NYC Administrative Code Title 29, Chapter 2 New York City Fire Code, part 9 of 15
Section FC 3504 to Section FC 5003: 28 sections.
Section FC 3504. Fire Safety Requirements
3504.1 Protection of combustibles.
Combustible material and combustible waste shall be protected during hot work operations in accordance with FC 3504.1.1 through 3504.1.9.
3504.1.1 Separation from combustibles.
Hot work operations involving cutting or welding shall be conducted at least 35 feet (10 668 mm) from combustible materials and combustible waste or shall be provided with appropriate shielding to prevent sparks, slag or heat from igniting exposed combustibles. All other hot work operations shall be conducted at least 25 feet (7620 mm) from combustible materials and combustible waste or shall be provided with appropriate shielding to prevent sparks, slag or heat from igniting exposed combustibles.
3504.1.2 Openings.
Openings or cracks in walls, floors, ducts or shafts within 35 feet (10 668 mm) of the hot work area shall be tightly covered to prevent the passage of sparks to adjacent combustible areas, or shielded by metal fire-resistant guards, or provided with curtains to prevent passage of sparks or slag.
3504.1.3 Housekeeping.
Combustible waste shall not be allowed to accumulate on floors and other surfaces within the hot work area. Hot work areas shall be regularly cleaned and combustible waste removed and disposed of lawfully.
3504.1.4 Conveyor systems.
Conveyor systems that are capable of carrying sparks to distant combustibles shall be shielded or shut down.
3504.1.5 Partitions.
Partitions segregating hot work areas from other areas of the building shall be of noncombustible construction. In fixed hot work areas, the partitions shall be securely connected to the floor such that no gap exists between the floor and the partition. Partitions shall prevent the passage of sparks, slag, and heat from the hot work area.
3504.1.5.1 Motor-fuel dispensing facilities.
The use of a torch within a repair garage located on a property upon which a motor-fuel dispensing facility is situated shall be conducted within a fire-rated enclosure. All doors of such enclosure shall be fireproof and self-closing.
3504.1.5.2 Repair garages.
In a repair garage with a capacity for more than one vehicle, hot work shall be conducted within a fire-rated enclosure in compliance with FC 3504.1.5.1 or behind a noncombustible screen that is positioned and of sufficient size to prevent the passage of sparks, slag and heat from the hot work area.
3504.1.6 Floors.
Areas designed for hot work operations shall have floors with noncombustible surfaces.
3504.1.7 Precautions in hot work.
Except as otherwise provided in FC 3510.4, hot work shall not be performed on a container or equipment that contains or has contained a flammable solid, flammable or combustible liquid or flammable gas until the container or equipment has been thoroughly cleaned, inerted or purged. Hot work on flammable and combustible liquid storage tanks shall be conducted in accordance with FC 3510. Hot work involving any flammable solid in any form shall be conducted only with the approval of the department.
3504.1.8 Sprinkler protection.
Sprinkler system protection shall not be shut off or impaired while hot work is performed unless approved by the commissioner. Where hot work is performed close to sprinklers, noncombustible barriers or damp cloth guards shall shield the individual sprinkler heads and shall be removed when the work is completed. If the work extends over several days, the shields shall be removed at the end of each workday.
3504.1.9 Fire detection systems.
Approved precautionary measures shall be taken to avoid accidental operation of automatic fire detection systems.
3504.2 Fire watch.
A fire watch shall be maintained and fire guards provided in accordance with FC 3504.2.1 through 3504.2.7.1.
3504.2.1 When required.
A fire watch shall be maintained during hot work operations. The fire watch shall continue for a minimum of 30 minutes after the conclusion of the work. The commissioner, or the responsible person implementing a hot work program, may extend the duration of the fire watch based on the hazards or work being performed.
3504.2.2 Location.
The fire watch shall observe the entire hot work area. Hot work conducted in areas with vertical or horizontal fire exposures that are not observable by a single individual shall have additional personnel assigned to ensure that exposed areas are monitored, including compliance with FC 3504.2.7.1.
3504.2.3 Duties.
Persons conducting a fire watch shall have the duties and responsibilities set forth in FC 901.7.2.1 with respect to the areas being monitored in connection with hot work operations.
3504.2.4 Reserved.
3504.2.5 Fire hoses.
Where hose lines are required, they shall be connected, charged and ready for operation.
3504.2.6 Portable fire extinguishers.
A minimum of one portable fire extinguisher complying with the requirements of FC 906 and with a minimum 2-A:20-B:C rating shall be provided and readily accessible within a 30 feet (9144 mm) travel distance of the location where hot work is performed and where the fire guards are positioned.
3504.2.7 Fire guards for torch operations.
The fire watch for torch operations conducted at the following locations shall be conducted by fire guards:
1. Construction sites.
2. On any rooftop, or in connection with any torch-applied roofing system operation.
3. In any building or structure, when the torch operation is conducted by a person holding a citywide permit for torch operations.
3504.2.7.1 Construction sites and torch-applied roofing systems.
A fire watch shall be maintained for each torch operation at a construction site and torch-applied roofing system operations in compliance with the requirements of FC 3504.2.7.1.1 and 3504.2.7.1.2.
3504.2.7.1.1 Fire watch coverage.
A fire guard shall be provided for each torch in operation, except that a single fire guard may be designated to conduct a fire watch for more than one torch operation on the same floor or level if each torch operation is not more than 50 feet (15 240 mm) from the fire guard, as measured by the actual path of travel, and the field of view of such fire guard encompasses all of the horizontal fire exposures of such torch operations.
3504.2.7.1.2 Fire watch on floors below.
In addition to the fire guard required by FC 3504.2.7.1.1, if the torch operation is being conducted at or near the edge of an unenclosed floor of a building, or near a floor opening, or other location where sparks and slag may travel to one or more lower floors or levels, a fire guard shall conduct a fire watch on each lower floor or level containing combustible surfaces or materials within 35 feet (10 668 mm) of the area of such floor or level that potentially would be exposed to such sparks or slag. Prior to commencement of the torch operation, the fire safety manager or responsible person shall inspect the lower floors or levels and take all necessary and appropriate precautions to protect any combustible surfaces and materials that potentially would be exposed to sparks and slag from the torch operation. A certification to that effect shall be made on the hot work authorization.
Exceptions:
1. A fire watch is not required on the floors or levels below a torch operation on a construction site when:
1.1. the torch operation is not being conducted at or near the edge of an unenclosed floor of a building;
1.2. the floor upon which the torch operation is being conducted is of noncombustible construction;
1.3. there are no floor or exterior building openings within 35 feet (10 668 mm) of the torch operation; and
1.4. prior to commencement of the torch operation, the fire safety manager or responsible person conducts an inspection and takes the precautions required pursuant to FC 3504.2.7.1.2.
2. Notwithstanding the foregoing exception, if sparks or slag generated by the torch operation are observed to extend beyond 35 feet (10 668 mm), thereby potentially exposing lower floors or levels, the torch operation shall be immediately discontinued, and the floors or levels below shall be inspected for any fire condition. If there is any potential exposure to combustible surfaces or materials on the floors below from such sparks and slag, noncombustible barriers shall be provided and any other necessary or appropriate precautions shall be taken. If such barriers and precautions fail to block the passage of sparks and slag, a fire watch shall be established on the floors or levels below.
3504.3 Area reviews.
Before hot work is authorized and at least once per day while the authorization is in effect, the hot work area shall be inspected by the responsible person to ensure that it is a fire safe area.
3504.3.1 Pre-hot work check.
A pre-hot work check shall be conducted by the responsible person prior to work to ensure that all equipment is safe and hazards are recognized and protected. A report of the check shall be kept at the work site during the work and for a minimum of 48 hours after work is completed, and made available for inspection by any representative of the department. The pre-hot work check shall be conducted at least once per day and shall verify the following:
1. The hot work equipment is in good working order.
2. The hot work area is clear of combustibles and flammable solids or that such materials present in the area are protected in accordance with FC 3504.1.1.
3. Exposed construction is of noncombustible materials or, if combustible, is protected.
4. Openings are protected.
5. Hot work area floors are clear of combustible waste accumulation.
6. Reserved.
7. Fire watch personnel, where required, are assigned.
8. Approved actions have been taken to prevent accidental activation of fire extinguishing systems and detection equipment in accordance with FC 3504.1.8 and 3504.1.9.
9. Portable fire extinguishers and fire hoses (where provided) are operable and available.
10. All persons performing hot work possess certificates of fitness, where such certificates are required.
11. All persons performing hot work requiring a permit possess a site-specific permit or citywide permit, authorizing such work.
Section FC 3505. Gas Welding and Cutting
3505.1 General.
Devices or attachments mixing air or oxygen with flammable gases prior to consumption, except at the burner or in a standard torch or blow pipe, shall not be allowed unless approved.
3505.2 Container storage, handling and use.
Storage, handling and use of compressed gas containers shall be in accordance with this section and FC Chapter 53.
3505.2.1 Containers connected for use.
A single container of oxygen and a single container of flammable gas may be installed on a cart without the separation of containers required by FC 5804.1.3 provided that the containers are connected to regulators, equipped with apparatus designed for cutting, welding or other hot work operation, and are otherwise ready for use, and are stored, handled and used in compliance with the following requirements:
1. Carts shall be designed and used in accordance with FC 5003.10.3.
2. Container valves shall have a fixed hand wheel, or other approved means by which the flow of gas may be immediately shut down during hot work operations.
3. Container valves shall be closed at the end of each workday and whenever work is discontinued or the cart moved.
4. Container valve outlet connections shall conform to the requirements of CGA V-1.
5. Separation of the cart from the hot work operation shall be maintained in accordance with FC 3505.5, or fire-resistant shields shall be provided.
6. A separation distance of 20 feet (6096 mm) shall be maintained between such carts.
3505.3 Precautions.
Oxygen containers and oxygen container valves, regulators, hose and other apparatus and fittings shall be kept free of oil or grease. Oxygen containers, apparatus and fittings shall not be handled with oily hands, oily gloves, or greasy tools or equipment.
3505.4 Acetylene gas.
Acetylene gas shall not be piped except in approved container manifolds and container manifold connections, or piped or utilized at a pressure exceeding 15 pounds per square inch gauge (psig) (103 kPa). Acetylene gas stored in containers shall be dissolved in a suitable solvent. Acetylene gas shall not be brought in contact with unalloyed copper, except in a torch.
3505.5 Remote locations.
Oxygen and fuel gas containers shall be located at a distance from the hot work area sufficient to protect such containers from heat, sparks, slag, or misdirection of the torch flame.
3505.6 Container shutoff.
The torch valve shall be closed and the gas supply to the torch completely shut off when hot work operations are discontinued for a period of 1 hour or more.
3505.6.1 Emergency shutoff.
Oxygen and fuel gas container valves shall be accessible to the torch operator or fire guard for immediate shutoff of the gas supply in the event of an emergency.
3505.7 Prohibited operations.
It shall be unlawful to conduct the following hot work operations:
1. Welding or cutting operations supported by or resting on compressed gas containers.
2. Torch-applied roof system operations on roofs constructed of combustible materials.
3. Use of an acetylene generator for hot work operations.
3505.8 Tests.
It shall be unlawful to test piping equipment or systems for leaks using a flame. Tests for suspected leaks in piping equipment and systems shall be made using soapy water.
Section FC 3506. Electric Arc Hot Work
3506.1 General.
The frame or case of electric hot work machines, except internal-combustion-engine-driven machines, shall be grounded. Ground connections shall be mechanically strong and electrically adequate for the required current.
3506.2 Return circuits.
Welding current return circuits from the work to the machine shall have proper electrical contact at joints. The electrical contact shall be periodically inspected.
3506.3 Disconnecting.
Electrodes shall be removed from the holders when electric arc welding or cutting is discontinued for any period of 1 hour or more. The holders shall be located to prevent accidental contact and the machines shall be disconnected from the power source.
3506.4 Emergency disconnect.
A switch or circuit breaker shall be provided so that fixed electric welders and control equipment can be disconnected from the supply circuit. The disconnect shall be installed in accordance with the Electrical Code.
3506.5 Damaged cable.
Damaged cable shall be removed from service until properly repaired or replaced.
Section FC 3507. Reserved
BetaNYC's copy has no text for this section. Read Section FC 3507 at American Legal Publishing.
Section FC 3508. Reserved
BetaNYC's copy has no text for this section. Read Section FC 3508 at American Legal Publishing.
Section FC 3509. Piping Manifolds and Hose Systems for Fuel Gases and Oxygen
3509.1 General.
The use of piping manifolds, protective equipment and hose systems in oxygen-fuel gas systems, including natural gas supplied from a utility for use in an oxygen-fuel gas system, shall be designed, installed, operated and maintained in accordance with FC 3509, FC Chapter 53 and NFPA 51.
3509.2 Protection.
Piping shall be protected against physical damage.
3509.3 Signage.
Signage shall be provided for piping and hose systems as follows:
1. Aboveground piping systems shall be marked in accordance with ASME A13.1.
2. Station outlets shall be marked to indicate their intended usage.
3. Signs shall be posted, indicating clearly the location and identity of section shutoff valves.
3509.4 Manifolding of containers.
Oxygen manifolds shall be located at least 20 feet (6096 mm) away from combustible waste and combustible material, including oil and grease, and gas containers containing flammable gases, unless the gas containers are separated from each other by a fire partition.
3509.5 Identification of manifolds.
Signs shall be posted for oxygen manifolds with service pressures not exceeding 250 psig (1379 kPa). Such signs shall read as follows:
LOW-PRESSURE MANIFOLD DO NOT CONNECT HIGH-PRESSURE CONTAINERS MAXIMUM PRESSURE 250 PSIG
3509.6 Clamps.
Hose connections shall be clamped or otherwise securely fastened.
3509.7 Inspection.
Hoses shall be inspected frequently for leaks, burns, wear, loose connections or other defects.
3509.8 Piped natural gas precautions.
When piped natural gas is used with oxygen in any hot work operation, a listed protective device that serves as a combination flashback arrester and backflow check valve shall be provided at an approved location on both the natural gas and oxygen supply lines so as to ensure the safe operation of all devices, equipment and systems, including the utility gas meter. Where pressure of the piped natural gas supply is insufficient to ensure such safe operation, approved equipment shall be provided between the gas meter and the fuel-consuming appliance that increases such pressure to the level required for such safe operation. Notwithstanding any section of this code to the contrary, such flashback arresters and check valves, pressure-increasing equipment, shall be installed as components of both new and existing installations. Installations involving the use of piped natural gas with oxygen in any hot work operation shall additionally comply with the rules.
Section FC 3510. Hot Work on Flammable and Combustible Liquid Storage Tanks
3510.1 General.
Hot work performed on the interior or exterior of tanks that hold or have held flammable or combustible liquids, when approved, shall be conducted in accordance with this section and NFPA 326.
3510.2 Department approval.
Approval shall be obtained from the department prior to conducting hot work on a tank that holds or has held flammable or combustible liquids. The application shall justify the need to conduct such hot work and identify the potential hazards and methods of controlling such hazards.
3510.3 Hazard prevention.
A pre-hot work check shall be performed in accordance with FC 3504.3.1. A fire watch shall be maintained with a combustible gas detector, to continuously monitor the work area and any other affected areas.
3510.4 Hot tapping.
Hot tapping may be conducted at bulk plants and terminals on tanks and piping only when approved by the department. Such work shall be conducted by persons with approved qualifications.
Section FC 3601. General
3601.1 Scope.
This section shall govern the design, installation, operation and maintenance of marinas mooring or storing more than five marine vessels or watercraft 65 feet (19812 mm) or less in length.
3601.2 General.
Marinas shall be designed, installed, operated and maintained in accordance with the requirements of NFPA 303 and this section.
