feet shall divide the storage area.

b. Distance to noncombustible walls is allowed to be reduced to 2 feet.

c. For detached storage buildings or outdoor storage areas, see FC Table 6204.1.2 for maximum quantities. For indoor storage, see FC Table 5003.8.2 for maximum quantities.

d. The distance shall not be less than one-half the pile height.

6204.2.5 Separation.

In addition to the requirements of 5003.9.8, outdoor storage areas for organic peroxides in amounts exceeding those specified in FC Table 5003.8.2 shall be located a minimum distance of 50 feet (15 240 mm) from other hazardous material storage.

Section FC 6205. Handling and Use

Open this section

6205.1 General.

Organic peroxides in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1) or 5003.1.1(3) shall be handled and used in accordance with FC 5001, 5003, 5005 and this chapter.

Section FC 6206. Manufacturing Restrictions

Open this section

6206.1 Organic peroxides classified as a Class IV material.

Organic peroxides classified as a Class IV material as defined in Section 42-272 of the Zoning Resolution may be utilized in manufacturing processes or other production in manufacturing districts only when authorized by a special permit pursuant to Section 42-276 of the Zoning Resolution.

6206.1.1 Manufacture of organic peroxides classified as a Class IV material.

It shall be unlawful to manufacture organic peroxides classified as a Class IV material as defined in Section 42-272 of the Zoning Resolution.

6206.1.2 Storage of organic peroxides classified as a Class IV material.

It shall be unlawful to store organic peroxides classified as a Class IV material as defined in Section 42-272 of the Zoning Resolution, except that accessory storage authorized by a special permit pursuant to Section 42-276 of the Zoning Resolution shall be allowed.

Section FC 6301. General

Open this section

6301.1 Scope.

This chapter shall govern the manufacture, storage, handling and use of solid and liquid oxidizers, oxidizing gases and oxidizing cryogenic fluids.

Exceptions:

1. Display and storage in Group M and storage in Group S occupancies in accordance with FC 5003.11.

2. Storage, handling and use of liquid oxygen in a residential or residential health care setting in a Group I-1, I-4 or R occupancy in accordance with FC 6306.

6301.2 Permits.

Permits shall be required as set forth in FC 105.6.

6301.3 General.

Oxidizers shall be manufactured, stored, handled and used in accordance with this chapter and FC Chapter 50.

6301.3.1 Oxidizing gases.

Oxidizing gases shall additionally comply with the requirements of FC Chapter 53.

6301.3.2 Ammonium nitrate.

Oxidizers containing ammonium nitrate shall additionally comply with the requirements of NFPA 400.

6301.3.3 Bulk oxygen systems.

Bulk oxygen systems at industrial and institutional consumer sites shall additionally comply with the requirements of NFPA 55.

6301.3.4 Bulk nitrous oxide systems.

Bulk nitrous oxide systems at industrial and institutional consumer sites shall additionally comply with the requirements of CGA G-8.1.

6301.3.5 Oxidizing cryogenic fluids.

Oxidizing cryogenic fluids shall additionally comply with the requirements of FC Chapter 55.

6301.4 Supervision.

The handling and use of oxidizers in quantities requiring a permit shall be under the personal supervision of a certificate of fitness holder. The storage of oxidizers in quantities requiring a permit shall be under the general supervision of a certificate of fitness holder.

Section FC 6302. Definitions

Open this section

6302.1 Definitions.

The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.

BULK NITROUS OXIDE SYSTEM.

BULK OXYGEN SYSTEM.

LIQUID OXYGEN AMBULATORY CONTAINER.

LIQUID OXYGEN HOME CARE CONTAINER.

OXIDIZER.

Class 1.

Class 2.

Class 3.

Class 4.

OXIDIZING CRYOGENIC FLUID.

OXIDIZING GAS.

Section FC 6303. General Requirements

Open this section

6303.1 Quantities not exceeding the maximum allowable quantity per control area.

The storage, handling and use of oxidizers in amounts not exceeding the maximum allowable quantity per control area indicated in FC 5003.1 shall be in accordance with FC 5001, 5003, 6301, 6303, and 6307 and with FC Chapters 53 and 55, as applicable.

6303.1.1 Prohibited indoor storage, handling and use by occupancy.

It shall be unlawful to store, handle or use:

1. Class 4 oxidizers in Group A, E, I, R or U occupancies.

2. Class 4 liquid and solid oxidizers in offices in Group B, F, M or S occupancies, and any areas of such occupancies that are accessible to the public.

3. Oxidizing gases in portable containers exceeding an individual capacity of 250 SCF (7 m 3 ) for maintenance purposes, patient care or operation of equipment in Group A and E occupancies; Group B occupancy offices; and Group I and R occupancies, except as authorized by FC 6306.*

* Editor's note: "FC" prefix added at the discretion of the editor.

6303.1.2 Emergency shutoff.

Oxidizing gas piping systems shall be provided with approved manual or automatic emergency shutoff valves that can be activated at each point of use and each source.

6303.1.2.1 Shutoff at source.

A manual or automatic fail-safe emergency shutoff valve shall be installed on supply piping at the container or other source of supply. Manual or automatic valves on the containers supplying the oxidizing gas may serve as the emergency shutoff valve when the containers are the sole source of supply and are not manifolded.

6303.1.2.2 Shutoff at point of use.

A manual or automatic emergency shutoff valve shall be installed on the supply piping at the point of use or at a point where the equipment using the gas is connected to the supply system.

6303.1.3 Ignition source control.

Ignition sources in areas containing oxidizing gases shall be controlled in accordance with FC 5003.7.

6303.2 Quantities exceeding the maximum allowable quantity per control area.

The storage, handling and use of oxidizers in amounts exceeding the maximum allowable quantity per control area indicated in FC 5003.1 shall be in accordance with FC Chapter 50 and this chapter.

6303.3 Multiple hazard sign.

Where more than one class of oxidizer is stored in immediate proximity to one another, such area shall be provided with hazard identification signs pursuant to FC Chapter 50 for the most severe class present.

6303.4 Multiple class storage.

Except as otherwise specifically provided in this code, where more than one class of oxidizer is stored in the same control area, the maximum quantity allowed of each oxidizer shall be limited as follows: the maximum quantity shall be reduced by multiplying the maximum allowable quantity for each such material by the proportional amount that such material bears to the total quantity of oxidizer stored in the control area. The total of the proportional amounts shall not exceed 100 percent.

6303.5 Filling of portable containers.

Portable containers of oxidizing gases shall be filled at a compressed gas dispensing facility, except that:

1. liquid oxygen home care containers alternatively may be filled outdoors from a cargo tank designed to supply such containers. When a liquid oxygen home care container is filled from a cargo tank on an asphalt or combustible surface, a drip pan compatible with liquid oxygen shall be provided under home care container fill and vent connections during the filling process to minimize the risk of ignition of the combustible surface; and

2. liquid oxygen ambulatory containers alternatively may be filled in the residence or residential health care setting from the liquid oxygen home care container designed for such purpose, in accordance with the manufacturer's instructions.

6303.5.1 Smoking prohibited.

Smoking shall be prohibited in rooms or areas where liquid oxygen containers are filled.

Section FC 6304. Storage

Open this section

6304.1 Indoor storage.

Indoor storage of oxidizers in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1) shall be in accordance with FC 5001, 5003, 5004 and this chapter.

6304.1.1 Detached storage.

Storage of liquid and solid oxidizers shall be in a detached building when required by FC 5003.8.2.

6304.1.2 Distance from detached storage buildings to exposures.

In addition to the requirements of the construction codes, including the Building Code, detached storage buildings shall be located in accordance with FC Table 6304.1.2.

FC Table 6304.1.2 Oxidizer (Liquids and Solids) – Distance from Detached Storage Buildings and Outdoor Storage Areas to Exposures

Oxidizer Class Weight (pounds) Minimum Distance to Buildings, Lot Lines, Public Streets, Private Roads or Building Exits (feet) 1 Note a Not Required 2 Note a 35 3 Note a 50 4 Up to 10 50 greater than 10 up to 100 75 greater than 100 up to 500 100 greater than 500 up to 1,000 125 greater than 1,000 up to 3,000 200 greater than 3,000 up to 5,000 300 greater than 5,000 up to 10,000 400 over 10,000 As required by the commissioner

For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg.

a. Any quantity over the amount required for detached storage in accordance with FC 5003.8.2, or over the outdoor maximum allowable quantity for outdoor control areas.

6304.1.3 Explosion control.

Any room or other area in which Class 4 liquid or solid oxidizers are stored shall be provided with explosion control in accordance with FC 911 and the construction codes, including the Building Code.

6304.1.4 Sprinkler system.

Solid and liquid oxidizer storage areas shall be protected by a sprinkler system in accordance with NFPA 400.

6304.1.5 Liquid-tight floor.

In addition to FC 5004.12, floors of storage areas for liquid and solid oxidizers shall be of liquid-tight construction.

6304.1.6 Smoke detection.

An approved supervised smoke detection system in accordance with the construction codes, including the Building Code shall be installed in liquid and solid oxidizer storage areas. Such smoke detection system shall be monitored by an approved central station.

Exception: Detached storage buildings protected by a fire extinguishing system.

6304.1.6.1 Smoke and heat venting.

Smoke and heat venting shall be provided in accordance with FC 910 and the construction codes, including the Building Code.

6304.1.7 Storage conditions.

The maximum quantity of oxidizers that may be stored in a detached storage building shall not exceed the quantities set forth in FC Tables 6304.1.7(1) through 6304.1.7(4).

FC Table 6304.1.7(1) Storage Requirements for Class 1 Oxidizer (Liquids and Solids) in Combustible Containers a

Storage Configuration Limits (feet) Piles Maximum length Maximum width Maximum height Minimum distance to next pile Minimum distance to walls No Limit 50 20 3 2 Maximum quantity per pile No Limit Maximum quantity per building No Limit

For SI: 1 foot = 304.8 mm.

a. Storage in noncombustible containers or in bulk in detached storage buildings is not limited as to quantity or arrangement.

FC Table 6304.1.7(2) Storage Requirements for Class 2 Oxidizer (Liquids and Solids) a, b

Storage Configuration Limits Segregated storage Cutoff storage rooms c Detached building Piles Maximum width Maximum height Minimum distance to next pile Minimum distance to walls 16 feet 10 feet Note d 2 feet 25 feet 12 feet Note d 2 feet 25 feet 12 feet Note d 2 feet Maximum quantity per pile 20 tons 50 tons 200 tons Maximum quantity per building 200 tons 500 tons No Limit

For SI: 1 foot = 204.8 mm, 1 ton = 0.907185 metric ton.

a. Storage in noncombustible containers is not limited as to quantity or arrangement, except that piles shall be at least 2 feet from walls in buildings protected throughout by a sprinkler system and 4 feet from walls in buildings not protected throughout by a sprinkler system; the distance between piles shall not be less than the pile height.

b. Quantity limits shall be reduced by 50 percent in buildings or portions of buildings used for retail sales.

c. Cutoff storage rooms shall be separated from the remainder of the building by 2-hour fire barriers.

d. Aisle width shall not be less than the pile height.

