NYC Administrative Code Title 29, Chapter 2 New York City Fire Code, part 6 of 15
Section FC 905 to Section FC 2305: 65 sections.
Section FC 905. Standpipe Systems
905.1 General.
Standpipe systems shall be provided where required by the construction codes, including the Building Code, this code or the rules. Fire hose threads used in connection with standpipe systems shall be approved by the commissioner. Standpipe systems in buildings used for high-piled combustible storage shall be in accordance with FC Chapter 32.
905.1.1 Standpipe system operator.
In buildings with a multi-zone standpipe system, such system shall be continuously under the personal supervision of a person holding a certificate of fitness, who shall be immediately available to assist the department in the operation of such system.
905.2 Installation standards.
Standpipe systems shall be installed in accordance with the construction codes, including the Building Code.
905.3 Standpipe elevation markings.
The elevation above grade of each floor level shall be conspicuously marked on or adjacent to the standpipe hose outlet on each floor of a building or structure more than 240 feet in height. The elevation shall be indicated in feet. In lieu of markings, durable signage may be posted adjacent to the standpipe hose outlet on each floor.
905.4 Standpipe elevation chart.
A chart listing the floor number (consistent with elevator operation) and corresponding elevation above grade of each floor level of the building shall be prepared for each building or structure more than 240 feet in height and kept at the fire command center or other approved location.
905.5 Fire department connections.
Fire department connections serving a standpipe system shall be marked in accordance with FC 912.
905.6 Reserved.
905.7 Cabinets.
Cabinets containing firefighting equipment, such as standpipes, fire hose, portable fire extinguishers and water supply control valves, shall not be obstructed from use or obscured from view.
905.8 Reserved.
905.9 Valve supervision.
Valves controlling water supplies shall be supervised in the open position so that a change in the normal position of the valve will generate a supervisory signal at the central station required by FC 903.4. Where a fire alarm system is provided, a signal shall also be transmitted to the fire alarm system control panel.
Exceptions:
1. Valves to underground key or hub valves in roadway boxes provided by the municipality or public utility do not require supervision.
2. Valves locked in the normal position and inspected as provided in this code in buildings not equipped with a fire alarm system.
905.10 During construction.
Standpipe systems required during construction, alteration and demolition operations shall be provided in accordance with Chapter 33 of the Building Code and FC 3313.
905.11 Reserved.
905.12 Maintenance.
Standpipe systems shall be maintained, including all required inspection, testing and servicing, in accordance with this section, FC 901.6 and NFPA 25.
905.12.1 Standpipe hydrostatic pressure and flow tests.
Upon order of the commissioner, but at least once every 5 years, the standpipe system shall be subjected to a hydrostatic pressure test and a flow test to demonstrate its suitability for department use. These tests shall be conducted in compliance with the requirements of the rules and shall be conducted at the owner's risk, by his or her representative before a representative of the department.
Section FC 906. Portable Fire Extinguishers
906.1 Where required.
Portable fire extinguishers shall be installed in the following locations.
1. In all Group A, B, E, F, H, I, M, R-1, R-2 adult homes and enriched housing, and S occupancies.
2. Within 30 feet (9144 mm) of commercial cooking equipment.
3. In areas where flammable or combustible liquids are manufactured, stored, handled and used, including dispensing, in quantities requiring a permit pursuant to FC 105.6.
4. On each floor of structures under construction, alteration or demolition, except detached Group R-3 occupancies, in accordance with FC 3315.1.
5. Where required by the sections indicated in FC Table 906.1.
6. Special-hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the commissioner.
7. Where required by other provisions of this code or the rules.
FC Table 906.1 Additional Required Portable Fire Extinguishers
Section Subject 303.5 Tar kettles and asphalt melters 307.4 Open fires 307.5.4 Portable outdoor barbecues 308.5.3.2 Flaming food and beverage preparation in Group A occupancies and public gathering places 308.6.4 Alcohol fueled decorative open-flame device 309.4 and 309.7* Powered industrial trucks and storage areas 310.7.3.4 Non-tobacco hookah establishment 315.3.6 Outdoor storage of combustible material 317.5.2 Automotive salvage and wrecking facilities 603.3.1 Fuel oil-burning equipment 609.9 Commercial kitchen 2005.2 Aircraft towing vehicles 2005.3 Aircraft welding apparatus 2005.4 Aircraft-fueling vehicles 2005.5 Aircraft hydrant-fueling vehicles 2005.6 Aircraft fuel-dispensing stations 2007.7 Heliports and helistops 2010.6.2 Helicopter lift operations 2108.4 Dry cleaning facilities 2305.5 Automotive liquid motor fuel-dispensing facilities 2308.7.4.2 CNG motor fuel-dispensing facilities 2310.6.4 Marine liquid motor fuel-dispensing facilities 2311.7 and 2311.8.7 Repair garages 2404.4.10 Spraying spaces 2404.5.5 Limited spraying areas 2405.5.3 Dip-tank rooms and spaces 2406.4.6 Powder coating rooms and spaces 2410.1.2 Floor finishing operations 2808.8 Storage of wood chips and other wood waste materials 2809.5 Exterior lumber storage 2903.5 Organic-coating areas 3006.3 Industrial furnaces 3104.12 Tents and other membrane structures 3206.10 High-piled storage 3315.1 Buildings, structures, premises and facilities under construction, alteration or demolition 3317.3 Roofing operations 3408.2 Tire rebuilding/storage 3504.2.6 Welding and other hot work 3605.2.3 Marina fire protection systems and equipment 3703.6 and 3706.6.4 Combustible fibers 4006.14 Distilleries 5007.9.3 Transportation of flammable and combustible liquids in cargo tanks 5306.7 Medical gas storage 5606.8 Powder-actuated tool loads at a construction site 5609.6.1 Special effects 5703.2.1 Flammable and combustible liquids, general 5704.3.3.1 Indoor storage of flammable and combustible liquids 5704.3.7.5.2 Liquid storage rooms for flammable and combustible liquids 5705.4.9 Solvent distillation units 5706.2.7 Construction sites – flammable and combustible liquids storage 5706.2.8 Construction sites – dispensing from cargo tanks 5706.4.10.1 Bulk plants and terminals for flammable and combustible liquids 5706.8.1(20) Vapor recovery and processing equipment at bulk plants and terminals 5707.8 Fleet fueling operations 5806.5 Sterilizers using flammable gas containing ethylene oxide 6108.2 LPG
* Editor's note: correct reference should be 309.2.5, 309.3.3 and 309.3.4.
906.2 General requirements.
Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Exceptions:
1. The travel distance to reach a portable fire extinguisher shall not apply to the spectator seating portions of Group A-5 occupancies.
2. In Group I-3, portable fire extinguishers may be provided at staff locations.
906.2.1 Maintenance.
Portable fire extinguishers shall be maintained in accordance with FC 901.6 and this section.
906.2.1.1 Monthly inspection.
An inspection to verify that the portable fire extinguishers are readily available and in good working order shall be conducted at least once a month. The person conducting such inspections shall keep records of all portable fire extinguishers inspected, including the date the inspection was performed, the person performing the inspection, and those portable fire extinguishers found to require corrective action. Such recordkeeping shall be either kept on a tag or label securely attached to the portable fire extinguisher, on an inspection checklist maintained on file or by an approved electronic method that provides a permanent record.
Exception: An inspection to verify that the portable fire extinguishers are readily available and in good working order shall be conducted at least once every 3 years for dry-chemical or halogenated agent portable fire extinguishers that are monitored by a listed and approved electronic monitoring device complying with all of the following requirements:
1. The electronic monitoring device shall continuously confirm the proper location and charge of each portable fire extinguisher so monitored.
2. Loss of power to the electronic monitoring device or other interruption of the proper functioning of such device shall initiate a trouble signal at an approved location on the premises at which the portable fire extinguisher being monitored is installed.
3. The portable fire extinguisher being monitored shall be located indoors or in cabinets outdoors. The portable fire extinguisher being monitored shall not be in a corrosive environment.
4. The periodic inspection of the portable fire extinguisher shall include inspection and testing of the electronic monitoring device.
5. An electronic record that the electronic monitoring of the portable fire extinguisher is being maintained, and that the portable fire extinguisher is properly located and charged, shall be maintained in accordance with FC 107.7.
906.2.1.2 Servicing.
Annual servicing and recharging shall be conducted in accordance with NFPA 10 by an approved portable fire extinguisher servicing company and a technician meeting the requirements of FC 901.6.3.1.
906.2.1.3 Hydrostatic testing.
Periodic hydrostatic testing of portable fire extinguishers shall be done in accordance with NFPA 10.
906.2.1.4 Proof of compliance.
A portable fire extinguisher servicing company holding a company certificate shall document its servicing of a portable fire extinguisher by affixing to the portable fire extinguisher the proof of compliance approved for such purposes and in such other manner as may be required by the rules.
906.3 Size and distribution.
The size and distribution of portable fire extinguishers shall be in accordance with FC 906.3.1 through 906.3.4.
906.3.1 Class A fire hazards.
The minimum size, number and placement of portable fire extinguishers in occupancies in which there is a Class A fire hazard risk (ordinary combustible materials) shall be in accordance with FC Table 906.3.1.
906.3.1.1 Sprinklered areas.
In buildings classified as Group A-3 occupancy houses of worship and Group B occupancy office buildings that are protected throughout by a sprinkler system, the maximum floor area per unit of A required by FC Table 906.3.1 may be doubled.
906.3.2 Class B fire hazards.
The minimum size, number and placement of portable fire extinguishers in occupancies in which there is a Class B fire hazard risk (flammable or combustible liquids with depths of less than or equal to 0.25-inch (6.35 mm)) shall be in accordance with FC Table 906.3.2. The minimum size, number and placement of portable fire extinguishers in occupancies in which there is a Class B fire hazard risk (flammable or combustible liquids with depths greater than 0.25-inch (6.35 mm)) shall be in accordance with NFPA 10.
906.3.3 Class C fire hazards.
The minimum size, number and placement of portable fire extinguishers in which there is a Class C fire hazard risk (energized electrical equipment) shall be in accordance with NFPA 10.
906.3.4 Class D fire hazards.
The minimum size, number and placement of portable fire extinguishers in occupancies in which there is a Class D fire hazard risk (combustible metals) shall be in accordance with NFPA 10.
FC Table 906.3.1 Portable Fire Extinguishers for Class a Fire Hazards
Light (Low) Hazard Occupancy d Ordinary (Moderate) Hazard Occupancy d Extra (High) Hazard Occupancy d Minimum Rated Single Extinguisher 2-A c 2-A 4-A a Maximum Floor Area Per Unit of A 3,000 square feet e 1,500 square feet 1,000 square feet Maximum Travel Distance to Extinguisher 75 feet 75 feet 75 feet
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m 2 , 1 gallon = 3.785 L.
a. Two 2 1/2-gallon water-type extinguishers shall be deemed the equivalent of one 4-A rated extinguisher.
b. Reserved.
c. Two water-type extinguishers each with a 1-A rating shall be deemed the equivalent of one 2-A rated extinguisher for Light (Low) Hazard Occupancies.
d. For the purposes of FC Table 906.3.1, the terms "Light (Low) Hazard", "Ordinary (Moderate) Hazard" and "Extra (High) Hazard" shall be as defined in NFPA 10.
e. In occupancies classified as Groups A-3, B, or E which are protected throughout by a sprinkler system, the maximum floor area per unit of A may be doubled.
FC Table 906.3.2 Flammable or Combustible Liquids with Depths of less than or Equal to 0.25-inch a
Type of Hazard Basic Minimum Portable Fire Extinguisher Rating Maximum Travel Distance to Portable Fire Extinguishers (feet) Light (Low) 5-B 10-B 30 50 Ordinary (Moderate) 10-B 20-B 30 50 Extra (High) 40-B 80-B 30 50
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. For requirements on water-soluble flammable liquids and alternative sizing criteria, see NFPA 10.
906.4 Cooking grease fires.
Portable fire extinguishers provided for the protection of cooking grease fires shall be of an approved type compatible with the fire extinguishing system agent and in accordance with FC 609.9.
906.5 Conspicuous location.
Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the commissioner determines that the hazard posed indicates the need for placement away from normal paths of travel.
Exceptions:
1. Portable fire extinguishers subject to theft, malicious use or damage may be located in locations approved by the commissioner.
2. In rooming houses and single room occupancies, as defined in the New York State Multiple Dwelling Law, with over 15 sleeping rooms, a 2-A rated portable fire extinguisher may be kept in the apartment of the manager or the building superintendent.
906.6 Unobstructed and unobscured.
Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, signs or other markings shall be provided to indicate the locations of portable fire extinguishers.
906.7 Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.
906.8 Cabinets.
Cabinets used to house portable fire extinguishers shall be readily identifiable and shall not be locked.
Exceptions:
1. Portable fire extinguishers subject to theft, malicious use or damage, if provided with an approved means of ready access.
2. Portable fire extinguishers in Group I-3 occupancies and in mental health areas in Group I-2 occupancies may be locked or located in staff locations, provided the staff of the institution has ready access to the cabinet or other storage location.
906.9 Extinguisher installation.
The installation of portable fire extinguishers shall be in accordance with FC 906.9.1 through 906.9.3.
906.9.1 Extinguishers weighing 40 pounds or less.
Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that the top of the extinguisher is not more than 5 feet (1524 mm) above the floor.
906.9.2 Extinguishers weighing more than 40 pounds.
Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that the top of the extinguisher is not more than 3.5 feet (1067 mm) above the floor.
906.9.3 Floor clearance.
The clearance between the floor and the bottom of installed hand-held portable fire extinguishers shall not be less than 4 inches (102 mm).
906.10 Wheeled units.
Wheeled portable fire extinguishers shall be kept in a designated location that is readily accessible.
Section FC 907. Fire Alarm and Detection Systems
907.1 General.
This section governs the design, installation, operation and maintenance of fire alarm systems and their components.
907.2 Where required.
An approved manual, automatic, or manual and automatic fire alarm system shall be provided where required by the construction codes, including the Building Code or this code.
907.3 Design and installation.
An approved manual, automatic, or manual and automatic fire alarm system shall be installed in accordance with the construction codes, including the Building Code, the Electrical Code and NFPA 72, as modified by FC Appendix B.
907.3.1 Design and installation documents.
Design and installation documents for fire alarm systems shall be submitted to the department for review and approval prior to system installation. Design and installation documents shall include such design and installation details as may be required by the construction codes, including the Building Code, and this code.
907.3.2 Fire alarm system control panel.
Fire alarm system control panels shall be of a type for which a certificate of approval has been issued in accordance with FC 112 and the rules. Fire alarm control panels shall be installed at an approved location and, when applicable, in accordance with FC 904.3.6. Fire alarm system control panel design and operation for mass notification purposes shall require department approval.
907.3.3 Fire extinguishing systems.
Fire extinguishing systems shall be connected to the building fire alarm system whenever a fire alarm system is required or is otherwise installed.
907.3.4 Manual fire alarm box protective covers.
The department may require the installation of manual fire alarm box protective covers to prevent malicious false alarms or provide the manual fire alarm box with protection from physical damage.
907.4 Fire command center.
Where required by this code or the construction codes, including the Building Code, a fire command center shall be provided for a building, structure or premises.
907.4.1 Location.
A plan identifying the proposed location and layout of the fire command center, including the location of the fire alarm system control panel, shall be submitted to the department for approval prior to installation. The location and layout of the fire command center shall be approved by the department in accordance with the following requirements and such other design, installation, operational and maintenance requirements as it may prescribe:
1. The primary fire command center, as required by Sections 403 and 911 of the Building Code, shall be installed in the building lobby at the main front entrance, mounted in the front desk, on the wall behind the front desk, on a wall in the lobby that provides a clear view of the elevators and lobby, or other approved location.
