NYC Administrative Code Title 29, Chapter 2 New York City Fire Code, part 5 of 15

Section FC 608 to Section FC 904: 18 sections.

Section FC 608. Stationary Energy Storage Systems

Open this section

608.1 Scope.

This section shall govern stationary energy storage systems, including emergency power, standby power, uninterruptible power and mobile systems.

608.2. General.

Stationary energy storage systems shall be designed, installed, operated and maintained in accordance with this section, the rules, manufacturer's specifications, and, to the extent not inconsistent with this code and rules, NFPA 855, as modified by FC Appendix B.

608.3 Permits.

Permits shall be required as set forth in FC 105.6.

608.4 Testing and listing standards.

All stationary energy storage systems shall be tested and listed by a nationally recognized testing laboratory to the standards set forth in FC 608.4.1 through 608.4.3 (or later editions of these standards when necessary to address evolving standards applicable to a rapidly developing technology):

608.4.1 Listing standards.

Stationary energy storage systems shall be listed to the following standards:

1. Underwriters Laboratories (UL) Standard 1741 (2010 edition), entitled "Inverters, Converters, Controllers and Interconnection System Equipment for Use With Distributed Energy Resources;"

2. Underwriters Laboratories (UL) Standard 1973 (2018 edition), entitled "Batteries for Use in Light Electric Rail (LER) Applications and Stationary Applications;" and

3. Underwriters Laboratories (UL) Standard 9540 (2020 edition), entitled "Energy Storage Systems and Equipment."

Exceptions:

1. Any stationary energy storage system technology or application not subject to one or more of these listing standards shall comply with such other testing or listing standards as may be approved by the department.

2. A stationary energy storage system that received a listing under Underwriters Laboratories (UL) Standard 9540 (2016 edition) prior to the effective date of this section may be considered for a certificate of approval provided that such listing is still valid and the system was subjected to full-scale testing in accordance with FC 608.4.2.

3. A stationary energy storage system approved by the department under a listing standard superseded by a later edition may continue to be operated under such listing standard and department certificate of approval, provided that the listing is still valid and except as may be required by the department in accordance with FC 102.5.

608.4.2 Full-scale testing.

Stationary energy storage systems shall be subjected to full-scale testing (referred to as "large-scale testing" in NFPA 855) in accordance with ANSI/Underwriters Laboratories (UL) Test Method 9540A (4th edition), entitled "Test Method for Evaluating Thermal Runaway Fire Propagation in Battery Energy Storage Systems," or other approved test method, or its failure mode and effects documented by other approved test data.

608.4.3 Listing with installation conditions.

Upon approval by the department and the Department of Buildings of a listing standard that is used to establish listings with installation conditions based upon test data, such approved listing standard shall replace the existing listing and testing standards set forth in FC 608.4.1 and 608.4.2. The approved listing standard and listings shall supersede the equipment approval process set forth in FC 608.5 and, to the extent addressed in such approved listing, the required separation distances.

608.5 Equipment approval.

The design of each storage battery unit, including pre-engineered and pre-packaged systems, shall be approved by the department. The manufacturer of the storage battery unit shall obtain a certificate of approval for such unit in accordance with FC 112 and the rules. Application for a certificate of approval shall include the results of the full-scale testing of the storage battery unit in accordance with FC 608.4.2, including a failure modes and effects analysis (FMEA) or other approved hazard mitigation analysis. The certificate of approval may set forth terms and conditions for stationary energy storage system use. Such terms and conditions may authorize below-grade installation, or indoor installation in Group R-3 occupancies, based on the hazards demonstrated by the full-scale testing data and the mitigation thereof.

608.6 Installation approval.

The design of each stationary energy storage system installation shall be reviewed and approved by the department as required by FC 608.6.1 and 608.6.2.

608.6.1 Indoor systems.

Department review and approval of indoor system installations is required for systems utilizing equipment not approved by the department or not in accordance with the terms and conditions of the certificate of approval, equipment listing or requirements of this code. Otherwise, indoor system installation shall be reviewed and approved by the Department of Buildings in accordance with that agency's requirements, with department review and approval of energy storage management systems and monitoring stations, smoke control and smoke purge systems, explosion mitigation, and such fire protection and hazard mitigation systems and measures as are required to be reviewed by the department under this code or the construction codes.

608.6.2 Outdoor systems.

Department review and approval of outdoor system installations, including mobile and rooftop systems, shall be in accordance with the rules.

608.7 Supervision.

Stationary energy storage systems shall be operated and maintained under the supervision of a person holding the certificate of fitness required for such purpose.

608.7.1 Indoor systems.

Except as may be otherwise provided in the rules, indoor systems shall be operated and maintained under the general supervision of such certificate of fitness holder, provided, however, that an FLS director, FEP coordinator, certificate of qualification holder or other responsible person with approved qualifications shall be on the premises during the regular business hours in any building with an indoor system with an aggregate rated energy capacity of one megawatt (1 MWh) or more. Such person shall be responsible for assisting emergency responders, including coordinating with such certificate of fitness holder and the remote monitoring facility in accordance with the emergency management plan.

608.7.2 Outdoor systems.

Outdoor systems shall be operated and maintained under the general supervision of such certificate of fitness holder, except as may be otherwise provided in the rules.

608.7.3 Qualifications and responsibilities.

A certificate of fitness holder responsible for a stationary energy storage system shall possess the following qualifications and shall have the following duties and responsibilities and such other duties and responsibilities as may be set forth in the notice of examination for such certificate:

1. Be trained and knowledgeable in the installation and operation of the stationary energy storage system, such as a person engaged in the design or installation of such systems;

2. Possess the manufacturer's installation and operating specifications for each stationary energy storage system and any associated fire protection systems;

3. Immediately report any emergency condition affecting a stationary energy storage system to the department; and

4. Provide technical assistance about the stationary energy storage system installation to the department in accordance with FC 608.8 and the rules, and, in coordination with the energy storage management system monitoring facility, identify a subject matter expert who can provide technical assistance about the stationary energy storage system's design and performance in the event of an emergency condition affecting the stationary energy storage system.

608.8 Emergency management plan.

The owner, manufacturer and/or installer of a stationary energy storage system shall have an emergency management plan or protocol that includes procedures for notifications, provision of technical assistance to the department, mitigation of hazardous conditions, and decommissioning or restoration to normal operation. The department may require that a representative of the stationary energy storage system manufacturer or other subject matter expert with technical knowledge of the system and its operation be available in a timely manner to provide technical assistance to the department during an emergency involving or affecting the system.

608.9 Design and installation.

Stationary energy storage systems shall comply with the requirements set forth in FC 608.9.1 through 608.9.4.

Exception: Lead acid and nickel-cadmium stationary energy storage systems with a maximum operating voltage of 50 volts alternating current or 60 volts direct current, designed and installed for the purpose of supplying emergency power, standby power or uninterruptible power to telecommunications equipment under the exclusive control of a telecommunications provider, when such systems are located outdoors or in an indoor telecommunications facility used exclusively for powering telecommunications equipment, and are in compliance with the requirements of NFPA 855, as adopted and modified by the Department of Buildings, and NFPA 76.

608.9.1 Maximum aggregate rated energy capacity.

The maximum aggregate rated energy capacity of stationary energy storage systems shall be in accordance with FC 608.9.1.1 and 608.9.1.2.

608.9.1.1 Indoor systems.

The aggregate rated energy capacity per control area of indoor systems shall not exceed the limitations set forth in FC Table 608.9.1.1.

FC Table 608.9.1.1 Maximum Aggregate Rated Energy Capacity of Indoor Stationary Energy Storage Systems

Type of Storage Battery Maximum Aggregate Rated Energy Capacity (kWh) per Control Area a, b Lead-acid, all types 600 c Nickel, all types except sodium nickel chloride 600 c Lithium-ion, all types 400 Sodium nickel chloride 400 Flow 400 Other As prescribed by rules or approved by the department

a. Subject to the control area limitations set forth in FC Table 5003.8.3.3

b. The control areas on a floor of a dedicated use building, other than on a high-rise floor, may be combined or otherwise modified, provided that the total maximum aggregate rated energy capacity of indoor systems allowed per floor is not exceeded.

c. Except where a greater maximum aggregate rated capacity is allowed per floor by FC 608.9.4.1.10.

608.9.1.2 Outdoor systems.

The aggregate rated energy capacity of outdoor stationary energy storage systems (including mobile systems) shall be as approved by the department, unless the department prescribes by rule a maximum aggregate rated energy capacity for such systems.

608.9.2 Energy storage management system monitoring.

All stationary energy storage systems shall be designed with an energy storage management system that transmits data regarding energy storage system status and temperature to a remote monitoring facility or other approved location. Indoor systems shall be provided with approved remote monitoring stations at the building's fire command center and/or other approved location.

608.9.3 Fire protection and hazard mitigation.

Stationary energy storage systems shall be designed to address the hazards identified by full-scale testing, including protecting the stationary energy storage system and the building or enclosure that houses such system with, as applicable, fire barriers, fire alarm systems, explosion mitigation, gas detection and other emergency alarm systems, fire extinguishing systems and ventilation systems.

608.9.3.1 Indoor systems.

Indoor systems shall be provided with the fire protection and hazard mitigation systems and measures required by the conditions of the system's listing and equipment approval, this section, the construction codes, the Electrical Code and the rules.

608.9.3.2 Outdoor systems.

Outdoor systems shall be provided with the fire protection and hazard mitigation systems and measures required by the rules.

608.9.4 Location.

Stationary energy storage systems shall be installed in accordance with the location requirements and restrictions set forth in FC 608.9.4.1 and 608.9.4.2.

608.9.4.1 Indoor systems.

Indoor systems shall be installed in accordance with FC 608.9.4.1.1 through 608.9.4.1.9.

608.9.4.1.1 Below-grade locations.

Indoor systems shall not be installed below grade, except when approved by the department in a dedicated use building, or as otherwise approved pursuant to FC 608.5.

608.9.4.1.2 Sprinkler protection required.

Indoor systems may be installed only in buildings fully protected throughout by a sprinkler system, except as otherwise provided in FC 608.9.4.1.9. Control areas housing stationary energy storage systems shall be fully protected throughout by a sprinkler system designed in accordance with NFPA 15, except as may otherwise be approved based on equipment listings and testing results pursuant to FC 608.4.

608.9.4.1.3 Occupancy restrictions.

Indoor systems may be installed in Group A, Group R-1, Group R-2 and Group I buildings and occupancies only when the building is of noncombustible construction, except as otherwise provided in FC 608.9.4.1.9.

608.9.4.1.4 Control areas.

Indoor systems shall be installed only in control areas designed, installed, operated and maintained in accordance with this section. The maximum aggregate rated energy capacity of indoor systems per control area shall be in accordance with FC 608.9.1. The design and number of control areas per floor shall be in accordance with FC 5003.8.3.3, including FC Table 5003.8.3.3, except that (subject to FC 608.9.4.1.9 and FC 608.9.4.1.10) each control area housing an indoor stationary energy storage system shall be designed and constructed as a high-hazard occupancy, and rooftop installations shall be treated as outdoor installations.

608.9.4.1.5 Smoke detection.

Control areas housing stationary energy storage systems shall be protected by a fire alarm system or, if a fire alarm system is not otherwise required in the building or occupancy, by a dedicated smoke detection system.

608.9.4.1.6 Ventilation.

Control areas housing stationary energy storage systems shall be equipped with ventilation systems designed for high-hazard occupancies in accordance with the construction codes. Such ventilation systems shall be adequate to exhaust any flammable or other gases generated during the normal operation and/or failure of the stationary energy storage system.

608.9.4.1.7 Spill control, neutralization, drainage and containment.

Control areas housing stationary energy storage systems shall be provided with a means to control leaks and spills of liquid electrolyte and such containment and drainage systems as may be required by the construction codes and NFPA 855, as modified by FC Appendix B.

608.9.4.1.8 Emergency power.

All fire protection and hazard mitigation systems required by this section shall be provided with an emergency power system in accordance with the Building Code.

608.9.4.1.9 Exceptions for certain battery systems for fire and life safety.

Lead acid battery systems, and nickel-cadmium battery systems, and where approved by the certificate of approval based on their testing results, other types of energy storage systems, designed and installed solely for the purpose of supplying emergency or standby power for building fire safety and life safety systems in accordance with the construction codes and this code may be:

1. installed in buildings that are not protected throughout by a sprinkler system.

2. installed in buildings of combustible construction.

3. housed in control areas that are not constructed as high-hazard occupancies but meet such fire separation standards as may be set forth in the construction codes.

608.9.4.1.10 Exceptions for certain battery systems for business operations.

The exceptions set forth in FC 608.9.4.1.9 shall also be applicable to lead acid battery systems and nickel-cadmium battery systems, not exceeding a maximum aggregate rated energy capacity of 70 kWh per floor, and where approved by the certificate of approval, other types of energy storage systems, designed and installed for the purpose of supplying emergency power, standby power or uninterruptible power, for business operations, in accordance with the construction codes and this code.

608.9.4.2 Outdoor systems.

Outdoor systems, including reach-in and walk-in facilities and mobile systems, shall be designed and installed in accordance with the rules. Rooftop systems with an aggregate rated energy capacity exceeding 400 kWh, other than lead acid battery systems, may be installed only on the rooftops of buildings of noncombustible construction.

608.10 Commissioning and decommissioning.

Stationary energy storage systems shall be installed and activated for use (commissioned) and deactivated from use and removed from the premises (decommissioned) in accordance with this section, the rules and NFPA 855, as modified by FC Appendix B.

608.10.1 Commissioning.

Stationary energy storage systems shall be installed by trained and knowledgeable persons in accordance with manufacturer's specifications. Upon completion of the installation, the certificate of fitness holder assuming responsibility for supervision of the system shall authorize it to be activated, after confirming that the energy storage system is in good working order and operating in accordance with manufacturer's specifications. Approved fire protection, smoke control and smoke purge, and hazard mitigation systems and measures installed to protect the system shall also be inspected and tested by a person holding the qualifications required by this code, the construction codes and/or the Electrical Code, and any required acceptance testing conducted, prior to activation of the system.

608.10.2 Decommissioning.

The certificate of fitness holder supervising a stationary energy storage system shall be responsible for its decommissioning. The deactivation, de-energizing, dismantling and removal of the system shall be conducted by trained and knowledgeable persons in accordance with manufacturer's specifications. The owner, manufacturer, installer, hazardous materials carrier or other party responsible for removal, transportation and/or disposal of the stationary energy storage system shall ensure that the energy storage system is lawfully decommissioned, transported and disposed of in accordance with DOTn hazardous materials regulations and other applicable laws, rules and regulations.

608.10.3 Notice to department.

Notice of the commissioning and decommissioning of stationary energy storage systems shall be given to the department¸ and the removal of a malfunctioning system coordinated with the department, in accordance with the rules.

608.11 Operation and maintenance.

Stationary energy storage systems shall be operated and maintained in accordance with FC 608.11.1 through 608.11.6.