Section FC 3602. Definitions
3602.1 Definitions.
The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.
FLOAT.
MARINA.
PIER.
VESSEL.
WHARF.
Section FC 3603. General Precautions
3603.1 Fire safety precautions.
Marinas shall comply with the fire safety precautions set forth in NFPA 303 and this section.
3603.2 Combustible waste.
Marinas shall be kept free of accumulations of combustible waste in accordance with FC 304. Rubbish and other combustible waste shall not be allowed to accumulate beneath marina structures, piers or wharves.
3603.3 Sources of ignition.
Open flames and open-flame devices shall not be used within 3 feet (914 mm) of combustible material. Open flames, open-flame devices and other sources of ignition shall not be stored or used in the areas in which smoking is prohibited pursuant to FC 3603.3.1. Portable electric lights approved for use in a hazardous location shall be used where flammable vapors may be present, and shall be equipped with safety devices designed to prevent physical damage to the bulbs.
3603.3.1 Smoking.
It shall be unlawful to smoke in the following areas of a marina, and any other areas as the commissioner may prescribe by rule:
1. Where fuels are stored or dispensed.
2. Where flammable or combustible liquids are stored, handled or used.
3. Battery storage and battery charging areas.
4. Covered or enclosed boat storage areas.
3603.4 Lumber and other combustible material storage.
Lumber and other combustible materials shall be stored in accordance with FC Chapter 28, at a location separate from the area in which marine vessel construction or repair, marine vessel or watercraft fueling, or other work involving the handling or use of flammable or combustible liquids or open flames is conducted.
Section FC 3604. Marina Operations
3604.1 General.
Marinas shall be operated in accordance with NFPA 303 and this section.
3604.2 Storage.
Marine vessels and watercraft shall be stored in accordance with Chapter 7 of NFPA 303 and this section.
3604.2.1 Clearances.
No vessel or watercraft shall be stored closer than 3 feet (914 mm) to any lot line, or closer than 3 feet (914 mm) horizontally from another vessel, unless access for firefighting operations is provided in another approved manner.
3604.2.2 Combustible waste and cargo.
All combustible waste and cargo shall be removed from vessels and watercraft in storage.
3604.2.3 Batteries and fuel.
Where practicable, batteries and all fuel shall be removed from the vessel. Where removal of batteries is impracticable, precautions during charging of batteries shall be taken in accordance with FC 3603. Where removal of fuel is impracticable, all tank stop valves shall be closed and the tank inspected to ensure that there are no leaks. Adequate ventilation shall be provided for hull and bilge areas.
3604.2.4 Covers.
Shrink-wrapped plastic or other material used to cover vessels in storage shall be flame-resistant in accordance with FC Chapter 8 and the rules.
3604.3 Hot work operations.
Hot work operations and other use of open flames shall comply with the requirements of FC Chapter 35 and this section. All flammable liquid, combustible liquid or flammable gas, except the fuel in stationary storage tanks of vessels, shall be removed from the vessel before any hot work is performed on the vessel. In addition, before hot work is performed batteries and battery terminals shall be protected against accidental shorting or sparking, or the batteries shall be removed. If hot work is to be conducted on a vessel's stationary fuel tank or fuel piping, both the tank and the piping shall first be emptied and purged. All areas of the vessel, including the bilge, shall be ventilated to eliminate any flammable and combustible vapors before any hot work is commenced.
3604.4 Engine test stand fuel supply.
Engine test stands shall be supplied by a fuel storage system complying with the requirements of FC Chapter 57. The fuel tank supplying the engine test stand shall be installed outdoors, and the fuel tank and piping located a safe distance from engine exhaust. The fuel piping shall be of steel construction and provided with an automatic shutoff valve designed to shut off the fuel supply in the event of a fire.
3604.5 Flammable and combustible liquids and flammable gases.
The storage, handling and use of flammable and combustible liquids and flammable gases shall be in accordance with FC Chapters 57, 58 and 61 and this section.
3604.5.1 Marine liquid fuel dispensing.
Marine liquid motor fuel-dispensing facilities shall be designed, installed, operated and maintained in accordance with FC Chapter 23.
3604.5.2 Use for cleaning.
Use of flammable and combustible liquids for cleaning purposes shall be in accordance with FC 5705.3.6.1.
3604.5.3 Storage arrangements.
Except when displayed for sale in sealed containers, flammable and combustible liquids shall be stored in liquid storage cabinets, liquid storage rooms or in approved underground storage systems. Such installations shall comply with the requirements of FC Chapters 23 and 57.
3604.5.4 Quantity limitations when stored for sale.
Flammable and combustible liquids displayed for sale in sealed containers shall comply with the requirements of FC Chapters 23 and 57, as applicable, except in no case shall the quantities displayed exceed 200 gallons (757 L).
3604.5.5 Flammable gases.
LPG on vessels used for residential purposes shall be stored, handled and used in compliance with the requirements of FC Chapter 61 and the rules. CNG on vessels used for residential purposes shall be stored, handled and used in compliance with the requirements of FC Chapter 58 and the rules.
Section FC 3605. Fire Protection, Equipment and Access
3605.1 General.
Marinas requiring fire protection and fire department access shall comply with this section. Marine liquid motor fuel-dispensing facilities shall additionally comply with FC 2310.
3605.2 Fire protection systems and equipment.
Marinas shall be equipped with fire protection systems and equipment in accordance with this section.
3605.2.1 Standpipes.
If the furthest point of any pier or float exceeds 250 feet (76200 mm) from a fire apparatus-accessible location, the pier or float shall be equipped throughout with a standpipe system in accordance with NFPA 303. Systems shall be provided with hose connections located such that no point on the marina pier or float system exceeds 150 feet (45 720 mm) from a standpipe hose connection. Such system shall have a design capacity of 250 gallons per minute (946 L/min) and shall be provided with one or more fire department connections at an approved location, and when required by the commissioner, to an approved water supply. Standpipe hose connection locations shall be clearly identified by a flag or other approved means designed to be readily visible from the pier accessing the float system.
3605.2.2 Yard hydrant system.
Fire apparatus-accessible locations as required by FC 3605.3.1 shall be within 250 feet (76 200 mm) of a fire hydrant or other approved water supply, and shall be situated such that a hose stream from 250 feet (76 200 mm) of hose line stretched from such location will reach all portions of the premises.
3605.2.3 Portable fire extinguishers.
One non-freezing type portable fire extinguisher of the ordinary (moderate) hazard type shall be provided at each required standpipe hose connection. Where there is no standpipe connection, one non-freezing type portable fire extinguisher with at least a 2-A rating shall be provided for every 2,500 square feet (232 m 2 ), or part thereof. Additional portable fire extinguishers, suitable for the hazards involved, shall be provided and maintained in accordance with FC 906.
3605.3 Fire department access.
Fire apparatus access shall be provided as set forth in Chapters 4 and 7 of NFPA 303, and FC 3605.3.1 through 3605.3.5.
3605.3.1 Access road.
A road capable of supporting a department firefighting apparatus, with a width of not less than 20 feet (6096 mm) or a width as required by FC 503, where applicable, shall be provided from a public street to one or more fire apparatus-accessible locations on the premises.
3605.3.2 Aisles.
Any outdoor area of the marina shall be accessible by fire apparatus on all four sides, with a distance between the fire apparatus-accessible aisles of not more than 75 feet (22 860 mm). Such access aisles shall be kept unobstructed.
3605.3.3 Parking.
Motor vehicles shall not be parked on fire apparatus access roads or aisles, unless approved.
3605.3.4 Slip identification.
Slips and other mooring spaces shall be individually identified by a number and/or letter, which shall be conspicuously marked or posted. The direction to each slip and mooring space shall be conspicuously marked or posted at the base of each pier, finger pier, float and finger float.
3605.3.5 Fire department staging areas.
Staging areas for fire department access and firefighting operations shall be provided on all floats. An area at least 4 feet wide by 10 feet long (1219 mm by 3048 mm), exclusive of walkways, with a curb or barrier having a minimum height of 4 inches (102 mm) shall be provided and maintained unobstructed at each standpipe hose connection for this purpose. Each staging area shall be identified by a durable sign reading "FIRE DEPARTMENT STAGING AREA – KEEP CLEAR."
3605.4 Emergency communications and preparedness.
Emergency communications and emergency preparedness shall be in accordance with FC 3605.4.1 and 3605.4.2.
3605.4.1 Communications.
The marina shall be provided with a public address system or other approved means of notifying occupants of a fire on the premises. A telephone not requiring a coin to operate or another approved, clearly identified means to notify the department, shall be provided on the premises in an approved location.
3605.4.2 Emergency preparedness.
Marina owners shall designate and train a fire brigade in fire emergency procedures, including the sounding of an alarm, notification to the department, and operation of fire protection systems and portable fire extinguishers. A chart designating the members of the fire brigade and indicating each person's responsibilities shall be posted on the premises in a conspicuous approved location.
Section FC 3701. General
3701.1 Scope.
This chapter shall govern the storage and handling of combustible fibers.
3701.2 General.
Combustible fibers shall be stored and handled in accordance with this chapter.
3701.3 Permits.
Permits shall be required as set forth in FC 105.6.
3701.4 Approved facility or location.
Combustible fibers in quantities requiring a permit shall be stored in an approved facility or other approved location.
3701.5 Prohibition.
It shall be unlawful to store combustible fibers in a quantity that covers more than two-thirds of the floor area of any floor or in a quantity that is to a height greater than two-thirds of the distance from the floor to the ceiling.
Section FC 3702. Definitions
3702.1 Definitions.
The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.
BALED COTTON.
BALED COTTON, DENSELY PACKED.
COMBUSTIBLE FIBERS.
SEED COTTON.
Section FC 3703. General Requirements
3703.1 Combustible waste.
Ashes, rubbish or other combustible waste shall not be placed in wooden or other combustible containers and shall be removed daily from the facility.
3703.2 Vegetation.
Grass, vines, weeds, brush or other combustible vegetation shall not be allowed to accumulate within 15 feet (4570 mm) of any combustible fiber storage location.
3703.3 Clearances.
A minimum clearance of 3 feet (914 mm) shall be maintained between sprinkler heads and the top of piles.
3703.4 Agricultural products.
Hay, straw, seed cotton or similar agricultural products shall not be stored in an area adjoining any combustible fiber storage location unless a clear horizontal distance equal to the height of a pile is maintained between such agricultural products and such storage location. Storage shall be limited to stacks of 100 tons (91 metric tons) each. Stacks shall be separated by a minimum of 20 feet (6096 mm) of clear space.
3703.5 Dust collection.
Where located within a building, devices, equipment and systems that generate or emit combustible fibers shall be provided with an approved dust-collecting and exhaust system. Such system shall comply with the requirements of FC Chapter 22 and the construction codes, including the Mechanical Code.
3703.6 Portable fire extinguishers.
Portable fire extinguishers shall be provided in accordance with FC 906 governing extra-hazard occupancy protection, as set forth in FC Table 906.3.1.
Section FC 3704. Loose Fiber Storage
3704.1 Reserved.
3704.2 Storage of 100 cubic feet or less.
Loose combustible fibers in quantities of not more than 100 cubic feet (3 m 3 ) located in a building or structure shall be stored in a metal or metal-lined bin equipped with a self-closing cover.
3704.3 Storage of more than 100 cubic feet to 500 cubic feet.
Loose combustible fibers in quantities exceeding 100 cubic feet (3 m 3 ) but not exceeding 500 cubic feet (14 m 3 ) shall be stored in rooms enclosed with 1-hour fire-resistance-rated fire barriers, with openings protected by an approved opening protective assembly having a fire protection rating of 3/4-hour, constructed in accordance with the construction codes, including the Building Code.
3704.4 Storage of more than 500 cubic feet to 1,000 cubic feet.
Loose combustible fibers in quantities exceeding 500 cubic feet (14 m 3 ) but not exceeding 1,000 cubic feet (28 m 3 ) shall be stored in rooms enclosed with 2-hour fire-resistance-rated fire barriers, with openings protected by an approved opening protective assembly having a fire protection rating of 1 1/2-hours, and constructed in accordance with the construction codes, including the Building Code.
3704.5 Storage of more than 1,000 cubic feet to 2,500 cubic feet.
Loose combustible fibers in quantities exceeding 1,000 cubic feet (28 m 3 ) but not exceeding 2,500 cubic feet (70 m 3 ) shall be stored in rooms enclosed with 2-hour fire-resistance-rated fire barriers, with openings protected by an approved opening protective assembly having a fire protection rating of 1 1/2-hours, and constructed in accordance with the construction codes, including the Building Code. The storage room shall be protected throughout by a sprinkler system.
3704.6 Storage of more than 2,500 cubic feet; detached storage structure.
Loose combustible fibers in quantities exceeding 2,500 cubic feet (70 m 3 ) but not exceeding 10,000 cubic feet (280 m 3 ) shall be stored in a detached structure suitably located, with openings protected against entrance of sparks. The structure shall not be occupied for any other purpose. Loose combustible fibers in quantities exceeding 10,000 cubic feet (280 m 3 ) may be stored only with the approval of the commissioner.
3704.7 Separation from hazardous materials.
No hazardous material shall be stored in any room or detached structure containing loose combustible fibers.
Section FC 3705. Baled Storage
3705.1 Bale size and separation.
Baled combustible fibers shall be limited to single blocks or piles not more than 25,000 cubic feet (700 m 3 ) in volume, not including aisles or clearances. Blocks or piles of baled fiber shall be separated from adjacent storage by aisles not less than 5 feet (1524 mm) wide, or by flash-fire barriers constructed of continuous sheets of noncombustible material extending from the floor to a minimum height of 1 foot (305 mm) above the highest point of the piles and projecting not less than 1 foot (305 mm) beyond the sides of the piles.
3705.2 Special baling conditions.
Sisal and other fibers in bales bound with combustible tie ropes, jute and other fibers that swell when wet, shall be stored to allow for expansion in any direction without affecting building walls, ceilings or columns. A minimum clearance of 3 feet (914 mm) shall be required between walls and sides of piles, except that where the storage compartment is not more than 30 feet (9144 mm) wide, the minimum clearance at side walls shall be 1 foot (305 mm), provided that a center aisle not less than 5 feet (1524 mm) wide is maintained.
Section FC 3706. Storage of Combustible Fibers on Waterfront Structures
3706.1 Scope.
This section shall govern the storage and handling of combustible fibers on waterfront structures, including piers, wharfs and bulkheads except when combustible fibers are stored and handled exclusively in sealed metal shipping containers.
3706.2 General.
Combustible fiber shall be stored and handled on waterfront structures in accordance with this section.
3706.3 Prohibitions.
It shall be unlawful to:
1. Unload and store loose combustible fibers on a waterfront structure.
2. Conduct hot work operations on a waterfront structure where combustible fibers are in storage or being handled.
3706.4 Supervision of standpipe and sprinkler systems.
A person holding a certificate of fitness for a standpipe system and a certificate of fitness for sprinkler system maintenance shall inspect the standpipe and sprinkler systems not more than 24 hours prior to the delivery of the combustible fibers. Combustible fibers shall not be unloaded if the standpipe or sprinkler system is out of service. While combustible fibers are present on the waterfront structure, the certificate of fitness holder shall inspect the standpipe and sprinkler systems, and portable fire extinguishers at least once each day. A record of all inspections shall be maintained on the premises and made available for inspection by any representative of the department.
3706.5 Notification.
Before combustible fibers are unloaded to a waterfront structure from any marine vessel, watercraft or motor vehicle, advance notice of at least 48 hours shall be given to the department by the owner of the waterfront structure.
3706.6 Fire protection.
Waterfront structures where combustible fibers are stored or handled shall be provided with fire protection in accordance with FC 3706.6.1 through 3706.6.4.