2. The secondary fire command center, when required by Appendix G to the Building Code or voluntarily installed, shall be installed at a location above the flood elevation in close proximity to the building lobby at the main front entrance, on the second floor near the elevators and/or stairwells, or other approved location.
3. The fire command center shall not be installed in a room.
4. The fire command center fire alarm control unit display shall not be mounted more than 6 feet (1829 mm) above the finish floor.
5. A durable sign reading "Fire Command Center" in 2-inch red letters on a white background shall be conspicuously posted at the fire command center.
907.4.2 Fire command center printer.
Buildings with a fire command center shall be equipped with a printer or other approved device connected to the fire alarm system control panel to facilitate review by firefighting personnel of the incident history associated with an alarm activation.
907.4.3 Required documentation and other items for firefighting operations.
Access keys for building rooms and areas and any other items that will assist firefighting or other emergency response operations shall be kept at the fire command center, together with the following documentation when required by the code or the rules:
1. Building information card.
2. Emergency preparedness plan.
3. Floor plans.
4. Non-sequential floor numbering chart.
5. Safety data sheets.
6. Standpipe elevation chart.
907.5 Reserved.
907.6 Reserved.
907.7 Reserved.
907.8 Presignal system.
Where a presignal system is installed, personal supervision shall be provided at an approved location, in order that the alarm signal can be activated in the event of fire or other emergency.
907.9 Reserved.
907.10 Reserved.
907.11 Reserved.
907.12 Reserved.
907.13 Access.
Access shall be provided to each detector for periodic inspection, testing and other maintenance.
907.14 Reserved.
907.15 Monitoring.
Where required by this code, the rules or by the construction codes, including the Building Code, such monitoring by a central station shall be performed in compliance with the requirements of the rules.
Exception: Central station monitoring is not required for:
1. Single- and multiple-station smoke alarms required by Section 907.2.10* of the Building Code.
* Editor's note: correct reference should be Section 907.2.11 of the Building Code.
2. Smoke detectors in Group I-3 occupancies.
3. Sprinkler systems in Group R-3 occupancies.
907.15.1 Discontinuance or other change of service.
Notification shall be made to the department in accordance with the rules upon discontinuance, change of service provider or other change in service of central station monitoring.
907.16 Automatic telephone-dialing devices.
Automatic telephone-dialing devices used to transmit an emergency alarm shall not be connected to any department telephone number unless approved by the commissioner.
907.17 Acceptance testing.
Upon completion of the installation of a fire alarm system, including alarm notification appliances and circuits, alarm-initiating devices and circuits, supervisory-signal initiating devices and circuits, signaling line circuits, and primary and secondary power supplies, such system shall be tested in accordance with FC 901.5.
907.18 Record of completion.
A record of completion in accordance with NFPA 72, as modified by FC Appendix B, this code and the rules, verifying that the system has been installed in accordance with the approved design and installation documents and specifications shall be provided by the installing contractor.
907.19 Instructions.
Inspection, testing, operation and maintenance instructions, as built design and installation documents and equipment specifications shall be provided on site at an approved location.
907.20 Inspection, testing and other maintenance.
Fire alarm and fire alarm detection systems shall be operated and maintained in accordance with this code, FC 901, the rules and NFPA 72, as modified by FC Appendix B.
907.20.1 Reserved.
907.20.2 Testing.
Testing shall be performed in accordance with the schedules in NFPA 72, as modified by FC Appendix B, or more frequently where required by the commissioner.
Exception: Devices or equipment that are inaccessible for safety considerations shall be tested during scheduled shutdowns where approved by the commissioner, but not less than every 18 months.
907.20.3 Detector sensitivity.
Detector sensitivity shall be checked in compliance with the manufacturer's instructions and NFPA 72, as modified by FC Appendix B, and the rules. Detectors which are connected to a fire alarm system that automatically transmit signals to the department or to a central station shall, as applicable, also be checked in compliance with the rules.
907.20.4 Method.
To verify that each smoke detector is within its listed and marked sensitivity range, it shall be tested using one of the following methods or types of equipment, and detectors found to have a sensitivity outside the listed and marked sensitivity range shall be cleaned and recalibrated or replaced:
1. A calibrated test method;
2. The manufacturer's calibrated sensitivity test instrument;
3. Listed control equipment arranged for the purpose;
4. A smoke detector/control unit arrangement whereby the detector causes a signal at the control unit where its sensitivity is outside its acceptable sensitivity range; or
5. Another calibrated sensitivity test method acceptable to the commissioner.
Exceptions:
1. Detectors listed as field adjustable shall be allowed to be either adjusted within the listed and marked sensitivity range and cleaned and recalibrated or they shall be replaced.
2. This requirement shall not apply to single-station smoke alarms.
907.20.4.1 Testing device.
Smoke detector sensitivity shall not be tested or measured using a device that administers an unmeasured concentration of smoke or other aerosol into the detector.
907.20.5 Maintenance.
The owner shall maintain all types of fire alarm and detection systems in good working order at all times. Service personnel shall possess the qualifications set forth in NFPA 72, as modified by FC Appendix B, and the rules, for inspecting, testing, servicing and otherwise maintaining such systems. When required by the rules, a smoke detector maintenance log book and an alarm log book shall be maintained.
907.20.5.1 Five-year retest.
All fire alarm and other detection systems shall be retested once every five years from the date of acceptance of the system. The first retest of fire alarm and other detection systems lawfully existing on the effective date of this provision shall be conducted on or before the fifth anniversary of the date of acceptance after such effective date. Such test shall be conducted, and reported to the department, in the manner prescribed by rule, by a person holding a certificate of fitness for professional certification of fire alarm and emergency alarm installations and testing, as set forth in FC 104.2.1(1) and the rules, or a fire alarm system installer with NICET-Level II certification licensed by or registered with the State of New York and holding a certificate of fitness in accordance with the rules.
907.20.6 Smoke detector maintenance.
The owner of any premises, or part thereof, monitored by a fire alarm system or sub-system thereof, whether required or not required by this code, which automatically transmits signals to the department or to a central station, shall be responsible for preventing unnecessary and unwarranted alarms as set forth in rules. Cleaning and testing of smoke detectors shall be performed as set forth in the rules.
907.20.7 Hold-open devices.
The fire alarm system connections for hold-open devices installed on fire doors pursuant to the Building Code, including hold-open devices provided for vertical exit enclosure doors pursuant to the exception to Section BC 708.7* of the Building Code, shall be inspected, tested and otherwise maintained in accordance with FC 703.2 and 907.20 and NFPA 72. Hold-open devices and automatic door closers provided for such vertical exit enclosure doors shall be inspected and tested annually to ensure the proper functioning of:
* Editor's note: correct reference should be Section BC 713.7 of the Building Code.
1. the manual control on the fire alarm system control panel, or the fire command center where a fire command center is required, that transmits a signal to release the hold-open devices;
2. the fire alarm system output programming, which automatically transmits a signal to release the hold-open devices upon activation of an automatic alarm initiating device or manual elevator recall;
3. the circuitry for each hold-open device, which upon receipt of a manual or automatic signal, releases the door; and
4. each automatic door closer, which, upon release of the door by the hold-open device, mechanically moves the door to its fully closed position.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2014/017.
Section FC 908. Emergency Alarm Systems
908.1 General.
Emergency alarm systems required by the construction codes, this code or the rules for the detection and notification of a release of a hazardous material or other hazardous materials incident, or other physical or health hazard, including systems designed to detect flammable, toxic, asphyxiant and other gases, shall be designed, installed, operated and maintained in compliance with the construction codes, the Electrical Code, the code requirements referenced in FC Table 908.1, this section and the manufacturer's instructions.
FC Table 908.1 Required Emergency Alarms
Hazard Occupancy / Use a Section Carbon dioxide Occupancies with a carbon dioxide beverage dispensing system 5307 Carbon monoxide Residential occupancies; other occupancies with carbon monoxide-producing equipment Building Code BC 915 Flammable alcohol vapors Distilleries 4003 Gaseous hydrogen Hydrogen fuel gas rooms 5808 Hazardous materials High-hazard occupancies (Group H) 5004 and 5005 Hazardous production materials Semiconductor production facilities (Group H-5) 2703 Lighter-than-air motor fuels Motor fuel-dispensing facilities; repair garages for vehicles fueled by lighter-than-air motor fuels 2308, 2309 and 2311 Medical gases Hospitals, nursing homes and hyperbaric facilities with a medical gas system 5306 Natural gas and other flammable gases (except lighter-than-air motor fuels) Mechanical rooms, microturbine rooms and power plants with flammable gas distribution piping operating above 15 psig; residential occupancies 5810; Building Code BC 908 Ozone gas Ozone gas-generator rooms 6005 Refrigerants Mechanical rooms with a refrigerating system 606 Toxic/highly toxic materials Group H-3 occupancies 6004
a. Typical occupancy/use. Other occupancies/uses as approved.
908.2 Plan approval.
Design and installation documents for emergency alarm systems shall be submitted for department review and approval when required by FC 105.4 and the rules.
908.3 Signage.
Signs shall be posted in a conspicuous location near the emergency alarm system control panel and each alarm notification device to inform building occupants in the affected area of the meaning of the alarm activation and the appropriate response.
908.4 Central station monitoring.
Emergency alarm systems required to transmit an alarm signal to a central station shall transmit such signal through the central station-monitored fire alarm system for the building or occupancy, or through an approved central station-monitored control panel. Such central station connections shall be maintained in compliance with the requirements of NFPA 72, as modified by FC Appendix B, and the rules.
908.5 Periodic inspection and testing.
Sensors and other mechanical and electrical components of emergency alarm systems shall be tested by a trained and knowledgeable person on not less than an annual basis to ensure that they are in good working order, and a record kept of such testing.
908.5.1 Five-year retest.
All emergency alarm systems and other detection systems shall be retested once every five years from the date of acceptance of the system. The first retest of emergency alarm systems lawfully existing on the effective date of this provision shall be conducted on or before the fifth anniversary of the date of acceptance after such effective date. Such test shall be conducted, and reported to the department, in the manner prescribed by rule, by a person holding a certificate of fitness for professional certification of fire alarm and emergency alarm installations and testing, as set forth in FC 104.2.1(1) and the rules, or a fire alarm system installer with NICET-Level II certification licensed by or registered with the State of New York and holding a certificate of fitness in accordance with the rules.
Section FC 909. Smoke Control Systems
909.1 Smoke control systems.
Smoke control systems, including stairwell pressurization, shall be provided as required by the construction codes, including the Building Code, and shall be designed, installed and tested as required by such codes.
909.1.1 Smoke control system maintenance.
Smoke control systems shall be maintained in good working order. Periodic testing, inspection and other maintenance shall be performed in accordance with the manufacturer's instructions and FC 909.1.1.1 through 909.1.1.3.
909.1.1.1 Schedule.
A written maintenance program, including periodic inspection and testing, shall be established and implemented immediately upon installation of the smoke control system.
909.1.1.2 Recordkeeping.
A logbook or other approved form of recordkeeping documenting each inspection and test shall include the date of the maintenance, identification of servicing personnel, description of any operating defects or deficiencies, notifications made, corrective action taken, including parts replaced, and/or other information prescribed by the department by rule.
909.1.1.3 Testing.
Operational testing of the smoke control system shall include all components of the system, including initiating devices, fans, dampers, controls, doors and windows. Dedicated smoke control systems shall be tested semiannually. Nondedicated smoke control systems shall be tested annually. All systems shall be tested under both normal power and emergency power.
909.2 Post-fire smoke purge systems.
Post-fire smoke purge systems shall be provided as required by the construction codes, including the Building Code, and shall be designed, installed and tested as required by such codes.
909.2.1 Post-fire smoke purge system maintenance.
Post-fire smoke purge systems shall be maintained in good working order. A record of inspections and tests shall be maintained in accordance with FC 107.7.
Section FC 910. Smoke and Heat Vents
910.1 General.
Smoke and heat vents or, where approved by the Commissioner of Buildings, mechanical smoke exhaust systems, and draft curtains shall be installed when required by the construction codes, including the Building Code, this code or the rules, and shall be designed and installed in accordance with the construction codes, including the Building Code.
910.2 Maintenance.
Automatically and manually operated heat vents and engineered mechanical smoke exhaust systems shall be inspected periodically and an operational test of each shall be conducted at least once every 12 months. A record of each inspection and test shall be maintained as required by FC 107.7 and 901.6.2.
Exception: Gravity operated drop out vents need only be inspected.
Section FC 911. Explosion Control
911.1 General.
Explosion control shall be provided in the following locations:
1. Where a structure, room or space is occupied for purposes involving explosion hazards as set forth in FC Table 911.1.
2. Where quantities of hazardous materials specified in FC Table 911.1 exceed the maximum allowable quantities set forth in FC Table 5003.1.1(1).
Such areas shall be provided with explosion (deflagration) venting, explosion (deflagration) prevention systems, or barricades in accordance with this section and NFPA 69 or NFPA 495, as applicable. Deflagration venting shall not be utilized as a means to protect buildings from detonation hazards.
FC Table 911.1 Explosion Control Requirements
Material Class Explosion Control Methods Barricade Construction Explosion (deflagration) venting or explosion (deflagration) prevention systems Hazard Category Combustible dusts a — Not required Required Cryogenic fluids Flammable Not required Required Explosives Division 1.1 Division 1.2 Division 1.3 Division 1.4 Division 1.5 Division 1.6 Required Required Not required Not required Required Required Not required Not required Required Required Not required Not required Flammable gas Gaseous Liquefied Not required Not required Required Required Flammable liquids IA b IB c Not required Not required Required Required Organic peroxides e Unclassified Detonable I Required Required Not permitted Not permitted Oxidizer liquids and solids 4 Required Not permitted Pyrophoric material e Detonable Required Not permitted Pyrophoric gases e Nondetonable Not required Required Unstable (reactive) e 4 3 detonable 3 nondetonable Required Required Not required Not permitted Not permitted Required Water-reactive liquids and solids e 3 detonable 3 nondetonable 2 detonable 2 nondetonable Required Not required Required Not required Not permitted Required Not permitted Required Special Uses Energy Storage System — Required Required Grain processing — Not required Required Where explosion hazards exist d Detonation Deflagration Required Not required Not permitted Required
a. Combustible dusts that are generated during manufacturing or processing. See definition of Combustible Dust in FC Chapter 2.
b. Storage or use.
c. In open use or dispensing.
d. Rooms containing dispensing and use of hazardous materials when an explosive environment can occur because of the characteristics or nature of the hazardous materials or as a result of the dispensing or use process.
e. Unclassified detonable organic peroxides (see FC Chapter 62), detonable pyrophoric materials (see FC Chapter 64), detonable unstable (reactive) materials (see FC Chapter 66) and detonable water-reactive materials (see FC Chapter 67) are considered as explosives for purposes of storage.
911.2 Required deflagration venting.
Areas that are required to be provided with deflagration venting shall comply with the following requirements:
1. Walls, ceilings and roofs exposing surrounding areas shall be designed to resist a minimum internal pressure of 100 pounds per square foot (psf) (4788 Pa). The minimum internal design pressure shall not be less than five times the maximum internal relief pressure specified in FC 911.2(5).
2. Deflagration venting shall be provided only in exterior walls and roofs.
Exception: Where sufficient exterior wall and roof venting cannot be provided because of inadequate exterior wall or roof area, deflagration venting shall be allowed by specially designed shafts vented to the exterior of the building.
3. Deflagration venting shall be designed to prevent unacceptable structural damage. Where relieving a deflagration, vent closures shall not produce projectiles of sufficient velocity and mass to cause life threatening injuries to the occupants or other persons on the property or adjacent public streets.
4. The aggregate clear area of vents and venting devices shall be governed by the pressure resistance of the construction assemblies specified in FC 911.2(1) and the maximum internal pressure allowed by FC 911.2(5).