608.11.1 Remote monitoring of energy storage management system and reporting.

Except for telecommunications equipment subject to the exception set forth in FC 608.9, the owner of a stationary energy storage system shall arrange for data transmissions from the energy storage system's energy storage management system to be continuously monitored (on a 24/7 basis) by a remote monitoring facility staffed by trained and knowledgeable persons retained by the manufacturer or installer of the energy storage system. The remote monitoring facility shall, without delay, make all necessary notifications, as required by the rules and the emergency management plan, including notifications to the department, the certificate of fitness holder and the subject matter expert, in the event a stationary energy storage system installed in New York City exceeds or appears likely to exceed thresholds at which fire, explosion or other serious adverse consequences may result.

608.11.2 Central station monitoring of fire protection systems.

All fire protection systems protecting the stationary energy storage system installation, including any fire extinguishing system, and fire and gas detection or other emergency alarm system, shall be monitored by an approved central station.

608.11.3 Signage.

Stationary energy storage systems shall be identified by signs or markings in accordance with the rules. The department may require that such signs and markings provide required warnings, location of controls, emergency shut down procedures, energy storage management system monitoring facility and other emergency contact information, and other necessary information.

608.11.4 Maintenance.

The owner shall ensure that stationary energy storage systems are periodically inspected, tested, serviced and otherwise maintained in accordance with manufacturer's specifications and the requirements of this section by a person trained and knowledgeable in the specific system. The department may prescribe by rule stationary energy storage system periodic inspection requirements.

608.11.5 Restoration to service after serious failure.

Any stationary energy storage system that undergoes a serious failure, including one that results in a fire, release of flammable or toxic gas, and/or physical damage to system components, shall be removed from service forthwith. The stationary energy storage system shall not be restored to service until it has been evaluated and, if necessary, repaired or replaced, by a trained and qualified person, and recommissioned by the certificate of fitness holder responsible for the system.

608.11.6 Replacement components.

Any replacement storage battery units or other stationary energy storage system components shall be designed for the same storage battery technology and/or chemistry and be compatible with the existing energy storage system installation. In-kind replacement of existing components (consistent with the listing for the storage battery unit or stationary energy storage system) constitutes maintenance and does not require department review and approval. Department review and approval, and, as applicable, Department of Buildings review and approval, is required in the same manner as an application for a new stationary energy storage system installation for replacement of existing components that effect an alteration of the energy storage system, including:

1. replacement of components included in the storage battery unit listing, or that could otherwise affect the results of the full-scale testing of the battery storage unit;

2. replacement components that use different battery technologies or chemistries (including the electrolyte chemistry in a flow system); and

3. replacement components that change the storage/generating capacity or other functionality of the stationary energy storage system.

608.12 Recordkeeping.

A written record of the following information shall be maintained at the premises or other approved location by the certificate of fitness holder and by the owner or operator of the stationary energy storage system, except as otherwise prescribed by the department by rule:

1. Stationary energy storage system installation and commissioning;

2. Stationary energy storage system maintenance, including all inspections, servicing and repair;

3. Stationary energy storage system decommissioning and removal;

4. Installation and maintenance of stationary energy storage system fire protection systems, including all inspection, testing, servicing and repair; and

5. Fires or other incidents involving or affecting the stationary energy storage system.

608.13 Group R-3 occupancies.

Stationary energy storage systems installed in or on the premises of Group R-3 occupancies (indoor and outdoor systems) shall comply with the foregoing provisions of this section, except as follows:

1. Notwithstanding any provision of FC 608.7 to the contrary, both indoor systems and outdoor systems shall be operated and maintained under the general supervision of such certificate of fitness holder.

2. In lieu of FC 608.9, the following provisions shall apply to the design and installation of stationary energy storage systems in a Group R-3 dwelling and any attached or detached garage space serving such a dwelling:

2.1. No indoor system shall be installed below grade in such a dwelling or garage except when approved by the department.

2.2. No indoor system shall be installed in such a dwelling except when approved for such installation by its certificate of approval based on UL9540 listing meeting the performance-cell level test requirements of UL9540A or as otherwise approved pursuant to FC 608.5.

2.3. The maximum rated energy capacity of any storage battery in an energy storage system installed in such a dwelling, attached garage or detached garage or mounted outdoors on an exterior wall thereof, shall not exceed 20 kWh, and the maximum aggregate rated energy capacity of such energy storage system shall not exceed the following amounts:

2.3.1 in any such dwelling, 20 kWh per dwelling unit, except as may be approved by the department; or

2.3.2 in any such attached garage, or when mounted outdoors on an exterior wall of such a dwelling or attached garage, 40 kWh, provided that there is an approved two-hour fire barrier separating such indoor system or wall mounted installation from the dwelling, or other approved measure based on the testing results of the energy storage systems; or

2.3.3 in any such detached garage, or mounted on an exterior wall thereof, 40 kWh.

2.4. Indoor systems installed in such a dwelling shall be protected by a one-hour fire barrier. Indoor systems shall otherwise be located, installed and protected in such dwellings and garages in accordance with the construction codes, the Electrical Code and the rules.

2.5. Indoor systems shall be equipped with an energy storage management system in accordance with FC 608.9.2.

3. Outdoor systems shall be designed and installed in accordance with the rules.

Section FC 609. Commercial Cooking Systems

Open this section

609.1 General.

Commercial cooking systems shall be designed, installed, operated and maintained in accordance with this section.

609.2 Unlawful operation.

It shall be unlawful to operate a commercial cooking appliance that generates smoke or grease-laden vapors, smoke or fumes:

1. without a permit for the operation of the commercial kitchen in which the commercial cooking appliance is installed.

2. when the appliance is not an approved commercial cooking appliance.

3. when the appliance is a portable fueled device, unless otherwise authorized by the department.

4. without an approved, lawfully-installed and tested fire extinguishing system.

5. without an approved and lawfully-installed exhaust system.

6. without the required grease filters.

7. when its fire extinguishing system or exhaust system is out of service.

8. when the operation of a commercial cooking appliance is unsafe due to excessive grease accumulation on or in such appliance or in the commercial cooking exhaust system.

609.3 Supervision.

Commercial cooking appliances shall be attended at all times while in operation. A person holding a certificate of fitness shall supervise commercial cooking system cleaning and fire protection.

609.3.1. Cleaning of commercial cooking exhaust system.

Commercial cooking exhaust systems shall be cleaned by a company holding a company certificate and persons employed by such company who hold a certificate of fitness, except that ductless hoods may be inspected and cleaned by the owner or trained and knowledgeable employees of the owner.

609.3.1.1 Commercial cooking cleaning company.

It shall be unlawful for any person engaged in the business of inspecting and cleaning commercial cooking exhaust systems as required by the provisions of this code to perform such services without a commercial cooking exhaust system servicing company certificate. Such cleaning company shall possess the vehicles, tools, equipment and supplies required to perform such services.

609.3.1.2 Certificate of fitness.

All persons engaged in the cleaning of commercial cooking exhaust systems, including any individual who assists such persons, shall hold a certificate of fitness for that purpose.

609.3.2 Commercial cooking fire extinguishing system.

Fire extinguishing systems protecting commercial cooking systems in accordance with FC 904 shall be maintained in accordance with FC 904.5 by a master fire suppression piping contractor holding a certificate of fitness in accordance with FC 901.6.3.

609.4 Commercial cooking appliances.

Commercial cooking appliances shall be designed and installed in accordance with FC 609.4.1 through 609.4.3.

609.4.1 Design and installation.

Commercial cooking appliances requiring a fire extinguishing system shall be designed and installed in accordance with the construction codes, including the Mechanical Code and Fuel Gas Code, and the Electrical Code. Commercial cooking appliances shall not be relocated, or replaced with appliances utilizing a different power source, change in gas valve, or other change affecting the design of the commercial cooking fire extinguishing system, without prior department approval.

609.4.1.1 Deep fat fryers.

Deep fat fryers shall be designed and installed in accordance with this section.

609.4.1.1.1 Separation.

Deep fat fryers shall be separated from any adjacent cooking equipment that uses an open flame by:

1. A separation distance of at least 16 inches (406 mm); or

2. A 16-inch (406-mm) high by 1/8-inch (3.2-mm) thick steel baffle permanently attached to the longer of the two adjacent cooking appliances. The baffle shall extend to the full depth of the cooking equipment to which it is attached; or

3. A combination of separation distance and baffle height equal to at least 16 inches.

609.4.1.1.2 High-limit controls.

Deep fat fryers shall be equipped with an independent high-limit control in addition to the adjustable operating control (thermostat). Such high-limit control shall be designed and installed to shut off the fuel supply, including electrical energy, when the temperature of the fat 1 inch (25 mm) below the liquid surface reaches a temperature of 475°F (246°C). All high-limit controls shall be replaced every 3 years with a new or rebuilt device certified by the manufacturer to activate at the designated temperature of 475°F (246°C).

609.4.1.2 Solid fuel burning appliances.

Commercial cooking appliances burning solid fuel shall be installed on floors of noncombustible construction that extend 3 feet (914 mm) from the cooking equipment in all directions. Cooking equipment burning solid fuel shall not be installed within 3 feet (914 mm) horizontally of combustible surfaces or construction, or within 6 feet (1829 mm) vertically of such surfaces or construction.

609.4.2 Solid fuel commercial cooking operations.

Solid fuel commercial cooking operations shall additionally comply with the requirements of FC 609.4.2.1 through 609.4.2.5. Unless otherwise approved by the Department of Buildings, the burning of solid fuel, such as briquettes, mesquite, hardwood, or charcoal, in commercial cooking appliances shall be allowed only for purposes of flavor enhancement. The use of solid fuel for flavor enhancement shall be in accordance with NFPA 96, including the use of a listed smoker box.

609.4.2.1 Solid fuel storage.

Solid fuel used for commercial cooking operations shall be stored in accordance with FC 315.7.

609.4.2.2 Lighting.

Solid fuel shall be ignited with a match or other approved means. Combustible or flammable liquids shall not be used. Matches shall not be stored in the immediate vicinity of cooking equipment.

609.4.2.3. Handling.

Solid fuel shall be added to the fire in a safe manner and only in quantities that will not create a flame higher than required. Long-handled tongs, hooks and other required devices shall be provided and used in order to safely add fuel, adjust the fuel, position and control the fire without having to reach into the fire box.

609.4.2.4 Water supply.

A water supply with a flexible hose shall be readily available to solid fuel commercial cooking appliances and masonry ovens to cool down any fire that becomes too hot and to completely extinguish any fire at the conclusion of cooking operations. The water source shall be a fixed pipe system with a hose of adequate length to reach to the combustion and cooking chambers of the appliance. The nozzle shall be equipped with a manual shutoff device, and shall be of the type to provide a fine to medium spray. A full flow or strong stream shall not be used to cool down and extinguish any cooking fire.

609.4.2.5 Spent fuel.

Spent fuel, ash, cinders and other fire debris shall be removed from the fire box at regular intervals, but at least once a day, and, once removed, shall not be stored indoors. Adequate long handle rakes, hoes, scrapers and shovels shall be provided for such removal. When being removed from the fire box, the spent fuel shall be wetted down and cooled with water from the required water supply. Metal containers with covers shall be used when transporting such spent fuel removal. Such metal containers shall be of a minimum 16 gauge construction and shall be limited in size to a capacity not exceeding 20 gallons (75.7 L), so as to facilitate easy handling by any employee assigned to the task and to enable such containers to easily pass through any door or passageway. The spent fuel shall be placed outdoors in a dumpster or heavy metal container with a lid or cover used exclusively for this purpose and kept closed at all times. Such dumpster or container shall be kept separate from combustible construction, combustible materials and combustible waste.

609.4.3 Movable commercial cooking appliance markings.

The designated location for movable (wheeled) commercial cooking appliances shall be outlined on the floor in durable 1-inch (25-mm) wide yellow line markings or other approved means. Such location shall be determined in relation to the location of the fire extinguishing system nozzle protecting such movable commercial cooking equipment. The owner or operator of a commercial cooking system shall ensure that each movable appliance is positioned at its designated location before commencing cooking.

609.5. Commercial cooking exhaust system.

Commercial cooking exhaust systems, including the hood, grease filters, ducts, exhaust fans and emission control devices, shall be designed and installed in accordance with the construction codes, including the Mechanical Code, the Electrical Code and this code.

609.5.1 Design and installation.

Commercial cooking exhaust systems shall be designed and installed in accordance with FC 609.5.1.1 through 609.5.1.5.

609.5.1.1 Exhaust hoods.

Commercial cooking systems shall be equipped with a Type I hood suitable for commercial cooking appliances in accordance with Mechanical Code. Prefabricated hoods shall be of a type for which a certificate of approval has been issued in accordance with FC 112 and the rules. Exhaust hoods shall not be painted and scratch protection sheeting shall be removed.

609.5.1.2 Exhaust ducts.

Commercial cooking exhaust ducts shall be provided with clean out openings in accordance with Mechanical Code, to allow for cleaning and other maintenance. The department may require installation of additional access panels when the department determines, based on a report from a commercial cooking exhaust system cleaning company or other good cause, that there is inadequate access to conduct a proper cleaning of the system. The department shall give the owner notice and an opportunity to be heard prior to ordering compliance with any such determination; evaluate objections asserted on the basis on engineering considerations and impracticability; and address proposed alternatives.

609.5.1.3 Emission control devices.

When required by the Air Pollution Code, commercial cooking systems shall be equipped with a precipitator or other emission control device of a type for which a certificate of approval has been issued in accordance with FC 112 and the rules.

609.5.1.4 Ductless hoods.

Ductless hoods shall be of a type for which a certificate of approval has been issued in accordance with FC 112 and the rules.

609.5.1.5 Grease filters.

Grease filters shall be of a type for which a certificate of approval has been issued in accordance with FC 112 and the rules.

609.5.2 Operation.

Commercial cooking exhaust systems shall be operated in accordance with FC 609.5.2.1 through 609.5.2.5.

609.5.2.1 Operation during cooking.

The exhaust system shall be in operation at all times whenever a commercial cooking appliance is in use. The exhaust system shall continue to operate as designed in the event of an automatic or manual activation of the fire extinguishing system, with the exception of any emission control device designed to shut off in the event of fire.

609.5.2.2 Maintenance of airflow.

The required rate of exhaust airflow for the commercial cooking exhaust system shall be maintained at all times. Fixed air supply openings installed to provide make-up air for air exhausted through the exhaust system shall not be restricted by covers, dampers, or any other means that would reduce the operating efficiency of the exhaust system. The department may require that the exhaust system be tested in accordance with the Mechanical Code if, upon inspection, the exhaust airflow appears to be insufficient to allow proper exhausting of grease vapors, steam, fumes, smoke and/or odors.

609.5.2.3 Grease filters.

Approved grease filters shall be in place in the proper position at all times when cooking appliances are in use.

609.5.2.4 Grease extractors.

When installed, grease extractors and other grease removal devices, equipment and systems shall be operated at all times while cooking equipment is in use.

609.5.2.5 Combustible materials.

Combustible materials shall not be placed on the exhaust hood, other than the required proof of compliance.

609.5.3 Cleaning and other maintenance.

The entire exhaust system, including exhaust hoods, grease filters, grease extractors, exhaust ducts, exhaust fans, emission control devices, and other exhaust system components, shall be inspected and cleaned in accordance with FC 609.5.3.1 through 609.5.3.6.