3706.6.1 Superstructure.
The superstructure of the waterfront structure shall be protected throughout by a sprinkler system.
3706.6.2 Substructure.
The substructure of the waterfront structure shall be protected by one of the following methods:
1. Fire stops at intervals of 150 feet (45 720 mm); and
1.1. A sprinkler system arranged for discharge of water to the entire substructure area; or
1.2. Protected openings through decking for revolving nozzles or other water discharge equipment, so arranged as to permit water discharge onto the entire substructure area. Such openings shall be a minimum of 6 1/2 inches (165 mm) in diameter and spaced at 25 feet (7620 mm) intervals longitudinally and transversely. No cargo shall be stored on deck openings adjacent to the substructure fire stops and those in the main and fire hose aisles.
2. A system of water spray nozzles arranged to permit water discharge onto the entire substructure area and installed in accordance with the Building Code.
3. A system of trenches across the waterfront structure every 100 feet (30 480 mm). Such trenches shall not exceed 12 inches (305 mm) in width, shall be of substantial construction that conforms to the rest of the waterfront structure, shall extend to within 5 feet (1524 mm) of the sides of the waterfront structure, and shall have openings protected in sections not to exceed 25 feet (7620 mm) for access or removal in the event of fire. No cargo shall be placed directly above these openings, and durable signs shall be conspicuously posted on the waterfront structure to indicate the location of these openings.
4. A system of deck openings and under-deck sprinkler protection approved by the commissioner. Openings shall be spaced at 25 feet (7620 mm) intervals longitudinally and transversely. No cargo shall be placed directly above these openings, and durable signs shall be conspicuously posted on the waterfront structure to indicate the location of these openings.
3706.6.3 LPG or gasoline-fueled equipment.
Any LPG or gasoline-fueled devices, equipment or systems used to handle combustible fibers, or operated in the immediate area of combustible fiber storage or handling, shall be equipped with exhaust spark arresters and carburetor traps.
3706.6.4 Portable fire extinguishers.
The combustible fiber storage area shall be provided with portable fire extinguishers in accordance with FC 906 governing extra-high hazards (Class A fires).
3706.7 Storage and handling.
Bales of combustible fibers facing aisles shall be covered on top and sides with tarpaulins or other suitable covering. Whenever possible, the combustible fibers shall be stacked on one side of the waterfront structure only, preferably at the water end of waterfront structure. Combustible fibers shall be tiered no higher than 12 feet (3658 mm) and a clearance of not less than 18 inches (457 mm) between the sprinkler head and the upper level of the top tier shall be maintained. An aisle space of not less than 5 feet (1524 mm) extending to the side of the waterfront structure shall be provided at right angles to the main aisle at intervals not exceeding 75 feet (22 860 mm) in the combustible fiber storage area.
3706.8 Operation and maintenance.
Waterfront structures upon which combustible fibers are stored or handled shall be operated and maintained in compliance with the requirements of FC 3706.8.1 through 3706.8.3.
3706.8.1 Fire guard.
A fire guard shall be required and positioned approximately every 200 feet (60 960 mm) throughout the length of the combustible fiber storage area. Persons conducting a fire watch shall have the duties and responsibilities set forth in FC 901.7.2.1 with respect to the areas being monitored in connection with combustible fiber storage, and shall be familiar with the location of fire alarm manual pull stations, and standpipe system hose and hose connections in the area.
3706.8.2 Access.
Access to combustible fibers and the aisles between the stored combustible fibers shall be restricted to personnel handling the combustible fibers, fire guards and representatives of the department.
3706.8.3 Loading and unloading.
When loading and unloading combustible fibers, two persons shall be assigned to each loading or unloading operation to stand by with the standpipe hose. These persons shall be instructed as to the location and use of the standpipe system valves and hoses.
Section FC 4001. General
4001.1 Scope.
This chapter governs the design, installation, operation and maintenance of distilleries, including the manufacturing, storage, handling and use of distilled spirits in such facilities. Storage of distilled spirits in a warehouse or a liquid storage warehouse that is not a distillery is governed by FC 5704.3. Any occupancy with ancillary distillery operations is a distillery regulated by this section.
Exceptions:
1. Storage of distilled spirits in a warehouse, liquid storage warehouse or other storage facility that is not a distillery is governed by FC 5704.3.
2. Bottling and related processing of distilled spirits, including blending, filtering, and other handling of distilled spirits, but excluding distilling, in a warehouse, liquid storage warehouse or other storage facility that is not a distillery, shall be conducted in accordance with FC 5705 or as otherwise provided in the rules.
4001.2 Permits.
Permits shall be required as set forth in FC 105.6.
4001.3 General.
The design, installation, operation and maintenance of distilleries, including the manufacturing, storage, handling and use of distilled spirits, shall be in accordance with this chapter. Nothing contained in this chapter shall authorize operations or facilities in contravention of Federal, State and City laws, rules and regulations governing distilled spirits, including the regulations of the Tax and Trade Bureau of the United States Treasury Department and the New York State Liquor Authority.
4001.3.1 Special approval for distilleries with widely-separated operations.
The department, in its discretion, may approve alternative design, installation, operational and maintenance standards, including alcohol storage in excess of 20,000 gallons (75 700 L), on a case-by-case basis, for any distillery housed in a detached building exclusively occupied for such purpose, which, by reason of its size (floor area and ceiling height) is able to mitigate the hazards associated with the distilling process by maintaining substantial separation between its stills and other distillery equipment and between its distilled spirits processing area and other distillery operations. The department may apply distilled spirits industry design standards for such distilleries, in whole or in part, in light of the distillery's design, construction and location.
4001.3.2 Special approval for distilleries based on performance standards.
The department, in its discretion, may approve alternative design, installation, operation and maintenance requirements, including distilled spirits industry design standards, where the applicant demonstrates that the design of the still, alcohol storage and handling equipment, grain handling equipment and/or other equipment mitigate the hazards associated with distillery operations.
4001.3.3 Special approval for existing distilleries.
The department, in its discretion, may approve by rule and/or individual modification alternative design and installation requirements for distilleries existing prior to the effective date of this section.
4001.4 Acceptance testing.
Prior to commencement of distillery operations:
1. The still and all piping associated with alcohol processing equipment shall be inspected and tested by, or in the presence of, a certificate of fitness holder at the time of installation to ensure that the equipment is in good working order; and
2. Electrical wiring, equipment and installations shall be installed in accordance with the construction codes, including the Building Code and the Electrical Code.
4001.5 Prohibitions.
It shall be unlawful to:
1. Store more than 20,000 gallons (75 700 L) of alcohol in any distillery, except as may be authorized by the department pursuant to FC 4001.3.1
2. Conduct distilling, alcohol processing or bottling above the second floor of any building, or in any basement, cellar or other below grade location, except as authorized by the department.
3. Establish or operate a distillery in any building housing a Group E, R-2 or I occupancy, or in which Group A occupancy is the dominant occupancy, except as authorized by the department.
4001.6 Supervision.
Distilleries and distillery operations shall be under the supervision of a certificate of fitness holder, as follows:
1. Still operation, and periodic testing of stills, shall be personally conducted by a certificate of fitness holder.
2. Distillery equipment other than stills shall be operated under the personal supervision of a certificate of fitness holder.
3. All other distillery operations, including the storage of raw alcohol and distilled spirits, shall be under the general supervision of a certificate of fitness holder.
4. The installation, alteration, repair or servicing of stills and other distillery equipment shall be conducted under the personal supervision of a still installation certificate of fitness holder or other person with approved qualifications.
4001.7 Other alcohol products.
Manufacturing, storage, handling and use in a distillery of alcohol products that are not raw alcohol or distilled spirits shall comply with the requirements of FC 4007.
4001.8 Very low flammability.
Any distillery that exclusively manufactures, stores, handles and uses beverage alcohol that is a Class I liquid with an alcohol content by volume of 20 percent or less (including raw alcohol, process alcohol and finished products) may apply to the Department to be exempted from design and installation requirements of this chapter.
4001.9 Combustible dust.
Any distillery that generates combustible dust shall comply with the requirements for combustible dust-producing operations set forth in FC Chapter 22 and this chapter.
4001.10 Emergency response plan.
Each distillery shall prepare and maintain an emergency response plan to address fires; spills, vapor releases and other accidental discharges; and distillery equipment alarms. Distilleries may utilize emergency plans developed in compliance with OSHA or New York State Department of Labor regulations, provided that they address all matters required by this chapter. The certificate of fitness holder shall train all distillery staff to implement such emergency response plan, including appropriate mitigating and reporting actions necessitated by fire, leak or spill.
Section FC 4002. Definitions
4002.1 Definitions.
The following terms shall, for the purposes of this chapter and used elsewhere in this code, have the meanings set forth in FC 202.
ALCOHOL STORAGE AREA.
BEVERAGE ALCOHOL.
Distilled Spirits.
Finished Goods.
Process Alcohol.
Raw Alcohol.
CHEMICAL STORAGE BUILDING.
DISTILLED SPIRITS PROCESSING AREA.
DISTILLERY.
Small Distillery.
Medium Distillery.
Large Distillery.
DISTILLERY EQUIPMENT.
Alcohol Process Tank.
Closed Alcohol Process Tank.
Open Alcohol Process Tank.
Alcohol Storage Equipment.
Barrel.
Intermediate Bulk Container.
Alcohol Storage Tank.
Still.
DISTILLERY OPERATIONS.
Alcohol Processing.
Bottling.
Distilling.
DISTILLERY SERVING AREA.
DISTILLERY WASTE PRODUCTS.
Section FC 4003. Design and Installation Requirements for Distillery Facilities
4003.1 General.
The building housing a distillery shall be designed and installed in accordance with this section. Design and installation documents shall be submitted for department review and approval.
4003.2 Occupancy type.
Distilleries shall be housed in buildings and occupancies with the following occupancy classifications:
1. A small distillery shall be located in a building or space designed as an F-1 factory occupancy as set forth in FC 4003.4.1. Such factory occupancy may be located in a mixed-occupancy building, except as otherwise provided in FC 4001.5(3).
2. A medium distillery shall be located in a high-hazard occupancy, as set forth in FC 4003.4.1, in a building in which Group F occupancy is the dominant occupancy
3. A large distillery shall be located in a separate building or in a detached building, which is classified as a high-hazard occupancy.
4003.3 Maximum still capacity and maximum allowable quantity.
Maximum still capacities shall be based upon distillery size, as set forth in FC Table 4003.3. The maximum allowable quantity of alcohol, of any type, shall not exceed the amounts set forth in FC Table 4003.3 and FC 4003.3.1 through 4003.3.3, except as authorized by the department.
FC Table 4003.3 Maximum Still Capacities and Maximum Allowable Quantities
Distillery Size Maximum Individual Still Capacity Aggregate Maximum Still Capacity Maximum Allowable Quantity per Control Area a Aggregate Maximum Allowable Quantity b Additional Storage Allowance per Control Area for Beverage Alcohol and Precursors £ 20% ABV c Maximum Aggregate Allowable Quantity of Beverage Alcohol and Precurso rs £ 20% ABV d Small distillery 125 gallons (473 L) 250 gallons (946 L) 750 gallons (2839 L) 1,500 gallons (5678 L) 750 gallons (2839 L) 1,500 gallons (5678 L) Medium distillery 750 gallons (2839 L) 1,500 gallons (5678 L) 2,000 gallons (7570 L) 6,000 gallons (22 710 L) 4,000 gallons (15 140 L) 8,000 gallons (30 280 L) Large distillery 2,000 gallons (7570 L) 8,000 gallons (30 280 L) 4,000 gallons (15 140 L) 20,000 gallons (75 700 L) 8,000 gallons (30 280 L) 16,000 gallons (60 560 L)
a. The maximum allowable quantity per control area comprises all raw alcohol and distilled spirits stored on the premises, excluding the amounts of finished goods allowed by FC 4005.2.5.
b. The aggregate maximum allowable quantity comprises all raw alcohol and distilled spirits stored on the premises, excluding the amounts of finished goods allowed by FC 4005.2.5. These amounts are reduced in a combined fire area pursuant to FC 4003.4.2 to 1,000 gallons (small distillery); 2,000 gallons (medium distillery); and 4,000 gallons (large distillery).
c. Additional allowance per control area applies to beverage alcohol and flammable beverage alcohol precursors, up to a maximum of 20% alcohol content by volume (ABV), clearly labelled as such in accordance with Federal or other applicable regulations.
d. Maximum aggregate allowable quantity stored on the premises of beverage alcohol and flammable beverage alcohol precursors, up to a maximum 20% alcohol content by volume (ABV), clearly labelled as such in accordance with Federal or other applicable regulations. These amounts are reduced in a combined fire area pursuant to FC 4003.4.2 to 1,000 gallons (small distillery); 4,000 gallons (medium distillery); and 8,000 gallons (large distillery).
4003.3.1 Small distillery.
The maximum allowable quantity in a small distillery shall be 750 gallons (2839 L) per control area. An additional 750 gallons (2839 L) of beverage alcohol and flammable beverage alcohol precursors, with an alcohol content by volume of 20 percent or less, may be stored, handled or used per control area.
4003.3.2 Medium distillery.
The maximum allowable quantity in a medium distillery shall be 2,000 gallons (7570 L) per control area. An additional 4,000 gallons (15 140 L) of beverage alcohol and flammable beverage alcohol precursors, with an alcohol content by volume of 20 percent or less, may be stored, handled or used per control area.
4003.3.3 Large distillery.
The maximum allowable quantity in a large distillery shall be 4,000 gallons (15 140 L) per control area. An additional 8,000 gallons (30 280 L) of beverage alcohol and flammable beverage alcohol precursors, with an alcohol content by volume of 20 percent or less, may be stored, handled or used per control area.
4003.4 Fire separations.
Except as otherwise provided in FC 4003.4.1 and 4003.4.2, a minimum of 1-hour fire barriers or horizontal assemblies, or both, constructed in accordance with the Building Code, including self-closing doors, shall be installed to separate the following distillery operations from each other:
1. Distilled spirits processing areas.
2. Alcohol storage areas, except barrel storage.
3. Barrel storage areas.
4. Distillery serving area.
5. General business operations area and/or finished goods storage in excess of 250 gallons (946 L).
6. Other alcohol production areas.
4003.4.1 Factory and high-hazard areas.
The distilled spirits processing areas, alcohol storage areas and barrel storage areas shall be constructed, in small distilleries, with the fire barriers and horizontal assemblies required for a factory occupancy, and, in medium distilleries, with the fire barriers and horizontal assemblies required for a high-hazard occupancy.
4003.4.2 Combined fire areas.
The distilled spirits processing areas, alcohol storage areas, barrel storage areas and other alcohol production areas may be located in a single fire area subject to the following requirements:
1. The total quantity of alcohol stored, handled or used in the fire area is limited as follows: 1,000 gallons (3785 L) in a small distillery; 2,000 gallons (7570 L) in a medium distillery; 4,000 gallons (15 140 L) in a large distillery, and a maximum allowable quantity of twice that amount for beverage alcohol and flammable beverage alcohol precursors, with an alcohol content by volume of 20 percent or less, for medium and large distilleries, and, in a small distillery, a maximum quantity of 1,000 gallons (3785 L).
2. Barrel storage shall be in accordance with FC 4005.3. The barrel storage area shall be separated by a wall, bollards or other approved separation designed to minimize the risk from rolling barrels.
3. The entire fire area shall be provided with emergency alarm detection and exhaust ventilation systems in accordance with FC 4003.5.3 and 4003.7.
4. The entire fire area shall be provided with electrical wiring and equipment in accordance with FC 4003.8.
5. Grain mashing and fermenting may be conducted in such combined fire area. All grain conveyance shall be in enclosed containers or systems. A combustible dust collection system shall be provided for any unenclosed grain handling. No grain milling shall be conducted in such combined fire area.