FC Table 6304.1.7(3) Storage Requirements for Class 3 Oxidizer (Liquids and Solids) a, b

Storage Configuration Limits Segregated storage Cutoff storage rooms c Detached building Piles Maximum width Maximum height Minimum distance to next pile Minimum distance to walls 12 feet 8 feet Note d 4 feet 16 feet 10 feet Note d 4 feet 20 feet 10 feet Note d 4 feet Maximum quantity per pile 20 tons 30 tons 150 tons Maximum quantity per building 100 tons 500 tons No Limit

For SI: 1 foot = 204.8 mm, 1 ton = 0.907185 metric ton.

a. Storage in noncombustible containers is not limited as to quantity or arrangement, except that piles shall be at least 2 feet from walls in sprinklered buildings and 4 feet from walls in nonsprinklered buildings; the distance between piles shall not be less than the pile height.

b. Quantity limits shall be reduced by 50 percent in buildings or portions of buildings used for retail sales.

c. Cutoff storage rooms shall be separated from the remainder of the building by 2-hour fire barriers.

d. Aisle width shall not be less than the pile height.

FC Table 6304.1.7(4) Storage Requirements for Class 4 Oxidizer (Liquids and Solids)

Storage Configuration Limits (feet) Piles Maximum length Maximum width Maximum height Minimum distance to next pile 10 4 8 8 Maximum quantity per building No Limit

For SI: 1 foot = 304.8 mm.

6304.1.7.1 Liquid and solid oxidizers.

The storage configuration for liquid and solid oxidizers shall be as set forth in FC Tables 6304.1.7(1) through 6304.1.7(4).

6304.1.7.2 Class 2 oxidizers.

Class 2 oxidizers shall not be stored in basements, cellars or other areas below grade, except when such storage is in stationary tanks.

6304.1.7.3 Class 3 and 4 oxidizers.

Class 3 and 4 oxidizers in amounts exceeding the maximum allowable quantity per control area set forth in FC 5003.1 shall be stored on the ground floor only.

6304.1.8 Separation of Class 4 oxidizers from other materials.

In addition to the requirements in FC 5003.9.8, Class 4 oxidizer liquids and solids shall be separated from other hazardous materials by not less than a 1-hour fire barrier or stored in hazardous materials storage cabinets. Detached storage buildings for Class 4 oxidizer liquids and solids shall be located a minimum of 50 feet (15 240 mm) from other hazardous materials storage.

6304.1.9 Contamination.

Liquid and solid oxidizers shall not be stored on or against combustible surfaces. Liquid and solid oxidizers shall be stored in a manner to prevent contamination.

6304.2 Outdoor storage.

Outdoor storage of oxidizers in amounts exceeding the maximum allowable quantities per control area set forth in FC Table 5003.1.1(3) shall be in accordance with FC 5001, 5003, 5004 and this chapter.

6304.2.1 Distance from storage to exposures for liquid and solid oxidizers.

Outdoor storage areas for liquid and solid oxidizers shall be located in accordance with FC Table 6304.1.2.

6304.2.2 Distance from storage to exposures for oxidizing gases.

Outdoor storage areas for oxidizing gases shall be located in accordance with FC Table 6304.2.2.

FC Table 6304.2.2 Oxidizing Gases – Distance from Storage to Exposures a

Quantity of Gas Stored SCF Distance to a Building Not Associated with the Manufacture or Distribution of Oxidizing Gases or Public Street, Private Road or Lot Line (feet) Distance Between Storage Areas (feet) greater than 3,000 up to 50,000 5 5 greater than 50,000 up to 100,000 10 10 greater than 100,000 15 15

For SI: 1 foot = 304.8 mm, 1 cubic foot = 0.02832 m 3 .

a. The distances do not apply when protective structures having a minimum fire-resistance rating of 2 hours interrupt the line of sight between the storage container and the exposure. The protective structure shall be at least 5 feet from the exposure. The configuration of the protective structure shall be designed to allow natural ventilation to prevent the accumulation of hazardous gas concentrations.

6304.2.2.1 Oxidizing cryogenic fluids.

Outdoor storage areas for oxidizing cryogenic fluids shall be located in accordance with FC Chapter 55.

6304.2.3 Storage configuration for liquid and solid oxidizers.

Storage configuration for liquid and solid oxidizers shall be in accordance with FC Tables 6304.1.7(1) through 6304.1.7(4).

6304.2.4 Storage configuration for oxidizing gases.

Storage configuration for oxidizing gases shall be in accordance with FC Table 6304.2.2.

Section FC 6305. Handling and Use

Open this section

6305.1 Scope.

Oxidizers in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1) or 5003.1.1(3) shall be handled and used in accordance with FC 5001, 5003, 5005 and this chapter.

Section FC 6306. Liquid Oxygen for Residential Health Care Use

Open this section

6306.1 General.

Liquid oxygen home care containers and liquid oxygen ambulatory containers used for medical purposes in residential health care settings in Group I-1, I-4 and R occupancies shall be stored, handled and used in accordance with the manufacturer's instructions and labeling and in compliance with the requirements of this section. Storage, handling and use of liquid oxygen, including liquid oxygen home care containers and liquid oxygen ambulatory containers, in Group I-1, I-4 and R occupancies, other than in dwelling units and sleeping rooms, shall be in accordance with FC 6301 through 6305 and FC Chapter 50.

6306.2 Supplier requirements.

Persons engaged in the business of supplying liquid oxygen home care containers and liquid oxygen ambulatory containers shall provide to the person who will be using the liquid oxygen:

1. the manufacturer's instructions, and informational materials detailing the safe storage, handling and use of the containers in accordance with this section, including the prohibition set forth in FC 6306.3.4 relating to LPG storage, handling and use;

2. unless the person who will be using the liquid oxygen is already in possession of such a device suitable for the container being supplied, a base, hand truck or other device or devices designed to support the container in an upright or other approved position, to secure the container from movement, and to enable the container to be safely handled; and

3. two signs that read, "OXYGEN – NO SMOKING", and instruct the person who will be using the liquid oxygen to conspicuously post one sign in the living area of the dwelling unit and one in the person's sleeping room, to remind all occupants of the dwelling unit and all visitors of the danger of fire associated with smoking near an oxygen supply.

6306.3 Storage, handling and use requirements.

Liquid oxygen home care containers and liquid oxygen ambulatory containers shall be stored, handled and used in residential dwelling units and residential health care dwelling units or sleeping rooms in Group I-1, I-4 and R occupancies in compliance with the requirements of FC 6306.3.1 through 6306.3.4.

6306.3.1 Quantity limits.

The maximum aggregate quantity of liquid oxygen that may be stored, handled and used in a residential dwelling unit or residential health care dwelling unit or sleeping room shall be limited to 31.6 gallons (120 L).

6306.3.2 Storage and use locations.

Containers shall not be stored or used in any location in the dwelling unit or sleeping room where they obstruct egress from the room; can be struck by a door or falling object; are exposed to a heat source, including a radiator, baseboard heater, steam pipe, portable electric heater, or halogen lamp; or are exposed to any open flame or other ignition source, including a stove or torch.

6306.3.3 Securing and handling containers.

Liquid oxygen home care containers and liquid oxygen ambulatory containers shall be kept in an upright or other approved position, secured from movement, and handled in accordance with the manufacturer's instructions, using the base, hand truck or other device or devices supplied for such purpose or other suitable device. Liquid oxygen ambulatory containers may be hand carried.

6306.3.4 Prohibition.

LPG containers shall not be stored, handled or used in any room in the dwelling unit or sleeping room in which liquid oxygen home care containers and liquid oxygen ambulatory containers are being stored or are in use.

6306.4 Filling of containers.

Liquid oxygen home care containers and liquid oxygen ambulatory containers shall be filled in accordance with FC 6303.5.

6306.5 Smoking prohibited.

Smoking shall be prohibited in rooms or areas where liquid oxygen is in use.

6306.6 Signage.

Where required by the department, an approved sign shall be affixed to a lower quadrant of the public corridor side of the door, within 12 inches (305 mm) from the bottom of the door, indicating the presence of liquid oxygen home care containers within the dwelling unit or sleeping room.

Section FC 6307. Manufacturing Restrictions

Open this section

6307.1 Oxidizers classified as a Class IV material.

Oxidizers classified as a Class IV material as defined in Section 42-272 of the Zoning Resolution may be utilized in manufacturing processes or other production in manufacturing districts only when authorized by a special permit pursuant to Section 42-276 of the Zoning Resolution.

6307.1.1 Manufacture of oxidizers classified as a Class IV material.

It shall be unlawful to manufacture oxidizers classified as a Class IV material as defined in Section 42-272 of the Zoning Resolution.

6307.1.2 Storage of oxidizers classified as a Class IV material.

It shall be unlawful to store oxidizers classified as a Class IV material as defined in Section 42-272 of the Zoning Resolution, except that accessory storage authorized by a special permit pursuant to Section 42-276 of the Zoning Resolution shall be allowed.

Section FC 6401. General

Open this section

6401.1 Scope.

This chapter shall govern the manufacture, storage, handling and use of pyrophoric materials.

6401.2 Permits.

Permits shall be required as set forth in FC 105.6.

6401.3 General.

Pyrophoric materials shall be manufactured, stored, handled and used in accordance with this chapter. Pyrophoric materials that are compressed gases shall additionally comply with the requirements of FC Chapter 53.

6401.4 Prohibitions.

It shall be unlawful to:

1. Manufacture, store, handle and/or use detonable pyrophoric materials, except as specifically authorized in compliance with the requirements of FC Chapter 56.

2. Compress any pyrophoric material that is a gas.

6401.5 Supervision.

The handling and use of pyrophoric materials in quantities requiring a permit shall be under the personal supervision of a certificate of fitness holder. The storage of pyrophoric materials in quantities requiring a permit shall be under the general supervision of a certificate of fitness holder.

Section FC 6402. Definitions

Open this section

6402.1 Definition.

The following term shall, for the purposes of this chapter and as used elsewhere in this code, have the meaning set forth in FC 202.

PYROPHORIC MATERIAL.

Section FC 6403. General Requirements

Open this section

6403.1 Quantities not exceeding the maximum allowable quantity per control area.

The storage, handling and use of pyrophoric materials in amounts not exceeding the maximum allowable quantity per control area indicated in FC 5003.1 shall be in accordance with FC 5001, 5003, 6401, 6403 and 6406.

6403.1.1 Emergency shutoff.

Compressed gas systems conveying pyrophoric gases shall be provided with approved manual or automatic emergency shutoff valves that can be activated at each point of use and each source.

6403.1.1.1 Shutoff at source.

A manual or automatic fail-safe emergency shutoff valve shall be installed on supply piping at the container or other source of supply. The shutoff valve shall be operated by a remotely located manually activated shutdown control located not less than 15 feet (4572 mm) from the source of supply. Manual or automatic container valves on the containers supplying the pyrophoric material may serve as the emergency shutoff valve when the containers are the sole source of supply and are not manifolded.

6403.1.1.2 Shutoff at point of use.

A manual or automatic emergency shutoff valve shall be installed on the supply piping at the point of use or at a point where the equipment using the gas is connected to the supply system.

6403.2 Quantities exceeding the maximum allowable quantity per control area.

The storage, handling and use of pyrophoric materials in amounts exceeding the maximum allowable quantity per control area indicated in FC 5003.1 shall be in accordance with FC Chapter 50 and this chapter.