609.5.3.1 Frequency of exhaust system inspection.

The entire exhaust system shall be inspected with a minimum frequency as set forth in FC Table 609.5.3.1, except as otherwise provided in the rules:

FC Table 609.5.3.1 Commercial Cooking Exhaust System Inspection

Type of Commercial Cooking or Cooking Device / Equipment / System a Minimum Frequency of Inspection Qualifications All commercial cooking exhaust systems, except ductless hoods Every 3 months Approved cleaning company Ductless hoods In accordance with the terms and conditions of the certificate of approval and the manufacturer's instructions but not less than once every three months Trained/knowledgeable person Grease filters Daily Trained / knowledgeable person High-volume cooking Weekly Trained / knowledgeable person Every three months Approved cleaning company Solid fuel cooking Monthly Trained / knowledgeable person Commercial cooking appliance exhaust flue Annually Trained / knowledgeable person

a. Emission control devices shall be inspected in accordance with the inspection frequency for the commercial cooking system for which the device has been installed.

609.5.3.2 Cleaning of grease filters and other grease removal devices.

Grease filters and other grease removal devices associated with a commercial cooking system shall be cleaned in accordance with FC 609.5.3.2.1 through 609.5.3.2.3.

609.5.3.2.1 Grease filters.

Grease filters shall be inspected daily by a trained and knowledgeable person, and cleaned as necessary by such a person, but at least once a month. Additionally, grease filters shall be cleaned at the end of the workday when high-volume cooking is being conducted and/or when grease accumulation exceeds 1/8 inch (3.175 mm) as measured by a depth gauge comb or other approved device.

609.5.3.2.2 Charcoal grease filters.

Charcoal filters in emission control devices shall be replaced by a person holding a certificate of fitness for emission control device cleaning, in accordance with the terms and conditions of the certificate of approval, if specified therein, or the manufacturer's instructions, but not less than once every 3 months.

609.5.3.2.3 Grease removal devices.

Grease traps, grease extractors and other grease removal devices, equipment and systems shall be cleaned by a trained and knowledgeable person, as necessary, in accordance with manufacturer's instructions, but at least once a week for grease traps and at least once a month for all other types of devices.

609.5.3.3 Exhaust system cleaning.

The commercial cooking exhaust system, including the hood, ducts, fans and air emission control devices, shall be cleaned by an approved cleaning company in accordance with the following requirements, except as otherwise provided in the rules:

FC Table 609.5.3.3 Commercial Cooking Exhaust System Cleaning

Type of Commercial Kitchen Cleaning Required Minimum Frequency of Cleaning High-volume cooking All hoods; all exhaust ducts and fans for a distance of 3 floors above such kitchen; all exhaust duct elbows and other horizontal portions on all floors; and all emission control devices Every 3 months Exhaust ducts and fans on floors more than 3 floors above such kitchen Every 3 months All other commercial kitchens All hoods; all exhaust ducts and fans for a distance of 3 floors above such kitchen; all exhaust duct elbows and other horizontal portions on all floors; and all emission control devices Every 3 months Exhaust ducts and fans on floors more than 3 floors above such kitchen Every 6 months All commercial kitchens All affected areas. Such cleaning shall not replace the regularly scheduled cleaning (and the existing frequency of cleaning shall be maintained) unless a complete cleaning of the commercial cooking system (as set forth above) is conducted Additional cleaning when grease accumulation in the commercial cooking exhaust system exceeds 1/8 inch (3.175 mm)

609.5.3.4 Standard for cleaning.

Surfaces shall be cleaned to bare metal. The powder residue or other foreign substance left by saponifying agents or other cleaning materials shall be removed. Flammable cleaning fluids shall not be used. Cleaning fluids shall not be applied to fusible links or other detection devices of the fire extinguishing system.

609.5.3.5 System deactivation.

Unless necessary to accomplish cleaning, components of the fire extinguishing system shall not be rendered inoperable during the cleaning process. If electrical switches, detection devices, or other components of the fire extinguishing system must be deactivated during the cleaning process, such deactivation shall be performed by a licensed master fire suppression piping contractor. Immediately upon completion of the cleaning process the licensed master fire suppression piping contractor shall restore the system to good working order. Electrical switches that may be accidentally activated during the cleaning process shall be electrically locked out during such process.

609.5.3.6 Responsibility.

The owner shall ensure that the commercial cooking exhaust system is inspected, cleaned and serviced by a commercial cooking cleaning company holding a commercial cooking exhaust system servicing company certificate as required by this section. The commercial cooking cleaning company shall be responsible for inspecting, cleaning and servicing the commercial cooking exhaust system in accordance with the standards and requirements of this section. The owner shall be responsible for the owner's cleaning of a commercial cooking system when such cleaning is authorized by this section and shall be held to the same standard as a commercial cooking cleaning company.

609.5.3.7 Proof of compliance.

The approved commercial cooking cleaning company shall document its cleaning of the commercial cooking exhaust system by affixing to each exhaust hood the proof of compliance approved for such purposes, and in such other manner as may be required by the rules.

609.5.4 Exposed ducts.

Commercial cooking exhaust system ducts not concealed within walls and ceilings shall be periodically inspected for defects, and defective ducts repaired or replaced to maintain their integrity. The inspection shall include the condition of the insulation, and confirm the absence of deterioration or cracking of the duct, which would allow the release of grease vapors, steam, fumes, smoke or odors.

609.6 Commercial cooking fire extinguishing systems.

Commercial cooking appliances shall be protected by a commercial cooking fire extinguishing system in accordance with the Building Code and FC 904.

609.6.1 Acceptance testing.

Commercial cooking fire extinguishing systems shall be subject to an acceptance test in accordance with FC 904.3.8.

609.6.2 Periodic inspection.

A visual inspection of a commercial cooking fire extinguishing system shall be conducted at least once a month by a trained and knowledgeable person in accordance with FC 904.5.1 to confirm that the system appears to be in good working order, including the following conditions:

1. The fire extinguishing system is intact and undamaged, including the extinguishing agent container, system piping, nozzles and protective nozzle caps.

2. The fire extinguishing system is charged and operational. Check the pressure gauge and/or control head (on a wet chemical system) to confirm that system is operational and the extinguishing agent has not been discharged. On other systems monitored by a fire alarm system, check the fire alarm system control panel to confirm that there are no supervisory or trouble signals.

3. The fusible links or other heat detection devices are not coated with grease.

4. Any movable commercial cooking appliances are in position under the proper fire extinguishing system nozzle, in accordance with approved floor markings, so that the nozzles are centered over the commercial cooking appliance.

5. Access to the manual activation device for the commercial cooking fire extinguishing system is not obstructed and the tamper indicator is intact.

6. The maintenance tag is in place for the commercial cooking fire extinguishing system and has not expired.

609.6.3 Inspection, testing and other maintenance by certificate of fitness holder.

A master fire suppression piping contractor holding a certificate of fitness for fire extinguishing systems, who is trained and knowledgeable in the installation, operation and maintenance of the specific fire extinguishing system, shall inspect, test, service and otherwise maintain such system in accordance with FC 904.5.2.

609.7 Signage.

The following signage, legibly printed and laminated or framed under a clear glass or plexiglas cover, shall be posted in accordance with FC Table 609.7 at a conspicuous location near the entrance to each kitchen or other separate cooking area that is a commercial kitchen.

FC Table 609.7 Commercial Cooking Fire Extinguishing and Exhaust System Signage

Content of Sign Minimum Size Location Purpose Exhaust system diagram (origin, run, and terminus of the exhaust system) 8 1/2" x 11" Immediately outside of main entrance to each kitchen Assist firefighting personnel Location of emission control devices (type, model and exact location) 3" x 5" Adjacent to exhaust system diagram Assist firefighting personnel Identification of emission control device, including, if applicable, high voltage warning in accordance with the Electrical Code 3" x 5" On or adjacent to each emission control device Assist firefighting personnel Operation/maintenance (approved summary of operating and cleaning instructions) 8 1/2" x 11" Immediately inside main entrance to each kitchen Kitchen staff instructions Instructions for fire extinguishing system manual activation 3" x 5" Adjacent to each manual activation device Kitchen staff instructions Portable fire extinguisher warning sign (to activate fire extinguishing system prior to portable fire extinguisher use) 3" x 5" Adjacent to each kitchen portable fire extinguisher Kitchen staff instructions

609.8 Staff training.

The owner or operator of a commercial cooking system shall train all staff, at time of employment, in the proper procedure for the use and cleaning of all grease removal devices, including the cleaning or replacement of grease filters, and the manual operation of the commercial cooking fire extinguishing system. Refresher training shall be provided at least once every 6 months.

609.9 Portable fire extinguishers.

Each commercial kitchen shall be provided with one or more Class K portable fire extinguishers, which shall be readily available for use in the cooking area but in any event no further than 30 feet (9144 mm) of travel distance from any commercial cooking appliance.

609.9.1 Deep fat fryers.

When deep fat fryers are installed in a commercial kitchen, additional Class K portable fire extinguishers shall be provided, as follows:

1. For up to four fryers individually having a maximum cooking medium capacity of 80 pounds (36.3 kg) and a maximum surface area of 6 square feet (0.56 m 2 ): One Class K portable fire extinguisher having a minimum 1 1/2 gallon (6 L) capacity.

2. For every additional group of up to four fryers, individually having a maximum cooking medium capacity of 80 pounds (36.3 kg) and a maximum surface area of 6 square feet (0.56 m 2 ) each: One additional Class K portable fire extinguisher having a minimum 1 1/2 gallon (6 L) capacity.

3. For individual fryers having a maximum cooking medium capacity exceeding 80 pounds (36.3 kg) or 6 square feet (0.56 m 2 ) in surface area: Provide Class K portable fire extinguishers in accordance with the portable fire extinguisher manufacturer's recommendations.

609.9.2 Solid fuel cooking equipment.

When solid fuel cooking equipment is installed in a commercial kitchen, additional Class K portable fire extinguishers shall be provided, as follows:

1. For equipment with individual fireboxes of 5 cubic feet (0.14 m 3 ) or less in volume: One Class K portable fire extinguisher having a minimum 2 1/2 gallon (9 L) capacity, or two Class K portable fire extinguishers having a minimum 1 1/2 gallon (6 L) capacity.

2. For equipment with fireboxes exceeding 5 cubic feet (0.14 m 3 ): Provide Class K portable fire extinguishers in accordance with the portable fire extinguisher manufacturer's recommendations.

609.10 Recordkeeping.

A record shall be maintained of the following commercial cooking system maintenance in accordance with FC 107.7:

609.10.1. Commercial cooking appliances.

The owner of a commercial cooking system shall maintain records of any required inspection and other maintenance of commercial cooking appliances, including the replacement of deep fat fryer high-limit controls as required by FC 609.4.1.1.2, and the cleaning of cooking appliance exhaust flues.

609.10.2 Commercial cooking exhaust system.

The owner of a commercial cooking system shall keep records of each required inspection and cleaning conducted by a person in the owner's employ, including the date of each required inspection and each cleaning or replacement of the grease filters, and the date of each inspection and cleaning by an approved cleaning company. Approved cleaning companies shall keep such documentation of the cleaning of the exhaust system, including conditions existing prior to and after cleaning, as may be required by the rules.

609.10.3 Commercial cooking fire extinguishing system.

The date and cause of each activation of the commercial cooking fire extinguishing system, and the date of each inspection, testing and servicing of such system in accordance with FC 904.5 and the rules.

609.10.4 Portable fire extinguishers.

The date of each inspection and servicing of the portable fire extinguishing system as required by FC 906. Such recordkeeping shall be made as entries on the department-issued tag affixed to each portable fire extinguisher in accordance with FC 906 and the rules or as otherwise authorized therein.

Section FC 610. Commercial Kitchen Cooking Oil Storage Systems

Open this section

610.1 General.

Storage of unused (fresh) and/or used (waste) cooking oil in an aboveground storage system in a commercial kitchen shall be in accordance with FC 610.2 through 610.4 and NFPA 30.

610.2 Storage tanks.

Cooking oil tanks shall be designed and constructed so as to be capable of withstanding the heating associated with the operation of cooking oil storage systems. Cooking oil shall be stored in metallic storage tanks listed in accordance with UL 142 or UL 80, and shall be installed in accordance with the tank manufacturer's instructions. Cooking oil may be stored in nonmetallic tanks only when approved by the department.

610.3 Cooking oil storage system components.

Cooking oil storage system components, including piping, connections, fittings, valves, tubing, hose, pumps and vents, may be of metallic or nonmetallic construction, and shall be designed for the working pressure and maximum operating temperature of the storage system. All electrical components shall comply with the Electrical Code. Electrical components used to heat the cooking oil shall additionally be listed to UL 499.

610.4 Tank venting.

Normal and emergency venting shall be provided for cooking oil storage tanks and shall terminate outdoors.

610.4.1 Normal vents.

Normal vents shall be located above the maximum normal liquid line, and shall have a minimum effective area not smaller than the largest filling or withdrawal connection.

610.4.2 Emergency vents.

Emergency vents shall be located above the maximum normal liquid line, and shall be in the form of a device or devices that will relieve excessive internal pressure caused by a fire.

Section FC 611. Automated Parking Garages

Open this section

611.1 Scope.

This section shall govern the design, installation, operation and maintenance of automated parking garages.

611.2 General.

Automated parking garages shall be designed, installed, operated and maintained in accordance with this section and the construction codes.

611.3 Design and installation.

Automated parking garages shall be designed and installed in accordance with the construction codes and the requirements of the Department of Buildings. Application shall be made to the Department of Buildings and the department for review and approval.

611.3.1 Emergency shut-down device.

A manually-activated emergency shut down device shall be installed at a conspicuous, readily-accessible location at or near the main entrance to the automated parking garage, and, if required by the Department, at other approved locations suitable for firefighting operations.

611.3.2 Location of control panels.

The control panels for all fire protection systems and smoke purge systems shall be installed at a conspicuous, readily-accessible location at or near the main entrance to the automated parking garage, or other approved location suitable for firefighting operations.

611.4 Operational requirements.

Automated parking garages shall be operated in accordance with FC 611.4.1 through 611.4.4.

611.4.1 Notification to department.

At least 2 weeks prior to occupancy or operation of the automated parking system, the owner shall give written notice of same to the department, in the manner prescribed by the department, to allow the department to inspect the installation and familiarize itself with its operation.

611.4.2 Automated parking garage information card.

An information card depicting the operation of the automated parking system and setting forth other information, in the form prescribed by the department by rule, shall be prepared by the owner for all automated parking garages prior to occupancy or operation of the automated parking system.

611.4.3 Recordkeeping.

A record of the maintenance of the automated parking system and associated fire protection and other safety systems shall be maintained on the premises in the office of the parking garage attendant, in a first responder box, or other approved location.

611.4.4 Emergency communications.

A telephone not requiring a coin to operate or other approved means to communicate an emergency in the automated parking garage shall be provided and identified by a durable and conspicuously posted sign or markings, as follows:

1. A means to notify the department of an emergency shall be provided for public use at the facility at an approved location.

2. A means for firefighters or other department representatives to contact, on a 24/7 basis, a trained and knowledgeable person who can provide technical assistance with respect to the operation of the automated parking garage. This telephone or other approved means may be secured by key box operated by a citywide standard (2642) key.

Section FC 701. General

Open this section

701.1 Scope.

This chapter shall govern the maintenance of fire-resistance-rated construction.

701.2 General.

Fire-resistance-rated construction shall be maintained in accordance with this chapter.