6. Additional quantities of alcohol shall be stored in a listed and approved chemical storage building within the space, at an approved location, or in a separate fire area.
4003.5 Fire protection systems.
Fire protection systems shall be provided in accordance with FC 4003.5.1 through 4003.5.3.
4003.5.1 Sprinkler system.
Distilleries shall be protected throughout by a sprinkler system designed in accordance with the Building Code. The sprinkler system in a small distillery shall be designed to be of an extra hazard type. The sprinkler system in a medium or large distillery shall be designed for a high-hazard occupancy. Sprinkler systems for high-piled barrel storage shall comply with the sprinkler requirements for such storage systems in accordance with FC 3206.4. Sprinkler systems for distilleries producing combustible dust shall comply with the sprinkler requirements of NFPA 652.
4003.5.2 Fire alarm system.
Distilleries shall be provided with a manual and automatic fire alarm system. If the fire alarm system is part of a building system that provides protection to other occupancies, a separate sprinkler water flow device shall be provided for the distillery occupancy, except in a small distillery equipped with a smoke detection system. Such fire alarm system shall activate alarm notification devices throughout the distillery and be monitored by a central station.
4003.5.3 Emergency alarm system.
Distilleries shall be provided with a gas detection system designed to detect flammable vapors in accordance with FC 908 in the distilled spirits processing area and alcohol storage areas, and in any area of the distillery in which flammable vapors in more than de minimis quantities may be released or accumulate. Such emergency alarm system shall activate alarm notification devices throughout the distillery.
4003.6 Explosion control.
Medium and large distilleries shall be provided with explosion control designed in accordance with FC 911 to mitigate the impact of an explosion.
4003.7 Exhaust ventilation.
Exhaust ventilation shall be provided in accordance with Section 502.8 of the Mechanical Code in the distilled spirits processing area and alcohol storage areas, and in any area of the distillery in which flammable vapors in more than de minimis quantities may be released or accumulate.
4003.8 Electrical wiring and equipment.
Electrical wiring and equipment shall be installed in accordance with the Electrical Code. Class 1, Division 1 electrical wiring and equipment shall be provided in the distilled spirits processing areas and alcohol storage areas, except that where a closed system as defined in FC 202 is being utilized in a distilled spirits processing area or alcohol storage area, electrical wiring and equipment shall be provided as follows:
1. Class1, Division1 and Class I, Division 2 electrical wiring and equipment in accordance with FC Table 5703.1.1 (for indoor equipment where flammable vapor/air mixtures could exist under normal operations); and
2. Class 1, Division 1 electrical wiring and equipment in pits and behind containment barriers where flammable vapor cannot dissipate horizontally; and
3. Class 2, Division 1 electrical wiring and equipment in any other area where combustible dust may be present.
4003.8.1 Lighting.
Distilled spirits processing areas, excluding barrel storage areas, shall be well lighted to facilitate safe operation of distillery equipment and visibility of signage.
4003.9 Mechanical equipment.
All stationary and portable electrically-powered and/or heat-producing devices, equipment and systems, including space heating and cooling systems; mechanical refrigerating systems; and conveyers, installed or used in a distilled spirits processing area or alcohol storage area shall be suitable for a classified location in accordance with the Electrical Code, the Mechanical Code and NFPA 30, as applicable, except where all alcohol handling is in a closed system or where an explosion mitigation analysis indicates that the equipment is outside of the classified area. No mechanical equipment with burners, or using other flames or exposed electrical elements, shall be installed or used in distilled spirits processing areas and alcohol storage areas. Air-driven power tools shall be used whenever practicable instead of electrical tools; when electrical tools must be used, no distilling, alcohol processing or bottling operations shall be conducted and the control area shall be clear of any flammable vapors.
4003.10 Environmental control.
Stills shall be operated within the ambient temperature range recommended by the still manufacturer and in accordance with distilled spirits industry standards.
4003.11 Emergency power.
Gas detection systems and any exhaust ventilation system designed to maintain flammable vapor concentration below the lower explosive limit shall be provided with an emergency power system in accordance with the Building Code.
4003.12 Spill control.
Drainage or containment systems to restrict and control spills, including noncombustible and liquid-tight floors, shall be provided in distilled spirits processing areas and alcohol storage areas in accordance with FC 5004.2. A hose suitable for a classified environment connected to a water supply shall be provided to facilitate dilution of any spills.
4003.13 Storage areas.
Storage areas shall be designed and installed in accordance with FC 4005.
4003.14 Impact protection.
Distillery equipment used to manufacture, store, handle or use beverage alcohol, including storage tanks, shall be protected from accidental impact from powered industrial trucks and other mechanical handling equipment in accordance with NFPA 505 and distilled spirits industry standards.
4003.15 Lightning protection.
Medium and large distilleries that occupy a separate building shall be provided with lightning protection in accordance with the Electrical Code and NFPA 780.
Section FC 4004. Design and Installation Requirements for Distillery Equipment
4004.1 General.
Distillery equipment shall be designed and installed in accordance with this section and distilled spirits industry standards.
4004.2 Listed or labeled.
Distillery equipment used to manufacture, store, handle or use beverage alcohol shall be listed or labeled for the intended use, if listing and labeling exists for such equipment. The department may accept international or other approved certifications for components which are not listed and labeled by a nationally recognized testing laboratory.
4004.3 Electrical wiring and equipment.
Distillery equipment used to manufacture, store, handle or use beverage alcohol shall be bonded and grounded to protect against electrical discharge in accordance with the Electrical Code.
4004.4 Piping systems.
Piping systems for conveying Class I liquids, including piping, tubing, valves, pumps, and fittings shall be designed, installed and maintained in accordance with FC 5703.6 and ASME B31.3, except that acceptance testing shall be conducted in accordance with FC 4001.4.
4004.5 Stills.
Stills shall be designed and installed in accordance with FC 4004.5.1 through 4004.5.4.
4004.5.1 Certificate of approval.
Stills shall be of a type for which a certificate of approval has been issued in accordance with FC 112 and the rules. On an interim basis, the department may grant a site-specific approval of a still for which a manufacturer has not obtained a certificate of approval upon a satisfactory showing by the permit applicant as to the still manufacturer's design and installation specifications and operational and maintenance requirements.
4004.5.2 Installation.
Stills shall be stationary, by securing them in an approved manner.
4004.5.3 Heat source.
Heating shall be by indirect means, using steam, hot water or other approved method. Mechanical equipment with burners, or using other flames or exposed electrical elements, shall not be installed. An emergency shutoff switch for the heat source shall be provided at the entrance to the processing area.
4004.5.4 Ingredients.
All liquid and solid ingredients shall be suitable for use in the still for which a certificate of approval is sought.
4004.6 Tanks and containers.
Alcohol handled and used during distilling and alcohol processing shall be stored in alcohol process tanks in accordance with FC 4005.
4004.7 Barrels.
Barrels and barrel storage shall be designed in accordance with FC 4005.3 and distilled spirits industry standards.
4004.8 Powered industrial trucks and other mechanical handling equipment.
Powered industrial trucks shall be stored and used in accordance NFPA 505 and distilled spirits industry standards. Other mechanical handling equipment shall be stored and used in accordance with distilled spirits industry standards.
Section FC 4005. Storage of Alcohol in Distilleries
4005.1 Alcohol storage tanks and containers.
In a distillery, raw alcohol and distilled spirits shall be stored in tanks and containers designed and installed in accordance with FC Chapter 32 and NFPA 30, as applicable, except as otherwise provided in FC 4005.1.1 through 4005.1.5.
4005.1.1 Aboveground storage.
Notwithstanding the provisions of FC 5701.7(3) and 5704.1.1, in a distillery raw alcohol, distilled spirits and other alcohol that is a Class II or III liquid, shall be stored in an aboveground storage tank or aboveground intermediate bulk container.
4005.1.2 Tank and container construction.
All tanks and containers in which alcohol is stored and handled, except barrel storage, shall be constructed of stainless steel and designed in accordance with FC 5704, 5705.2 and 5705.3. Raw alcohol delivered to a distillery in a plastic intermediate bulk container shall be expeditiously (but not later than the end of the workday) transferred into a stainless steel storage tank or stainless steel intermediate bulk container in accordance with FC 4005.
4005.1.3 Tank and container installation.
All tanks and containers in the distilled spirits processing area and all tanks and containers which transfer their contents by piping or which are otherwise part of a stationary installation, shall be securely affixed to the floor, to prevent movement.
4005.1.4 Portable tanks and containers.
Portable tanks and containers not required to be affixed to the ground shall be placed in a location and manner in which they will remain stable. Portable tanks and portable containers shall not be stacked unless such tanks and containers are designed and listed for that purpose, and, if so, shall not be stacked more than two tiers or 12 feet (3658 mm) above the floor. Powered industrial trucks or other suitable devices, equipment or systems shall be used to lift and lower the portable tanks and portable containers.
4005.1.5 Open tanks and containers.
Any open alcohol process tank or alcohol storage equipment shall have a vapor-tight lid or other similar form of closure. Such lid or closure shall be kept closed at all times when the tank or container contains alcohol or alcohol residues, except as necessary during handling and processing operations.
4005.1.6 Separation and aisles.
Separation and aisles between storage tanks and containers shall be in accordance with FC 5704.3.7.2.2.
4005.2 Distillery storage locations.
In a distillery, raw alcohol and distilled spirits shall be stored in the locations specified in FC 4005.2.1 through 4005.2.6, except as otherwise provided in FC 4003.4.2.
4005.2.1 Storage of raw alcohol.
Raw alcohol shall be stored in an alcohol storage area. Raw alcohol shall not be stored in distilled spirits processing areas, but shall be transferred from the alcohol storage area to the still.
4005.2.2 Storage of process alcohol.
Process alcohol shall be stored in the distilled spirits processing area in alcohol process tanks, except for alcohol temporarily stored in portable containers during processing, and barrel storage. Process alcohol undergoing aging in barrels shall be stored in a separate fire area as set forth in FC 4003.4.
4005.2.3 Storage of distilled spirits ready for bottling.
Distilled spirits ready for bottling or other packaging as finished goods shall be stored in distilled spirits process area in alcohol process tanks or alcohol storage area.
4005.2.4 Distillery waste products.
Any methanol, stillage or other residue that is susceptible to spontaneous ignition or otherwise presents an imminent hazard shall be stored in an alcohol storage area or other approved location. Any other distillery waste product, such as materials contaminated with alcohol, shall be stored in a noncombustible container in the business operations area and disposed of in accordance with FC 304.
4005.2.5 Finished goods.
Finished goods may be stored in the general business operations area, distillery serving area, alcohol storage room and barrel storage room. Finished goods shall not be counted toward the maximum allowable quantity of alcohol allowed in that fire area.
4005.3 Barrel storage.
Alcohol shall be stored in barrels in accordance with FC 4005.3.1 through 4005.3.2.
4005.3.1 Barrel storage.
Barrels shall be stored on the floor, in a secure rack of substantial construction in accordance with distilled spirits industry standards, or on pallets (with barrels stored on their flat ends). Barrel storage shall be limited such that the top of the stored barrels shall not exceed a height of 12 feet (3658 mm) above the floor, except as may be otherwise approved by the department based on the location and manner of such high-piled storage and a determination that barrel handling (including the dropping of a barrel or pallet of barrels) does not present an undue hazard to other distillery operations. Barrels stored above floor level shall be on approved shelves or racks designed and/or listed for such purpose. Barrel storage more than 6 feet (1829 mm) above the floor shall be in compliance with Building Code requirements, the high-piled combustible storage requirements of FC Chapter 32, and distilled spirits industry standards.
4005.3.2 Used barrels.
Barrels previously filled with distilled spirits shall be handled and stored as if full unless cleaned and purged of vapors in accordance with distilled spirits industry standards.
Section FC 4006. Operational and Maintenance Requirements for Distilleries
4006.1 General.
Distilleries shall be operated and maintained in accordance with this section and distilled spirits industry standards.
4006.2 Operation of distillery serving area in distilleries.
Tasting rooms or other distillery serving areas may be housed or operated in a distillery provided that such tasting rooms and distillery serving areas are protected by a fire separation in accordance with FC 4003.4. Any commercial kitchen shall be operated in a fire area separated from distilled spirits processing areas and alcohol storage areas in accordance with the Building Code.
4006.3 Business operations area.
To the maximum extent practicable, the distilled spirits processing areas and alcohol processing areas in a distillery shall be used solely for distilling and alcohol processing. All other business operations, storage of other business equipment, deliveries (including deliveries of raw alcohol and other raw materials) and shipments (including shipment of finished goods), shall be conducted in a separate business operations area. Whenever practicable, deliveries of raw alcohol and other raw materials shall not be made through the distillery serving area or other area accessible to the public, or shall be made when those areas are closed to the public.
4006.4 Alcohol handling.
All transfers of alcohol into and between distillery equipment shall be in accordance with FC 5705.2.4, or other approved means.
4006.5 Barrel filling and emptying.
Barrel filling and emptying, including the blending of distilled spirits from barrel storage, shall be conducted in the alcohol processing area or bottling area, except as otherwise provided in FC 4003.4.2.
4006.6 Staffing of facility.
A certificate of fitness holder shall be present on the premises at all times when distilling and alcohol processing is being conducted, shall personally conduct any distilling, and shall tend to the still at all times when in operation in accordance with distilled spirits industry standards. The certificate of fitness holder shall also be present on the premises during the transfer of raw alcohol from a shipping container into distillery equipment. At least one other trained and knowledgeable person shall be present on the premises when the quantity of alcohol undergoing distillation or alcohol processing exceeds 5 gallons (19 L).
4006.7 Spill mitigation and reporting.
Leaks, spills or other uncontrolled discharges of raw alcohol or distilled spirits shall be mitigated and reported in accordance with FC 4006.7.1, 4006.7.2, and 5003.3.
4006.7.1 Spill mitigation.
Spills of raw alcohol or distilled spirits shall be contained and, if practicable, promptly diluted by water. Spills shall be mitigated using a spill kit suitable for flammable alcohol and the flammable or combustible waste disposed of in accordance with applicable laws, rules and regulations. Floor drains shall only be used for collection and/or disposal of spills when approved by the department. The distillery's spill mitigation and reporting procedures shall be set forth in the distillery's emergency response plan.
4006.7.2 Cessation of distillery operations.
In the event of a leak, spill or uncontrolled discharge, distillery operations unrelated to the mitigation of the release shall immediately cease. Distillery operations shall resume only when the hazard has been mitigated and the spilled material has been removed.
4006.8 Combustible materials.
Packaging materials and other combustible materials shall not be stored in the distilled spirits processing area or barrel storage areas except as needed for immediate use. Additional (bulk) storage of such materials shall be located in the business operations area of the distillery. Idle pallets of wood and other combustible materials shall be stored in the business operations area of the distillery in accordance with FC Chapter 32.
4006.9 Distillery waste products.
Any methanol, stillage or other distillery waste product shall be collected and disposed of in accordance with FC 304. Such waste shall be removed from the distilled spirits processing areas and alcohol processing areas immediately upon completion of the distilling or alcohol processing operation from which it was generated, and stored in accordance with FC 4005.2.4.
4006.10 Public access and tours.
Persons not conducting necessary distillery operations shall not be allowed in the distilled spirits processing areas and alcohol storage areas during distilling or alcohol processing operations, except distillery tours may be conducted in designated locations within such areas, as authorized by the department, and supervised by a certificate of fitness holder. Non-distillery staff shall be restricted to the distillery serving area and general business operations area.
4006.11 Maintenance of equipment.
All distillery equipment shall be periodically inspected, tested and otherwise maintained in accordance with the original equipment manufacturer's instructions, distilled spirits industry standards, and all applicable laws, rules and regulations. The original equipment manufacturer's manuals for the installation, operation and maintenance of all distillery equipment shall be maintained on the premises and made available for inspection by any representative of the department.
