NYC Administrative Code Title 29, Chapter 2 New York City Fire Code, part 3 of 15
Section FC 306 to Section FC 407: 27 sections.
Section FC 306. Motion Picture Film and Screens
306.1 Motion picture projection rooms.
Electric arc, xenon or other light source projection equipment which develops hazardous gases, dust or radiation and the projection of ribbon-type cellulose nitrate film, regardless of the light source used in projection, shall be operated within a motion picture projection room complying with the requirements of Chapter 4 of the Building Code.
306.2 Cellulose nitrate film storage, handling and use.
Cellulose nitrate film shall be stored, handled and used in accordance with NFPA 40 and subject to the approval of the commissioner.
306.2.1 Supervision.
The handling and use of cellulose nitrate film, including motion picture projection, shall be under the personal supervision of a person holding a certificate of fitness. The storage of cellulose nitrate film shall be under the general supervision of a person holding a certificate of fitness.
306.3 Motion picture screens.
The screens upon which motion pictures are projected shall be of noncombustible construction as set forth in Chapter 6 of the Building Code, or shall meet the flame propagation performance criteria of NFPA 701, or shall comply with the requirements for a Class A interior finish in accordance with Chapter 8 of the Building Code. Screens installed prior to the effective date of this code shall comply with the applicable Building Code requirements. The construction supporting such motion picture screens shall be of noncombustible construction as set forth in Chapter 6 of the Building Code, and shall comply with the load bearing requirements of the Building Code.
Section FC 307. Open Fires
307.1 General.
Kindling, building, maintaining or using an open fire is prohibited.
Exceptions:
1. Portable outdoor barbecues as authorized by FC 307.5.
2. Outdoor noncommercial barbecue fires in equipment provided by and located in city parks where such open fires are allowed by the Department of Parks and Recreation.
3. In connection with training of fire brigades or similar purposes by persons or entities where such training is required by law, rule or regulation.
4. Approved open fires used for special effects in connection with television, motion picture, theatrical and other entertainment productions.
5. Coke-fueled salamanders at a construction site in accordance with FC 307.6 and the rules.
6. Lighting of charcoal for hookah use on the premises of non-tobacco hookah establishments in accordance with FC 310 and the rules.
7. Residential fire pits as authorized by FC 307.7.
307.2 Authorization.
Open fires allowed pursuant to FC 307.1 may only be kindled, built, maintained or used with the prior written authorization of the agencies with regulatory jurisdiction, property owner and other required approvals, and only when such open fires are maintained in compliance with all conditions of such authorization or approval. The commissioner may prohibit the kindling, building, maintaining or use of open fire or order the extinguishment of any open fire allowed by this section, upon a determination that such open fire will create an undue hazard because of conditions in the surrounding environment.
307.3 Reserved.
307.4 Attendance.
Open fires shall be constantly attended until the fire is extinguished. A minimum of one portable fire extinguisher complying with the requirements of FC 906 with a minimum 4-A rating or other approved on-site fire-extinguishing equipment, such as a garden hose connected to an approved water supply, shall be available for immediate use.
307.5 Portable outdoor barbecues.
Charcoal, electric, and LPG and piped natural gas-fueled portable outdoor barbecues may be operated and maintained in compliance with the requirements of this section.
307.5.1 General.
Portable outdoor barbecues burning charcoal, powered by electricity, or fueled by LPG containers or piped natural gas may be stored and used on any residential premises in compliance with the requirements of this section and the rules. Portable outdoor barbecues burning charcoal, powered by electricity, or fueled by piped natural gas may be stored and used on any other premises in compliance with the requirements of this section and the rules, except as may be restricted by the Zoning Resolution or the Department by rule or order. Stationary outdoor grills and other outdoor cooking equipment shall be installed in accordance with the Building and Mechanical Codes, and operated and maintained in accordance with this section.
307.5.2 Grate area.
The total grate area of a portable outdoor barbecue shall not exceed 10 square feet (0.929 m 2 ).
307.5.3 Clearance distances.
Portable outdoor barbecues shall not be stored or used within 10 feet (3048 mm) of any combustible waste, combustible material, or any combustible building surface, including combustible roofs and decks. To the maximum extent feasible, windows, doors and other building openings within 10 feet (3048 mm) of a barbecue in use shall be kept closed. An entrance door shall be closed immediately after entering or exiting the building while the barbecue is in use.
307.5.4 Fire extinguishing equipment.
A garden-type hose attached to a water supply, or a minimum of one portable fire extinguisher complying with the requirements of FC 906 with a minimum 4-A rating, shall be provided for any portable outdoor barbecue, and shall be readily accessible whenever the portable outdoor barbecue is in use. A portable fire extinguisher complying with the requirements of FC 906 and with a Class K rating shall be provided for any portable outdoor barbecue used for commercial cooking purposes, and shall be readily accessible whenever such barbecue is in use.
307.5.5 Natural gas piping.
The natural gas piping supplying portable outdoor barbecues designed to use piped natural gas shall be designed and installed in accordance with the Fuel Gas Code.
307.5.6 LPG containers.
Portable outdoor barbecues fueled by LPG containers shall additionally comply with the requirements of FC 307.5.6.1 and 307.5.6.2.
307.5.6.1 Group R-2 occupancies.
Only portable outdoor barbecues designed for use with LPG containers with a capacity of 16.4 ounces (0.465 kg) may be stored or used on the premises of a Group R-2 occupancy. Indoor storage of 16.4-ounce (0.465 kg) LPG containers for this or any other purpose is limited to a maximum of four such containers per dwelling unit.
307.5.6.2 Group R-3 occupancies.
Portable outdoor barbecues designed for use with LPG containers with a capacity of 20 pounds (9.08 kg) or LPG containers with a capacity of 16.4 ounces (0.465 kg) may be stored or used on the premises of a Group R-3 occupancy. Twenty-pound LPG containers shall not be stored or used indoors, or on any rooftop or balcony. A maximum of two 20-pound LPG containers may be used to fuel a portable outdoor barbecue. Indoor storage of 16.4-ounce (0.465 kg) LPG containers for this or any other purpose is limited to a maximum of four such containers per dwelling unit.
307.5.7 Cleaning.
Portable outdoor barbecues shall be periodically cleaned by removing grease or fat accumulations from grills and in trays below the grill.
307.6 Coke-fueled salamanders.
Coke and coke-fueled salamanders may be stored, handled and used for construction-related curing and drying at construction sites in accordance with this section and the rules.
307.6.1 Supervision.
The handling and use of coke and coke-fueled salamanders at construction sites, including the extinguishment of the coke, shall be under the personal supervision of a certificate of fitness holder. A certificate of fitness holder may not supervise the handling or use of more than fifty coke-fueled salamanders, or the handling or use of coke or coke-fueled salamanders that are located on more than one floor. The storage of coke and coke-fueled salamanders at construction sites shall be under the general supervision of a certificate of fitness holder.
307.7 Residential Fire Pits.
Residential fire pits may be stored and used to maintain an open fire in compliance with the requirements of this section and the rules on the premises of a detached Group R-3 occupancy in any R1, R2, or R3 residential zoning district.
307.7.1 Safe operations.
Residential fire pits must be operated in accordance with manufacturer instructions for such residential fire pit, and shall be constantly attended while a fire is lit.
307.7.2 Clearance distances.
Residential fire pits shall not be stored or used within 10 feet (3048 mm) of any combustible waste, combustible material, or any combustible building surface. To the extent feasible, windows, doors and other building openings within 25 feet (7620 mm) of a residential fire pit in use shall be kept closed. An entrance door shall be closed immediately after entering or exiting the building while a residential fire pit is in use.
307.7.3 Design and operation.
The department may establish by rule standards for the design, installation, operation and maintenance for residential fire pits, provided that such rules are consistent with provisions established by this section.
307.7.4 Hazardous environmental conditions.
The department may prohibit use of residential fire pits in any location upon determination that such activity creates an undue fire hazard because of conditions in the surrounding environment, including during wind conditions or red flag weather.
Section FC 308. Open Flames
308.1 General.
This section governs the use of open flames in all buildings, structures and premises.
308.2 Use of open flames.
Open flames may be lighted, maintained and used only as allowed in this section. Stationary appliances, including cooking, space heating and water heating appliances, are not open-flame devices subject to this section and shall be designed and installed in accordance with the construction codes. Portable fueled devices, equipment and systems, including LPG-fueled cookstoves and torches, shall be operated in accordance with FC 313.
308.3 Prohibitions.
It shall be unlawful to:
1. cause or allow an open flame to be lit or maintained in any room or other area of a building, structure, premises, marine vessel, watercraft or other place in which a hazardous material is stored, handled or used, or where conditions exist that could cause ignition of flammable vapors or combustible material.
2. use or maintain in any area in which smoking is prohibited, as set forth in FC 310 or elsewhere in this code, a lighted match or other flame which has not been approved for use by the department in such areas.
3. place or discard, or cause to be placed or discarded, an open flame, lighted match or other flaming substance or object on any surface or article where it can cause the ignition of combustible material or combustible waste, or otherwise cause an unwanted fire.
4. store or use candles, incense or similar open-flame producing items in Group R-1 college and university dormitories.
5. use or maintain an open flame or open-flame device in or on a building, structure or premises as a signal or marker, except that fusees may be used on roadways to alert motorists to stopped vehicles or other emergency condition.
6. light and release or allow to become airborne any lantern, balloon, or other item or craft containing or fueled by a flame or other heat-producing material, except for balloon operations authorized by FC Chapter 20 and other operations authorized by the department.
308.4 General safety precautions.
Open flames and open-flame devices are ignition sources that can readily ignite combustible materials. When their use is allowed by this section, all safety precautions appropriate to the circumstances shall be observed, including the following requirements:
1. Candles and other unenclosed open flames shall be constantly attended while lit.
2. Open flames and open-flame devices, including lighted candles, shall be protected from accidental contact by appropriate placement, and secured from tipping or other movement by a suitable candleholder or other device.
3. Open flames and open-flame devices, including lighted candles, except open-flame devices designed to be surface mounted, shall be placed on a noncombustible surface.
4. Open flames and open-flame devices, including lighted candles, shall be kept at least 3 feet (914 mm) from any combustible material or combustible waste.
5. Open flames and open-flame devices, including lighted candles, shall not be placed or kept in any corridor, stairwell or exit.
6. Open flame food warming devices shall be placed on non-combustible surfaces and constantly attended while lit. LPG-fueled open flame food warming devices shall not be used for food warming except where authorized by the department by issuance of an open flame permit.
308.5 Use of open flames in assembly occupancies and places of public gathering.
Open flames may be lighted, maintained and used in Group A occupancies and public gathering places only as allowed in FC 308.5.1 through 308.5.4 and the rules.
308.5.1 Prohibitions.
It shall be unlawful to light, maintain or use an open flame in a Group A occupancy or other building or structure used for a public gathering.
Exceptions:
1. Open flames are allowed in the following locations when used for the following purposes, provided that safety precautions are taken to prevent ignition of combustible material and otherwise ensure the safety of occupants in accordance with FC 308.4, other applicable provisions of this code and the rules, and the terms and conditions of the permit or other approval:
1.1. Use of candles and open-flame devices in accordance with FC 308.5.2.
1.2. The preparation of flaming foods or beverages in accordance with FC 308.5.3.
1.3. Special effects in connection with a theatrical performance or other event for which a special effect permit has been granted in accordance with FC 308.5.4.
1.4. Open-flame devices for food warming in accordance with the rules.
1.5. Open-flame devices for demonstrations in exhibitions or trade shows in accordance with the rules.
1.6. Where necessary for ceremonial or religious purposes.
2. Natural gas light fixtures installed in compliance with the requirements of the Building Code and the Plumbing Code, and approved precautions are taken to prevent ignition of combustible materials.
308.5.2 Open-flame decorative devices.
Open-flame decorative devices, including wall-mounted candles, torch sconces, insect-repellant candles in glass jars or metal cans, tabletop candles and oil lamps, free standing torch holders and candelabras, shall comply with the following requirements:
1. Use of Class I and Class II liquids, including alcohol, and LPG in open flame decorative devices, is prohibited.
2. Liquid- or solid-fueled lighting devices containing more than 8 ounces (237 ml) of fuel must self-extinguish and not leak fuel at a rate of more than 0.25 teaspoon per minute (1.26 ml per minute) if tipped over.
3. The device or holder shall be constructed to prevent the spillage of liquid fuel or wax at the rate of more than 0.25 teaspoon per minute (1.26 ml per minute) when the device or holder is not in an upright position.
4. The device or holder shall be designed so that it will return to the upright position after being tilted to an angle of 45 degrees from vertical.
Exception: Devices that self-extinguish if tipped over and do not spill fuel or wax at the rate of more than 0.25 teaspoon per minute (1.26 ml per minute) if tipped over.
5. The flame shall be enclosed except where openings on the side are not more than 0.375 inch (9.5 mm) diameter or where openings are on the top and the distance to the top is such that a piece of tissue paper placed on the top will not ignite in 10 seconds.
6. Enclosures shall be made of noncombustible materials and securely attached to the open-flame device.
Exception: An enclosure is not required to be attached to any open-flame decorative device that will self-extinguish if the device is tipped over.
7. Fuel canisters shall be safely sealed for storage.
8. Storage and handling of combustible liquids shall be in accordance with FC Chapter 57.
9. Shades, where used, shall be made of noncombustible materials and securely attached to the open-flame device holder or enclosure.
10. Candelabras with flame-lighted candles shall be securely fastened in place to prevent overturning, and shall be located away from occupants using the area and away from possible contact with drapes, curtains or other combustibles.
11. Open-flame devices shall not be placed in any aisle, standing area, corridor or component of the means of egress.
308.5.3 Flaming food and beverage preparation.
The preparation and serving of flaming foods and beverages in Group A occupancies and public gathering places shall be in accordance with FC 308.5.3.1 through 308.5.3.4.
308.5.3.1 Dispensing of liquid.
Alcohol or other flammable or combustible liquid used in the preparation of flaming food and beverages shall be stored in a container with a capacity not exceeding 1 quart (946.5 ml) and dispensed from such container using a controlled-pouring device limiting the flow to a 1-ounce (29.6 ml) serving. The container shall have a secure cap or lid or one designed to prevent spillage when not in use.
308.5.3.2 Ignition and serving of flaming food.
Flaming food shall be ignited and served as follows:
1. Flaming food shall be ignited on a noncombustible surface or, if the surface is combustible, it shall be protected by a noncombustible mat that covers the entire top surface of the table.
2. The flames generated for flaming food shall not exceed 6 inches (152.4 mm) above the serving dish. Any pouring, ladling or spooning of liquids is restricted to a maximum height of 8 inches (203 mm) above the receiving receptacle.
3. Flaming food shall not be ignited on or above the table at which the patrons to whom the food is to be served are seated. Flaming food shall be ignited on a nearby serving table or cart at least 3 feet (914 mm) from patrons, or lighted in the kitchen and transported to the table on a serving cart.
4. The flames generated by flaming food shall be extinguished before the food is placed on the table before the patron.
5. The person preparing the flaming foods shall have a wet cloth towel immediately available for use in smothering the flames in the event of an emergency. In addition to portable fire extinguishers required by FC 906, a portable fire extinguisher with a minimum 2-A:10B rating shall be kept at or near the location where flaming food or beverage is ignited.