5. Vents shall be designed to withstand loads in accordance with the construction codes, including the Building Code. Vents shall consist of any one or any combination of the following to relieve at a maximum internal pressure of 20 pounds per square foot (958 Pa), but not less than the loads required by the construction codes, including the Building Code:
5.1. Exterior walls designed to release outward.
5.2. Hatch covers.
5.3. Outward swinging doors.
5.4. Roofs designed to uplift.
5.5. Venting devices listed for the purpose.
6. Vents designed to release from the exterior walls or roofs of the building when venting a deflagration shall discharge directly outdoors where an unoccupied space not less than 50 feet (15 240 mm) in width is provided between the exterior walls of the building and the property line.
Exception: Vents complying with the requirements of FC 911.2(7).
7. Vents designed to remain attached to the building when venting a deflagration shall be so located that the discharge opening shall not be less than 10 feet (3048 mm) vertically from window openings and exits in the building and 20 feet (6096 mm) horizontally from exits in the building, from window openings and exits in adjacent buildings on the same property, and from the property line.
8. Vent lines shall discharge outdoors.
911.3 Explosion prevention systems.
Explosion prevention systems shall be of an approved type and installed in accordance with this code and NFPA 69. Where the building or structure or part thereof is provided with a fire alarm system, explosion prevention system alarms shall be transmitted to the fire alarm system control panel and to an approved central station.
911.4 Barricades.
Barricades shall be designed and installed in accordance with NFPA 495.
Section FC 912. Fire Department Connections
912.1 Installation.
Fire department connections shall be installed in accordance with the construction codes, including the Building Code.
912.2 Location.
The location of fire department connections shall be in accordance with the Building Code.
912.2.1 Visible location.
Fire department connections shall be located on the street side of buildings, fully visible and recognizable from the street or nearest point of fire department apparatus access, or as otherwise approved by the commissioner.
912.2.2 Distance from hydrant.
Fire department connections shall be located at a distance from the nearest fire hydrant as required by the Building Code.
912.3 Access.
Immediate access to fire department connections shall be maintained at all times, without obstruction by fences, posts, bushes, trees, rubbish containers, vehicles, walls or other objects.
Exception: Access to fire department connections may be obstructed by a fence, provided that such fence has an approved access gate complying with the design, installation, operation and maintenance requirements of FC 912, including signage complying with FC 912.4, and a means of emergency operation.
912.3.1 Locking fire department connection caps.
The commissioner may require locking caps on fire department connections for sprinkler and standpipe systems.
912.3.2 Clear space around connections.
A working space of not less than 36 inches (914 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided and maintained in front of and around wall-mounted and free-standing fire department connections, except as otherwise required or approved.
912.3.3 Physical protection.
Where fire department connections are subject to impact by a motor vehicle whose normal operation brings it into proximity with such connections, such as when fire department connections are located curbside or adjacent to loading or parking areas, vehicle impact protection shall be provided in accordance with FC 312.
912.4 Signs and markings.
Fire department connections shall be marked in accordance with FC 912.4.1 and 912.4.2.
912.4.1 Identification of fire department connections.
Fire department connections serving:
1. only a standpipe system shall be provided with caps painted red and identified by markings and signage that reads "STANDPIPE";
2. only an automatic sprinkler system shall be provided with caps painted green and identified by markings or signage that reads "SPRINKLER," provided, however, that if the automatic sprinkler system only serves a portion of the building, a sign shall additionally identify the portion of the building protected;
3. only a non-automatic (manually activated) sprinkler system shall be provided with caps painted silver and identified by markings or signage that reads "SPRINKLER", provided, however, that if the non-automatic sprinkler system only serves a portion of the building, a sign shall additionally identify the portion of the building protected;
4. combination standpipe and sprinkler systems shall be provided with caps painted yellow and identified by markings or signage that reads "COMBINATION STANDPIPE AND SPRINKLER SYSTEMS";
5. in addition to the foregoing, a standpipe, sprinkler or combination system in a building other than the building upon which the fire department connection is mounted shall be provided with a sign identifying the address of the other building served by the fire department connection; and
6. in addition to the foregoing, a standpipe, sprinkler or combination system serving more than one zone in a single building shall be provided with a sign identifying each zone served by the fire department connection. Such sign shall specify the maximum height (in feet) above grade of each zone and any other necessary identifying information.
912.4.2 Design of signs and markings.
Cap markings on fire department connections shall be deep cast in the body of the cap in letters 1 inch (25 mm) high and 1/8 inch (3.2 mm) deep. Alternatively, fire department connections may be identified by a durable non-ferrous metal plate secured to the connections or conspicuously mounted on the wall.
912.5 Reserved.
912.6 Maintenance.
Sprinkler system and standpipe system fire department connections shall be periodically inspected, tested, serviced and otherwise maintained in accordance with FC 901.6 and NFPA 25. Upon order of the commissioner, but at least once every 5 years, such fire department connections shall be subjected to a hydrostatic pressure test to demonstrate their suitability for department use. The test shall be conducted in accordance with the rules and at the owner's risk, by his or her representative before a representative of the department.
Section FC 913. Fire Pumps
913.1 General.
Where provided, fire pumps shall be installed in accordance with this section, the construction codes, including the Building Code, and NFPA 20.
913.2 Protection against interruption of service.
The fire pump, driver, and controller shall be protected in accordance with NFPA 20 against possible interruption of service through damage caused by explosion, fire, flood, earthquake, rodents, insects, windstorm, freezing, vandalism and other adverse conditions.
913.3 Temperature of pump room.
Suitable means shall be provided for maintaining the temperature of a pump room or pump house, where required, above 40°F (5°C).
913.3.1 Engine manufacturer's recommendation.
Temperature of the pump room, pump house or area where engines are installed shall never be less than the minimum recommended by the engine manufacturer. The engine manufacturer's recommendations for oil heaters shall be followed.
913.4 Valve supervision.
Where provided, the fire pump suction, discharge and bypass valves, and the isolation valves on the backflow prevention device or assembly shall be supervised open by a fire alarm system and monitored by an approved central station.
913.4.1 Test outlet valve supervision.
Fire pump test outlet valves shall be supervised in the closed position.
913.5 Operation and maintenance.
Fire pumps shall be operated and maintained in compliance with the requirements of this section, FC 901.6 and NFPA 25, including all required inspection, testing and servicing.
913.5.1 Acceptance test.
Acceptance testing shall be done in accordance with FC 901.5 and NFPA 20. Acceptance tests shall be conducted at the owner's risk by his or her representative before a representative of the department.
913.5.2 Generator sets.
Engine generator sets supplying emergency power to fire pump assemblies shall be periodically tested in accordance with FC 604 and the Electrical Code.
913.5.3 Transfer switches.
Automatic transfer switches shall be periodically tested in accordance with FC 604 and the Electrical Code.
913.5.4 Pump room environmental conditions.
Tests of pump room environmental conditions, including heating, ventilation and illumination shall be made to ensure proper manual or automatic operation of the associated equipment.
913.6 Fire pump supervision.
The following fire pump operations shall be electrically supervised by the fire alarm system in accordance with the Electrical Code and NFPA 20; and monitored by a central station in accordance with this code and the rules:
1. Pump running.
2. Pump power failed.
3. Pump phase reversal.
Section FC 914. Yard Hydrant Systems
914.1 General.
Yard hydrant systems shall be installed where required by the construction codes, including the Building Code, this code, including FC 507.2.3, or the rules.
914.2 Operation and maintenance.
Yard hydrant systems shall be operated and maintained in accordance with FC 901.6 and NFPA 25.
914.3 Supervision.
At all times when the area served by the yard hydrant system is in use, the system shall be under the personal supervision of a certificate of fitness holder, who shall be available to assist the department in the operation of such system.
Section FC 1001. General
1001.1 Scope.
This chapter shall govern the maintenance of means of egress from all buildings, structures and premises in all occupancy classifications.
1001.2 General.
Buildings, structures and premises, or parts thereof, shall be provided with a means of egress system as required by the construction codes, including the Building Code. The maintenance of means of egress from all buildings, structures and premises and all occupancies shall be in accordance with this chapter.
Section FC 1002. Definitions
1002.1 Definitions.
The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.
EMERGENCY ESCAPE AND RESCUE OPENING.
EXIT.
EXIT ACCESS.
EXIT DISCHARGE.
EXIT DISCHARGE, LEVEL OF.
MEANS OF EGRESS.
Section FC 1003. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1003 at American Legal Publishing.
Section FC 1004. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1004 at American Legal Publishing.
Section FC 1005. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1005 at American Legal Publishing.
Section FC 1006. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1006 at American Legal Publishing.
Section FC 1007. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1007 at American Legal Publishing.
Section FC 1008. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1008 at American Legal Publishing.
Section FC 1009. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1009 at American Legal Publishing.
Section FC 1010. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1010 at American Legal Publishing.
Section FC 1011. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1011 at American Legal Publishing.
Section FC 1012. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1012 at American Legal Publishing.
Section FC 1013. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1013 at American Legal Publishing.
Section FC 1014. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1014 at American Legal Publishing.
Section FC 1015. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1015 at American Legal Publishing.
Section FC 1016. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1016 at American Legal Publishing.
Section FC 1017. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1017 at American Legal Publishing.
Section FC 1018. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1018 at American Legal Publishing.
Section FC 1019. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1019 at American Legal Publishing.
Section FC 1020. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1020 at American Legal Publishing.
Section FC 1021. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1021 at American Legal Publishing.
Section FC 1022. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1022 at American Legal Publishing.
Section FC 1023. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1023 at American Legal Publishing.
Section FC 1024. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1024 at American Legal Publishing.
Section FC 1025. Emergency Escape and Rescue
1025.1 General.
Emergency escape and rescue openings as required by the Building Code shall be provided in Group R occupancies.
1025.2 Reserved.
1025.3 Reserved.
1025.4 Operational constraints.
Emergency escape and rescue openings and windows or other openings onto fire escapes, as that term is defined in the New York State Multiple Dwelling Law, shall be operational from the inside of the room without the use of keys or tools. Bars, grilles, grates or similar devices are allowed to be placed over emergency escape and rescue openings and windows or other openings onto fire escapes, provided the minimum net clear opening size complies with the requirements of the construction codes, including the Building Code and the New York State Multiple Dwelling Law, and such devices are releasable or removable from inside of the room without the use of a key, tool or force greater than that which is required for normal operation of the escape and rescue opening, window or other opening.
1025.5 Certificate of approval.
Bars, grilles, grates or similar devices placed over emergency escape and rescue openings, and windows or other openings onto fire escapes, shall be of a type for which a certificate of approval has been issued in accordance with this code and the rules.
Section FC 1026. Reserved
BetaNYC's copy has no text for this section. Read Section FC 1026 at American Legal Publishing.
Section FC 1027. Maintenance of the Means of Egress
1027.1 General.
The means of egress for buildings, structures or premises, or parts thereof, shall be maintained in accordance with the construction codes, including the Building Code and this section.
1027.2 Prohibition.
It shall be unlawful to obstruct or impede access to any required means of egress, including any exit, exit access or exit discharge.
1027.3 Unobstructed and unimpeded egress required.
All required means of egress, including each exit, exit access and exit discharge, shall be continuously maintained free from obstructions and impediments to immediate use in the event of fire or other emergency. An exit or exit passageway shall not be used for any purpose inconsistent with its use as a means of egress, including storage of combustible or noncombustible materials, except as authorized by law, rule or regulation.
1027.3.1 Door hardware.
Door hardware and other devices and physical components of the means of egress shall be maintained in good working order at all times.
1027.3.2 Security devices.
Security devices affecting means of egress shall be subject to the approval of the Commissioner of Buildings in consultation with the department.
1027.3.3 Snow and ice.
All required means of egress shall be maintained free from the accumulation of snow and ice.
1027.3.4 Overcrowding.
Premises shall not be caused, allowed or maintained in such a manner as to become overcrowded, such that the number of persons present on the premises and/or their location thereon obstructs or impedes access to any means of egress.
1027.3.5 Furnishings and decorations.
Furnishings, decorations or other objects shall not be placed so as to obstruct exits, access thereto, egress therefrom, or visibility thereof. Furnishings and decorations shall not be placed in building hallway corridors or elevator lobbies except as authorized by FC 1027.4 or other provision of this code. Hangings and draperies shall not be placed over exit doors or otherwise be located to conceal or obstruct an exit except as authorized by the commissioner. Mirrors shall not be placed on exit doors. Mirrors shall not be placed in or adjacent to any exit in such a manner as to confuse the direction of exit.
1027.3.6 Corridor storage.
It shall be unlawful to store combustible materials or combustible waste in corridors except as authorized by FC 1027.4 or other provision of this code or by the commissioner by rule.
1027.3.7 Fire escapes.
Access to fire escapes shall be maintained in accordance with FC 1027.7.
1027.3.8 Security grilles.
When the installation of security grilles is allowed by the Building Code, such grilles shall be secured in the full-open position during the period of occupancy, except when the Building Code provides otherwise.
1027.4 Residential building hallway corridor and elevator lobby furnishings, decorations and storage.
This section governs the placement of furnishings and decorations, and storage of combustible materials in building hallway corridors (excluding hallways within dwelling units) and in elevator lobbies above the street level, in Group R-2 buildings and occupancies. The department may by rule prohibit any type of building hallway corridor or elevator lobby furnishing, decoration or storage allowed by this section, or by order direct removal from a particular premises of any such furnishing, decoration or stored item, upon a determination that the size, materials or location of such furnishing, decoration or stored item presents an undue fire hazard.
1027.4.1 Incidental furnishings.
A building hallway corridor or elevator lobby may be furnished with a console table, console bench, mirror, and umbrella stand, provided that the minimum required egress width is maintained. All such furnishings must be incidental to hallway use in that the purpose of such furnishings is primarily decorative and/or for the convenience of persons passing through the hallways. Incidental furnishings shall not include furniture used to hold or store clothing or other combustible items, or storage in the hallway of furniture, such as beds and dining room tables, whose primary purpose is not decorative or for the temporary accommodation of passersby.
1027.4.2 Draperies, area rugs and decorative greens.
Draperies, area rugs and decorative greens shall be installed and maintained in building hallway corridors in compliance with the requirements of FC Chapter 8, including the requirement that they be inherently noncombustible or flameproofed by an approved method, and the prohibition against the display in building hallway corridors of Christmas trees and other conifers, and wreathes made of conifers.
1027.4.3 Artwork.
The walls of building hallway corridors may be decorated with combustible artwork, including artworks made of paper, canvas, wood or fabric, when in compliance with the requirements of FC 805.1.
1027.4.4 Carpeting.
Carpeting and other interior finishes shall comply with the requirements of Chapter 8 of the Building Code.
1027.4.5 Personal property.
Bicycles, baby strollers, clothing and other items of personal property, excluding those set forth in FC 1027.4.1 through 1027.4.4, shall not be stored in building hallway corridors, except as may be authorized or allowed by the department.
1027.4.6 Rubbish.
Household rubbish, including trash cans, shall not be stored in building hallway corridors. All such items shall be stored in compactor rooms or other lawful storage areas.
1027.5 Educational and day care building hallway corridor and elevator lobby decorations and storage.
Artwork and other decorations shall be displayed and maintained in the corridors and lobbies of Group E and I-4 occupancies in accordance with FC Chapter 8. Clothing and personal effects shall not be stored in corridors and lobbies of such occupancies, unless stored in metal lockers or in corridors protected throughout by a sprinkler system and the minimum required egress width is maintained.
1027.6 Group I-2 building hallway corridors.
This section governs the placement of equipment for patient care use in Group I-2 building hallway corridors designed for patient bed movement, with a minimum corridor width of 96 inches (2438 mm). The following equipment, up to a maximum of one item of equipment per patient sleeping room or patient care room per smoke compartment, may be placed and kept in such corridors for patient use where all the following conditions are met:
1. The entire corridor shall be protected throughout by a sprinkler system.
2. The equipment does not reduce the effective clear width for egress to less than 5 feet (1524 mm) and such width is clearly indicated by approved floor markings.