4006.12 Sources of ignition.
Safety precautions shall be taken to prevent ignition of flammable liquids or vapors from any potential ignition source, including any heat, friction or electrical current generated in connection with cleaning, maintenance and repair work.
4006.12.1 Smoking.
It shall be unlawful to smoke in a distillery. "No Smoking" signs shall be posted in accordance with FC 310.
4006.12.2 Open flames.
Open flames, including barrel charring operations, are prohibited in the distilled spirits processing area and other alcohol production areas, except as authorized by the department.
4006.12.3 Environmental control.
The ambient room temperature and other environmental factors in the distilled spirits processing area and storage areas shall be kept within limits suitable for safe distilling and alcohol processing operations and alcohol storage, as applicable.
4006.13 Signage and markings.
NFPA 704 signage shall be posted at the entrance to the distilled spirits processing areas, and storage and barrel storage areas, in accordance with FC 5003.5. The piping shall be marked in accordance with FC 5703.5.
4006.14 Portable fire extinguishers.
Portable fire extinguishers shall be provided in accordance with FC 906.
4006.15 Safety data sheets.
Safety data sheets shall be maintained on the premises in accordance with FC 5003.4.
Section FC 4007. Other Alcohol Production
4007.1 Scope.
This section governs the materials and processes used to produce alcohol for distilling, including grain storage, handling and milling, mashing and fermenting, and any byproducts generated from those processes.
4007.2 General.
All materials and processes governed by this section shall be designed, installed, operated and maintained in accordance with this section and distilled spirits industry standards.
4007.3 Grain storage, handling and milling.
Distilleries shall be designed, installed operated and maintained to safely store, handle and use any grain or other raw material used in milling, mashing and fermenting operations that generates combustible dust, as defined in FC 2202.1. A hazard analysis shall be conducted based on the quantity and processing of the grain or other combustible dust-producing raw material in accordance with NFPA 652. The distillery shall be designed and/or equipped as required by NFPA 652 based on the type and amount of combustible dust that could be generated, including the following safety measures, as applicable:
1. Except as otherwise provided in FC 4003.2(1), the storage, handling and milling of grain or other combustible dust-producing raw material shall be conducted in a space that is constructed as a high hazard occupancy in accordance with the Building Code; and/or
2. Except as otherwise provided in FC 4003.4.2, the storage, handling and milling of grain or other combustible dust-producing raw material shall be conducted in a space separated by fire separations from the distilled spirits processing areas and alcohol processing areas and alcohol storage areas; and/or
3. A mechanical ventilation system shall be provided to prevent the concentration of combustible dust from reaching explosive levels in accordance with FC Table 2204.1; and/or
4. Specialized dust collection systems and devices shall be provided to reduce the amount of atmospheric combustible dust; and/or
5. Grain or other combustible dust-producing raw material shall be stored in suitable containers; and/or
6. Limitations shall be established on the quantity of grain or other combustible-dust producing raw material that can be stored, handled and milled at the distillery at one time.
4007.4 Design of facility.
The space used for grain storage, handling and milling, mashing and fermenting, and/or related operations shall meet the requirements of FC 4007.4.1 through 4007.4.3.
4007.4.1 Separation from distilled spirits and alcohol processing areas.
Such space shall be separated by fire separations from the distilled spirits processing areas and alcohol processing areas and alcohol storage areas, or shall meet the requirements for such areas as set forth in FC 4003.
4007.4.2 Fire protection systems.
Such space shall be equipped with fire protection systems in accordance with FC 4003.5, notwithstanding the provision of fire separation pursuant to FC 4007.4.1.
4007.4.3 Mechanical equipment.
No mechanical equipment with burners or using other flames or exposed electrical elements, may be installed or used, notwithstanding the provision of fire separation pursuant to FC 4007.4.1.
4007.5 Other alcohol production waste.
Any byproduct or residue generated by grain storage, handling and milling, mashing and fermenting and/or related operations, including combustible liquids, combustible waste and carbon dioxide, shall be handled or mitigated in a manner appropriate for the level of hazard that it presents. Where the carbon dioxide generated by other alcohol production may exceed United States Occupational Safety and Health Administration safety limits, an oxygen sensor or other approved or listed device shall be installed.
Section FC 5001. General
5001.1 Scope.
This chapter shall govern the storage, handling, use and transportation of hazardous materials. Hazardous material storage, handling and use shall additionally comply with the requirements of the New York State Department of Environmental Conservation regulations, as set forth in 6 NYCRR Parts 596 through 613.
Exceptions:
1. The storage, handling and use in retail or wholesale mercantile occupancies of alcoholic beverages, medicines, foodstuffs, cosmetics, and consumer products containing not more than 50 percent by volume of water-miscible liquids and with the remainder of the solutions not being flammable, when packaged in individual containers not exceeding 1.3 gallons (5 L) in volume.
2. Storage, handling and use of hazardous materials for agricultural purposes as a pesticide, fertilizer or similar application, when approved for such use by the regulatory agency having jurisdiction and when such storage, handling and use is in accordance with the manufacturer's instructions.
3. Reserved.
4. Reserved.
5. Refrigerating systems when designed, installed, operated and maintained in accordance with the Mechanical Code and FC 606.
6. Stationary energy storage systems when designed, installed, operated and maintained in accordance with FC 608 and the rules.
7. The storage, handling and use, including storage for sale, of fireworks, in accordance with FC Chapter 56.
8. The storage, handling and use of corrosives in Group M occupancies, including storage for sale, of personal and household products, when in the manufacturer's original consumer packaging.
9. The storage of wines in wooden barrels and casks.
10. The manufacturing, storage, handling and use of distilled spirits in distilleries in accordance with FC Chapter 40.
11. The use of dispensers containing alcohol-based hand rubs classified as Class I or Class II liquids, when stored, handled and used in accordance with FC 5705.5.
5001.1.1 Relationship with other chapters.
This chapter shall apply to all hazardous materials, including those materials regulated elsewhere in this code, except that when specific requirements inconsistent with the provisions of this chapter are set forth elsewhere in this code, those specific requirements shall apply to the extent that they are inconsistent. Where a material is in multiple hazard categories, compliance with each hazard category shall be required. Where a material is both a physical hazard and a health hazard, compliance with the requirements for each hazard category shall be required.
5001.2 Material classification.
Hazardous materials shall be classified by physical hazard, health hazard and/or other hazards associated with the properties of the material, or if the hazardous material is a mixture, with the hazards associated with the mixture as a whole. The commissioner may determine the appropriate hazard classification of a hazardous material, or may accept the classification set forth in nationally recognized standards, safety data sheets, or other approved standard or method.
5001.2.1 Reserved.
5001.2.2 Hazard categories.
Hazardous materials shall be classified according to hazard categories. The categories include materials regulated by this chapter and materials regulated elsewhere in this code.
5001.2.2.1 Physical hazards.
The material categories listed in this section are classified primarily as physical hazards.
1. Explosives and blasting agents.
2. Combustible liquids.
3. Flammable solids, liquid and gases.
4. Organic peroxide solids or liquids.
5. Oxidizing solids or liquids.
6. Oxidizing gases.
7. Pyrophoric solids or liquids.
8. Unstable (reactive) solids, liquids or gases.
9. Water-reactive solids and liquids.
10. Cryogenic fluids.
5001.2.2.2 Health hazards.
The material categories listed in this section are classified primarily as health hazards.
1. Highly toxic and toxic materials.
2. Corrosive materials.
5001.3 Reserved.
5001.4 Retail and wholesale storage and display.
For retail and wholesale storage and display of nonflammable solid and nonflammable or noncombustible liquid hazardous materials in Group M occupancies and storage in Group S occupancies, see FC 5003.11.
5001.5 Permits.
Permits shall be required as set forth in FC 105.6.
5001.5.1 Hazardous Materials Management Plan.
The commissioner may require an application for a permit to include a Hazardous Materials Management Plan (HMMP). Such plan shall be drawn approximately to scale. The HMMP shall contain the following:
1. Access to each area where hazardous materials are stored, handled or used.
2. Location of emergency equipment.
3. Location where liaison required by FC 5003.9.1.1 will meet emergency responders.
4. Facility evacuation meeting point locations.
5. The predominant use and/or occupancy of areas within the building where hazardous materials are not stored or used.
6. Location of all aboveground and underground hazardous material storage tanks and their appurtenances including, but not limited to, sumps, vaults, below-grade treatment systems and piping.
7. The hazard classes of hazardous materials stored or used in each area.
8. Locations of all control areas and Group H occupancies.
9. Locations of exits.
10. Such other information and documentation as the commissioner may prescribe.
5001.5.2 Hazardous materials reporting.
The storage of hazardous materials shall be reported as required by the New York State General Municipal Law Section 209-u. The commissioner may require an application for a permit pursuant to this code to include a copy of the current filing pursuant to such New York State General Municipal Law for the facility or premises for which a permit is sought. The commissioner may also require an application for a permit to include a Hazardous Materials Inventory Statement (HMIS), such as a statement prepared for purposes of the Superfund Amendments and Reauthorization Act of 1986 (SARA) Title III, Tier II Report, or other approved statement. The HMIS shall include the following information:
1. Product name.
2. Chemical composition.
3. Chemical Abstract Service (CAS) number.
4. Location where stored or used.
5. Container size.
6. Hazard classification.
7. Quantity in storage.
8. Quantity in use-closed systems.
9. Quantity in use-open systems.
5001.6 Facility closure.
Facilities shall be placed permanently out of service in accordance with FC 5001.6.2 and 5001.6.3 and, as applicable, with the New York State Department of Environmental Conservation regulations as set forth in 6 NYCRR Sections 598.10 and 613.
5001.6.1 Reserved.
5001.6.2 Permanently out-of-service facilities.
Facilities that are not operated for a period of more than 1 year or for which a permit has lapsed for more than 1 year shall be deemed to be permanently out of service and shall be closed in an approved manner.
5001.6.3 Facility closure plan.
The commissioner may require permittees to apply for approval to permanently close a facility that manufactures, stores, handles or uses hazardous materials. Such application shall be submitted at least 30 calendar days prior to the planned closure of the facility. Such plan and/or such other requirements as the commissioner may prescribe shall demonstrate that hazardous materials that are manufactured, stored, handled or used in the facility will be lawfully disposed of in a manner that eliminates the need for further maintenance and any threat to public health and safety.
Section FC 5002. Definitions
5002.1 Definitions.
The following terms shall, for the purposes of this chapter, FC Chapters 51 through 67, and as used elsewhere in this code, have the meanings set forth in FC 202.
BOILING POINT.
CARGO TANK.
CEILING LIMIT.
CHEMICAL.
CHEMICAL NAME.
CLOSED CONTAINER.
CONTAINER.
CONTROL AREA.
DEFLAGRATION.
DESIGN PRESSURE.
DETACHED BUILDING.
DISPENSING.
EXCESS FLOW CONTROL.
EXHAUSTED ENCLOSURE.
EXPLOSION.
FLAMMABLE VAPORS OR FUMES.
GAS CABINET.
GAS ROOM.
HAZARDOUS MATERIALS.
HEALTH HAZARD.
IMMEDIATELY DANGEROUS TO LIFE AND HEALTH (IDLH).
INCOMPATIBLE MATERIALS.
LABORATORY CHEMICAL.
LABORATORY UNIT.
LIQUID.
LOWER EXPLOSIVE LIMIT (LEL).
LOWER FLAMMABLE LIMIT (LFL).
MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA.
NON-PRODUCTION LABORATORY.
NORMAL TEMPERATURE AND PRESSURE (NTP).
OUTDOOR CONTROL AREA.
PERMISSIBLE EXPOSURE LIMIT (PEL).
PESTICIDE.
PRESSURE VESSEL.
SAFETY CAN.
SAFETY DATA SHEET (SDS).
SECONDARY CONTAINMENT.
SOLID.
STANDARD CUBIC FEET (SCF).
SYSTEM.
TANK, ATMOSPHERIC.
TANK, PORTABLE.
TANK, STATIONARY.
VAPOR PRESSURE.
Section FC 5003. General Requirements
5003.1 General.
Hazardous materials shall be manufactured, stored, handled, used and transported in accordance with this chapter.
5003.1.1 Maximum allowable quantity per control area.
The maximum allowable quantity per control area shall be as specified in FC Tables 5003.1.1(1) through 5003.1.1(4), and for retail and wholesale storage and display in Group M occupancies, and Group S storage, as specified in FC 5003.11.
Exceptions: The maximum allowable quantity per control area requirements set forth in FC Tables 5003.1.1(1) through 5003.1.1(4) shall not apply to:
1. A construction site in an unoccupied building prior to issuance of a certificate of occupancy or temporary certificate of occupancy for such building. Maximum allowable quantity per control area requirements shall apply to a construction site in an occupied or partially occupied building, except as may be otherwise authorized by the department in writing.
2. Liquid or gaseous fuel in fuel tanks on motor vehicles.
3. Gaseous fuels in piping systems and fixed appliances regulated by the Fuel Gas Code.
4. Liquid fuels in piping systems and fixed appliances regulated by the Mechanical Code.
5003.1.2 Conversion.
A conversion factor of 10 pounds per gallon (1.2 kg/L) shall be used to ascertain the weight per gallon of liquid when such weight is not provided or otherwise available to the commissioner.
5003.1.3 Quantities not exceeding the maximum allowable quantity per control area.
The storage, handling and use of hazardous materials in quantities not exceeding the maximum allowable quantity per control area indicated in FC Tables 5003.1.1(1) through 5003.1.1(4) shall be in accordance with FC 5001 and 5003.
5003.1.4 Quantities exceeding the maximum allowable quantity per control area.
The storage, handling and use of hazardous materials in quantities exceeding the maximum allowable quantity per control area indicated in FC Tables 5003.1.1(1) through 5003.1.1(4) shall be in accordance with this chapter and, in a high-hazard occupancy, the requirements of the Building Code.
5003.1.5 Additional specific requirements.
The storage, handling and use of hazardous materials shall additionally comply with the specific requirements of FC Chapters 51 through 67, as applicable.