Section FC 702. Definitions

Open this section

702.1 Terms defined in FC Chapter 2.

Terms used in this chapter and defined in FC 202 shall have the meanings set forth therein.

Section FC 703. Fire-Resistance-Rated Construction

Open this section

703.1 Maintenance.

The required fire-resistance rating of fire-resistance-rated construction, including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems, shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self-closing or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.

703.1.1 Fireblocking and draftstopping.

Required fireblocking and draftstopping in combustible concealed spaces shall be maintained to provide continuity and integrity of the construction.

703.1.2 Smoke barriers and smoke partitions.

Required smoke barriers and smoke partitions shall be maintained to prevent the passage of smoke. All openings protected with approved smoke barrier doors or smoke dampers shall be maintained in accordance with NFPA 105.

703.1.3 Fire walls, fire barriers and fire partitions.

Required fire walls, fire barriers and fire partitions shall be maintained to prevent the passage of fire. All openings protected with approved doors, fire dampers or smoke dampers shall be maintained in accordance with NFPA 80.

703.2 Maintenance of openings.

Fire doors and fire windows shall be maintained in good working order in accordance with NFPA 80. Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made inoperable. Fusible links shall be replaced promptly whenever fused, damaged or otherwise rendered inoperable. Fire door assemblies shall not be modified.

703.2.1 Signs.

Where required by the commissioner, a sign shall be permanently displayed on or near each fire door in letters not less than 1 inch (25 mm) high to read as follows:

1. For doors designed to normally be kept open: FIRE DOOR – DO NOT BLOCK.

2. For doors designed to normally be kept closed: FIRE DOOR – KEEP CLOSED.

703.2.2 Hold-open devices and automatic door closers.

Hold-open devices for fire doors and automatic door closers for self-closing fire doors, where provided, shall be inspected, tested, and otherwise maintained in accordance with FC 703.2 and 907.20. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position.

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2014/017.

703.2.3 Door operation.

Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position.

703.3 Ceilings.

The hanging of decorative material, merchandise displayed for sale or other display items from acoustical ceiling systems that are part of a fire-resistance-rated floor/ceiling or roof/ceiling assembly shall be prohibited.

703.4 Testing.

Horizontal and vertical sliding and rolling fire doors shall be inspected and tested annually to confirm proper operation and full closure.

Section FC 704. Floor Openings and Shafts

Open this section

704.1 Enclosures.

Interior vertical shafts, including stairways, elevator hoistways, service and utility shafts, that connect two or more stories of a building shall be enclosed or protected as specified in the construction codes, including the Building Code. When openings are required to be protected by the construction codes, including the Building Code, openings into such shafts shall be maintained self-closing or automatic-closing by smoke detection. Existing fusible-link-type automatic door-closing devices are allowed if the fusible link rating does not exceed 135°F (57°C).

Section FC 801. General

Open this section

801.1 Scope.

This chapter shall govern furnishings, decorative vegetation, decorations and scenery in buildings and structures.

801.2 General.

The furnishings, decorative vegetation, decorations and scenery governed by this chapter shall be designed, stored, handled and used in accordance with this chapter.

801.3 Flame-retardant treatments.

When a material or item is treated with a flame-retardant chemical to meet the requirements of this chapter for a flame-resistant material, such chemical and its method of application shall be approved. Flame-retardant treatments shall be maintained so as to retain the effectiveness of the treatment under conditions encountered in actual use.

801.4 Fire-retardant coating.

When a material or item is coated with a fire-retardant coating to meet the requirements of this chapter for a flame-resistant material, such coating and its method of application shall be approved. Flame-retardant coatings shall be maintained so as to retain the effectiveness of the coating under conditions encountered in actual use.

801.5 Prohibited decorative vegetation, decorations and scenery.

It shall be unlawful in Group A, E and I occupancies to store or use decorative vegetation, decorations or scenery that consists of or is coated with pyroxylin or similarly hazardous base.

801.6 Obstructions.

The required width of any portion of a means of egress shall not be obstructed by any furnishing, decorative vegetation, decoration or scenery nor shall such furnishing, decorative vegetation, decoration or scenery obstruct any exit or the visibility thereof.

801.7 Supervision.

Compliance with flame resistance standards shall be under the supervision of a certificate of fitness holder in accordance with FC 801.7.1 and 801.7.2.

801.7.1. Application of flame-retardant chemical.

When a material or item is treated with a flame-retardant chemical to meet the requirements of this chapter for a flame-resistant material, the application of the chemical shall be conducted by or under the personal supervision of a certificate of fitness holder.

801.7.2 Certification of compliance.

Certification of compliance with the requirements of this section shall be prepared by a certificate of fitness holder and made available to department representatives in accordance with the rules or upon request of any department representative, provided, however, that a manufacturer's certification, in a form acceptable to the department, may be presented for an article that is inherently flame-resistant.

801.8 Certificate of approval.

Any flame-retardant chemical used to render a material flame-resistant to meet the requirements of this chapter shall be of a type for which a certificate of approval has been issued in accordance with FC 112 and the rules.

Section FC 802. Definitions

Open this section

802.1 Definitions.

The following terms shall, for the purposes of this chapter and used elsewhere in this code, have the meanings set forth in FC 202.

CONIFER.

DECORATION.

FIRE-RETARDANT COATING.

FLAME-RESISTANT MATERIAL.

FLAME-RETARDANT TREATMENT.

FLAME SPREAD.

FURNISHING.

INTERIOR FINISH.

NATURAL DECORATIVE GREEN.

NATURAL TREE.

NATURAL VEGETATION.

SCENERY.

Section FC 803. Upholstered Furniture and Mattresses

Open this section

803.1 Upholstered furniture.

Upholstered furniture newly introduced in Occupancy Groups I-1, I-2, I-3 and R-1 college and university dormitories after the effective date of this section shall comply with the resistance to ignition by cigarettes and maximum heat release rate requirements of this section.

803.1.1 Ignition by cigarettes.

Newly-introduced upholstered furniture in Occupancy Groups I-1, I-2, I-3 and R-1 college and university dormitories shall be shown to resist ignition by cigarettes as determined by tests conducted in accordance with one of the following standards:

1. Mocked-up composites of the upholstered furniture shall have a char length not exceeding 1 1/2 inches (38 mm) when tested in accordance with NFPA 261.

2. The components of the upholstered furniture shall meet the requirements for Class I when tested in accordance with NFPA 260.

Exception: The requirements of FC 803.1.1(1) and 803.1.1(2) shall not apply to upholstered furniture owned by the resident of a Group I-2 occupancy, provided such furniture is located in the sleeping room of the resident and such sleeping room is provided with a smoke detector in accordance with the requirements of the Building Code.

803.1.2 Heat release rate.

Newly-introduced upholstered furniture in Occupancy Groups I-1, I-2, I-3 and R-1 college and university dormitories shall have limited rates of heat release when tested in accordance with California Technical Bulletins 116 and 117.

803.1.3 Listing and labeling.

Upholstered furniture shall be listed and labeled in compliance with the requirements of FC 803.1.1 and 803.1.2.

803.2 Mattresses.

Mattresses newly introduced in Occupancy Groups I-1, I-2, I-3 and R-1 college and university dormitories after the effective date of this section shall comply with the resistance to ignition by cigarettes and maximum heat release rate requirements of this section.

803.2.1 Ignition by cigarettes.

Newly-introduced mattresses in Occupancy Groups I-1, I-2, I-3, and R-1 college and university dormitories shall be shown to resist ignition by cigarettes as determined by tests conducted in accordance with 16 CFR Part 1632 and shall have a char length not exceeding 2 inches (51 mm).

803.2.2 Heat release rate.

Newly-introduced mattresses shall have limited rates of heat release when tested in accordance with ASTM E 1590 or California Technical Bulletin 129, as follows:

1. The peak rate of heat release for the single mattress shall not exceed 100 kW, except mattresses in rooms or spaces protected throughout by a sprinkler system.

2. The total energy released by the mattress during the first 10 minutes of the test shall not exceed 25 MJ, except mattresses in rooms or spaces protected throughout by a sprinkler system.

Exception: The exceptions set forth in FC 803.2.2(1) and 803.2.2(2) for mattresses in rooms or spaces protected throughout by a sprinkler system shall not apply to Occupancy Group I-3.

803.2.3 Listing and labeling.

Mattresses shall be listed and labeled in compliance with the requirements of FC 803.2.1 and 803.2.2.

Section FC 804. Decorative Vegetation

Open this section

804.1 Natural trees and cut natural trees.

Natural trees and cut natural trees shall be stored, sold, displayed and maintained in accordance with FC 804.1.1 through 804.1.6.

804.1.1 Indoor display of cut natural trees.

Cut natural trees may be displayed in a building, except in Group A, B, E, I, M, R-1 and R-2 occupancies and any building or structure used for a public gathering. Notwithstanding the foregoing occupancy restrictions, cut natural trees may be displayed in houses of worship and dwelling units in Group R-2 apartment house occupancies.

804.1.2 Indoor storage of cut natural trees.

It shall be unlawful to store cut natural trees in any building, except in connection with a display allowed under FC 804.1.1.

804.1.3 Indoor storage and display of natural trees.

Natural trees, except conifers, may be stored and displayed in a building, provided they are maintained in a healthy condition and are not allowed to become dry. It shall be unlawful to store or display natural trees that are conifers in any building.

804.1.4 Support devices.

Cut natural trees for display in any building shall have the trunk bottoms cut off at least 1/2 inch (12.7 mm) above the original cut and shall be placed in a support device. The support device shall be of a type that is stable, holds the tree in an upright position and meets all of the following criteria:

1. The device shall hold the tree securely and be of adequate size to avoid tipping over of the tree.

2. The device shall be capable of containing a minimum 2-day supply of water.

3. The water level, when full, shall cover the tree stem at least 2 inches (51 mm). The water level shall be maintained above the fresh cut and checked at least once daily.

804.1.5 Dryness.

Natural trees and cut natural trees shall be removed from the building whenever the needles or leaves fall off readily when a tree branch is shaken or if the needles are brittle and break when bent between the thumb and index finger. Trees shall be checked daily for dryness.

804.1.6 Retail sale of cut natural trees.

Merchants of cut natural trees, including Christmas trees, shall, at the time of retail sale of each such tree, attach to the tree a printed tag containing appropriate instructions for its safe and lawful display and disposal.

804.2 Natural vegetation.

Natural vegetation shall be maintained in a healthy condition to prevent the vegetation from becoming dry and ignitable. Natural vegetation that has become dry and readily ignitable shall be promptly removed from the premises. Natural vegetation shall be regularly pruned to prevent the vegetation from becoming overgrown and expanding beyond the space designated for it.

804.3 Open flames.

Candles and other open flames shall not be used or maintained on or near decorative vegetation. Natural cut trees shall be kept a distance at least equal to the height of the tree from heat sources, including fireplaces, portable heaters and vents, and open-flame or heat-producing devices.

804.3.1 Electrical fixtures and wiring.

Electrical wiring and lighting used on natural cut trees and decorative vegetation shall be listed. It shall be unlawful to use electrical wiring and lighting on metal artificial trees.

804.4 Artificial vegetation.

Artificial decorative vegetation, including artificial trees, shall be made of flame-resistant material in the buildings and occupancies set forth in FC 805.1. Alternatively, artificial decorative vegetation shall have a maximum heat release rate of 100 kW when tested in accordance with NFPA 289, using a 20 kW ignition source.

804.5 Natural decorative greens.

Natural decorative greens shall be stored and displayed in a building in accordance with FC 804.5.1 through 804.5.4.

804.5.1 Storage.

It shall be unlawful to store natural decorative greens in any building, except merchandise for sale or displayed for sale which does not contain conifers.

804.5.2 Display.

Natural decorative greens may be displayed in buildings on a temporary basis. The display of natural decorative greens in Group A, E, I, and M occupancies, in common areas of Group R-1, R-2 and B occupancies, and any building or structure used for a public gathering, except display of works of art in museums and houses of worship, shall comply with the restrictions set forth in FC 804.5.3.

804.5.3 Restrictions on display.

It shall be unlawful to display in any building natural decorative greens that:

1. Contain pitch, such as hemlock, balsam, pine or Spanish moss.

2. Are displayed at a location less than 3 feet (914 mm) from upholstered furniture, rugs, or other combustible material or contain combustible decorations.

3. Are on a combustible framework or displayed in conjunction with combustible material unless such material is flame resistant.

804.5.4 Dryness.

Any natural decorative green shall be removed from a building at the first sign of deterioration or dryness. Natural decorative greens shall be checked at least daily for dryness.

Section FC 805. Decorations and Scenery

Open this section

805.1 Decorations.

Except as otherwise specifically provided in this chapter, decorations shall be made of flame-resistant material in Group A, E, I and M occupancies, Group R-1 college and university dormitories, common areas in Group B, R-1 and R-2 occupancies, and any building or structure used as a place of public gathering.

Exceptions:

1. Acoustical or other decorative materials consisting of foam plastics with a maximum heat release rate of 100 kW when tested in accordance with UL 1975.

2. Artwork in a museum or art gallery.

3. Artwork on the walls of building hallway corridors in Group B office and Group R-2 occupancies, provided that the wall area covered by such artwork does not exceed 20 percent of any wall in any occupancy not protected throughout by a sprinkler system or 50 percent of any wall in any occupancy protected throughout by a sprinkler system, and the artwork is affixed in a manner that prevents it from moving freely.

4. Artwork and educational materials in classrooms in Group E and I-4 occupancies, and on the walls of corridors in such occupancies, provided that the corridor wall area covered by such artwork and materials does not exceed 20 percent of any wall, and the artwork and materials are affixed in a manner that prevents them from moving freely.

5. Curtains, draperies, hangings and other decorative materials suspended from walls of sleeping units and dwelling units in Occupancy Group R-1 dormitories protected throughout by a sprinkler system, where the total amount of such materials does not exceed 25 percent of the aggregate area of walls.

6. Decorations displayed for sale.

7. Guest rooms in hotels and motels.

8. Decorations in houses of worship, including wood used for screening or ornamental purposes.

9. Decorations in private offices in commercial buildings.

805.1.1 Fabric partitions.

In Group B and M occupancies, fabric partitions suspended from the ceiling and not supported by the floor shall be flame-resistant material.

805.1.2 Trim and decorative materials.

The type and quantity of interior trim allowed shall be as set forth in Chapter 8 of the Building Code. The quantity of flame resistant materials used in decorations when combined with combustible trim shall not exceed 10 percent of the specific wall or ceiling area to which it is attached.

805.1.3 Reserved.

805.1.4 Motion picture screens.

Motion picture screens and supporting construction shall comply with the requirements of FC 306.3.

805.2 Scenery.

All scenery in Group A occupancies shall be made of materials that are inherently flame-resistant, have a Class A flame-spread rating, or rendered flame resistant by the application of a fire-retardant coating, except that the commissioner may authorize the use of scenery not complying with any of the above requirements where provision is made to ensure an equivalent level of fire safety. Foam plastic materials used for scenery shall have a maximum heat release rate of 100 kW when tested in accordance with UL 1975, or when tested in accordance with NFPA 289 using the 20 kW ignition source.