3. The equipment is low hazard, wheeled and designed to be used for the following purposes:
3.1. Computer and other patient recordkeeping stations;
3.2. Equipment and carts for medical emergencies and infection control;
3.3. Other equipment and carts while in active use in providing patient care; and
3.4. Stretchers, wheelchairs and other patient lift and transportation equipment.
4. Where feasible, all large equipment, including patient lifts, stretchers and medical emergency and infection control carts, shall be kept on one side of the corridor.
1027.7 Fire escapes.
Fire escapes, and access thereto, shall be maintained in a safe and operational condition, and continuously maintained free from obstructions and impediments to immediate use in the event of fire or other emergency.
1027.7.1 Maintenance.
All fire escape components shall be painted or otherwise protected from deterioration and all moving parts shall be maintained in good working order.
1027.7.2 Window gates.
Bars, grilles, grates or similar devices placed over windows or other openings onto fire escapes shall be maintained in good working order.
1027.7.3 Air conditioners.
An air conditioner shall not be installed in a window providing access to a fire escape unless such fire escape may be accessed from another window in the same room that is unobstructed and of the size required for such purpose by the Building Code, New York State Multiple Dwelling Law, or other applicable law, rule or regulation. Air conditioners installed in windows adjoining fire escapes shall not obstruct the path of egress on the fire escape.
1027.7.4 Fire escape ladders.
The operation of a fire escape ladder, including a drop ladder that is lowered vertically to the ground, or a counterbalanced stair ladder which swings to the ground, shall not be obstructed by awnings, stationary furniture, portable fueled space heaters, parked cars, or other obstructions. Where construction work is being performed at a location adjoining a fire escape, provision shall be made for safe egress from the fire escape ladder.
1027.8 Nonexit door identification.
Any door that is not an exit or otherwise part of the means of egress from a building, structure or premises, but which, by reason of its proximity or similar construction, can be confused with an exit door or other door that is part of the means of egress, shall be identified with an approved sign that reads "Not An Exit" and identifies the room into which the nonexit door provides access.
1027.9 Emergency Lighting.
Emergency lighting for means of egress shall be maintained in accordance with FC 107 and periodically inspected and tested in accordance with FC 1027.9.1 and 1027.9.2.
1027.9.1 Activation test.
Emergency lighting equipment shall be tested by a trained and knowledgeable person for a duration of not less than 30 seconds. The test shall be conducted manually at least once a month, unless the equipment is designed with an automated self-testing and self-diagnostic feature. When the equipment is tested by such an automated feature, a visual inspection of the emergency lighting equipment shall be conducted at least once a month to check the display for a supervisory or trouble signal, or for any other indication that the equipment is not in good working order.
1027.9.2 Power test.
Battery-powered emergency lighting equipment shall be tested by a qualified person in accordance with FC 604.5 by operating the equipment on battery power for not less than 90 minutes. The test shall be conducted at least once a year.
Section FC 2001. General
2001.1 Scope.
This chapter shall govern the design, installation, operation and maintenance of aviation facilities, including aircraft landing sites, airports, heliports, helistops, helicopter landings, seaplane bases and helicopter lift operations.
2001.2 Regulations not covered.
Except as otherwise provided in this chapter or any other federal, state or local law, rule or regulation, aviation facilities and related operations shall be operated or conducted in accordance with nationally recognized standards.
2001.3 General.
Aircraft landing sites, airports, heliports, helistops and seaplane bases shall be designed, installed, operated and maintained in accordance with this chapter. Aviation operations, including helicopter landings, helicopter lift operations and hot air balloon operations, shall be conducted in accordance with this chapter.
2001.4 Permits.
Permits shall be obtained for aircraft fueling vehicles, helicopter landing operations, helicopter lift operations and hot air balloon operations, as set forth in FC 105.6.
Section FC 2002. Definitions
2002.1 Definitions.
The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.
AIRCRAFT LANDING SITE.
AIRCRAFT OPERATION AREA.
AIRPORT.
AVIATION FACILITY.
DISCHARGE AREA.
EXTERNAL LOAD.
HELICOPTER LIFT OPERATION.
HELIPORT.
HELISTOP.
HOT AIR BALLOON OPERATION.
HYDRANT-FUELING VEHICLE.
SEAPLANE BASE.
STAGING AREA.
Section FC 2003. General Precautions
2003.1 Sources of ignition.
It shall be unlawful to use or maintain an open flame, flame-producing device or other source of ignition in an aircraft hangar or other location within 50 feet (15 240 mm) of an aircraft-fueling or defueling operation.
2003.2 Smoking.
It shall be unlawful to smoke in an aircraft hangar or other location used for aircraft fueling or defueling, cleaning, paint removal or painting operations. "No Smoking" signs shall be provided in accordance with FC 310.
2003.3 Maintenance.
The aircraft operation area and related areas shall be kept free from combustible waste at all times.
2003.4 Fire apparatus access roads.
Fire apparatus access roads shall be provided and maintained in accordance with FC Chapter 5 and the construction codes, including the Building Code. Fire apparatus access roads and aircraft parking positions shall be designed in a manner so as to preclude the possibility of fire vehicles traveling under any portion of a parked aircraft.
2003.5 Dispensing of flammable and combustible liquids.
Flammable and combustible liquids shall be dispensed and otherwise stored, handled and used in accordance with this chapter and FC Chapter 57. Automotive liquid motor fuel-dispensing facilities shall be designed, installed, operated and maintained in accordance with FC Chapter 23.
2003.6 Combustible material storage.
Combustible materials stored in aircraft hangars shall be stored in approved locations and containers.
2003.7 Hazardous material storage.
Hazardous materials shall be stored in accordance with FC Chapter 50.
Section FC 2004. Aircraft Maintenance
2004.1 Transferring flammable and combustible liquids.
Flammable and combustible liquids shall not be dispensed into or removed from a container, tank, vehicle or aircraft, except in approved locations.
2004.2 Application of flammable and combustible liquid finishes.
The application of flammable or Class II combustible liquid finishes shall be conducted in an approved location, using methods and procedures in accordance with FC Chapter 24.
2004.3 Cleaning parts.
Class IA flammable liquids shall not be used to clean aircraft, aircraft parts or aircraft engines. Cleaning with other flammable and combustible liquids shall be in accordance with FC 5705.3.6.
2004.4 Spills.
The following actions shall be taken in response to spills of flammable and combustible liquids and other hazardous materials, in addition to the procedures set forth in FC 2006.11.
2004.4.1 Cessation of work.
Activities in the affected area not related to the mitigation of the spill shall cease until the spilled material has been removed or the hazard has been mitigated.
2004.4.2 Vehicle movement.
Aircraft or other vehicles shall not be moved through the spill area until the spilled material has been removed or the hazard has been mitigated.
2004.4.3 Mitigation.
Spills shall be reported, documented and mitigated in accordance with this chapter and FC 5003.3, and any other applicable law, rule or regulation.
2004.5 Running engines.
Aircraft engines shall not be operated in aircraft hangars, except in approved engine test areas.
2004.6 Open flame.
Repair of aircraft requiring the use of open flames, spark-producing devices or the heating of parts above 500°F (260°C) shall only be performed outdoors or in an area complying with the requirements of the construction codes, including the requirements of the Building Code for a Group F-1 occupancy.
Section FC 2005. Portable Fire Extinguishers
2005.1 General.
Portable fire extinguishers suitable for flammable or combustible liquid and electrical-type fires shall be provided as set forth in FC 2005.2 through 2005.7, and 906. Portable fire extinguishers required by this section shall be inspected and maintained in accordance with FC 906.
2005.2 Towing vehicles.
Vehicles used for towing aircraft shall be equipped with a minimum of one listed portable fire extinguisher complying with the requirements of FC 906 and having a minimum rating of 20-B:C.
2005.3 Welding apparatus.
Welding apparatus shall be equipped with a minimum of one listed portable fire extinguisher complying with the requirements of FC 906 and having a minimum rating of 2-A:20-B:C.
2005.4 Aircraft-fueling vehicles.
Aircraft-fueling vehicles shall be equipped with a minimum of two listed portable fire extinguishers complying with the requirements of FC 906, each having a minimum rating of 20-B:C. A portable fire extinguisher shall be readily accessible from either side of the vehicle.
2005.5 Hydrant-fueling vehicles.
Hydrant-fueling vehicles shall be equipped with a minimum of one listed portable fire extinguisher complying with the requirements of FC 906, and having a minimum rating of 20-B:C.
2005.6 Fuel-dispensing stations.
Portable fire extinguishers shall be provided as follows:
1. Where the open-hose discharge capacity of the fueling system is not more than 200 gallons per minute (13 L/s), a minimum of two listed portable fire extinguishers complying with the requirements of FC 906 and having a minimum rating of 20-B:C shall be provided.
2. Where the open-hose discharge capacity of the fueling system is more than 200 gallons per minute (13 L/s) but not more than 350 gallons per minute (22 L/s), a minimum of one listed wheeled portable fire extinguisher complying with the requirements of FC 906 and having a minimum rating of 80-B:C, and a minimum agent capacity of 125 pounds (57 kg), shall be provided.
3. Where the open-hose discharge capacity of the fueling system is more than 350 gallons per minute (22 L/s), a minimum of two listed wheeled portable fire extinguishers complying with the requirements of FC 906 and having a minimum rating of 80-B:C each, and a minimum agent capacity of 125 pounds (57 kg) of each, shall be provided.
2005.6.1 Location of portable fire extinguishers.
Portable fire extinguishers at aircraft fuel-dispensing stations shall be located such that pumps or dispensers are not more than 75 feet (22 860 mm) from one such extinguisher.
2005.7 Fire extinguisher access.
Portable fire extinguishers required by this chapter shall be accessible at all times. Where necessary, provisions shall be made to clear accumulations of snow, ice and other forms of weather-related obstructions.
2005.7.1 Cabinets.
Cabinets and enclosed compartments used to house portable fire extinguishers shall be clearly marked with the words "FIRE EXTINGUISHER" in letters at least 2 inches (51 mm) high. Cabinets and compartments shall be readily accessible at all times.
Section FC 2006. Aircraft and Motor Vehicle Fueling
2006.1 Motor vehicle fuel-dispensing facilities.
Motor vehicle fuel-dispensing facilities at aviation facilities shall be designed, installed, operated and maintained in accordance with FC Chapter 23.
2006.2 Aircraft-fueling systems.
Aircraft-fueling systems shall be designed and constructed in accordance with NFPA 407.
Exception: Aircraft fueling systems may be designed and constructed as a full service automotive liquid motor vehicle fuel-dispensing facility in accordance with FC Chapter 23, subject to such conditions as the commissioner may require.
2006.3 Design of aircraft-fueling vehicles.
Aircraft-fueling vehicles shall be designed in accordance with FC 2006 and NFPA 407.
2006.3.1 Transfer apparatus.
Aircraft-fueling vehicles shall be equipped and maintained with an approved transfer apparatus.
2006.3.1.1 Internal combustion type.
Where such transfer apparatus is operated by an individual unit of the internal-combustion-motor type, such power unit shall be located as remotely as practicable from pumps, piping, meters, air eliminators, water separators, hose reels, and similar equipment, and shall be housed in a separate compartment from any of the aforementioned items. The fuel tank in connection therewith shall be suitably designed and installed, and the maximum fuel capacity shall not exceed 5 gallons (19 L) where the tank is installed on the engine. The exhaust pipe, muffler and tail pipe shall be shielded.
2006.3.1.2 Gear operated.
Where operated by gears or chains, the gears, chains, shafts, bearings, housing and all parts thereof shall be of an approved design and shall be installed and maintained in an approved manner.
2006.3.1.3 Vibration isolation.
Flexible connections for the purpose of eliminating vibration are allowed if the material used therein is designed, installed, operated and maintained in an approved manner, provided such connections do not exceed 24 inches (610 mm) in length.
2006.3.2 Pumps.
Pumps of a positive-displacement type shall be provided with a bypass relief valve set at a pressure of not more than 35 percent in excess of the normal working pressure of such unit. Such units shall be equipped and maintained with a pressure gauge on the discharge side of the pump.
2006.3.3 Dispensing hoses and nozzles.
Hoses shall be designed for the transferring of hydrocarbon liquids and shall not be any longer than necessary to provide efficient fuel transfer operations. Hoses shall be equipped with an approved shutoff nozzle. Fuel-transfer nozzles shall be self-closing and designed to be actuated by hand pressure only. Notches and other devices shall not be used for holding a nozzle valve handle in the open position. Nozzles shall be equipped with a bonding cable complete with proper attachment for aircraft to be serviced.
2006.3.4 Protection of electrical equipment.
Electric wiring, switches, lights and other sources of ignition, when located in a compartment housing piping, pumps, air eliminators, water separators, hose reels or similar equipment, shall be enclosed in a vapor-tight housing. Electrical motors located in such a compartment shall be of a type approved for use as specified in the Electrical Code.
2006.3.5 Venting of equipment compartments.
Compartments housing piping, pumps, air eliminators, water separators, hose reels and similar equipment shall be adequately ventilated at floor level or within the floor itself.
2006.3.6 Accessory equipment.
Ladders, hose reels and similar accessory equipment used for aircraft-fueling operations shall be of an approved type, as follows:
1. Ladders constructed of noncombustible material are allowed to be used with or attached to aircraft-fueling vehicles, provided the manner of attachment or use of such ladders is approved and does not constitute an additional fire or accident hazard in the operation of such fueling vehicles.
2. Hose reels used in connection with fueling vehicles shall be constructed of noncombustible materials and shall be provided with a packing gland or other device which will preclude fuel leakage between reels and fuel manifolds.
2006.3.7 Electrical bonding provisions.
Transfer apparatus shall be metallically interconnected with tanks, chassis, axles and springs of aircraft-fueling vehicles.
2006.3.7.1 Bonding cables.
Aircraft-fueling vehicles shall be provided and maintained with a substantial heavy-duty electrical cable of sufficient length to be bonded to the aircraft to be serviced. Such cable shall be metallically connected to the transfer apparatus or chassis of the aircraft-fueling vehicle on one end and shall be provided with a suitable metal clamp on the other end, to be fixed to the aircraft.
2006.3.7.2 Bonding cable protection.
The bonding cable shall be bare or have a transparent protective sleeve and be stored on a reel or in a compartment provided for no other purpose. It shall be carried in such a manner that it will not be subjected to sharp kinks or accidental breakage under conditions of general use.
2006.3.8 Smoking.
It shall be unlawful to smoke in aircraft-fueling vehicles. Signs to this effect shall be conspicuously posted in the driver's compartment of all fueling vehicles.
2006.3.9 Smoking equipment.
Smoking equipment such as cigarette lighters and ash trays shall not be provided in aircraft-fueling vehicles.
2006.4 Operation, maintenance and use of aircraft-fueling vehicles.
The operation, maintenance and use of aircraft-fueling vehicles shall be in accordance with FC 2006.4.1 through 2006.4.5 and other applicable provisions of this chapter.
2006.4.1 Proper maintenance.
Aircraft-fueling vehicles and all related equipment shall be properly maintained and kept in good repair. Oil, grease, fuel and other flammable or combustible waste shall not be allowed to accumulate. Maintenance and servicing of such equipment shall be accomplished in approved areas.
2006.4.2 Vehicle integrity.
Tanks, pipes, hoses, valves and other fueling equipment shall be maintained leak free at all times.
2006.4.3 Removal from service.
Aircraft-fueling vehicles and related equipment which are in violation of FC 2006.4.1 or 2006.4.2 shall be immediately defueled, removed from service and properly repaired or disposed of.
2006.4.4 Identification of operator.
Aircraft-fueling vehicles that are operated by a person, firm or corporation other than the permittee or the permittee's authorized employee shall be provided with a legible sign visible from outside the vehicle showing the name of the person, firm or corporation operating such unit.