FC Table 5003.1.1(1) Maximum Allowable Quantity per Control Area of Hazardous Materials Posing a Physical Hazard a, j, m, n
Material Class Group When the Maximum Allowable Quantity Is Exceeded t Storage b Use-Closed Systems b Use-Open Systems b Solid pounds (cubic feet) Liquid gallons (pounds) Gas SCF Solid pounds (cubic feet) Liquid gallons (pounds) Gas SCF Solid pounds (cubic feet) Liquid gallons (pounds) Combustible dust Not Applicable H-2 See Note q Not Applicable Not Applicable See Note q Not Applicable Not Applicable See Note q Not Applicable Combustible fiber q Loose Baled o H-3 (100) (1,000) Not Applicable Not Applicable (100) (1,000) Not Applicable Not Applicable (20) (200) Not Applicable Combustible liquid c, i, r II IIIA IIIB H-2 or H-3 H-2 or H-3 Not Applicable Not Applicable 120 d, e 330 d, e 13,200 e, f Not Applicable Not Applicable 120 d 330 d 13,200 f Not Applicable Not Applicable 30 d 80 d 3,300 f Cryogenics flammable Not Applicable H-2 Not Applicable 45 d Not Applicable Not Applicable 45 d Not Applicable Not Applicable 10 d Cryogenics inert Not Applicable Not Applicable Not Applicable Not Applicable Not Limited Not Applicable Not Applicable Not Limited Not Applicable Not Applicable Cryogenics oxidizing Not Applicable H-3 Not Applicable 45 d Not Applicable Not Applicable 45 d Not Applicable Not Applicable 10 d Explosives Division 1.1 Division 1.2 Division 1.3 Division 1.4 Division 1.4G Division 1.5 Division 1.6 H-1 H-1 H-1 or H-2 H-3 H-3 H-1 H-1 0 1 e, g 5 e, g 50 e, g 125 e, l 1 e, g 1 e, g 0 (1) e, g (5) e, g (50) e, g Not Applicable (1) e, g Not Applicable Not Applicable 0 0.25 g 1 g 50 g Not Applicable 0.25 g Not Applicable 0 (0.25) g (1) g (50) g Not Applicable (0.25) g Not Applicable Not Applicable 0 0.25 g 1 g Not Applicable Not Applicable 0.25 g Not Applicable 0 (0.25) g (1) g Not Applicable Not Applicable (0.25) g Not Applicable Flammable gas Gaseous Liquefied H-2 Not Applicable Not Applicable (150) d, e 1,000 d, e Not Applicable Not Applicable Not Applicable (150) d, e 1,000 d, e Not Applicable Not Applicable Not Applicable Flammable liquids c, r IA s IB and IC H-2 or H-3 Not Applicable 30 d, e 120 d, e Not Applicable Not Applicable 30 d 120 d Not Applicable Not Applicable 10 d 30 d Flammable liquid, combination (IA s , IB, IC) Not Applicable H-2 or H-3 Not Applicable 120 d, e, h Not Applicable Not Applicable 120 d, h Not Applicable Not Applicable 30 d, h Flammable solid Not Applicable H-3 125 d, e Not Applicable Not Applicable 125 d Not Applicable Not Applicable 25 d Not Applicable Inert gas Gaseous Liquefied Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Limited Not Limited Not Applicable Not Applicable Not Applicable Not Applicable Not Limited Not Limited Not Applicable Not Applicable Not Applicable Not Applicable Organic peroxide p Unclassified Detonable I II III IV V H-1 H-2 H-3 H-3 Not Applicable Not Applicable 1 e, g 5 d, e 50 d, e 125 d, e Not Limited Not Limited (1) e, g (5) d, e (50) d, e (125) d, e Not Limited Not Limited Not Applicable 0.25 g 1 d 50 d 125 d Not Limited Not Limited (0.25) g (1) d (50) d (125) d Not Limited Not Limited Not Applicable 0.25 g 1 d 10 d 25 d Not Limited Not Limited (0.25) g (1) d (10) d (25) d Not Limited Not Limited Oxidizer 4 3 k 2 1 H-1 H-2 H-3 H-3 1 g 10 d, e 250 d, e 4,000 e, f (1) e, g (10) d, e (250) d, e (4,000) e, f Not Applicable 0.25 g 2 d 250 d 4,000 f (0.25) g (2) d (250) d (4,000) f Not Applicable 0.25 g 2 d 50 d 1,000 f (0.25) g (2) d (50) d (1,000) f Oxidizing gas u Gaseous Liquefied H-3 Not Applicable Not Applicable (150) d, e 1,500 d, e Not Applicable Not Applicable Not Applicable (150) d, e 1,500 d, e Not Applicable Not Applicable Not Applicable Pyrophoric material p detonable Not Applicable H-1 1 e, g (1) e, g 10 e, g 0.25 g (0.25) g 2 e, g 0 0 Pyrophoric material nondetonable Not Applicable H-2 4 e, g (4) e, g 50 e, g 1 g (1) g 10 e, g 0 0 Unstable (reactive) p detonable 4 3 H-1 H-1 1 e, g 1 e, g (1) e, g (1) e, g 10 e, g 10 e, g 0.25 g 0.25 g (0.25) g (0.25) g 2 e, g 2 e, g 0.25 g 0.25 g (0.25) g (0.25) g Unstable (reactive) nondetonable 4 3 2 1 H-1 H-1 or H-2 H-3 Not Applicable 1 e, g 5 d, e 50 d, e Not Limited (1) e, g (5) d, e (50) d, e Not Limited 10 e, g 50 d, e 250 d, e 750 d, e 0.25 g 1 d 50 d Not Limited (0.25) g (1) d (50) d Not Limited 2 e, g 10 d, e 250 d, e 750 d, e 0.25 g 1 d 10 d Not Limited (0.25) g (1) d (10) d Not Limited Water-reactive detonable p 3 2 H-1 H-1 1 e, g 1 e, g (1) e, g (1) e, g Not Applicable 0.25 g 0.25 g (0.25) g (0.25) g Not Applicable 0.25 g 0.25 g (0.25) g (0.25) g Water-reactive nondetonable 3 2 1 H-2 H-3 Not Applicable 5 d, e 50 d, e Not Limited (5) d, e (50) d, e Not Limited Not Applicable 5 d 50 d Not Limited (5) d (50) d Not Limited Not Applicable 1 d 10 d Not Limited (1) d (10) d Not Limited
For SI: 1 cubic foot = 0.02832 m 3 , 1 pound = 0.454 kg, 1 gallon = 3.785 L.
a. For use of control areas, see FC 5003.8.3.
b. The aggregate quantity in storage, handling and use shall not exceed the quantity listed for storage.
c. The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited providing the liquids are packaged in individual containers not exceeding 1.3 gallons. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, or consumer products, and cosmetics containing not more than 50 percent by volume of water-miscible liquids with the remainder of the solutions not being flammable shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons.
d. Maximum allowable quantities, except for liquefied petroleum gas and flammable liquid motor fuel, may be increased 100 percent in buildings protected throughout by a sprinkler system. Where Note e applies, the quantities may be increased as set forth in both notes.
e. Maximum allowable quantities, except for liquefied petroleum gas and flammable liquid motor fuel, may be increased 100 percent when stored in approved storage cabinets, gas cabinets, gas rooms, exhausted enclosures or listed safety cans. Listed safety cans shall be in accordance with FC 5003.9.10. Where Note d applies, the quantities may be increased as set forth in both notes.
f. Quantities shall not be limited in a building protected throughout by a sprinkler system.
g. Allowed only in buildings protected throughout by a sprinkler system.
h. Containing not more than the maximum allowable quantity per control area of Class IA, Class IB or Class IC flammable liquids.
i. Stationary fuel oil storage tanks shall comply with the requirements of the construction codes, including the Mechanical Code.
j. Quantities shown in the table in parentheses have the units shown in parentheses at the head of the column.
k. A maximum quantity of 200 pounds of solid or 20 gallons of liquid Class 3 oxidizers is allowed when such materials are necessary for maintenance and operation of equipment when the storage containers and the manner of storage are approved.
l. Reserved.
m. For gallons of liquids, divide the amount in pounds by 10 in accordance with FC 5003.1.2.
n. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with the requirements of FC 5003.11, see FC Table 5003.11.1.
o. Densely-packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class.
p. Unclassified detonable organic peroxides (see FC Chapter 62), detonable pyrophoric materials (see FC Chapter 64), detonable unstable (reactive) materials (see FC Chapter 66) and detonable water-reactive materials (see FC Chapter 67) shall be treated as explosives for purposes of storage, handling and use (see FC Chapter 56).
q. Where manufactured, generated or used in such a manner that the concentration and conditions create a re or explosion hazard based on information prepared in accordance with FC 104.7.2.
r. For storage of flammable and combustible liquids in Group M occupancy, see FC Chapter 57. For storage of flammable and combustible liquids in distilleries, see FC Chapter 40. The maximum allowable quantities shall not apply to alcohol-based hand rubs classified as Class I or II liquids in dispensers that are installed or placed for use on a premises in accordance with FC 5705.5.1 and 5705.5.2.
s. For purposes of this table, gasoline and other flammable liquid motor fuels are classified as a Class IA flammable liquid.
t. The maximum allowable quantities shall be limited by FC 5006 for non-production laboratories classified as Occupancy Group B.
u. Medical gas storage in hospitals and other medical facilities classified as Occupancy Group B and I shall be subject to the requirements as set forth in FC 5306.
FC Table 5003.1.1(2) Maximum Allowable Quantity per Control Area of Hazardous Material Posing a Health Hazard a, c, f, h, i, j
Material Storage b Use-Closed Systems b Use-Open Systems b Solid pounds d, e Liquid gallons (pounds) d, e Gas SCF (pounds) d Solid pounds d Liquid gallons (pounds) d Gas SCF (pounds) d Solid pounds d Liquid gallons (pounds) d Corrosive 5,000 500 Gaseous 810 e Liquefied (150) 5,000 500 Gaseous 810 e Liquefied (150) 1,000 100 Highly toxic 10 (10) Gaseous 20 g Liquefied (4) g 10 (10) Gaseous 20 g Liquefied (4) g 3 (3) Toxic 500 (500) Gaseous 810 e Liquefied (150) e 500 (500) Gaseous 810 e Liquefied (150) e 125 (125)
For SI: 1 cubic foot = 0.02832 m 3 , 1 pound = 0.454 kg, 1 gallon = 3.785 L.
a. For use of control areas, see FC 5003.8.3.
b. The aggregate quantity in storage, handling and use shall not exceed the quantity listed for storage.
c. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs or consumer products, and cosmetics, containing not more than 50 percent by volume of water-miscible liquids and with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons.
d. Maximum allowable quantities may be increased 100 percent in buildings protected throughout by a sprinkler system. Where Note e applies, the quantities increased shall be as set forth in both notes.
e. Maximum allowable quantities may be increased 100 percent when stored in approved storage cabinets, gas cabinets, or exhausted enclosures. Where Note d applies, the quantities increased shall be as set forth in both notes.
f. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with the requirements of FC 5003.11, see FC Table 5003.11.1.
g. Allowed only when stored in approved exhausted gas cabinets or exhausted enclosures.
h. Quantities shown in the table in parentheses have the units shown in parentheses at the head of the column.
i. For gallons of liquids, divide the amount in pounds by 10 in accordance with FC 5003.1.2.
j. The maximum allowable quantities shall be limited by FC 5006 for non-production laboratories classified as Occupancy Group B.
FC Table 5003.1.1(3) Maximum Allowable Quantity per Control Area of Hazardous Materials Posing a Physical Hazard in an Outdoor Control Area a, c, d, f
Material Class Storage b Use-Closed Systems b Use-Open Systems b Solid pounds Liquid gallons (pounds) Gas SCF Solid pounds Liquid gallons (pounds) Gas SCF Solid pounds Liquid gallons (pounds) Flammable gas Gaseous Liquefied Not Applicable Not Applicable (150) 1,000 Not Applicable Not Applicable Not Applicable (150) 1,000 Not Applicable Not Applicable Not Applicable Flammable solid Not Applicable 125 Not Applicable Not Applicable 25 Not Applicable Not Applicable 25 Not Applicable Inert gas Cryogenic inert Gaseous Liquefied Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Limited Not Limited Not Limited Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Limited Not Limited Not Limited Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Organic peroxide e Unclassified Detonable 1 (1) Not Applicable 0.25 (0.25) Not Applicable 0.25 (0.25) Organic peroxide I II III IV V 5 50 125 500 Not Limited (5) (50) (125) (500) Not Limited Not Applicable 1 50 125 500 Not Limited (1) (50) (125) (500) Not Limited Not Applicable 1 10 25 100 Not Limited (1) (10) (25) (100) Not Limited Oxidizer 4 3 2 1 1 10 250 4,000 (1) (10) (250) (4,000) Not Applicable 0.25 2 250 4,000 (0.25) (2) (250) (4,000) Not Applicable 0.25 2 50 1,000 (0.25) (2) (50) (1,000) Oxidizing gas Gaseous Liquefied Not Applicable Not Applicable 15 1,500 Not Applicable Not Applicable Not Applicable 15 1,500 Not Applicable Not Applicable Not Applicable Pyrophoric material e detonable Not Applicable 1 (1) 10 0.25 (0.25) 2 0 0 Pyrophoric material nondetonable Not Applicable 4 (4) 50 1 (1) 10 0 0 Unstable (reactive) e detonable 4 3 1 1 (1) (1) 10 10 0.25 0.25 (0.25) (0.25) 2 2 0.25 0.25 (0.25) (0.25) Unstable (reactive) nondetonable 4 3 2 1 1 5 50 Not Limited (1) (5) (50) Not Limited 10 50 250 750 0.25 1 50 Not Limited (0.25) (1) (50) Not Limited 2 10 250 750 0.25 1 10 Not Limited (0.25) (1) (10) Not Limited Water- reactive e detonable 3 2 1 1 (1) (1) Not Applicable 0.25 0.25 (0.25) (0.25) Not Applicable 0.25 0.25 (0.25) (0.25) Water- reactive nondetonable 3 2 1 5 50 Not Limited (5) (50) Not Limited Not Applicable 5 50 Not Limited (5) (50) Not Limited Not Applicable 1 10 Not Limited (1) (10) Not Limited
For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 cubic foot = 0.02832 m 3 .
a. For gallons of liquids, divide the amount in pounds by 10 in accordance with FC 5003.1.2.
b. The aggregate quantities in storage and use shall not exceed the quantity listed for storage.
c. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed in outdoor storage per single property under the same ownership or control used for retail or wholesale sales is allowed to exceed the maximum allowable quantity per control area when such storage is in accordance with FC 5003.11.
d. Quantities shown in the table in parentheses have the units shown in parentheses at the head of the column.
e. Unclassified detonable organic peroxides (see FC Chapter 62), detonable pyrophoric materials (see FC Chapter 64), detonable unstable (reactive) materials (see FC Chapter 66) and detonable water-reactive materials (see FC Chapter 67) shall be treated as explosives for purposes of storage (see FC Chapter 56).
f. In addition to these requirements, the outdoor storage and use of hazardous materials shall comply with applicable requirements of the Zoning Resolution.
FC Table 5003.1.1(4) Maximum Allowable Quantity per Control Area of Hazardous Materials Posing a Health Hazard in an Outdoor Control Area a, c, f, g
Material Storage b Use-Closed Systems b Use-Open Systems b Solid pounds Liquid gallons (pounds) Gas SCF (pounds) Solid pounds Liquid gallons (pounds) Gas SCF (pounds) Solid pounds Liquid gallons (pounds) Corrosives 5,000 500 Gaseous 810 Liquefied (150) 5,000 500 Gaseous 810 Liquefied (150) 1,000 100 Highly toxics 10 (10) Gaseous 20 d Liquefied (4) d 10 (10) Gaseous 20 d Liquefied (4) d 3 (3) Toxics 500 (500) e Gaseous 810 Liquefied (150) 500 50 e Gaseous 810 Liquefied (150) 25 (25) e
For SI: 1 cubic foot = 0.02832 m 3 , 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 pound per square inch absolute = 6.895 kPa, °C = (°F-32)/1.8.
a. For gallons of liquids, divide the amount in pounds by 10 in accordance with FC 5003.1.2.
b. The aggregate quantities in storage and use shall not exceed the quantity listed for storage.
c. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed in outdoor storage on a single property under the same ownership or control used for retail or wholesale sales is allowed to exceed the maximum allowable quantity per control area when such storage is in accordance with FC 5003.11.
d. Allowed only when used in approved exhausted gas cabinets, exhausted enclosures or under fume hoods.
e. The maximum allowable quantity per control area for toxic liquids with vapor pressures in excess of 1 psia at 77°F shall be the maximum allowable quantity per control area listed for highly toxic liquids.
f. Quantities shown in the table in parentheses have the units shown in parentheses at the head of the column.
g. In addition to these requirements, the outdoor storage and use of hazardous materials shall comply with the applicable requirements of the Zoning Resolution.
5003.2 Devices, equipment, systems and processes.
Devices, equipment, systems and processes utilized for storage, handling and use of hazardous materials shall be in accordance with FC 5003.2.1 through 5003.2.8 and the regulations of the New York State Department of Environmental Conservation as set forth in 6 NYCRR Parts 596, 598, 599, 613.