Section FC 6404. Storage

Open this section

6404.1 Indoor storage.

Indoor storage of pyrophoric materials in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1), shall be in accordance with FC 5001, 5003, 5004 and this chapter. The storage of silane gas and gas mixtures with a silane gas concentration of 1.37 percent or more by volume, shall be in accordance with CGA G-13.

6404.1.1 Liquid-tight floor.

In addition to the requirements of FC 5004.12, floors of storage areas containing pyrophoric liquids shall be of liquid-tight construction.

6404.1.2 Pyrophoric solids and liquids.

Storage of pyrophoric solids and liquids shall be limited to a maximum area of 100 square feet (9.3 m 2 ) per pile. Storage shall not exceed 5 feet (1524 mm) in height. Individual containers shall not be stacked. Aisles between storage piles shall be a minimum of 10 feet (3048 mm) in width. Individual tanks or containers shall not exceed 500 gallons (1893 L) in capacity.

6404.1.3 Pyrophoric gases.

Storage of pyrophoric gases shall be in detached buildings where required by FC 5003.8.2.

6404.1.4 Separation from incompatible materials.

In addition to the requirements of FC 5003.9.8, indoor storage of pyrophoric materials shall be isolated from incompatible hazardous materials by 1-hour fire barriers with openings protected in accordance with the construction codes, including the Building Code.

Exception: Storage in approved hazardous materials storage cabinets constructed in accordance with FC 5003.8.7.

6404.2 Outdoor storage.

Outdoor storage of pyrophoric materials in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(3) shall be in accordance with FC 5001, 5003, 5004 and this chapter. The storage of silane gas, and gas mixtures with a silane gas concentration of 1.37 percent or more by volume, shall be in accordance with CGA G-13.

6404.2.1 Distance from storage to exposures.

The separation of pyrophoric solids, liquids and gases from buildings, lot lines, public streets, private roads or means of egress shall be in accordance with the following:

1. Solids and liquids. Two times the separation required by FC Chapter 57 for Class IB flammable liquids.

2. Gases. The location and maximum amount of pyrophoric gas per storage area shall be in accordance with FC Table 6404.2.1.

FC Table 6404.2.1 Pyrophoric Gases – Distance from Storage to Exposures a

Maximum Amount per Storage Area (cubic feet) Minimum Distance Between Storage Areas (feet) Minimum Distance to Lot Lines (feet) Minimum Distance to Public Streets and Private Roads (feet) Minimum Distance to Buildings on the Same Property Nonrated construction or openings within 25 feet Two-hour construction and no openings within 25 feet Four-hour construction and no openings within 25 feet 250 5 25 5 5 0 0 2,500 10 50 10 10 5 0 7,500 20 100 20 20 10 0

For SI: 1 foot = 304.8 mm, 1 cubic foot = 0.02832 m 3 .

a. The minimum required distances shall be reduced to 5 feet when protective structures having a minimum fire resistance of 2 hours interrupt the line of sight between the container and the exposure. The protective structure shall be at least 5 feet from the exposure. The configuration of the protective structure shall allow natural ventilation to prevent the accumulation of hazardous gas concentrations.

6404.2.2 Fire protection.

When overhead construction is provided for sheltering outdoor storage areas of pyrophoric materials, the storage areas shall be protected throughout by a fire extinguishing system.

Section FC 6405. Handling and Use

Open this section

6405.1 General.

Pyrophoric materials in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1) or 5003.1.1(3) shall be handled and used in accordance with FC 5001, 5003, 5005 and this chapter.

6405.2 Fire protection.

When overhead construction is provided for sheltering of outdoor use areas of pyrophoric materials, the use areas shall be protected throughout by a fire extinguishing system.

6405.3 Silane gas.

The handling and use of silane gas, and gas mixtures with a silane gas concentration of 1.37 percent or more by volume, shall be in accordance with CGA G-13.

Section FC 6406. Manufacturing Restrictions

Open this section

6406.1 Pyrophoric materials classified as a Class IV material.

Pyrophoric materials classified as a Class IV material as defined in Section 42-272 of the Zoning Resolution may be utilized in manufacturing processes or other production in manufacturing districts only when authorized by a special permit pursuant to Section 42-276 of the Zoning Resolution.

6406.1.1 Manufacture of pyrophoric materials classified as a Class IV material.

It shall be unlawful to manufacture pyrophoric materials classified as a Class IV material as defined in Section 42-272 of the Zoning Resolution.

6406.1.2 Storage of pyrophoric materials classified as a Class IV material.

It shall be unlawful to store pyrophoric materials classified as a Class IV material as defined in Section 42-272 of the Zoning Resolution, except accessory storage authorized by a special permit pursuant to Section 42-276 of the Zoning Resolution.

Section FC 6501. General

Open this section

6501.1 Scope.

This chapter shall govern the manufacture, storage, handling and use of pyroxylin plastic, except cellulose nitrate motion picture film, which shall comply with the requirements of FC 306.

6501.2 Permits.

Permits shall be required as set forth in FC 105.6.

6501.3 General.

Pyroxylin plastics shall be manufactured, stored, handled and used in accordance with this chapter.

6501.4 Prohibitions.

It shall be unlawful to:

1. Manufacture raw pyroxylin plastics.

2. Store raw pyroxylin plastics, except accessory storage authorized by a special permit pursuant to Section 42-276 of the Zoning Resolution.

6501.5 Supervision.

The handling and use of raw pyroxylin plastics in quantities requiring a permit shall be under the personal supervision of a certificate of fitness holder. The storage of raw pyroxylin plastics in quantities requiring a permit shall be under the general supervision of a certificate of fitness holder.

Section FC 6502. Definitions

Open this section

6502.1 Definitions.

The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.

FINISHED PYROXYLIN PLASTIC PRODUCTS.

PYROXYLIN PLASTIC.

RAW PYROXYLIN PLASTIC.

Section FC 6503. General Requirements

Open this section

6503.1 Displays.

Finished pyroxylin plastic products displayed in areas to which the public has access shall be placed on tables not more than 3 feet (914 mm) wide and 10 feet (3048 mm) long. Tables shall be spaced at least 3 feet (914 mm) apart. Where articles are displayed on counters, they shall be arranged in a like manner.

6503.2 Space under tables.

Spaces underneath tables on which finished pyroxylin plastic products are displayed shall be kept free from storage of any kind and accumulation of rubbish or other combustible waste or any other combustible material.

6503.3 Location.

Tables on which finished pyroxylin plastic products are displayed shall be so located that in the event of a fire at the table, the table will not interfere with any means of egress.

6503.4 Lighting.

Lighting shall not be located directly above pyroxylin plastics, unless provided with a suitable guard to prevent heated particles or broken bulb elements from falling.

Section FC 6504. Storage, Handling and Use

Open this section

6504.1 Pyroxylin plastics in Group F buildings.

Pyroxylin plastics in a Group F building shall be stored, handled and used in accordance with FC 6504.1.1 through 6504.1.7.

6504.1.1 Storage of incoming material.

Where raw pyroxylin plastics in excess of 25 pounds (11 kg) are received in a building or fire area, an approved vented cabinet or approved vented vault protected by a sprinkler system shall be provided for the storage of material.

6504.1.2 Capacity limitations.

Storage in any one workroom shall not exceed 1,000 pounds (454 kg) of raw pyroxylin plastics. A storage cabinet shall not contain more than 500 pounds (227 kg). Each compartment shall not contain more than 250 pounds (114 kg).

6504.1.3 Storage of additional material.

Raw pyroxylin plastics in excess of that allowed by FC 6504.1.2 shall be kept in vented vaults not exceeding 1,500-cubic-foot capacity (43 m 3 ) of total vault space, and with construction, venting and sprinkler system protection approved by the commissioner.

6504.1.4 Heat sources.

Pyroxylin plastics shall not be stored within 2 feet (610 mm) of heat-producing appliances, steam pipes, radiators or chimneys.

6504.1.5 Accumulation of material.

In factories manufacturing pyroxylin plastic products, approved vented cabinets, vaults or storage rooms protected by a sprinkler system shall be provided to prevent the accumulation in workrooms of raw pyroxylin plastics in process and finished pyroxylin plastic products.

6504.1.6 Operators.

In workrooms of factories manufacturing finished pyroxylin plastic products, operators shall not be stationed closer together than 3 feet (914 mm), and the amount of material per operator shall not exceed one-shift's supply and shall be limited to the capacity of three tote boxes, including material awaiting removal or use.

6504.1.7 Waste material.

Waste pyroxylin plastics, such as shavings, chips, turnings, sawdust, edgings and trimmings, shall be kept under water in metal receptacles until removed from the premises.

6504.2 Fire protection.

The storage, handling or use of pyroxylin plastic in quantities exceeding 100 pounds (45 kg) shall be located in a building or part thereof protected throughout by a sprinkler system, except for storage exclusively of finished pyroxylin plastic products in a quantity not exceeding 6,000 pounds (2724 kg).

6504.3 Sources of ignition.

Sources of ignition shall not be allowed in rooms in which pyroxylin plastics in excess of 25 pounds (11 kg) are stored, handled or used.

6504.4 Heating.

Rooms in which pyroxylin plastics are handled or stored shall be heated by low-pressure steam or hot water radiators. Radiators shall be not less than 4 inches (102 mm) above the floor. All steam pipes and risers within 6 feet (1829 mm) of the floor shall be protected with noncombustible pipe covering. All heating radiators, coils, boilers, pipes and other heating apparatus situated so as to come in contact with any combustible material, including the tops of radiators, shall be protected with 1/4-inch (6-mm) mesh galvanized steel of No. 20 U.S. gauge or equivalent. The tops of such guards shall slope so as to prevent their use as a shelf.

6504.5 Prohibitions.

It shall be unlawful to store, handle or use raw pyroxylin plastics as follows:

1. In any building situated within 50 feet (15 240 mm) of the nearest wall of a building occupied as a school, hospital, or Group A occupancy.

2. In any Group R occupancy.

3. In any building of combustible construction as defined in Section 602 of the Building Code.

Section FC 6505. Manufacturing Restrictions

Open this section

6505.1 Raw pyroxylin plastics.

Raw pyroxylin plastics shall be treated as a Class IV material as defined in Section 42-272 of the Zoning Resolution. Raw pyroxylin plastics may be utilized in manufacturing processes or other production in manufacturing districts only when authorized by a special permit pursuant to Section 42-276 of the Zoning Resolution.

Section FC 6601. General

Open this section

6601.1 Scope.

This chapter shall govern the manufacture, storage, handling and use of unstable (reactive) materials, except for the display and storage of unstable (reactive) materials in Group M and storage of unstable (reactive) materials in Group S occupancies complying with the requirements of FC 5003.11.

6601.2 Permits.

Permits shall be required as set forth in FC 105.6.

6601.3 General.

Unstable (reactive) materials shall be manufactured, stored, handled and used in accordance with this chapter. Unstable (reactive) materials that are compressed gases shall additionally comply with the requirements of FC Chapter 53.

6601.4 Prohibited manufacture, storage, handling and use.

It shall be unlawful to manufacture, store, handle and/or use detonable unstable (reactive) materials except as specifically authorized by FC Chapter 56.

6601.5 Supervision.

The handling and use of unstable (reactive) materials in quantities requiring a permit shall be under the personal supervision of a certificate of fitness holder. The storage of unstable (reactive) materials in quantities requiring a permit shall be under the general supervision of a certificate of fitness holder.