2006.4.5 Training.
Aircraft-fueling vehicles shall be attended and operated by competent personnel familiar with the safety hazards of each type of fuel used at the facility.
2006.5 Fueling and defueling.
Aircraft-fueling and defueling operations shall be conducted in accordance with FC 2006.5.1 through 2006.5.4.
2006.5.1 Positioning of aircraft-fueling vehicles.
Aircraft-fueling vehicles shall not be parked or otherwise allowed to stop or stand in a position where such vehicle would obstruct egress from an aircraft, including emergency exits. Aircraft-fueling vehicles shall not be parked or otherwise allowed to stop or stand under any portion of an aircraft.
Exception: Aircraft-fueling vehicles shall be allowed to be located under aircraft wings during underwing fueling of turbine-engine powered aircraft.
2006.5.1.1 Fueling vehicle egress.
A clear path shall be maintained for aircraft-fueling vehicles to allow ready access to and egress from the fueling area.
2006.5.1.2 Aircraft vent openings.
A clear space of at least 10 feet (3048 mm) shall be maintained between aircraft fuel-system vent openings and an aircraft-fueling vehicle.
2006.5.1.3 Parking.
Prior to leaving the cab, the operator of an aircraft-fueling vehicle shall set the parking brake. At least two chock blocks not less than 5 inches by 5 inches by 12 inches (127 mm by 127 mm by 305 mm) in size and dished to fit the contour of the tires shall be utilized and positioned in such a manner so as to preclude movement of the vehicle in any direction.
2006.5.2 Electrical bonding.
Aircraft-fueling vehicles shall be electrically bonded to the aircraft being fueled or defueled. Bonding connections shall be made prior to making fueling connections and shall not be disconnected until the fuel-transfer operations are completed and the fueling connections have been removed. Where a hydrant service vehicle or cart is used for fueling, the hydrant coupler shall be connected to the hydrant system prior to bonding the fueling equipment to the aircraft.
2006.5.2.1 Conductive hose.
In addition to the bonding cable required by FC 2006.5.2, conductive hose shall be used for all fueling operations.
2006.5.2.2 Bonding conductors on transfer nozzles.
Transfer nozzles shall be equipped with approved bonding conductors which shall be clipped or otherwise positively engaged with the bonding attachment provided on the aircraft adjacent to the fuel tank cap prior to removal of the cap.
Exception: In the case of overwing fueling where no appropriate bonding attachment adjacent to the fuel fill port has been provided on the aircraft, the fueling operator shall touch the fuel tank cap with the nozzle spout prior to removal of the cap. The nozzle shall be kept in contact with the fill port until fueling is completed.
2006.5.2.3 Funnels.
It shall be unlawful to use funnels in aircraft-fueling operations.
2006.5.3 Training.
All personnel engaged in fuel storage and aircraft-fueling operations shall receive appropriate hazard and fire safety training relating to such storage and fueling operation, including training in the use of fire extinguishing equipment. The owner or operator of the aviation facilities shall maintain on the premises a record of all such training in accordance with FC 107.7.
2006.5.4 Transfer personnel.
During fuel-transfer operations, a qualified person shall be in control of each transfer nozzle and another qualified person shall be in immediate control of the fuel-pumping equipment to shut off or otherwise control the flow of fuel from the time fueling operations are begun until they are completed.
Exceptions:
1. For underwing refueling, the person stationed at the point of fuel intake is not required.
2. For overwing refueling, the person stationed at the fuel pumping equipment shall not be required when the person at the fuel dispensing device is within 75 feet (22 800 mm) of the emergency shutoff device, is not on the wing of the aircraft and has a clear and unencumbered path to the fuel pumping equipment; and, the fuel dispensing line does not exceed 50 feet (15 240 mm) in length.
2006.5.4.1 Monitoring during fueling.
The fueling operator shall monitor the panel of the fueling equipment and the aircraft control panel during pressure fueling or shall monitor the fill port during overwing fueling.
2006.6 Emergency fuel shutoff.
Emergency fuel shutoff controls and procedures shall comply with the requirements of FC 2006.6.1 through 2006.6.4.
2006.6.1 Accessibility.
Emergency fuel shutoff controls shall be readily accessible at all times when the fueling system is being operated.
2006.6.2 Notification of the department.
The owner or operator of the aviation facility shall establish a procedure by which the department will be notified in the event of an emergency involving the activation of an emergency fuel shutoff control.
2006.6.3 Determining cause.
Prior to reestablishment of normal fuel flow, the cause of emergency fuel shutoff conditions shall be determined and corrected.
2006.6.4 Testing.
Emergency fuel shutoff devices shall be operationally tested at intervals not exceeding 3 months. The fueling-system operator shall maintain suitable records of these tests.
2006.7 Protection of hoses.
Before an aircraft-fueling vehicle is moved, fuel transfer hoses shall be properly placed on the approved reel or in the compartment provided, or stored on the top decking of the fueling vehicle if proper height rail is provided for security and protection of such equipment. Fuel-transfer hose shall not be looped or draped over any part of the fueling vehicle, except as herein provided. Fuel-transfer hose shall not be dragged when a fueling vehicle is moved from one fueling position to another.
2006.8 Loading and unloading of aircraft-fueling vehicles.
Aircraft-fueling vehicles shall be loaded only at an approved loading rack, except that aircraft-fueling vehicles may be loaded from the fuel tanks of an aircraft during defueling operations. Such loading racks shall be in accordance with FC Chapter 57.
2006.8.1 Unloading of aircraft-fueling vehicles.
The fuel cargo of such vehicles shall be unloaded only by approved transfer apparatus into the fuel tanks of aircraft, approved underground storage tanks or approved aboveground storage tanks.
2006.9 Passengers.
Passenger traffic is not allowed during the time that fuel transfer operations are in progress.
2006.10 Sources of ignition.
It shall be unlawful to smoke, or light or maintain an open flame, within 50 feet (15 240 mm) of any location where fuel is being transferred. Electrical and motor-driven devices shall not be connected to or disconnected from an aircraft at any time fueling operations are in progress on such aircraft.
2006.11 Fuel spill prevention and procedures.
Fuel spill prevention and the procedures for handling spills shall comply with the requirements of FC 2006.11.1 through 2006.11.7.
2006.11.1 Fueling equipment maintenance.
Aircraft fueling equipment shall be maintained and kept free from leaks. Fueling equipment that malfunctions or leaks shall be immediately defueled, removed from service and properly repaired or disposed of.
2006.11.2 Transporting fuel nozzles.
Fuel nozzles shall be carried utilizing appropriate handles. Dragging fuel nozzles along the ground is prohibited.
2006.11.3 Drum fueling.
Fueling from drums or other containers is prohibited.
2006.11.4 Fuel spill procedures.
The owner or operator of the aviation facility shall establish comprehensive procedures to implement in the event of a fuel spill, which shall include the following actions:
1. Upon observation of a fuel spill, the aircraft-fueling operator shall immediately stop the delivery of fuel by releasing hand pressure from the fuel flow-control valve.
2. Failure of the fuel control valve to stop the continued spillage of fuel shall be cause for the activation of the appropriate emergency fuel shutoff device.
3. A supervisor shall respond to the fuel spill area immediately.
2006.11.5 Notification of the department.
The department shall be notified of any fuel spill which is considered a hazard to people or property or which meets one or more of the following criteria:
1. Any dimension of the spill is greater than 10 feet (3048 mm).
2. The spill area is greater than 50 square feet (4.65 m 2 ).
3. The release of fuel is continuing.
2006.11.6 Investigation required.
An investigation shall be conducted by the owner or operator of the aviation facility into the cause of all spills requiring notification of the department, the response thereto by the persons in charge of the aircraft fueling operation and other aviation facility personnel. Should it be determined that corrective measures are necessary to prevent future incidents of the same nature, such measures shall be implemented in a timely manner.
2006.11.7 Multiple fuel delivery vehicles.
Simultaneous delivery of fuel from more than one aircraft-fueling vehicle to a single aircraft-fueling manifold is prohibited unless proper backflow prevention devices are installed to prevent fuel flow into the aircraft-fueling vehicles.
2006.12 Aircraft engines and heaters.
Aircraft onboard engines and combustion heaters shall be shut down prior to commencing fueling operations and shall remain off until the fueling operation is completed.
Exception: In an emergency, a single jet engine is allowed to be operated with the onboard engine running during fueling operations where all of the following conditions are met:
1. The emergency shall have resulted from an onboard failure of the aircraft's auxiliary power unit.
2. Restoration of auxiliary power to the aircraft by ground support services is not available.
3. The engine to be operated is either at the rear of the aircraft or on the opposite side of the aircraft from the fueling operations.
4. The emergency operation is in accordance with a written procedure approved by the commissioner.
2006.13 Vehicle and equipment restrictions.
During aircraft-fueling operations, only aircraft-fueling vehicles or other equipment actively involved in the fueling operation are allowed within 50 feet (15 240 mm) of the aircraft being fueled. Other aircraft-fueling vehicles or equipment are prohibited in this area until the fueling operation is complete.
Exception: Aircraft-fueling operations utilizing single-point refueling with a sealed, mechanically locked fuel line connection and the fuel is not a flammable liquid.
2006.13.1 Overwing fueling.
Vehicles or equipment shall not be allowed beneath the trailing edge of the wing when aircraft fueling takes place over the wing and the aircraft fuel-system vents are located on the upper surface of the wing.
2006.14 Electrical equipment.
Electrical equipment, including but not limited to, battery chargers, ground or auxiliary power units, fans, compressors or tools, shall not be operated, nor shall they be connected or disconnected from their power source, during fueling operations.
2006.14.1 Other equipment.
Electrical or other spark-producing equipment shall not be used within 10 feet (3048 mm) of fueling equipment, aircraft fill or vent points, or spill areas unless such equipment is intrinsically safe and approved for use in an explosive atmosphere.
2006.15 Reserved.
2006.16 Lightning.
The commissioner may require the owner or operator of an aviation facility to establish criteria for the suspension and resumption of aircraft-fueling operations and other written procedures to implement in the event of lightning flashes at or near the aviation facility.
2006.17 Fuel-transfer locations.
It shall be unlawful to conduct aircraft-fueling operations indoors.
Exception: In aircraft hangars designed in accordance with the Building Code for Group F-1 occupancies, aircraft fuel-transfer operations are allowed where:
1. Such operation is necessary to accomplish aircraft fuel-system maintenance operations. Such operations shall be performed in accordance with nationally recognized standards; or
2. The fuel being used has a flash point greater than 100°F (37.8°C).
2006.17.1 Position of aircraft.
Aircraft being fueled shall be positioned such that any fuel system vents and other fuel tank openings are a minimum of:
1. Twenty-five feet (7620 mm) from buildings or structures other than jet bridges; and
2. Fifty feet (15 240 mm) from air intake vents for boiler, heater or incinerator rooms.
2006.17.2 Fire equipment access.
Access for fire service equipment to aircraft shall be maintained during aircraft-fueling operations.
2006.18 Defueling operations.
The requirements for aircraft-fueling operations contained in this section shall also apply to aircraft-defueling operations. Additional procedures shall be established by the owner or operator of the aviation facility to prevent overfilling of the cargo tank or other vehicle used in the defueling operation.
2006.19 Maintenance of aircraft-fueling hose.
Aircraft-fueling hoses shall be maintained in accordance with FC 2006.19.1 through 2006.19.4.
2006.19.1 Inspections.
Hoses used to fuel or defuel aircraft shall be inspected periodically to ensure their serviceability and suitability for continued service.
2006.19.1.1 Daily inspection.
Hoses shall be inspected daily. This inspection shall include a complete visual scan of the exterior for evidence of damage, blistering or leakage. Each coupling shall be inspected for evidence of leaks, slippage or misalignment.
2006.19.1.2 Monthly inspection.
A more thorough inspection, including pressure testing, shall be performed on each hose on a monthly basis. This inspection shall include examination of the fuel delivery inlet screen for rubber particles, which may indicate deterioration of the hose lining.
2006.19.2 Damaged hose.
Hose that has been damaged shall be immediately removed from service.
2006.19.3 Repairing hose.
Hoses are allowed to be repaired by removing the damaged portion and recoupling the undamaged end. When recoupling hoses, only couplings designed and approved for the size and type of hose in question shall be used. Hoses repaired in this manner shall be visually inspected and hydrostatically tested prior to being placed back in service.
2006.19.4 New hose.
New hose shall be visually inspected prior to being placed into service.
2006.20 Aircraft-fueling vehicles parking.
Unattended aircraft-fueling vehicles shall be parked in areas that provide for both the unencumbered dispersal of vehicles in the event of an emergency and the control of leakage such that adjacent buildings and storm drains are not contaminated by leaking fuel.
2006.20.1 Parking area design.
Parking areas for aircraft-fueling vehicles shall be designed and utilized such that a clearance of 10 feet (3048 mm) is maintained between each parked vehicle for department access. In addition, a minimum clearance of 50 feet (15240 mm) shall be maintained between aircraft-fueling vehicles and parked aircraft and structures other than those used for the maintenance of aircraft-fueling vehicles. Aircraft-fueling vehicles shall not be stored indoors.
2006.21 Radar equipment.
Aircraft-fueling operations shall be prohibited while the weather-mapping radar of that aircraft is operating. Aircraft-fueling or other operations in which flammable liquids, vapors or mists may be present shall not be conducted within 300 feet (91440 mm) of an operating aircraft surveillance radar. Aircraft-fueling operations shall not be conducted within 300 feet (91 440 mm) of airport flight traffic surveillance radar equipment. Aircraft-fueling or other operations in which flammable liquids, vapors or mists may be present shall not be conducted within 100 feet (30 480 mm) of airport ground traffic surveillance radar equipment.
2006.21.1 Direction of radar beams.
The beam from ground radar equipment shall not be directed toward fuel storage or loading racks.
Exceptions:
1. Fuel storage and loading racks in excess of 300 feet (91 440 mm) from airport flight traffic surveillance equipment.
2. Fuel storage and loading racks in excess of 100 feet (30 480 mm) from airport ground traffic surveillance equipment.
Section FC 2007. Helistops and Heliports
2007.1 General.
Helistops and heliports shall be maintained in accordance with this section. Helistops and heliports on buildings or structures shall be constructed in accordance with the construction codes, including the Building Code.
2007.2 Clearances.
The touchdown area shall be surrounded on all sides by a clear area having minimum average width at roof level of 15 feet (4572 mm) but no width less than 5 feet (1524 mm). The clear area shall be maintained.
2007.3 Flammable and Class II combustible liquid spillage.
Landing areas on buildings or structures shall be maintained so as to confine flammable or Class II combustible liquid spillage to the landing area itself, and provisions shall be made to drain such spillage away from exits or stairways serving the helicopter landing area or from a structure housing such exit or stairway.
2007.4 Exits.
Exits and stairways shall be maintained in accordance with the construction codes, including the Building Code.
2007.5 Standpipe systems.
Where a building with a rooftop helistop or heliport is equipped with a standpipe system, the system shall be extended to the roof level on which the helistop or heliport is located. All portions of the helistop and heliport area shall be within 150 feet (45 720 mm) of a standpipe system outlet connection.
2007.6 Foam protection.
Foam fire-protection capabilities shall be provided for rooftop heliports as required by the construction codes, including the Building Code. Such systems shall be designed, installed, operated and maintained in accordance with FC Chapter 9.
2007.6.1 Initial foam fire extinguishing system test.
Upon installation, a foam fire extinguishing system shall be tested in accordance with FC Chapter 9. The test shall be conducted at the owner's risk by his or her representative before a representative of the department.
2007.6.2 Periodic foam fire extinguishing system test.
The foam fire extinguishing system shall be inspected, tested and maintained in accordance with FC Chapter 9. Additionally, the foam fire extinguishing system shall be tested at least once every 2 years, as required in FC 5706.4.10.7.
