NYC Administrative Code Title 29, Chapter 2 New York City Fire Code, part 8 of 15

Section FC 2701 to Section FC 3503: 75 sections.

Section FC 2701. General

Open this section

2701.1 Scope.

This chapter shall govern the design, installation, operation and maintenance of semiconductor fabrication facilities and comparable research and development facilities classified as Group H-5 occupancies, and the storage, handling and use of hazardous materials therein.

2701.2 Application.

The requirements set forth in this chapter are requirements specific only to Group H-5 and shall be applied as exceptions or additions to applicable requirements set forth elsewhere in this code.

2701.3 Multiple hazards.

Where a material poses multiple hazards, all hazards shall be addressed in accordance with FC 5001.1.

2701.4 General.

Semiconductor fabrication facilities and comparable research and development facilities classified as Group H-5 occupancies shall be designed, installed, operated and maintained in accordance with this chapter . Such facilities and hazardous materials shall additionally comply with the requirements of the construction codes, including the Building Code.

2701.5 Permits.

Permits shall be required as set forth in FC 105.6.

Section FC 2702. Definitions

Open this section

2702.1 Definitions.

The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.

CONTINUOUS GAS DETECTION SYSTEM.

EMERGENCY CONTROL STATION.

FABRICATION AREA.

HAZARDOUS PRODUCTION MATERIAL (HPM).

HPM FLAMMABLE LIQUID.

HPM ROOM.

PASS-THROUGH.

SEMICONDUCTOR FABRICATION FACILITY.

SERVICE CORRIDOR.

TOOL.

WORKSTATION.

Section FC 2703. General Safety Provisions

Open this section

2703.1 Emergency control station.

An emergency control station shall be maintained in accordance with FC 2703.1.1 through 2703.1.3.

2703.1.1 Location.

The emergency control station shall be located on the premises at an approved location outside of the fabrication area.

2703.1.2 Staffing.

Trained personnel shall continuously staff the emergency control station.

2703.1.3 Signals.

The emergency control station shall monitor signals from emergency equipment and alarm and detection systems, including the following systems, whether required by this code or the construction codes or voluntarily installed:

1. Sprinkler system alarm and monitoring systems.

2. Manual fire alarm systems.

3. Emergency alarm systems.

4. Continuous-gas detection systems.

5. Smoke detection systems.

6. Emergency power systems.

7. Automatic detection and alarm systems for pyrophoric liquids and Class 3 water-reactive liquids required by FC 2705.2.3.4.

8. Exhaust ventilation flow alarm devices for pyrophoric liquids and Class 3 water-reactive liquids cabinet exhaust ventilation systems required by FC 2705.2.3.4.

2703.2 Devices, equipment and systems.

Devices, equipment and systems including, containers, piping, tubing, valves and fittings shall comply with the requirements of this section, FC 5003.2, and other applicable provisions of this code, and the construction codes, including the Building Code and the Mechanical Code.

2703.2.1 Additional regulations for HPM supply piping and tubing.

The requirements set forth in FC 5003.2.2.2 shall apply to supply piping and tubing for HPM gases and liquids. Supply piping and tubing for HPM gases and liquids having a health-hazard ranking of 3 or 4 shall be welded throughout, except for connections located within a ventilated enclosure if the material is a gas, or an approved method of drainage or containment is provided for connections if the material is a liquid.

2703.3 Design and installation requirements.

Semiconductor fabrication facilities shall be designed and installed in accordance with FC 2703.3.1 through 2703.3.9.

2703.3.1 Fabrication areas.

Design, installation and location of fabrication areas shall comply with the requirements of the construction codes, including the Building Code.

2703.3.2 Pass-throughs in exit access corridors.

Pass-throughs in exit access corridors shall be constructed in accordance with the construction codes, including the Building Code.

2703.3.3 Liquid storage rooms.

Liquid storage rooms shall comply with the requirements of FC Chapter 57 and the construction codes, including the Building Code.

2703.3.4 HPM rooms.

HPM rooms shall comply with the requirements of the construction codes, including the Building Code.

2703.3.5 Gas cabinets.

Gas cabinets shall comply with the requirements of FC 5003.8.6.

2703.3.6 Exhausted enclosures.

Exhausted enclosures shall comply with the requirements of FC 5003.8.5.

2703.3.7 Gas rooms.

Gas rooms shall comply with the requirements of FC 5003.8.4.

2703.3.8 Service corridors.

Service corridors shall comply with the requirements of FC 2705.3.3 and the Building Code.

2703.3.9 Cabinets containing pyrophoric liquids or water-reactive Class 3 liquids.

Cabinets in fabrication areas containing pyrophoric liquids or Class 3 water-reactive liquids in containers or in amounts greater than 1/2 gallon (2 L) shall comply with FC 2705.2.3.4.

2703.4 Emergency plan.

An emergency preparedness plan shall be prepared in accordance with FC Chapter 4.

2703.5 Maintenance of devices, equipment, systems and processes.

Maintenance of devices, equipment, systems and processes shall comply with the requirements of FC 5003.2.6.

2703.6 Reserved.

2703.7 Electrical wiring and equipment.

Electrical wiring and equipment in HPM facilities shall comply with the requirements of FC 2703.7.1 through 2703.7.3.

2703.7.1 Fabrication areas.

Electrical wiring and equipment in fabrication areas shall comply with the requirements of the Building Code and Electrical Code.

2703.7.2 Workstations.

Electrical equipment and devices within 5 feet (1524 mm) of workstations in which flammable or pyrophoric gases or flammable liquids are used shall comply with the requirements of the Electrical Code for Class I, Division 2 hazardous locations. Workstations shall not be energized without adequate exhaust ventilation in accordance with FC 2703.14.

Exception: Class I, Division 2 hazardous electrical equipment is not required when the air removal from the workstation or dilution will prevent the accumulation of flammable vapors and fumes on a continuous basis.

2703.7.3 Hazardous production material (HPM) rooms, gas rooms and liquid storage rooms.

Electrical wiring and equipment in HPM rooms, gas rooms and liquid storage rooms shall comply with the requirements of the Electrical Code.

2703.8 Reserved.

2703.9 Reserved.

2703.10 Sprinkler system.

A sprinkler system shall be provided in accordance with FC 2703.10.1 through 2703.10.5, FC Chapter 9 and the Building Code.

2703.10.1 Workstations and tools.

The design of the sprinkler system in the area shall take into consideration the spray pattern and the effect on the equipment.

2703.10.1.1 Combustible workstations.

A sprinkler head shall be installed within each branch exhaust connection or individual plenums of workstations of combustible construction. The sprinkler head in the exhaust connection or plenum shall be located not more than 2 feet (610 mm) from the point of the duct connection or the connection to the plenum. When necessary to prevent corrosion, the sprinkler head and connecting piping in the duct shall be coated with approved or listed corrosion-resistant materials. The sprinkler head shall be accessible for periodic inspection in accordance with FC Chapter 9.

Exceptions:

1. Alternative fire extinguishing systems shall be allowed where approved. Activation of such systems shall deactivate the related processing equipment.

2. Process equipment that operates at temperatures exceeding 932°F (500°C) and has automatic shutdown capabilities that will interrupt HPM flow for hazardous materials.

3. Exhaust ducts 10 inches (254 mm) or less in diameter from flammable gas storage cabinets that are part of a workstation.

4. Ducts listed or approved for use without internal sprinkler protection.

2703.10.1.2 Combustible tools.

Where the horizontal surface of a combustible tool is obstructed from ceiling sprinkler discharge, sprinkler protection that covers the horizontal surface of the tool shall be provided.

Exceptions:

1. A gaseous fire extinguishing local surface application system shall be allowed as an alternative to sprinklers when approved. Gaseous fire extinguishing systems shall be actuated by infrared (IR) or ultraviolet/infrared (UVIR) optical detectors.

2. Tools constructed of materials that are listed as Class 1 or Class 2 in accordance with UL 2360 or approved for use without internal fire extinguishing system protection.

2703.10.2 Gas cabinets and exhausted enclosures.

A sprinkler system shall be provided in gas cabinets and exhausted enclosures containing HPM compressed gases.

Exception: Gas cabinets located in a HPM room other than those cabinets containing pyrophoric gases.

2703.10.3 Pass-throughs in exit access corridors.

Pass-throughs in exit access corridors shall be protected throughout by a sprinkler system.

2703.10.4 Exhaust ducts for HPM.

A sprinkler system shall be provided in exhaust ducts conveying gases, vapors, fumes, mists or dusts generated from HPM in accordance with this section and the Mechanical Code and the Building Code.

2703.10.4.1 Metallic and noncombustible nonmetallic exhaust ducts.

A sprinkler system shall be provided in metallic and noncombustible nonmetallic exhaust ducts when the following conditions apply:

1. The largest cross-sectional diameter is equal to or greater than 10 inches (254 mm).

2. The ducts are within the building.

3. The ducts are conveying flammable gases, vapors or fumes.

2703.10.4.2 Combustible nonmetallic exhaust ducts.

A sprinkler system shall be provided in combustible nonmetallic exhaust ducts when the largest cross-sectional diameter of the duct is equal to or greater than 10 inches (254 mm).

Exceptions:

1. Ducts listed or approved for applications without sprinkler system protection.

2. Ducts not more than 12 feet (3658 mm) in length installed below ceiling level.

2703.10.4.3 Exhaust connections and plenums of combustible workstations.

Fire extinguishing system protection for exhaust connections and plenums of combustible workstations shall comply with the requirements of FC 2703.10.1.1.

2703.10.4.4 Exhaust duct sprinkler system requirements.

Sprinkler systems installed in exhaust duct systems shall be hydraulically designed to provide 1/2 gallon per minute (gpm) (1.9 L/min) over an area derived by multiplying the distance between the sprinklers in a horizontal duct by the width of the duct. Minimum discharge shall be 20 gpm (76 L/min) per sprinkler from the five hydraulically most remote sprinklers.

2703.10.4.4.1 Sprinkler head locations.

Sprinkler heads shall be installed at 12-foot (3658 mm) intervals in horizontal ducts and at changes in direction. In vertical runs, sprinkler heads shall be installed at the top and at alternate floor levels.

2703.10.4.4.2 Control valve.

A separate indicating control valve shall be provided for sprinkler heads installed in exhaust ducts.

2703.10.4.4.3 Drainage.

Drainage shall be provided to remove sprinkler water discharged in exhaust ducts.

2703.10.4.4.4 Corrosive atmospheres.

Where corrosive atmospheres exist, exhaust duct sprinkler heads and pipe fittings shall be manufactured of corrosion-resistant materials or coated with approved materials.

2703.10.4.4.5 Maintenance and inspection.

Sprinkler heads in exhaust ducts shall be accessible for inspection and maintenance and shall be inspected and maintained on not less than an annual basis.

2703.10.5 Sprinkler alarms and supervision.

Sprinkler systems shall be electrically supervised and provided with alarms in accordance with the construction codes, including the Building Code. Sprinkler system alarm and supervisory signals shall be transmitted to the emergency control station.

2703.11 Manual fire alarm system.

A manual fire alarm system shall be installed throughout buildings containing a Group H-5 occupancy. Activation of the alarm system shall initiate a local alarm and transmit a signal to the emergency control station. Manual fire alarm systems shall be designed and installed in accordance with the construction codes, including the Building Code.

2703.12 Emergency alarm system.

Emergency alarm systems shall be provided in accordance with this section, FC 5004.9 and FC 5005.4.4. The maximum allowable quantity per control area provisions of FC 5004.1 shall not apply to emergency alarm systems required for HPM.

2703.12.1 Where required.

Emergency alarm systems shall be provided in the areas indicated in FC 2703.12.1.1 through 2703.12.1.3.

2703.12.1.1 Service corridors.

An approved emergency alarm system shall be provided in service corridors, with at least one alarm device in the service corridor.

2703.12.1.2 Exit access corridors and exit enclosures.

Emergency alarms for exit access corridors and exit enclosures shall comply with the requirements of FC 5005.4.4.

2703.12.1.3 Liquid storage rooms, HPM rooms and gas rooms.

Emergency alarms for liquid storage rooms, HPM rooms and gas rooms shall comply with the requirements of FC 5004.9.

2703.12.2 Alarm-initiating devices.

An approved emergency telephone system, local alarm manual pull stations, or other approved alarm-initiating devices are allowed to be used as emergency alarm-initiating devices.

2703.12.3 Alarm signals.

Activation of the emergency alarm system shall sound a local alarm and transmit a signal to the emergency control station.

2703.13 Continuous gas detection systems.

A continuous gas detection system shall be provided for HPM gases when the physiological warning properties of the gas are at a higher level than the accepted permissible exposure limit (PEL) for the gas and for flammable gases in accordance with the construction codes, including the Building Code.

2703.14 Exhaust ventilation systems for HPM.

Exhaust ventilation systems and materials for exhaust ducts utilized for the exhaust of HPM shall comply with the requirements of this section, other applicable provisions of this code, the construction codes, including the Building Code and the Mechanical Code.

2703.14.1 Where required.

Exhaust ventilation systems shall be provided in the following locations in accordance with this section and the construction codes, including the Building Code:

1. Fabrication areas: Exhaust ventilation for fabrication areas shall comply with the requirements of the construction codes, including the Building Code. Additional manual control switches shall be provided as may be required by the commissioner.

2. Workstations: A ventilation system shall be provided to capture and exhaust fumes and vapors at workstations.

3. Liquid storage rooms: Exhaust ventilation for liquid storage rooms shall comply with the requirements of FC 5004.3.1 and the construction codes, including the Building Code and Mechanical Code.

4. HPM rooms: Exhaust ventilation for HPM rooms shall comply with the requirements of FC 5004.3.1 and the construction codes, including the Building Code and the Mechanical Code.

5. Gas cabinets: Exhaust ventilation for gas cabinets shall comply with the requirements of FC 5003.8.6.2. The gas cabinet ventilation system is allowed to connect to a workstation ventilation system. Exhaust ventilation for gas cabinets containing highly toxic or toxic gases shall additionally comply with the requirements of FC Chapter 60.

6. Exhausted enclosures: Exhaust ventilation for exhausted enclosures shall comply with the requirements of FC 5003.8.5.2. Exhaust ventilation for exhausted enclosures containing highly toxic or toxic gases shall additionally comply with the requirements of FC Chapter 60.

7. Gas rooms: Exhaust ventilation for gas rooms shall comply with the requirements of FC 5003.8.4.2. Exhaust ventilation for gas rooms containing highly toxic or toxic gases shall additionally comply with the requirements of FC Chapter 60.

8. Cabinets containing pyrophoric liquids or Class 3 water-reactive liquids: Exhaust ventilation for cabinets in fabrication areas containing pyrophoric liquids or Class 3 water-reactive liquids shall be as required in FC 2705.2.3.4.

2703.14.2 Penetrations.

Exhaust ducts penetrating fire barrier assemblies shall be contained in a shaft of equivalent fire-resistance-rated construction. Exhaust ducts shall not penetrate fire walls. Fire dampers shall not be installed in exhaust ducts.

2703.14.3 Treatment systems.

Treatment systems for highly toxic and toxic gases shall comply with the requirements of FC Chapter 60.

2703.15 Emergency power system.

An emergency power system shall be provided in Group H-5 occupancies where required by the construction codes, including the Building Code. The emergency power system shall be designed to supply power automatically to required electrical systems when the normal supply system is interrupted.

2703.15.1 Required electrical systems.

Emergency power shall be provided for electrically operated equipment and connected control circuits as required by Chapter 4 of the Building Code or this code.

2703.16 Sub-atmospheric pressure gas systems.

Sub-atmospheric pressure gas systems (SAGS) shall be designed, installed, operated and maintained in accordance with NFPA 318.

Section FC 2704. Storage

Open this section

2704.1 General.

Hazardous materials shall be stored in semiconductor fabrication facilities in accordance with this section and the provisions of other applicable chapters of this code.