805.3. Outdoor decorative installations.

In an outdoor place of assembly, outdoor place of public gathering or other outdoor common area in a building or occupancy set forth in FC 805.1, any decorative installation that is freestanding, more than 4 feet (1219 mm) in height, and under, through or around which the public or building occupants can enter or pass, shall be flame-resistant material, except as otherwise authorized by the department.

Section FC 806. Interior Finishes

Open this section

806.1 General.

The quantity and type of interior finishes shall comply with the requirements of Chapter 8 of the Building Code.

806.2 Foam plastic signs.

Foam plastic signs that are not interior finishes shall have a maximum heat release rate of 150 kW when tested in accordance with UL 1975, or when tested in accordance with NFPA 289 using the 20 kW ignition source.

Section FC 901. General

Open this section

901.1 Scope.

This chapter shall govern the design, installation, operation and maintenance, including inspection and testing, of fire protection devices, equipment and systems, and other fire protection measures for the control and extinguishment of fire.

901.1.1 General.

Fire protection systems shall be designed, installed, operated and maintained in accordance with this chapter and the reference standards set forth in FC Table 901.6.1.

901.1.2 Emergency alarm systems.

Except as otherwise provided in the construction codes, this code or the rules, emergency alarm systems shall be designed, installed, operated and maintained in the same manner as fire alarm systems.

901.2 Design and installation documents.

The commissioner may require design and installation documents and calculations to be submitted for review for all fire protection systems. Design and installation documents required or regulated by this code or the rules shall be submitted for review and approval prior to installation, and shall certify that the design complies with the requirements of this code and the rules.

901.3 Permits.

Permits shall be required as set forth in FC 105.6.

901.4 Design and installation.

Fire protection systems shall be designed and installed in accordance with FC 901.4.1 through 901.4.6.

901.4.1 Required fire protection systems.

Fire protection systems shall be designed and installed in accordance with the construction codes, including the Building Code, and, as applicable, this code and the rules, and the applicable referenced standards listed in this code. Required systems shall be extended or altered as necessary to maintain and continue protection whenever the building or structure is altered. Alterations to fire protection systems shall be performed in compliance with the requirements of this code, the rules, and the construction codes, as applicable. Buildings and structures shall be provided with such fire hose, portable fire extinguishers and other means of preventing and extinguishing fires as the commissioner may direct.

901.4.1.1 Fire protection systems deemed required.

A fire protection system for which a design option, exception or reduction to the provisions of this code or the construction codes has been granted shall be deemed a required system.

901.4.2 Fire protection systems not required by code.

Any fire protection system or portion thereof not required by this code, the rules or the construction codes, including the Building Code, may be installed to provide partial or complete protection of a building or structure, provided such system meets the requirements of this code, the rules and the construction codes, including the Building Code, as applicable. Where the design and installation of such fire protection system is governed by this code or the rules, the commissioner may modify such requirements, consistent with the interests of fire safety, upon a determination that such modification will promote public safety by encouraging the installation of such systems.

901.4.3 Additional fire protection systems.

Where an existing or proposed storage, handling or use of a material or the conduct of an operation in a particular occupancy gives rise to special hazards in addition to the normal hazards of the occupancy, or where the commissioner determines that size, design and arrangement of the occupancy would unduly delay the ability of firefighting personnel to gain access to the hazard, the commissioner may require additional fire protection or other fire safety measures. Such measures may include the following: automatic fire detection systems, fire alarm systems, fire extinguishing systems, standpipe systems, or portable or fixed extinguishers. Where a certificate of occupancy limits the commissioner's authority to order the installation of such additional systems or the implementation of such additional measures, the commissioner may apply to the Board of Standards and Appeals for a modification of such certificate of occupancy, and such application shall be granted upon a showing that such additional systems or measures will reasonably mitigate the special hazard or delayed access.

901.4.4 Prohibition of deceptive equipment.

It shall be unlawful to install or maintain any device that has the physical appearance of fire protection equipment but that does not perform the fire protection function, in any building, structure or premises where it may be confused with actual fire protection equipment.

901.4.5 Certificate of approval.

The fire protection devices, equipment and systems listed in FC 112 shall be of a type for which a certificate of approval has been issued in accordance with this code, or which was approved by the Department of Buildings or the Board of Standards and Appeals prior to the effective date of this section, unless such approval by the Department of Buildings or the Board of Standards and Appeals is amended or repealed by the commissioner.

901.4.6 Connection to water supply.

Sprinkler systems, and other fire extinguishing and fire protection systems, connected to a potable water supply shall be protected against backflow in accordance with the construction codes and Department of Environmental Protection requirements.

901.5 Installation acceptance testing.

Fire detection and alarm systems, fire extinguishing systems, private fire hydrant systems, yard hydrant systems, standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as set forth in the installation standards specified in this code. Where required by the construction codes, including the Building Code, this code or the rules, such tests shall be conducted, at the owner's risk, by his or her representative before a representative of the department. When an installation does not pass an acceptance test required to be witnessed by the department, the necessary corrections shall be made and the installation retested, or, when authorized by the rules, certification of such corrections by a licensed or certified professional submitted to the department.

901.5.1 Occupancy.

It shall be unlawful to occupy any portion of a building or structure until all required fire detection systems, fire alarm systems, standpipe systems and fire extinguishing systems have been tested and approved, except as follows:

1. In a new building undergoing construction, a completed floor below the level of ongoing construction may be occupied upon installation, testing and approval of the required fire protection systems on all floors up to and including the occupied floor.

2. In an existing building undergoing alteration, a completed floor may be occupied upon installation, testing and approval of the required fire protection systems for such floor in accordance with Building Code and Department of Buildings requirements.

901.5.2 Correction of non-compliant conditions.

When the Department of Buildings authorizes occupancy of a building notwithstanding the existence of installation defects or other non-compliant conditions in the fire protection systems on the floors of the building in which occupancy has been authorized, any and all prior written inspection findings of such defects and other noncompliance shall, upon issuance of the occupancy authorization, constitute an enforceable violation of this code. Such violations shall be corrected within the time for correction set forth in the inspection finding, but in any event within 60 days of occupancy, unless additional time for compliance is granted by the department.

901.6 Maintenance.

Fire protection systems shall be maintained in good working order at all times. Any fire protection system that is not in good working order shall be repaired or replaced as necessary to restore such system to good working order, or, where authorized by the Building Code, removed from the premises.

901.6.1 Standards.

Fire protection systems shall be inspected, tested, serviced and otherwise maintained in accordance with this section, the rules and the referenced standards listed in FC Table 901.6.1. Where required by this section, such inspection, testing and maintenance shall additionally comply with the rules. Where applicable, the requirements of the reference standards listed in FC Table 901.6.1 shall be in addition to those requirements specified in the rules.

FC Table 901.6.1 Fire Protection System Maintenance Standards

Fire Protection System Referenced Standard Fire alarm systems NFPA 72 Fire extinguishing systems Aerosol fire extinguishing systems NFPA 2010 Clean agent fire extinguishing systems NFPA 2001 Carbon dioxide fire extinguishing system NFPA 12 Dry chemical fire extinguishing systems NFPA 17 Expansion foam systems (low, medium and high) NFPA 11 and NFPA 25 Foam water sprinkler and spray systems NFPA 16 and NFPA 25 Halon 1301 fire extinguishing systems NFPA 12A Water mist fire extinguishing systems NFPA 25 Wet chemical fire extinguishing systems NFPA 17A Portable fire extinguishers NFPA 10 Water-based fire protection systems (including hydrant, fire hose, sprinkler and standpipe systems) NFPA 25

901.6.2 Records.

Records of all system inspections, tests, servicing and other maintenance required by this code, the rules or the referenced standards shall be maintained in accordance with FC 107.7.

901.6.2.1 Standpipe and sprinkler systems.

A visual inspection shall be completed monthly by the certificate of fitness holder in accordance with the requirements of NFPA 25. Periodic testing and other maintenance, as required by NFPA 25, shall be conducted by a certificate of fitness holder possessing the requisite qualifications. All defects or violations shall be noted on the inspection report.

901.6.3 Supervision.

The inspection, testing, servicing and other maintenance of the following fire protection systems shall be personally conducted by a certificate of fitness holder, provided, however, that when required by the construction codes or other applicable law, rule or regulation to conduct such maintenance work, such certificate of fitness holder shall hold a master fire suppression piping contractor license, master electrician license or other required license, or be under the direction and control of such license holder.

1. Fire extinguishing systems.

Exception: Sprinkler systems in Group R-3 occupancies.

2. Standpipe systems.

3. Fire alarm systems.

4. Private fire hydrant systems.

5. Yard hydrant systems.

901.6.3.1 Servicing of portable fire extinguishers.

It shall be unlawful for any person engaged in the business of servicing portable fire extinguishers to service portable fire extinguishers without a portable fire extinguisher servicing company certificate. Any person that services portable fire extinguishers shall hold a certificate of fitness, except that a person training for such certificate of fitness may service portable fire extinguishers under the personal supervision of a certificate of fitness holder. Nothing in this section shall preclude portable fire extinguishers that are maintained on a premises for use at such premises from being serviced by the owner or occupant of the premises, or an employee of such owner or occupant, who possesses a certificate of fitness for portable fire extinguisher servicing and the tools, materials, equipment and facility necessary to perform such services.

901.6.3.2 Portable fire extinguisher sales.

It shall be unlawful for any person to engage in the business of selling portable fire extinguishers door to door to owners of buildings or businesses for use on their premises without a portable fire extinguisher sales company certificate. Persons performing such services for or on behalf of licensed portable fire extinguisher sales companies shall possess a certificate of fitness for portable fire extinguisher sales.

Exception: Sale to owners of Group R-2 and R-3 occupancy buildings.

901.6.3.3 Reserved.

901.6.3.4 Smoke detector cleaning and testing.

The cleaning and testing for smoke entry and sensitivity of smoke detectors installed in a fire alarm system shall be performed by a person holding a certificate of fitness for smoke detector maintenance. Such work shall be performed under the supervision and by employees of a person holding a smoke detector maintenance company certificate, except that such smoke detector cleaning and testing may be performed by an owner or occupant of the premises, or an employee of such owner or occupant, who possesses a certificate of fitness for smoke detector maintenance, and possesses the tools, instruments or other equipment necessary to perform such services in accordance this code and the rules. All other smoke detector maintenance shall be performed by a person possessing the requisite qualifications and experience, and any applicable license or certificate.

901.6.3.5 Central station fire alarm monitoring.

It shall be unlawful for any person to operate a central station that monitors fire alarm systems and maintain transmitters in protected premises without a certificate of operation.

901.6.4 Verification of system functionality.

Any fire protection system which is or may have been damaged or rendered out of service in whole or in part as result of exposure to fire or water or other cause, shall be inspected to verify that the system is in good working order. If not in good working order, the system shall be repaired or otherwise restored to good working order forthwith.

901.7 Out-of-service systems.

The owner and the impairment coordinator for a standpipe system, sprinkler system or fire alarm system shall comply with the requirements of this section whenever such fire protection system is out of service. The department may direct that, until such fire protection system has been returned to service, fire safety measures appropriate to the size, configuration, occupancy, use and hazards be implemented that are in addition to or in lieu of those required by this section.

901.7.1 Impairment coordinator.

The building owner shall designate an impairment coordinator to take the actions required by this section when a standpipe system, sprinkler system or fire alarm system is out of service. In the absence of a specific designee, the owner shall be considered the impairment coordinator.

901.7.2 Fire watch.

Unless otherwise directed by the department, the building shall be evacuated or a fire watch maintained in accordance with this section when a standpipe system, sprinkler system or fire alarm system is out of service. Such fire watch shall be conducted in compliance with the requirements of FC 901.7.2.1 through 901.7.2.3.

901.7.2.1 Duties and responsibilities.

Persons conducting a fire watch shall:

1. continuously patrol the area affected by the out-of-service fire protection system to which such person has been assigned, keeping constant watch for fires;

2. be provided with at least one approved means for notification of the department and any FLS director, FEP coordinator or FEP staff on the premises;

3. immediately report any fire to the department and notify emergency preparedness staff on the premises;

4. be trained in the use of portable fire extinguishers and equipped with a portable fire extinguisher, or made aware of the location of readily accessible portable fire extinguishers in the area to which such person has been assigned to maintain a fire watch;

5. be responsible for extinguishing fires when they are limited in size and spread such that they can readily be extinguished using a portable fire extinguisher;

6. maintain a record of such fire watch on the premises during the fire watch and for a minimum of 48 hours after the fire watch has concluded; and

7. have no other duties.

901.7.2.2 Fire guards required.

The fire watch required when a standpipe system, sprinkler system or fire alarm system is out of service shall be maintained in accordance with FC 901.7.2.2.1 and this section.

Exception: The impairment coordinator or other building staff trained and knowledgeable in conducting a fire watch may conduct a fire watch in lieu of a fire guard during the initial 4 hours of a planned removal from service, or after discovery of an unplanned out-of-service condition, provided that the floor or area in which the fire protection system is out of service does not exceed 50,000 square feet (4645 m 2 ).

901.7.2.2.1 Fire guards required.

The fire watch required for an out-of-service standpipe system, sprinkler system or fire alarm system shall be maintained by one or more fire guards.

901.7.2.3 Fire watch coverage.

A sufficient number of fire guards shall be provided such that each floor or area in which the fire protection system is out of service is patrolled at least once an hour. The area to be patrolled by each fire guard shall not exceed more than 50,000 square feet (4645 m 2 ) of floor area. The area patrolled by each fire guard may be further limited by the department depending on the configuration of the premises, impediments to patrol, nature of the occupancy, fire risk, and other fire safety considerations.

901.7.3 Planned removal from service.

The impairment coordinator shall be made aware in advance of any planned removal from service of a standpipe system, sprinkler system or fire alarm system, or system component, for repair, servicing, alteration, testing and other maintenance of the system or component, or to allow construction to be performed in the area protected by the system without unnecessarily activating it. The impairment coordinator shall authorize and personally supervise the placing of the fire protection system out of service. Before authorizing the placing of the fire protection out of service the impairment coordinator shall:

1. notify the certificate of fitness holder responsible for supervising the maintenance of the standpipe system, sprinkler system or fire alarm system.

2. determine the extent and expected duration of the out-of-service condition.

3. inspect the areas or buildings involved and assess the increased risks.

4. make appropriate recommendations to the owner.

5. notify the department in accordance with FC 901.7.5, if required.

6. notify the responsible person designated by the owner to issue hot work authorizations in accordance with FC Chapter 35.

7. notify the central station and insurance carrier.

8. notify the occupants in the affected areas if the duration of time the sprinkler system or fire alarm system will be out of service is estimated to be more than 30 minutes.

9. place a tag at each fire department connection, standpipe and sprinkler system control valve and fire command center, indicating which fire protection system, or part thereof, is out of service.

10. maintain the fire protection system in service until work is ready to begin.

901.7.4 Unplanned out-of-service condition.

Any person, upon becoming aware of any condition, except a planned removal from service, rendering a standpipe system, sprinkler system or fire alarm system, or part thereof, inoperable in whole or in part, shall notify the owner and the impairment coordinator of such condition. The impairment coordinator shall take the actions set forth in FC 901.7.3 and 901.7.5, and such other actions as are necessary or appropriate to protect the occupants of the building and promptly restore the system to service.