308.5.3.3 Ignition and serving of flaming beverages.
Ignition and serving of flaming beverages at patron tables shall be conducted in the same manner as flaming food, as set forth in FC 308.5.3.2. Flaming beverages shall not be ignited and served on bars and counters at which the public is seated unless a safe perimeter of at least 3 feet (914 mm) from any patrons can be established and maintained while the beverage is lighted and flaming.
308.5.3.4 Staff training.
Any staff serving flaming food or beverages shall be trained and knowledgeable in the safe ignition and handling of such food or beverages.
308.5.4 Special effects.
Use of open flames as a special effect is allowed in conjunction with theatrical performances and in other places of assembly or public gathering only when authorized by the department. When approved, open flames shall be used in accordance with FC Chapter 56 and NFPA 160.
308.6 Alcohol-fueled decorative open-flame devices.
Alcohol-fueled decorative open-flame devices shall be designed, installed, operated and maintained in accordance with FC 308.6.1 through 308.6.5.
308.6.1. Prohibitions.
It shall be unlawful to install or use a stationary or portable alcohol-fueled open-flame device in Group A, E and I occupancies, and public gathering spaces. It shall be unlawful to use portable alcohol-fueled open-flame devices in Group R occupancies.
308.6.2 Design.
Stationary and portable alcohol-fueled open-flame devices installed or used in New York City shall be designed in accordance with the following requirements:
1. The device shall be constructed of metal, fire-resistant glass and/or other noncombustible material of sufficient thickness as to be capable of withstanding the heat generated by the open flames.
2. The device shall be constructed to provide protection from the flames at the maximum flame height the device is capable of generating.
3. The open flame shall be generated in a controlled manner through the use of a wick, valve or other approved method. A device that generates a flame in an uncontrolled manner is an open fire prohibited by FC 307.1.
4. The device shall have a means of manually extinguishing the flame, either by a shutoff valve, a means of manually closing the device that cuts off the supply of oxygen to the flame thereby extinguishing the flame, or other approved method. The method by which the flame is extinguished shall not require use of a battery-powered device.
5. The device shall use solid fuel or be fueled through a pump or other means of liquid fuel transfer from a container to the device without spillage. Only the type of fuel specified for the device shall be used.
6. The fuel capacity of the device shall not exceed 64 fluid ounces (1888 ml) or the equivalent in solid fuel, except as authorized by the department.
7. The device shall be listed by a nationally recognized testing laboratory.
308.6.3 Installation.
All stationary and portable alcohol-fueled open-flame devices shall be installed or placed in accordance with listing requirements, manufacturer's instructions and the following fire safety requirements:
1. The device shall be installed or placed at a location protected from movement and air drafts, and at least 3 feet (914 mm) from combustible surfaces and materials, including upholstered furniture, draperies, and wood surfaces.
2. The device shall be installed or placed in a room of sufficient size and ventilation to avoid dangerous accumulations of carbon monoxide or carbon dioxide, taking into consideration the capacity of the device's alcohol reservoir and rate of burning. In no event shall a device be installed or used in a room smaller than that recommended by the manufacturer's instructions.
3. Devices designed for stationary installation shall be securely affixed to the floor, wall or ceiling or in furniture to prevent movement. No devices shall be installed in or on a wall or ceiling, or in a wooden cabinet or other furniture of combustible construction, unless it is of a type for which a certificate of approval has been issued by the department.
308.6.4 Safety precautions.
Alcohol-fueled decorative devices shall be used in accordance with manufacturer's instructions and the following safety precautions:
1. A lighted device shall not be left unattended. Flames shall be extinguished when the person responsible for attending to the operation of the device leaves the room or goes to sleep. The shutoff switch or device closure shall be used to ensure that the alcohol flames, which are not always readily visible, are extinguished.
2. A device shall not be fueled or moved when it is lighted or when it is not lighted but still hot.
3. A smoke alarm and a carbon monoxide alarm, or detectors, shall be installed in any room in which an alcohol-fueled decorative device is installed or used.
4. A portable fire extinguisher for household use shall be kept readily available in any room in which an alcohol-fueled decorative open-flame device is installed or used.
308.6.5 Storage of fuel.
Alcohol stored for use in alcohol-fueled decorative open-flame devices shall be stored in a tightly sealed container in a cool location, away from heat and ignition sources. Such fuel storage is limited to 1 gallon (3.8 L).
Section FC 309. Powered Industrial Trucks, Equipment and Mobility Devices
309.1 General.
Powered industrial trucks, powered industrial equipment and powered mobility devices shall be designed, operated and maintained in accordance with this section.
309.2 Powered industrial trucks.
Powered industrial trucks fueled by flammable or combustible liquids or flammable gases shall be designed and operated in accordance with FC 309.2.1 through 309.2.5.
309.2.1 Hazardous locations.
Powered industrial trucks that are operated in areas designated as hazardous (classified) locations in accordance with the Electrical Code shall be listed and labeled for use in such environments in accordance with NFPA 505. Entry by equipment that is not listed or approved as suitable for the specific classified location may be allowed for the purpose of maintenance or other necessary business operation where the owner has established an entry authorization procedure and has verified that the entry area is clear of hazardous environment and will remain so for the duration of the entry.
309.2.2 Powered industrial trucks using flammable gas fuel.
Powered industrial trucks that use LPG or other flammable gas as fuel shall be limited to one fuel container with a capacity not greater than 40 pounds (18.16 kg) or 340 SCF (9.63 m 3 ) of flammable gas, whichever is less, except that powered industrial trucks used to resurface ice that are designed to operate with more than one such container shall be limited to operating with two such containers. Liquefied gas containers installed in a horizontal position shall be of such a design that the pressure relief valve will discharge vapor properly. Powered industrial trucks that use LPG or other flammable gas as fuel shall not be parked near open flames or other heat or ignition sources, or near open pits, underground entrances, elevator shafts, or similar areas. Such powered industrial trucks shall be stored and used in locations with adequate ventilation. It shall be unlawful to store or use such powered industrial trucks in a basement, cellar or other areas below grade.
(Am. L.L. 2021/165, 12/24/2021, eff. 12/24/2021)
309.2.3 Fueling.
Powered industrial trucks using a flammable or combustible liquid or flammable gas fuel shall be fueled in compliance with the requirements of FC 309.2.3.1 through 309.2.3.4.
309.2.3.1 Location.
All fueling, including container replacement, shall be conducted outdoors or in areas specifically approved for that purpose, and in accordance with this code and the rules.
309.2.3.2 Liquid fuels.
Fixed liquid fuel-dispensing equipment for powered industrial trucks shall be designed, installed, operated and maintained in accordance with FC Chapter 23. Emergency refueling of powered industrial trucks using portable containers shall be in accordance with FC Chapters 23 and 57. The engine of a powered industrial truck shall be shut off and the operator shall not be on or inside the truck during refueling.
309.2.3.3 Container replacement.
Outdoor connecting and disconnecting of fuel gas containers shall be conducted away from open pits, underground entrances, or other areas below grade, and away from all open flames or other heat or ignition sources. Fueling of powered industrial trucks shall be in accordance with FC Chapter 61, if LPG-powered, and FC Chapters 23 and 58, if CNG-powered, and the rules
309.2.3.4 Hydrogen fueling.
Filling of containers for powered industrial trucks with hydrogen, including metal hydride hydrogen storage system containers, shall be conducted in accordance with FC 2309.
309.2.4 Repairs.
Repairs to fuel systems or electrical systems, and repairs utilizing open flame or welding, shall be done in an indoor or outdoor location approved for that purpose.
309.2.5 Storage.
When not in use, powered industrial trucks shall be stored in approved designated storage areas. Each storage area shall be provided with a portable fire extinguisher complying with the requirements of FC 906 having a minimum 4-A:20-B:C rating.
309.3 Battery-powered industrial trucks, industrial equipment and mobility devices.
Powered industrial trucks, powered industrial equipment and powered mobility devices using a storage battery shall be designed in accordance with FC 309.3.1, and shall be charged and stored in a storage, charging and/or repair facility, including any storage or charging area in Group B, R-2 or M occupancy, that is designed, installed, operated and maintained in accordance with the construction codes, Electrical Code and FC 309.3.2 through 309.3.4.
Exceptions.
1. Storage and charging in a Group R-3 occupancy or in a dwelling unit in a Group R-2 occupancy of not more than 5 powered mobility devices using a storage battery, provided that such devices are for personal use.
2. Charging of a single powered mobility device by and in the presence of its owner or user.
309.3.1 Battery chargers.
Powered industrial trucks, powered industrial equipment and powered mobility devices using a storage battery shall be charged in accordance with the manufacturer's instructions and the applicable listing standard using the original equipment manufacturer-supplied charging equipment, or other charging equipment suitable for the purpose, that is designed in accordance with applicable federal, New York State and/or New York City laws, rules or regulations, and listed:
1. pursuant to UL Standard 1564 or other approved listing of an approved testing laboratory; or
2. for use with the truck, item of equipment or device in accordance with UL Standard 2272, UL Standard 2849 or other approved listing of an approved testing laboratory.
309.3.2 Battery inspection.
A storage battery shall be inspected for cracks, punctures, leaking contents or other damage prior to charging or re-charging if the battery was dropped, involved in a collision or otherwise subjected to a potential mechanism of damage. Damaged batteries shall not be re-used. Damaged batteries and batteries at the end of their useable life shall be promptly removed from the premises and lawfully disposed of.
309.3.3 Battery charging areas.
Powered industrial trucks, powered industrial equipment and powered mobility devices using a storage battery shall be charged in a suitable indoor room or area or outdoor location that:
1. has sufficient natural or mechanical ventilation in accordance with the Mechanical Code to prevent the accumulation of any flammable or other gases that may be discharged during normal charging operations;
2. has an adequate electrical supply and a sufficient number of electrical receptacles to allow the charging equipment for each truck, item of equipment or device to be directly connected to a receptacle. Extension cords and power strips shall not be used. A minimum of 3 feet (914 mm) shall be maintained between each truck, item of equipment or device during charging operations;
3. has an adequate electrical supply and a sufficient number of electrical receptacles to allow the charging equipment for battery packs and other removable storage batteries to be directly connected to a receptacle. Extension cords and power strips shall not be used. Battery packs and other removable storage batteries shall not be stacked or charged in an enclosed cabinet (unless the cabinet is specially designed and approved by the department for such purpose). Except as otherwise approved by the department, a minimum distance of 2 feet (610 mm) shall be maintained between each battery pack or other removable storage battery during charging operations, provided that the aggregate energy capacity of battery packs or other removable storage batteries that can be charged in a single fire area does not exceed 20 kWh. A minimum distance of 3 feet (914 mm) shall be maintained if the aggregate energy capacity exceeds 20 kWh. The aggregate energy capacity of battery packs or other removable batteries that can be charged in a single fire area shall not exceed 50 kWh.
4. is not used for the storage of combustible materials, combustible waste or hazardous materials;
5. is separated by a fire barrier with a minimum one-hour fire-resistance rating from areas in which repairs or other servicing is conducted on the storage battery or other electrical components of the truck, item of equipment or mobility device;
6. where six or more trucks, items of industrial equipment or devices using a storage battery are being charged at a single indoor location, is dedicated for battery charging and secured from unauthorized entry; separated by a fire barrier which encloses the entire space with a minimum one-hour fire-resistance rating; and protected by a fire sprinkler system and one or more smoke detectors or smoke alarms. If the building or occupancy is equipped with a fire alarm system, the smoke detector shall be connected to such system. If the ambient temperature of the room during battery charging operations exceeds the limitations set forth in the manufacturer's instructions or the equipment listing, the room or area shall be temperature controlled to prevent over-heating or other unsafe battery condition; and
7. is provided with a portable fire extinguisher complying with the requirements of FC 906 having a minimum 4-A:20-B:C rating.
309.3.4 Storage areas.
Indoor storage rooms or areas or outdoor enclosures used for the storage, but not charging or repair, of powered industrial trucks, powered industrial equipment and powered mobility devices using a storage battery shall comply with the requirements of FC 309.3.3(4), (5) and (7).
309.3.5 Second-use batteries.
It shall be unlawful to:
1. assemble or recondition a lithium-ion battery using cells removed from used storage batteries; or
2. sell or offer for sale a lithium-ion battery that uses cells removed from used storage batteries.
(L.L. 2023/042, 3/20/2023, eff. 3/20/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/042.
309.4 Enforcement of certification requirements.
The department is hereby authorized to enforce the provisions of section 20-610 of the administrative code, which, in part, prohibits the distribution, sale, lease, or rental of powered bicycles and powered mobility devices, as defined in that section, unless the storage batteries and electrical systems of such devices have been certified by an accredited testing laboratory, as defined in the rules of the Department of Consumer and Worker Protection.
(L.L. 2024/050, 3/29/2024, eff. 9/25/2024)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2024/050.
Section FC 310. Smoking
310.1 General.
Smoking, including the carrying of a lighted pipe, cigar, cigarette or any other type of smoking paraphernalia or material, shall be conducted in accordance with this section.
310.2 Prohibitions.
It shall be unlawful to:
1. smoke in any area in which smoking is prohibited, as set forth in this section or elsewhere in this code.
2. place or discard, or cause to be placed or discarded, any lighted pipe, cigar, cigarette or other type of smoking paraphernalia or material where it can cause the ignition of combustible material or combustible waste, or otherwise cause an unwanted fire.
3. smoke in any building, structure, premises or part thereof where flammable or combustible materials or explosives are manufactured, stored, handled, used or transported.
4. smoke in the following occupancies and spaces:
4.1. Cellars and basements, except in R-3 occupancies.
4.2. Group A occupancies and public gathering places, except for smoking non-tobacco smoking products in a non-tobacco hookah establishment in accordance with FC 310.7.
4.3. Group M occupancies, except for smoking non-tobacco smoking products in a non-tobacco hookah establishment in accordance with FC 310.7.
4.4. Hospitals, nursing homes, rehabilitation facilities and similar medical facilities housing the ill, aged and infirm.
4.5. On any bulkhead, dock, drydock, shipyard, pier, wharf, warehouse or shed on the waterfront.
4.6. On board any ship, barge, ferry, lighter, carfloat, scow, and all other similar floating watercraft or equipment whether berthed or moored at a dock, wharf, pier, or to a marine vessel made fast thereto or in a shipyard.
4.7. Factories as set forth in Section 283 of the New York State Labor Law.
4.8. Lumber yard or woodworking facility as set forth in FC 2803.5.3.
4.9. As otherwise prohibited by this code or the rules.
(Am. L.L. 2017/187, 10/16/2017, eff. 4/14/2018)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2017/187.
310.3 "No Smoking" signs.
When smoking is prohibited by this code or the rules, durable "No Smoking" signs shall be conspicuously posted at approved locations throughout the facility or other location in accordance with FC 310, or as otherwise specifically provided in this code. The content, lettering, size and color of required "No Smoking" signs shall be in accordance with the rules, or as otherwise approved by the commissioner.
310.3.1 Location.
"No Smoking" signs shall be conspicuously posted at all entrances to facilities in which smoking has been entirely prohibited and any area therein where hazardous materials are stored, handled or used. Facilities or areas within such facilities in which smoking is allowed in designated areas shall have signs indicating that smoking is allowed in designated areas only.
310.4 Removal of signs prohibited.
A posted "No Smoking" sign shall not be removed, obscured or rendered illegible.