Section FC 6602. Definitions

Open this section

6602.1 Definition.

The following term shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.

UNSTABLE (REACTIVE) MATERIAL.

Section FC 6603. General Requirements

Open this section

6603.1 Quantities not exceeding the maximum allowable quantity per control area.

The storage, handling and use of unstable (reactive) materials in amounts not exceeding the maximum allowable quantity per control area indicated in FC 5003.1 shall be in accordance with FC 5001, 5003, 6601, 6603 and 6606.

6603.1.1 Prohibited indoor storage, handling and use by occupancy.

It shall be unlawful to store, handle or use:

1. Class 3 and 4 unstable (reactive) materials in Group A, E, I, R or U occupancies.

2. Class 3 and 4 unstable (reactive) materials in offices in Group B, F, M or S occupancies, or any other areas of such occupancies that are accessible to the public.

6603.2 Quantities exceeding the maximum allowable quantity per control area.

The storage, handling and use of unstable (reactive) materials in amounts exceeding the maximum allowable quantity per control area indicated in FC 5003.1 shall be in accordance with FC Chapter 50 and this chapter.

6603.3 Multiple hazard sign.

Where two or more classes of unstable (reactive) materials are stored in immediate proximity to one another, such area shall be provided with hazard identification signs pursuant to FC Chapter 50 for the most severe class present.

6603.4 Multiple class storage.

Except as otherwise specifically provided in this code, where more than one class of unstable (reactive) materials is stored in the same control area, the maximum quantity allowed of each unstable (reactive) material shall be limited as follows: the maximum quantity shall be reduced by multiplying the maximum allowable quantity for each such material by the proportion that such material bears to the total quantity of unstable (reactive) material stored in the control area. The total of the proportional amounts shall not exceed 100 percent.

6603.5 Temperature-sensitive material.

Where the required storage temperature range, as specified by the manufacturer, extends beyond normal ambient temperatures, high or low temperature limit switches, as applicable, shall be provided in addition to normal temperature controls. These limit switches shall activate an alarm in a supervised area to ensure reporting to the fire department.

Section FC 6604. Storage

Open this section

6604.1 Indoor storage.

Indoor storage of unstable (reactive) materials in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1) shall be in accordance with FC 5001, 5003, 5004 and this chapter.

6604.1.1 Detached storage.

Storage of unstable (reactive) materials shall be in a detached building when required in FC 5003.8.2.

6604.1.2 Explosion control.

Indoor storage rooms, areas and buildings containing Class 3 or 4 unstable (reactive) materials shall be provided with explosion control in accordance with FC 911 and the construction codes, including the Building Code.

6604.1.3 Liquid-tight floor.

In addition to FC 5004.12, floors of storage areas for liquids and solids shall be of liquid-tight construction.

6604.1.4 Storage configuration.

Unstable (reactive) materials stored in quantities greater than 500 cubic feet (14 m 3 ) shall be separated into piles, each not larger than 500 cubic feet (14 m 3 ). Aisle width shall not be less than the height of the piles or 4 feet (1219 mm), whichever is greater.

Exception: Materials stored in tanks.

6604.1.5 Location.

Unstable (reactive) materials shall not be stored in basements or other areas below grade.

6604.1.6 Smoke and heat venting.

Smoke and heat venting shall be provided in accordance with FC 910 and the construction codes, including the Building Code.

6604.2 Outdoor storage.

Outdoor storage of unstable (reactive) materials in amounts exceeding the maximum allowable quantities per control area indicated in FC Table 5003.1.1(3) shall be in accordance with FC 5001, 5003, 5004 and this chapter.

6604.2.1 Distance to exposures from Class 3 and 4 (detonable) material outdoor storage areas.

Outdoor storage of Class 3 (detonable) or 4 unstable (reactive) material shall be in accordance with FC Table 5604.5.2(3). The number of pounds of material listed in the table shall be the net weight of the material present. Alternatively, the number of pounds of material shall be based on a trinitrotoluene (TNT) equivalent weight.

6604.2.2 Distance to exposures from Class 3 (deflagratable) material outdoor storage areas.

Outdoor storage of deflagratable Class 3 unstable (reactive) materials shall be in accordance with FC Table 5604.5.2(4). The number of pounds of material listed shall be the net weight of the material present.

6604.2.3 Distance to exposures from Class 1 and 2 material outdoor storage areas.

Outdoor storage of Class 1 or 2 unstable (reactive) materials shall not be within 20 feet (6096 mm) of buildings not associated with the manufacture or distribution of such materials, lot lines, public streets, private roads or means of egress. The minimum required distance shall not apply when fire barriers that have no openings or penetrations and have a minimum fire-resistance rating of 2 hours interrupt the line of sight between the storage and the exposure. The fire barrier shall either be an independent structure, or the exterior wall of the building adjacent to the storage area.

6604.2.4 Storage configuration.

Piles of unstable (reactive) materials shall not exceed 1,000 cubic feet (28 m 3 ).

6604.2.5 Aisle widths.

Aisle widths between piles shall not be less than one-half the height of the pile or 10 feet (3048 mm), whichever is greater.

Section FC 6605. Handling and Use

Open this section

6605.1 General.

Unstable (reactive) materials in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1) or 5003.1.1(3) shall be handled and used in accordance with FC 5001, 5003, 5005 and this chapter.

Section FC 6606. Manufacturing Restrictions

Open this section

6606.1 Unstable (reactive) material classified as a Class IV material.

Unstable (reactive) material classified as a Class IV material as defined in Section 42-272 of the Zoning Resolution may be utilized in manufacturing processes or other production in manufacturing districts only when authorized by a special permit pursuant to Section 42-276 of the Zoning Resolution.

6606.1.1 Manufacture of unstable (reactive) material classified as a Class IV material.

It is unlawful to manufacture unstable (reactive) material classified as a Class IV material as defined in Section 42-272 of the Zoning Resolution.

6606.1.2 Storage of unstable (reactive) materials classified as a Class IV material.

It shall be unlawful to store unstable (reactive) material classified as a Class IV material as defined in Section 42-272 of the Zoning Resolution, except that accessory storage authorized by a special permit pursuant to Section 42-276 of the Zoning Resolution shall be allowed.

Section FC 6701. General

Open this section

6701.1 Scope.

This chapter shall govern the manufacture, storage, handling and use of water-reactive solids and liquids, except for the display and storage of water-reactive solids and liquids in Group M occupancies complying with the requirements of FC 5003.11, and storage of water-reactive solids and liquids in Group S occupancies complying with the requirements of FC 5003.11.

6701.2 Permits.

Permits shall be required as set forth in FC 105.6.

6701.3 General.

Water-reactive solids and liquids shall be manufactured, stored, handled and used in accordance with this chapter.

6701.4 Prohibited manufacture, storage, handling and use.

It shall be unlawful to manufacture, store, handle or use detonable water-reactive solids and liquids, except as specifically authorized by FC Chapter 56.

6701.5 Supervision.

The handling and use of water-reactive solids and liquids in quantities requiring a permit shall be under the personal supervision of a certificate of fitness holder. The storage of water-reactive solids and liquids in quantities requiring a permit shall be under the general supervision of a certificate of fitness holder.

Section FC 6702. Definitions

Open this section

6702.1 Definition.

The following term shall, for the purposes of this chapter and as used elsewhere in this code, have the meaning set forth in FC 202.

WATER-REACTIVE MATERIAL.

Section FC 6703. General Requirements

Open this section

6703.1 Quantities not exceeding the maximum allowable quantity per control area.

The storage, handling and use of water-reactive solids and liquids in amounts not exceeding the maximum allowable quantity per control area indicated in FC 5003.1 shall be in accordance with FC 5001, 5003, 6701, 6703 and 6706.

6703.1.1 Prohibited indoor storage, handling and use by occupancy.

It shall be unlawful to store, handle or use:

1. Class 3 water-reactive solids and liquids in Group A, E, I, R or U occupancies.

2. Class 3 water-reactive solids and liquids in offices in Group B, F, M or S occupancies, or any other areas of such occupancy accessible to the public.

6703.2 Quantities exceeding the maximum allowable quantity per control area.

The storage, handling and use of water-reactive solids and liquids in amounts exceeding the maximum allowable quantity per control area indicated in FC 5003.1 shall be in accordance with FC Chapter 50 and this chapter.

6703.3 Multiple hazard sign.

Where more than one class of water-reactive solids and liquids is stored in immediate proximity to one another, such area shall be provided with hazard identification signs pursuant to FC Chapter 50 for the most severe class present.

6703.4 Multiple class storage.

Except as otherwise specifically provided in this code, where more than one class of water-reactive solids and liquids is stored in the same control area, the maximum quantity allowed of each water-reactive solid or liquid shall be limited as follows: the maximum quantity shall be reduced by the maximum allowable quantity for each such solid or liquid by the proportion that such solid or liquid bears to the total quantity of water-reactive solid and liquid stored in the control area. The total of the proportional amounts shall not exceed 100 percent.

Section FC 6704. Storage

Open this section

6704.1 Indoor storage.

Indoor storage of water-reactive solids and liquids in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1), shall be in accordance with FC 5001, 5003, 5004 and this chapter.

6704.1.1 Detached storage.

Storage of water-reactive solids and liquids shall be in a detached building when required by FC 5003.8.2.

6704.1.2 Liquid-tight floor.

In addition to the provisions of FC 5004.12, floors in storage areas for water-reactive solids and liquids shall be of liquid-tight construction.

6704.1.3 Waterproof room.

Rooms or areas used for the storage of water-reactive solids and liquids shall be constructed in a manner which resists the penetration of water through the use of waterproof materials. Piping carrying water for other than sprinkler systems shall not be within such rooms or areas.

6704.1.4 Water-tight containers.

When Class 2 and/or Class 3 water-reactive solids and liquids are stored in areas protected by a sprinkler system, the materials shall be stored in closed water-tight containers.

6704.1.5 Storage configuration.

Water-reactive solids and liquids stored in quantities greater than 500 cubic feet (14 m 3 ) shall be separated into piles, each not larger than 500 cubic feet (14 m 3 ). Aisle widths between piles shall not be less than the height of the pile or 4 feet (1219 mm), whichever is greater.

Exception: Water-reactive solids and liquids stored in tanks.

6704.1.5.1 Class 2 storage in basements or other areas below grade.

Class 2 water-reactive solids and liquids shall not be stored in basements or other areas below grade unless such materials are stored in closed water-tight containers or tanks.

6704.1.5.2 Class 3 storage in basements or other areas below grade.

Class 3 water-reactive solids and liquids shall not be stored in basements or other areas below grade.

6704.1.5.3 Flammable liquids.

Class 2 or Class 3 water-reactive solids and liquids shall not be stored with flammable liquids.

6704.1.6 Explosion control.

Indoor storage rooms, areas and buildings containing Class 2 or Class 3 water-reactive solids and liquids shall be provided with explosion control in accordance with FC 911 and the construction codes, including the Building Code.

6704.1.7 Smoke and heat venting.

Rooms or areas for the storage of water-reactive solids and liquids shall be provided with smoke and heat venting in accordance with FC 910 and the construction codes, including the Building Code.

6704.2 Outdoor storage.

Outdoor storage of water-reactive solids and liquids in quantities exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(3) shall be in accordance with FC 5001, 5003, 5004 and this chapter.