5003.2.1 Design and construction of containers and tanks.
Containers and tanks shall be designed and constructed in accordance with approved standards. Containers, tanks and other means used for containment of hazardous materials shall be of an approved type.
5003.2.2 Piping, tubing, valves and fittings.
Piping, tubing, valves and fittings conveying hazardous materials, except piping for inlet connections to prevent backflow or piping for pressure relief devices, shall be designed and installed in accordance with approved standards and FC 5003.2.2.1 and 5003.2.2.2.
5003.2.2.1 Design and construction.
Piping, tubing, valves, fittings and ancillary equipment used for hazardous materials shall be in accordance with the following:
1. Piping, tubing, valves, fittings and ancillary equipment shall be designed and fabricated from materials compatible with the material to be contained and shall be of adequate strength and durability to withstand the pressure, structural and seismic stress, and exposure to which they are subjected.
2. Piping and tubing shall be identified in accordance with ASME A13.1 to indicate the material conveyed.
3. Readily accessible manual valves, or automatic remotely-activated fail-safe emergency shutoff valves, shall be installed on supply piping and tubing at the point of use and at the tank, container or other source of supply.
4. Emergency shutoff valves shall be clearly visible and readily accessible. A durable sign shall be conspicuously posted immediately adjacent to such valves that identifies their location.
5. Backflow prevention or check valves shall be provided when the backflow of hazardous materials could create a hazardous condition or cause the unauthorized discharge of hazardous materials.
6. Where gases or liquids having a hazard ranking of health hazard Class 3 or 4, flammability Class 4, or instability Class 3 or 4 in accordance with NFPA 704 are conveyed in pressurized piping above 15 pounds per square inch gauge (psig) (103 kPa), an approved means of leak detection and emergency shutoff or excess flow control shall be provided. Where the piping originates from within a hazardous material storage room or area, the excess flow control shall be located within the storage room or area. Where the piping originates from any other source of supply, the excess flow control shall be located as close to the source of supply as practical.
Exceptions:
1. Piping for inlet connections designed to prevent backflow.
2. Piping for pressure relief devices.
5003.2.2.2 Additional regulations for supply piping for health-hazard materials.
Supply piping and tubing for gases and liquids having a health-hazard ranking of 3 or 4 in accordance with NFPA 704 shall be in accordance with ASME B31.3 and the following:
1. Piping and tubing utilized for the transmission of highly toxic, toxic or highly volatile corrosive liquids and gases shall have welded, threaded or flanged connections throughout, except where connections are located within a ventilated enclosure if the material is a gas, or an approved method of drainage or containment is provided for connections if the material is a liquid.
2. Piping and tubing shall not be located within corridors, within any portion of a means of egress required to be enclosed in fire-resistance-rated construction or in concealed spaces in areas not classified as Group H occupancies.
Exception: Piping and tubing within the space defined by the walls of corridors and the floor or roof above or in concealed spaces above other occupancies when installed in accordance with Section 415 of the Building Code for Group H-5 occupancies.
5003.2.3 Devices, equipment and systems.
Devices, equipment and systems, including required detection and alarm systems, installed or used in conjunction with the storage, handling and use of hazardous materials shall be listed or approved.
5003.2.4 Installation of tanks.
Installation of tanks shall be in accordance with FC 5003.2.4.1 through 5003.2.4.3 and with the regulations of the New York State Department of Environmental Conservation as set forth in 6 NYCRR Sections 599 and 613.
5003.2.4.1 Underground tanks.
Underground tanks used for the storage of liquid hazardous materials shall be provided with secondary containment.
5003.2.4.2 Aboveground tanks.
Aboveground stationary tanks used for the storage of liquid hazardous materials shall be located and protected in compliance with the requirements for outdoor storage of the particular material involved.
5003.2.4.2.1 Marking.
Aboveground stationary tanks shall be marked as required by FC 5003.5.
5003.2.4.3 Flood hazard.
Hazardous materials storage tanks located in areas of special flood hazard or on the premises of Group I-2 occupancies that are hospitals located in shaded X-Zones (as defined in Section G201.2 of the Building Code) shall comply with Section G307.5 of Appendix G of the Building Code.
5003.2.5 Empty containers and tanks.
Empty containers and tanks previously used for the storage of hazardous materials shall be free from residual material and vapor in compliance with the requirements of DOTn, the Resource Conservation and Recovery Act (RCRA) or other governmental agencies having jurisdiction, or shall be stored, handled and used in compliance with the requirements of this code.
5003.2.6 Maintenance.
In addition to the requirements of FC 5003.2.3, all devices, equipment and systems used in conjunction with hazardous materials, including tanks, and detection and alarm systems, shall be maintained in good working order. Defective devices, equipment and systems shall be removed from service and repaired or replaced, or disposed of lawfully.
5003.2.6.1 Tanks out of service for 30 days.
Stationary tanks not used for a period of 30 calendar days or more shall be properly safeguarded or removed in an approved manner. Such tanks shall have the fill line, gauge opening and pump connection secured against tampering. Vent lines shall be properly maintained. Stationary tanks containing flammable and combustible liquid out of service for a period of 30 calendar days or more shall additionally comply with the requirements of FC 5704.2.13.
5003.2.6.1.1 Return to service.
Tanks that are returned to service shall be tested in an approved manner prior to use.
5003.2.7 Liquid-level limit control.
Atmospheric tanks that contain hazardous material liquids shall be equipped with a liquid-level limit control or other approved means to prevent overfilling of the tank.
Exception: Tanks with a capacity not exceeding 500 gallons (1893 L) that are filled from a source other than a cargo tank or tank car.
5003.2.8 Seismic protection.
Machinery and equipment utilizing hazardous materials shall be braced and anchored in accordance with the seismic design requirements of the Building Code for the seismic design category in which the machinery or equipment is classified.
5003.2.9 Testing.
The following devices, equipment and systems shall be tested at the time of installation and not less than annually thereafter, provided that testing shall be conducted at least as often as is recommended by the manufacturer of such device, equipment or system:
1. Gas detection systems, alarms and automatic emergency shutoff valves required by FC 6004.2.2.10 for highly toxic and toxic gases.
2. Limit control systems for liquid level, temperature and pressure required by FC 5003.2.7, 5004.8 and 5005.1.4.
3. Emergency alarm systems required by FC 5004.9 and 5005.4.4.
4. Monitoring and supervisory systems required by FC 5004.10 and 5005.1.6.
5. Manually activated shutdown controls required by FC 6403.1.1.1 for compressed gas systems conveying pyrophoric gases.
5003.3 Release and disposal of hazardous materials.
It shall be unlawful to release or dispose of any amount of hazardous material, including pesticides and fertilizers used for domestic, agricultural or horticultural purposes, into a sewer, storm drain, ditch, drainage canal, creek, stream, river, lake or tidal waterway or on the ground, sidewalk, street, highway or into the atmosphere, except when allowed by federal, state or local regulations or permits, including the regulations of the New York State Department of Environmental Conservation, as set forth in 6 NYCRR Parts 597 and 611.
5003.3.1 Reporting of discharges.
When hazardous materials are released in quantities reportable under federal, state or local regulations, the commissioner shall be notified and the following procedures required in accordance with FC 5003.3.1.1 through 5003.3.1.4.
5003.3.1.1 Records.
Accurate records shall be kept of the discharge of hazardous materials.
5003.3.1.2 Preparation.
Provisions shall be made for controlling and mitigating accidental discharges.
5003.3.1.3 Control.
When a discharge is caused by a container failure, the container shall be repaired or removed from service.
5003.3.1.4 Responsibility for cleanup.
The owner of a facility or other person responsible for an accidental discharge shall undertake all actions necessary to remediate such discharge. When deemed necessary by the commissioner, cleanup may be initiated by the department or other city agency. Costs associated with such cleanup shall be borne by the owner or other person responsible for the discharge. The department shall give such owner or other person written notice of such costs and an opportunity to be heard. Payment of such costs shall be recoverable in any manner authorized by law, rule or regulation. Failure to pay such costs shall cause a lien to be placed upon the premises pursuant to the provisions of FC 117.4, as applicable, or against vehicles or other personal property in accordance with the provisions applicable thereto. Nothing in this section shall be construed to preclude the implementation of response measures, or the recovery of the costs of such measures, by any other city agency, either prior or subsequent to any response measure implemented pursuant to this section.
5003.4 Safety data sheets.
A safety data sheet (SDS) for each hazardous material stored, handled or used on a premises shall be maintained on such premises at a location where the SDS is readily available for reference by persons handling or using such hazardous materials or supervising such storage, handling or use, and by any department representative.
5003.5 Hazard identification signs.
Unless otherwise exempted by the commissioner, hazard identification signs as set forth in NFPA 704 for the specific material contained shall be conspicuously affixed on stationary containers and aboveground tanks and at entrances to locations where hazardous materials are stored, handled or used, including dispensing, in quantities requiring a permit, including locations where such materials are dispensed, and at such other locations as may be designated by the commissioner.
5003.5.1 Markings.
Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. Signs reading "COMPRESSED GAS" shall be conspicuously posted at the entrance to rooms or on cabinets containing compressed gases.
5003.6 Signs.
Signs and markings required by FC 5003.5 and 5003.5.1 shall not be obscured or removed, shall be in English as a primary language or in symbols allowed by this code, shall be durable, and the size, color and lettering shall be acceptable to the commissioner.
5003.7 Sources of ignition.
Sources of ignition shall comply with the requirements of FC 5003.7.1 through 5003.7.3.
5003.7.1 Smoking.
It shall be unlawful to smoke in the following locations, and "No Smoking" signs in compliance with the requirements of FC 310 shall be conspicuously posted:
1. In rooms or areas where hazardous materials are stored or used in open systems in amounts requiring a permit.
2. Within 25 feet (7620 mm) of outdoor hazardous material storage, handling and use areas, including dispensing areas.
3. In rooms or areas where flammable or combustible hazardous materials are stored, handled or used.
5003.7.2 Open flames.
Open flames and devices that generate or operate at a high temperature shall be kept a safe distance from hazardous material in storage or use.
5003.7.3 Industrial trucks.
Powered industrial trucks used in areas designated as hazardous (classified) locations in accordance with the Electrical Code shall be listed and labeled in accordance with NFPA 505.
5003.8 Construction requirements.
Buildings, structures, control areas, enclosures and cabinets for hazardous materials shall be designed and constructed in accordance with FC 5003.8.1 through 5003.8.7.
5003.8.1 Buildings.
Buildings, structures, or portions thereof, in which hazardous materials are stored, handled or used shall be constructed in accordance with the construction codes, including the Building Code.
5003.8.2 Required detached buildings.
Group H occupancies containing quantities of hazardous materials in excess of those set forth in FC Table 5003.8.2 shall be in detached buildings.
FC Table 5003.8.2 Required Detached Storage
Detached Storage Is Required When the Quantity of Material Exceeds That Listed Herein Material Class Solids and liquids (tons) a, b Gases (SCF) a, b Explosives a Division 1.1 Division 1.2 Division 1.3 Division 1.4 Division 1.4 c Division 1.5 Division 1.6 Maximum Allowable Quantity Maximum Allowable Quantity Maximum Allowable Quantity Maximum Allowable Quantity 1 Maximum Allowable Quantity Maximum Allowable Quantity Not Applicable Oxidizers Class 4 Maximum Allowable Quantity Maximum Allowable Quantity Unstable (reactives) detonable Class 3 or 4 Maximum Allowable Quantity Maximum Allowable Quantity Water-reactives detonable Class 2 or 3 Maximum Allowable Quantity Not Applicable Oxidizer, liquids and solids Class 3 Class 2 1,200 2,000 Not Applicable Organic peroxides Unclassified Detonable Class I Class II Class III Maximum Allowable Quantity Maximum Allowable Quantity 25 50 Not Applicable Unstable (reactives) nondetonable Class 4 Class 3 Class 2 Maximum Allowable Quantity 1 25 Maximum Allowable Quantity 2,000 10,000 Water-reactives nondetonable Class 3 Class 2 1 25 Not Applicable Pyrophoric material detonable Not Applicable Maximum Allowable Quantity Maximum Allowable Quantity Pyrophoric gases nondetonable Not Applicable Not Applicable 2,000
For SI: 1 pound = 0.454 kg, 1 cubic foot = 0.02832 m 3 , 1 ton = 2,000 pounds = 907.2 kg.
a. For materials that are detonable, the distance to other buildings or lot lines shall be as specified in the Building Code. For materials classified as explosives, the required separation distances shall be as specified in FC Chapter 56. Unclassified detonable organic peroxides (see FC Chapter 62), detonable pyrophoric materials (see FC Chapter 64), detonable unstable (reactive) materials (see FC Chapter 66) and detonable water-reactive materials (see FC Chapter 67) shall be treated as explosives for purposes of storage, handling and use (see FC Chapter 56).
b. "Maximum Allowable Quantity" means the maximum allowable quantity per control area set forth in FC Table 5003.1.1(1).
c. Limited to Division 1.4 materials and articles, including articles packaged for shipment, that are not regulated as an explosive under Bureau of Alcohol, Tobacco, Firearms and Explosives regulations, or unpackaged articles used in process operations that do not propagate a detonation or deflagration between articles, providing the net explosive weight of individual articles does not exceed 1 pound.
5003.8.3 Control areas.
Control areas shall be in accordance with FC 5003.8.3.1 through 5003.8.3.5.
5003.8.3.1 Construction requirements.
Control areas shall be separated from each other by fire barriers constructed in accordance with Chapter 7 of the Building Code or horizontal assemblies constructed in accordance with Chapter 7 of the Building Code, or both.
5003.8.3.2 Percentage of maximum allowable quantities.
The percentage of maximum allowable quantities of hazardous materials per control area allowed at each floor level within a building shall be in accordance with FC Table 5003.8.3.3.
5003.8.3.3 Number.
The maximum number of control areas per floor within a building or structure shall be in accordance with FC Table 5003.8.3.3.
FC Table 5003.8.3.3 Design and Number of Control Areas
Floor Level Percentage of the Maximum Allowable Quantity per Control Area a Number of Control Areas per Floor Fire-Resistance Rating for Fire Barriers in Hours b Above grade plane Higher than 9 7 - 9 6 5 4 3 2 1 5 5 12.5 12.5 12.5 50 75 100 1 2 2 2 2 2 3 4 2 2 2 2 2 1 1 1 Below grade plane 1 2 Lower than 2 75 50 Not Allowed 3 2 Not Allowed 1 1 Not Allowed
a. Percentages shall be of the maximum allowable quantity per control area shown in FC Tables 5003.1.1(1) and 5003.1.1(2), with all increases allowed in the footnotes to those tables.
b. Fire barriers shall include walls and floors as necessary to provide separation from other portions of the building.
5003.8.3.4 Fire-resistance rating requirements.
The required fire-resistance rating for fire barriers shall be in accordance with FC Table 5003.8.3.3. The floor assembly of the control area and the construction supporting the floor of the control area shall have a minimum 2-hour fire-resistance rating.
Exception: The floor assembly of the control area and the construction supporting the floor of the control area may be 1-hour fire-resistance rated in a building of Type IIA, IIIA and VA construction that is three stories or less in height and protected throughout by a sprinkler system.
5003.8.3.5 Hazardous materials in Group M display and storage areas and in Group S storage areas.
The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials allowed within a single control area of a Group M display and storage area or a Group S storage area is allowed to exceed the maximum allowable quantities specified in FC Tables 5003.1.1(1) and 5003.1.1(2) without classifying the building or use as a Group H occupancy, provided that the materials are displayed and stored in accordance with FC 5003.11.
5003.8.4 Gas rooms.
Where a gas room is provided to comply with the requirements of FC Chapter 60, the gas room shall be in accordance with FC 5003.8.4.1 and 5003.8.4.2.