2007.7 Portable fire extinguishers.
A minimum of one portable fire extinguisher having a minimum 80-B:C rating shall be provided for each permanent takeoff and landing area and for the aircraft parking areas. Installation, inspection and maintenance of these portable fire extinguishers shall be in accordance with FC 906.
2007.8 Federal approval.
Before operating helicopters from helistops and heliports, approval shall be obtained from the Federal Aviation Administration and any other federal, state or city authority having jurisdiction.
Section FC 2008. Seaplane Base Operations
2008.1 General.
Seaplane bases shall be operated in accordance with the requirements of FC 2001 through 2006, as applicable. Notwithstanding any provision of this code to the contrary, a waterfront liquid motor fuel dispensing facility used for the fueling of seaplanes shall be deemed to constitute a marine liquid motor fuel dispensing facility.
Section FC 2009. Helicopter Landing Operations
2009.1 General.
Helicopter landing operations, at other than an approved heliport or helistop, shall be conducted in accordance with this section.
2009.2 Permit application.
The owner or operator of the helicopter conducting the helicopter landing operation shall make a permit application to the department at least 20 calendar days prior to the proposed landing. The permit applications shall be on such form and include such information and documentation as the commissioner may require, including the following:
1. A site map of the area in which the helicopter landing operation is proposed to be conducted.
2. Proof of a liability and casualty insurance policy in an amount to be determined by the commissioner but not less than two million dollars. Such insurance policy shall cover the permit holder and the permit holder's employees, agents and contractors for any loss, damage or injury to persons or property by reason of the conduct of the helicopter landing operation, or the failure to comply with any requirement of this chapter or the rules, or the terms and conditions of the permit.
3. A copy of the pilot's license issued by the Federal Aviation Administration.
4. A copy of the aircraft's airworthiness certificate issued by the Federal Aviation Administration.
5. An affidavit of the property owner authorizing the helicopter landing operation on their property.
2009.3 Required clearances.
The location at which the helicopter landing operations are to be conducted is subject to the approval of the department. The commissioner may specify the open space clearances to be provided.
Section FC 2010. Helicopter Lift Operations
2010.1 General.
Helicopter lift operations shall be conducted in accordance with this section.
2010.1.1 Department of Buildings approval.
Helicopter lift operations shall not be conducted except when the Commissioner of Buildings has authorized such operation.
2010.2 Permit application.
The owner or operator of the helicopter used to conduct the lift operation shall make application to the department for a permit at least 20 calendar days prior to the proposed lift operation. The permit application shall be on such form and include such information and documentation as the commissioner may require, including the following:
1. A site map of the area in which the lifting operation is proposed to be conducted.
2. Proof of a liability and casualty insurance policy in an amount to be determined by the commissioner but not less than five million dollars. Such insurance policy shall cover the permit holder and the permit holder's employees, agents and contractors from any loss, damage or injury to persons or property by reason of the conduct of the lift operation, or the failure to comply with any requirement of this chapter or the rules, or the terms and conditions of the permit.
3. A copy of the pilot's license issued by the Federal Aviation Administration.
4. A copy of the aircraft's airworthiness certificate issued by the Federal Aviation Administration.
5. An affidavit of the property owner authorizing the helicopter lift operation on their property.
2010.3 Helicopter fueling.
It shall be unlawful to fuel helicopters in the staging or discharge area.
2010.3.1 Portable fuel tanks.
Portable fuel tanks or drums within or on the exterior of the helicopter are prohibited. Auxiliary fuel storage tanks may be used provided they are an integral part of the aircraft's fuel system and of a type meeting the requirements of the Federal Aviation Administration.
2010.4 Smoking.
It shall be unlawful to smoke within 100 feet (30 480 mm) of a fuel storage area or fueling operation. It shall be unlawful to smoke within 100 feet (30 480 mm) of the helicopter staging area or discharge area while lift operations are being conducted.
2010.5 Staging and discharge areas.
The location of the staging and discharge areas, and their distance from any buildings or other impediments to flight, shall be subject to the approval of the commissioner, and shall be arranged and operated as set forth in FC 2010.5.1 and 2010.5.2.
2010.5.1 Emergency access.
Entrances to and exits from any premises or other location wherein lifting operations are being conducted shall be safeguarded in accordance with applicable laws, rules and regulations, but shall not be obstructed in a manner that prevents access or egress in the event of an emergency.
2010.5.2 Restricted locations.
Bulk plants or terminals or other premises where hazardous operations or occupancies are maintained shall not be used as a staging area or discharge area unless approved by the commissioner.
2010.6 Fire protection.
An adequate supply of water shall be provided at the location where lifting operations are conducted. When the discharge area or other area of the lifting operation requires the use of a fire pump or other auxiliary equipment to augment the water supply, such equipment shall be under the personal supervision of a certificate of fitness holder.
2010.6.1 Foam protection.
An air foam nozzle, pick-up tube and a minimum of 5 gallons (19 L) of foam, suitable for the fuel hazard presented, shall be available on site.
2010.6.2 Portable fire extinguishers.
Both the staging area and discharge area shall be provided with a minimum of two portable fire extinguishers each having a minimum 80-B:C rating.
2010.6.3 Department monitoring.
Lift operations allowed pursuant to this section may be monitored by representatives of the department to ensure compliance with the requirements of this chapter and the rules. Such representatives shall be allowed within the perimeter of the lift operation for such purpose.
2010.7 Communication.
Radio and/or other two-way wireless communication shall be maintained between the helicopter pilot and the ground at all times during the lift operation. The department representatives monitoring the lifting operation shall be provided with the ability to monitor such communications.
2010.8 Discontinuance.
Department representatives may temporarily suspend or cancel any lifting operation if, in their judgment, conditions exist that endanger public safety.
Section FC 2011. Hot Air Balloon Operations
2011.1 General.
Hot air balloon operations shall be conducted in accordance with this section.
2011.1.1 Storage, handling and use of flammable gas.
The storage, handling and use of LPG or other flammable gas for hot air balloon operations shall additionally be conducted in accordance with FC Chapters 58 and 61, as applicable, and the rules.
2011.2 Permit application.
The owner or operator of the hot air balloon, or in the case of an event involving multiple owners or operators of hot air balloons, the sponsor of such event, shall make application to the department for a permit at least 20 calendar days prior to any anticipated or scheduled operation. Permit applications shall be on such form and include such information and documentation as the commissioner may require, including the following:
1. A site map of the area in which the hot air balloon operation is proposed to be conducted.
2. Proof of a liability and casualty insurance policy in an amount to be determined by the commissioner but not less than two million dollars. Such insurance policy shall cover the permit holder and the permit holder's employees, agents and contractors from any loss, damage or injury to persons or property by reason of the conduct of the lifting operation, or the failure to comply with any requirement of this chapter or the rules, or the terms and conditions of the permit.
3. A copy of the pilot's license issued by the Federal Aviation Administration.
4. A copy of the aircraft's airworthiness certificate issued by the Federal Aviation Administration.
5. An affidavit of the property owner authorizing the hot air balloon operation on their property.
6. All information and documentation required for issuance of a permit for LPG storage, handling and use in connection with the hot air balloon operation pursuant to FC Chapter 61 and the rules.
2011.3 Required clearances.
The location at which hot air balloon operations are to be conducted are subject to the approval of the department, provided, however, that a balloon shall not be secured or filled unless there is at least 150 feet (45 720 mm) of open space in all directions when measured from the center of the balloon.
2011.4 Securing of balloons.
Balloons shall have at least a three-point tie down to substantially immovable objects.
2011.5 Weather conditions.
Hot air balloon operations shall be conducted only under weather conditions conducive to such operation and in no circumstance when prevailing winds exceed 15 miles (24.135 km) per hour.
2011.6 Discontinuance.
Department representatives may temporarily suspend or cancel any hot air balloon operation if, in their judgment, conditions exist that endanger public safety.
Section FC 2101. General
2101.1 Scope.
This chapter shall govern the design, installation, operation and maintenance of dry cleaning facilities.
2101.2 Permits.
Permits shall be required as set forth in FC 105.6.
2101.3 General.
Dry cleaning facilities shall be designed, installed, operated and maintained in accordance with this chapter.
2101.4 Supervision.
Dry cleaning facilities using Class II or III solvents in dry cleaning systems shall be under the general supervision of a certificate of fitness holder. Such certificate of fitness holder shall be an employee of the dry cleaning facility. The certificate of fitness holder shall monitor the equipment and facilities, ensure that the equipment and facilities are operated and maintained in accordance with this section, and instruct all employees who use or supervise the use of equipment in the proper operation and maintenance of such equipment.
Exception: Dry cleaning facilities may be operated under the general supervision of a person who is not an employee of the dry cleaning facility, provided that such person:
1. Holds a certificate of fitness.
2. Is an authorized representative of the manufacturer of the dry cleaning equipment, and provides the owner of the dry cleaning facility with appropriate proof of such authority.
3. Instructs all employees of the dry cleaning facility who use or supervise the use of the equipment in the proper operation and maintenance of the equipment.
4. Personally conducts a monthly inspection of the equipment and facility to ensure that they are being operated and maintained in accordance with this section.
5. Records each monthly inspection in a logbook maintained on the premises by the owner of the dry cleaning facility, by making the following entries: the date of the inspection, the name, address, and certificate of fitness number and expiration date of the person conducting the inspection and the certification that the equipment and facility are being operated and maintained in accordance with this section.
2101.4.1 Proof of qualification.
Photocopies of the certificates of fitness of all persons responsible for the supervision of a dry cleaning facility, and of the proof that such person is an authorized representative of the manufacturer, where applicable, shall be maintained on the premises and made available for inspection by any representative of the department.
Section FC 2102. Definitions
2102.1 Definitions.
The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.
DRY CLEANING.
DRY CLEANING FACILITY.
DRY CLEANING ROOM.
DRY CLEANING SYSTEM.
Section FC 2103. Classifications
2103.1 Dry cleaning solvent classifications.
Dry cleaning solvents shall be classified according to their flash points as follows:
1. Class I solvents are flammable liquids having a flash point below 100°F (38°C).
2. Class II solvents are combustible liquids having a flash point at or above 100°F (38°C) and below 140°F (60°C).
3. Class IIIA solvents are combustible liquids having a flash point at or above 140°F (60°C) and below 200°F (93°C).
4. Class IIIB solvents are combustible liquids having a flash point at or above 200°F (93°C).
5. Class IV solvents are liquids that are neither flammable nor combustible.
2103.2 Classification of dry cleaning systems and facilities.
Dry cleaning systems shall be classified based on the use of solvents as follows:
1. Type I – systems using Class I solvents.
2. Type II – systems using Class II solvents.
3. Type III-A – systems using Class IIIA solvents.
4. Type III-B – systems using Class IIIB solvents.
5. Type IV – systems using Class IV solvents in which dry cleaning is not conducted by the public.
6. Type V – systems using Class IV solvents in which dry cleaning is conducted by the public.
2103.2.1 Multiple solvents.
Dry cleaning facilities using more than one class of dry cleaning system shall be classified based on the numerically lowest type of system.
2103.2.2 Spotting and pretreating operations.
Spotting and pretreating operations conducted in accordance with FC 2106 shall not affect the classification of the dry cleaning system or facility.
2103.3 Design.
Dry cleaning facilities shall be designed and constructed in accordance with the construction codes, including the Building Code, and located in accordance with the Zoning Resolution, including Sections 32-15(A) and 32-25(D).
Section FC 2104. General Requirements
2104.1 Prohibited dry cleaning systems.
It shall be unlawful to install, operate or maintain a Type I dry cleaning system.
2104.1.1 Allowed use of Class I solvents.
Class I solvents stored, handled and used in the amounts authorized by FC 2106 are allowed in dry cleaning facilities.
2104.2 Building services and systems.
Building services and systems shall be designed, installed, operated and maintained in accordance with this section, FC Chapter 6 and the construction codes, including the Building Code.
2104.2.1 Ventilation.
Ventilation shall be provided in accordance with the construction codes, including Chapter 5 of the Mechanical Code, and United States Department of Labor regulations, as set forth in 29 CFR Section 1910.1000, as applicable.
2104.2.2 Heating.
In Type II dry cleaning facilities, heating shall be by indirect means using steam or hot water.
2104.2.3 Electrical wiring and equipment.
Electrical wiring and equipment in dry cleaning rooms or other portions of the facility exposed to flammable vapors shall be installed in accordance with the Electrical Code.
2104.2.4 Bonding and grounding.
Storage tanks, treatment tanks, filters, pumps, piping, ducts, dry cleaning units, stills, tumblers, drying cabinets and other dry cleaning equipment, where not inherently electrically conductive, shall be bonded together and grounded. Isolated equipment shall be grounded.
2104.2.5 Smoking prohibited.
It shall be unlawful to smoke in a dry cleaning facility. "NO SMOKING" signs in compliance with the requirements of FC 310 shall be conspicuously posted.
Section FC 2105. Operating and Maintenance Requirements
2105.1 General.
Dry cleaning systems shall be operated and maintained in compliance with the requirements of this section, the manufacturer's specifications and the construction codes, including the Building Code.
2105.1.1 Written instructions.
The manufacturer's manuals for the installation, operation and maintenance of the equipment shall be maintained on the premises and made available for inspection by any representative of the department.
2105.1.1.1 Type II, III-A, III-B and IV systems.
Type II, III-A, III-B and IV dry cleaning systems shall be operated in accordance with the instructions provided by the manufacturer. The owner shall ensure that all persons operating dry cleaning equipment comply with such instructions.
2105.1.1.2 Type V systems.
Operating instructions for customer use of Type V dry cleaning systems shall be conspicuously posted in a location near the dry cleaning equipment. A telephone number shall be provided for emergency assistance.
2105.1.2 Equipment identification.
The manufacturer shall permanently affix to dry cleaning equipment nameplates indicating the class of solvent for which each piece of equipment is designed. The name of the dry cleaning solvent approved for use in dry cleaning equipment shall be clearly and conspicuously marked or posted at the fill connection of the equipment.
2105.1.3 Prohibited operations.
It shall be unlawful to dry clean by immersion and agitation in open systems.
2105.1.4 Prohibited use of solvent.
Only solvents of a type listed for a particular piece of equipment shall be used in such equipment.
2105.1.5 Equipment maintenance and housekeeping.
Proper operating practices and maintenance shall be observed in order to prevent the leakage of solvent or the accumulation of lint. The handling of waste generated by dry cleaning operations and the maintenance of facilities shall comply with the requirements of this section.
2105.1.5.1 Floors.
Class I and II liquids as defined in FC 202 shall not be used for cleaning floors.
2105.1.5.2 Filters.
Filter residue and other waste containing solvent shall be stored in covered metal containers and disposed of lawfully.
2105.1.5.3 Lint.
Lint and other waste shall be removed from traps daily, deposited in approved waste cans and disposed of lawfully. Lint traps shall remain in place while the dry cleaning equipment is in operation.
2105.1.5.4 Customer areas.
In Type V dry cleaning systems, customer areas shall be kept free of rubbish and other combustible waste.
2105.2 Type II systems.
Type II dry cleaning systems shall be operated in accordance with the following additional requirements.
2105.2.1 Inspection of items.
Items to be dry cleaned shall be searched thoroughly, and foreign materials, including matches and metallic substances, shall be removed.
2105.2.2 Transfer.
In removing dry cleaned items from the washer, provision shall be made to minimize the dripping of solvent onto the floor. Where items are transferred from a washer to a drain tub, a nonferrous metal drip apron shall be placed so that the apron rests on the drain tub and the cylinder of the washer.
2105.2.3 Ventilation.
A mechanical ventilation system shall be installed in dry cleaning rooms and in drying rooms in accordance with the construction codes, including the Mechanical Code. The ventilation system shall operate automatically when the dry cleaning equipment is in operation and shall have manual controls at an approved location.