6704.2.1 General.

Outdoor storage of water-reactive solids and liquids shall be within tanks or closed water-tight containers and shall be in accordance with FC 6704.2.2 through 6704.2.5.

6704.2.2 Distance to exposures from Class 3 material outdoor storage areas.

Class 3 water-reactive solids and liquids shall not be stored within 75 feet (22 860 mm) of buildings, lot lines, public streets, private roads or means of egress.

6704.2.3 Distance to exposures from Class 1 and Class 2 material outdoor storage areas.

Outdoor storage of Class 1 and Class 2 water-reactive solids and liquids shall not be within 20 feet (6096 mm) of buildings, lot lines, public streets, private roads or means of egress. A 2-hour fire barrier wall without openings or penetrations, and extending not less than 30 inches (762 mm) above and to the sides of the storage area, is allowed in lieu of such distance. The wall shall either be an independent structure, or the exterior wall of the building adjacent to the storage area.

6704.2.4 Storage conditions.

Class 3 water-reactive solids and liquids shall be limited to piles not greater than 500 cubic feet (14 m 3 ).

6704.2.4.1 Class 1 and Class 2 piles.

Class 1 and Class 2 water-reactive solids and liquids shall be limited to piles not greater than 1,000 cubic feet (28 m 3 ).

6704.2.4.2 Aisle widths.

Aisle widths between piles shall not be less than one-half the height of the pile or 10 feet (3048 mm), whichever is greater.

6704.2.5 Containment.

Secondary containment shall be provided in accordance with FC 5004.2.2.

Section FC 6705. Handling and Use

Open this section

6705.1 General.

Water-reactive solids and liquids in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1) or 5003.1.1(3) shall be handled and used in accordance with FC 5001, 5003, 5005 and this chapter.

Section FC 6706. Manufacturing Restrictions

Open this section

6706.1 Water-reactive solids and liquids classified as a Class IV material.

Water-reactive solids and liquids classified as a Class IV material as defined in Section 42-272 of the Zoning Resolution may be utilized in manufacturing processes or other production in manufacturing districts only when authorized by a special permit pursuant to Section 42-276 of the Zoning Resolution.

6706.1.1 Manufacture of water-reactive solids and liquids classified as a Class IV material.

It shall be unlawful to manufacture water-reactive solids and liquids classified as a Class IV material as defined in Section 42-272 of the Zoning Resolution.

6706.1.2 Storage of water-reactive solids and liquids classified as a Class IV material.

It shall be unlawful to store water-reactive solids and liquids classified as a Class IV material as defined in Section 42-272 of the Zoning Resolution, except that accessory storage authorized by a special permit pursuant to Section 42-276 of the Zoning Resolution shall be allowed.

Section FC 8001. General

Open this section

8001.1 Scope.

This chapter lists the standards that are referenced in this code.

8001.2 Edition.

The edition of each standard referenced in this code shall be as indicated by the standard reference number.

8001.3 Relationship with code and rules.

The application of the referenced standards and their relationship with the provisions of this code and the rules shall be as set forth in FC 102.6.

Section FC 8002. List of Referenced Standards

Open this section

ANSI American National Standards Institute 25 West 43rd Street, Fourth Floor New York, NY 10036 Standard Reference Number Title Reserved.

API American Petroleum Institute 1220 L Street, Northwest Washington, DC 20005-4070 Standard Reference Number Title Std 650—2007 Welded Steel Tanks for Oil Storage, 11th edition, including Addendum 1 (2008), Addendum 2 (2009) and Addendum 3 (2011) Std 653—2009 Tank Inspection, Repair, Alteration, and Reconstruction, 4th edition, including Addendum 1 (2010) and Addendum 2 (2012) RP 1604—1996 Reaffirmed 2010 Closure of Underground Petroleum Storage Tanks Std 2000—2009 Venting Atmosphere and Low Pressure Storage Tanks: Nonrefrigerated and Refrigerated RP 2028—2002 Reaffirmed 2012 Flame Arrestors in Piping Systems RP 2350—2012 Overfill Protection for Storage Tanks in Petroleum Facilities, 4th edition

ASHRAE American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. 1791 Tullie Circle, NE Atlanta, GA 30329 Standard Reference Number Title 15—2013 Safety Standard for Refrigeration Systems

ASME The American Society of Mechanical Engineers Three Park Avenue New York, NY 10016-5990 Standard Reference Number Title A13.1—15 Scheme for the Identification of Piping Systems B31.1—12 Power Piping B31.3—12 Process Piping B31.4—12 Pipeline Transportation Systems for Liquids and Slurries B31.9—17 Building Services Piping BPVC—2010 ASME Boiler and Pressure Vessel Code, (Sections I, II, IV, V, VI and VIII), including 2011 addenda

ASTM ASTM International 100 Barr Harbor Drive West Conshohocken, PA 19428-2959 Standard Reference Number Title D 56—05 (2010) Test Method for Flash Point by Tag Closed Tester D 86—2012 Test Method for Distillation of Petroleum Products at Atmospheric Pressure D 92—12b Test Method for Flash and Fire Points by Cleveland Open Cup D 93—12 Test Method for Flash Point by Pensky-Martens Closed Cup Tester D 323—08 Test Method for Vapor Pressure of Petroleum Products (Reid Method) D 3278—96 (2011) Test Methods for Flash Point of Liquids by Small Scale Closed-cup Apparatus E 681—09 Test Method for Concentration Limits of Flammability of Chemicals (Vapors and Gases) E 1354—13 Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter E 1529—13 Test Method for Determining Effects of Large Hydrocarbon Pool Fires on Structural Members and Assemblies E 1590—13 Test Method for Fire Testing of Mattresses F 2200—13 Standard Specification for Automated Vehicular Gate Construction

CA State of California Department of Consumer Affairs Bureau of Home Furnishings and Thermal Insulation 3485 Orange Grove Avenue North Highlands, CA 95660-5595 Standard Reference Number Title California Technical Bulletin 116 Requirements, Test Procedure and Apparatus for Testing the Flame Retardance of Upholstered Furniture California Technical Bulletin 117—2013 Requirements, Test Procedure and Apparatus for Testing the Smolder Resistance of Materials Used in Upholstered Furniture California Technical Bulletin 129—1992 Flammability Test Procedure for Mattresses for Use in Public Buildings

CGA Compressed Gas Association 4221 Walney Road, 5th Floor Chantilly, VA 20151 Standard Reference Number Title C-7—(2011) Guide to the Preparation of Precautionary Labeling and Marking of Compressed Gas Containers G-8.1—(2007) Nitrous Oxide Systems at Consumer Sites G-13—(2006) Storage and Handling of Silane and Silane Mixtures P-1—(2008) Safe Handling of Compressed Gases in Containers P-18—(2006) Standard for Bulk Inert Gas Systems at Consumer Sites S-1.1—(2011) Pressure Relief Device Standards – Part 1 – Cylinders for Compressed Gases S-1.2—(2005) Pressure Relief Device Standards – Part 2 – Cargo and Portable Tanks for Compressed Gases S-1.3—(2008) Pressure Relief Device Standards – Part 3 – Stationary Storage Containers for Compressed Gases V-1—(2005) Standard for Gas Cylinder Valve Outlet and Inlet Connections

CGR Coast Guard Regulations c/o Superintendent of Documents U.S. Government Printing Office Washington, DC 20402-9325 Standard Reference Number Title Reserved.

CPSC Consumer Product Safety Commission 4330 East West Highway Bethesda, MD 20814 Standard Reference Number Title 16 CFR Section 1500.41 Method for Testing Primary Irritant Substances 16 CFR Section 1500.42 Test for Eye Irritants 16 CFR Section 1500.44 Method for Testing Extremely Flammable and Flammable Solids

DOC U.S. Department of Commerce 100 Bureau Drive, Stop 3460 Gaithersburg, MD 20899 Standard Reference Number Title 16 CFR Part 1632 Standard for the Flammability of Mattress and Mattress Pads (FF 4—72, Amended)

DOJ U.S. Department of Justice Bureau of Alcohol, Tobacco, Firearms and Explosives c/o Superintendent of Documents U.S. Government Printing Office Washington, DC 20402-9325 Standard Reference Number Title 27 CFR Part 555 Commerce in Explosives

DOL U.S. Department of Labor c/o Superintendent of Documents U.S. Government Printing Office Washington, DC 20402-9325 Standard Reference Number Title 29 CFR Section 1910.1000 Air Contaminants 29 CFR Section 1910.1200 Hazard Communication

DOTn U.S. Department of Transportation Office of Hazardous Material Standards 400 7th Street, Southwest Washington, DC 20590 Standard Reference Number Title 49 CFR Parts (100-180) Hazardous Materials Regulations 49 CFR Parts 190-199 Pipeline Safety 49 CFR Parts 350-399 Federal Motor Carrier Safety Regulations

EN European Committee for Standardization (EN) Central Secretariat Rue de Stassart 36 B-10 50 Brussels Standard Reference Number Title European Standard EN 1081: 1998 Resilient Floor Coverings – Determination of the Electrical Resistance

EPA Environmental Protection Agency Ariel Rios Building 1200 Pennsylvania Avenue, NW Washington, DC 20460 Standard Reference Number Title 40 CFR Part 112 Oil Pollution Prevention 40 CFR Part 280 Technical Standards and Corrective Action Requirements for Owners and Operators of Underground Storage Tanks (UST)

FM Factory Mutual Global Research Standards Laboratories Department 1301 Atwood Avenue, P.O. Box 7500 Johnston, RI 02919 Standard Reference Number Title ANSI/FM 4996—13 Approval Standard for Classification of Pallets and Other Material Handling Products as Equivalent to Wood Pallets

IIAR International Institute of Ammonia Refrigeration 1001 N. Fairfax Street, Suite 503 Alexandria, VA 22314 Standard Reference Number Title IIAR-2—2014 Equipment, Design and Installation of Closed-Circuit Ammonia Refrigerating Systems IIAR-6—2019 Inspection, Testing, and Maintenance of Safe Closed-Circuit Ammonia Refrigeration Systems IIAR-7—2019 Developing Operating Procedures for Closed-Circuit Ammonia Mechanical Refrigerating Systems IIAR-8—2020 Decommissioning of Closed-Circuit Ammonia Refrigeration Systems IIAR-9—2020 Minimum System Safety Requirements for Existing Closed-Circuit Ammonia Refrigeration Systems

IKECA International Kitchen Exhaust Cleaning Association 100 North 20th Street, Suite 400 Philadelphia, PA 19103 Standard Reference Number Title C10—2011 ANSI/IKECA Standard for Cleaning of Commercial Kitchen Exhaust Systems

ISO International Organization for Standardization (ISO) ISO Central Secretariat 1 ch, de la Voie-Creuse, Case postale 56 CH-1211 Geneva 20, Switzerland Standard Reference Number Title ISO 8115—86 Cotton Bales – Dimensions and Density

NEMA National Electrical Manufacturer's Association 1300 N. 17th Street Suite 1847 Rosslyn, VA 22209 Standard Reference Number Title 250—2003 Enclosures for Electrical Equipment (1,000 Volt Maximum)