901.7.5 Notification to department.

The department shall be notified that a standpipe system, sprinkler system or fire alarm system is out of service, whether by reason of a planned removal from service or an unplanned out-of-service condition, where required by FC 901.7.5.1 through 901.7.5.3.

901.7.5.1 Standpipe systems.

Notification shall be made to the department whenever a standpipe system is or will be out of service for any period of time.

901.7.5.2 Sprinkler systems and fire alarm systems.

Notification that a sprinkler system or fire alarm system, or any part thereof, is or will be out of service shall be made to the department under the following circumstances:

1. The sprinkler system or fire alarm system is or will be out of service on more than one floor of a building; or

2. With respect to a sprinkler system, the work or repairs cannot be completed, and the system restored to service, within 8 hours of the time the system was placed or went out of service; or

3. With respect to a fire alarm system, the work or repairs will require the fire alarm system to be out of service for 8 hours or more in any 24-hour period or 30 hours or more (consecutive or non-consecutive) in any month; or

4. One or more other fire protection systems in the area in which a fire protection system is out of service are or will also be out of service at the same time.

901.7.5.3 Reporting requirements.

Notification of an out-of-service condition pursuant to this section shall be made by the impairment coordinator to the department at the applicable telephone number set forth in FC 901.10. Such notification shall include the following information:

1. The owner or impairment coordinator's name and contact information;

2. The building address;

3. The type of fire protection system that is out of service;

4. Whether the fire protection system is out of service by reason of a planned removal from service (and if so, the reason for placing it out of service) or an unplanned out-of-service condition;

5. If a planned removal from service, the date and time the fire protection system will be placed out of service, and the estimated duration the system will be out of service;

6. If an unplanned out-of-service condition, the estimated duration the system will be out of service;

7. The floors or areas in which the fire protection system is out of service;

8. Whether the other fire protection systems are in good working order; and

9. The name and certificate number of the certificate of fitness holder responsible for supervision of the fire protection system that is out of service.

901.7.6 Restoring systems to service.

When an out-of-service device, equipment or system is restored to service, the impairment coordinator shall:

1. conduct necessary inspections and tests to verify that the affected systems are operational.

2. notify the department in accordance with FC 901.10.

3. notify the owner, central station, insurance carrier, emergency preparedness staff, and, if previously notified, the occupants in the affected areas.

4. remove the out-of-service tags.

901.7.7 Out-of-service standpipe systems at construction sites.

The owner, fire safety manager and/or impairment coordinator shall take the following actions whenever a standpipe system at a construction site is out of service:

1. Immediately notify the department in accordance with FC 901.10 of any unplanned out-of-service condition, and otherwise comply with the requirements of FC 901.7.4.

2. Notify the department in accordance with FC 901.10 at least 24 hours prior to any planned removal of the standpipe system from service, and otherwise comply with the requirements of FC 901.7.3.

3. Ensure that a fire watch is continuously maintained in compliance with the requirements of FC 901.7.2 while the standpipe system is out of service.

4. Repair the standpipe system and return it to service in compliance with the requirements of FC 901.7.6 and Section 3303.8.1 of the Building Code. The construction site may continue to be occupied, and construction, demolition or alteration activities may continue, pending such repair and restoration to service, except:

4.1. as otherwise provided in Section 3303.8.1 of the Building Code; and/or

4.2. as otherwise directed by the commissioner upon a determination that, in the absence of an operable standpipe system, the conduct of certain construction, demolition or alteration activities would be imminently perilous to life or property; and

4.3. that in no circumstance shall hot work be conducted on the construction site until such time as the standpipe system is restored to service and the standpipe alarm reactivated.

901.8 Tampering with or rendering equipment inoperable.

Fire protection systems and related apparatus shall not be tampered with or rendered inoperable, except as set forth in FC 107.4.

901.9 Recall of fire protection system components.

A component of a fire protection system regulated by this code that is subject to a voluntary or mandatory recall under federal law shall be replaced with an approved, listed component in compliance with the referenced standards. A record of the replacement of the component shall be maintained in accordance with FC 107.7.

901.10 Telephone numbers for department notification.

Except as otherwise required by the rules or order of the department, when this code requires non-emergency notification to be made to the department, such notification shall be made by calling one of the following telephone numbers, depending upon the borough in which the property is located:

Bronx properties (718) 430-0200

Brooklyn properties (718) 965-8300

Manhattan properties (212) 570-4300

Queens properties (718) 476-6200

Staten Island properties (718) 494-4296

Section FC 902. Definitions

Open this section

902.1 Definitions.

The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.

ALARM NOTIFICATION APPLIANCE.

ALARM SIGNAL.

ANNUNCIATOR.

AUTOMATIC.

CENTRAL STATION.

CERTIFICATE OF OPERATION.

CLEAN AGENT.

COMMERCIAL COOKING EXHAUST SYSTEM SERVICING COMPANY CERTIFICATE.

COMMERCIAL COOKING SYSTEM.

DOMESTIC COOKING HOOD.

DOMESTIC COOKING SYSTEM.

EMERGENCY ALARM SYSTEM.

FIRE ALARM BOX, MANUAL.

FIRE ALARM SIGNAL.

FIRE ALARM SYSTEM.

FIRE DETECTOR, AUTOMATIC.

FIRE EXTINGUISHING SYSTEM.

FIRE PROTECTION SYSTEM.

FIRE PUMP.

FIRE SUPPRESSION PIPING CONTRACTOR.

IMPAIRMENT COORDINATOR.

INITIATING DEVICE.

MULTIPLE-STATION ALARM DEVICE.

OUT-OF-SERVICE SYSTEM.

PLUMBER.

PORTABLE COOKING EQUIPMENT.

PORTABLE FIRE EXTINGUISHER SALES COMPANY CERTIFICATE.

PORTABLE FIRE EXTINGUISHER SERVICING COMPANY CERTIFICATE.

PRESIGNAL SYSTEM.

PROTECTED PREMISES.

SINGLE-STATION SMOKE ALARM.

SMOKE ALARM.

SMOKE DETECTOR.

SMOKE DETECTOR MAINTENANCE COMPANY CERTIFICATE.

SPRINKLER SYSTEM.

STANDPIPE, MULTI-ZONE.

STANDPIPE SYSTEM.

SUPERVISORY SIGNAL.

SUPERVISORY SIGNAL-INITIATING DEVICE.

TROUBLE SIGNAL.

Unnecessary alarm.

Unwarranted alarm.

WATER MIST SYSTEM.

Section FC 903. Sprinkler Systems

Open this section

903.1 General.

Sprinkler systems shall comply with the requirements of this section.

903.2 Where required.

Sprinkler systems shall be provided in buildings, structures, premises, or parts thereof, when required by the construction codes, including the Building Code, this code or the rules.

903.2.1 Reserved.

903.2.2 Reserved.

903.2.3 Reserved.

903.2.4 Reserved.

903.2.5 Reserved.

903.2.6 Reserved.

903.2.7 Reserved.

903.2.8 Reserved.

903.2.9 Reserved.

903.2.10 Reserved.

903.2.11 During construction.

Sprinkler systems required during construction, alteration and demolition operations shall be provided in accordance with Chapter 33 of the Building Code and FC 3314.

903.2.12 Reserved.

903.2.13 Other required fire extinguishing systems.

In addition to the requirements of FC 903.2, the provisions indicated in FC Table 903.2.13 also require the installation of a fire extinguishing system for certain buildings and areas.

FC Table 903.2.13 Additional Required Fire Extinguishing Systems

Section Subject 314.5.1 Covered kiosks, displays, booth or concession stands 315.7.2.1 Indoor additional storage of solid fuel 317.4.3.3 Defueling area 321.4 Construction shanties and construction storage facilities and areas – fixed guideway transit and passenger rail systems 322.4 Construction shanties and construction storage facilities and areas – road tunnels, bridges and other limited access highways 501.4.3.1 Altered buildings on substandard width public streets and fire apparatus access roads 503.2.10 Buildings fronting on substandard width fire apparatus access roads 503.3.2 Buildings fronting on substandard width public streets 608.9.4 Energy storage system, stationary (NFPA 13 system, where required/allowed) 1027.6 Equipment storage in Group I-2 building hallway corridors 2108.2 Newly-established dry cleaning facilities 2108.3 Lawfully existing dry cleaning facilities 2306.8 Flammable liquid motor fuel-dispensing areas 2308.7.4 Indoor CNG compressing, storage and dispensing areas 2309.3.4.2 Hydrogen motor fuel-dispensing areas under canopies 2311.8.2 Repair garage for vehicle fueled by lighter-than-air motor fuel 2404.3.3 Spray rooms and spray booths 2405.2 Dip-tank rooms 2405.3.4 Dip tanks 2405.4.4 Hardening and tempering tanks 2406.3.3.1 Powder coating rooms and booths 2407.3.2.1 Electrostatic spray finishing operations 2408.2.2 Spraying operations involving the use of organic peroxides and other dual-component coatings 2409.2.1 Resin application areas 2703.10 HPM facilities 2703.10.1.1 HPM work station exhaust 2703.10.1.2 HPM combustible tools 2703.10.2 HPM gas cabinets and exhaust enclosures 2703.10.3 HPM corridors 2703.10.4 HPM exhaust 2703.10.4.1 HPM noncombustible ducts 2703.10.4.2 HPM combustible ducts 2903.4 Organic coating manufacturing facility 3006.1 Class A and B furnaces 3006.2 Class C and D furnaces FC Table 3206.2 High-piled storage fire protection 3206.4 High-piled storage 3207.2 Solid-piled and shelf storage 3208.2 Rack storage 3208.5.1 Extra-high-rack combustible storage 3209.2 Automated storage 3704.5 Storage of more than 1,000 cubic feet of loose combustible fibers 3706.6 Combustible fibers, storage at waterfront structure 4003.5.1 Distilleries 5003.8.4.1 Gas rooms 5003.8.5.3 Exhausted enclosures 5004.5 Indoor storage of hazardous materials 5005.1.8 Indoor handling and use of hazardous materials 5104.4.1 Aerosol warehouses 5106.3.2 Retail aerosol displays over 8 feet high 5306.2.1 Medical gas rooms 5306.2.3 Medical gas cabinets 5606.7 Storage of small arm ammunition, powder-actuated tool loads, black powder or smokeless propellant 5704.3.5.1 Below grade storage of combustible liquids 5704.3.7.5.1 Flammable and combustible liquid storage rooms 5704.3.8.4 Flammable and combustible liquid storage warehouses 5705.3.7.3 Flammable and combustible liquid Group H-2 or H-3 areas 5706.4.10.5 Bulk plants and terminals 5706.4.10.5.1 Cargo tank loading racks 5806.3.2 Sterilization systems 6004.1.2.2 Gas cabinets for highly toxic and toxic gas 6004.1.3.1 Exhausted enclosures for highly toxic and toxic gas 6004.2.2.6 Gas rooms for highly toxic and toxic gas 6004.3.3 Outdoor storage for highly toxic and toxic gas 6109.9 Storage of LPG within buildings accessible to the public 6304.1.4 Solid and liquid oxidizer storage areas 6404.2.2 Outdoor storage areas of pyrophoric materials with overhead construction 6504.1.1 Pyroxylin plastic storage cabinets and vaults 6504.1.3 Pyroxylin plastic storage vaults 6504.2 Pyroxylin plastic storage, handling and use Building Code Sprinkler requirements as set forth in the construction codes, including the Building Code

For SI: 1 cubic foot = 0.023 m 3 .

903.3 Installation requirements.

Except as otherwise provided in this code, sprinkler systems shall be designed and installed in accordance with the construction codes, including the Building Code.

903.3.1 Inspector's test gauge.

A pressure gauge shall be installed at or near the inspector's test connection in Group R-2 occupancies, converted dwellings, and single room occupancies to enable persons responsible for inspecting or testing the sprinkler system, including certificate of fitness holders, plumbers, master fire suppression contractors and department representatives, to visually confirm the static pressure in the system. Installation of a pressure gauge shall constitute an operational requirement of this code.

903.4 Sprinkler system supervision and alarms.

All valves controlling the water supply for sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures, and water-flow switches on all sprinkler systems shall be electrically supervised by the fire alarm system where a fire alarm system is required by Section 907 of the Building Code.

Exceptions:

1. Sprinkler systems protecting Group R-3 occupancies.

2. Reserved.

3. Sprinkler systems installed in accordance with NFPA 13R, as modified by FC Appendix B, where a common supply main is used to supply both domestic water and the sprinkler system, and a separate shutoff valve for the sprinkler system is not provided, except where the Building Code requires such sprinkler system to be supervised.

4. Jockey pump control valves that are sealed or locked in the open position.

5. Control valves to commercial kitchen hoods, paint spray booths or dip tanks that are sealed or locked in the open position.

6. Valves controlling the fuel supply to fire pump engines that are sealed or locked in the open position.

7. Trim valves to pressure switches in dry, preaction and deluge sprinkler systems that are sealed or locked in the open position.

903.5 Maintenance.

Sprinkler systems shall be periodically inspected, tested, serviced and otherwise maintained in accordance with FC 901.6 and the rules. Except as otherwise provided in FC 903.5.1 through 903.5.3, sprinkler systems shall be inspected and otherwise maintained as follows:

1. Sprinkler systems shall be inspected at least once a month by a person holding a certificate of fitness, employed by the owner, to ensure that all parts of the system are in perfect working order, and that the department connections, if any, are ready for immediate use by the department. A detailed record of each inspection shall be kept for examination by any representative of the department.

2. There shall be one or more employees instructed in the maintenance of sprinkler systems.

3. There shall be kept available at all times in the premises a supply of at least six extra sprinkler heads, representative of the sprinkler heads installed on the sprinkler system, to replace promptly any fused or damaged sprinklers.

4. Fire department connections shall be hydrostatically tested at least once every 5 years, in accordance with FC 912.6.

903.5.1 Sprinkler systems in converted dwellings and single room occupancies.

In any converted dwelling or tenement used in whole or in part for single room occupancy, regardless of occupancy classification, in which a sprinkler system has been installed pursuant to the requirements of the Multiple Dwelling Law, such sprinkler system shall be inspected and otherwise maintained as follows:

1. Sprinkler systems shall be inspected at least once a month by a person employed by the owner, holding a certificate of fitness issued by the department, a fire suppression contractor license issued by the Department of Buildings, or, for a sprinkler system with not more than thirty sprinkler heads, a plumber, to ensure that all parts of the system are in perfect working order, and that the department connections, if any, are ready for immediate use by the department. Such inspection shall include a check of all control valves on the system, including the main supply control valve, making certain the valves are fully open and sealed in such open position; a check of the static pressure in the sprinkler system from a pressure gauge located at or near the inspector's test connection, making certain the system design pressure is being maintained; a check that all sprinkler heads are in place; and such other requirements as the commissioner may prescribe. A detailed record of each inspection shall be kept for examination by any representative of the department.

2. There shall be one or more employees instructed in the location and status of the sprinkler system control valves.

3. There shall be kept available at all times in the premises a supply of at least six extra sprinkler heads, representative of the sprinkler heads installed at the premises, to replace promptly any fused or damaged sprinklers, except that a supply of at least three extra sprinkler heads shall be kept available for any sprinkler system installed in accordance with NFPA 13R, as modified by FC Appendix B.