310.5 Compliance with "No Smoking" signs.
It shall be unlawful to smoke, or discard or deposit any burning substance, in any building, structure or premises or part thereof, in which "No Smoking" signs are posted pursuant to this code or the rules or otherwise for fire safety purposes.
310.6 Ash trays.
Where smoking is allowed, suitable noncombustible ash trays or receptacles shall be provided at appropriate locations.
310.7 Non-tobacco hookah establishments.
Smoking of non-tobacco smoking products is allowed in non-tobacco hookah establishments lawfully operating pursuant to Chapter 5 of Title 17 of the Administrative Code (as those terms are defined therein), provided that such establishments are designed, installed, operated and maintained in accordance with the following requirements:
(L.L. 2017/187, 10/16/2017, eff. 4/14/2018)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2017/187.
310.7.1. Permits.
Permits shall be required as set forth in FC 105.6.
(L.L. 2017/187, 10/16/2017, eff. 4/14/2018)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2017/187.
310.7.2 Supervision.
The storage of coal and other solid or liquid flammable and combustible materials in non-tobacco hookah establishments shall be under the general supervision of a person holding a certificate of fitness. The handling and use of charcoal and other solid or liquid flammable and combustible materials in non-tobacco hookah establishments shall be under the personal supervision of a person holding a certificate of fitness.
(L.L. 2017/187, 10/16/2017, eff. 4/14/2018)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2017/187.
310.7.3 Use of charcoal or other material for smoking paraphernalia.
Where smoking paraphernalia requires the use of lighted charcoal or any other solid or liquid flammable or combustible material, such material shall be stored, handled and used in accordance with this section and the rules.
(L.L. 2017/187, 10/16/2017, eff. 4/14/2018)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2017/187.
310.7.3.1 Smoking paraphernalia.
Smoking paraphernalia shall comply with such safety measures as may be prescribed in the rules to minimize the risk of fire associated with the use of such paraphernalia.
(L.L. 2017/187, 10/16/2017, eff. 4/14/2018)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2017/187.
310.7.3.2 Storage of charcoal.
Charcoal shall be stored in accordance with FC 315.7. Other flammable or combustible materials shall be stored in compliance with the requirements of this code and the rules.
(L.L. 2017/187, 10/16/2017, eff. 4/14/2018)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2017/187.
310.7.3.3 Preparation, handling and disposal of charcoal and other materials.
Charcoal shall be prepared for use in an approved indoor or outdoor area, on a noncombustible surface, using an approved device heated by an electric element or other approved device or method, stored in an oven or other approved noncombustible vessel, and vented by means of a hood, or in a room with an approved ventilation system, or other approved method, as set forth in the rules. Lighted charcoal and ashes, cinders and other fire debris, and other combustible waste shall be handled and disposed of in such manner as may be prescribed in the rules to minimize the risk of fire.
(L.L. 2017/187, 10/16/2017, eff. 4/14/2018)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2017/187.
310.7.3.4 Portable fire extinguishers.
In addition to complying with the requirements of FC 906, a portable fire extinguisher with at least a 2-A:10-B:C rating shall be provided and maintained in a non-tobacco hookah establishment in the charcoal preparation area and in each area in which non-tobacco smoking products are smoked.
(L.L. 2017/187, 10/16/2017, eff. 4/14/2018)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2017/187.
310.7.3.5 Decorations.
Decorations in non-tobacco hookah establishments shall be flame-resistant in accordance with FC 805 and the rules.
(L.L. 2017/187, 10/16/2017, eff. 4/14/2018)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2017/187.
310.8 Hazardous environmental conditions.
The commissioner may prohibit lighted matches, cigarettes, cigars or other burning substances in any location upon a determination that such activity creates an undue fire hazard because of conditions in the surrounding environment.
Section FC 311. Vacant and Temporarily Unoccupied Premises
311.1 Vacant buildings.
Any vacant building, structure or premises, or part thereof, shall be deemed to constitute a temporarily unoccupied building and shall be safeguarded and maintained in compliance with the requirements of this section, unless such building, structure or premises has been deemed unsafe pursuant to Article 216 of Title 28 of the Administrative Code, in which case it shall be safeguarded and maintained in compliance with the requirements of the Department of Buildings and/or the Department of Housing, Preservation and Development, as applicable.
311.2 Temporarily unoccupied buildings.
Temporarily unoccupied buildings, structures, premises or parts thereof, including tenant spaces, shall be secured and protected in accordance with this section.
311.2.1 Security.
Exterior openings and interior openings accessible to unauthorized persons, including tenants, shall be locked or otherwise protected to prevent entry by unauthorized persons.
311.2.2 Fire protection.
Fire alarm, sprinkler and standpipe systems shall be maintained in an operable condition at all times, except as authorized by the commissioner.
311.2.3 Fire separation.
Fire-resistance-rated partitions, fire barriers, and fire walls, including those separating temporarily unoccupied tenant spaces from the remainder of the building shall be maintained. Openings, joints, and penetrations in fire-resistance-rated assemblies shall be protected in accordance with Chapter 7 of the Building Code.
311.3 Removal of combustible waste.
The owner of any building, structure or premises, or part thereof, that is deemed unsafe, and any temporarily unoccupied building, structure or premises, or part thereof, shall remove therefrom and prevent accumulations of rubbish and other combustible waste by regular cleaning of the premises.
Exception: Temporarily unoccupied buildings, structures, premises or parts thereof undergoing construction or repair in accordance with the Building Code, where rubbish and other combustible waste is controlled and removed in accordance with FC 304.
311.4 Removal of hazardous materials.
The owner of any vacant building, structure or premises, or part thereof, that contains hazardous materials and that is deemed unsafe pursuant to Article 216 of Title 28 of the Administrative Code shall comply forthwith with the facility closure requirements of FC 5001.6. The owner of a temporarily unoccupied building, structure or premises, or part thereof, that contains hazardous materials regulated by FC Chapter 50 shall comply with the facility closure requirements of FC 5001.6. Vacant and temporarily unoccupied buildings, structures or premises, and all parts thereof, shall thereafter be maintained free of hazardous materials, including hazardous waste material, except as approved by the commissioner.
311.5 Covered malls.
Unoccupied tenant spaces in covered malls shall be:
1. kept free from the storage of any combustible materials.
2. kept separate from other tenant spaces and areas of the mall by maintaining any fire separation requirement of the Building Code during the period of time that the space remains unoccupied or under reconstruction.
3. periodically inspected on at least a weekly basis to ensure that the space is being maintained in accordance with this section. Doors to spaces shall be secured from entry by keeping all doors locked at all times when the space is unoccupied.
4. kept free from rubbish and other combustible waste.
Section FC 312. Vehicle Impact Protection
312.1 General.
Vehicle impact protection required by this code shall be provided by posts that comply with the requirements of FC 312.2 or FC 312.3, and FC 312.4.
312.2 Posts.
Posts used to provide vehicle impact protection shall comply with the following requirements:
1. Constructed of steel not less than 4 inches (102 mm) in diameter and concrete filled.
2. Spaced not more than 4 feet (1219 mm) between posts on center.
3. Set not less than 3 feet (914 mm) deep in a concrete footing of not less than a 15-inch (381-mm) diameter.
4. Set with the top of the posts not less than 3 feet (914 mm) above grade.
5. Located not less than 3 feet (914 mm) from the protected object.
312.3 Other barriers.
Barriers meant to resist, deflect or visually deter vehicular impact, other than posts in accordance with FC 312.2, shall be designed and installed in an approved manner commensurate with anticipated impact scenarios.
312.4 Fire apparatus access.
Posts and other barriers that may obstruct or impede fire apparatus access shall be removable by the department in an approved manner.
Section FC 313. Portable Fueled Equipment
313.1 Scope.
The storage, handling and use of portable fueled equipment shall be governed by this section and the rules.
313.2 General.
Portable fueled equipment shall be stored, handled and used in accordance with this section.
313.3 Prohibitions.
It shall be unlawful to:
1. Store, handle or use indoors portable fueled equipment, including lawn-care equipment, snow blowers, portable generators, kerosene and other portable space heaters, and any portable fueled device, equipment or system that generates a flame, other than one installed in accordance with the construction codes. The owner of a building, structure or premises shall not provide, or cause to be provided, any such equipment, including equipment designed for space heating.
Exceptions:
1. Indoor storage of lawn-care equipment, power washers, snow blowers, portable generators and other portable fueled equipment designed for outdoor use in a garage or garage space separated from dwelling spaces or other occupancies in accordance with the Building Code, or in a building classified as a Group U occupancy; or in another approved storage area in a building. This exception shall not apply to portable space heaters.
2. The indoor storage, handling and use of portable fueled equipment where authorized by this code, including portable fueled equipment allowed by this section, open-flame devices allowed by FC 308, displays allowed by FC 314, and construction equipment allowed by FC Chapter 33, and portable fueled equipment allowed for demonstrations at exhibitions and trade shows by the rules.
3. The storage of portable fueled equipment for sale or distribution in a mercantile or storage occupancy.
4. The storage, handling and use of portable fueled equipment in a business, factory or mercantile occupancy engaged in the business of manufacturing or repairing of such equipment, provided that portable space heaters are operated solely in connection with such manufacturing or repair, and are not used for space heating purposes.
2. Store, handle or use for space heating, other than storage for sale, any portable fueled equipment that utilizes a flammable liquid as a fuel, or, except as authorized by FC 313.5, that utilizes a combustible liquid as a fuel. Any such portable fueled equipment that shows evidence of having been used shall be deemed to be or have been in use.
3. Use any portable fueled equipment that utilizes waste oil as a fuel. Any such portable fueled equipment that shows evidence of having been used shall be deemed to be or have been in use.
4. Remove paint in or on buildings, structures or premises with a torch or any other flame-generating device. Paint removal may be conducted using heat-producing devices other than portable fueled equipment. The person using such heat-producing device to remove the paint shall remain at the location where the heating operation was conducted to maintain a fire watch for not less than 1 hour after using such device.
313.4 Confiscation and removal.
The commissioner may confiscate or order the removal of portable fueled equipment from indoor or outdoor locations where the storage, handling or use of such equipment is determined by the commissioner to be hazardous.
313.5 Portable space heaters.
Portable fueled equipment used for space heating shall additionally be stored, handled and used in accordance with FC 313.5.1 and 313.5.2.
313.5.1 Listing and labeling of space heaters.
Portable space heaters and other portable fueled equipment used for space heating shall be listed and labeled.
313.5.2 Authorized uses.
Portable space heaters may be used for space heating as set forth in FC 313.5.2.1 through 313.5.2.6.
313.5.2.1 Portable natural gas heaters.
Portable space heaters fueled by piped natural gas may be stored, handled and used for outdoor use when designed, installed, operated and maintained in accordance with this code, including FC 313.6, the rules and the construction codes, including the Building Code.
313.5.2.2 Construction sites.
Portable space heaters may be stored, handled and used at construction sites in accordance with FC Chapter 33 and the rules.
313.5.2.3 Reserved.
313.5.2.4 Local emergency.
In the event of failure during severe cold weather of a central heating unit in any building or structure other than a private dwelling, multiple dwelling or Group A occupancy, portable space heaters approved for such indoor use may be used for a period not to exceed 2 weeks when such use has been approved.
313.5.2.5 Public emergencies.
In the event of a public emergency which disrupts, interferes with or impairs the operation or use of equipment, supplies or utilities normally utilized for heating, use of portable space heaters for indoor or outdoor use may be authorized by the commissioner upon a declaration of emergency by the mayor.
313.5.2.6 Supervision.
The handling and use of portable space heaters shall be under the personal supervision of a certificate of fitness holder or a plumber. The storage of portable space heaters, and the fuel therefor, shall be under the general supervision of a certificate of fitness holder or a plumber.
Exception: Group R-3 occupancies.
313.6 Portable natural gas heaters.
Portable space heaters fueled by piped natural gas shall be designed, operated and maintained in accordance with FC 313.6.1 through 313.6.5.
313.6.1 Clearance to buildings.
Heaters shall be located outdoors and at least 5 feet (1524 mm) from any building or structure.
313.6.2 Clearance to combustible materials.
Heaters shall not be located beneath, or closer than 5 feet (1524 mm) to combustible decorations and combustible overhangs, awnings, sun control devices or similar combustible attachments to buildings or structures.
313.6.3 Proximity to exits.
Heaters shall not be located within 5 feet (1524 mm) of exits or exit discharges.
313.6.4 Tip-over switch.
Heaters shall be equipped with a tilt or tip-over switch that automatically shuts off the flow of gas if the appliance is tilted more than 15 degrees (0.26 rad) from the vertical.
313.6.5 Guard against contact.
The heating element or combustion chamber of heaters shall be permanently protected so as to prevent accidental contact by persons or material.
313.7 Torches.
Where allowed, indoor use of torches shall be in accordance with FC Chapters 35, 58 and 61 and the rules. Indoor use of LPG-fueled torches in residential occupancies for soldering, food browning and other household uses, shall be limited to torches with an LPG container capacity of 16.4 ounces in accordance with FC Chapter 61 and the rules.
Section FC 314. Indoor Displays
314.1 General.
Indoor displays in any occupancy shall be designed and installed in accordance with FC 314.2 through 314.4.
314.2 Fixtures and displays.
Fixtures and displays of goods for sale to the public shall be arranged so as to maintain free, immediate and unobstructed access to exits as required by FC Chapter 10 and the construction codes, including the Building Code.
314.3 Highly combustible goods.
It shall be unlawful to display highly combustible goods, including flammable or combustible liquids, liquefied flammable gases, oxidizing materials, pyroxylin plastics and agricultural goods, in main exit access aisles, corridors, common areas of covered malls, or within 5 feet (1524 mm) of entrances to exits and exterior exit doors.
314.4 Vehicles and watercraft.
Fueled and electric vehicles (including motor vehicles, motorcycles and mopeds) and watercraft that are displayed indoors shall comply with the following requirements:
1. Vehicle and watercraft engines shall not be operated at any time when the display is open to the public. Liquid-fueled vehicle and watercraft engine batteries shall be disconnected or the engine otherwise disabled from starting by installation of an ignition lock, "kill switch" (relay) or other approved means. Battery or other electrical connections that are disconnected shall be adequately taped to prevent arcing. For electric and gaseous-fueled vehicles:
1.1. Battery power necessary to preserve vehicle safety features shall be maintained.
1.2. Appropriate safety measures shall be implemented to prevent the engine from being started and/or the vehicle from moving or other approved means, including securing the engine start key or fob and preventing remote engine start.
2. Fuel in fuel tanks shall not exceed one-eighth tank or 2.5 gallons (9.5 L) (whichever is less). Gaseous-fueled vehicles or watercraft shall contain no more fuel than the energy equivalent of 2.5 gallons (9.5 L) of gasoline.
3. Fuel tanks and fill openings shall be closed and secured with a locking gas cap.
4. Fueling or defueling shall not be conducted indoors.
5. No repairs or other work shall be conducted on a motor vehicle or watercraft in the display area.
6. Where indoor display of motor vehicles and watercraft is in Group A occupancies and other public gathering places, aisles with an unobstructed minimum width of 3 feet (914 mm) shall be maintained.
7. Such other requirements as the department may promulgate by rule.
314.5 Required clearance from fire safety systems.
Sprinklers and fire alarm systems shall not be obstructed by indoor displays.