NFPA National Fire Protection Association Batterymarch Park Quincy, MA 02269 Standard Reference Number Title 2—16 Hydrogen Technologies Code 10—13 Portable Fire Extinguishers 11—10 Low-, Medium- and High-Expansion Foam 12—11 Carbon Dioxide Extinguishing Systems 12A—09 Halon 1301 Fire Extinguishing Systems 13—16 Installation of Sprinkler Systems 13R—16 Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies 15—17 Standard for Water Spray Fixed Systems for Fire Protection 16—15 Installation of Foam-Water Sprinkler and Foam-Water Spray Systems 17—13 Dry Chemical Extinguishing Systems 17A—13 Wet Chemical Extinguishing Systems 20—16 Installation of Stationary Pumps for Fire Protection 22—13 Water Tanks for Private Fire Protection 24—13 Installation of Private Fire Service Mains and their Appurtenances 25—14 Inspection, Testing and Maintenance of Water-Based Fire Protection Systems 30—12 Flammable and Combustible Liquids Code 30A—15 Code for Motor Fuel-Dispensing Facilities and Repair Garages 30B—15 Manufacture and Storage of Aerosol Products 32—16 Standard for Drycleaning Facilities 33—16 Spray Application Using Flammable or Combustible Materials 34—15 Dipping, Coating, and Printing Processes Using Flammable or Combustible Liquids 35—11 Manufacture of Organic Coatings 40—11 Storage and Handling of Cellulose Nitrate Film 45—15 Fire Protection for Laboratories Using Chemicals 51—13 Design and Installation of Oxygen-Fuel Gas Systems for Welding, Cutting, and Allied Processes 52—13 Vehicular Natural Gas Fuel Systems Code 55—13 Compressed Gases and Cryogenic Fluids Code 56—12 Standard for Fire and Explosion Prevention During Cleaning and Purging of Flammable Gas Piping Systems 58—14 Liquefied Petroleum Gas Code 61—13 Prevention of Fires and Dust Explosions in Agricultural and Food Processing Facilities 68—2018 Standard on Explosion Protection by Deflagration Venting 69—14 Explosion Prevention Systems 72—16 National Fire Alarm and Signaling Code 76—16 Standard for the Fire Protection of Telecommunications Facilities 77—07 Recommended Practice on Static Electricity 80—13 Fire Doors and Other Opening Protectives 85—15 Boiler and Combustion System Hazards Code 86—15 Ovens and Furnaces 88A—19 Standard for Parking Structures 96—17 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations 99—15 Health Care Facilities Code 105—13 Standard for Smoke Door Assemblies and Other Opening Protectives 110—13 Emergency and Standby Power Systems 111—13 Stored Electrical Energy Emergency and Standby Power Systems 120—15 Fire Prevention and Control in Coal Mines 130—20 Fixed Guideway Transit and Passenger Rail Systems 140—18 Standard on Motion Picture and Television Production Studio Soundstages, Approved Production Facilities, and Production Locations 160—11 Use of Flame Effects Before an Audience 241—13 Safeguarding Construction, Alteration, and Demolition Operations 260—13 Methods of Tests and Classification System for Cigarette Ignition Resistance of Components of Upholstered Furniture 261—13 Method of Test for Determining Resistance of Mock-Up Upholstered Furniture Material Assemblies to Ignition by Smoldering Cigarettes 289—13 Method of Fire Test for Individual Fuel Packages 303—11 Fire Protection Standard for Marinas and Boatyards 307—2021 Standard for the Construction and Fire Protection of Marine Terminals, Piers, and Wharves 318—15 Standard for the Protection of Semiconductor Fabrication Facilities 326—10 Standard for the Safeguarding of Tanks and Containers for Entry, Cleaning or Repair 385—12 Standard for Tank Vehicles for Flammable and Combustible Liquids 400—13 Hazardous Materials Code 407—12 Aircraft Fuel Servicing 484—15 Combustible Metals 495—13 Explosive Materials Code 498—13 Safe Havens and Interchange Lots for Vehicles Transporting Explosives 502—20 Road Tunnels, Bridges and Other Limited Access Highways 505—13 Fire Safety Standard for Powered Industrial Trucks Including Type Designations, Areas of Use, Conversions, Maintenance, and Operations 652—16 Standard on the Fundamentals of Combustible Dust 654—13 Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids 655—12 Prevention of Sulfur Fires and Explosions 664—12 Standard for the Prevention of Fires and Explosions in Wood Processing and Woodworking Facilities 701—10 Standard Methods of Fire Tests for Flame-Propagation of Textiles and Films 704—12 Identification of the Hazards of Materials for Emergency Response 720—15 Installation of Carbon Monoxide (CO) Detection and Warning Equipment 750—15 Standard on Water Mist Fire Protection Systems 780—08 Standard for the Installation of Lightning Protection Systems 820—08 Fire Protection in Wastewater Treatment and Collection Facilities 850—10 Fire Protection for Electric Generating Plants and High Voltage Direct Current Converter Stations 855—20 Standard for the Installation of Stationary Energy Storage Systems 1122—13 Model Rocketry 1123—14 Fireworks Display 1124—17 Code for the Manufacture, Transportation, Storage, and Retail Sales of Fireworks and Pyrotechnic Articles 1125—12 Manufacture of Model Rocket and High Power Rocket Motors 1126—11 Use of Pyrotechnics Before a Proximate Audience 1127—13 High Power Rocketry 2001—15 Clean Agent Fire Extinguishing Systems 2010—15 Fixed Aerosol Fire Extinguishing Systems

UL Underwriters Laboratories, Inc. 333 Pfingsten Road Northbrook, IL 60062 Standard Reference Number Title 30—95 Metal Safety Cans – with Revisions through July 2009 80—07 Standard for Steel Tanks for Oil-Burner Fuels and Other Combustible Liquids – with revisions through August 2009 142—06 Standard for Steel Aboveground Tanks for Flammable and Combustible Liquids – with revisions through February12, 2010 268—09 Standard for Smoke Detectors for Fire Alarm Systems 300—05 Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment – with revisions through July 2010 300A—06 Outline of Investigation for Extinguishing System Units for Residential Range Top Cooking Surfaces 325—02 Door, Drapery, Gate, Louver, and Window Operators and Systems – with Revisions through February 2006 499—05 Standard for Electric Heating Appliances – with revisions through February 2013 864—03 Standard for Control Units and Accessories for Fire Alarm Systems – with revisions through December 2014 900—04 Air Filter Units – with revisions through February 2012 1275—05 Flammable Liquid Storage Cabinets – with Revisions through February 2010 1313—93 Standard for Nonmetallic Safety Cans for Petroleum Products – with Revisions through November 2012 1315—95 Standard for Safety for Metal Waste Paper Containers – with Revisions through September 2012 1564—15 Standard for Industrial Battery Chargers 1741—10 Standard for Inverters, Converters, Controllers and Interconnection System Equipment for Use With Distributed Energy Resources 1973—18 Standard for Batteries for Use in Stationary, Vehicle Auxiliary Power and Light Electric Rail (LER) Applications 1975—06 Fire Tests for Foamed Plastics Used for Decorative Purpose 2017—08 Standard for General-Purpose Signaling Devices and Systems – with revisions through May 2011 2075—13 Standard for Gas and Vapor Detectors and Sensors 2085—97 Protected Aboveground Tanks for Flammable and Combustible Liquids – with Revisions through September 2010 2200—12 Standard for Stationary Engine Generator Assemblies – with revisions through June 2013 2208—10 Solvent Distillation Units – with revisions through March 2011 2272—16 Standard for Electrical Systems for Personal E-Mobility Devices 2335—10 Fire Tests of Storage Pallets – with Revisions through September 2012 2360—00 Standard for Test Methods for Determining the combustibility characteristics of Plastics Used in Semi-Conductor Tool Construction – with revisions through May 2013 2849—20 Standard for Electrical Systems for eBikes 9540—20 Standard for Energy Storage Systems and Equipment 9540A—19 Standard for Test Method for Evaluating Thermal Runaway Fire Propagation in Battery Energy Storage Systems, 4th edition, November 2019

Section FC A01. Certificates

Open this section

A01.1 Certificate fees.

Applicants for certificates required pursuant to the provisions of this code or the rules shall pay the fees specified in this section. Fees for certificates shall be per year, except as otherwise indicated. Fees for written and practical examinations shall be per examination.

Fee 1. Blasting contractor certificate Original application $105.00 Renewal application $50.00 2. Certificate of approval (per application) Original application $625.00 Amended application $625.00 Change of ownership $625.00 Change in manufacturing process, chemical composition or design $625.00 Renewal application $50.00 Change of identification, including change in name of article, model number or name of manufacturer $210.00 3. Certificate of fitness Original application (including written examination) (for 3 years) (except fire and life safety director) $25.00 Fire and life safety director Original application (including one written examination) (for 3 years) $25.00 Each additional written examination $25.00 Practical (on-site) examination for fire and life safety director (fire safety and non-fire emergency components) $750.00 Practical (on-site) examination (fire safety component only) $445.00 Practical (on-site) examination (non-fire emergency component only) $305.00 Renewal application (without examination) $5.00 4. Certificate of license for flammable and combustible liquid storage systems Original application (including written examination) $145.00 Renewal application (without examination) $15.00 5. Certificate of license for liquid motor fuel storage and dispensing systems Original application (including written examination) $145.00 Renewal application (without examination) $15.00 6. Certificate of operation Original application $3500.00 Renewal application $2500.00 7. Certificate of qualification for refrigerating system operating engineer Original application (including written examination) (for 3 years) $60.00 Practical examination $225.00 Renewal application (without examination) $5.00 8. Commercial cooking exhaust system servicing company certificate Original application $105.00 Renewal application $50.00 9. Fireworks contractor certificate Original application $110.00 Renewal application $110.00 10. Fumigation and insecticidal fogging operation company certificate Original application $105.00 Renewal application $50.00 11. Portable fire extinguisher sales company certificate Original application $105.00 Renewal application $50.00 12. Portable fire extinguisher servicing company certificate Original application $100.00 Renewal application $50.00 13. Pyrotechnic supplier certificate Original application $105.00 Renewal application $50.00 14. Registration of expeditors Original registration application $105.00 Renewal registration application $50.00 15. Smoke detector maintenance company certificate Original application $105.00 Renewal application $50.00 16. ARC system testing company certificate Original application $105.00 Renewal application $50.00 Original portable radio programming (per radio) $75.00 Portable radio inspection (per radio) $75.00 17. Fire alarm system installation, inspection, testing and servicing Original application $105.00 Renewal application $50.00

Section FC A02. Training Schools

Open this section

A02.1 Training school accreditation fees.

Applicants for training school accreditation required pursuant to the provisions of this code or the rules shall pay the fees specified in this section. All accreditation fees are per year, unless otherwise indicated.

Fee 1. FLS director and FEP Coordinator training school Original application $2,940.00 Renewal application $420.00 2. Refrigeration and related technology training school Original application $2,940.00 Renewal application $420.00 3. Construction site fire safety manager training schools Original application $2,940.00 Renewal application $420.00 4. Continuing education training schools, including training schools for building operation, maintenance and recordkeeping, and active shooter and medical emergency preparedness Original application $2,940.00 Renewal application $420.00

Section FC A03. Permits, Inspections and Plan Examinations

Open this section

A03.1 Permit, inspection and plan examination fees.

The owner or applicant shall pay the following fees for permits, inspections, witnessing of tests, and other services. All such fees are per year, except when based on frequency of inspection or hourly rate, as indicated. Hourly rates are per inspector.