4. Fire department connections shall be hydrostatically tested at least once every 5 years in accordance with FC 912.6.

5. A flow test of the sprinkler system shall be conducted at least once every year. Such test shall be conducted at the owner's risk by his or her representative, who shall be a plumber or licensed master fire suppression contractor. Upon order of the commissioner, but at least once every 5 years, such flow test shall be conducted before a representative of the department. A report of each test, on an approved form, shall be certified by such plumber or licensed master fire suppression contractor and shall be kept for not less than 5 years and made available for inspection by any representative of the department.

6. The owner or managing agent of any building subject to the requirements of this section shall maintain a record of each inspection and test and a listing of all outstanding violations issued pursuant to this section. Such records and listing shall be made available for inspection by occupants of such residential buildings during regular business hours.

903.5.2 Sprinkler systems in other R-2 occupancies.

Except as otherwise provided in FC 903.5.1, in Group R-2 occupancies, sprinkler system shall be inspected and otherwise maintained as follows:

1. Sprinkler systems shall be inspected at least once a month by a person employed by the owner, holding a certificate of fitness issued by the department, a fire suppression contractor license issued by the Department of Buildings, or, for a sprinkler system with not more than thirty sprinkler heads, a plumber, to ensure that all parts of the system are in perfect working order, and that the department connections, if any, are ready for immediate use by the department. Such inspection shall include a check of all control valves on the system, including the main supply control valve, making certain the valves are fully open and sealed in such open position; a check of the static pressure in the sprinkler system from a pressure gauge located at or near the inspector's test connection, making certain the system design pressure is being maintained; a check that all sprinkler heads are in place; and such other requirements as the commissioner may prescribe. A detailed record of each inspection shall be kept for examination by any representative of the department.

2. There shall be one or more employees instructed in the location and status of the sprinkler system control valves.

3. There shall be kept available at all times in the premises a supply of at least six extra sprinkler heads, representative of the sprinkler heads installed at the premises, to replace promptly any fused or damaged sprinklers, except that a supply of at least three extra sprinkler heads shall be kept available for any sprinkler system installed in accordance with NFPA 13R, as modified by FC Appendix B.

4. Fire department connections shall be hydrostatically tested at least once every 5 years in accordance with FC 912.6.

5. A flow test of the sprinkler system shall be conducted upon order of the commissioner, but at least once every 30 months. Such test shall be conducted at the owner's risk by his or her representative, who shall be a plumber or licensed master fire suppression contractor. Upon order of the commissioner, but at least once every 5 years, such test shall be conducted before a representative of the department. A report of each test, on an approved form, shall be certified by such plumber or licensed master fire suppression contractor and shall be kept for not less than 5 years and made available for inspection by any representative of the department.

6. The owner or managing agent of any building subject to the requirements of this section shall maintain a record of each inspection and test and a listing of all outstanding violations issued pursuant to this section. Such records and listing shall be made available for inspection by occupants of such residential buildings during regular business hours.

903.5.3 Sprinkler systems in Group R-3 occupancies.

Sprinkler systems in buildings classified in Group R-3 occupancies shall be maintained in perfect working order.

903.5.4 Sprinkler system control valve signage.

A sign identifying the location of the sidewalk box housing the sprinkler system control valve shall be conspicuously posted on the exterior wall of the building directly opposite the sidewalk box. Such sign shall have red letters 1 inch (25 mm) in height on a white background and read: "Sprinkler System Shutoff Valve (indicate distance ) Feet Opposite This Sign" or other approved design.

903.6 Dry pipe sprinkler system valves.

In addition to the maintenance requirements set forth in FC 903.5, any dry pipe valve installed in a sprinkler system shall be trip tested at least once every 5 years and whenever the system is altered. Such trip test shall be conducted at the owner's risk, with the control valve fully open and the quick-opening device, if provided, in service, by a master fire suppression contractor licensed by the Department of Buildings before a representative of the department.

Section FC 904. Fire Extinguishing Systems

Open this section

904.1 General.

Fire extinguishing systems shall be designed, installed, operated and maintained in accordance with this section, FC 901, the terms and conditions of the listing, if applicable, the applicable referenced standards set forth in FC Table 904.1, and the manufacturer's instructions.

Exception: Sprinkler systems, which are governed by FC 903.

FC Table 904.1 Fire Extinguishing System Referenced Standards

Fire Extinguishing System Referenced Standard Aerosol fire extinguishing systems NFPA 2010 Carbon dioxide fire extinguishing system NFPA 12 Clean agent fire extinguishing systems NFPA 2001 Dry chemical fire extinguishing systems NFPA 17 Expansion foam systems (low, medium and high) NFPA 11 Foam water sprinkler and spray systems NFPA 16 and NFPA 25 Halon 1301 fire extinguishing systems NFPA 12A Water mist fire extinguishing systems NFPA 750 Water Spray Fixed Systems for Fire Protection NFPA 15 Wet chemical fire extinguishing systems NFPA 17A

904.1.1 Fire extinguisher system design.

Fire extinguishing systems may be engineered or pre-engineered. Pre-engineered systems shall be of a type for which a certificate of approval has been issued in accordance with FC 112 and 901.4.5. Except as otherwise provided in this code or other applicable law, rule, regulation or standard, fire extinguishing systems may be designed as local applications or as total flooding systems. All activation devices and other system components shall be listed and installed in accordance with the listing and the manufacturer's instructions.

904.1.2 Installation acceptance testing.

All fire extinguishing systems shall be subject to acceptance test conducted at the owner's risk by his or her representative before a representative of the department. The owner's representative shall furnish the necessary equipment required to conduct the test. A discharge test may be required as set forth in the applicable installation standard or as required by the department when there is evidence that the system will not provide the necessary level of protection.

904.1.3 Additional safeguards.

If an area is protected by a fire extinguishing system which uses an extinguishing agent that will make the protected area hazardous by its discharge or thermal decomposition, suitable safeguards shall be provided to ensure prompt evacuation, to prevent entry into such atmospheres, and to provide means for prompt rescue of any trapped personnel. Such safeguards shall include establishment of a trained brigade, equipped with and qualified in the use of self-contained breathing apparatus with 30-minute minimum supply, for prompt search of the protected area.

Exception: Self-contained breathing apparatus shall not be required for a clean agent fire extinguishing system installation if:

1. The installation is provided with an alarm system that is connected to an approved central station.

2. The protected area is provided with an approved fixed emergency forced ventilation system able to expel the extinguishing agent. Such emergency forced ventilation system shall have a capacity sufficient to effect at least twenty air changes per hour.

3. The protected area is of a size, design and/or occupied in such a manner that egress will not be impeded.

4. The protected area is not normally occupied by any individual requiring assistance in evacuation.

904.1.4 Prohibited fire extinguishing systems.

It shall be unlawful to install carbon dioxide, halon and clean agent fire extinguishing systems as set forth in FC 904.1.4.1 through 904.1.4.3.

904.1.4.1 Existing carbon dioxide systems.

It shall be unlawful to install or continue to maintain total flooding carbon dioxide fire extinguishing systems within normally occupied areas, including commercial kitchens. Total flooding carbon dioxide systems installed in normally occupied areas prior to July 1, 2008 were required by this code to be removed by July 1, 2013. Existing total flooding carbon dioxide fire extinguishing systems in such areas shall be removed and a replacement fire extinguishing system installed, where required, in accordance with the Building Code, this code or other applicable laws, rules and regulations.

904.1.4.2 Existing halon systems.

It shall be unlawful to install a halon system in any building or occupancy. Lawfully existing halon fire extinguishing systems shall be maintained in accordance with FC 904.5. If a lawfully existing system cannot be maintained under the laws, rules, regulations, standards and design and installation approvals under which it was installed, such system shall be removed and replaced with a type of fire extinguishing system complying with this code.

904.1.4.3 Clean agent systems.

It shall be unlawful to install clean agent systems that are not total flooding systems. Lawfully existing clean agent fire extinguishing systems that are not total flooding systems shall be maintained in accordance with FC 904.5. If a lawfully existing system cannot be maintained under the laws, rules, regulations, standards and design and installation approvals under which it was installed, such system shall be removed and replaced with a type of fire extinguishing system complying with this code.

904.2 Where required.

Where this code or the rules requires the installation of a fire extinguishing system, other than a sprinkler system, the commissioner shall approve the type of fire extinguishing system to be installed. Fire extinguishing systems installed as an alternative to sprinkler systems otherwise required by this code or the construction codes, including the Building Code, shall be approved by the commissioner. Such a system may be accepted by the commissioner where the nature of the fire hazard is such that water would be ineffective or hazardous as an extinguishing agent, or the need to preserve the historic, irreplaceable or special nature of the contents of the occupancy militates against the installation of a sprinkler system. Sprinklers shall not be omitted from any room or area merely because it is of fire-resistance-rated construction or contains electrical equipment except as allowed by Section 903 of the Building Code.

If a system using a fixed amount of extinguishing agent is authorized to be installed in lieu of a required sprinkler system or any other fire extinguishing system otherwise required by law, a connected reserve of charged agent cylinders equal to the primary supply shall be provided. The commissioner may impose additional requirements on the installation of any fire extinguishing system to be installed in lieu of any required sprinkler system. Fire extinguishing systems shall not be considered alternatives for the purposes of exceptions or reductions allowed by other requirements of this code.

904.3 Installation.

Fire extinguishing systems shall be installed in accordance with this section.

904.3.1 Electrical wiring.

Electrical wiring shall be in accordance with the Electrical Code.

904.3.2 Activation.

Unless otherwise provided by this code or the rules, fire extinguishing systems shall be designed and installed to activate automatically. Automatically activating fire extinguishing systems shall additionally be provided with a manual means of activation.

904.3.3 System interlocking.

Automatic equipment interlocks with fuel shutoffs, ventilation controls, door closers, window shutters, conveyor openings, smoke and heat vents, and other features necessary for proper operation of the fire extinguishing system shall be provided as required by the construction code or other design and installation standard utilized for the hazard.

904.3.4 Alarms and warning signs.

Where alarms are required to indicate the operation of fire extinguishing systems, distinctive audible, visible alarms and warning signs shall be provided to warn of pending agent discharge. Where exposure to automatic-extinguishing agents poses a hazard to persons and a delay is required to ensure the evacuation of occupants before agent discharge, a separate warning signal shall be provided to alert occupants once agent discharge has begun. Carbon dioxide fire extinguishing systems, where allowed, shall comply with the signage requirements of NFPA 12.

904.3.5 Monitoring.

All indoor fire extinguishing systems, except commercial cooking, domestic cooking and spray finishing fire extinguishing systems, installed after the effective date of this section shall be monitored by an approved central station. Where a building fire alarm system is installed, all such indoor fire extinguishing systems, except domestic cooking systems, shall be monitored by such fire alarm system.

904.3.6 Flood hazard.

Non-water fire extinguishing system control panels located in areas of special flood hazard or on the premises of Group I-2 occupancies that are hospitals located in shaded X-Zones (as defined in Section G201.2 of Appendix G of the Building Code) shall be located at or above the design flood elevation in accordance with Appendix G of the Building Code.

904.3.7 Additional safety measures.

Additional safety measures shall be provided for the fire extinguishing systems as set forth in FC 904.3.7.1 and 904.3.7.2.

904.3.7.1 Carbon dioxide systems.

Carbon dioxide systems, where allowed, shall be provided with the additional safety measures set forth in FC 904.3.7.1.1 through 904.3.7.1.8.

904.3.7.1.1 Egress precautions.

All areas whose atmospheres will be made hazardous by the discharge of carbon dioxide shall be provided with:

1. Exit and exit routes that are kept clear at all times.

2. Lighting and exit directional signs in accordance with the construction codes, including the Building Code.

3. Only outward swinging, self-closing doors at exits, and panic hardware on any such doors that are secured with a locking or latching device.

904.3.7.1.2. Ventilation and other safety equipment.

A carbon dioxide system shall be provided with a fixed emergency forced ventilation system able to clear the area with sufficient capacity to accomplish at least 6 air changes per hour, and such other safety equipment as may be prescribed by the commissioner.

904.3.7.1.3 Detection, activation, alarm and control.

Detection, predischarge alarms and discharge alarms shall be provided within and outside the protected area and such other areas that are made hazardous by a carbon dioxide discharge. Such alarms shall be audible and visible.

904.3.7.1.3.1 Automatic operation.

The carbon dioxide fire extinguishing system shall be activated by an automatic cross-zoned detection system in which activation of a detection device in one zone shall sound a local alarm and transmit an alarm to an approved central station, and activation of a detection device in the cross zone shall initiate the predischarge warning signal and after a time delay, initiate the discharge of carbon dioxide. The predischarge warning signal time delay shall be of sufficient duration to allow for evacuation from the protected area. Distinct alarms shall indicate the activation of a detector in one zone, the activation of a detector in a cross zone (predischarge alarm) and the discharge of carbon dioxide. Such alarms shall be continued until the atmosphere has been returned to normal except that the alarm for the detector in one zone may be discontinued when the alarm for the cross-zoned detector is activated.

Exceptions:

1. A carbon dioxide fire extinguishing system activated solely by manual means may be installed with department approval upon a showing satisfactory to the department of the need for such a system.

2. A detection system that is not cross-zoned may be installed with department approval upon a showing satisfactory to the department of the need for such a detection and activation system.

904.3.7.1.3.2 Manual operation.

A manual pull station shall be provided which, upon activation, transmits an alarm to an approved central station, overrides any delay other than the predischarge delay, and causes the carbon dioxide to discharge. Activation of a carbon dioxide fire extinguishing system by means of a manual pull station shall result in a complete predischarge delay sequence prior to system discharge.

904.3.7.1.3.3 Abort systems.

Abort systems may be installed, but shall be limited to systems activated by smoke detectors. Abort controls shall be located in the protected area near the means of egress for the area, and shall be designed to cause the discharge of carbon dioxide after a time delay unless the abort control is reactivated for another cycle of delay. Abort controls shall not interfere with transmission of local alarms or central station alarms.

904.3.7.1.3.4 Power supply.

Power supply to the alarm system shall be in accordance with applicable requirements of the Electrical Code and the construction codes, including the Building Code.

904.3.7.1.4 Pressure relief venting.

The protected area enclosure shall be provided with suitable pressure relief venting which vents outdoors.

Exception: Such venting shall not be required when a registered design professional certifies that the walls, ceilings and floors comprising the protected space have sufficient porosity and leakage to prevent damage to the integrity of such space upon discharge of the extinguishing agent, and that the inert gas agent leakage into other non-flooded rooms and spaces will not reach dangerous concentrations.

904.3.7.2 Clean agent systems.

Clean agent systems, where allowed, shall be provided with the additional safety measures set forth in FC 904.3.7.2.1 through 904.3.7.2.6.

904.3.7.2.1 System alarm and activation.

Audible and visible alarms shall be installed both inside and outside the protected area to signal the activation of an automatic detection device and the operation of the fire extinguishing system. Such signals shall continue until the atmosphere has been returned to normal. Activation of a single automatic detection device shall sound a local alarm and transmit an alarm to an approved central station. Unless the alarm is cancelled by an abort system as set forth in FC 904.3.7.2.3, activation of a second automatic detection device shall, within 30 seconds, initiate the discharge of clean agent. Power supply to the alarm system shall be in accordance with the Electrical Code, the construction codes, including the Building Code, and NFPA 2001, as modified by FC Appendix B.