2704.2 Fabrication areas.

Hazardous materials shall be stored in accordance with FC 2704.2.1 through 2704.2.2.1.

2704.2.1 Location of HPM storage in fabrication areas.

Storage of HPM in fabrication areas shall be within approved or listed storage cabinets, gas cabinets or within a workstation as follows:

1. Flammable and combustible liquid storage cabinets shall comply with the requirements of FC Chapter 57.

2. Hazardous materials storage cabinets shall comply with the requirements of FC 5003.8.7.

3. Gas cabinets shall comply with the requirements of FC 5003.8.6. Gas cabinets for highly toxic or toxic gases shall additionally comply with the requirements of FC 6004.1.2.

4. Exhausted enclosures shall comply with FC 5003.8.5. Exhausted enclosures for highly toxic or toxic gases shall also comply with FC 6004.1.3.

5. Workstations shall comply with the requirements of FC 2705.2.3.

2704.2.2 Maximum aggregate quantities in fabrication areas.

The aggregate quantities of hazardous materials stored, handled and used in a single fabrication area shall be limited as specified in this section.

Exception: Fabrication areas containing quantities of hazardous materials not exceeding the maximum allowable quantities per control area established by FC 5003.1.1, 5704.3.4 and 5704.3.5.

FC Table 2704.2.2.1 Quantity Limits for Hazardous Materials in a Single Fabrication Area in Group H-5 a

Hazard Category Solids (pounds / square foot) Liquids (gallons / square foot) Gas (SCF / square foot) Physical-Hazard Materials Combustible dust Note b Not Applicable Not Applicable Combustible fiber Loose Baled Note b Notes b, c Not Applicable Not Applicable Combustible liquid Class II Class IIIA Class IIIB Combination Class I, II and IIIA Not Applicable 0.01 0.02 Not Limited 0.04 Not Applicable Cryogenic gas Flammable Oxidizing Not Applicable Not Applicable Note d 1.25 Explosives Note b Note b Note b Flammable gas Gaseous Liquefied Not Applicable Not Applicable Note d Note d Flammable liquid Class IA Class IB Class IC Combination Class IA, IB and IC Combination Class I, II and IIIA Not Applicable 0.0025 0.025 0.025 0.025 0.04 Not Applicable Flammable solid 0.001 Not Applicable Not Applicable Organic peroxide Unclassified detonable Class I Class II Class III Class IV Class V Note b Note b 0.025 0.1 Not Limited Not Limited Not Applicable Not Applicable Oxidizing gas Gaseous Liquefied Combination of Gaseous and Liquefied Not Applicable Not Applicable 1.25 1.25 1.25 Oxidizer Class 4 Class 3 Class 2 Class 1 Combination oxidizer Class 1, 2, 3 Note b 0.003 0.003 0.003 0.003 Note b 0.03 0.03 0.03 0.03 Not Applicable Pyrophoric Note b 0.00125 Notes d and e Unstable reactive Class 4 Class 3 Class 2 Class 1 Note b 0.025 0.1 Not Limited Note b 0.0025 0.01 Not Limited Note b Note b Note b Not Limited Water reactive Class 3 Class 2 Class 1 Note b 0.25 Not Limited 0.00125 0.025 Not Limited Not Applicable Health-Hazard Materials Corrosives Not Limited Not Limited Not Limited Highly toxics Not Limited Not Limited Note d Toxics Not Limited Not Limited Note d

For SI: 1 pound per square foot = 4.882 kg/m 2 , 1 gallon per square foot = 0.025 L/m 2 , 1 cubic foot = 0.02832 m 3 .

a. Hazardous materials within piping shall not be included in the calculated quantities.

b. Quantity of hazardous materials in a single fabrication area shall not exceed the maximum allowable quantities per control area in FC Tables 5003.1.1(1) and 5003.1.1(2).

c. Densely packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class.

d. The aggregate quantity of flammable, pyrophoric, toxic and highly toxic gases shall not exceed 9,000 SCF.

e. The aggregate quantity of pyrophoric gases in the building shall not exceed the amounts set forth in FC Table 5003.8.2.

2704.2.2.1 Storage and use in fabrication areas.

The maximum quantities of hazardous materials stored in a single fabrication area shall not exceed the quantities set forth in FC Table 2704.2.2.1.

2704.3 Indoor storage outside of fabrication areas.

The indoor storage of hazardous materials outside of fabrication areas shall be in accordance with FC 2704.3.1 through 2704.3.3.

2704.3.1 HPM storage.

The indoor storage of HPM in quantities greater than those listed in FC 5003.1.1 and 5704.3.4 shall be in a room complying with the requirements of the construction codes, including the Building Code, and this code for a liquid storage room, HPM room or gas room as appropriate for the materials stored.

2704.3.2 Other hazardous materials storage.

The indoor storage of other hazardous materials shall comply with the requirements of FC 5001, 5003 and 5004 and other applicable provisions of this code.

2704.3.3 Separation of incompatible hazardous materials.

Incompatible hazardous materials in storage shall be separated from each other in accordance with FC 5003.9.8.

2704.4 Exit access corridors and exit enclosures.

Hazardous materials shall not be stored in exit access corridors or exit access enclosures.

Section FC 2705. Handling and Use

Open this section

2705.1 General.

Hazardous materials shall be handled and used in accordance with this section, FC 2703 and other applicable provisions of this code.

2705.2 Fabrication areas.

The use of hazardous materials in fabrication areas shall be in accordance with FC 2705.2.1 through 2705.2.3.4.

2705.2.1 Location of HPM in use in fabrication areas.

Hazardous production materials in use in fabrication areas shall be within approved or listed gas cabinets, exhausted enclosures or within a workstation, in accordance with FC Chapter 50.

2705.2.2 Maximum aggregate quantities in fabrication areas.

The aggregate quantities of hazardous materials in a single fabrication area shall comply with the requirements of FC 2704.2.2, and FC Table 2704.2.2.1. The quantity of HPM in use at a workstation shall not exceed the quantities listed in FC Table 2705.2.2.

FC Table 2705.2.2 Maximum Quantities of Hpm at a Workstation d

HPM Classification State Maximum Quantity Flammable, highly toxic, pyrophoric and toxic combined Gas Combined aggregate volume of all containers at a workstation shall not exceed an internal container volume of 39.6 gallons or 5.29 cubic feet Flammable Liquid 15 gallons a, b Solid 5 pounds a, b Corrosive Gas Combined aggregate volume of all containers at a workstation shall not exceed an internal container volume of 39.6 gallons or 5.29 cubic feet Liquid Use - Open System: 25 gallons b Use - Closed System: 150 gallons b, e Solid 20 pounds a, b Highly toxic Liquid 15 gallons a Solid 5 pounds a Oxidizer Gas Combined aggregate volume of all containers at a workstation shall not exceed an internal container volume of 39.6 gallons or 5.29 cubic feet Liquid Use - open system: 12 gallons b Use - closed system: 60 gallons b Solid 20 pounds a, b Pyrophoric Liquid 1/2 gallon c, f Solid See FC Table 2704.2.2.1 Toxic Liquid Use - open system: 15 gallons b Use - closed system: 60 gallons b Solid 5 pounds a, b Unstable reactive Class 3 Liquid 1/2 gallon a, b Solid 5 pounds a, b Water-reactive Class 3 Liquid 1/2 gallon c, f Solid See FC Table 2704.2.2.1

For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L.

a. Maximum allowable quantities may be increased 100 percent for closed systems operations. When Note b applies, the quantities increased may be as set forth in both notes.

b. Quantities may be increased 100 percent when workstations are internally protected throughout by a fire extinguishing system complying with the requirements of FC Chapter 9. When Note a applies, the quantities increased may be as set forth in both notes. When Note e applies, the maximum increase authorized by both Notes b and e shall not exceed 100 percent.

c. Allowed only in workstations that are internally protected throughout by a fire extinguishing system compatible with the reactivity of materials in use at the workstation.

d. The quantity limits apply only to materials classified as HPM.

e. Quantities may be increased 100 percent for nonflammable, noncombustible corrosive liquids when the materials of construction for workstations are listed or approved for use without internal fire extinguishing system protection. When Note b applies, the maximum increase authorized by both Notes b and e shall not exceed 100 percent.

f. A maximum quantity of 5.3 gallons shall be allowed at a workstation when in accordance with FC 2705.2.3.4.

2705.2.3 Workstations.

Workstations in fabrication areas shall be in accordance with FC 2705.2.3.1 through 2705.2.3.4.

2705.2.3.1 Construction.

Workstations in fabrication areas shall be constructed of materials compatible with the materials stored and used at the workstation. The portion of the workstation that serves as a cabinet for HPM gases and flammable liquids shall be noncombustible and, if of metal, shall not be less than 0.0478-inch (1.2-mm) (18 gauge) steel.

2705.2.3.2 Protection of vessels.

Vessels containing hazardous materials located in or connected to a workstation shall be protected as follows:

1. HPM: Vessels containing HPM shall be protected from physical damage and shall not project from the workstation.

2. Hazardous cryogenic fluids, gases and liquids: Hazardous cryogenic fluids, gases and liquid vessels located within a workstation shall be protected from seismic forces in an approved manner in accordance with the construction codes, including the Building Code.

3. Compressed gases: Protection for compressed gases shall additionally comply with the requirements of FC 5303.3.

4. Cryogenic fluids: Protection for cryogenic fluid vessels shall additionally comply with FC 5503.5.

2705.2.3.3 Drainage and containment for HPM liquids.

Each workstation utilizing HPM liquids shall be provided with all of the following:

1. Drainage piping systems connected to a compatible system for disposition of such liquids.

2. The work surface provided with a slope or other means for directing spilled materials to the containment or drainage system.

3. An approved means of containing or directing spilled or leaked liquids to the drainage system.

2705.2.3.4 Pyrophoric liquids and Class 3 water-reactive liquids.

Pyrophoric liquids and Class 3 water-reactive liquids in containers of greater than 1/2-gallon (2-L) but not more than 5.3-gallon (20-L) capacity shall be allowed at workstations when located inside cabinets and the following conditions are met:

1. Maximum amount per cabinet: The maximum amount per cabinet shall be limited to 5.3 gallons (20 L).

2. Cabinet construction: Cabinets shall be constructed in accordance with the following:

2.1. Cabinets shall be constructed of not less than 0.097-inch (2.5-mm) (12 gauge) steel.

2.2. Cabinets shall be allowed to have self-closing limited access ports or noncombustible windows that provide access to equipment controls.

2.3. Cabinets shall be provided with self- or manual-closing doors. Manual-closing doors shall be equipped with a door switch that will initiate local audible and visual alarms when the door is in the open position.

3. Cabinet exhaust ventilation system: An exhaust ventilation system shall be provided for cabinets and shall comply with the following:

3.1. The system shall be designed to operate at a negative pressure in relation to the surrounding area.

3.2. The system shall be equipped with a pressure monitor and a flow switch alarm monitored at the on-site emergency control station.

4. Cabinet spill containment: Spill containment shall be provided in each cabinet, with the spill containment capable of holding the contents of the aggregate amount of liquids in containers in each cabinet.

5. Valves: Valves in supply piping between the product containers in the cabinet and the workstation served by the containers shall fail in the closed position upon power failure, loss of exhaust ventilation and upon actuation of the fire control system.

6. Fire detection system: Each cabinet shall be equipped with an automatic fire detection system complying with the following conditions:

6.1. Automatic detection system: UV/IR, high-sensitivity smoke detection (HSSD) or other approved detection systems shall be provided inside each cabinet.

6.2. Automatic shutoff: Activation of the detection system shall automatically close the shutoff valves at the source on the liquid supply.

6.3. Alarms and signals: Activation of the detection system shall initiate a local alarm within the fabrication area and transmit a signal to the emergency control station. The alarms and signals shall be both visual and audible.

2705.2.4 Exit access corridors and exit enclosures.

Hazardous materials shall not be used in exit access corridors or exit access enclosures.

2705.2.5 Service corridors.

Hazardous materials shall not be used in service corridors.

2705.3 Handling.

The handling of hazardous materials shall comply with the requirements of this section and other applicable provisions of this code.

2705.3.1 Exit corridors access and exit enclosures.

Exit access corridors and exit enclosures shall not contain HPM except as allowed for exit access corridors by the construction codes, including the Building Code.

2705.3.2 Reserved.

2705.3.3 Service corridors.

A service corridor shall be provided where it is necessary to move HPM during handling from a liquid storage room, HPM room, gas room or from the outdoors to the perimeter wall of a fabrication area. Service corridors shall be designed and constructed in accordance with the construction codes, including the Building Code.

2705.3.4 Carts and hand trucks.

Carts and hand trucks used to move HPM during handling in exit access corridors and exit enclosures shall comply with the requirements of FC 5003.10.3.

2705.3.4.1 Identification.

Carts and hand trucks shall be marked to indicate the contents.

Section FC 2801. General

Open this section

2801.1 Scope.

This chapter shall govern the manufacture, storage and handling of lumber, wood products and wood waste material.

2801.2 Permit.

Permits shall be required as set forth in FC 105.6.

2801.3 General.

Lumber and wood waste materials shall be stored and handled in accordance with this chapter. Facilities used for such purposes shall be designed, installed, operated and maintained in accordance with this chapter.

2801.4 Manufacturing prohibited.

The manufacture of lumber, including plywood and other manufactured wood sheets, from trees and other natural wood materials, is prohibited, except as approved by the commissioner.

Section FC 2802. Definitions

Open this section

2802.1 Terms defined in FC Chapter 2.

Terms used in this chapter and defined in FC 202 shall have the meanings set forth therein.

Section FC 2803. General Requirements

Open this section

2803.1 Open yards.

Open yards required by the construction codes, including the Building Code, shall be maintained around buildings and other structures in which lumber and wood waste are stored and handled.

2803.2 Dust control.

Indoor installations that generate combustible dust shall be provided with explosion protection and other combustible dust mitigation measures in accordance with FC Chapter 22 and the construction codes.

2803.3 Housekeeping.

Lumber yards, woodworking facilities and other locations at which lumber is cut or otherwise processed and/or wood waste materials generated, shall be cleaned at the end of each workday, to collect and remove from the premises sawdust and other waste materials.

2803.4 Reserved.

2803.5 Control of ignition sources.

Protection shall be provided from ignition sources in accordance with FC Chapter 3 and FC 2803.5.1 through 2803.5.3.

2803.5.1 Hot work.

Hot work shall comply with the requirements of FC Chapter 35.

2803.5.2 Static electricity.

Static electricity shall be prevented from accumulating on equipment and systems subject to static electricity buildup by permanent grounding and bonding wires or other approved means.

2803.5.3 Smoking.

It shall be unlawful to smoke in a lumber yard, woodworking facility or other facility in which wood or wood waste materials are manufactured, stored or handled.

Section FC 2804. Reserved

Open this section

BetaNYC's copy has no text for this section. Read Section FC 2804 at American Legal Publishing.

Section FC 2805. Reserved

Open this section

BetaNYC's copy has no text for this section. Read Section FC 2805 at American Legal Publishing.

Section FC 2806. Reserved

Open this section

BetaNYC's copy has no text for this section. Read Section FC 2806 at American Legal Publishing.

Section FC 2807. Reserved

Open this section

BetaNYC's copy has no text for this section. Read Section FC 2807 at American Legal Publishing.

Section FC 2808. Outdoor Storage of Wood Chips and Other Wood Waste Materials

Open this section

2808.1 General.

Wood chips and other wood waste materials shall be stored and handled in accordance with this section.

2808.2 Storage areas.

Storage areas shall be level and on solid ground or other all-weather surface. Storage areas shall be thoroughly cleaned before transferring wood products to the area.

2808.3 Size of piles.

Piles shall not exceed 25 feet (7620 mm) in height, 150 feet (45 720 mm) in width and 250 feet (76 200 mm) in length.