Fee 1. Aerosol products Store, handle or use up to and including 2,500 pounds (1135 kg) $105.00 Store, handle or use more than 2,500 pounds (1135 kg) $210.00 2. Alcohol-based hand rubs Store, handle or use more than 275 gallons (1041 L) of flammable or combustible alcohol-based hand rubs in portable container designed for consumer use with a capacity not exceeding 68 fluid ounces (2.01 L), that does not require handling of the contents $105.00 3. Asphalt melters Store, handle or use an asphalt melter $105.00 4. Assembly occupancies (places of assembly) Fire safety inspection/permit (frequency of inspection as required by code or rule) Occupancy 75 to 149 $415.00 Occupancy 150 to 499 $520.00 Occupancy 500 to 999 $625.00 Occupancy 1,000 to 2,499 $725.00 Occupancy 2,500 to 9,999 $830.00 Occupancy 10,000 or greater, and arenas and stadiums (per hour) $210.00 5. Automotive liquid motor fuel-dispensing facilities Establish and operate an automotive liquid motor fuel-dispensing facility $105.00 Precision test of underground tank and piping (frequency of inspection as required by code or rule) (per hour) $210.00 Leak detection functionality test (per hour) (frequency of test as required by code or rule) $210.00 Tank test (per site) (frequency of test as required by code or rule) $355.00 Tank reopening and repair (frequency of inspection as required by code or rule) $320.00 Installation and alteration (frequency of inspection as required by code or rule) With discharge lines For tank with capacity of 4,000 gallons (15 140 L) or less $980.00 Each additional tank $210.00 For tank with a capacity greater than 4,000 gallons (15 140 L) $1,210.00 Each additional tank $420.00 Without discharge lines For tank with capacity of 4,000 gallons (15 140 L) or less $665.00 Each additional tank $195.00 For tank with a capacity greater than 4,000 gallons (15 140 L) $840.00 Each additional tank $385.00 Fire extinguishing system test Initial installation acceptance test (per system) (per hour) $210.00 Periodic test (frequency of test as required by code or rule) (per system) (per hour) $210.00 6. Automotive salvage and wrecking facilities Establish and operate an automotive salvage and wrecking facility $105.00 7. Aviation facilities and operations Maintain or operate an aircraft-fueling vehicle $105.00 Conduct a helicopter landing at other than an approved heliport, helistop or airport $315.00 Conduct a helicopter lift operation $315.00 Conduct a hot air balloon operation $315.00 8. Bulk plants and terminals and bulk transfer facilities Store and/or use flammable and combustible liquids in stationary tanks (per equivalent unit of storage) $70.00 Use following algorithm to determine "equivalent unit of storage": Equivalent unit of storage = (number of millions of gallons of tank capacity at facility) + (3 x number of tanks at facility) Fire protection system inspection (frequency of inspection as required by code or rule) (per hour) $210.00 Fire department connection inspection (frequency of inspection as required by code or rule) (per hour) $210.00 Periodic inspection and/or test (frequency of inspection as required by code or rule) (per hour) $210.00 Installation of devices, equipment and systems (new or altered), including fire protection systems (frequency of inspection as required by code or rule) (per hour) $210.00 9. CNG motor fuel-dispensing facilities Establish and operate a CNG motor fuel-dispensing facility $625.00 Installation of devices, equipment and systems (new or altered), including fire protection systems (frequency of inspection as required by code or rule) (per hour) $210.00 10. Cellulose nitrate film Store Up to and including 100,000 feet (30 480 000 mm) $105.00 More than 100,000 feet (30 480 000 mm) $210.00 Handle and use $105.00 11. Coke-fueled salamanders Store, handle or use coke-fueled salamanders at a construction site $105.00 12. Combustible dust-producing operations Establish and operate a combustible dust-producing facility $105.00 13. Combustible fibers Store less than 20,000 pounds (9080 kg) $105.00 Store 20,000 pounds (9080 kg) or more $210.00 14. Combustible liquids (excluding paints, varnishes and lacquers) Store, handle or use liquids with a flash point of 300°F (149°C) or less In containers each equal to or less than 55 gallons (208 L): Up to and including 550 gallons (2082 L) $105.00 More than 550 gallons (2082 L) up to and including 2,500 gallons (9463 L) $210.00 Each additional 2,500 gallons (9463 L) or portion thereof $105.00 In tanks each larger than 55 gallons (208 L) Up to and including twenty tanks $125.00 More than twenty tanks $415.00 Store, handle or use fuel oil in tanks each larger than 55 gallons (208 L) In buildings where no oil burner certificate of fitness is required $90.00 In buildings where an oil burner certificate of fitness is required, or for any other purpose Up to and including twenty tanks $105.00 More than twenty tanks $210.00 Store kerosene Store for retail sale $105.00 Store for wholesale $210.00 Store for use $105.00 Store or handle essential oils Less than 500 pounds (227 kg) $50.00 500 pounds (227 kg) or more $105.00 Store, handle or use petroleum products with a flash point exceeding 300°F (149°C) In containers each equal to or less than 55 gallons (208 L) Up to and including 550 gallons (2082 L) $105.00 More than 550 gallons (2082 L) up to and including 2,500 gallons (9463 L) $210.00 Each additional 2,500 gallons (9463 L) or portion thereof $105.00 In tanks each larger than 55 gallons (208 L) Up to and including twenty tanks $125.00 More than twenty tanks $415.00 Store, handle or use waxes, oils and fats (animal, vegetable or mineral) More than 400 pounds (182 kg) of wax $105.00 More than 250 gallons (946 L) of oils and/or fats $105.00 Manufacture combustible liquid $210.00 Store and/or use fuel oil stored on a marine vessel or watercraft moored to or anchored at privately-owned waterfront property Included in fees set forth in FC A03.1(8); tank on the vessel is treated as a stationary tank Store and use fuel oil on a mobile heating and power generation trailer (citywide) $105.00 15. Combustible materials Store more than 2,000 cubic feet (57 m 3 ) $105.00 Store flammable plastic foam Up to and including 6,000 pounds (2724 kg) $105.00 More than 6,000 pounds (2724 kg) $210.00 16. Commercial kitchen Establish and operate each commercial kitchen or other separate cooking area that is a commercial kitchen $70.00 Acceptance test of fire extinguishing system As set forth in FC A03.1(29) 17. Compressed gases Store, handle or use corrosive $210.00 Store, handle or use flammable (nonliquefied) $210.00 Store, handle or use flammable (liquefied, noncryogenic, except LPG) $210.00 Store, handle or use liquefied petroleum gas (LPG) at construction site $210.00 Store, handle or use nonflammable (nonliquefied) $210.00 Store, handle or use nonflammable (liquefied, noncryogenic) $210.00 Store, handle or use anhydrous liquid ammonia $210.00 Store, handle or use carbon dioxide, low pressure carbon dioxide beverage dispensing systems $105.00 Store, handle or use carbon dioxide, all other $210.00 Store, handle or use acetylene $210.00 Store, handle or use highly toxic $210.00 Store, handle or use liquefied chlorine $105.00 Store, handle or use toxic $210.00 Store, handle or use unstable (reactive) $210.00 Store, handle or use water reactive $210.00 Store, handle or use pyrophoric $210.00 18. Compressing gases Maintain or operate a device, equipment or system to compress flammable gas Compress to a pressure up to and including 15 psig (103.4 kPa) $210.00 Compress to a pressure more than 15 psig (103.4 kPa) $415.00 Maintain or operate a device, equipment or system to compress nonflammable gas $210.00 Maintain or operate a device, equipment or system to compress atmospheric air Up to and including three compressors $105.00 Each additional six compressors or portion thereof $105.00 19. Construction sites Fire safety inspection (annual fee) $315.00 20. Corrosive materials Store, handle or use solid $50.00 Store, handle or use liquid In portable containers $50.00 In tanks (each unit of 1,000 gallons (3785 L) or portion thereof) $50.00 21. Cryogenic fluids Store, handle or use flammable $210.00 Store, handle or use nonflammable Up to and including 1,300 gallons (4921 L) $210.00 Each additional 3,900 gallons (14 762 L) or portion thereof $105.00 22. Distilleries Establish and operate a distillery, including manufacturing or distilling liquor, spirits or alcohol $210.00 Store liquor, spirits, raw alcohol or other alcohol (except retail liquor stores and premises where alcohol is sold for consumption on the premises) In containers, each equal to or less than 55 gallons (208 L), storage tanks, or intermediate bulk container More than 500 gallons (1893 L) up to and including 1,500 gallons (5678 L) $105.00 More than 1,500 gallons (5678 L) up to and including 8,000 gallons (30 283 L) $210.00 Each additional 5,000 gallons (18 925 L) or portion thereof in tanks each larger than 55 gallons (208 L) or intermediate bulk container $105.00 23. Dry cleaning facilities Establish and operate a dry cleaning facility $125.00 24. Decorations Fire safety inspection of combustible decorations and scenery in: An assembly occupancy Included in fee set forth in FC A03.1(4) Other public gathering places Included in fee set forth in FC A03.1(68) 25. Energy storage systems, stationary Install and operate a stationary energy storage system $210.00 26. Explosives Store, handle and sell explosives at vendor's facility (frequency of inspection as required by code or rule) Initial inspection $210.00 Subsequent inspection (per hour) $210.00 Store, handle and use explosives at a job site (frequency of inspection as required by code or rule) (per hour) $210.00 Store small arms ammunition for sale Up to and including 25 percent of the maximum allowable code quantities $105.00 More than 25 percent of the maximum allowable code quantities $210.00 Store black powder or smokeless propellant Less than 14 pounds (6.4 kg) $50.00 14 pounds (6.4 kg) or more $105.00 Store, sell or offer for sale low explosives at a location other than a vendor's facility or job site (frequency of inspection as required by code) (per hour) $210.00 27. Fire apparatus services (as required by code, rule, permit or hazardous materials release) Firefighting apparatus (per hour) (per apparatus) $525.00 Other services Hourly fee based on cost of services, including travel time, overtime, expenses and overhead 28. In-building auxiliary radio communication systems and other in-building radio communication systems To maintain and operate an in-building auxiliary radio communication system or other in-building radio communication system $105.00 29. Fire protection systems Acceptance tests Commercial cooking fire extinguishing system (per system) Mechanical only $285.00 Mechanical and electrical $580.00 Fire and carbon monoxide alarm and communication systems (per system) (per hour) $210.00 Fire extinguishing systems, mechanical and electrical, (per system) (per hour) Aerosol $210.00 Carbon dioxide $210.00 Clean agent $210.00 Dry chemical $210.00 Foam $210.00 Water mist $210.00 Wet chemical $210.00 Fire and booster pumps (per pump) (per hour) Electric driven, mechanical and electrical $210.00 Engine driven $210.00 Periodic tests (frequency of inspection as required by code or rule) Sprinkler system One fire department connection $320.00 Each additional fire department connection $275.00 Trip test (per valve) (per hour) $210.00 Flow test $105.00 Standpipe system One fire department connection $365.00 Each additional fire department connection $210.00 Combination sprinkler/standpipe system One fire department connection $365.00 Each additional fire department connection $210.00 30. Fireworks displays Permit application $210.00 Site inspection (per hour) $210.00 Monitoring of fireworks display (including pre-display operations and post-display safety measures) (per hour) $210.00 31. Flammable liquids (excluding paint, varnish and lacquer) Store, handle or use in containers, each equal to or less than 55 gallons (208 L) Up to and including 550 gallons (2082 L) $105.00 More than 550 gallons (2082 L) up to and including 2,500 gallons (9463 L) $210.00 