314.5.1 Sprinkler systems.
A sprinkler system shall be installed in or under covered kiosks, displays, booths, or concession stands that exceed 4 feet (1219 mm) in width. The clearance between any sprinkler head deflector installed above the top of the kiosks, displays, booths, or concession stands shall not be less than 18 inches (457 mm).
Exception: Open-grid and drop-out ceilings complying with the requirements of NFPA 13, as modified by FC Appendix B, may be installed beneath sprinklers.
314.5.2 Fire alarm systems.
Sufficient clearance shall be provided between kiosks, displays, booths, or concession stands and fire alarm and carbon monoxide systems equipment and devices including detectors and strobes, so as not to interfere with their operation.
Section FC 315. Combustible Materials Storage and Other Storage Hazards
315.1 General.
Storage of materials shall be in accordance with this section.
Exception: Storage of materials during construction and demolition operations shall comply with the requirements of FC Chapter 33.
315.2 Storage in buildings.
Storage of materials in buildings shall be orderly and stacked materials shall be stable. Storage of combustible materials shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur.
315.2.1 Ceiling clearance.
Storage shall be maintained 2 feet (610 mm) or more below the ceiling in areas of buildings not protected by a sprinkler system, or a minimum of 18 inches (457 mm) below sprinkler head deflectors in areas protected by a sprinkler system, provided, however, that storage of noncombustible materials to the ceiling may be authorized by the department when such storage is within 30 inches (762 mm) of a fire partition.
315.2.2 Means of egress.
Materials shall not be stored in a manner that obstructs egress from any building, structure or premises.
315.2.3 Equipment rooms.
Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms.
315.2.4 Attic, under-floor and concealed spaces.
Attic, under-floor and concealed spaces used for storage of combustible materials shall be protected on the storage side as required for 1-hour fire-resistance-rated construction. Openings shall be protected by assemblies that are self-closing and are of noncombustible construction or solid wood core not less than 1.75 inches (44.5 mm) in thickness. Storage shall not be placed on exposed joists.
Exceptions:
1. Areas protected throughout by sprinkler systems.
2. Group R-3 and Group U occupancies.
3. Groups S-1 and S-2 occupancies.
315.3 Outdoor storage.
Outdoor storage of combustible materials in quantities in excess of 32 cubic feet (0.91 m 3 ) shall comply with FC 315.3.1 through 315.3.6.
315.3.1 Property line.
Except as otherwise provided in FC 315.3.5, outdoor storage of combustible materials shall not be located within 10 feet (3048 mm) of a property line.
315.3.2 Adjoining properties.
Except as otherwise provided in FC 315.3.5, outdoor storage of combustible materials shall not be located within 50 feet (15 240 mm) of the nearest wall of a building occupied as a Group A occupancy, Group E educational occupancy, Group I-2 occupancy, or any building, structure or premises used for a public gathering.
315.3.3 Building walls, openings and overhead projections.
Except as otherwise provided in FC 315.3.5, outdoor storage of combustible materials shall not be located:
1. Within 10 feet (3048 mm) of any building wall that is constructed of a combustible material;
2. Within 10 feet (3048 mm) of any building opening, regardless of the wall construction; and
3. Under building eaves, canopies, awnings and other overhangs.
315.3.4 Height.
Outdoor storage shall not exceed 20 feet (6096 mm) in height or such lower maximum height allowed by the Building Code or Zoning Resolution.
315.3.5 Reduced separation distance.
The separation distances set forth in FC 315 may be reduced when the combustible materials are:
1. Stored in approved cabinets or containers as set forth in FC 315.7.2.2, or other approved cabinet or container suitable for the type or quantity of stored combustible material;
2. Where appropriate to the type of stored combustible material, enclosed by a solid fence of an approved noncombustible material and an approved height. The combustible materials shall not be piled higher than 2 feet (610 mm) below the top of the fence; and/or
3. One or more other approved fire protection measures are provided.
315.3.6 Portable fire extinguishers.
At least one portable fire extinguisher with a rating of at least 4-A shall be provided for every 2,500 square feet (232.3 m 2 ) of storage area, or portion thereof, or in lieu thereof, a hose of at least 1 inch (25 mm) in diameter, equipped with a nozzle of at least 1/2 inch (12.7 mm) in diameter, sufficient in length to reach all parts of the enclosure, and connected to an adequate water supply may be provided.
315.4 Space underneath grandstands and bleachers.
Except where enclosed in not less than 1-hour fire-resistance-rated construction in accordance with the Building Code, spaces underneath grandstand and bleacher seating shall not be occupied or utilized for purposes other than means of egress.
315.5 Storage underneath high-voltage transmission lines.
It shall be unlawful to store hazardous materials or combustible materials outdoors within the utility easement underneath high-voltage transmission lines.
315.6 Storage in plenums.
It shall be unlawful to use plenums for storage of combustible or other material, including equipment and cabling that has been taken out of service and abandoned, unless such equipment and cables have been tagged for future use in accordance with Electrical Code. The accessible portion of such abandoned equipment and cables shall be removed.
315.7 Storage of solid fuel.
Storage of wood, charcoal or other combustible material for use as solid fuel, including for use in commercial cooking appliances, fireplaces or solid fuel-burning equipment approved by the Department of Buildings, and in non-tobacco hookah establishments, shall be in accordance with FC 315.7.1 through 315.7.3, except that storage of solid fuel in Group R-2 occupancies shall be in accordance with FC 315.7.4.
Exceptions:
1. Storage for sale of solid fuel in a mercantile establishment.
2. Group R-3 occupancies.
315.7.1 Supply for immediate use.
Not more than a one-day supply of solid fuel may be kept in the same room as the solid fuel-burning equipment or in the room with the fuel loading or clean-out doors or other opening. Unless the solid fuel-burning equipment is designed for internal storage of solid fuel, the solid fuel stored in such room shall not be located:
1. Within 3 feet (914 mm) of the solid-fuel burning equipment or any other heating or cooking appliance;
2. Within 6 feet (1829 mm) of any solid fuel loading opening or door of the solid fuel-burning equipment; or
3. Above any cooking or heating equipment, flue or vent.
315.7.2 Additional solid fuel storage.
Solid fuel in excess of a one-day supply shall be stored indoors and/or outdoors in accordance with FC 315.7.2.1 through 315.7.2.2.
315.7.2.1 Indoor.
Solid fuel may be stored indoors in:
1. A room dedicated to the storage of not more than 150 cubic feet (4.3 m 3 ) of solid fuel, provided that such storage room is protected by a sprinkler system and enclosed by a minimum of 1-hour fire barriers and horizontal assemblies (walls, floor and ceiling) constructed in accordance with the Building Code; or
2. A building or occupancy protected throughout by a sprinkler system, in metal cabinets dedicated to the storage of solid fuel that:
2.1. Are designed and constructed in accordance with FC 5003.8.7 (for hazardous materials storage);
2.2. Are placed on a stable, noncombustible surface; and
2.3. Have a maximum aggregate capacity of 75 cubic feet (2.1 m 3 ); or
3. Metal cabinets designed and installed in accordance with FC 315.7.2.1(2) that are located in a room that is protected by a sprinkler system and enclosed by a minimum of 1-hour fire barriers and horizontal assemblies (walls, floor, and ceiling) constructed in accordance with the Building Code, but such room is not required to be dedicated solely to the storage of solid fuel.
315.7.2.2 Outdoor.
Solid fuel shall be stored in well-constructed metal cabinets or containers (with welded seams) dedicated to the storage of solid fuel that:
1. Have securely-closing, close-fitting metal door or lids;
2. Are placed on a concrete or other stable, noncombustible surface;
3. Have a maximum aggregate capacity of 75 cubic feet (2.1 m 3 ); and
4. Are designed and constructed in accordance with FC 5003.8.7 (for hazardous materials storage) or, if not located within 6 feet (1829 mm) of a combustible surface, are designed and well-constructed of steel having a thickness of not less than 0.0478 inch (1.2 mm) (18 gauge).
315.7.3. Protection of solid fuel.
Solid fuel shall be protected by:
1. Keeping the doors or lids to a solid fuel storage room, cabinet or container closed;
2. Posting a durable sign or marking that reads "SOLID FUEL – KEEP FIRE AWAY" at the entrance to a solid fuel storage room or storage cabinet or container; and
3. Storing charcoal and similar combustible materials in their original packaging, or in noncombustible containers with securely-closing lids and an internal vertical dimension of not more than 48 inches (1219 mm).
315.7.4 Storage of solid fuel in Group R-2 occupancies.
Storage of solid fuel in Group R-2 occupancies, including storage for use in fireplaces and solid fuel-burning equipment approved by the Department of Buildings, shall be in accordance with FC 315.7.4.1 and 315.7.4.2.
315.7.4.1 Indoor storage.
Indoor storage of solid fuel shall not exceed 4 cubic feet (0.11 m 3 ) of solid fuel in each dwelling unit, which shall be stored in a safe manner away from sources of ignition.
315.7.4.2 Outdoor storage.
Outdoor storage of solid fuel shall be in accordance with FC 315.7.2.2.
Section FC 316. Hazards to Emergency Responders
316.1 Hoistway and shaftway protection.
The doors and/or gates to hoistways, freight elevator shafts, trap doors and other means used to provide access to vertical openings, shall be kept closed and secured, or otherwise protected, except when being used to provide access, and shall be closed, secured or otherwise protected, as applicable, at the end of each work day.
316.2 Shaftway markings.
Vertical shafts shall be identified as required by this section.
316.2.1 Exterior access to shaftways.
Outside openings accessible to the department and which open directly on a hoistway or shaftway communicating between two or more floors in a building shall be plainly marked with the word SHAFTWAY in red letters at least 6 inches (152 mm) high on a white background. Such warning signs shall be placed so as to be readily discernible from the outside of the building.
316.2.2 Interior access to shaftways.
Door or window openings to a hoistway or shaftway from the interior of the building shall be plainly marked with the word SHAFTWAY in red letters at least 6 inches (152 mm) high on a white background. Such warning signs shall be placed so as to be readily discernible.
Exception: Marking shall not be required on shaftway openings which are readily discernible as openings onto a shaftway by the construction or arrangement.
316.3 Pitfalls.
Installations designed to disable, injure, maim or kill intruders are prohibited. No person shall install or use firearms, sharp or pointed objects, razor wire, explosives, flammable or combustible liquid containers, or dispensers containing highly toxic, toxic, irritant, piercing sounds or other hazardous materials in a manner which may passively or actively disable, injure, maim or kill a firefighter or other emergency responder who enters a building or premises, forcibly or otherwise, for the purpose of controlling or extinguishing a fire, rescuing trapped occupants or rendering other emergency assistance.
316.4 Security device.
It shall be unlawful to install, operate or maintain a security device that emits any substance that could obscure a means of egress in any building, structure or premises.
Section FC 317. Automotive Salvage and Wrecking Facilities
317.1 General.
Automotive salvage and wrecking facilities shall be designed, installed, operated and maintained in accordance with this section. The design and installation provisions of this section shall apply to both new and existing facilities.
317.2 Prohibitions.
It shall be unlawful to:
1. Dispose of any fuel or flammable or combustible liquid waste by discharging or otherwise disposing of such fuel or liquid waste in any drain or sewer, upon any premises, or in any river, stream or other body of water.
2. Light or maintain an open fire for the burning, dismantling, salvaging, scrapping wrecking of motor vehicles or parts thereof.
317.3 Supervision.
Automotive salvage and wrecking facilities shall be supervised as follows:
1. The facility shall be under the personal supervision of a person holding a certificate of fitness for automotive salvage and wrecking facilities, who shall ensure that the facility is designed, installed, operated and maintained in accordance with this code and other applicable laws, rules, and regulations.
2. The defueling of motor vehicle fuel tanks and the transfer of fuel from the defueling equipment shall be conducted by or under the personal supervision of a certificate of fitness holder.
3. Hot work shall be personally conducted by a person holding a certificate of fitness for such work in accordance with FC Chapter 35.
317.4 Facility requirements.
Automotive salvage and wrecking facilities shall be in accordance with FC 317.4.1 through 317.4.3.
317.4.1 Licensing.
Department permits and other approvals shall be issued to an automotive salvage and wrecking facility only if such facility is licensed and maintained in accordance with requirements of the New York State Department of Motor Vehicles and the New York City Department of Consumer and Worker Protection.
(Am. L.L. 2020/080, 8/28/2020, eff. 8/28/2020)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2020/080.
317.4.2 Lawful occupancy.
Department permits and other approvals shall be issued to automotive salvage and wrecking facilities only if use of the premises for such facility is authorized by the certificate of occupancy or otherwise constitutes a lawful use of the premises.
317.4.3 Design requirements.
Automotive salvage and wrecking facilities shall be designed in accordance with FC 317.4.3.1 through 317.4.3.3.
317.4.3.1 Facility enclosure.
The facility shall be enclosed on all sides by a solid, opaque fence or wall at least 8 feet (2438 mm) in height in accordance with the Building Code and the Zoning Resolution.
317.4.3.2 Fire apparatus roads.
The facility shall be accessible from fire apparatus roads with a minimum unobstructed width of 20 feet (6096 mm). An outdoor area of the facility shall be accessible by fire apparatus roads on all four sides with a distance between such roads of not greater than 50 feet (15 240 mm) by 100 feet (30 480 mm).
317.4.3.3 Defueling area.
The defueling of motor vehicle fuel tanks shall be conducted at an approved location that is protected throughout by a fire extinguishing system.
317.5 Operation and maintenance.
Automotive salvage and wrecking facilities shall be operated and maintained in accordance with FC 317.5.1 through 317.5.4.
317.5.1 Fire apparatus access roads.
Fire apparatus access roads shall be maintained unobstructed to provide access for department apparatus.
317.5.2 Torch operations.
Torch operations shall be conducted in accordance with FC Chapter 35 and in compliance with the following requirements:
1. Torch operations shall be conducted at least 35 feet (10 668 mm) from combustible waste, other motor vehicles, stacks of motor vehicles or other combustible material, unless protection in the form of noncombustible shields or covers are provided to restrict the scattering of sparks and molten metal.
2. Torch operations shall not be conducted in any location where hazardous gases or vapors may be present. Fuel tanks of motor vehicles shall be emptied of fuel and purged of all flammable vapors before any torch operations are commenced.
3. Compressed gas containers, when in use, shall be properly supported and placed a safe distance from torch operations.
4. Compressed gas containers, when not in use, and reserve containers, shall be properly supported and stored in a location remote from torch operations. The valves of such containers shall be closed and protected from mechanical damage by the placement of protective caps. Empty containers shall be treated as full.
5. Torch operation areas shall be protected by a charged hose line, at least 1 inch (25 mm) in diameter, connected to an approved source of water. In lieu of such hose line, at least four portable fire extinguishers with a minimum 2-A rating each may be provided.
6. The torch operator or a person designated as a fire watch shall search the torch operation area immediately after operations to determine that no sparks or molten metal remain in the area. Additionally, a second such search shall be conducted 1/2 hour thereafter. A record of such searches shall be maintained in a log book at the premises and made available for inspection by any representative of the department.
317.5.3 Draining of motor vehicle fluids.
The draining of fluids from motor vehicles shall be in accordance with FC 317.5.3.1 and 317.5.3.2.
