NYC Administrative Code Section FC 3006 Fire Protection

3006.1 Required protection.

Class A and B furnaces that contain, or are utilized for the processing of, combustible materials shall be protected throughout by a fire extinguishing system complying with the requirements of FC Chapter 9.

3006.2 Fixed fire extinguishing systems.

A fixed fire extinguishing system shall be provided for Class C or D furnaces to protect against such hazards as overheating, spillage of molten salts or metals, quench tanks, ignition of hydraulic oil and escape of fuel.

3006.3 Portable fire extinguishers.

Portable fire extinguishers complying with the requirements of FC 906 shall be provided not closer than 15 feet (4572 mm) or a maximum of 50 feet (15240 mm) from each furnace or in accordance with NFPA 10.