904.3.7.2.2 Warning and instruction signs.

Warning and instruction signs shall be posted at entrances to and within the protected area subject to flooding.

904.3.7.2.3 Abort systems.

Abort systems may be installed only on systems activated by smoke detectors. Abort controls shall be manually operated, shall be located in the protected area, and shall cause the discharge of the clean agent after a 2-minute delay unless the abort control is reactivated for another cycle of delay. A manual pull station shall be provided which, upon activation, shall transmit an alarm to an approved central station, override the delay and cause the clean agent to discharge immediately. Abort controls shall not interfere with transmission of local alarms or central station alarms.

904.3.7.2.4 Means of egress.

Where the protected area is normally occupied, provision shall be made for adequate clear routes of exit with doors opening in direction of travel. Emergency lighting shall be provided for such exits. Exit directional signs shall clearly indicate the path of egress and exits shall be clearly marked.

904.3.7.2.5 Fixed emergency forced ventilation.

When the protected area is normally occupied, a fixed emergency forced ventilation system sufficient to accomplish at least six air changes per hour of the flooded protected area shall be provided unless all of the following apply:

1. The clean agent fire extinguishing system is used to extinguish a Class A fire.

2. The design concentration does not exceed the "no observable adverse effect level" for halocarbon agents, or "no effect level" for inert gas agents as defined in NFPA 2001, as modified by FC Appendix B.

3. If other than inert gas agents are used, the quantity of the thermal decomposition products formed from such agents is below the dangerous toxic load (DTL) for humans as described in Meldrum's "Toxicology of Substances in Relation to Major Hazards: Hydrogen Fluoride" (HMSO, London, 1993). Upon request, documentation of hazard assessment of thermal decomposition products formed from such agents shall be filed with the department.

904.3.7.2.6 Pressure relief venting.

Clean agent fire extinguishing systems using inert gas agents shall be provided with suitable pressure relief venting for the flooded protected area that discharges outdoors.

Exception: Such venting shall not be required when a registered design professional certifies that the walls, ceilings and floors comprising the protected space have sufficient porosity and leakage to prevent damage to the integrity of such space upon discharge of the extinguishing agent, and that the inert gas agent leakage into other non-flooded rooms and spaces will not reach dangerous concentrations.

904.3.8 Commercial cooking systems.

Commercial cooking fire extinguishing systems shall be installed in accordance with FC 904.3.8.1 through 904.3.8.3.

904.3.8.1 Types of systems approved for commercial cooking operations.

Commercial cooking operations shall be protected by one of the following types of fire protection systems, as listed for commercial cooking operations.

1. Wet chemical fire extinguishing systems designed in accordance with NFPA 17A, as modified by FC Appendix B, and tested in accordance with UL 300.

2. Foam-water sprinkler system or foam-water spray systems designed in accordance with NFPA 16, as modified by FC Appendix B.

3. Water mist systems designed in accordance with NFPA 750, as modified by FC Appendix B.

904.3.8.1.1 Dry chemical, non-listed wet chemical and carbon dioxide systems.

Dry chemical systems, wet chemical systems not listed to the UL 300 standard and carbon dioxide systems may not be used for commercial cooking operations and shall be removed and replaced with a type of fire extinguishing system complying with this code.

904.3.8.2 Manual activation device.

A manual activation device for the fire extinguishing system, except foam-water systems, shall be installed at a location near a means of egress that is readily accessible from the cooking area and not less than 10 feet (3048 mm) nor more than 20 feet (6096 mm) from the commercial cooking appliances protected by the fire extinguishing system, or other approved location. The manual activation device shall be located a minimum of 42 inches (1067 mm) and a maximum of 48 inches (1219 mm) above the floor. The manual activation device shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to activate the fire extinguishing system. A sign or marking in accordance with FC Table 609.7 that clearly identifies the commercial cooking appliances being protected shall be posted on or adjacent to the manual activation device. The manual activation device shall be kept unobstructed at all times.

904.3.8.3 System interconnection.

The activation of the fire extinguishing system shall automatically shut down the fuel and electrical power supply to the cooking equipment. The fuel and electrical supply reset shall be manual.

904.4 Installation inspection and testing.

Fire extinguishing systems shall be inspected and tested upon completion of the installation prior to the installation acceptance testing required by FC 904.1.2.

904.4.1 Inspection.

The fire extinguishing system shall be inspected for the following conditions:

1. Hazard specification for consistency with design hazard.

2. Type, location and spacing of automatic- and manual-initiating devices.

3. Size, placement and position of nozzles or discharge orifices.

4. Location and identification of audible and visible alarm devices.

5. Identification of devices with proper designations.

6. Operating instructions, to ensure that the system is correctly operated during the acceptance testing.

904.4.2 Alarm testing.

Notification appliances, connections to fire alarm systems, and connections to an approved central station shall be tested to verify proper operation, including the following conditions:

1. The audibility and visibility of notification appliances signaling agent discharge or system operation, where required, shall be verified.

2. Central station connections shall be tested to verify proper identification and retransmission of alarms.

904.5 Maintenance of fire extinguishing systems.

Fire extinguishing systems shall be periodically inspected, tested and otherwise maintained in accordance with FC 901, 904.1.1 and 904.4, the applicable NFPA standard, and the system listing. Additional maintenance shall be performed as set forth in FC 904.5.1 through 904.5.13*, FC Table 904.5.2, and the rules.

* Editor's note: correct reference should be FC 904.5.1 through 904.5.3.

904.5.1 Monthly inspection.

At least once a month, a visual inspection of the fire extinguishing system shall be conducted by a trained and knowledgeable person to confirm that the system appears to be in good working order, including the following conditions:

1. The fire extinguishing system is intact and undamaged, including the extinguishing agent container, system piping, nozzles and protective nozzle caps.

2. Any fusible links or other fire detection devices are clean.

3. Access to each manual activation device, if required, for the fire extinguishing system is not obstructed and any tamper indicator is intact.

4. Check the pressure gauge, control panel or control unit, as applicable, to determine whether the fire extinguishing system is operational and whether there are any supervisory or trouble signals.

5. If an automatic foam system or water mist system, check the water supply valve to confirm that it is in the locked, open position; if the system is manually operated, confirm that the water supply is in good working order.

6. The maintenance tag for the fire extinguishing system is in place and has not expired.

904.5.2. Semiannual inspection.

A licensed master fire suppression piping contractor holding a certificate of fitness properly trained and having knowledge of the installation, operation and maintenance of the specific fire extinguishing system, or a person holding a certificate of fitness under the direction and control of such license holder, shall inspect, test, service and otherwise maintain such system in accordance with this section and the manufacturer's specifications and servicing manuals at least on a semiannual basis. Such semiannual inspection, testing and servicing shall include all procedures necessary to determine that the system is in good working order, including the following actions:

1. Verification that the hazard has not changed.

2. Verification that the fire extinguishing system has not been altered.

3. Examination of all detection systems, alarms, manual stations, extinguishing agent containers, releasing devices, piping, hose assemblies, nozzles, and all ancillary equipment.

4. Verification that the extinguishing agent has not been discharged.

5. Verification that the agent distribution piping is not obstructed.

6. Verification that the extinguishing agent container and/or ancillary pressure containers have been, as applicable, inspected, retested and marked in conformance with the requirements of the United States Department of Transportation.

7. A test of the system's automatic and manual releasing devices, including any associated equipment. Fixed temperature-sensing elements shall be maintained to ensure proper operation of the system.

8. A test of the gas and electric power source shut-off (interlock) devices, if applicable.

9. Preparation and submission to the owner of a written report of any system defects.

10. Upon satisfactory completion of the semiannual inspection and correction of all defects, providing the owner with an inspection, testing and service compliance tag. Such tag shall indicate the date issued, the name and license number of the licensed master fire suppression piping contractor issuing the tag and the certificate of fitness holder conducting the inspection, and that the system was found to be in compliance with the requirements of this section.

FC Table 904.5.2 Fire Extinguishing System Inspection, Testing and Maintenance Schedule

System Inspection Testing Other Maintenance Aerosol fire extinguishing systems Monthly Annually Carbon dioxide fire extinguishing system Monthly Semiannually Annually Clean agent fire extinguishing systems Monthly Semiannually Annually Dry chemical fire extinguishing systems Monthly Semiannually Expansion foam systems (low, medium and high) Monthly Annually Foam water sprinkler and spray systems See NFPA 25 Halon 1301 fire extinguishing systems Monthly Semiannually Water mist fire extinguishing systems See NFPA 25 Wet chemical fire extinguishing systems Monthly Semiannually

904.5.3 Five-year retest.

All fire extinguishing systems shall be retested once every five years from the date of acceptance of the system. The first retest of fire extinguishing systems lawfully existing on the effective date of this provision shall be conducted on or before the fifth anniversary of the date of acceptance after such effective date. Such test shall be conducted, and reported to the department, in the manner prescribed by rule, by a licensed master fire suppression contractor holding a certificate of fitness, properly trained and having knowledge of the installation, operation and maintenance of the specific fire extinguishing system, or a person holding a certificate of fitness under the direction and control of such license holder.

Exception: Commercial cooking and domestic cooking fire extinguishing systems.

904.6 Additional maintenance requirements.

The following fire extinguishing systems shall be maintained in accordance with the additional maintenance requirements set forth in FC 904.6.1 through 904.6.10.

904.6.1 Aerosol systems.

Aerosol fire extinguishing systems shall be maintained in accordance with FC 901.6.1 and 904.5.

904.6.2 Carbon dioxide systems.

Carbon dioxide systems shall be maintained in accordance with FC 901.6.1, 904.5 and 904.6.2.1 through 904.6.2.4.

904.6.2.1 High-pressure containers.

High-pressure containers shall be weighed and the date of the last hydrostatic test shall be verified at 6-month intervals. Where a container shows a loss in original content of more than 10 percent, the container shall be refilled or replaced.

904.6.2.2 Low-pressure containers.

The liquid-level gauges of low-pressure containers shall be observed at one-week intervals. Where a container shows a content loss of more than 10 percent, the container shall be refilled to maintain the minimum gas requirements.

904.6.2.3 System hoses.

System hoses shall be examined at 12-month intervals for damage. Damaged hoses shall be replaced or tested. At five-year intervals, all hoses shall be tested.

904.6.2.3.1 Test procedure.

Hoses shall be tested at not less than 2,500 pounds per square inch (psi) (17 238 kPa) for high-pressure systems and at not less than 900 psi (6206 kPa) for low-pressure systems.

904.6.2.4 System components.

System components, such as switches, door and window releases, interconnected valves, damper releases and supplementary alarms, shall be manually operated at 12-month intervals to ensure that such components are in proper operating condition.

904.6.3 Clean agent systems.

Clean agent systems shall be maintained in accordance with FC 901.6.1, 904.5, 904.6.3.1 and 904.6.3.2.

904.6.3.1 Containers.

The extinguishing agent quantity and pressure of the containers shall be checked at 6-month intervals. Where a container shows a loss in original weight of more than 5 percent or a loss in original pressure, adjusted for temperature, of more than 10 percent, the container shall be refilled or replaced. The weight and pressure of the container shall be recorded on a tag attached to the container.

904.6.3.2 System hoses.

System hoses shall be examined at 12-month intervals for damage. Damaged hoses shall be replaced or tested. All hoses shall be tested at 5-year intervals.

904.6.4 Dry chemical systems.

Dry chemical systems shall be maintained in accordance with FC 901.6.1, 904.5 and 904.6.4.1.

904.6.4.1. Additional maintenance requirements.

Extinguishing agent containers shall be weighed to verify the required amount of agent. Stored pressure-type units shall be checked for the required pressure. The cartridge of cartridge-operated units shall be weighed and replaced at intervals specified by the manufacturer.

904.6.5 Foam systems.

Foam systems shall be maintained in accordance with FC 901.6.1, 904.5 and 904.6.5.1.

904.6.5.1 Commercial cooking installations.

Foam fire extinguishing systems installed to protect a commercial cooking operation shall additionally comply with the requirements of FC 904.3.8.

904.6.6 Halon systems.

Lawfully existing halon systems shall be maintained in accordance with FC 901.6.1, 904.5 and 904.6.6.1 through 904.6.6.3. All other halon systems shall be removed in accordance with FC 904.1.4.2.

904.6.6.1 Containers.

The extinguishing agent quantity and pressure of containers shall be checked at least on a semiannual basis. Where a container shows a loss in original weight of more than 5 percent or a loss in original pressure (adjusted for temperature) of more than 10 percent, the container shall be refilled or replaced. The weight and pressure of the container shall be recorded on a tag attached to the container.

904.6.6.2 System hoses.

System hoses shall be examined at 12-month intervals for damage. Damaged hoses shall be replaced or tested. At 5-year intervals, all hoses shall be tested.

904.6.6.2.1 Test procedure.

For Halon 1301 systems, hoses shall be tested at not less than 1,500 psi (10 343 kPa) for 600 psi (4137 kPa) charging pressure systems and not less than 900 psi (6206 kPa) for 360 psi (2482 kPa) charging pressure systems. For Halon 1211 hand-hose line systems, hoses shall be tested at 2,500 psi (17 238 kPa) for high-pressure systems and 900 psi (6206 kPa) for low-pressure systems.

904.6.6.3 System components.

System components, such as switches, door and window releases, interconnected valves, damper releases and supplementary alarms, shall be manually operated at 12-month intervals to ensure such components are in proper operating condition.

904.6.7 Water mist systems.

Water mist systems shall be maintained in accordance with FC 901.6.1, 904.5 and NFPA 750, as modified by FC Appendix B.

904.6.8 Wet chemical systems.

Wet chemical systems shall be maintained in accordance with FC 901.6.1, 904.5 and 904.6.8.1 through 904.6.8.3.

904.6.8.1 Additional maintenance requirements.

Extinguishing agent containers shall be weighed to verify the required amount of agent. Stored pressure-type units shall be checked for the required pressure. The cartridge of cartridge-operated units shall be weighed and replaced at intervals specified by the manufacturer.

904.6.8.2 Fusible link maintenance.

Fixed temperature-sensing elements shall be maintained to ensure proper operation of the system.

904.6.8.3 Commercial cooking installations.

Wet chemical fire extinguishing systems installed to protect a commercial cooking operation shall additionally comply with the requirements of FC 904.3.8.

904.6.9 Commercial cooking systems.

Commercial cooking fire extinguishing systems shall be maintained in accordance with FC 609, 901.6.1, 904.5 and 904.6.9.1.

904.6.9.1 Fusible link and sprinkler head replacement.

Fusible links and foam water sprinkler heads shall be replaced at least annually, and other protection devices shall be serviced or replaced in accordance with the manufacturer's instructions.

Exception: Frangible bulbs are not required to be replaced annually.

904.6.10 Domestic cooking systems.

Fire extinguishing systems installed on domestic cooking hoods in Group I-2 occupancies, or in any other occupancy, shall be installed and maintained in accordance with FC 904.6.10.1 and 904.6.10.2.

904.6.10.1 Installation.

Such fire extinguishing systems shall be installed by a master fire suppression piping contractor, who shall certify to the department that the installation is in compliance with the construction codes and this code. Such certification shall be submitted to the department in the manner prescribed by the department.

904.6.10.2 Maintenance.

Such fire extinguishing systems shall be maintained in accordance with FC 901.6.1 and 904.5.