317.5.3.1 Draining of motor vehicle fuel tanks.
As soon as practicable after arrival, the fuel tank of motor vehicles received at salvage and wrecking facilities shall be defueled through the vehicle's fuel connection, or other approved procedure. Defueling equipment shall be listed for such purpose as a complete assembly and shall have a container capacity not exceeding 65 gallons (246 L). The fuel recovered by the defueler shall be transferred to a storage tank complying with the requirements of FC Chapter 23 or 57, as applicable. Defueling equipment shall not be used to fuel motor vehicles.
317.5.3.2 Draining of other motor vehicle fluids.
Crankcase oil and other flammable or combustible liquid waste shall be removed from motor vehicles and stored outdoors, in tanks complying with the requirements of FC Chapter 57, or, when approved, portable containers.
317.5.4 Emergency operations.
In automotive salvage and wrecking facilities provided with cranes for the purpose of moving or stacking motor vehicles, procedures shall be developed by the owner such that a crane operator would be made available in a reasonable period of time in the event that crane operation is required during a fire or other emergency.
317.6 Excessive fires.
The occurrence of more than two fires in an automotive salvage and wrecking facility during any 12-month period shall give rise to a rebuttable presumption that the owner has failed to properly maintain the facility in compliance with the requirements of this section, and shall be grounds for revocation of department permits and other approvals, or other appropriate enforcement action.
317.7 Air bags.
Undeployed waste air bags shall be stored and handled at automotive salvage and wrecking facilities in accordance with the FC 317.7.1 through 317.7.3.
317.7.1 Limitation on storage.
Not more than 250 undeployed waste air bags shall be stored at an automotive salvage and wrecking facility unless the facility is an approved air bag waste collection facility in accordance with EPA regulations and registered with the New York State Department of Environmental Conservation.
317.7.2 Storage of undeployed waste air bags.
No later than the end of each workday, undeployed waste air bags shall be packaged for shipment and disposal in compliance with DOTn regulations and stored in a cool, dry and secure area, free of oil, grease, detergent, or water, at least 50 feet from any hot work area or other source of ignition. The air bag leads shall be protected from stray current by shunting them and wrapping them in electrical tape or by other approved method. Storage of more than 250 undeployed waste air bags shall require that the automotive salvage and wrecking facility be an approved air bag waste collection facility.
317.7.3 Removal of undeployed waste air bags.
Undeployed waste air bags shall be disposed of by a lawful waste hauler in accordance with EPA, DOTn and New York State Department of Environmental Conservation regulations.
Section FC 318. Rooftop Gardens and Landscaping
318.1 General.
Rooftop gardens and landscaping, including living walls, shall be designed, installed, operated and maintained in accordance with the construction codes, including the Building Code and this section.
318.2 Rooftop access and obstructions.
Rooftop gardens and landscaping subject to the rooftop access and obstruction provisions of FC 504.4 shall be designed and installed in compliance with the requirements of that section.
318.3 Maintenance of vegetation.
Rooftop gardens and landscaping shall be maintained in a healthy condition and shall not be allowed to encroach upon areas required to be kept clear. Vegetation shall be regularly pruned for these purposes and vegetation capable of being ignited shall be regularly cleared and removed from the rooftop and the building.
318.4 Maintenance equipment.
Portable fueled equipment, including flammable and combustible liquid fuels, used for the maintenance of rooftop garden and landscaping vegetation shall be stored in accordance with FC 313 and 5704.3.4.4.
318.5 Water supply.
Rooftop gardens or landscaping exceeding 250 square feet (23 m 2 ) shall be provided with a rooftop garden hose connected to an approved water supply. Where the size of the rooftop garden, extent of landscaping, type of vegetation, and/or premises maintenance history warrant, the department may require installation of an irrigation system or other approved method of hydration to ensure proper maintenance of the vegetation.
Section FC 319. Reserved
BetaNYC's copy has no text for this section. Read Section FC 319 at American Legal Publishing.
Section FC 320. Laundry Carts
320.1 Laundry carts with a capacity of 1 cubic yard or more.
Laundry carts with an individual capacity of 200 gallons (1 cubic yard or 0.76 m 3 ) or more used for laundry purposes shall be constructed of noncombustible materials or of materials having a peak rate of heat release not exceeding 300 kW/m 2 at an incident heat flux of 50 kW/m 2 when tested in a horizontal orientation in accordance with ASTM E 1354, and shall be listed and labeled as such.
Section FC 321. Fixed Guideway Transit and Passenger Rail Systems
321.1 Scope.
This section shall govern the design, installation, operation and maintenance of underground, open cut, surface and elevated fixed guideway transit and passenger rail systems.
321.2 Design and installation.
The design and installation of fire safety and life safety systems for fixed guideway transit and passenger rail systems, including emergency ventilation systems, emergency voice communication systems, fire protection systems and means of egress, shall be in accordance with NFPA 130 and all Annexes thereto, as modified by FC Appendix B; the Electrical Code; the provisions of the construction codes applicable to fire safety and life safety systems; and this section.
321.2.1 Fire scenario design parameters.
Approved fire scenarios used for designing fixed guideway transit and passenger rail systems shall be in accordance with Sections 4.4 and A 4.4.2 of NFPA 130, as modified by FC Appendix B, and the following:
1. The worst case scenario, as set forth in NFPA 130, as modified by FC Appendix B, shall be used for both the station and trainway designs.
2. Computational fluid dynamics analysis for the fire simulation shall be performed for an approved period of time, both with and without mitigating systems, including but not limited to ventilation and sprinkler protection.
3. The tenable condition parameters reported in the computational fluid dynamics analysis, including but not limited to heat, visibility and carbon monoxide, shall be precisely reported in the analysis.
321.3 Operation and maintenance.
The operation and maintenance of fixed guideway transit and passenger rail systems shall be in accordance with NFPA 130 and all Annexes thereto, as modified by FC Appendix B.
321.4 Construction site fire safety.
Construction operations of fixed guideway transit and passenger rail systems, including stations and tunnels, shall be conducted in accordance with Chapter 33 of the Building Code; this code, including FC Chapter 33; and NFPA 130, as modified by FC Appendix B. Approved fire extinguishing systems shall be provided for construction shanties and construction storage facilities and areas.
Section FC 322. Road Tunnels, Bridges and Other Limited Access Highways
322.1 Scope.
This section shall govern the design, installation, operation and maintenance of road tunnels, bridges and other limited access highways used or designed to be used by motor vehicles.
322.2 Design and installation.
The design and installation of fire safety and life safety systems for road tunnels, bridges and other limited access highways, including emergency ventilation systems, emergency voice communication systems, fire protection systems and means of egress, shall be in accordance with NFPA 502, as modified by FC Appendix B; the Electrical Code; the provisions of the construction codes applicable to fire safety and life safety systems; and this section.
322.2.1 Fire scenario design parameters.
Approved fire scenarios used for designing road tunnels shall be in accordance with NFPA 502, as modified by FC Appendix B, and the following:
1. The worst case scenario, as set forth in NFPA 502, as modified by FC Appendix B, shall be used for designs.
2. Computational fluid dynamics analysis for the fire simulation shall be performed for an approved period of time, both with and without mitigating systems, including but not limited to ventilation and sprinkler protection.
3. The tenable condition parameters reported in the computational fluid dynamics analysis, including but not limited to heat, visibility and carbon monoxide, shall be precisely reported in the analysis.
322.3 Operation and maintenance.
The operation and maintenance of road tunnels, bridges and other limited access highways used or designed to be used by motor vehicles shall be in accordance with NFPA 502, as modified by FC Appendix B.
322.4 Construction site fire safety.
Construction operations of road tunnels, bridges and other limited access highways shall be conducted in accordance with Chapter 33 of the Building Code; this code, including FC Chapter 33; and NFPA 502, as modified by FC Appendix B. Approved fire extinguishing systems shall be provided for construction shanties and construction storage facilities and areas.
Section FC 323. Wastewater Treatment and Collection Facilities
323.1 Scope.
This section shall govern the design, installation, operation and maintenance of fire protection systems and other fire safety measures at wastewater treatment and collection facilities.
323.2 General.
Fire protection systems and other fire safety measures at wastewater treatment facilities shall be designed, installed, operated and maintained in accordance with NFPA 820.
Section FC 324. Electric Generating Plants
324.1 Scope.
This section shall govern the design, installation, operation and maintenance of fire protection systems and other fire safety measures at electric generating plants.
324.2 General.
Fire protection systems and other fire safety measures at electric generating plants shall be designed, installed, operated and maintained in accordance with NFPA 850, except for microturbine installations, which shall be designed, installed, operated and maintained in accordance with FC 5810.
Section FC 325. Production Locations
325.1 Scope.
This section shall govern the protection of fire safety at production locations used for filming and rigging, except for soundstages, production studios and approved production facilities, as those terms are defined in NFPA 140.
(L.L. 2021/033, 3/28/2021, eff. 7/26/2021)
325.2 General.
Production locations shall comply with the fire safety measures required by this section and by NFPA 140, as applicable.
(L.L. 2021/034, 3/28/2021, eff. 7/26/2021)
325.3 Permits.
Permits shall be required as set forth in FC 105.6.
(L.L. 2021/034, 3/28/2021, eff. 7/26/2021)
325.4 Interagency coordination.
The department shall develop and establish, in consultation with the Mayor's Office of Film, Theatre and Broadcasting, or an officer, employee or unit of the Department of Small Business Services as may be authorized to issue permits in accordance with paragraph r of subdivision 1 of section 1301 of the charter or pursuant to its rules, and such other agencies as the department determines to be necessary and appropriate, a protocol and other processes to:
1. Provide to the department real-time access to information submitted to the Mayor's Office of Film, Theatre and Broadcasting, or an officer, employee or unit of the Department of Small Business Services as may be authorized to issue permits in accordance with paragraph r of subdivision 1 of section 1301 of the charter or pursuant to its rules, in connection with permit applications;
2. Provide notification to the local firehouse each time a permit for filming or rigging is issued for activities that occur at a production location within the area of response for such firehouse.
3. Enable the department to evaluate relevant fire safety considerations at production locations, familiarize local firehouses or other members of the department with field conditions, including alterations being performed at such locations, in advance of and during the course of rigging and filming, and provide additional production location information in a timely manner to firefighters and other emergency response personnel during fire and non-fire emergencies; and
4. Coordinate approval of permit applications to allow the department to determine whether any premises associated with the proposed production location is subject to any outstanding department or Department of Buildings violation that the department determines constitutes a life safety hazard sufficient to warrant denial of the application. The Mayor's Office of Film, Theatre and Broadcasting, or an officer, employee or unit of the Department of Small Business Services as may be authorized to issue permits in accordance with paragraph r of subdivision 1 of section 1301 of the charter or pursuant to its rule, shall deny such permit application when the department makes such a determination.
(L.L. 2021/034, 3/28/2021, eff. 7/26/2021)
325.5 Fire safety at production locations.
The department shall promulgate rules addressing fire safety at production locations. Such rules shall establish fire safety standards, procedures and requirements in consideration of such location's occupancy, construction and condition, including factors such as whether means of egress are impeded and a working sprinkler system exists, and the nature of the production activities to take place at such location, including set construction or other alterations, and whether pyrotechnic or other special effects will be conducted. Such rules may require the following fire safety measures:
1. The presence of one or more production location fire safety managers, to be designated by the permit holder, during production activities determined by the department to require such supervision. Production location fire safety managers shall have such qualifications and duties as set forth in FC 325.6 and the rules.
2. The presence of department representatives or standby fire apparatus during production activities, as determined by the department.
3. Directing the cessation of filming activities when an unsafe condition arises that is detrimental to fire safety, until such time as such condition is corrected.
4. Such other fire safety measures as the department may require.
(L.L. 2021/033, 3/28/2021, eff. 7/26/2021; Am. L.L. 2021/034, 3/28/2021, eff. 7/26/2021)
325.6 Production location fire safety manager.
When required by the rules, production locations shall be under the personal supervision of one or more production location fire safety managers, each of whom shall hold the required certificate of fitness. The permit holder shall designate such production location fire safety managers before the commencement of the activity authorized by a permit for rigging and shooting pursuant to 43 RCNY § 9-01.
(L.L. 2021/033, 3/28/2021, eff. 7/26/2021; Am. L.L. 2021/034, 3/28/2021, eff. 7/26/2021)
325.6.1 Fire safety manager duties.
The production location fire safety manager shall have such duties and responsibilities as set forth in the rules, including but not limited to:
1. Ensuring compliance with the requirements of this code and other laws, rules and regulations enforced by the department.
2. Personally inspecting and monitoring the production location, confirming that permits or other required approvals have been obtained, and completing fire safety surveys or other recordkeeping.
3. Notifying the permit holder of any conditions detrimental to fire safety in accordance with the rules.
(L.L. 2021/033, 3/28/2021, eff. 7/26/2021; Am. L.L. 2021/034, 3/28/2021, eff. 7/26/2021)
325.7 Means of egress.
Means of egress shall be maintained free from obstruction at production locations. Prior approval of the Department of Buildings and/or the department shall be obtained in accordance with applicable laws, rules and regulations for any alteration or obstruction of the means of egress.
(L.L. 2021/034, 3/28/2021, eff. 7/26/2021)
325.8 Housekeeping.
All production locations shall be maintained free of accumulation of combustible waste in accordance with FC 304.
(L.L. 2021/034, 3/28/2021, eff. 7/26/2021)
325.9 Portable fire extinguishers.
The permit holder responsible for a production location shall provide one or more portable fire extinguishers when required by the rules.
(L.L. 2021/034, 3/28/2021, eff. 7/26/2021)
Section FC 401. General
401.1 Scope.
This chapter governs emergency reporting, planning and preparedness.
401.2 Emergency reporting.
401.2.1 Reporting to department.
Any owner, occupant or other person who becomes aware of a fire or explosion or any other emergency shall immediately report such emergency to the department. No owner or other person shall issue any directive or take any action to prevent or delay the reporting of a fire or other emergency to the department.
401.2.2 Signage.
A durable, legible sign setting forth the following information for reporting a fire or other emergency (including the text to be inserted based on the building's location) shall be posted in a conspicuous location in the lobby of the main front entrance of a Group A, B, E, F, I, M and R-1 building:
Fire alarm box at __________________ and ____________________ (Name of street) (Name of street)
or
To report a fire or other emergency by telephone dial "911." Such sign may include, in buildings or occupancies with a designated telephone number for reporting of emergencies occurring in or affecting the building or occupancy, such telephone number, provided that such signage states that the fire and emergency first be reported to "911."
Exception: Buildings exempt from such sign requirement as set forth in the rules.
401.3 Emergency preparedness plans.
The emergency preparedness plans required by this chapter shall serve to assure that procedures are in place that can be timely implemented in the event of a fire or non-fire emergency to provide the information, guidance, direction and assistance needed to protect the safety of building occupants, including, if necessary, effecting their evacuation, relocation or sheltering in place. Such emergency preparedness plans shall further serve to assure that knowledgeable assistance is readily available on the premises to emergency response personnel responding to a fire or non-fire emergency at the premises.
401.3.1 General.
The owner of any premises required by this chapter to have an emergency preparedness plan shall cause such plan to be prepared for such premises in the form prescribed by the commissioner, and periodically reviewed and amended, in accordance with this section and the rules. The commissioner may prescribe by rule the qualifications of the person preparing such plans.