Exception: The commissioner may authorize increased pile sizes provided that adequate fire safety is ensured by installing additional fire protection in accordance with FC Chapter 9 and the construction codes, including the Building Code. The increase shall be based upon the capabilities of the system installed.

2808.4 Pile separation.

Piles shall be separated from adjacent piles by approved fire apparatus access roads.

2808.5 Combustible waste.

The storage of wood chips or other wood waste materials, the accumulation and handling of combustible materials, the control of vegetation and the disposal of combustible waste shall comply with the requirements of FC Chapter 3.

2808.6 Pile protection.

Piles of wood chips or other wood waste materials shall be monitored by an approved means to measure internal temperatures within the piles. Internal pile temperatures shall be measured and recorded weekly.

2808.7 Reserved.

2808.8 Fire protection.

The commissioner may require that a yard hydrant system and/or monitor nozzles connected to a fixed water supply be installed upon the premises where the facility arrangement, pile arrangement, pile heights, number of piles or total volume of piles would hamper the effectiveness of hose streams to control or extinguish a fire. Portable fire extinguishers in compliance with the requirements of FC 906 and with a minimum rating of 4-A:60-B:C shall be readily available throughout the premises.

2808.9 Material-handling equipment.

Approved material-handling equipment shall be available for moving wood chips and other wood waste materials during firefighting operations.

Section FC 2809. Outdoor Storage of Finished Lumber Products

Open this section

2809.1 General.

Finished lumber products shall be stored in accordance with this section.

2809.2 Size of piles.

Outdoor lumber storage shall be arranged to form stable piles with a maximum height of 20 feet (6096 mm). Piles shall not exceed 150,000 cubic feet (4248 m 3 ) in volume.

2809.3 Fire apparatus access roads.

Fire apparatus access roads in accordance with FC 503 and the construction codes, including the Building Code, shall be located so that a maximum grid system unit of 50 feet by 150 feet (15 240 mm by 45 720 mm) is established.

2809.4 Security.

Permanent outdoor lumber storage areas shall be surrounded with an approved fence.

2809.5 Fire protection.

The commissioner may require that the yard hydrant system specified in FC 507.2.3 to include monitor nozzles connected to the fixed water supply where the facility arrangement, pile arrangement, pile heights, number of piles or total volume of piles would hamper the effectiveness of hose streams to control or extinguish a fire. Portable fire extinguishers shall be provided in accordance with FC 906 for extra-high hazards and located so that the travel distance to the nearest portable fire extinguisher does not exceed 75 feet (22 860 mm).

Section FC 2901. General

Open this section

2901.1 Scope.

This chapter shall govern facilities and processes where flammable and combustible liquids are used for the manufacture of organic coatings, other than facilities and processes using nonflammable coatings and operations applying coating materials.

2901.2 Permits.

Permits shall be required as set forth in FC 105.6.

2901.3 Maintenance.

Service equipment within a building, structure or premises shall be maintained in accordance with this code and NFPA 35.

2901.4 General.

Organic coating manufacturing facilities and processes shall be designed, installed, operated and maintained in accordance with this chapter.

2901.5 Prohibited organic coatings.

It shall be unlawful to use nitrocellulose in the manufacture of an organic coating.

Section FC 2902. Definitions

Open this section

2902.1 Definition.

The following term shall, for the purposes of this chapter and as used elsewhere in this code, have the meaning set forth in FC 202.

ORGANIC COATING.

Section FC 2903. General Precautions

Open this section

2903.1 Building design.

Manufacturing of organic coatings shall be conducted only in buildings or structures that do not have pits, basements or other areas below grade.

2903.2 Location.

Organic coating manufacturing operations and operations incidental to or connected with organic coating manufacturing shall not be located in buildings having other occupancies.

2903.2.1 Location restrictions.

It shall be unlawful to manufacture organic coatings in any building that is located within 50 feet (15 240 mm) of a building occupied as a multiple dwelling, school, hospital, theater, or other place of assembly.

2903.3 Firefighting access.

Organic coating manufacturing operations shall be accessible from at least one side for the purpose of fire control. Approved aisles shall be maintained for the unobstructed movement of personnel and fire suppression equipment.

2903.4 Fire protection systems.

It shall be unlawful to manufacture an organic coating in any building unless the building is protected throughout by a fire extinguishing system. Fire protection systems shall be designed, installed, operated and maintained, including performing all required tests and inspections, in accordance with FC Chapter 9 and the Building Code.

2903.5 Portable fire extinguishers.

A minimum of one portable fire extinguisher complying with the requirements of FC 906 for extra hazard shall be provided in organic coating areas.

2903.6 Open flames.

Open flames and open-flame devices are prohibited in areas where flammable vapor-air mixtures exist.

2903.7 Smoking.

It shall be unlawful to smoke in any organic coating manufacturing facility.

2903.8 Power equipment.

Power-operated equipment and industrial trucks shall be of a type approved for the location.

2903.9 Tank maintenance.

The cleaning of tanks that have contained flammable or combustible liquids shall be performed under the supervision of a person trained in and knowledgeable about the fire and explosion potential.

2903.9.1 Repairs.

Where necessary to make repairs involving hot work, the work shall be conducted in accordance with FC Chapter 35.

2903.9.2 Reserved.

2903.10 Drainage.

Drainage shall be provided to direct flammable and combustible liquid leakage and fire protection water to an approved location away from the building, any other structure, storage area or adjoining premises.

2903.11 Alarm system.

An approved fire alarm system shall be provided in accordance with the construction codes, including the Building Code.

Section FC 2904. Electrical Equipment and Protection

Open this section

2904.1 Wiring and equipment.

Electrical wiring and equipment shall be designed, installed, operated and maintained in accordance with this chapter and the Electrical Code.

2904.2 Hazardous locations.

Where Class I liquids are exposed to the air, the facility, including all equipment and the ventilation system, shall be designed in a manner that limits Class I, Division 1, locations to the following:

1. Piping trenches.

2. Within the equipment.

3. The immediate vicinity of pumps or equipment locations, such as dispensing stations, open centrifuges, plate and frame filters, opened vacuum filters, change cans and the surfaces of open equipment. The immediate vicinity shall include a zone extending from the vapor liberation point 5 feet (1524 mm) horizontally in all directions and vertically from the floor to a level 3 feet (914 mm) above the highest point of vapor liberation.

2904.2.1 Other locations.

Locations within the confines of the manufacturing room where Class I liquids are handled shall be Class I, Division 2, except locations indicated in FC 2904.2.

2904.2.2 Ordinary equipment.

Ordinary electrical equipment, including switchgear, is prohibited except where installed in a room maintained under positive pressure with respect to the hazardous area. The air or other media utilized for pressurization shall be obtained from a source that will not cause any amount or type of flammable vapor to be introduced into the room.

2904.3 Bonding.

In any area of the facility in which an ignitable mixture may be present in the atmosphere, equipment, including, but not limited to, tanks, machinery and piping, shall be bonded and connected to a ground.

2904.3.1 Piping.

Electrically isolated sections of metallic piping or equipment shall be grounded or bonded to the other grounded portions of the system.

2904.3.2 Vehicles.

Cargo tanks loaded or unloaded through open connections shall be grounded and bonded to the receiving system.

2904.3.3 Containers.

Where a flammable mixture is transferred from one portable container to another, a bond shall be provided between the two containers, and one shall be grounded.

2904.4 Ground.

Metal framing of buildings shall be grounded with resistance of not more than 5 ohms.

Section FC 2905. Process Structures

Open this section

2905.1 Design.

Process structures shall be designed and constructed in accordance with the construction codes, including the Building Code.

2905.2 Fire apparatus access.

Fire apparatus access complying with the requirements of FC 503 shall be provided for the purpose of fire control to at least one side of organic coating manufacturing operations.

2905.3 Drainage.

Drainage facilities shall be provided in accordance with FC 2903.10 where topographical conditions are such that flammable and combustible liquids are capable of flowing from the organic coating manufacturing operation so as to constitute a fire hazard to other premises.

2905.4 Explosion control.

Explosion control shall be provided in areas subject to potential deflagration hazards as set forth in NFPA 35. Explosion control shall be provided in accordance with FC 911.

2905.5 Ventilation.

Buildings in which Class I liquids are processed or handled shall be ventilated at a rate of not less than 1 cubic foot per minute per square foot (0.00508 m 3 /s/m 2 ) of solid floor area. Ventilation shall be accomplished by exhaust fans that take suction at floor levels and discharge to a safe location outdoors. Noncontaminated intake air shall be introduced in such a manner that all portions of solid floor areas are provided with continuous uniformly distributed air movement.

2905.6 Heating.

Heating provided in hazardous areas shall be by indirect means. Ignition sources such as open flames or electrical heating elements, except as provided for in FC 2904, are prohibited within the building.

Section FC 2906. Process Mills and Kettles

Open this section

2906.1 Mills.

Mills, operating with close clearances, which process flammable and heat-sensitive materials shall be located in a detached building or in a noncombustible structure without other occupancies. The amount of flammable material brought into the area shall not be more than the amount required for a batch.

2906.2 Mixers.

Mixers shall be of the enclosed type or, where of the open type, shall be provided with properly fitted covers. Where flow is by gravity, a shutoff valve shall be installed as close as practical to the mixer, and a control valve shall be provided near the end of the fill pipe.

2906.3 Open kettles.

Open kettles shall be located in outdoor areas provided with a protective roof; in a separate structure of noncombustible construction; or separated from other areas by a noncombustible wall having a fire-resistance rating of at least 2 hours.

2906.4 Closed kettles.

Contact-heated kettles containing solvents shall be equipped with safety devices that, in case of a fire, will turn off the process heat, turn on the cooling medium and inject inert gas into the kettle.

2906.4.1 Vaporizer location.

The vaporizer section of heat-transfer systems that heat closed kettles containing solvents shall be remotely located.

2906.5 Kettle controls.

The kettle and thin-down tank shall be instrumented, controlled and interlocked so that any failure of the controls will not result in an unsafe condition. The kettle shall be provided with a pressure-rupture disc in addition to the primary vent. The vent piping from the rupture disc shall be of minimum length and shall discharge to an approved location. The thin-down tank shall be adequately vented. Thinning operations shall be provided with a vapor removal system capable of ensuring a safe atmosphere.

Section FC 2907. Process Piping

Open this section

2907.1 Design.

All piping, valves and fittings shall be designed for the working pressures and structural stresses to which the piping, valves and fittings will be subjected, and shall be of steel or other material approved for the service intended.

2907.2 Valves and fittings.

Valves shall be of an indicating type. Terminal valves on remote pumping systems shall be of the dead-man type, shutting off both the pump and the flow of solvent. Valves and fittings shall not be constructed of cast iron.

2907.3 Support.

Piping systems shall be supported and protected against physical damage. Piping shall be pitched to avoid unintentional trapping of liquids, or approved drains shall be provided.

2907.4 Connectors.

Approved flexible connectors shall be installed where vibration exists or frequent movement is necessary. Hoses at dispensing stations shall be of an approved type.

2907.5 Tests.

Before being placed in service, all piping shall be free of leaks when tested for a minimum of 30 minutes at not less than one and one-half times the working pressure or a minimum of 5 pounds per square inch gauge (psig) (35 kPa) at the highest point in the system.

Section FC 2908. Raw Materials in Process Areas

Open this section

2908.1 Reserved.

2908.2 Organic peroxides.

Organic peroxides brought into the process area shall be in the original shipping container. When in the process area, the organic peroxide shall not be placed in locations exposed to ignition sources, heat, mechanical shocks or flammable liquids, except that organic peroxide may be exposed to flammable liquid during raw material processing.

Section FC 2909. Raw Materials and Finished Products

Open this section

2909.1 General.

The storage, handling and use of flammable and combustible liquids in process areas shall be in accordance with FC Chapter 57. The storage, handling and use of organic peroxides shall be in accordance with FC Chapter 62 and the storage, handling and use of oxidizers shall be in accordance with FC Chapter 63.

2909.2 Tank storage.

Tanks for the storage of flammable and combustible liquids shall be installed in accordance with FC Chapter 57. Process equipment storing or using flammable or combustible liquids and storage in quantities necessary for maintaining the operation is allowed in the process area.

2909.3 Loading and unloading.

Tank car and cargo tank loading and unloading stations for Class I liquids shall be separated from the process area, other facility structures, the nearest lot line, public street or private road by a minimum distance in accordance with FC Chapter 57.

2909.3.1 Loading.

Loading and unloading structures and platforms for flammable and combustible liquids shall be designed and installed in accordance with FC Chapter 57.

2909.3.2 Safety.

Tank cars and cargo tanks for flammable and combustible liquids shall be loaded and unloaded in accordance with FC Chapter 57.

2909.4 Reserved.

2909.5 Organic peroxide storage.

The storage of organic peroxides shall be in accordance with FC Chapter 62.

2909.5.1 Size.

The size of the package containing organic peroxide shall be selected so that, as nearly as practical, full packages are utilized at one time. Spilled peroxide shall be promptly removed and disposed of lawfully.

2909.6 Finished products.

Finished products that are flammable or combustible liquids shall be stored outdoors, in a separate building, or in a room separate from the process area, in accordance with the construction codes, including the Building Code. The storage of finished products shall be in tanks or closed containers in accordance with FC Chapter 57.

Section FC 3001. General

Open this section

3001.1 Scope.

This chapter shall govern the design, installation, operation and maintenance of industrial furnaces used for commercial and industrial processing of materials.

3001.2 Permits.

Permits shall be required as set forth in FC 105.6.

3001.3 General.

Industrial furnaces shall be designed, installed, operated and maintained in accordance with this chapter, NFPA 86, and the construction codes, including the Fuel Gas Code and the Mechanical Code.

Section FC 3002. Definitions

Open this section

3002.1 Definitions.

The following words shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.

FURNACE.

Class A.

Class B.

Class C.

Class D.

Section FC 3003. Location

Open this section

3003.1 Ventilation.

Enclosed rooms, basements or other areas below grade containing industrial furnaces shall be provided with combustion air in accordance with the construction codes, including the Mechanical Code and the Fuel Gas Code, and with ventilation in accordance with the Mechanical Code.

3003.2 Location.

Industrial furnaces and heaters shall be located such that in the event of fire or explosion resulting from overheating or from the escape of fuel gas or fuel oil, damage to the building and injury to persons is minimized.

3003.3 Ignition source.

Industrial furnaces shall be located so as not to pose an ignition hazard to flammable vapors or mists or combustible dusts that may be present as a result of a manufacturing operation or other lawful use and occupancy of the building.

3003.4 Temperatures.

Roofs and floors of furnaces shall be insulated and ventilated to prevent temperatures at combustible ceilings and floors from exceeding 160°F (71°C).

Section FC 3004. Fuel Piping

Open this section

3004.1 Fuel-gas piping.

Fuel-gas piping serving industrial furnaces shall be designed and installed in accordance with the Fuel Gas Code. Piping for other fuel sources shall comply with the requirements of this section.

3004.2 Shutoff valves.

Each industrial furnace shall be provided with an approved manual fuel shutoff valve in accordance with the construction codes, including the Mechanical Code and the Fuel Gas Code.

3004.2.1 Fuel supply lines.

Valves for fuel supply lines shall be located within 6 feet (1829 mm) of the appliance served.

Exception: When approved and the valve is located in the same general area as the appliance served.

3004.3 Valve position.

The design of manual fuel shutoff valves shall incorporate a permanent feature that visually indicates the open or closed position of the valve. Manual fuel shutoff valves shall not be equipped with removable handles or wrenches unless the handle or wrench can only be installed parallel with the fuel line when the valve is in the open position.

Section FC 3005. Interlocks

Open this section

3005.1 Shut down.

Interlocks shall be provided for Class A furnaces so that conveyors or sources of flammable or combustible materials shall shut down if either the exhaust or recirculation air supply fails.

Section FC 3006. Fire Protection

Open this section

3006.1 Required protection.

Class A and B furnaces that contain, or are utilized for the processing of, combustible materials shall be protected throughout by a fire extinguishing system complying with the requirements of FC Chapter 9.