2105.3 Type III, IV and V systems.
Type III, IV and V dry cleaning systems shall be provided with an automatically activated exhaust ventilation system as required and in accordance with the construction codes, including the Mechanical Code.
2105.4 Periodic inspection and testing.
All dry cleaning equipment using Class II or III solvents shall be inspected and tested on at least an annual basis. The owner of the dry cleaning facility shall remove from service any equipment that is found to be defective, and shall promptly repair such equipment or remove it from the premises. Such equipment shall not be returned to service until it has been inspected and tested. All such inspection and testing shall be performed by a person holding a certificate of fitness.
2105.4.1 Inspection reports.
The individual performing the inspection and testing of equipment shall prepare a written report identifying any defects in the condition and operation of the equipment and/or certifying that the equipment can be safely operated in accordance with this chapter. A certification that all equipment in service is in proper working order in accordance with this chapter shall be maintained on the premises for 3 years and made available for inspection by any representative of the department.
2105.5 Filling and emptying.
The filling and emptying of dry cleaning equipment with Class II or III solvents shall be performed by a certificate of fitness holder. Each filling and emptying of dry cleaning equipment with a Class II or III solvent shall be recorded in a logbook. Such records shall include the date of the filling or emptying, the type and amount of dry cleaning solvent, the equipment filled or emptied, and the name and certificate number of the certificate of fitness holder who performed the filling or emptying.
Section FC 2106. Spotting and Pretreating
2106.1 General.
The storage, handling and use of dry cleaning solvents for spotting and pretreating operations in any dry cleaning facility shall comply with the requirements of this section, based on the classification of the solvent.
2106.2 Class I solvents.
The maximum quantity of Class I solvents allowed at any dry cleaning facility shall be 1 gallon (4 L). Class I solvents shall be stored in approved metal containers or safety cans of not more than 2 quarts (2 L) capacity.
2106.3 Class II and III solvents.
Spotting and pretreating, including scouring and brushing, shall be conducted with Class II or III solvents. The maximum quantity of Class II or III solvents allowed at any work station shall be 1 gallon (4 L). In an occupancy other than a Group H-2 occupancy, the aggregate quantities of solvents shall not exceed the maximum allowable quantity per control area for use-open systems.
2106.3.1 Spotting tables.
Scouring, brushing or spotting tables on which items are soaked in solvent shall have a liquid-tight top with a curb on all sides not less than 1 inch (25 mm) high. The top of the table shall be pitched to ensure thorough draining to a 1 1/2-inch (38-mm) drain connected to an approved container.
2106.3.2 Special handling.
Items that may be damaged from being washed in the washing equipment may be manually cleaned in scrubbing tubs. Scrubbing tubs shall comply with the following requirements:
1. Only Class II or III liquids shall be used.
2. The total amount of solvent used in such tubs shall not exceed 3 gallons (11 L).
3. Scrubbing tubs shall be secured to the floor.
4. Scrubbing tubs shall be provided with permanent 1 1/2-inch (38-mm) drains. Such drains shall be provided with a trap and shall be connected to an approved container.
2106.3.3 Ventilation.
Scrubbing tubs, scouring, brushing or spotting operations shall be located such that solvent vapors are captured and exhausted by the ventilating system.
2106.3.4 Bonding and grounding.
Metal scouring, brushing and spotting tables and scrubbing tubs shall be permanently and effectively bonded and grounded.
2106.4 Reserved.
2106.5 Prohibited spotting and pretreating operation.
It shall be unlawful to store, handle or use any Class I, Class II or Class III solvent for spotting or pretreating operations in any Type V dry cleaning facility or in connection with the use of any Type V dry cleaning system.
Section FC 2107. Dry Cleaning Systems
2107.1 General equipment requirements.
Dry cleaning systems, including dry cleaning units, washing equipment, stills, drying cabinets, tumblers, and their appurtenances, including pumps, piping, valves, filters and solvent coolers, shall be designed, installed, operated and maintained in accordance with NFPA 32, the manufacturer's specifications, and the construction codes, including the Building Code.
2107.2 Type II systems.
Type II dry cleaning and solvent tank storage rooms shall not be located below grade or above the lowest floor level of the building and shall comply with the requirements of FC 2107.2.1 through 2107.2.3.
Exception: Solvent storage tanks installed underground, in vaults or in special enclosures in accordance with FC Chapter 57.
2107.2.1 Firefighting access.
Type II dry cleaning facilities shall be located so that access is provided and maintained from at least one side for firefighting and fire control purposes in accordance with FC 503 and the construction codes, including the Building Code.
2107.2.2 Means of egress.
Type II dry cleaning rooms shall have not less than two means of egress through doors located at opposite ends of the room, at least one of which shall lead directly to the outdoors.
2107.2.3 Spill control and secondary containment.
Curbs, drains, or other provisions for spill control and secondary containment shall be provided in accordance with FC 5004.2 to collect solvent leakage and fire protection water and direct it to a safe location.
2107.3 Solvent storage tanks.
Solvent storage tanks for Class II, IIIA and IIIB liquids shall conform to the requirements of FC Chapter 57 and be located underground, or outdoors, aboveground.
Exception: Indoor storage tanks in compliance with the requirements of NFPA 32 and FC Chapter 57.
Section FC 2108. Fire Protection
2108.1 General.
Where required by this section, fire protection devices, equipment and systems shall be designed, installed, operated and maintained in accordance with FC Chapter 9 and the construction codes, including the Building Code.
2108.2 Fire extinguishing systems in newly-established dry cleaning facilities.
Dry cleaning facilities established after the effective date of FC 2108.2 shall be protected throughout by a sprinkler system, provided, however, that a heretofore lawfully-existing dry cleaning establishment in a newly-established facility may comply with the requirements of FC 2108.3 if the newly-established facility does not constitute a change in the use or occupancy of the premises, as determined by the Department of Buildings. The sprinkler system shall be designed and installed in accordance with the Building Code.
2108.2.1 Type II dry cleaning facilities.
Type II dry cleaning facilities shall be protected throughout by a sprinkler system. Type II dry cleaning units, washer-extractors and drying tumblers in such facilities shall additionally be protected by an approved automatic non-sprinkler fire extinguishing system installed and maintained in accordance with FC 904.
2108.3 Fire extinguishing systems in lawfully existing dry cleaning facilities.
Type III dry cleaning facilities lawfully existing as of the effective date of this provision (FC 2108.3) shall be subject to the design and installation requirements set forth in FC 2108.3.1 through 2108.3.3, as applicable.
2108.3.1 Fully-sprinklered facilities.
A Type III dry cleaning facility protected throughout by a sprinkler system designed and installed in accordance with the Building Code shall maintain such existing fire protection system and is not subject to the dry cleaning system design requirements of FC 2108.3.3.
2108.3.2 Partially-sprinklered facilities.
A Type III dry cleaning facility in which the dry cleaning system is protected by one or more sprinkler heads shall maintain such existing fire protection system and is not subject to the dry cleaning system design requirements of FC 2108.3.3. Any Type III dry cleaning equipment newly-introduced after the effective date of this provision shall comply with the requirements of FC 2108.3.3(2). The aggregate quantity of Type III dry cleaning solvent stored, handled and used in the dry cleaning facility, including the solvent used in the dry cleaning system, shall not exceed 330 gallons (1249 L).
2108.3.3 Unprotected facilities.
A lawfully existing Type III dry cleaning facility that is not in compliance with FC 2108.3.1 or 2108.3.2 shall, upon alteration on or after the effective date of this provision (FC 2108.3), be subject to the following requirements:
1. Two or more sprinkler heads designed and installed in accordance with the Building Code shall protect the dry cleaning system; and
2. The dry cleaning system shall be designed and listed to accomplish one or more of the following criteria:
2.1. Prevent oxygen concentrations from reaching 8 percent or more by volume; and/or
2.2. Keep the temperature of the solvent at least 30°F (16.7°C) below the ash point; and/or
2.3. Maintain the solvent vapor concentration at a level lower than 25 percent of the lower explosive limit (LEL); and/or
2.4. Utilize equipment approved for use in Class I, Division 2 hazardous locations in accordance with the Electrical Code; and/or
2.5. Utilize an integrated dry chemical, clean agent or water mist automatic re-extinguishing system designed in accordance with FC Chapter 9*; and
* Editor's note: "FC" prefix added at the discretion of the editor.
3. The occupancy housing the dry cleaning establishment shall be in compliance with the Building Code and Mechanical Code. If not required and/or constructed with a 2-hour fire separation, the dry cleaning equipment shall be protected by a 1-hour fire rated enclosure provided with mechanical ventilation in accordance with the Mechanical Code.
4. The aggregate quantity of Type III-A dry cleaning solvent stored, handled and used in the dry cleaning facility, including the solvent used in the dry cleaning system, shall not exceed 330 gallons (1249 L).
5. The aggregate quantity of Type III-B dry cleaning solvent stored, handled and used in the dry cleaning facility, including the solvent used in the dry cleaning system, shall not exceed 660 gallons (2498 L).
2108.4 Portable fire extinguishers.
Portable fire extinguishers shall be provided and maintained in accordance with this section and FC 906. A minimum of two 2-A:10-B:C rated portable fire extinguishers shall be provided near the doors inside dry cleaning rooms containing Type II, Type III-A and Type III-B dry cleaning systems.
Section FC 2201. General
2201.1 Scope.
This chapter shall govern combustible dust-producing operations, and the equipment and processes utilized in connection with such operations in order to minimize and mitigate dust explosion hazards.
2201.2 Permits.
Permits shall be required as set forth in FC 105.6.
2201.3 General.
Combustible dust-producing operations, including manufacturing, processing and handling operations, shall be conducted in accordance with this chapter. All devices, equipment, systems and processes utilized in connection with such operations shall be designed, installed, operated and maintained in accordance with this chapter.
2201.3.1 Powder coating operations.
Powder coating shall additionally comply with the requirements of FC Chapter 24.
2201.3.2 Woodworking facilities.
Operations that produce deflagrable wood dust shall additionally comply with the requirements of FC Chapter 28.
2201.3.3 Special effect.
Special effects utilizing combustible dust shall additionally comply with the requirements of FC Chapter 56.
Section FC 2202. Definitions
2202.1 Definitions.
The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.
COMBUSTIBLE DUST.
DEFLAGRABLE WOOD DUST.
Section FC 2203. Precautions
2203.1 Sources of ignition.
It shall be unlawful to smoke, or use heating or other devices employing an open flame or spark-producing equipment, in areas where combustible dust is generated, processed or otherwise stored, handled or used.
2203.2 Housekeeping.
Accumulation of combustible dust shall be kept to a minimum indoors. Accumulated combustible dust shall be collected by vacuum cleaning or other means that will not place combustible dust into suspension in air. Forced air or similar methods shall not be used to remove dust from surfaces. When a normally inaccessible area such as a duct or cockloft is made accessible for purposes of an alteration, repair or other reason, any accumulation of combustible dust shall be removed from such area.
Section FC 2204. Additional Requirements
2204.1 Explosion protection standards.
An approved dust collection system shall be installed and/or other measures taken to collect and otherwise manage combustible dust generated by combustible dust-producing operations in order to prevent or mitigate combustible dust explosions. Facilities in which combustible dust-producing operations are to be conducted shall be designed, installed, operated and maintained in accordance with the industry or product-specific standards set forth in FC Table 2204.1.
FC Table 2204.1 Explosion Protection Standards
Standard Subject NFPA 61 Prevention of Fires and Dust Explosions in Agricultural and Food Processing Facilities NFPA 69 Explosion Prevention Systems NFPA 85 Boiler and Combustion Systems Hazards Code NFPA 120 Fire Prevention and Control in Coal Mines NFPA 484 Combustible Metals NFPA 652 Fundamentals of Combustible Dust NFPA 654 Prevention of Fires and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids NFPA 655 Prevention of Sulfur Fires and Explosions NFPA 664 Prevention of Fires and Explosions in Wood Processing and Woodworking Facilities Electrical Code Electrical Installations
2204.2 Dust hazard analysis.
A dust hazard analysis shall be conducted in accordance with NFPA 652 upon commencement of combustible dust-producing operations for any operation generating visible atmospheric dust and/or dust accumulations at locations other than the point of dust generation, to determine whether:
1. the equipment designed and installed to collect combustible dust and other mitigation measures is effective in achieving its design objectives and is preventing fugitive dust; or
2. the operation is generating an amount of combustible dust as to require the installation of combustible dust collection equipment and other mitigation measures.
Section FC 2301. General
2301.1 Scope.
This chapter shall govern the design, installation, operation and maintenance of fleet motor fuel-dispensing facilities, full-service motor fuel-dispensing facilities, self-service motor fuel-dispensing facilities, and repair garages.
2301.2 Permits.
Permits shall be required as set forth in FC 105.6.
2301.3 Design and installation documents.
Design and installation documents shall be submitted to the department for review and approval in accordance with FC 105.4 prior to the installation, alteration, repair or construction of fleet motor fuel-dispensing facilities, full-service motor fuel-dispensing facilities, self-service motor fuel-dispensing facilities, and repair garages for vehicles fueled by lighter-than-air motor fuels. Design and installation documents shall include the location of all storage tanks, dispensers, compressors, piping, fire protection systems and emergency shutdown devices.
2301.3.1 Compliance with other codes.
The installation or alteration of a liquid motor fuel storage and dispensing system regulated by this chapter shall not be approved by the department unless the design and installation documents demonstrate that the proposed work complies with the regulations of the United States Environmental Protection Agency, as set forth in 40 CFR Part 280, and the regulations of the New York State Department of Environmental Conservation, as set forth in 6 NYCRR Part 613 as applicable.
2301.4 General.
All fleet motor fuel-dispensing facilities, full-service motor fuel-dispensing facilities, self-service motor fuel-dispensing facilities and repair garages shall be designed, installed, operated and maintained in accordance with this chapter, FC Chapter 57 and the construction codes, including the Building Code, the Fuel Gas Code and the Mechanical Code, and, as applicable, NFPA 30A.
2301.5 Electrical.
Electrical wiring and equipment shall be suitable for the locations in which they are installed and shall comply with the requirements of FC 605, NFPA 30A and the Electrical Code, as applicable. Upon request, proof of compliance with the Electrical Code shall be filed with the department.
2301.6 Heat-producing appliances.
Heat-producing appliances shall be suitable for the locations in which they are installed and shall comply with the requirements of the construction codes, including the Building Code, the Mechanical Code and the Fuel Gas Code, and NFPA 2 and 30A, as applicable.
2301.7 Supervision of dispensing operations.
The dispensing of motor fuel at fleet motor fuel-dispensing facilities, full-service motor fuel-dispensing facilities and self-service motor fuel-dispensing facilities shall be conducted by or under the personal supervision of a certified attendant, who shall be responsible for ensuring that dispensing operations are conducted and the facility is maintained in accordance with this chapter and the rules.
2301.8 Supervision of defueling operations.
The defueling of liquid motor fuel from the fuel tank of a motor vehicle shall be conducted by or under the personal supervision of a person holding a certificate of fitness.
2301.9 Certificate of license.
Persons who install, alter, test or repair any automotive or marine liquid motor fuel storage and dispensing systems, including liquid motor fuel storage and dispensing systems at a bulk plant or terminal, shall hold a certificate of license or shall be employed by and perform such duties under the general supervision of a person holding such certificate.
2301.10 Records of inspections and testing.
Records of all inspections and testing required by this chapter shall be kept in a bound log book or other approved recordkeeping, maintained on the premises for a minimum of 4 years, except that records of the required 5 year tests as set forth in FC 2306.9.4, 2306.9.6 and 2308.7.4.1 shall be maintained on the premises for a minimum of 6 years.
2301.11 Prohibition.
It shall be unlawful to operate as a self-service motor fuel-dispensing facility any motor fuel-dispensing facility or a motor fuel dispenser installed and approved as a fleet or full-service motor fuel-dispensing facility or dispenser.