401.3.2 Types of emergency preparedness plans.
This chapter establishes the following three types of emergency preparedness plans, which reflect the use, size, complexity and risk vulnerability of the building or occupancy; the presence of building staff and/or other building occupants capable of implementing such plan; the availability of voice communication capability; and other considerations:
1. Level 1: comprehensive fire safety/emergency action plan (FC 401.4).
2. Level 2: fire and emergency preparedness plan (FC 401.5).
3. Level 3: fire and emergency preparedness guide and notices (FC 401.6).
401.3.2.1 Multi-building campus plans.
The fire commissioner may approve a multi-building campus emergency preparedness plan, including specific minimum staffing qualifications and levels, for educational and health care occupancies subject to FC 408, 410 and/or FC 413, with certain specified emergency preparedness functions performed by staff assigned to multiple campus buildings. Such multi-building campuses shall consist of a single block, contiguous blocks or other approved geographic area, or a series of physically interconnected buildings.
401.3.3 Maintenance on premises.
A copy of the emergency preparedness plan shall be maintained at the premises for which such plan is required and kept readily available for inspection at all times. The department may require that the emergency preparedness plan be maintained at an approved location on the premises in an approved first responder box secured by a citywide standard key to ensure availability of the plan at all times.
401.3.4 Building information card and floor plans.
In buildings or occupancies required to prepare a comprehensive fire safety and emergency action plan, and in high-rise buildings and large-area buildings required to prepare a fire and emergency preparedness plan, or such other building or occupancy as required by this chapter or the rules, a building information card depicting and/or setting forth the fire safety information prescribed by the commissioner by rule shall be maintained on the premises and submitted or otherwise made available to the department as set forth in the rules. An amended building information card shall be submitted for department review and approval as set forth in the rules. When required by this code or rule, building floor plans shall be submitted to the department in an approved manner.
401.3.5 Periodic review and revision.
Emergency preparedness plans and building information cards shall be reviewed and updated as necessitated by changes in staff assignments, use or occupancy, or the design and arrangement of the premises, but at least annually. An entry shall be made in the log book required by FC 401.8 documenting such review, and indicating the general nature of any amendments to be made to such plan. Submission of an amended emergency preparedness plan shall not be required solely by reason of staffing changes or revisions to the building information card. Fire and emergency preparedness guides and notices shall be reviewed prior to each distribution required by this code or the rules, and shall be revised within 60 days of any change in building construction or service equipment materially affecting the content of such guide or notice.
401.3.6 Applicability to existing buildings and occupancies.
The preparation of an emergency preparedness plan shall constitute an operational requirement. Except as otherwise provided in this section, owners of buildings and occupancies required by this chapter to have a comprehensive fire safety and emergency action plan shall have 24 months from the promulgation of rules implementing such emergency preparedness plan provisions of this chapter to prepare such plan and submit it to the department for acceptance. Owners of buildings and occupancies required by this chapter to have any other emergency preparedness plan shall have 18 months from the promulgation of rules implementing such emergency preparedness plan provisions of this chapter to prepare such plan and, if required by this chapter, submit it to the department for acceptance.
401.3.6.1 New and existing buildings and occupancies.
Until rules implementing the emergency preparedness plan provisions of this chapter take effect, buildings and occupancies required to prepare an emergency preparedness plan under this code shall comply with the emergency preparedness plan requirements set forth in the Fire Code and rules in effect on the date prior to the effective date of this section.
401.3.7 Existing emergency preparedness staffing.
Any building or occupancy that prior to March 30, 2014, obtained department approval of the voluntary installation of a fire alarm system with a staged evacuation sequence and was required to provide a fire safety director or other specified emergency preparedness staffing shall provide staffing in accordance with this chapter and the rules.
401.3.8 Cooperation.
All owners, employers of building occupants (including lessees of tenant spaces and similar occupancies) and building occupants shall cooperate in the development and coordination of emergency preparedness plans, including designation of building occupants to assist in the implementation of such plan.
401.4 Comprehensive fire safety/emergency action plan (Level 1).
Level 1 plans and staffing shall be in accordance with FC 401.4.1 through 401.4.5, the provision of the FC 404 through 415, as applicable, and the rules.
401.4.1 General.
The commissioner shall promulgate rules establishing standards, procedures and requirements for a written comprehensive fire safety and emergency action plan that addresses the safety of occupants of premises in the event of a fire, explosion, biological, chemical or nuclear incident or release, natural disaster, or other emergency, or the threat thereof, or a declaration of emergency by a lawful authority, and for the coordination of the emergency response to a medical emergency at the premises.
401.4.2 Form.
The rules shall specify the form of the comprehensive fire safety and emergency action plan and supporting documentation.
401.4.3 Content.
The rules shall specify the information to be contained in the comprehensive fire safety and emergency action plan, which shall include the following information and documentation, and/or such other information and documentation as the commissioner may prescribe:
1. The designation of an FLS director and other FLS staff, and their respective duties and responsibilities, including FLS staff responsible for the operation of building elevators, fire protection systems, mechanical ventilation systems, building utilities, and other building service equipment.
2. The procedures for reporting a fire or other emergency to the department, including the primary and alternative means of such reporting.
3. The procedures for coordinating with firefighting, emergency medical service and other emergency response personnel, including notifying such personnel upon arrival of the location of the emergency and the response thereto.
4. The means provided for receiving and monitoring public emergency notification systems in accordance with FC 401.9.
5. The procedures for notifying building occupants of a fire or other emergency, including the primary and alternative means of such notification, the alarm or tone sounded to alert building occupants, and the information communicated to building occupants.
6. The actions to be taken in response to a fire and each type of non-fire emergency, and whether the response will require the sheltering in place, in-building relocation, partial or full evacuation of building occupants, or combination thereof, and the procedures for each such response.
7. The procedures for accounting for building occupants after such occupants have been in-building relocated, or partially or fully evacuated to a safe area.
8. The procedures for identifying any persons on the premises who are qualified and willing to provide cardio-pulmonary resuscitation or other emergency medical care to building occupants upon notification by the FLS director.
9. Site plans indicating the following:
9.1. Surrounding buildings and streets, including cross streets, and fire apparatus access roads.
9.2. The location of building occupant assembly areas.
10. A written description of the following building components and service equipment and their location, as applicable:
10.1. Access to and egress from the building, including entrances and exits.
10.2. Corridors and exit passageways providing access to exit stairwells or exit discharges.
10.3. Stairwells with letter designation.
10.4. Access and convenience stairs.
10.5. Elevators, with bank letter and car number designations.
10.6. Fire command center.
10.7. Floor warden and firefighter telephones.
10.8. Manual fire alarm boxes.
10.9. Fire department connections, and sprinkler and standpipe system control valves.
10.10. Areas of the building not protected by a sprinkler system.
10.11. Emergency power generators and associated fuel storage.
10.12. Evacuation and in-building relocation routes.
10.13. Areas of refuge and in-building relocation areas.
10.14. Any evacuation assistance devices.
10.15. Automatic external defibrillators required by law to be maintained for public use.
11. Sprinkler system and standpipe system riser diagrams, identifying the locations of the following, as applicable:
11.1. Water supply.
11.2. Fire department connections.
11.3. Gravity and pressure tanks.
11.4. Fire pumps.
11.5. Water supply control valves.
11.6. Piping, except branch sprinkler piping.
12. Locations of hazardous material storage in quantities requiring a permit, and hazardous material operations and facilities regulated by this code.
13. Procedures for identifying in advance building occupants who require assistance to participate in the plan because of an infirmity or disability or other special need, and approved procedures for providing for such assistance.
14. A fire safety maintenance program.
15. A building information card in accordance with FC 401.3.4.
401.4.4 Submission and acceptance.
Every comprehensive fire safety and emergency action plan shall be submitted to the department for acceptance in the manner prescribed by the department. Acceptance of such plans shall be obtained prior to occupancy of the building or occupancy.
401.4.5 Fire and life safety staff.
The owner of any premises required by this chapter to have a comprehensive fire safety and emergency action plan shall designate competent persons to act as FLS staff, including a person designated to serve as FLS director. The owner shall employ or otherwise retain sufficient FLS staff to implement such plan during regular business hours and to otherwise comply with the requirements of this chapter and the rules. The persons designated as FLS staff shall possess such qualifications and/or hold such certificates of fitness as are required by this chapter or the rules.
401.4.5.1 Fire and life safety director.
The comprehensive fire safety and emergency action plan shall designate an FLS director and deputy FLS directors who shall hold an FLS director certificate of fitness. The FLS director shall have the following duties and responsibilities and such other duties and responsibilities as the commissioner may prescribe by rule:
1. The FLS director shall be present in the building at all times during regular business hours. When the FLS director is absent during regular business hours, a deputy FLS director shall be present in the building and shall perform the duties of the FLS director. When a building other than a Group R-1 transient residential building or occupancy is occupied, but the number of building occupants falls below the level requiring the presence of an FLS director, the FLS building evacuation supervisor may perform the duties of the FLS director. The FLS director shall endeavor to ensure that adequate FLS staff is present during regular business hours, and, in the absence of designated staff, shall designate interim FLS staff.
2. In the event of a fire, a medical emergency or other non-fire emergency in the building, the FLS director shall report to the fire command center or designated alternative location; implement such fire safety and/or non-fire emergency actions as are warranted by the circumstances, in accordance with the provisions of the comprehensive fire safety and emergency action plan, this code and the rules; notify arriving emergency response personnel of the nature of the emergency and the response thereto; and comply with the directions of the emergency response personnel and/or other lawful authority.
3. The FLS director designated shall be fully familiar with the provisions of the comprehensive fire safety and emergency action plan and shall conduct the FLS staff training and fire and non-fire emergency drills required by FC 401.4.5.2 and 401.7.
Exception: FLS staff training and fire and non-fire emergency drills may be conducted by a person holding a certificate of fitness as FEP coordinator or fire drill conductor under the personal supervision of the FLS director.
401.4.5.2 Training.
FLS staff shall be trained in the performance of their duties in accordance with the comprehensive fire safety and emergency action plan.
401.4.5.2.1 Initial training.
FLS staff shall receive initial training in the contents of the comprehensive fire safety and emergency action plan upon their designation as FLS staff. Such training shall familiarize them with:
1. their duties in the event that it is necessary to implement fire safety or non-fire emergency actions in accordance with such plan; and
2. appropriate fire prevention measures for the occupancy.
401.4.5.2.2 Refresher training.
With the exception of the FLS director, FLS staff shall receive, and participate in, periodic refresher training to maintain their state of readiness.
401.4.5.2.3 Duration and frequency of training.
The duration and frequency of initial and refresher training of FLS staff shall be in accordance with FC Table 401.4.5.2.3.
FC Table 401.4.5.2.3 FLS Staff Training
FLS Staff Member Initial Training Duration Refresher Training Duration and Frequency Fire Safety Non-fire Emergency Fire Safety Non-fire Emergency Deputy FLS directors (all occupancies) Not applicable Not applicable 1 hour annually 1 hour semiannually FLS building evacuation supervisors 2 hours 3 hours 1 hour annually 1 hour semiannually All other FLS staff 1 hour 2 hours 1 hour annually 1 hour annually
401.4.5.2.4 Training methods.
FLS staff training sessions shall be provided in the form of live instruction and, if desired, computerized training. At least one-half (1/2) of the FLS staff training sessions required each year shall be in the form of live instruction, which may incorporate video presentations and/or review of other educational materials. The balance of the required training sessions may be conducted in the form of approved computerized training, without live instruction, provided that such computerized training is interactive, and includes an evaluation of the FLS staff members' understanding of the training materials.
401.4.5.2.5 Recordkeeping.
A written record of FLS staff training shall be maintained in the log book required by FC 401.8. An entry shall be made in such log book for each training session conducted.
401.5 Fire and emergency preparedness plan (Level 2).
Level 2 plans and staffing shall be in accordance with FC 401.5.1 through 401.5.5, the provisions of FC 404 through 415, as applicable, and the rules.
401.5.1 General.
The commissioner shall promulgate rules establishing standards, procedures and requirements for a written fire and emergency preparedness plan that provides for fire safety and non-fire emergency preparedness in buildings or occupancies of a lesser size, complexity, and/or risk vulnerability than those requiring a comprehensive fire safety and emergency action plan, and for the coordination of the emergency response to a medical emergency at the premises.
401.5.2 Form.
Fire and emergency preparedness plans shall have a simplified, standardized format that allows for completion by persons without specialized qualifications. The rules promulgated by the commissioner shall specify the form of such plans and any supporting documentation.
401.5.3 Content.
The rules promulgated by the commissioner shall specify the information to be contained in the fire and emergency preparedness plan, which shall include the following information and documentation, and/or such other information and documentation as the commissioner may prescribe:
1. The designation of the FEP coordinator, by name, certificate number and position at the premises, and other FEP staff, by name and/or position at the premises, and certificate number, if required.
2. The procedure by which a fire or other emergency is reported to the department, and the FEP staff responsible for ensuring such reporting.
3. The procedure for notifying building occupants of a fire or other emergency, and the FEP staff responsible for ensuring such notification.
4. The procedure for coordinating with firefighting, emergency medical service and other emergency response personnel, including notifying such personnel upon arrival of the location of the emergency and the response thereto, and the FEP staff responsible for such coordination.
5. The procedure for monitoring a public emergency notification system in accordance with FC 401.9.
6. Procedures for identifying and assisting building occupants who require assistance because of an infirmity, disability or other special need.
7. Identification of fire prevention measures appropriate to the occupancy, to be included in staff training and drills, and the FEP staff or building staff responsible for addressing any unsafe conditions, including:
7.1. Unobstructed and unimpeded access to means of egress.
7.2. Proper storage and removal of combustible materials and combustible waste on the premises.
7.3. Maintenance of decorative vegetation.
7.4. Proper use of extension cords, outlets and electrical equipment.
7.5. Maintenance of sprinkler head clearances.
7.6. Posting and maintenance of "No Smoking" signs required by this code.
8. The procedure for the ongoing monitoring of the premises during regular business hours to verify compliance with the following requirements, and the FEP staff responsible for such monitoring:
8.1. Access to the means of egress is unobstructed and unimpeded.
8.2. The premises does not become overcrowded.
8.3. Allowable use of open flames and open-flame devices is being conducted properly and safely.
8.4. The prohibition against smoking, where required by this code or the rules, is being observed.
401.5.4 Submission and acceptance.
Except as otherwise provided in FC 401.5.4.1, fire and emergency preparedness plans prepared for a high-rise building or a large-area building shall be submitted for department acceptance, prior to occupancy of the building or occupancy, in the manner prescribed by the department. All other fire and emergency preparedness plans shall be maintained on the premises and made available for review by a department representative. If such plan is unavailable or determined to be deficient, the department may order that a plan prepared in compliance with this chapter and the rules be submitted to the department for acceptance.
401.5.4.1 Submission of plans not required.
Fire and emergency preparedness plans prepared for a high-rise building or a large-area building are not required to be submitted for department acceptance in the following circumstances:
1. High-rise buildings and large-area buildings with a fire alarm that is programmed for full, not staged, evacuation;
2. Low-rise, large-area Group I-1 buildings; and
3. Low-rise Group R-1 dormitories and low-rise Group R-2 student apartments, with more than fifty rooms above street level (which are treated as large-area buildings by the Building Code).