3006.2 Fixed fire extinguishing systems.

A fixed fire extinguishing system shall be provided for Class C or D furnaces to protect against such hazards as overheating, spillage of molten salts or metals, quench tanks, ignition of hydraulic oil and escape of fuel.

3006.3 Portable fire extinguishers.

Portable fire extinguishers complying with the requirements of FC 906 shall be provided not closer than 15 feet (4572 mm) or a maximum of 50 feet (15240 mm) from each furnace or in accordance with NFPA 10.

Section FC 3007. Operation and Maintenance

Open this section

3007.1 Furnace operation and maintenance instructions.

The furnace manufacturer's complete installation, inspection, testing, operation and maintenance instructions shall be available on the premises to those individuals responsible for the operation, maintenance and supervision of the furnace.

3007.2 Furnace nameplate.

The following data for Class A furnaces shall be furnished on the manufacturer's nameplate:

1. The solvent used.

2. The number of gallons (liters) used per batch or per hour of solvent entering the furnace.

3. The required purge time.

4. The oven operating temperature.

5. The exhaust blower rating for the number of gallons (liters) of solvent per hour or batch at the maximum operating temperature, or with regard to low-oxygen furnaces, the maximum allowable oxygen concentration.

3007.3 Training.

The operation and maintenance of furnaces shall be performed by a person knowledgeable and trained in the operation and maintenance of such furnaces.

3007.4 Equipment maintenance.

Equipment shall be maintained in accordance with the manufacturer's instructions.

Section FC 3101. General

Open this section

3101.1 Scope.

This chapter shall govern membrane structures.

3101.2 Permits.

Permits shall be required as set forth in FC 105.6.

Section FC 3102. Definitions

Open this section

3102.1 Definitions.

The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.

AIR-INFLATED STRUCTURE.

AIR-SUPPORTED STRUCTURE.

MEMBRANE STRUCTURE.

TENT.

Section FC 3103. Reserved

Open this section

BetaNYC's copy has no text for this section. Read Section FC 3103 at American Legal Publishing.

Section FC 3104. Tents and Other Membrane Structures

Open this section

3104.1 General.

All membrane structures shall be designed, installed, operated and maintained in accordance with this section and the construction codes, including the Building Code.

3104.2 Flame-resistant treatment.

The owner or agent shall file with the commissioner a certificate issued by an approved testing laboratory, certifying that the tent materials and their appurtenances, sidewalls, drops and tarpaulins, floor coverings, bunting, combustible decorative materials and effects, including sawdust when used on floors or passageways, are composed of flame-resistant material meeting the flame propagation performance criteria of NFPA 701 or shall be treated with a flame retardant in an approved manner and meet the flame propagation performance criteria of NFPA 701, and that such flame resistance is effective for the period specified by the permit.

3104.2.1 Certification.

An affidavit or affirmation shall be submitted to the commissioner and a copy retained on the premises on which the tent is located. The affidavit shall attest to the information required in FC Chapter 8 and the rules.

3104.2.2 Label.

Membrane structures shall have a label permanently affixed to them identifying the type and quality of the fabric or other material.

3104.3 Location and access.

Membrane structures shall be placed and afforded access for firefighting apparatus in accordance with this section.

3104.3.1 Access.

Fire apparatus access roads shall be provided in accordance with FC 503 and the Building Code.

3104.3.2 Location.

Membrane structures shall not be located within 20 feet (6096 mm) of parked vehicles or internal combustion engines. For the purpose of determining required distances, support ropes and guy wires shall be considered as part of the membrane structure.

3104.3.3 Fire break.

An unobstructed fire break not less than 12 feet (3658 mm) wide and free from guy ropes or other obstructions shall be maintained on all sides of all membrane structures unless otherwise approved by the commissioner.

3104.4 Means of egress.

Means of egress for membrane structures shall be in accordance with this section and the construction codes, including the Building Code.

3104.4.1 Seating arrangements.

Seating in membrane structures shall be in accordance with the construction codes, including the Building Code.

3104.4.2 Exit openings from tents.

Exit openings from tents shall remain open unless covered by a flame-resistant curtain. The curtain shall comply with the following requirements:

1. Curtains shall be free sliding on a metal support. The support shall be a minimum of 80 inches (2032 mm) above the floor level at the exit. The curtains shall be so arranged that, when open, no part of the curtain obstructs the exit.

2. Curtains shall be of a color, or colors, that contrasts with the color of the tent.

3. Curtains shall be flame resistant in accordance with FC Chapter 8.

3104.4.2.1 Door operation in air-supported structures.

During high winds exceeding 50 miles per hour (80 kph) or in snow conditions, the use of doors in air-supported structures shall be controlled to avoid excessive air loss. Doors shall not be left open.

3104.4.3 Aisle arrangement and maintenance.

The arrangement of aisles shall be subject to the approval of the commissioner and shall be maintained clear at all times.

3104.4.4 Maintenance of means of egress.

The required width of exits, aisles and passageways to a public street shall be maintained at all times. Guy wires, guy ropes and other support members shall not cross a means of egress at a height of less than 8 feet (2438 mm). The surface of means of egress shall be maintained in an approved manner.

3104.5 Combustible materials.

Hay, straw, shavings or similar combustible materials shall not be located within any membrane structure containing an assembly occupancy, except the materials necessary for the daily feeding and care of animals. Sawdust and shavings utilized for a public performance or exhibit shall not be prohibited provided the sawdust and shavings are kept damp. Combustible materials shall not be allowed under stands or seats at any time.

3104.6 Smoking.

Smoking shall not be allowed in membrane structures. "No Smoking" signs complying with the requirements of FC 310 shall be conspicuously posted.

3104.7 Open or exposed flame.

Open flame or other devices emitting flame, fire or heat or any flammable or combustible liquids, gas, charcoal or other cooking device or any other unapproved devices shall not be allowed inside or located within 20 feet (6096 mm) of a membrane structure while open to the public unless an open-flame permit has been issued.

3104.8 Fireworks and special effects.

Any fireworks or special effects displays in or near any membrane structure shall be conducted in accordance with FC Chapter 56.

3104.9 Spot lighting.

Spot or effect lighting shall only be by electricity, and all combustible construction located within 6 feet (1829 mm) of such equipment shall be protected with approved noncombustible insulation not less than 9.25 inches (235 mm) thick.

3104.10 Safety film.

Motion pictures shall not be displayed in membrane structures unless the motion picture film is safety film.

3104.11 Clearance.

There shall be a minimum clearance of at least 3 feet (914 mm) between the surface of a membrane structure and all contents therein.

3104.12 Portable fire extinguishers.

Portable fire extinguishers shall be provided as required by FC 906.

3104.13 Fire protection equipment.

Fire hose lines, water supplies and other auxiliary fire equipment shall be maintained at the site in such numbers and sizes as required by the commissioner.

3104.14 Occupant load.

The occupant load allowed in a membrane structure, shall be determined in accordance with the construction codes, including the Building Code.

3104.15 Heating and cooking equipment.

Heating and cooking equipment shall be in accordance with this section.

3104.15.1 Installation.

Heating or cooking equipment, tanks, piping, hoses, fittings, valves, tubing and other related components shall be installed as set forth in the construction codes, including the Mechanical Code and the Fuel Gas Code.

3104.15.2 Venting.

Gas, liquid and solid fuel-burning equipment designed to be vented shall be vented to the outdoors in accordance with the construction codes, including the Mechanical Code and the Fuel Gas Code. Such vents shall be equipped with approved spark arresters when required. Where vents or flues are used, all portions of the membrane structure shall be not less than 12 inches (305 mm) from the flue or vent.

3104.15.3 Location.

Cooking and heating equipment shall not be located within 10 feet (3048 mm) of exits or combustible materials.

3104.15.4 Operations.

Operations such as warming of foods, cooking demonstrations and similar operations that use solid flammables shall be approved by the commissioner.

3104.15.5 Cooking.

Membrane structures in which cooking is performed shall be separated from other membrane structures by a minimum of 20 feet (6096 mm).

3104.15.6 Outdoor cooking.

Outdoor cooking that produces sparks or grease-laden vapors shall not be performed within 20 feet (6096 mm) from a membrane structure.

3104.15.7 Electrical heating and cooking equipment.

Electrical cooking and heating equipment shall comply with the requirements of the Electrical Code.

3104.16 LPG.

The storage, handling and use of LPG and LPG equipment shall be in accordance with this section and FC Chapter 61.

3104.16.1 General.

Stationary LPG installations, including tanks, piping, hoses, fittings, valves, tubing and other related components shall be approved and in accordance with FC Chapter 61.

3104.16.2 Location of containers.

LPG containers shall be located outside the membrane structure. Pressure relief valves shall be pointed away from the membrane structure.

3104.16.2.1 Containers.

Portable LPG containers shall have a minimum separation between the container and structure of not less than 10 feet (3048 mm).

3104.16.3 Protection from movement.

Portable LPG containers, piping, valves and fittings which are being used to fuel LPG-fueled devices, equipment or systems inside a membrane structure shall be located outside the membrane structure and shall be secured from movement or other hazard.

3104.17 Flammable and combustible liquids.

The storage of flammable and combustible liquids and the use of flammable-liquid-fueled equipment shall be in accordance with this section.

3104.17.1 Use.

Flammable-liquid-fueled equipment shall not be used in membrane structures.

3104.17.2 Flammable and combustible liquid storage.

Flammable and combustible liquids shall be stored outside the membrane structure in an approved manner not less than 50 feet (15240 mm) from the membrane structure. Storage shall be in accordance with FC Chapter 57.

3104.17.3 Refueling.

Refueling shall be performed at an approved location not less than 20 feet (6096 mm) from membrane structures.

3104.18 Display of liquid- and gas-fueled motor vehicles.

Liquid- and gas-fueled vehicles and equipment may be displayed within a membrane structure in accordance with this section and FC Chapter 3.

3104.18.1 Batteries.

Batteries shall be disconnected in an appropriate manner.

3104.18.2 Fuel systems.

Vehicles or equipment shall not be fueled or defueled within the membrane structure.

3104.18.2.1 Quantity limit.

Fuel in the fuel tank shall not exceed 1 gallon (3.8 L).

3104.18.2.2 Inspection.

Fuel systems shall be inspected for leaks.

3104.18.2.3 Closure.

Fuel tank openings shall be locked and sealed to prevent the escape of vapors.

3104.18.3 Location.

The location of vehicles or equipment shall not obstruct means of egress.

3104.18.4 Display of CNG/LPG vehicles.

When a compressed natural gas (CNG) or liquefied petroleum gas (LPG) powered vehicle is parked inside a membrane structure, all of the following conditions shall be met:

1. The quarter-turn shutoff valve or other shutoff valve on the outlet of the CNG or LPG container shall be closed and the engine shall be operated until it stops. Valves shall remain closed while the vehicle is indoors.

2. The hot lead of the battery shall be disconnected.

3. Dual-fuel vehicles equipped to operate on gasoline and CNG or LPG shall comply with the requirements of this section and FC 3104.18 through 3104.18.3 for gasoline-powered vehicles.

3104.18.5 Competitions and demonstrations.

Liquid and gas-fueled vehicles and equipment used for competition or demonstration within a membrane structure shall comply with the requirements of 3104.18.5.1.

3104.18.5.1 Fuel storage and dispensing.

Fuel for vehicles or equipment shall be stored and dispensed in an approved location outside of the membrane structure in accordance with FC 3104.17.2 and 3104.17.3, and FC Chapter 23.

3104.19 Separation of generators.

Generators and other internal combustion power sources shall be separated from membrane structures by a minimum of 20 feet (6096 mm) and shall be isolated from contact with the public by fencing, enclosure or other approved means.

3104.20 Fire guards.

When the interest of public safety so requires, the commissioner may order the owner of any membrane structure in which a performance, exhibition, display, contest or other activity is to be conducted to provide one or more fire guards or other qualified persons to remain on duty during the times such places are open to the public, or when such activity is being conducted. Persons conducting such fire watch shall have duties and responsibilities set forth in FC 901.7.2.1 with respect to the areas being monitored in connection with such membrane structure, and shall assist in the evacuation of the occupants from the structure in the event of a fire or other emergency.

3104.21 Vegetation removal.

Vegetation shall be removed from the area occupied by a membrane structure, and from areas within 30 feet (9144 mm) of such structures.

3104.22 Combustible waste and storage of combustible material.

The floor surface inside membrane structures and the grounds within 30 feet (9144 mm) of the membrane structure shall be kept free of combustible waste and storage of combustible materials.

Section FC 3201. General

Open this section

3201.1 Scope.

This chapter shall govern high-piled combustible storage, and the design, installation, operation and maintenance of any building, structure or premises used for such purpose.

3201.2 Permits.

Permits shall be required as set forth in FC 105.6.

3201.3 Permit application.

Applications for permits for high-piled combustible storage shall include design and installation documents that contain the following information, and such other information and documentation as the commissioner may prescribe:

1. Floor plan of the building showing locations and dimensions of high-piled storage areas.

2. Usable storage height for each storage area.

3. Number of tiers within each rack, if applicable.

4. Commodity clearance between top of storage and the sprinkler deflector for each storage arrangement.

5. Aisle dimensions between each storage array.

6. Maximum pile volume for each storage array.

7. Location and classification of commodities in accordance with FC 3203.

8. Location of commodities that are banded or encapsulated.

9. Location of required fire department access doors.

10. Type of fire extinguishing and fire detection systems.

11. Location of valves controlling the water supply of ceiling and in-rack sprinklers.

12. Type, location and specifications of smoke removal and curtain board systems.

13. Dimension and location of transverse and longitudinal flue spaces.

14. Such other information, regarding design features, commodities, storage arrangement and fire protection features within the high-piled storage area, as may be required by the commissioner to ensure compliance with the requirements of this chapter.

3201.3.1 Records.

A copy of the permit application documents shall be maintained on the premises and made available for inspection by any department representative.

3201.4 Egress plan.

Where the area of the high-piled combustible storage requires a permit, the owner shall prepare and familiarize employees with an egress plan that indicates the location and width of aisles, exits, exit access doors, exit signs, height of storage and location of hazardous materials. Such plan shall be maintained in an approved location and shall be made available for inspection by any representative of the department.

Exception: Any high-piled combustible storage facility or area required to have an emergency preparedness plan pursuant to FC Chapter 4.

3201.5 General.

All buildings, structures and premises that contain high-piled combustible storage shall be designed, installed, operated and maintained in accordance with this chapter. In addition to the requirements of this chapter, the following material-specific requirements shall apply:

1. Aerosols shall be in accordance with FC Chapter 51.

2. Flammable and combustible liquids shall be in accordance with FC Chapter 57.

3. Hazardous materials shall be in accordance with FC Chapter 50.

4. Storage of combustible paper records shall be in accordance with NFPA 13, as modified by FC Appendix B.

5. Storage of combustible fibers shall be in accordance with FC Chapter 37.

6. Storage of miscellaneous combustible material shall be in accordance with FC Chapter 3.

Section FC 3202. Definitions

Open this section

3202.1 Definitions.

The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.

ARRAY.

ARRAY, CLOSED.

AUTOMATED RACK STORAGE.

BIN BOX.

COMMODITY.

DRAFT CURTAIN.

EARLY SUPPRESSION FAST-RESPONSE (ESFR) SPRINKLER.

ENCAPSULATION.

EXPANDED PLASTIC.

EXTRA-HIGH-RACK COMBUSTIBLE STORAGE.

FLUE SPACE, LONGITUDINAL.

FLUE SPACE, TRANSVERSE.

HIGH-PILED COMBUSTIBLE STORAGE.

HIGH-PILED STORAGE AREA.

MANUAL STOCKING METHODS.

MECHANICAL STOCKING METHODS.

RACK STORAGE.

SHELF STORAGE.

SOLID SHELVING.