Each additional 2,500 gallons (9463 L) or portion thereof $105.00 Store, handle or use in tanks, each larger than 55 gallons (208 L) Up to and including ten tanks $210.00 More than ten tanks $415.00 Store, handle and use gasoline or other petroleum products in containers, each equal to or less than 55 gallons (208 L) Up to and including 55 gallons (208 L) $50.00 More than 55 gallons (208 L) $105.00 Store and handle for retail sale Up to and including 100 gallons (379 L) $95.00 More than 100 gallons (379 L) $105.00 Store and use gasoline in quantities exceeding 2 1/2 gallons (9.5 L) in a single item of portable fuel equipment or an aggregate of 10 gallons (38 L) in all portable fueled equipment $105.00 Manufacture flammable liquid $210.00 Manufacture or distill liquor, spirits or alcohol Included in fee set forth in FC A03.1(22) 32. Flammable solids Store, handle or use $105.00 Store, handle and use nitrocellulose products in manufacture $210.00 33. Fleet fueling Transfer of Class II and III liquids directly from a cargo tank into the fuel tank of a motor vehicle $210.00 34. Floor finishing operations Conduct a floor finishing operation $105.00 35. Fruit and crop ripening Establish and operate a fruit or crop ripening facility $105.00 36. Fumigation and insecticidal fogging Establish and operate a toxic or flammable fumigation and insecticidal fogging facility $105.00 37. High rise office buildings, and hotels and motels Fire safety inspection (frequency of inspection as required by code or rule) $570.00 38. Highly toxic materials Store, handle or use liquid $105.00 Store, handle or use solid $105.00 39. Hazardous production materials (HPM) Store, handle or use hazardous production materials at an HPM facility $315.00 40. High-piled combustible storage Maintain or operate a high-piled combustible storage facility Up to and including 5,000 square feet (465 m 2 ) of high-piled combustible storage $105.00 More than 5,000 square feet (465 m 2 ) of high-piled combustible storage $210.00 41. Hot work operations Citywide operations $105.00 Site-specific hot work program $105.00 Use of flammable gas with oxygen $105.00 Use of flammable gas without oxygen at a construction site $105.00 Use of electric arc equipment at a construction site $105.00 Use of any open flame in a torch-applied roof system $105.00 Public demonstration of hot work, other than in an accredited educational institution or program $105.00 42. Hydrogen fuel gas rooms Establish and operate a hydrogen fuel gas room for the generation, storage, handling and use of gaseous hydrogen $210.00 43. Hydrogen motor fuel-dispensing facilities Establish and operate a hydrogen motor fuel-dispensing facility $105.00 44. Industrial furnaces Install and operate an industrial furnace $105.00 45. Inspections, re-inspections and witnessed tests Inspections or witnessed tests required or authorized by the code or rules, the fee for which is not otherwise specified herein (per hour) $210.00 Re-inspections in connection with permit or inspection required or authorized by code or rule, to confirm correction of violation(s) (per hour) $210.00 Failure to provide access for a scheduled inspection or witnessed test $105.00 Late cancellation of a scheduled inspection or witnessed test (notice of less than one business day) $105.00 46. Laboratories, non-production Maintain or operate a non-production laboratory Original permit (per laboratory unit) Up to and including 2,500 square feet (232 m 2 ) $210.00 More than 2,500 square feet (232 m 2 ) $315.00 Renewal permits (per laboratory unit) Up to and including 2,500 square feet (232 m 2 ) $105.00 More than 2,500 square feet (232 m 2 ) $210.00 47. Liquefied petroleum gases Store, handle or use $210.00 48. Lumber yards Storage of lumber at lumber yards $105.00 49. Marine liquid motor fuel-dispensing facilities Establish and operate a marine liquid motor fuel-dispensing facility $105.00 Precision test of underground tank and piping (frequency of inspection as required by code or rule) (per hour) $210.00 Leak detection functionality test (frequency of test as required by code or rule) (per hour) $210.00 Tank test (per site) (frequency of test as required by code or rule) $355.00 Tank reopening and repair (frequency of inspection as required by code or rule) $320.00 Installation and alteration (frequency of inspection as required by code or rule) With discharge lines For tank with capacity up to and including 4,000 gallons (15 140 L) $980.00 Each additional tank $210.00 For tank with a capacity more than 4,000 gallons (15 140 L) $1,210.00 Each additional tank $420.00 Without discharge lines For tank with capacity up to and including 4,000 gallons (15 140 L) $665.00 Each additional tank $195.00 For tank with a capacity more than 4,000 gallons (15 140 L) $840.00 Each additional tank $385.00 Fire extinguishing system test Initial installation acceptance test (per system) $750.00 Periodic test (frequency of test as required by code or rule) (per system) $750.00 50. Methane recovery facilities Establish and operate a methane recovery facility (per hour) $210.00 Installation of devices, equipment and systems (new or altered), (frequency of inspection as required by code or rule) (per hour) $210.00 Periodic inspection/test (frequency of inspection as required by code or rule) (per hour) $210.00 51. Natural gas liquefaction facilities Establish and operate natural gas liquefaction facility (per hour) $210.00 Installation of devices, equipment and systems (new or altered), (frequency of inspection as required by code or rule) (per hour) $210.00 Periodic inspection/test (frequency of inspection as required by code or rule) (per hour) $210.00 52. Non-tobacco hookah establishments Establish and operate a non-tobacco hookah establishment $105.00 53. Open flames Fire safety inspection for use of an open flame in: A place of assembly Included in fee set forth in FC A03.1(4) Other public gathering places Included in fee set forth in FC A03.1(68) A covered mall (per hour) $210.00 54. Organic coatings Manufacture organic coating $210.00 55. Organic peroxides Store, handle or use liquid $210.00 Store, handle or use solid $210.00 56. Oxidizing materials Store, handle or use liquid (per hour) $210.00 Store, handle or use solid (per hour) $210.00 Store, handle or use hydrogen peroxide, (concentration of 35 percent or more) Up to and including 150 gallons (568 L) in containers $50.00 More than 150 (568 L) gallons in containers $105.00 In bulk, per 1,000 gallons (3785 L) or portion thereof $50.00 57. Paints, varnishes and lacquers with a flash point of 300°F (149°C) or less Store, handle or use paint, varnish and lacquer Up to and including 1,000 gallons (3785 L) $105.00 More than 1,000 gallons (3785 L) $210.00 Manufacture, mix or compound $210.00 58. Plan examinations Review of design and installation documents, except as otherwise provided in FC A03.1(51)* $420.00 * Editor's note: correct reference should be FC A03.1(58). Review of ARC system commissioning plan Original submission $420.00, plus $50.00 per building floor included in application Five-year recertification $420.00, plus $50.00 per building floor included in application Review of design and installation documents for commercial cooking systems $210.00 Review of fire protection plan $420.00 Review of fire safety and evacuation plan $210.00 Review of emergency action plan Original application $525.00 Amended application (per hour) (total not to exceed $525.00) $210.00 Review of combined fire safety and evacuation plan and emergency action plan Original application $630.00 Amended application (per hour) (total not to exceed $630.00) $210.00 Review of professionally certified application $210.00 Supplemental review of new technology applications (including plans filed pursuant to FC 102.8 and 104.9) and other applications requiring complex technical analyses $525.00 Late plan filing Filing of design and installation documents for new or altered facility or installation from the date of commencement of work without approved design and installation documents to one year from such date 50% surcharge Filing of design and installation documents for new or altered facility or installation more than one year after the date of commencement of work without approved design and installation documents 100% surcharge 59. Portable fueled space heaters Store, handle or use $210.00 60. Pyrophoric materials Store, handle or use liquid $105.00 Store, handle or use solid $105.00 61. Pyroxylin plastics Store, handle or use raw pyroxylin plastics $105.00 Use of raw pyroxylin plastics in manufacture of products $210.00 62. Refrigerating systems Install and operate a refrigerating system (per compressor) $105.00 63. Repair garages Establish and operate a repair garage $105.00 64. Smoking rooms Fire safety inspection in health care facilities (frequency of inspection as required by code or rule) $105.00 65. Special effects Special effects permit application $210.00 Production company special effects permit application $210.00 Site inspection (per hour) $210.00 Central storage facility permit application $210.00 Monitoring of special effects operations (per hour) $210.00 66. Special services Requests for an inspection, witnessing of test, or other services, at times other than regular business hours, or other special circumstances Hourly fee based on cost of services, including travel time, overtime, expenses and overhead 67. Spraying and dipping operations Conduct a spraying or dipping operation $310.00 68. Street fairs and other public gatherings or gathering places Review of site plan (per hour) $210.00 Fire safety inspection (per hour) $210.00 69. Sulfur Store, handle or use up to and including 1,500 pounds (681 kg) $50.00 Store, handle or use more than 1,500 pounds (681 kg) $105.00 70. Tar kettles Store, handle or use a tar kettle $105.00 71. Tire-rebuilding plants Establish and operate a tire-rebuilding plant $210.00 72. Tires, scrap tires and tire byproducts Store tires, scrap tires and tire byproducts $70.00 73. Toxic materials Store, handle or use liquid $105.00 Store, handle or use solid $105.00 74. Transportation of hazardous materials Combustible liquid by motor vehicle $105.00 Compressed gas by motor vehicle $105.00 Explosives by marine vessel or watercraft (per hour) $210.00 Explosives by motor vehicle (per hour) $210.00 Firefighting apparatus escort (as required by code or rule) (per hour) (per apparatus) $525.00 Flammable liquid by motor vehicle $105.00 75. Unstable (reactive) materials Store, handle or use liquid $105.00 Store, handle or use solid $105.00 76. Water-reactive materials Store, handle or use liquid $105.00 Store, handle or use solid $105.00 Store calcium carbide Up to and including 600 pounds (272 kg) $105.00 More than 600 pounds (272 kg) $210.00

Section FC A04. Administrative Services

Open this section

A04.1 Fees for administrative services.

Fees for administrative services shall be as follows:

Fee 1. Transcripts and special reports (per transcript or special report) (per premises) $10.00 2. Replacement of lost permit or certificate $5.00 3. Application for modification of certificate (except certificate of approval) $5.00 4. Violation dismissal notice (per violation) $5.00 5. Application for modification $200.00 6. Removal and storage of contraband material (per article, device or equipment reclaimed) $65.00 7. Payment returned for insufficient funds (per item) $20.00 8. Vacate order processing (upon dismissal for compliance) $525.00 9. Document management for fire alarm system, emergency alarm system, auxiliary radio communication system or fire extinguishing system application and for any other application not requiring a work permit from the Department of Buildings (per application) $165.00 10. Certification of corrected defects in fire alarm system installations (per certification) Certification of defects with or without documentation $210.00 Certification of required documentation only $105.00 11. Project authorization $105.00

Section FC A05. Late Renewals

Open this section

A05.1 Penalties for late renewals.

Penalties and fees for late renewal of certificates and permits shall be as follows:

Fee 1. Certificates and permits As set forth in FC 117.3