401.5.4.2 Electronic filing of plans.
The following emergency preparedness plans and, when required, building information cards, building floor plans and other supporting documentation, shall be electronically filed with the department for review and approval in the manner prescribed by the department:
1. Comprehensive fire safety/emergency action (Level1) plans.
2. Fire and emergency preparedness (Level 2) plans, when filing is required by the code or rules or ordered by the department for enforcement purposes.
401.5.5 Fire and emergency preparedness staff.
The owner of any premises required by this chapter to have a fire and emergency preparedness plan shall designate competent persons to act as FEP staff, including a person designated to serve as the FEP coordinator pursuant to FC 401.5.5.1. An owner of such a premises shall not be required to employ or otherwise retain staff solely for purposes of complying with the requirements of this chapter, but shall designate persons employed or otherwise working at the premises to serve as FEP staff and assign them the duties and responsibilities necessary to implement the fire and emergency preparedness plan and otherwise comply with the requirements of this chapter and the rules.
401.5.5.1 Fire/emergency preparedness coordinator.
A manager or other responsible FEP staff member employed at the premises shall be designated in the fire and emergency preparedness plan as the FEP coordinator and shall hold an FEP coordinator certificate of fitness. A person holding a certificate of fitness as an FLS director may serve as the FEP coordinator without obtaining a separate certificate of fitness. The FEP coordinator shall have the following duties and responsibilities and such other duties and responsibilities as the commissioner may prescribe by rule:
1. The FEP coordinator shall be fully familiar with the provisions of the fire and emergency preparedness plan and shall conduct the FEP staff training and fire and non-fire emergency drills required by FC 401.5.5.2 and 401.7.
Exception: FEP staff training and fire and non-fire emergency drills may be conducted by a person holding a certificate of fitness as fire drill conductor under the general supervision of the FEP coordinator.
2. The FEP coordinator need not be personally present on the premises during regular business hours, but shall be responsible for overseeing and monitoring the performance of the duties and responsibilities of the FEP staff set forth in the fire and emergency preparedness plan.
3. The FEP coordinator shall endeavor to ensure that adequate FEP staff is present during regular business hours, and, in the absence of designated FEP staff, shall designate interim FEP staff.
401.5.5.2 Training.
FEP staff shall be trained in the performance of their duties in accordance with the fire and emergency preparedness plan.
401.5.5.2.1 Initial training.
FEP staff shall receive 1 hour of initial training in the fire and emergency preparedness plan upon their designation as FEP staff. Such training shall familiarize them with:
1. their duties in the event the fire and emergency preparedness plan is implemented; and
2. appropriate fire prevention measures for the occupancy.
401.5.5.2.2 Refresher training.
With the exception of the FEP coordinator, FEP staff shall receive 30-minutes quarterly refresher training.
401.5.5.2.3 Training methods.
FEP staff training shall be provided in the manner set forth in FC 401.4.5.2.4.
401.5.5.2.4 Recordkeeping.
A written record of FEP staff training shall be maintained in the log book required by FC 401.8. An entry shall be made in such log book for each training session conducted.
401.6 Fire and emergency preparedness guide and notices (Level 3).
Level 3 guides and notices shall be in accordance with FC 401.6.1 through 401.6.5, and the rules.
401.6.1 General.
The commissioner shall promulgate rules establishing standards, procedures and requirements for a:
1. fire and emergency preparedness guide that serves to inform building occupants and building staff about the building, fire prevention measures and fire and non-fire emergency preparedness; and/or
2. fire and non-fire emergency notices that serve to inform building occupants, building staff and visitors as to whether to shelter in place or evacuate the building, and other procedures to be followed in the event of a fire or non-fire emergency.
401.6.2 Form.
The fire and emergency preparedness guide and notices shall be in such form as prescribed by the commissioner by rule.
401.6.3 Content.
The rules promulgated by the commissioner shall specify the information to be contained in the fire and emergency preparedness guide and notices, which shall include the following information, and/or such other information and documentation as the commissioner may prescribe:
1. Fire and Emergency Preparedness Guide.
1.1. Construction type.
1.2. Fire protection systems.
1.3. Voice communication systems.
1.4. Means of egress.
1.5. Guidance with respect to sheltering in place, evacuation and other procedures to be followed in the event of fire or non-fire emergency.
1.6. Lessons learned from fires in similar occupancies.
1.7. Medical emergencies.
2. Fire and Emergency Preparedness Notices.
2.1. Construction type.
2.2. Guidance with respect to sheltering in place, evacuation and other procedures to be followed in the event of fire or non-fire emergency.
401.6.4 Distribution and posting.
The fire and emergency preparedness guide shall be distributed to building occupants and building service employees as set forth in the rules. The fire and emergency preparedness notice shall be posted within each dwelling unit and at such other locations as set forth in the rules.
401.6.5 Occupancy-specific requirements.
The form, content, distribution and posting of the fire and emergency preparedness guide and notices may vary by occupancy. Occupancies required to prepare a fire and emergency preparedness guide and/or notices shall be as set forth in this chapter or the rules.
401.7 Drills and education for fire and non-fire emergencies.
Separate fire and non-fire emergency drills and education shall be conducted, in the manner prescribed in this section and the rules, and with the frequency set forth in FC Table 401.7.6, in buildings and occupancies required to have an emergency preparedness plan pursuant to this chapter and in such other buildings and occupancies as provided in this chapter. Group R-2 apartment buildings and occupancies are not required to conduct drills, except in high-rise megastructures and student apartment buildings.
401.7.1 Content.
Drills and other forms of education shall be conducted to enhance the fire and non-fire emergency preparedness of building occupants, including building staff and employees of building tenants. Drills shall serve to familiarize building occupants as to the proper actions to take in the event of a fire or other emergency, the primary and secondary evacuation and in-building relocation routes, and fire prevention measures appropriate to the occupancy. The commissioner shall promulgate rules prescribing standards, procedures and requirements for the conduct of fire and non-fire emergency drills and educational sessions, including their subject matter and duration. Drills shall be in the form of live instruction, except as authorized by the rules.
401.7.2 Reserved.
401.7.3 Timing.
Drills shall be scheduled in a manner that best assures the participation of regular building occupants. Drills may be conducted on different work shifts and/or during non-business hours to facilitate the participation of building occupants.
401.7.4 Participation in drills and education.
Except as otherwise provided in this chapter, all building occupants in the building or occupancy, or part thereof, wherein a fire and non-fire emergency drill or educational activity is being conducted, shall participate in such drill or educational activity, including building staff and FLS or FEP staff with responsibility for such building or occupancy, or part thereof. Owners and employers of building occupants, including lessees of tenant spaces and similar occupancies, shall require such participation.
401.7.5 Alarm activation.
The fire alarm system shall be activated each time a fire drill or non-fire emergency drill is conducted to initiate the drill and familiarize building occupants with the alarm tones. Nothing in this code shall be construed to prohibit the activation of the fire alarm signal for the purposes of conducting a fire drill or a non-fire emergency drill.
Exception: In buildings or occupancies in which all building occupants are not required by this code to participate in the drill, the fire alarm system need not be activated to initiate the drill, provided that, in accordance with the rules, another means is employed to familiarize those building occupants participating in the drill with the fire alarm tones that would be sounded in the event of an actual emergency.
401.7.6 Frequency.
The frequency of each required fire drill and each required non-fire emergency drill, for each type of occupancy, shall be in accordance with FC Table 401.7.6.
FC Table 401.7.6 Drill Participation and Frequency
Type of Building or Occupancy Required Participation Frequency Group A Regular building occupants. Participation of patrons, guests and visitors not required. Semiannually Group M Group R-1, except homeless shelters and dormitories a Group R-1 homeless shelters and emergency shelters All building occupants Monthly Group B office a All building occupants Semiannually Group B colleges and universities All building occupants In accordance with New York State Education Law Group E educational Group R-1 dormitory and Group R-2 student apartment buildings Group R-2 high-rise megastructures All building occupants Semiannually Group E day care facilities All building occupants Monthly Group F All building occupants Monthly Group H All building occupants Semiannually Group I-1 All building occupants Bimonthly b Group I-2 Regular building occupants. Participation of patients and visitors not required. Semiannually Group S Regular building occupants. Participation of visitors not required. Semiannually
a. In the 2 years following acceptance of a comprehensive fire safety and emergency action plan, drills shall be conducted quarterly.
b. In the first year of occupancy of an I-1 building or occupancy, drills shall be conducted monthly.
401.7.7 Non-fire emergency education.
When required by this chapter, building occupants shall receive non-fire emergency education. In buildings and occupancies in which non-fire emergency drills are not conducted, such education shall consist of the distribution of educational materials explaining the different types of non-fire emergencies and the types of responses to such emergencies, including sheltering in place, relocating within the building, or evacuating the building. Such materials shall be distributed to building staff and employees of building tenants prior to their commencing work at the premises.
401.7.8 Recordkeeping.
Drills and education shall be documented by entries in the logbook required to be maintained in accordance with FC 401.8.
401.8 Emergency preparedness recordkeeping.
Buildings and occupancies required to have an emergency preparedness plan pursuant to this chapter, except buildings and occupancies required to prepare a fire and emergency guide and notice, shall maintain a log book in accordance with this section.
401.8.1 General.
A log book or other approved system of recordkeeping shall be maintained for purposes of documenting emergency preparedness.
401.8.2 Format.
A bound log book with consecutive numbered pages, an approved electronic format, or other approved form of recordkeeping, shall be maintained in accordance with the requirements of FC 107.7.
401.8.3 Entries.
Entries shall be made in the log book to document drills, education, staff training, plan review and amendment, plan implementation and/or such other information as the commissioner may require by rule.
401.9 Access to public emergency notification systems.
While performing the duties of such position, FLS directors and FEP coordinators shall have access to NYC Notify, CorpNet or such other approved public emergency notification system providing notice of New York City emergencies as the commissioner may prescribe by rule. Such access may be by means of any portable or desktop device readily available for use on the premises under their supervision. The commissioner may prescribe by rule buildings and occupancies in which FLS directors and FEP coordinators shall have access to a public emergency notification system.
401.10 Periodic inspection.
Any building, occupancy, or part thereof required to have a comprehensive fire safety and emergency action plan, fire and emergency preparedness plan, and/or a public gathering site plan pursuant to the provisions of this chapter or the rules shall be subject to periodic fire safety inspection by the department, including inspection of any such plan to confirm that it has been prepared and/or implemented in compliance with the requirements of this chapter and the rules.
401.11 Workplace exit inspections.
In addition to any other inspections that the department may conduct, the department shall inspect Group M occupancies to determine whether workplace exits are locked in violation of Section 1001.3.1 of the Building Code. A minimum of fifty unannounced inspections shall be conducted each year. Such inspections shall include, but not be limited to, premises at which violations of such section are known or suspected to have occurred.
Section FC 402. Definitions
402.1 Definitions.
The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meaning set forth in FC 202.
ASSEMBLY AREA.
BUILDING OCCUPANTS.
COVERED MALL.
EMERGENCY SHELTER.
EVACUATION.
FEP.
FEP STAFF.
FIRE DRILL.
FLS.
FLS STAFF.
HIGH-RISE BUILDING.
HIGH-RISE FLOOR.
IN-BUILDING RELOCATION.
IN-BUILDING RELOCATION AREA.
LARGE-AREA BUILDING.
MIXED-OCCUPANCY BUILDING.
NON-FIRE EMERGENCY.
NON-FIRE EMERGENCY DRILL.
OFFICE BUILDING.
REGULAR BUSINESS HOURS.
SHELTER IN PLACE.
STAGED EVACUATION.
VOICE COMMUNICATION CAPABILITY.
Section FC 403. Public Gatherings
403.1 General.
The commissioner may establish requirements to ensure fire safety at indoor and outdoor public gatherings, including arcades, bazaars, cafes, carnivals, displays, entertainment, exhibits, rooftop events and street fairs. Such requirements may include preparation and submission to the department of a site plan, including identification of materials, operations and facilities regulated by the Fire Code that will be stored, conducted or maintained in conjunction with the public gathering; pre-event fire safety inspection; provision of fire guards or other qualified personnel; and provision and maintenance of fire apparatus access, and of aisles and other means of access to and egress from the public gathering. Persons conducting such fire watch shall have the duties and responsibilities set forth in FC 901.7.2.1 with respect to the areas being monitored in connection with public gatherings. The commissioner may conduct periodic inspections of public gathering places that are used or frequented on a regular basis.
403.2 Overcrowding prohibited.
Overcrowding shall not be caused, maintained or allowed in any indoor or outdoor area or space used for public gatherings.
403.3 Limitations on standing.
Where the Building Code, certificate of occupancy or approved seating plan allows audience members to stand at performing arts or other indoor or outdoor events at which seating is provided for the audience, standing areas shall be maintained in accordance with FC 407.5.
Section FC 404. Office Buildings
404.1 General.
Group B office buildings and occupancies shall comply with the emergency preparedness requirements set forth in FC 401, 416 and this section.
404.2 Emergency preparedness in office buildings and occupancies with comprehensive fire safety/emergency action plans.
Group B office buildings and occupancies required by FC 404.2.1 to have a comprehensive fire safety and emergency action plan shall comply with the emergency preparedness requirements of this section.
404.2.1 Comprehensive fire safety/emergency action plan (Level 1).
A comprehensive fire safety and emergency action plan in accordance with FC 401.4 shall be prepared for:
1. a high-rise or large-area Group B office building occupied or designed to be occupied by more than five hundred persons, or more than one hundred persons above or below the street level.
2. a Group B office occupancy occupied or designed to be occupied by a total of more than one hundred persons on one or more high-rise floors.
3. any other Group B office building, and any other Group B office occupancy, occupied or designed to be occupied by more than five hundred persons, or more than one hundred persons above or below the street level, that was required to have a fire safety director under the New York City Fire Prevention Code or this code prior to the effective date of this section.
4. any other Group B office building or occupancy as to which the commissioner determines that preparation of such a plan is in the interest of public safety given the location, use or occupancy of the building.
Exception: Office buildings and occupancies subject to FC 404.2.1(1), (2) and (3) that have lawfully installed a fire alarm system without voice communication capability.
404.2.2 Fire and life safety staff.
The comprehensive fire safety and emergency action plan required by FC 401.4 shall designate FLS staff consisting of an FLS director, deputy FLS directors, FLS building evacuation supervisors, FLS wardens, deputy FLS wardens, FLS brigade members and searchers, to exercise the authority and perform the duties of their respective FLS assignments. FLS staff shall be provided with initial and refresher FLS staff training in accordance with FC 401.4.5.2. FLS brigade members shall be trained in the use of portable fire extinguishers.
404.3 Emergency preparedness in office buildings and occupancies with fire and emergency preparedness plans.
Group B office buildings and occupancies required by FC 404.3.1 to have a fire and emergency preparedness plan shall comply with the emergency preparedness requirements of this section.
404.3.1 Fire and emergency preparedness plan (Level 2).
A fire and emergency preparedness plan in accordance with FC 401.5 shall be prepared for a Group B office building or occupancy occupied or designed to be occupied by more than five hundred persons, or more than one hundred persons above or below street level, other than buildings and occupancies subject to FC 404.2.
404.3.2 Fire and emergency preparedness staff.
The commissioner may prescribe by rule that, in Group B office buildings and occupancies that are provided with voice communication capability (other than buildings and occupancies subject to FC 404.2), there shall be present during regular business hours one or more members of the FEP staff required pursuant to FC 401.5.5 who hold a certificate of fitness for emergency announcements and other fire safety duties.