Section FC 3203. Commodity Classification

Open this section

This section has 1 picture (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read Section FC 3203 at American Legal Publishing.

3203.1 Classification of commodities.

Commodities shall be classified as Class I, II, III, IV or high hazard in accordance with this section. Materials listed within each commodity classification are assumed to be unmodified for improved combustibility characteristics. Use of flame-retarding modifiers or the physical form of the material could change the classification. Group A, B and C plastic commodities are classified in FC 3203.7 and plastic shelving and pallets are addressed in FC 3208.2.1.

3203.2 Class I commodities.

Class I commodities are essentially noncombustible products on wooden pallets, in ordinary corrugated cartons with or without single-thickness dividers, or in ordinary paper wrappings with or without pallets. Class I commodities are allowed to contain a limited amount of Group A plastics in accordance with FC 3203.7.4. Examples of Class I commodities include the following:

Alcoholic beverages not more than 20-percent alcohol

Cement in bags

Ceramics

Dairy products in nonwax-coated containers (excluding bottles)

Dry insecticides

Electrical appliances, noncombustible

Foods in noncombustible containers

Fresh fruits and vegetables in nonplastic trays or containers

Frozen foods

Glass

Glycol in metal cans

Gypsum board

Inert materials, bagged

Insulation, noncombustible

Liquids, noncombustible, in plastic containers having less than a 5-gallon (19 L) capacity

Metal products, noncombustible

3203.3 Class II commodities.

Class II commodities are Class I products in slatted wooden crates, solid wooden boxes, multiple-thickness paperboard cartons or equivalent combustible packaging material with or without pallets. Class II commodities are allowed to contain a limited amount of Group A plastics in accordance with FC 3203.7.4. Examples of Class II commodities include the following:

Alcoholic beverages not more than 20-percent alcohol, in combustible containers

Foods in combustible containers

Incandescent or fluorescent light bulbs in cartons

Thinly coated fine wire on reels or in cartons

3203.4 Class III commodities.

Class III commodities are commodities of wood, paper, natural fiber cloth, or Group C plastics or products thereof, with or without pallets. Products are allowed to contain limited amounts of Group A or B plastics, such as metal bicycles with plastic handles, pedals, seats and tires. Group A plastics shall be limited in accordance with FC 3203.7.4. Examples of Class III commodities include the following:

Aerosol, Level 1 (see FC Chapter 51)

Combustible fiberboard

Cork, baled

Feed, bagged

Fertilizers, bagged

Food in plastic containers

Furniture: wood, natural fiber, upholstered, nonplastic, wood or metal with plastic-padded and covered arm rests

Glycol in combustible containers not more than 25 percent

Liquids, noncombustible, in plastic containers having a capacity of more than 5 gallons (19 L)

Lubricating or hydraulic fluid in metal cans

Lumber

Mattresses, excluding foam rubber and foam plastics

Paints, oil base, in metal cans

Paper, waste, baled

Paper and pulp, horizontal storage, or vertical storage that is banded or protected with approved wrap

Paper in cardboard boxes

Pillows, excluding foam rubber and foam plastics

Plastic-coated paper food containers

Plywood

Rags, baled

Rugs, without foam backing

Sugar, bagged

Wood, baled

Wood doors, frames and cabinets

Yarns of natural fiber and viscose

3203.5 Class IV commodities.

Class IV commodities are Class I, II or III products containing Group A plastics in ordinary corrugated cartons and Class I, II and III products, with Group A plastic packaging, with or without pallets. Group B plastics and free-flowing Group A plastics are also included in this class. The total amount of nonfree-flowing Group A plastics shall be in accordance with FC 3203.7.4. Examples of Class IV commodities include the following:

Aerosol, Level 2 (see FC Chapter 51)

Alcoholic beverages, more than 20-percent but less than 80-percent alcohol, in cans or bottles in cartons

Clothing, synthetic or nonviscose

Combustible metal products (solid)

Furniture, plastic upholstered

Furniture, wood or metal with plastic covering and padding

Glycol in combustible containers (more than 25 percent and less than 50 percent)

Linoleum products

Paints, oil base in combustible containers

Pharmaceutical, alcoholic elixirs, tonics, etc.

Rugs, foam back

Shingles, asphalt

Thread or yarn, synthetic or nonviscose

3203.6 High-hazard commodities.

High-hazard commodities are high-hazard products presenting special fire hazards beyond those of Class I, II, III or IV. Group A plastics not otherwise classified are included in this class. Examples of high-hazard commodities include the following:

Aerosol, Level 3 (see FC Chapter 51)

Alcoholic beverages, more than 80-percent alcohol, in bottles or cartons

Commodities of any class in plastic containers in carousel storage

Flammable solids (except solid combustible metals)

Glycol in combustible containers (50 percent or more)

Lacquers, which dry by solvent evaporation, in metal cans or cartons

Lubricating or hydraulic fluid in plastic containers

Mattresses, foam rubber or foam plastics

Pallets and flats which are idle combustible

Paper, asphalt, rolled, horizontal storage

Paper, asphalt, rolled, vertical storage

Paper and pulp, rolled, in vertical storage which is unbanded or not protected with an approved wrap

Pillows, foam rubber and foam plastics

Pyroxylin

Rubber tires

Vegetable oil and butter in plastic containers

3203.7 Classification of plastics.

Plastics shall be designated as Group A, B or C in accordance with this section.

3203.7.1 Group A plastics.

Group A plastics are plastic materials having a heat of combustion that is much higher than that of ordinary combustibles, and a burning rate higher than that of Group B plastics. Examples of Group A plastics include the following:

ABS (acrylonitrile-butadiene-styrene copolymer)

Acetal (polyformaldehyde)

Acrylic (polymethyl methacrylate)

Butyl rubber

EPDM (ethylene propylene rubber)

FRP (fiberglass-reinforced polyester)

Natural rubber (expanded)

Nitrile rubber (acrylonitrile butadiene rubber)

PET or PETE (polyethylene terephthalate)

Polybutadiene

Polycarbonate

Polyester elastomer

Polyethylene

Polypropylene

Polystyrene (expanded and unexpanded)

Polyurethane (expanded and unexpanded)

PVC (polyvinyl chloride more than 15 percent plasticized, e.g., coated fabric unsupported film)

SAN (styrene acrylonitrile)

SBR (styrene butadiene rubber)

3203.7.2 Group B plastics.

Group B plastics are plastic materials having a heat of combustion and a burning rate higher than that of ordinary combustibles, but not as high as those of Group A plastics. Examples of Group B plastics include the following:

Cellulosics (cellulose acetate, cellulose acetate butyrate, ethyl cellulose)

Chloroprene rubber

Fluoroplastics (ECTFE, ethylene-chlorotrifluoroethylene copolymer; ETFE, ethylene-tetrafluoroethylene copolymer; FEP, fluorinated ethylene-propylene copolymer)

Natural rubber (nonexpanded)

Nylon (Nylon 6, Nylon 6/6)

PVC (polyvinyl chloride more than 5-percent, but not more than 15-percent plasticized)

Silicone rubber

3203.7.3 Group C plastics.

Group C plastics are plastic materials having a heat of combustion and a burning rate similar to those of ordinary combustibles. Examples of Group C plastics include the following:

Fluoroplastics (PCTFE, polychlorotrifluoroethylene; PTFE, polytetrafluoroethylene)

Melamine (melamine formaldehyde)

Phenol

PVC (polyvinyl chloride, rigid or plasticized less than 5 percent, e.g., pipe, pipe fittings)

PVDC (polyvinylidene chloride)

PVDF (polyvinylidene fluoride)

PVF (polyvinyl fluoride)

Urea (urea formaldehyde)

3203.7.4 Limited quantities of Group A plastics in mixed commodities.

FC Figure 3203.7.4 shall be used to determine the quantity of Group A plastics allowed to be stored in a package or carton or on a pallet without increasing the commodity classification.

FC Figure 3203.7.4 Mixed Commodities a, b

a. This figure is intended to determine the commodity classification of a mixed commodity in a package, carton or on a pallet where plastics are involved.

b. The following is an example of how to apply the figure: A package containing a Class III commodity has 12-percent Group A expanded plastic by volume. The weight of the unexpanded Group A plastic is 10 percent. This commodity is classified as a Class IV commodity. If the weight of the unexpanded plastic is increased to 14 percent, the classification changes to a high-hazard commodity.

c. Percent by volume = Volume of plastic in pallet load Total volume of plastic load, including pallet d. Percent by weight = Weight of plastic in pallet load Total weight of plastic load, including pallet

Section FC 3204. Designation of High-piled Storage Areas

Open this section

3204.1 General.

High-piled storage areas, and portions of high-piled storage areas for storage of a commodity class different from adjacent areas, shall be designed and specifically designated to contain Class I, Class II, Class III, Class IV or high-hazard commodities. The designation of a high-piled combustible storage area, or portion thereof intended for storage of a different commodity class, shall be based on the highest hazard commodity class stored except as provided in FC 3204.2.

3204.2 Designation based on engineering analysis.

The designation of a high-piled combustible storage area, or portion thereof, is allowed to be based on a lower hazard class than that of the highest class of commodity stored when a limited quantity of the higher hazard commodity has been demonstrated by engineering analysis to be adequately protected by the sprinkler system provided. The engineering analysis shall consider the ability of the sprinkler system to deliver the higher density required by the higher hazard commodity. The higher density shall be based on the actual storage height of the pile or rack and the minimum allowable design area for sprinkler operation as set forth in the density/area figures provided in NFPA 13, as modified by FC Appendix B. The contiguous area occupied by the higher hazard commodity shall not exceed 120 square feet (11 m 2 ), and additional areas of higher hazard commodity shall be separated from other such areas by 25 feet (7620 mm) or more. The sprinkler system shall be capable of delivering the higher density over a minimum area of 900 square feet (84 m 2 ) for wet pipe systems and 1,200 square feet (111 m 2 ) for dry pipe systems. The shape of the design area shall be in accordance with the construction codes, including the Building Code.

Section FC 3205. Housekeeping and Maintenance

Open this section

3205.1 Rack structures.

The structural integrity of racks shall be maintained.

3205.2 Ignition sources.

Clearance from ignition sources shall be provided in accordance with FC 305.

3205.3 Smoking.

Smoking is prohibited in high-piled storage areas. "No Smoking" signs complying with the requirements of FC 310 shall be conspicuously posted in such areas.

3205.4 Aisle maintenance.

When restocking is not being conducted, aisles shall be kept clear of stored or waste material. Fire department access doors, aisles and exit doors shall not be obstructed. During restocking operations using manual stocking methods, a minimum unobstructed aisle width of 24 inches (610 mm) shall be maintained in 48-inch (1219-mm) or smaller aisles, and a minimum unobstructed aisle width of one-half of the required aisle width shall be maintained in aisles greater than 48 inches (1219 mm). During mechanical stocking operations, a minimum unobstructed aisle width of 44 inches (1118 mm) shall be maintained in accordance with FC 3206.9.

3205.5 Pile dimension and height limitations.

Pile dimensions and height limitations shall comply with the requirements of FC 3207.3.

3205.6 Arrays.

Arrays shall comply with the requirements of FC 3207.4.

3205.7 Flue spaces.

Flue spaces shall comply with the requirements of FC 3208.3.

Section FC 3206. General Fire Protection and Life Safety Features

Open this section

3206.1 General.

Fire protection and life safety features for high-piled storage areas shall be in accordance with this section.

3206.2 Extent and type of protection.

Where required by FC Table 3206.2, fire detection systems, smoke and heat removal, draft curtains and sprinkler design densities shall extend the lesser of 15 feet (4572 mm) beyond the high-piled storage area or to a permanent partition. Where portions of high-piled storage areas have different fire protection requirements because of commodity, method of storage or storage height, the fire protection features required by FC Table 3206.2 within this area shall be based on the most restrictive design requirements.

3206.3 Separation of high-piled storage areas.

High-piled storage areas shall be separated from other portions of the building where required by FC 3206.3.1 through 3206.3.2.2.

3206.3.1 Separation from other uses.

Mixed occupancies shall be separated in accordance with the construction codes, including the Building Code.

3206.3.2 Multiple high-piled storage areas.

Multiple high-piled storage areas shall be designed and installed in accordance with FC 3206.3.2.1 or 3206.3.2.2.

3206.3.2.1 Aggregate area.

The aggregate of all high-piled storage areas within a building shall be used for application of FC Table 3206.2 unless such areas are separated from each other by 1-hour fire-resistance-rated fire barrier walls constructed in accordance with the construction codes, including the Building Code. Openings in such walls shall be protected by opening protective assemblies having a 1-hour fire protection rating.

3206.3.2.2 Multiclass high-piled storage areas.

High-piled storage areas classified as Class I through Class IV not separated from high-piled storage areas classified as high hazard shall utilize the aggregate of all high-piled storage areas as high hazard for purposes of application of FC Table 3206.2. To be considered as separated, 1-hour fire-resistance-rated fire barrier walls shall be constructed in accordance with the construction codes, including the Building Code. Openings in such walls shall be protected by opening protective assemblies having a 1-hour fire protection rating.

Exception: As provided for in FC 3204.2.

FC Table 3206.2 General Fire Protection and Life Safety Requirements

Commodity Class Size of High-Piled Storage Area a (square feet) (see FC 3206.2 and 3206.4) All Storage Areas (See FC 3206, 3207 and 3208) b Solid-Piled Storage, Shelf Storage and Palletized Storage (see FC 3207.3) Automatic fire- extinguishing system (see FC 3206.4) Fire detection system (see FC 3206.5) Building Access (see FC 3206.6) Smoke and heat removal (see FC 3206.7) Draft curtains (see FC 3206.7) Maximum pile dimension c (feet) Maximum permissible storage height d (feet) Maximum pile volume (cubic feet) I-IV 0 - 500 Not Required a Not Required Not Required e Not Required Not Required Not Required Not Required Not Required 501 - 2,500 Not Required a Yes i Not Required e Not Required Not Required 100 40 100,000 2,501 - 12,000 Public accessible Yes Not Required Not Required e Not Required Not Required 100 40 400,000 2,501 - 12,000 Nonpublic accessible (Option 1) Yes Not Required Not Required e Not Required Not Required 100 40 400,000 2,501 - 12,000 Nonpublic accessible (Option 2) Not Required a Yes Yes Yes j Yes j 100 30 f 200,000 12,001 - 20,000 Yes Not Required Yes Yes j Not Required 100 40 400,000 20,001 - 500,000 Yes Not Required Yes Yes j Not Required 100 40 400,000 Greater than 500,000 g Yes Not Required Yes Yes j Not Required 100 40 400,000 High hazard 0 - 500 Not Required a Not Required Not Required e Not Required Not Required 50 Not Required Not Required 501 - 2,500 Public accessible Yes Not Required Not Required e Not Required Not Required 50 30 75,000 501 - 2,500 Nonpublic accessible (Option 1) Yes Not Required Not Required e Not Required Not Required 50 30 75,000 501 - 2,500 Nonpublic accessible (Option 2) Not Required a Yes Yes Yes j Yes j 50 20 50,000 2,501 - 300,000 Yes Not Required Yes Yes j Not Required 50 30 75,000 300,001 - 500,000 g, h Yes Not Required Yes Yes j Not Required 50 30 75,000

For SI: 1 foot = 304.8 mm, 1 cubic foot = 0.02832 m 3 , 1 square foot = 0.0929 m 2 .

a. When sprinkler systems are required for reasons other than those in FC Chapter 32, the portion of the sprinkler system protecting the high-piled storage area shall be designed and installed in accordance with FC 3207 and 3208.

b. For aisles, see FC 3206.9.

c. Piles shall be separated by aisles complying with the requirements of FC 3206.9.

d. For storage in excess of the height indicated, special fire protection shall be provided in accordance with Note g when required by the commissioner. See also FC Chapters 51 and 57 for special limitations for aerosols and flammable and combustible liquids.

e. FC 503 shall apply for fire apparatus access.

f. For storage exceeding 30 feet in height, Option 1 shall be used.

g. Special fire protection provisions including fire protection of exposed steel columns; increased sprinkler density; additional in-rack sprinklers, without associated reductions in ceiling sprinkler density; or additional fire department hose connections shall be provided when required by the commissioner.

h. High-piled storage areas shall not exceed 500,000 square feet. A 2-hour fire wall constructed in accordance with the construction codes, including the Building Code shall be used to divide high-piled storage exceeding 500,000 square feet in area.

i. Not required when a fire extinguishing system is designed and installed to protect the high-piled storage area in accordance with FC 3207 and 3208.

j. Not required when storage areas are protected throughout by early suppression fast response (ESFR) sprinkler systems installed in accordance with NFPA 13, as modified by FC Appendix B.