Section FC 2302. Definitions
2302.1 Definitions.
The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.
ALCOHOL-BLENDED MOTOR FUEL.
BIODIESEL.
CERTIFIED ATTENDANT.
CNG.
DISPENSING DEVICE, OVERHEAD TYPE.
FLAMMABLE LIQUID MOTOR FUEL.
FLEET MOTOR FUEL-DISPENSING FACILITY.
FULL-SERVICE MOTOR FUEL-DISPENSING FACILITY.
LIQUEFIED NATURAL GAS (LNG).
LIQUID MOTOR FUEL.
LIQUID MOTOR FUEL STORAGE AND DISPENSING SYSTEM.
MOTOR VEHICLE.
REPAIR GARAGE.
SELF-SERVICE MOTOR FUEL-DISPENSING FACILITY.
Section FC 2303. Location of Liquid Motor Fuel Dispensing Devices
2303.1 Location of dispensing devices.
Dispensing devices for liquid motor fuel storage and dispensing systems shall be located as set forth in FC 2303.1.1 and 2303.1.2.
2303.1.1 Outdoor dispensing devices.
When installed outdoors, dispensing devices shall be located as follows:
1. Ten feet (3048 mm) or more from lot lines and building or structure openings.
2. Ten feet (3048 mm) or more from buildings or structures having combustible exterior wall surfaces or buildings or structures having noncombustible exterior wall surfaces that are not part of a 1-hour fire-resistance-rated assembly or buildings or structures having combustible overhangs.
Exception: Canopies constructed in accordance with the construction codes, including the Building Code, providing weather protection for the motor fuel dispensers.
3. Such that all portions of the vehicle being fueled will be on the premises of the motor fuel-dispensing facility.
4. Such that the nozzle, when the hose is fully extended, will not reach within 5 feet (1524 mm) of building or structure openings.
5. Twenty feet (6096 mm) or more from fixed sources of ignition.
6. Twenty-five feet (7620 mm) or more from the nearest subway grating, entrance or exit.
2303.1.2 Indoor dispensing devices.
When installed indoors, the dispensing area shall be located at street level, with no dispenser located more than 50 feet (15 240 mm) from an exit or entrance to the building or structure used by motor vehicles.
Section FC 2304. Dispensing of Liquid Motor Fuel
2304.1 General.
The dispensing of liquid motor fuels at motor fuel-dispensing facilities, and the design, installation, operation and maintenance of liquid motor fuel storage and dispensing systems and facilities shall be in accordance with this section.
2304.1.1 Prohibition.
It shall be unlawful to dispense motor fuel into a vehicle while:
1. smoking;
2. using or maintaining an open flame;
3. the engine of the vehicle being fueled is not shut down;
4. using any object to override, bypass or otherwise render the fuel dispensing nozzle's manual hold-open design feature inoperable.
2304.1.2 Emergency fuel shutoff.
An approved, clearly identified and readily accessible emergency fuel shutoff switch shall be provided at an approved location to immediately shut down the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency and activate an alarm audible in the dispensing area and any control booth. Such audible device may be the same device used to indicate activation of the fire extinguishing system installed to protect the fuel dispensers. An emergency fuel shutoff switch for outdoor fuel dispensers shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For indoor fuel dispensers, the emergency fuel shutoff switch shall be installed at an approved location. An approved sign shall be posted on or immediately adjacent to the emergency fuel shutoff switch, which reads: EMERGENCY FUEL SHUTOFF. Such emergency fuel shutoff switches shall be of a type that must be reset manually.
2304.1.3 Lighting.
Dispensing areas shall be well lighted whenever dispensing is being conducted.
2304.1.4 Dispensing area signage.
Durable signs shall be conspicuously posted in dispensing areas in motor fuel-dispensing facilities in compliance with the requirements of FC 2304.1.4.1 through 2304.1.4.4.
2304.1.4.1 Operating instructions.
A sign setting forth dispenser operating instructions shall be posted on every dispenser. Such sign shall also indicate the location of the emergency fuel shutoff switches required by FC 2304.1.2.
2304.1.4.2 Fuel dispensing warning sign.
A warning sign that reads as follows shall be posted on or immediately adjacent to each dispenser:
1. No smoking.
2. Shut off engine.
3. Before fueling, discharge any static electricity by touching a metal surface. Repeat before removing nozzle.
4. If a fire starts, do not remove nozzle leave the area immediately.
5. It is unlawful and dangerous to dispense fuel into unapproved containers or to fill portable containers in or on a motor vehicle.
6. It is unlawful for anyone other than the certified attendant to fill portable containers.
2304.1.4.3 Alcohol-blended motor fuel notice.
A sign or marking indicating the type and concentration of alcohol in the motor fuel being dispensed shall be posted on or affixed to each dispenser dispensing alcohol-blended motor fuel.
2304.1.4.4 Emergency procedures.
A sign setting forth emergency procedures that reads as follows shall be posted in the dispensing area, or other location designated in this section:
IN CASE OF FIRE OR SPILL: USE THE EMERGENCY FUEL SHUTOFF SWITCH TO STOP THE FLOW OF FUEL (for flammable fuel dispensers ) ACTIVATE THE FIRE EXTINGUISHING SYSTEM PROTECTING THE DISPENSING AREA. (SWITCH LOCATION): ( indicate location ) DIRECT VEHICLE OCCUPANTS TO EXIT VEHICLES AND LEAVE AREA IMMEDIATELY NOTIFY THE FIRE DEPARTMENT (CALL 911) (FACILITY ADDRESS) ( indicate address, with cross-street reference ). KEEP ALL PERSONS AWAY FROM THE AREA.
2304.1.5 Emergency telephone.
A telephone not requiring a coin to operate or another approved, clearly identified means to notify the department, shall be provided at the facility in an approved location.
2304.1.6 Dispensing on piers, docks or wharves.
Flammable liquid motor fuel shall not be dispensed into the fuel tanks of motor vehicles imported by ship to this country while on any pier, dock or wharf.
2304.1.7 Dispensing into portable containers.
The dispensing of liquid motor fuel into portable containers shall comply with the requirements of FC 2304.1.7.1 through 2304.1.7.5.
2304.1.7.1 Approved containers required.
Liquid motor fuel shall not be dispensed into a portable container unless such container is of approved material and construction, and has a tight closure with screwed or spring-loaded cover so designed that the contents can be dispensed without spilling. Liquids shall not be dispensed into portable tanks or cargo tanks.
2304.1.7.2 Container capacity.
Liquid motor fuel shall be dispensed into approved containers with an individual capacity not greater than 2 1/2 gallons (9.5 L).
2304.1.7.3 Nozzle operation.
When liquid motor fuel is being dispensed into a portable container the fuel dispensing nozzle shall be manually held open during the dispensing operation, whether or not the nozzle is provided with a latch-open device.
2304.1.7.4 Location of containers being filled.
Portable containers shall not be filled while located inside the trunk, passenger compartment or truck bed of a motor vehicle or upon a marine vessel or watercraft.
2304.1.7.5 Certified attendant.
Only a certified attendant shall dispense liquid motor fuel into portable containers.
2304.1.8 Dispensing from portable containers.
No motor vehicle, motorcycle, marine vessel or watercraft shall be fueled from a portable container while indoors.
2304.1.9 Vegetation.
Weeds, grass, vines, brush or other vegetation shall not be maintained within 10 feet (3048 mm) of any aboveground tank, tank fill connection or dispensing area.
2304.1.10 Combustible waste.
Rubbish and other combustible waste shall not be stored within 10 feet (3048 mm) of any aboveground tank, tank fill connection or dispensing area, except in the dispensing area when in an approved waste container with a capacity not exceeding 40 gallons (0.15 m 3 ).
2304.2 Self-service motor fuel-dispensing facilities.
Self-service motor fuel-dispensing facilities shall be designed, installed, operated and maintained in compliance with the requirements of FC 2304.2.1 through 2304.2.5.
2304.2.1 Duties of certified attendant.
The certified attendant's primary function shall be to supervise, observe and monitor the dispensing of fuel. The certified attendant shall prevent the dispensing of fuel into portable containers unless the dispensing is in compliance with the requirements of FC 2304.1.7. The certified attendant shall control sources of ignition, take immediate action upon an accidental spill or release, be ready to use a portable fire extinguisher, and activate the fixed fire extinguishing system. Nothing in this section shall be construed to prohibit a certified attendant from engaging in other activities so long as such activities do not interfere with the certified attendant's ability to supervise, observe and monitor the dispensing of fuel and other requirements of this chapter.
2304.2.2 Self-service dispensers.
Approved self-service devices, equipment and systems such as, but not limited to, card-operated and remote-preset types, are allowed at liquid motor fuel-dispensing facilities. The certified attendant shall set the dispensing devices in the "off" position when not in use if such dispensing device can be activated without the certified attendant's knowledge.
2304.2.3 Monitoring of dispensing.
A control booth shall be located on the premises of every self-service automotive liquid motor fuel-dispensing facility. The control booth shall be an interior or exterior enclosure to which the public has no access. The certified attendant shall be present within the control booth while dispensing operations are conducted. The control booth shall be designed and located so that the certified attendant stationed therein shall have a full, unobstructed clear view of dispensing operations, except that mirrors and/or an approved closed-circuit television installation may be provided to afford the certified attendant a clear view of dispensing operations when the view from the control booth is partially or temporarily obstructed. For purposes of this section, the "clear" view provided by a closed-circuit television installation shall mean that the image on the monitor shall be of such brightness and resolution as to allow ready identification of individuals and easy observation of activities at all times of day. Two properly labeled manual switches, one that activates the fire extinguishing system, and one that electrically disconnects the liquid motor fuel-dispensing pumps, shall be located adjacent to each other within the control booth. A console that controls the self-service liquid motor fuel dispensers shall be provided within the control booth and within 5 feet (1524 mm) of the manual switches.
2304.2.4 Communications.
A two-way voice communication system shall be installed to provide contact between the control booth and each dispensing island.
2304.2.5 Signage.
The signage required by FC 2304.1.4 shall be posted in the dispensing area of a self-service motor fuel-dispensing facility, except that the emergency procedures sign required by FC 2304.1.4.4 shall be posted in the control booth.
2304.3 Fleet motor fuel-dispensing facilities.
Fleet motor fuel-dispensing facilities shall be designed, installed, operated and maintained in compliance with the requirements of FC 2304.3.1 through 2304.3.3.
2304.3.1 Inspection of dispensing area.
The certified attendant responsible for supervision of the dispensing of liquid motor fuel at fleet motor fuel-dispensing facility shall inspect the dispensing area on a periodic basis in accordance with the rules to ensure that the facility is being maintained in accordance with this chapter and the rules. The certified attendant shall notify the owner and make any other notifications required by this code if there is any evidence that the facility is not in good working order. A record of such inspections and notifications shall be maintained at the premises in accordance with FC 107.7.
2304.3.2 Duties of fleet personnel.
Employees or other persons working for the owner of a fleet motor fuel-dispensing facility whose duties involve the dispensing of motor fuel shall be trained and knowledgeable in such dispensing in compliance with the requirements of this code and the rules.
2304.3.3 Quantity limits.
Dispensing equipment used at fleet automotive liquid motor fuel-dispensing facilities shall comply with one of the following:
1. Dispensing devices shall be programmed or set to limit uninterrupted liquid motor fuel delivery to not more than 25 gallons (95 L) and require a manual action to resume delivery.
2. For other than flammable liquid motor fuel, the amount of liquid motor fuel being dispensed shall be limited in quantity by a preprogrammed card as approved.
2304.4 Full-service motor fuel-dispensing facilities.
Full-service motor fuel-dispensing facilities shall be operated in compliance with the requirements of FC 2304.4.1.
2304.4.1 Duties of certified attendant.
The certified attendant at a full-service motor fuel-dispensing facility shall personally supervise the dispensing of motor fuel into vehicles by facility personnel. The certified attendant shall conduct a visual inspection of the dispensing area on a daily basis to monitor the condition of such installation. The certificate of fitness holder shall notify the owner and make any other notifications required by this code if there is any evidence that the installation is not in good working order. A record of such inspections and notifications shall be maintained at the premises in accordance with FC 107.7.
Section FC 2305. Operation and Maintenance of Liquid Motor Fuel-Dispensing Facilities
2305.1 Tank filling operations for liquid motor fuel.
Delivery operations to tanks for liquid motor fuel shall comply with the requirements of FC 2305.1.1 through 2305.1.3 and the applicable requirements of FC Chapter 57.
2305.1.1 Delivery vehicle location.
Where liquid delivery to a motor fuel storage tank is accomplished by positive-pressure operation, cargo tanks making delivery shall be positioned a minimum of 25 feet (7620 mm) from tanks receiving flammable liquids and 15 feet (4572 mm) from tanks receiving combustible liquids. During delivery, a cargo tank shall not obstruct a public street, private road, block motorists' view of roadways or impede the movement of vehicles or pedestrians.
2305.1.2 Tank capacity calculation.
The driver, operator or attendant of a cargo tank shall, before making delivery to a tank, determine the unfilled, available capacity of such tank by an approved tank level-indicating device or method. A measuring stick shall not be used to measure the contents of the tank through the fill connection line, except where there is a direct fill connection.
2305.1.3 Tank connections.
Delivery of liquid motor fuel shall be made by means of approved liquid- and vapor-tight connections between the delivery hose and tank fill pipe. Where tanks are equipped with any type of vapor recovery system, all connections required for the safe and proper functioning of the particular vapor recovery process shall be made. Such connections shall be made liquid- and vapor-tight and remain connected throughout the delivery process. Vapors shall not be discharged at grade level during delivery.
2305.2 Equipment maintenance.
Liquid motor storage and dispensing systems shall be maintained in good working order at all times in accordance with FC 2305.2.1 through 2305.2.3.
2305.2.1 Dispensing devices.
Where maintenance to dispensing devices becomes necessary and such maintenance could allow the accidental release or ignition of liquid, the following precautions shall be taken:
1. Only persons with a certificate of license and knowledgeable in performing the required maintenance shall perform the work.
2. Electrical power to the dispensing device and pump serving the dispenser shall be shut off at the main electrical disconnect panel before maintenance begins.
3. The emergency dispenser shutoff valve shall be closed before maintenance begins.
4. Vehicular traffic and unauthorized persons shall be prevented from coming within 12 feet (3658 mm) of the dispensing device before and during maintenance.
2305.2.2 Dispenser emergency shutoff valves.
Dispenser emergency shutoff valves required by FC 2306.7.4 shall be checked not less than once per year by manually tripping the hold-open linkage.
2305.2.3 Leak detection system.
The leak detection system required by FC 2306.7.7 shall be inspected monthly for proper operation and tested at least annually in accordance with the manufacturer's specifications to ensure that it is in good working order.
2305.3 Use of alcohol-blended motor fuel in existing liquid motor fuel storage and dispensing systems.
Department approval shall be obtained prior to using a liquid motor fuel storage and dispensing system for alcohol-blended motor fuel when such system has previously been used to store and dispense another type of motor fuel. If approved, such system may be used alternatively for the various approved fuel types.
2305.4 Signage.
Durable signs shall be conspicuously posted at motor fuel-dispensing facilities in accordance with this section.
2305.4.1 Tank overfill warning sign.
A warning sign shall be posted on or immediately adjacent to tank overfill alarm panel that reads: "CAUTION: WHEN ALARM ACTIVATES, TANK IS FILLED TO CAPACITY. DO NOT OVERFILL."
2305.5 Portable fire extinguishers.
Approved portable fire extinguishers complying with the requirements of FC 906 with a minimum rating of 40-B:C shall be provided and located such that an extinguisher is not less than 20 feet (6096 mm) but not more than 75 feet (22 860 mm) from pumps, dispensers or storage tank fill connections.