Section FC 405. Hotels, Motels and Other Transient Residential Occupancies
405.1 General.
Group R-1 buildings and occupancies, including any hotel, motel, boarding house, hostel and single room occupancy, shall comply with the emergency preparedness requirements set forth in FC 401, 405.2, 405.3, 405.5 and 416.
Exceptions:
1. Homeless shelters and emergency shelters, which shall comply with FC 401, 405.4, 405.5 and 416.
2. Dormitories operated by or affiliated with educational institutions, which shall comply with the requirements of FC 401, 410 and 416.
405.2 Emergency preparedness in transient residential buildings and occupancies with comprehensive fire safety/emergency action plans.
Group R-1 residential buildings and occupancies required by FC 405.2.1 to have a comprehensive fire safety and emergency action plan shall comply with the emergency preparedness requirements of this section.
405.2.1 Comprehensive fire safety/emergency action plan (Level 1).
A comprehensive fire safety and emergency action plan in accordance with FC 401.4 shall be prepared for:
1. a high-rise Group R-1 residential building, including hotels and club houses providing similar accommodation.
2. a Group R-1 residential building or occupancy with a total of more than fifty sleeping rooms above street level, or communal sleeping facilities above street level occupied or designed to be occupied by a total of more than fifty lodgers, and which is provided with voice communication capability.
405.2.2 Fire and life safety staff.
The comprehensive fire safety and emergency action plan required by FC 405.2.1 shall designate FLS staff consisting of an FLS director, deputy FLS directors and a sufficient number of FLS staff members to exercise the authority and perform the duties of their respective FLS assignments. FLS staff shall be provided with initial and refresher FLS staff training in accordance with FC 401.4.5.2. FLS staff members shall be trained in the use of portable fire extinguishers.
405.3 Emergency preparedness in transient residential buildings and occupancies with fire and emergency preparedness plans.
Group R-1 residential buildings and occupancies required by FC 405.3.1 to have a fire and emergency preparedness plan shall comply with the emergency preparedness requirements of this section.
405.3.1 Fire and emergency preparedness plan (Level 2).
A fire and emergency preparedness plan in accordance with FC 401.5 shall be prepared for a Group R-1 residential building or occupancy (other than buildings and occupancies subject to FC 405.2) with a total of more than thirty sleeping rooms, or more than fifteen sleeping rooms above street level, or communal sleeping facilities occupied or designed to be occupied by a total of more than thirty lodgers, or more than fifteen lodgers above the street level.
405.3.2 Fire and emergency preparedness staff.
The commissioner may prescribe by rule that in Group R-1 buildings and occupancies provided with voice communication capability (other than buildings and occupancies subject to FC 405.2) there shall be present during regular business hours one or more members of the FEP staff required pursuant to FC 401.5.5 who hold a certificate of fitness for emergency announcements and other fire safety duties.
Exception: Any Group R-1 residential building or occupancy with staged evacuation that was required by the New York City Fire Prevention Code or this code prior to the effective date of this section to have a fire safety director present in the building during regular business hours shall retain such staffing.
405.4 Emergency preparedness in homeless shelters and emergency shelters.
Group R-1 residential buildings or occupancies operated or occupied as a homeless shelter, and any emergency shelter, shall comply with the emergency preparedness requirements of this section.
405.4.1 Comprehensive fire safety/emergency action plan (Level 1).
A comprehensive fire safety and emergency action plan in accordance with FC 401.4 shall be prepared for a high-rise Group R-1 or high-rise Group I-1 homeless shelter.
405.4.2 Fire and life safety staff.
The comprehensive fire safety and emergency action plan required by FC 405.4.1 shall designate fire and life safety staff in accordance with FC 405.2.2.
405.4.3 Fire and emergency preparedness plan (Level 2).
A fire and emergency preparedness plan in accordance with FC 401.5 shall be prepared for a Group R-1 and GroupI-1 building or occupancy operated or occupied as a homeless shelter (other than buildings and occupancies subject to FC 405.4.1), and any emergency shelter.
405.4.4 Fire and emergency preparedness staff.
The fire and emergency preparedness plan required by FC 405.4.3 shall designate an FEP coordinator and a sufficient number of shelter coordinators, with such qualifications, duties and authority as set forth in the rules.
405.4.4.1 FEP coordinator and shelter coordinators.
The FEP coordinator and shelter coordinators designated in the fire and emergency preparedness plan shall hold the respective certificates of fitness for said duties, and shall have the following duties and responsibilities and such other duties and responsibilities as prescribed by rule:
1. The FEP coordinator shall have the duties and responsibilities set forth in FC 401.5.
2. The FEP coordinator or a shelter coordinator shall be present in the building at all times while the building is occupied. When the FEP coordinator is absent, a FEP shelter coordinator shall be present in the building and shall perform the emergency preparedness duties designated in the rules and the fire and emergency preparedness plan.
3. In the event of a fire, a medical emergency or other non-fire emergency, the FEP coordinator or the shelter coordinator on duty shall report to the fire command center or designated alternative location, and, if appropriate, implement the fire and emergency preparedness plan in accordance with its terms and the provisions of the rules, and notify arriving emergency response personnel and incident commander of the fire or non-fire emergency, the building response thereto, and the building's fire protection systems.
4. The FEP coordinator and shelter coordinators designated in the FEP plan shall be fully familiar with the provisions of the fire and emergency preparedness plan. The FEP coordinator shall conduct staff training and fire and non-fire emergency drills required by FC 401.
405.4.5 Fire guard patrols in emergency shelters.
Buildings or parts thereof occupied or operated to be occupied by emergency shelters shall be continuously patrolled by a fire guard. Every area of the building shall be patrolled at least once every hour.
405.5 Fire and emergency notice.
There shall be posted on or immediately adjacent to the main entrance door of guest rooms in Group R-1 buildings and occupancies and any emergency shelter a notice that provides the following information and guidance to building occupants, and/or such other information as the commissioner may prescribe by rule:
1. A visual representation of the location to each exit stairwell, the route thereto, and the number of doors opening onto the public corridor that must be passed to reach each such stairwell.
2. Location of manual fire alarm boxes.
3. A written description and/or visual representation of the procedures to be followed in the event of a fire, smoke condition or other emergency.
Section FC 406. Apartment Buildings
406.1 General.
Apartment buildings and other Group R-2 buildings and occupancies shall comply with the emergency preparedness requirements set forth in FC 401, 416 and this section.
406.2 Emergency preparedness in apartment buildings.
Apartment buildings and other Group R-2 buildings and occupancies shall comply with the following emergency preparedness requirements:
406.2.1 Fire emergency preparedness guide and notices (Level 3).
Fire and emergency preparedness guide and notices in accordance with FC 401.6 and the rules shall be prepared, and periodically reviewed and amended, for a Group R-2 building or occupancy.
406.2.2 Non-sequential or non-standard floor numbering.
The department shall promulgate rules establishing requirements for the electronic submission of floor numbering lists to the department by owners of Group R-2 buildings or occupancies that are 125 feet (38 100 mm) or more in height, and such other occupancies as the department may designate by rule. Such rules shall provide that each owner of a building with non-sequential or non-standard floor numbering, as defined by rule, shall submit to the department a floor numbering list indicating the floor numbers assigned to each floor, and submit an amended floor numbering list within 2 business days of a change in any floor numbering designation.
406.2.3 Hurricane evacuation notices.
The owner of any Group R-2 building or occupancy within a hurricane evacuation zone, as designated by the commissioner of the office of emergency management, shall cause a hurricane evacuation notice to be posted within the building or occupancy. Such notice shall serve to inform building occupants of the current hurricane evacuation zone designation for that building and the methodology for determining their closest hurricane evacuation centers, through 311 or the online Hurricane Evacuation Zone finder. Such notice shall be in such form as prescribed by the commissioner by rule and shall be posted within a common area of the building and such other locations as set forth in the rules.
(L.L. 2019/103, 6/8/2019, eff. 10/6/2019)
406.2.4 Fire and emergency preparedness plan (Level 2) and fire and emergency preparedness staff.
A fire and emergency preparedness plan in accordance with FC 401.5 shall be prepared for Group R-2 high-rise megastructure buildings and occupancies, in addition to compliance with the requirements of FC 401.6. There shall be present during regular business hours one or more members of the FEP staff required pursuant to FC 401.5.5 who hold a certificate of fitness for emergency announcements and other fire safety duties.
406.3 Responsibility of cooperative or condominium apartment owners.
In Group R-2 buildings and occupancies with a cooperative or condominium form of ownership and management, the board of directors, condominium association or other party generally responsible for maintenance of common areas shall be responsible for the preparation and distribution of the fire and emergency preparedness guide, the posting and maintenance of fire and emergency preparedness notices in common areas, and the preparation and distribution to individual dwelling unit owners or proprietary lessees of fire and non-fire emergency notices for dwelling unit doors, including instructions and the means for affixing the notice. The owners or proprietary lessees of the individual units in such residential buildings or parts thereof shall be responsible for the posting and maintenance of the fire and non-fire emergency notice on their respective dwelling unit doors. Such owners and proprietary lessees shall allow representatives of the building's management access to their individual dwelling units, upon reasonable notice, for purposes of confirming such owners and proprietary lessees' compliance with this section.
Section FC 407. Assembly Occupancies
407.1 General.
Group A occupancies and public gathering places, other than Group A occupancies operated or occupied exclusively for purposes of religious worship that have an occupant load less than two thousand, shall comply with the emergency preparedness requirements set forth in FC 401, 416 and this section. Such occupancies and places shall additionally comply with fire safety precautions required pursuant to FC 403.1.
407.2 Emergency preparedness in assembly occupancies with comprehensive fire safety/emergency action plans.
Group A occupancies required by FC 407.2.1 to have a comprehensive fire safety and emergency action plan shall comply with the emergency preparedness requirements of this section.
407.2.1 Comprehensive fire safety/emergency action plan (Level 1).
A comprehensive fire safety and emergency action plan in accordance with FC 401.4 shall be prepared for a Group A building with an occupancy of five thousand or more persons, or any other building or structure that houses one or more Group A occupancies where the combined occupancy of such Group A occupancies is five thousand or more persons.
407.2.2 Fire and life safety staff.
The comprehensive fire and emergency action plan required by FC 407.2.1 shall designate FLS staff consisting of an FLS director and such other FLS staff as the commissioner may prescribe by rule as appropriate for such building or occupancy. FLS staff shall be provided with initial and refresher FLS staff training in accordance with FC 401.4.5.2. The commissioner may prescribe by rule that there be present during regular business hours one or more members of the FLS staff who hold a certificate of fitness for place of assembly fire safety.
407.3 Emergency preparedness in assembly occupancies with fire and emergency preparedness plans.
Group A buildings or occupancies and public gathering places that are required by FC 407.3.1 to have a fire and emergency preparedness plan shall comply with the emergency preparedness requirements of this section.
407.3.1 Fire and emergency preparedness plan (Level 2).
A fire and emergency preparedness plan in accordance with FC 401.5 shall be prepared for a Group A building or occupancy or public gathering place not subject to FC 407.2 that:
1. is designed to be occupied by three hundred or more persons;
2. is provided with voice communication capability;
3. has a stage or in which entertainment or other activities that are the focus of attention are regularly conducted;
4. is occupied or designed to be occupied as a ballroom, dance hall or night club; or
5. is occupied or designed to be occupied as a bar, catering hall, restaurant or similar establishment, on one or more high-rise floors, including any rooftop area.
407.3.2 Fire and emergency preparedness staff.
The commissioner may prescribe by rule that in Group A buildings or occupancies and public gathering places that there be present during regular business hours one or more members of the FEP staff required pursuant to FC 401.5.5 who hold a certificate of fitness for place of assembly fire safety.
407.3.3 Assembly spaces without staff.
Halls or other assembly spaces that are rented or otherwise made available for events without dedicated staff, such as social halls in houses of worship and community organizations, are not required to prepare a fire and emergency preparedness plan pursuant to FC 407.3.1.
407.4 Seating plan.
A copy of the seating plan required for Group A occupancies by the Building Code shall be electronically submitted to the department prior to occupancy. A seating plan depicting the arrangement of seating in a place of assembly, location of aisles and such other information as may be required by rule shall be submitted in a manner prescribed by the department. A copy of the approved seating plan shall be maintained on the premises and made available for inspection by any department representative.
407.5 Limitations on standing in Group A occupancies and public gatherings.
Where the Building Code, certificate of occupancy or approved seating plan allows audience members to stand at performing arts or other indoor or outdoor events at which seating is provided for the audience, standing areas shall be maintained in accordance with FC 407.5.1 through 407.5.4.
407.5.1 Standing areas to be indicated.
The space to be occupied by standing audience members shall be separated from the space to be left clear for passage by a rope, tape or other thin material at a height of not less than 3 feet (914 mm) nor more than 4 feet (1219 mm) above the floor, supported by lightweight posts, all to be constructed and placed so as not to constitute an obstruction in case of panic or emergency. Such standing areas shall be clearly demarcated by durable markings on the floor indicating the boundaries of the standing area.
Exception: A single row of standees in an approved or other lawful area designated for such purpose in a performing arts theater, where the location for each such standee is durably marked in an approved manner.
407.5.2 Standing in aisles.
It shall be unlawful to stand, or allow any person to stand, in or at the head of an aisle.
407.5.3 Standing in passageways.
Standing is authorized in Group A occupancies and public gathering places in accordance with the following requirements.
1. If the passageway is more than 6 feet (1829 mm) and less than 16 feet (4877 mm) deep, persons may stand therein, provided an unobstructed passageway of at least 6 feet (1829 mm) in depth is left open, and there are no more than four rows of persons standing.
2. If the passageway is more than 16 feet (4877 mm) deep, any number of persons or rows of persons may stand therein, provided that an unobstructed passageway of at least 10 feet (3048 mm) in depth is left open.
3. In places of assembly having a passageway to the rear of the seats, 6 feet (1829 mm) or less in depth, and having in addition an outer passageway in the rear thereof, to which all aisle heads have straight and direct access, a maximum of two rows of persons may be permitted to stand in the passageway to the rear of such seats.
407.5.4 Standing in balconies.
Only one row of persons shall be allowed to stand in balconies.
407.6 Announcements.
In performing arts theaters or motion picture theaters, and in any other Group A occupancy in which there is a non-continuous performance or program, other than an occupancy regularly attended by the same audience, an audible announcement shall be made not more than 10 minutes prior to the start of each performance or program informing the occupants of the location of the exits to be used in the event of a fire or other emergency, provided, however, that in any theater the announcement may be projected upon a screen or other surface approved by the commissioner in a manner approved by the commissioner. Notwithstanding the foregoing, the commissioner may grant an exception from such requirement upon a determination that the occupancy has at least one exit clearly visible from every seat or standing area from which members of the audience are authorized to view the performance.
407.7 Trade shows.
The owner of any Group A occupancy wherein a trade show or other similar temporary exhibition is to be conducted shall, at least one month before the date of such exhibition, submit to the department a written notice and a plan containing the following information and such other information and documentation as the commissioner may prescribe:
1. The dates, times, location, and nature of the trade show or other exhibition, and whether the event will be open to the public or restricted to the trade.
2. The design and arrangement of the trade show or other exhibition, including aisles, display booths, decorations and drapes, and equipment using any hazardous material or open flame.