3206.4 Sprinkler systems.

Sprinkler systems shall be provided in accordance with FC 3207, 3208 and 3209.

3206.5 Fire detection.

Where fire detection is required by FC Table 3206.2, an approved automatic fire detection system shall be installed throughout the high-piled storage area. The system shall be monitored and be in accordance with FC 907.

3206.6 Building access.

Where building access is required by FC Table 3206.2, fire apparatus access roads in accordance with FC 503 shall be provided within 150 feet (45 720 mm) of all portions of the exterior walls of buildings used for high-piled storage.

Exception: Where fire apparatus access roads cannot be installed because of topography, railways, waterways, non-negotiable grades or other similar conditions, the commissioner may require additional fire protection.

3206.6.1 Access doors.

Where building access is required by FC Table 3206.2, fire department access doors shall be provided in accordance with this section. Access doors shall be accessible without the use of a ladder.

3206.6.1.1 Number of doors required.

A minimum of one access door shall be provided in each 100 lineal feet (30 480 mm), or fraction thereof, of the exterior walls which face required fire apparatus access roads. The required access doors shall be distributed such that the lineal distance between adjacent access doors does not exceed 100 feet (30480 mm).

3206.6.1.2 Door size and type.

Access doors shall not be less than 3 feet (914 mm) in width and 6 feet 8 inches (2032 mm) in height. Roll-up doors shall not be used unless approved.

3206.6.1.3 Locking devices.

Only approved locking devices shall be used.

3206.7 Smoke and heat removal.

Where smoke and heat removal are required by FC Table 3206.2, smoke and heat vents shall be provided in accordance with the construction codes, including the Building Code. Where draft curtains are required by FC Table 3206.2, they shall be provided in accordance with the construction codes, including the Building Code.

3206.8 Fire department hose connections.

Where exit passageways are required by the construction codes, including the Building Code for egress, a Class I standpipe system shall be provided in accordance with the construction codes, including the Building Code.

3206.9 Aisles.

Aisles providing access to exits and fire department access doors shall be provided in high-piled storage areas exceeding 500 square feet (46 m 2 ), in accordance with FC 3206.9.1 through 3206.9.3. Aisles separating storage piles or racks shall comply with the requirements of NFPA 13, as modified by FC Appendix B. Aisles shall also comply with the requirements of the construction codes, including the Building Code.

Exception: Where aisles are precluded by rack storage systems, alternate methods of access and protection are allowed when approved.

3206.9.1 Width.

Aisle width shall be in accordance with FC 3206.9.1.1 and 3206.9.1.2.

Exceptions:

1. Aisles crossing rack structures or storage piles, which are used only for employee access between aisles shall be a minimum of 24 inches (610 mm) wide.

2. Aisles separating shelves classified as shelf storage shall be a minimum of 30 inches (762 mm) wide.

3206.9.1.1 Sprinklered buildings.

Aisles in buildings protected throughout by a sprinkler system shall be a minimum of 44 inches (1118 mm) wide. Aisles shall be a minimum of 96 inches (2438 mm) wide in high-piled storage areas that exceed 2,500 square feet (232 m 2 ) in area, and that are accessible to the public and designated to contain high-hazard commodities.

Exception: Aisles in high-piled storage areas exceeding 2,500 square feet (232 m 2 ) in area, that are accessible to the public and designated to contain high-hazard commodities, and that are protected throughout by a sprinkler system designed for multiple-row racks of high-hazard commodities, shall be a minimum of 44 inches (1118 mm) wide. Aisles shall be a minimum of 96 inches (2438 mm) wide in areas accessible to the public where mechanical stocking methods are used.

3206.9.1.2 Nonsprinklered buildings.

Aisles in buildings not protected throughout by a sprinkler system shall be a minimum of 96 inches (2438 mm) wide.

3206.9.2 Clear height.

The required aisle width shall extend from floor to ceiling. Rack structural supports and catwalks are allowed to cross aisles at a minimum height of 6 feet 8 inches (2032 mm) above the finished floor level, provided that such supports do not interfere with fire department hose stream trajectory.

3206.9.3 Dead ends.

Dead-end aisles shall be in accordance with the construction codes, including the Building Code.

3206.10 Portable fire extinguishers.

Portable fire extinguishers shall be provided in accordance with FC 906.

Section FC 3207. Solid-Piled and Shelf Storage

Open this section

3207.1 General.

Shelf storage and storage in solid piles, solid piles on pallets and bin box storage in bin boxes not exceeding 5 feet (1524 mm) in any dimension, shall be designed and maintained in accordance with FC 3206 and this section.

3207.2 Fire protection.

Where sprinkler systems are required for solid-piled and shelf storage pursuant to FC Table 3206.2, a sprinkler system shall be provided in any area containing such storage that is enclosed in 1-hour fire-rated walls in accordance with the Building Code, or, if such storage is not enclosed within such fire-rated walls, throughout the building. Openings in such walls shall be protected by opening protective assemblies having 1-hour fire protection ratings. The design and installation of the sprinkler system and other applicable fire protection shall be in accordance with this code, the construction codes, including the Building Code, and NFPA 13, as modified by FC Appendix B.

3207.2.1 Shelf storage.

Shelf storage greater than 12 feet (3658 mm) but less than 15 feet (4572 mm) in height shall be in accordance with the fire protection requirements set forth in NFPA 13, as modified by FC Appendix B. Shelf storage 15 feet (4572 mm) or more in height shall be protected in an approved manner with special fire protection, such as in-rack sprinklers.

3207.3 Pile dimension and height limitations.

Pile dimensions, the maximum permissible storage height and pile volume shall be in accordance with FC Table 3206.2.

3207.4 Array.

Where a sprinkler system design utilizes protection based on a closed array, array clearances shall be provided and maintained as specified by the standard used.

Section FC 3208. Rack Storage

Open this section

3208.1 General.

Rack storage shall be designed and maintained in accordance with FC 3206 and this section. Bin boxes exceeding 5 feet (1524 mm) in any dimension shall be regulated as rack storage.

3208.2 Fire protection.

Where a sprinkler system is required for rack storage pursuant to FC Table 3206.2, a sprinkler system shall be provided in any area containing such storage that is enclosed in 1-hour fire-rated walls in accordance with the Building Code, or, if such storage is not enclosed within such fire-rated walls, throughout the building. Openings in such walls shall be protected by opening protective assemblies having 1-hour fire protection ratings. The design and installation of the sprinkler system and other applicable fire protection shall be in accordance with this code, the construction codes, including the Building Code, and NFPA 13, as modified by FC Appendix B.

3208.2.1 Plastic pallets and shelves.

Storage on plastic pallets or plastic shelves shall be protected by approved specially-engineered fire protection systems, except that plastic pallets listed and labeled in accordance with UL 2335 or FM 4996 shall be treated as wood pallets for determining required sprinkler protection.

3208.2.2 Racks with solid shelving.

Racks with solid shelving having an area greater than 32 square feet (3 m 2 ), measured between approved flue spaces at all four edges of the shelf, shall be in accordance with this section.

Exceptions:

1. Racks with mesh, grated, slatted or similar shelves having uniform openings not more than 6 inches (152 mm) apart, comprising at least 50 percent of overall shelf area, and with approved flue spaces, are allowed to be treated as racks without solid shelves.

2. Racks used for the storage of combustible paper records, with solid shelving, shall be in accordance with NFPA 13, as modified by FC Appendix B.

3208.2.2.1 Fire protection.

Fire protection for racks with solid shelving shall be in accordance with NFPA 13, as modified by FC Appendix B.

FC Table 3208.3 Required Flue Spaces for Rack Storage

Rack Configuration Sprinkler Protection Sprinkler at the Ceiling with or Without Minimumin-Rack Sprinklers In-Rack Sprinklers at Every Tier Non- sprinklered 25 feet > 25 feet Any height Any height Storage Height Option 1 Option 2 Single-row rack Transverse flue space Size b 3 inches Not Applicable 3 inches Not Required Not Required Vertically aligned Not Required Not Applicable Yes Not Applicable Not Required Longitudinal flue space Not Required Not Applicable Not Required Not Required Not Required Double-row rack Transverse flue space Size b 6 inches a 3 inches 3 inches Not Required Not Required Vertically aligned Not Required Not Required Yes Not Applicable Not Required Longitudinal flue space Not Required 6 inches 6 inches Not Required Not Required Multi-row rack Transverse flue space Size b 6 inches Not Applicable 6 inches Not Required Not Required Vertically aligned Not Required Not Applicable Yes Not Applicable Not Required Longitudinal flue space Not Required Not Applicable Not Required Not Required Not Required

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

a. Three-inch transverse flue spaces shall be provided at least every 10 feet where ESFR sprinkler protection is provided.

b. Random variations are allowed, provided that the configuration does not obstruct water penetration.

3208.3 Flue spaces.

Flue spaces shall be provided in accordance with FC Table 3208.3. Required flue spaces shall be maintained. When the flue spaces are not being maintained, the department may require the installation of approved devices to protect the flue spaces by preventing the placement or storage of obstructing materials in such spaces. Such protective devices shall not be removed or modified without department approval.

3208.4 Column protection.

Steel building columns shall be protected in accordance with NFPA 13, as modified by FC Appendix B.

3208.5 Extra-high-rack storage systems.

Approval of the commissioner shall be obtained prior to installing extra-high-rack combustible storage.

3208.5.1 Fire protection.

Buildings with extra-high-rack combustible storage shall be protected with a specially engineered sprinkler system. Extra-high-rack combustible storage shall be provided with additional special fire protection, such as separation from other buildings and additional built-in fire protection features and fire department access, when required by the commissioner.

Section FC 3209. Automated Storage

Open this section

3209.1 General.

Automated storage shall be designed and maintained in accordance with this section.

3209.2 Sprinkler systems.

Where a sprinkler system is required by FC Table 3206.2, a sprinkler system shall be installed throughout the building. The design and installation of such system shall be in accordance with this code and the construction codes, including the Building Code.

3209.3 Carousel storage.

High-piled storage areas having greater than 500 square feet (46 m 2 ) of carousel storage shall be provided with automatic shutdown in accordance with one of the following:

1. An automatic smoke detection system installed in accordance with the construction codes, including the Building Code, with coverage extending 15 feet (4572 mm) in all directions beyond unenclosed carousel storage systems and which sounds a local alarm at the operator's station and stops the carousel storage system upon the activation of a single detector.

2. An automatic smoke detection system installed in accordance with the construction codes, including the Building Code and within enclosed carousel storage systems, that sounds a local alarm at the operator's station and stops the carousel storage system upon the activation of a single detector.

3. A single dead-man-type control switch that allows the operation of the carousel storage system only when the operator is present. The switch shall be in the same room as the carousel storage system and located to allow for observation of the carousel system.

3209.4 Automated rack storage.

High-piled storage areas with automated rack storage shall be provided with a manually activated emergency shutdown switch for use by firefighters and other emergency response personnel. The switch shall be clearly marked and shall be located at the fire command center. In buildings without a fire command center, such switch shall be located in a conspicuous, readily accessible location near the entrance to the building, occupancy or area containing the automated rack storage, or other approved location.

Section FC 3210. Record Storage

Open this section

3210.1 General.

Records storage facilities used for the rack or shelf storage of combustible paper records greater than 12 feet (3658 mm) in height shall be designed, installed, operated and maintained in accordance with FC 3206 and 3208 and NFPA 13, as modified by FC Appendix B. Palletized storage of records shall be designed, installed, operated and maintained in accordance with FC 3207.

Section FC 3301. General

Open this section

3301.1 Scope.

This chapter shall govern fire safety measures during the construction, alteration, or demolition of buildings, structures, premises and facilities.

3301.2 General.

Buildings, structures, premises and facilities undergoing construction, alteration or demolition shall comply with the fire safety measures set forth in this chapter, and shall additionally comply with the requirements of NFPA 241 as to measures not specifically addressed herein.

3301.3 Permits.

Permits shall be required as set forth in FC 105.6.

3301.4 Prohibitions.

It shall be unlawful at a construction site to store, handle or use portable fueled space heating devices or equipment.

Exception: Portable space heating devices may be used for construction-related curing and drying in accordance with FC 3303.

Section FC 3302. Definitions

Open this section

3302.1 Definitions.

The following term shall, for the purposes of this chapter and as used elsewhere in this code, have the meaning set forth in FC 202.

CONSTRUCTION SITE.

Section FC 3303. Portable Fueled Space Heaters

Open this section

3303.1 Design.

Portable fueled space heaters shall be designed, listed and labeled in accordance with the construction codes, including the Mechanical Code and the Fuel Gas Code, this code, and standards promulgated by the commissioner by rule, as applicable. Portable fueled space heaters shall be installed, operated and maintained in accordance with this chapter, the terms of the listing, and manufacturer's specifications.

3303.2 Portable oil-fueled heaters.

Portable oil-fueled space heaters may be stored, handled and used at construction sites for construction-related curing and drying purposes during the heating season beginning on October 15 and ending on May 30 of the following year, and at such other times of year as may be authorized by permit. Such heaters shall be stored, handled and used in accordance with this code and the rules.

3303.3 Portable gas-fueled heaters.

Portable gas-fueled space heaters utilizing liquefied petroleum gas (LPG), compressed natural gas (CNG) and piped natural gas may be stored, handled and used at construction sites for construction-related curing and drying purposes during the heating season beginning on October 15 and ending on May 30 of the following year, and at such other times of year as may be authorized by permit. Such heaters shall be stored, handled and used in accordance with this code and the rules.

3303.4 Refueling.

Refueling operations shall be conducted in accordance with FC 5705. Portable fueled space heaters shall be shut down and cool to the touch before refueling.

3303.5 Installation.

Clearance to combustibles from portable fueled space heaters shall be maintained in accordance with the manufacturer's specifications. When in operation, portable fueled space heaters shall be fixed in place and protected from overturning, movement or damage in accordance with the manufacturer's specifications.

3303.5.1 Protection of heating element.

The heating element or combustion chamber shall have a permanent device to prevent accidental contact by persons or material.

3303.6 Supervision.

The handling and use of portable fueled space heaters shall be under the personal supervision of a person holding a certificate of fitness. The storage of portable fueled space heaters, and the fuel therefore, shall be under the general supervision of a certificate of fitness holder.

Section FC 3304. Precautions Against Fire

Open this section

3304.1 Smoking prohibited.

Smoking is prohibited at all construction sites.

3304.1.1 Areas affected.

At construction sites required by the Building Code to be enclosed with a fence, including buildings under construction or demolition, smoking shall be prohibited within the area enclosed by such fence, including in construction trailers and other indoor or outdoor areas. At construction sites not required by the Building Code to be enclosed with a fence, including existing buildings undergoing interior alterations, smoking shall be prohibited in those areas of the building in which work is to be conducted under the work permit issued by the Department of Buildings.