5003.8.4.1 Construction.
Gas rooms shall be protected throughout by a sprinkler system. Gas rooms shall be separated from the remainder of the building in accordance with the construction codes, including the Building Code, based on the occupancy group into which the building has been classified.
5003.8.4.2 Ventilation system.
The ventilation system for gas rooms shall be designed to operate at a negative pressure relative to the surrounding area. Highly toxic and toxic gases shall additionally comply with the requirements of FC 6004.2.2.6. The ventilation system shall be installed in accordance with the construction codes, including the Mechanical Code.
5003.8.5 Exhausted enclosures.
Where an exhausted enclosure is used to increase maximum allowable quantity per control area or when the location of hazardous materials in exhausted enclosures is provided to comply with the requirements of FC Chapter 60, the exhausted enclosure shall be in accordance with FC 5003.8.5.1 through 5003.8.5.3.
5003.8.5.1 Construction.
Exhausted enclosures shall be of noncombustible construction.
5003.8.5.2 Ventilation.
The ventilation system for exhausted enclosures shall be designed to operate at a negative pressure relative to the surrounding area. Ventilation systems used for highly toxic and toxic gases shall additionally comply with the requirements of FC 6004.1.3. The ventilation system shall be installed in accordance with the construction codes, including the Mechanical Code.
5003.8.5.3 Fire extinguishing system.
Exhausted enclosures where flammable materials are used shall be protected by a fire extinguishing system in accordance with FC Chapter 9 and the construction codes, including the Building Code.
5003.8.6 Gas cabinets.
Where a gas cabinet is used to increase the maximum allowable quantity per control area or when the location of compressed gases in gas cabinets is provided to comply with the requirements of FC Chapter 60, the gas cabinet shall be in accordance with FC 5003.8.6.1 through 5003.8.6.3.
5003.8.6.1 Construction.
Gas cabinets shall be constructed of not less than 0.097-inch (2.5-mm) (No. 12 gauge) steel; provided with self-closing limited access ports or noncombustible windows to give access to equipment controls; and have all interior surfaces treated, coated or constructed of materials that are compatible with the hazardous materials stored.
5003.8.6.2 Ventilation.
The ventilation system for gas cabinets shall be designed to operate at a negative pressure relative to the surrounding area. Ventilation systems used for highly toxic and toxic gases shall additionally comply with the requirements of FC 6004.1.2. The ventilation system shall be installed in accordance with the construction codes, including the Mechanical Code.
5003.8.6.3 Maximum number of containers per gas cabinet.
The number of containers stored in a single gas cabinet shall not exceed three.
5003.8.7 Hazardous materials storage cabinets.
Where storage cabinets are used to increase maximum allowable quantity per control area or to comply with the requirements of this chapter, such cabinets shall be in accordance with FC 5003.8.7.1 and 5003.8.7.2.
5003.8.7.1 Construction.
All interior surfaces of such cabinets shall be treated, coated or constructed of materials that are nonreactive with the hazardous material stored. Cabinets shall either be listed in accordance with UL 1275 as suitable for the intended storage or constructed in accordance with the following:
1. Cabinets shall be of steel having a thickness of not less than 0.0478 inch (1.2 mm) (No. 18 gauge). The cabinet, including the door, shall be double walled with a 1 1/2-inch (38 mm) airspace between the walls. Joints shall be riveted or welded and shall be tight fitting. Doors shall be well fitted, self-closing and equipped with a self-latching device.
2. The bottoms of cabinets utilized for the storage of liquids shall be liquid-tight to a minimum height of 2 inches (51 mm).
5003.8.7.1.1 Electrical equipment.
Electrical equipment and devices within cabinets used for the storage of hazardous gases or liquids shall be in accordance with the Electrical Code.
5003.8.7.2 Warning markings.
Cabinets shall be clearly identified in an approved manner with red letters on a contrasting background to read: HAZARDOUS – KEEP FIRE AWAY.
5003.9 General safety precautions.
General precautions for the safe storage, handling and use of hazardous materials shall be in accordance with FC 5003.9.1 through 5003.9.10.
5003.9.1 Personnel training and written procedures.
Persons responsible for the operation of areas in which hazardous materials are stored, handled or used, including dispensing, shall be familiar with the chemical nature of the materials and the appropriate mitigating actions necessary in the event of fire, leak or spill. A certificate of fitness shall be required when specified by this code or the rules or as a condition of a permit.
5003.9.1.1 Fire department liaison.
One or more responsible persons shall be designated to serve as a liaison to the department in connection with any emergency response to the premises, for purposes of providing access to the location where hazardous materials are stored on the premises, providing access to safety data sheets, and otherwise assisting in the development and implementation of emergency procedures. The names and telephone numbers of such responsible persons shall be included on the annual inventory required by New York State General Municipal Law Section 209-u and on a hazardous materials management plan when such plan is required. Telephone numbers shall include a 24-hour contact number for such responsible persons.
5003.9.2 Security.
Storage, handling and use areas, including dispensing areas, shall be secured against unauthorized entry and safeguarded in a manner approved by the commissioner.
5003.9.3 Protection from vehicles.
Posts or other approved means shall be provided to protect storage tanks and connected piping, valves and fittings; use areas; and dispensing areas subject to vehicular damage in accordance with FC 312.
5003.9.4 Electrical wiring and equipment.
Electrical wiring and equipment shall be installed and maintained in accordance with the Electrical Code.
5003.9.5 Static accumulation.
When conditions exist that could cause a flammable mixture to be ignited by static electricity, equipment shall be grounded and all other necessary and appropriate actions taken to prevent the accumulation of a static charge.
5003.9.6 Protection from light.
Materials that are sensitive to light shall be stored in containers designed to protect them from such exposure.
5003.9.7 Shock protection.
Materials that are sensitive to shock shall be padded, suspended or otherwise protected against jarring, seismic activity or other movement.
5003.9.8 Separation of incompatible materials.
Incompatible materials shall be separated while in storage or use except for stored materials in containers having a capacity of not more than 5 pounds (2 kg) or 1/2 gallon (2 L). Separation shall be accomplished by:
1. Segregating incompatible materials in storage by a distance of not less than 20 feet (6096 mm).
2. Isolating incompatible materials in storage by a noncombustible partition extending not less than 18 inches (457 mm) above and to the sides of the stored material.
3. Storing liquid and solid materials in hazardous material storage cabinets. Materials that are incompatible shall not be stored in the same cabinet.
4. Storing compressed gases in gas cabinets or exhausted enclosures in accordance with FC 5003.8.5 and 5003.8.6. Materials that are incompatible shall not be stored within the same cabinet or exhausted enclosure.
5003.9.9 Shelf storage.
Shelving shall be of substantial construction, and shall be braced and anchored in accordance with the seismic design requirements of the construction codes, including the Building Code, for the seismic zone in which the material is located. Shelving shall be treated, coated or constructed of materials that are compatible with the hazardous materials stored. Shelves shall be provided with a lip or guard when used for the storage of individual containers.
Exceptions:
1. Storage in hazardous material storage cabinets or laboratory furniture specifically designed for such use.
2. Storage of hazardous materials in amounts not requiring a permit in accordance with FC 105.6.
Shelf storage of hazardous materials shall be maintained in an orderly manner.
5003.9.10 Safety cans.
Safety cans shall be listed in accordance with UL 30 when used to increase the maximum allowable quantities per control area of flammable or combustible liquids in accordance with FC Table 5003.1.1(1). Safety cans listed in accordance with UL 1313 are allowed for flammable and combustible liquids when not used to increase the maximum allowable quantities per control area and for other hazardous material liquids in accordance with the listing.
5003.10 Handling.
In addition to the requirements of FC 5003.2, the handling of hazardous materials in corridors or exit enclosures shall be in accordance with FC 5003.10.1 through 5003.10.3.6.
5003.10.1 Valve protection.
Hazardous material gas containers and tanks moved during handling shall have their protective caps in place. Containers and tanks of highly toxic or toxic compressed gases shall have their valve outlets capped or plugged with an approved closure device in accordance with FC Chapter 53.
5003.10.2 Carts and hand trucks required.
Containers of hazardous materials having a hazard ranking of 3 or 4 pursuant to NFPA 704, and liquids in containers exceeding 5 gallons (19 L), shall be moved during handling on a cart or hand truck meeting the requirements of FC 5003.10.3, when moved through any corridor or exit enclosure.
Exceptions:
1. Two hazardous material liquid containers, which are hand carried in approved safety carriers.
2. Not more than four drums not exceeding 55 gallons (208 L) each, which are moved by suitable drum trucks.
3. Containers of compressed gases, which are moved by approved carts or hand trucks, and containers not exceeding 25 pounds (11 kg), which are hand carried.
4. Solid hazardous materials not exceeding 100 pounds (45 kg), which are moved by approved hand trucks, and a single container not exceeding 50 pounds (23 kg), which is hand carried.
5003.10.3 Carts and hand trucks.
Carts and hand trucks required by FC 5003.10.2 to be used to move hazardous materials shall be designed and constructed in accordance with FC 5003.10.3.1 through 5003.10.3.6.
5003.10.3.1 Design.
Carts and hand trucks used to move hazardous materials shall be designed to provide a stable base for such movement during handling and shall have a means of restraining containers to prevent accidental dislodgement. Compressed gas containers placed on carts and hand trucks shall be individually restrained.
5003.10.3.2 Speed-control devices.
Carts and hand trucks shall be provided with a device that will enable the operator to safely control movement by providing stops or speed-reduction devices.
5003.10.3.3 Construction.
The cart or hand truck shall be sturdily constructed of materials compatible with the material being moved.
5003.10.3.4 Spill control.
Carts and hand trucks used to move liquids shall be capable of containing a spill from the largest single container being moved.
5003.10.3.5 Attendance.
Carts and hand trucks used to move materials shall not obstruct or be left unattended in any corridor, exit enclosure, or other means of egress.
5003.10.3.6 Incompatible materials.
Incompatible materials shall not be kept on the same cart or hand truck.
5003.11 Group M storage and display and Group S storage.
The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials stored and displayed within a single control area of a Group M occupancy, or an outdoor control area, or stored in a single control area of a Group S occupancy, may exceed the maximum allowable quantity per control area indicated in FC 5003.1 when stored and displayed in accordance with FC 5003.11.1 through 5003.11.3.10.
5003.11.1 Maximum allowable quantity per control area in Group M or S occupancies.
The aggregate amount of nonflammable solid and nonflammable or noncombustible liquid hazardous materials stored and displayed within a single control area of a Group M occupancy or stored in a single control area of a Group S occupancy shall not exceed the amounts set forth in FC Table 5003.11.1.
FC Table 5003.11.1 Maximum Allowable Quantity per Indoor and Outdoor Control Area in Group M and S Occupancies Nonflammable Solids, Nonflammable and Noncombustible Liquids d, e, f
Condition Maximum Allowable Quantity per Control Area Material a Class Solids pounds Liquids gallons Health-Hazard Materials – Nonflammable and Noncombustible Solids and Liquids Corrosives b, c Not Applicable 9,750 975 Highly toxics Not Applicable 20 b, c 2 b, c Toxics b, c Not Applicable 1,000 100 Physical-Hazard Materials – Nonflammable and Noncombustible Solids and Liquids Oxidizers b, c 4 Not Allowed Not Allowed 3 1,150 g 115 2 2,250 h 225 1 18,000 i, j 1,800 i, j Nondetonable unstable (reactives) b, c 4 Not Allowed Not Allowed 3 550 55 2 1,150 115 1 Not Limited Not Limited Nondetonable water-reactives 3 b, c 550 55 2 b, c 1,150 115 1 Not Limited Not Limited
For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L, 1 cubic foot = 0.02832 m 3 .
a. Hazard categories are as specified in FC 5001.2.2.
b. Maximum allowable quantities shall be increased 100 percent in buildings protected throughout by a sprinkler system. When Note c applies, amounts increased shall be as set forth in both notes.
c. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets in accordance with FC 5003.8. When Note b applies, amounts increased shall be as set forth in both notes.
d. See FC Table 5003.8.3.3 for design and number of control areas.
e. Maximum allowable quantities for other hazardous material categories shall be in accordance with FC 5003.1.
f. Maximum allowable quantities shall be increased 100 percent in outdoor control areas.
g. Maximum allowable quantities may be increased to 2,250 pounds when individual packages are in the original sealed containers from the manufacturer or packager and do not exceed 10 pounds each.
h. Maximum allowable quantities may be increased to 4,500 pounds when individual packages are in the original sealed containers from the manufacturer or packager and do not exceed 10 pounds each.
i. Quantities are unlimited where protected by a sprinkler system.
j. Quantities are unlimited in an outdoor control area.
5003.11.2 Maximum allowable quantity per outdoor control area in Group M or S occupancies.
The aggregate amount of nonflammable solid and nonflammable or noncombustible liquid hazardous materials stored and displayed within a single outdoor control area of a Group M occupancy shall not exceed the amounts set forth in FC Table 5003.11.1.
5003.11.3 Storage and display.
Storage and display shall be in accordance with FC 5003.11.3.1 through 5003.11.3.10.
5003.11.3.1 Density.
Storage and display of solids shall not exceed 200 pounds per square foot (976 kg/m 2 ) of floor area actually occupied by solid merchandise. Storage and display of liquids shall not exceed 20 gallons per square foot (815 L/m 2 ) of floor area actually occupied by liquid merchandise.
5003.11.3.2 Storage and display height.
Display height shall not exceed 6 feet (1829 mm) above the finished floor in display areas of Group M occupancies. Storage height shall not exceed 8 feet (2438 mm) above the finished floor in storage areas of Group M and Group S occupancies.
5003.11.3.3 Container location.
Individual containers less than 5 gallons (19 L) or less than 25 pounds (11 kg) shall be stored or displayed on pallets, racks or shelves.
5003.11.3.4 Racks and shelves.
Racks and shelves used for storage or display shall be in accordance with FC 5003.9.9.
5003.11.3.5 Container type.
Containers shall be approved for the intended use and identified as to their content.
5003.11.3.6 Container size.
Individual containers shall not exceed 100 pounds (45 kg) for solids or 10 gallons (38 L) for liquids in storage and display areas.
5003.11.3.7 Incompatible materials.
Incompatible materials shall be separated in accordance with FC 5003.9.8.
5003.11.3.8 Floors.
Floors shall be in accordance with FC 5004.12.
5003.11.3.9 Aisles.
Aisles 4 feet (1219 mm) in width shall be maintained on three sides of the storage or display area.
5003.11.3.10 Signs.
Hazard identification signs shall be provided in accordance with FC 5003.5.
5003.12 Outdoor control areas.
Outdoor control areas for hazardous materials in amounts not exceeding the maximum allowable quantity per outdoor control area shall be in compliance with the following requirements:
1. Outdoor control area shall be kept free from vegetation, rubbish and other combustible waste, and combustible materials not necessary to the storage. The area surrounding an outdoor control area shall be kept clear of such materials for a minimum of 15 feet (4572 mm).
2. Outdoor control areas shall be located at least 5 feet (1524 mm) from a building opening and at least 15 feet (4572 mm) from Group A occupancies. Outdoor control areas shall be located at least 20 feet (6096 mm) from a lot line, public street or private road.
Exception: A 2-hour fire-resistance-rated wall without openings extending not less than 30 inches (762 mm) above and to the sides of the storage area is allowed in lieu of such distances required from a building opening, lot line, public street or private road.
3. Where a property exceeds 10,000 square feet (929 m 2 ), there may be two outdoor control areas separated by a minimum distance of 50 feet (15 240 mm), when approved.
4. Where a property exceeds 35,000 square feet (3252 m 2 ), there may be multiple outdoor control areas, separated a minimum distance of 50 feet (15 240 mm), when approved.