3304.1.2 Signage.

"No Smoking" signs complying with FC 310 shall be conspicuously posted at construction sites at the following locations:

1. at construction sites required by the Building Code to be enclosed with a fence, on all sliding and swinging gate openings, and any other openings allowing for access to the site by persons or vehicles;

2. at the entrances to any building or structure under construction or demolition;

3. on each floor at stairway, elevator and hoistway access points of any building undergoing alteration, construction or demolition;

4. at any indoor or outdoor areas on the construction site at which persons congregate; and

5. at such other locations as are necessary to provide notice to a person entering upon or working at the site of the prohibition against smoking.

3304.2 Waste disposal.

Combustible waste, including rubbish and construction and demolition material, shall not be allowed to accumulate within buildings and shall be removed from a building at least once a day. Accumulations of combustible waste not stored in containers in accordance with FC 304.3 and in a manner that obstructs movement on the floor, or containing flammable or combustible liquid residues, shall be removed from a building at the end of each work shift. Combustible waste, including rubbish and construction and demolition material, shall be removed from the premises or stored in noncombustible containers.

3304.3 Open fires.

It shall be unlawful to ignite or maintain an open fire at a construction site, except for the use of coke-fueled salamanders in accordance with FC 307.1 and 307.6, and the rules.

3304.4 Spontaneous ignition.

Materials susceptible to spontaneous ignition, such as oily rags, shall be stored in a container listed for such use.

3304.5 Fire watch.

The commissioner may require, at a demolition site, and at other construction sites that are unusually hazardous in nature, that a fire watch be maintained by fire guards. The fire guards conducting such fire watch shall have the duties and responsibilities set forth in FC 901.7.2.1.

3304.6 Cutting and welding.

Operations involving the use of cutting and welding shall be performed in accordance with FC Chapter 35.

3304.7 Electrical.

Temporary wiring for electrical power and lighting installations at construction sites shall comply with the requirements of the Electrical Code.

3304.8 Fire-resistance-rated construction.

Fire walls, fire barriers, and spray-on fire protection of structural members required by the Building Code for the completed building, shall be given construction priority. Required fire doors, with automatic closing devices, shall be installed on openings as soon as practicable. Required fire walls, fire barriers and fire doors shall be left in place in buildings undergoing alteration or demolition until construction operations necessitate their removal.

Section FC 3305. Flammable and Combustible Liquids

Open this section

3305.1 Storage, handling and use of flammable and combustible liquids.

Storage, handling and use of flammable and combustible liquids shall be in accordance with FC 5706.2 and such other provisions of FC Chapter 57 as may be applicable to the specific construction site material or operation.

3305.2 Ventilation.

Adequate ventilation shall be provided for operations involving the application of materials containing flammable solvents.

3305.3 Housekeeping.

Flammable and combustible liquid storage areas shall be maintained clear of vegetation and combustible waste. Such storage areas shall not be used for the storage of combustible materials.

3305.4 Precautions against fire.

Sources of ignition and smoking shall be prohibited in flammable and combustible liquid storage areas. "No Smoking" signs in compliance with the requirements of FC 310 shall be conspicuously posted.

3305.5 Handling at point of final use.

Class I and II liquids shall be stored in approved safety containers.

3305.6 Leakage and spills.

Leaking containers shall be immediately repaired or taken out of service. Spills shall be cleaned up immediately and all liquid and waste material disposed of lawfully.

Section FC 3306. Flammable Gases and Oxygen

Open this section

3306.1 Flammable gases.

The storage, handling and use of flammable gases shall comply with the requirements of FC Chapters 35, 58, and 61, as applicable.

3306.1.1 Cleaning and purging of flammable gas piping systems.

The cleaning and purging of flammable gas piping systems, including the cleaning and purging of such systems prior to placing them in service or removing them from service, shall be conducted in accordance with NFPA 56.

Exceptions:

1. Compressed gas piping systems subject to the requirements of FC Chapter 53*, other than fuel gas piping systems.

2. Piping systems regulated by the Fuel Gas Code.

3. LPG systems subject to the requirements of FC Chapter 61*.

* Editor's note: "FC" prefix added at the discretion of the editor.

3306.1.1.1 Prohibition.

It shall be unlawful to use a flammable gas to remove debris from or otherwise clean piping open to the atmosphere.

3306.2 Oxygen.

The storage, handling and use of oxygen shall comply with the requirements of FC 3306.2.1 through 3306.2.3, and FC Chapters 35 and 53, as applicable.

3306.2.1 Portable liquid oxygen containers.

The storage, handling and use of portable liquid oxygen containers shall be in accordance with FC 3306.2.1.1 through 3306.2.1.9.

3306.2.1.1 Design and installation documents.

A sketch showing the following information shall be submitted to the department for approval in connection with an application for a permit for oxygen storage:

1. Number and size of containers.

2. Enclosure, manifold and service piping construction.

3. Location of risers and outlets.

4. Location of all equipment and devices including vaporizers, valves and safety relief devices.

3306.2.1.2 Indoor storage restrictions.

Not more than one liquid oxygen container having a maximum water capacity of 6.2 cubic feet (0.176 m 3 ) may be stored indoors. Such container shall be connected for use with a flammable gas. Storage in excess of one liquid oxygen container shall be located outdoors.

3306.2.1.3 Ventilation.

The room used for the storage, handling and use of a liquid oxygen container shall be equipped with ventilation direct to the outdoors, and shall not contain any combustible material or flammable gas.

3306.2.1.4 Manifolds and vaporizers.

Manifolds and vaporizers shall be constructed of materials suitable for oxygen service at a pressure of 250 psig (1724 kPa). Such manifolds and vaporizers shall have a minimum bursting pressure of 1,000 psig (6895 kPa) and shall be protected with safety relief devices which will relieve at or below 500 psig (3448 kPa).

3306.2.1.4.1 Test.

The assembled vaporizer and manifold shall be pressure tested at 500 psig (3448 kPa) with an oil-free and nonflammable material as the testing medium.

3306.2.1.5 Service piping from the oxygen manifold.

Service piping from the oxygen manifold shall be copper tubing, stainless steel, wrought iron or steel, and shall run vertically outdoors to the floor or floors being serviced, where outlets may be provided for hose connections to approved torches. The service piping shall be properly secured, protected from damage from mechanical injury and properly labeled. Any connection between service piping and the manifold shall be made using not more than 5 feet (1524 mm) of hose capable of withstanding pressure up to at least 1,000 psig (6895 kPa).

3306.2.1.5.1 Service pressure.

Service piping shall be suitable for 250 psig (1724 kPa) service unless an intervening pressure regulator is provided at the manifold, and shall withstand a test of two times the maximum operating pressure, using an oil-free and nonflammable material as the testing medium.

3306.2.1.6 Hose and connectors.

Hose and connectors capable of withstanding pressure up to at least 1,000 psig (6895 kPa) and of a design suitable for oxygen service at a pressure of 250 psig (1724 kPa) shall be used to connect the outlets on the service piping to the blowpipes. Hose shall be rejected for use if it shows excessive wear, loose connections, leaks or burns; hose subjected to a flash back in use shall be tested to twice the service pressure, but not less than 200 psig (1379 kPa), before being returned to service.

3306.2.1.7 Signs.

Signs shall be posted in the vicinity of liquid oxygen container storage and use, reading: DANGER – LIQUID OXYGEN – NO SMOKING – NO OPEN FLAMES.

3306.2.1.8 Operating instructions.

Legible operating instructions shall be posted near any liquid oxygen manifold.

3306.2.1.9 Affidavit.

An affidavit shall be provided by the installer and/or contractor to certify that the vaporizer, valves, piping, hose and safety devices are of an approved type, that they meet the specifications for bursting test and design service pressure, and that they have been satisfactorily tested in accordance with this section.

3306.2.2 Oxygen trailers.

The storage and use of oxygen trailers shall be in accordance with FC 3306.2.2.1 through 3306.2.2.5.

3306.2.2.1 Design, construction, testing and maintenance.

Oxygen trailer containers shall be designed, constructed, tested and maintained in accordance with the United States Department of Transportation specifications and regulations.

3306.2.2.2 Instructions.

Legible operating instructions shall be posted in the trailer and on or near any oxygen manifold used indoors.

3306.2.2.3 License plates.

Oxygen trailers shall at all times have affixed to them a motor vehicle license plate as issued in accordance with New York State or other applicable motor vehicle license plate laws, rules or regulations.

3306.2.2.4 Notification.

The owner or operator of an oxygen trailer shall notify the department, in writing, of the delivery of the trailer to a construction site, at least 48 hours in advance of such delivery. Such notification shall include:

1. Contractor's name, address and telephone number.

2. Location of the construction site.

3. Quantity and frequency of oxygen delivery to the construction site.

4. Expected duration of oxygen storage and use at the construction site.

3306.2.2.5 Oxygen trailers having a capacity exceeding 20,000 SCF (566 m3).

The distance between oxygen trailers having a total aggregate capacity exceeding 20,000 SCF (566 m 3 ) and exposures shall be in accordance with NFPA 55.

3306.2.3 Supervision.

The handling and use of portable liquid oxygen containers and oxygen trailers shall be under the personal supervision of a certificate of fitness holder. The storage of liquid oxygen containers and oxygen trailers shall be under the general supervision of a certificate of fitness holder.

3306.3 Discontinued torch operations.

When hot work equipment is not in use, including when torch operations are discontinued for the workday, the oxygen and flammable gas containers shall be removed from the work area and moved to an approved storage area or removed from the premises.

Exception: Brief interruptions in work of not more than 2 hours, including lunch breaks and coffee breaks.

3306.3.1 Torch operation container floor storage.

Oxygen and flammable gas containers used for torch operations may be stored on the floors on which the torch work is being conducted only in an unoccupied building and only in an approved storage area. Oxygen or flammable gas containers, other than those necessary for the day's torch operations, shall be considered as reserve storage, and shall not be stored on such floors.

3306.3.1.1 Storage location.

Oxygen and flammable gas storage areas on the floors on which the torch work is being conducted shall comply with the distance to exposure requirements of FC 5804.1.3.

3306.3.1.2 Maximum storage quantities.

The maximum quantity of acetylene containers stored on any floor shall not exceed 3,500 SCF (99.11 m 3 ).

3306.3.1.3 Storage cabinet.

Oxygen and flammable gas containers shall be located within a compressed gas storage cabinet designed and secured to prevent unauthorized entry. The storage cabinet shall be conspicuously marked with a hazard identification sign as set forth in FC 5003.5.

3306.4 Reserve oxygen and flammable gas containers.

The storage of reserve oxygen and flammable gas containers at a construction site shall comply with the requirements of FC 3306.4.1 through 3306.4.4, and FC 3306.5.

3306.4.1 Storage location.

Oxygen and flammable gas container storage areas shall comply with the distance to exposure requirements of FC 5804.2.1.

3306.4.2 Storage cabinet.

Oxygen and flammable gas containers shall be located within a compressed gas storage cabinet designed and secured to prevent unauthorized entry. The storage cabinet shall be conspicuously marked with a hazard identification sign as set forth in FC 5003.5.

3306.4.3 Indoor acetylene storage.

Indoor reserve storage of acetylene containers shall be allowed only when outdoor storage is unavailable on the premises, the building is unoccupied, the containers are stored on the ground floor of the building, and the total quantities stored do not exceed 3,500 SCF ( 99.11 m 3 ).

3306.4.4 Outdoor acetylene storage.

Outdoor reserve acetylene container storage areas shall not exceed 3,500 SCF ( 99.11 m 3 ). More than one outdoor storage area may be authorized on the premises provided the distance from each outdoor storage area to each exposure identified in FC Chapter 58 complies with the requirements of FC Chapter 58.

3306.5 Maximum aggregate indoor acetylene storage quantities.

The aggregate of the indoor storage of acetylene authorized by FC 3306.3.1.2 and 3306.4.3 shall not exceed 15,000 SCF (424.8 m 3 ).

Section FC 3307. Explosive Materials

Open this section

3307.1 Storage and handling.

Explosive materials shall be stored, handled and used in accordance with FC 3318 and FC Chapter 56.

3307.2 Blasting operations.

Blasting operations shall be conducted in accordance with FC Chapter 56.

3307.3 Demolition using explosives.

Fire hoses and nozzles for use by demolition personnel, connected to an approved water supply under pressure, shall be provided and maintained at the demolition site whenever explosives are used for demolition. Such fire hoses, nozzles and water supply shall be available prior to explosives arriving at the site. Such fire hoses and nozzles shall be capable of a continuous flow of 180 gallons (681 L) per minute with a minimum reach of 35 feet (10 668 mm) from the nozzle and be capable of being brought to bear anywhere on the construction site. Hose shall be pressure tested to withstand at least 600 pounds per square inch gauge (psig) (2413 kPa).

Section FC 3308. Construction Site Fire Safety Manager

Open this section

3308.1 Fire safety manager.

Where a site safety manager or site safety coordinator is required by the Building Code, the owner shall designate a person to be the fire safety manager for the construction site. Such person shall hold a certificate of fitness as a construction site fire safety manager. The fire safety manager may be the site safety manager or site safety coordinator required by the Building Code, except that a separate fire safety manager shall be designated for a building under construction when such building reaches a height of twenty stories or more than 250 feet (76 200 mm), has a lot coverage of 200,000 square feet (1860 m 2 ) or greater, or as otherwise prescribed by rule. For purposes of this section, below grade stories shall be used to determine number of stories and building height.

Exception: Construction sites at which an existing building is undergoing alteration, the alteration work is limited to the facade, and no hot work is being performed.

3308.1.1 Fire safety manager duties.

The fire safety manager shall be responsible for ensuring compliance with the requirements of this code, including this chapter, and the rules. The fire safety manager shall conduct an inspection of the construction site and all fire safety measures on at least a daily basis, and maintain a record of same in a bound log book or other approved system of recordkeeping. Where fire watch service is provided, the fire safety manager shall be responsible for the general supervision of the fire guards.

3308.2 Pre-fire plans.

The fire safety manager shall develop and maintain at the construction site an approved pre-fire plan, and make it available for examination by any representative of the department. The department shall be notified of any changes in site conditions materially affecting the procedures set forth in such plan.

3308.3 Training.

The fire safety manager shall ensure that construction site personnel are acquainted with the operation of portable fire extinguishers and other fire protection equipment on the construction site.

3308.4 Fire protection devices.

The fire safety manager shall ensure that all fire protection equipment and systems are readily available and periodically inspected and tested, and maintained in accordance with this code, the rules and the Building Code.

3308.5 Hot work operations.

The fire safety manager shall be responsible for supervising the issuance of authorizations for hot work operations in accordance with FC Chapter 35.

3308.6 Impairment of fire protection systems.

The fire safety manager or impairment coordinator shall comply with the requirements of FC 901 in the event of impairment of any fire protection system.

3308.7 Temporary covering of fire protection devices.

Coverings placed on or over fire protection devices to protect them from damage during construction processes shall comply with the requirements of FC Chapter 9 and shall be immediately removed upon the completion of the construction processes in the room or area in which the devices are installed.

Section FC 3309. Fire Alarm Reporting

Open this section

3309.1 Emergency telephone.

A telephone not requiring a coin to operate, or another approved, clearly identified means to notify the department, shall be provided on site in an approved location. The street address of the construction site and the emergency telephone number of the fire department shall be posted adjacent to the telephone or other approved device.

Section FC 3310. Access for Firefighting

Open this section

3310.1 Required access.

Approved vehicle access for fire apparatus shall be provided to all construction sites. Vehicle access shall be provided to within 100 feet (30 480 mm) of temporary or permanent fire department connections. Vehicle access shall be provided by either temporary or permanent roads, capable of supporting vehicle loading under all weather conditions. Vehicle access shall be maintained until permanent fire apparatus access roads are available.

3310.2 Key boxes.

Key boxes shall be provided as required by FC Chapter 5 and the Building Code.

Section FC 3311. Means of Egress and Elevators

Open this section

3311.1 Stairways.

Stairways at construction sites shall be provided, maintained, and made available for department use in accordance with the construction codes, including the Building Code. Stairways providing egress from the building or structure under construction or alteration, and other components of the means of egress, shall be given construction priority.

3311.2 Maintenance.

Required means of egress shall be maintained during construction, alteration and demolition in accordance with this code and the Building Code.

3311.3 Elevators.

Elevators at construction sites shall be provided, maintained, and made available for department use in accordance with the construction codes, including the Building Code.

Section FC 3312. Water Supply for Fire Protection

Open this section

3312.1 Water supply.

An approved water supply for fire protection, either temporary or permanent, shall be made available prior to hazardous materials or combustible material arriving at the site. Any water source intended for firefighting operations, including standpipe outlets, street hydrants and yard hydrants, shall not be used for construction, alteration or demolition purposes, unless approved.

Section FC 3313. Standpipes

Open this section

3313.1 Standpipe systems.

Standpipe systems for use at construction sites shall be provided, maintained, and made available for department use in accordance with this code, and the construction codes, including the Building Code.

3313.2 Demolition operations.

Where a building or structure with an existing standpipe system is being demolished, such system shall be maintained for the use of the department in accordance with the construction codes, including the Building Code.

Section FC 3314. Sprinkler System

Open this section

3314.1 Sprinkler systems.

Sprinkler systems for use at construction sites shall be provided, maintained, and made available for department use, in accordance with this code, and the construction codes, including the Building Code.

3314.2 Completion before occupancy.

In buildings or structures where a sprinkler system is required by this code or the construction codes, including the Building Code, it shall be unlawful to occupy any portion of a building or structure until the sprinkler system installation has been tested and approved.

3314.3 Operation of valves.

Sprinkler control valves shall be operated only by authorized personnel. Such operation shall be under the general supervision of the fire safety manager where one is required pursuant to FC 3308. When the sprinkler system valves are being regularly closed and opened to facilitate connection of newly completed or disconnected segments, the sprinkler control valves shall be inspected at the end of each work day to ascertain that the system is in good working order.

Section FC 3315. Portable Fire Extinguishers

Open this section

3315.1 Where required.

Buildings or structures under construction, alteration or demolition shall be provided with not less than one approved portable fire extinguisher in accordance with FC 906 and sized for not less than ordinary hazard as follows:

1. At each stairway on all floor levels where combustible materials are being stored or combustible waste is being generated.

2. At the entrance of each storage and construction shed.

3. Additional portable fire extinguishers shall be provided where flammable and combustible liquids are stored, handled and used.

4. Cranes fueled by liquid motor fuel or flammable gas shall be provided with a portable fire extinguisher with a minimum 10-B:C rating located either in the crane's cab or in its immediate vicinity.

Section FC 3316. Internal-Combustion-Powered Equipment

Open this section

3316.1 Conditions of use.

Internal-combustion-powered construction equipment shall be used in accordance with the following requirements:

1. Equipment shall be located so that exhausts do not discharge against combustible material.

2. Exhausts shall be piped to the outdoors.

3. Equipment shall not be refueled while in operation.

4. Fuel for equipment shall be stored in an approved area.

5. Fuel for equipment shall be handled and used in approved containers with a capacity not greater than 5 gallons (19 L).

Section FC 3317. Safeguarding Roofing Operations

Open this section

3317.1 General.

Roofing operations utilizing heat-producing systems or other ignition sources shall be performed by a competent person. Roofing operations involving hot work shall comply with the requirements of FC Chapters 35, 58, and 61, as applicable.

3317.2 Tar kettles.

Tar kettles shall be handled and used in accordance with FC 303.

3317.3 Portable fire extinguishers for roofing operations.

Portable fire extinguishers shall be provided in accordance with FC 906. There shall be not less than one multi-purpose portable fire extinguisher with a minimum 3-A 40-B:C rating on the roof being covered or repaired.

3317.4 Prohibited operations.

It shall be unlawful to install any roofing material using a torch on a roof of combustible construction, or otherwise engage in roofing operations on roofs of combustible construction using hot work equipment.

Section FC 3318. Powder-Actuated Tool Loads

Open this section

3318.1 Storage, handling and use.

Small arms ammunition shall be stored, handled and used for powder-actuated tool loads at a construction site in accordance with FC 5606.8.

3318.1.1 Supervision.

Powder-actuated tools shall be used only by a certificate of fitness holder. Powder-actuated tools shall be handled only by a certificate of fitness holder. Storage of powder-actual tools shall be under the general supervision of a certificate of fitness holder.

Section FC 3319. First Responder Box

Open this section

3319.1 First responder box.

An approved lock box shall be provided for first responder use.

5601.5.1.1

Such box shall contain all keys required to obtain access to the construction site and operate the hoist; the pre-fire plan; permits; logbooks; and such other documents required by this code or the rules to be maintained on the premises. Such box shall be in an approved location and shall be openable by use of a citywide standard key.

Section FC 3401. General

Open this section

3401.1 Scope.

This chapter shall govern the design, operation and maintenance of tire rebuilding plants, tire storage and tire byproduct facilities.

3401.2 Permits.

Permits shall be required as set forth in FC 105.6.

3401.3 General.

Tire rebuilding plants, tire storage and tire byproduct facilities shall be designed, operated and maintained in accordance with this chapter, NFPA 13, as modified by FC Appendix B, and if applicable, FC Chapter 32.

Section FC 3402. Definitions

Open this section

3402.1 Terms defined in FC Chapter 2.

Terms used in this chapter and defined in FC 202 shall have the meanings set forth therein.

Section FC 3403. Tire Rebuilding

Open this section

3403.1 Construction.

Tire rebuilding plants shall comply with the requirements of the construction codes, including the Building Code.

3403.2 Location.

Buffing operations shall be conducted in a room separated from the remainder of the building housing the tire rebuilding or tire recapping operations by a 1-hour fire barrier.

Exception: Buffing operations are not required to be separated where the following requirements are complied with:

1. Buffing operations are protected throughout by a continuous water-spray fire protection system directed at the point of cutting action.

2. Buffing machines are connected to particle-collecting systems providing a minimum air movement of 1,500 cubic feet per minute (cfm) (0.71 m 3 /s) in volume and 4,500 feet per minute (fpm) (23 m/s) in-line velocity.

3. The collecting system shall discharge the rubber particles to an approved outdoor noncombustible or noncombustible container, which is emptied at frequent intervals to prevent overflow.

3403.3 Cleaning.

The buffing area shall be cleaned and combustible waste regularly removed and disposed of to prevent the accumulation of rubber particles.

3403.4 Spray rooms and booths.

Spray rooms or spray booths wherein flammable or combustible solvents are applied shall comply with the requirements of FC Chapter 24.

Section FC 3404. Precautions Against Fire

Open this section

3404.1 Open fires and flames prohibited.

It shall be unlawful in a tire storage yard to ignite or maintain an open fire or open flame.

3404.2 Hot work prohibited.

It shall be unlawful in a tire storage yard to conduct hot work operations.

3404.3 Smoking prohibited.

It shall be unlawful in a tire storage yard to smoke.

3404.4 Power lines.

Tire storage piles shall not be located beneath electrical power lines having a voltage in excess of 750 volts or near lines supplying power to fire emergency systems where a fire in such storage piles would damage such lines.

3404.5 Reserved.

3404.6 Emergency telephone.

A telephone not requiring a coin to operate, or another approved, clearly identified means to notify the department, shall be provided at the facility in an approved location. A sign shall be conspicuously posted at or near the telephone indicating that all fires shall be immediately reported to the department, and setting forth the facility's address with cross-street reference and the fire department telephone number.

Section FC 3405. Outdoor Storage

Open this section

3405.1 Individual piles.

Tire storage shall be restricted to individual piles not exceeding 5,000 square feet (464.5 m 2 ) of continuous area. Piles shall not exceed 50,000 cubic feet (1416 m 3 ) in volume or 10 feet (3048 mm) in height.

3405.2 Separation of piles.

Individual tire storage piles shall be separated from other piles by a clear space of at least 40 feet (12 192 mm).

3405.3 Distance between piles of other stored products.

Tire storage piles shall be separated by a clear space of at least 40 feet (12 192 mm) from piles of other stored product.

3405.4 Distance from lot lines and buildings.

Tire storage piles shall be located at least 50 feet (15 240 mm) from lot lines and buildings unless the commissioner approves a lesser separation distance of tire storage piles in accordance with the criteria set forth in NFPA 13.

3405.5 Fire breaks.

Storage yards shall be maintained free from combustible grass and weeds for a distance of 40 feet (12 192 mm) from the stored tires; and for a distance of 100 feet (30480 mm) from the stored tires to brush and forested areas.

3405.6 Volume more than 150,000 cubic feet.

Where the bulk volume of stored material is more than 150,000 cubic feet (4248 m 3 ), fire breaks shall be provided around the perimeter of each group of storage piles in accordance with the following:

1. Individual storage piles shall be arranged so that there are not more than 16 individual storage piles per group.

2. Fire breaks shall at least be 75 feet (22 860 mm) wide.

3405.7 Location.

Outdoor tire storage shall not be located under bridges, elevated trestles, elevated roadways or elevated railroads.

Section FC 3406. Fire Department Access

Open this section

3406.1 Required access.

New and existing tire storage yards shall be provided with fire apparatus access roads in accordance with FC 503 and this section.

3406.2 Location.

Fire apparatus access roads shall be located within all pile clearances identified in FC 3405.4 and within all fire breaks required in FC 3405.5 and 3405.6. Access roadways shall be within 150 feet (45 720 mm) of any point in the storage yard where storage piles are located, at least 20 feet (6096 mm) from any storage pile.

Section FC 3407. Fencing

Open this section

3407.1 Where required.

Where the bulk volume of stored material is more than 20,000 cubic feet (566 m 3 ), a firmly anchored fence or other approved method of security that controls unauthorized access to the storage yard shall surround the storage yard.

3407.2 Construction.

The fence shall be constructed of approved materials and shall be at least 6 feet (1829 mm) high and provided with gates at least 20 feet (6096 mm) wide. Where gates are constructed, they shall comply with the vertical clearance requirements of FC 503.

3407.3 Security.

All gates to the storage yard shall be locked when the storage yard is not staffed.

Section FC 3408. Fire Protection

Open this section

3408.1 Water supply.

A public or private fire protection water supply shall be provided in accordance with FC 507. The water supply shall be arranged such that any part of the storage yard can be reached by using not more than 300 feet (91 m) of hose.

3408.2 Portable fire extinguishers.

Buildings or structures shall be provided with portable fire extinguishers in accordance with FC 906. Fuel-fired vehicles operating in the storage yard shall be equipped with a minimum 2-A:20-B:C rated portable fire extinguisher.

Section FC 3409. Indoor Storage Arrangement

Open this section

3409.1 Pile dimensions.

Where tires are stored on-tread, the dimension of the pile in the direction of the wheel hole shall not be more than 50 feet (15 240 mm). Tires stored adjacent to or along one wall shall not extend more than 25 feet (7620 mm) from that wall. Other piles shall not be more than 50 feet (15 240 mm) in width.

Section FC 3501. General

Open this section

3501.1 Scope.

This chapter shall govern welding, cutting and other torch and hot work operations and equipment.

3501.2 Permits.

Permits shall be required as set forth in FC 105.6.

3501.3 Approved locations.

Hot work shall be conducted only in the areas set forth in this section or approved by the commissioner.

3501.3.1 Authorized areas.

Hot work may be conducted in the following areas:

1. Areas designed for hot work operations.

2. Areas authorized for that purpose by the responsible person at the premises when precautions have been taken in compliance with the requirements of this chapter.

3501.3.2 Restricted areas.

Hot work shall not be conducted in the following areas unless approval has been obtained from the commissioner:

1. Areas where the sprinkler system is impaired.

2. Areas where there exists the potential of an explosive atmosphere, such as locations where flammable gases, liquids or vapors are present.

3. Areas with readily ignitable materials, such as storage of large quantities of bulk sulfur, baled paper, cotton, lint, dust or loose combustible materials.

4. On board marine vessels or watercraft at dock under construction or repair.

3501.4 Containers.

Compressed gas containers shall be designed, installed, operated and maintained in accordance with this chapter and FC Chapter 53.

3501.5 Design and installation of oxygen-fuel gas systems.

An oxygen-fuel gas system shall be designed and installed in accordance with NFPA 51.

3501.5.1 Oxygen at construction sites.

The storage and use of oxygen at a construction site shall additionally comply with the requirements of FC Chapter 33.

3501.6 Torches.

Torches and tips that utilize a flammable gas for hot work operations shall be listed.

3501.7 Certificate of approval.

Devices used to increase the pressure of piped natural gas in accordance with FC 3509.8 shall be of a type for which a certificate of approval has been issued.

Section FC 3502. Definitions

Open this section

3502.1 Definitions.

The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.

COMBUSTIBLE GAS DETECTOR.

HOT TAPPING.

HOT WORK.

HOT WORK AREA.

HOT WORK EQUIPMENT.

HOT WORK PROGRAM.

HOT WORK PROGRAM AUTHORIZATIONS.

RESPONSIBLE PERSON.

TORCH-APPLIED ROOF SYSTEM.

Section FC 3503. General Requirements

Open this section

3503.1 General.

Hot work operations, including temporary and fixed hot work areas, shall be conducted in accordance with this chapter.

3503.1.1 Torch operations using LPG.

The use of LPG for torch operations shall additionally comply with the requirements of FC Chapter 61.

3503.1.2 Torch operations using CNG.

The use of CNG for torch operations shall additionally comply with the requirements of FC Chapter 58.

3503.2 Hot work program.

Whenever hot work is performed in any building or structure, on a building roof or on a building setback, the owner shall ensure that such work is performed in accordance with this chapter and shall designate a responsible person to ensure compliance.

3503.2.1 Hot work program responsible person.

The responsible person shall ensure that a permit has been obtained from the department when one is required, and ensure that the hot work is performed in compliance with the terms and conditions of the permit. The responsible person shall inspect the hot work site prior to issuing a hot work program authorization and periodically monitor the work as it is being performed to ensure there are no fire safety hazards.

3503.2.2 Responsible person supervision.

Hot work operations shall be conducted under the general supervision of the responsible person.

3503.3 Hot work program authorization.

A hot work program authorization bearing the signature of the responsible person shall be obtained for any project conducted on a premises involving hot work operations by the person in charge of such hot work operations. Hot work authorizations, issued by the responsible person, shall be available for inspection by any representative of the department during the performance of the work and for 48 hours after the work is complete.

3503.4 Qualifications of operators.

An authorization for hot work operations shall not be issued unless the individuals conducting such operations are capable of performing such operations safely. Demonstration of a working knowledge of the provisions of this chapter shall constitute acceptable evidence of compliance with this requirement.

3503.4.1 Torch operations.

Any torch operation, including torch operations using a flammable gas, with or without oxygen, and any torch operation for torch-applied roofing systems, shall be personally conducted by a certificate of fitness holder.

Exceptions:

1. Torch operations using oxygen and piped natural gas for manufacturing jewelry or in a dental laboratory may be conducted under the personal supervision of a certificate of fitness holder, who shall be responsible to regulate the pressure and flow of oxygen and natural gas to each torch.

2. Torch operation fueled by a LPG container with a capacity of 16.4 ounces (0.465 kg) or less, except at a construction site.

3. Arc welding authorized by the Department of Buildings.

3503.4.2 Use of portable fire extinguishers.

All persons conducting hot work operations shall be trained in the use of portable fire extinguishers, and shall be capable of extinguishing fires when they are limited in size and spread such that they can readily be extinguished using a portable fire extinguisher.

3503.5 Records.

The responsible person for the hot work area shall maintain "pre-hot work check" reports in accordance with FC 3504.3.1.

3503.6 Signage.

Visible hazard identification signs shall be provided where required by FC Chapter 50. Where the hot work area is accessible to persons other than the operator of the hot work equipment, signs shall be posted in a conspicuous location to warn others before they enter the hot work area. Such signs shall read as follows:

CAUTION HOT WORK IN PROGRESS STAY CLEAR.