Section FC 2306. Design and Installation Requirements for Liquid Motor Fuel-Dispensing Facilities

Open this section

2306.1 General.

Liquid motor fuel storage and dispensing systems shall be designed and installed in accordance with FC Chapter 57 except as otherwise specified in this chapter, including the requirements of this section.

2306.2 Method of storage.

Approved methods of storage for liquid motor fuel at motor fuel-dispensing facilities shall be in accordance with FC 2306.2.1 through 2306.2.4.

2306.2.1 Underground tanks.

The installation of underground tanks for the storage of liquid motor fuel shall comply with the requirements of FC Chapter 57 except as otherwise specified in this chapter.

2306.2.1.1 Inventory control for underground tanks.

Accurate daily inventory records shall be maintained and reconciled for underground liquid motor fuel storage tanks for indication of possible leakage from tanks and piping. Inventory reconciliation shall be in accordance with the regulations of the New York State Department of Environmental Conservation as set forth in 6 NYCRR Part 613. The records shall be maintained in accordance with FC 107.7. Records shall include daily reconciliation between sales, use, receipts and inventory on hand. Where there is more than one system consisting of tanks serving separate pumps or dispensers for a product, the reconciliation shall be maintained separately for each tank system. A consistent or accidental loss of product shall be immediately reported to the commissioner.

2306.2.1.2 Listing and approval.

Underground liquid motor fuel storage tanks shall be listed and approved.

2306.2.1.3 Tank design and construction.

Underground liquid motor fuel storage tanks shall be designed and constructed in accordance with the following:

1. Tanks shall be completely double-walled and constructed of steel, fiberglass-reinforced plastic or a combination of both materials. The secondary tank shall be capable of containing any leakage from the primary tank.

2. Tanks shall be designed and constructed to withstand one and one-half times the maximum operating loads and stresses, regardless of the amount of liquid motor fuel contained in the tank. Such capabilities shall be established by buoyancy calculations and load and stress analyses.

3. Tanks shall be designed and constructed to withstand a pressure of 15 pounds per square inch gauge (psig) (103.4 kPa) or one and one-half times the maximum anticipated static head pressure, whichever is greater, for the primary tank and 5 pounds per square inch gauge (psig) (34.5 kPa) for the secondary tank.

4. The capacity of each individual tank shall not exceed 12,000 gallons (45 420 L) of liquid motor fuel.

2306.2.1.4 Tank connections.

Tank connections shall be designed and located so as to:

1. Minimize the maneuvering necessary to position a cargo tank to make the delivery.

2. Minimize any obstructions of a public right of way or motorists' view of roadways, or any impediment to the movement of motor vehicles or pedestrians, during delivery.

3. Provide connections by means of approved liquid- and vapor-tight connections.

4. Comply with the requirements of FC 2305.1.3.

2306.2.1.5 Liquid level-indicating devices.

Tanks shall be provided with an approved liquid level-indicating device. The quantity of fuel in the tank as indicated on the liquid level-indicating device shall be accessible to the delivery operator. Liquid level-indicating devices shall be designed, constructed and installed to be vapor- and liquid-tight.

2306.2.1.6 Tank overfill alarm.

Tanks shall be provided with an approved overfill alarm designed to activate a local audible and visual alarm in an area supervised by the cargo tank delivery operator. Such alarms shall activate when the quantity of fuel in the tank exceeds a designated level, which shall not be more than 95 percent of capacity.

2306.2.2 Prohibited aboveground storage.

The storage of motor fuel in aboveground tanks shall be prohibited as set forth in FC 2306.2.2.1, 2306.2.2.2 and 2306.2.2.3.

2306.2.2.1 Storage of flammable liquid motor fuel.

It shall be unlawful to store flammable liquid motor fuel in aboveground tanks.

2306.2.2.2 Storage of combustible liquid motor fuel.

It shall be unlawful to store combustible liquid motor fuel in aboveground tanks, except outdoors at a fleet motor fuel-dispensing facility complying with the requirements of this chapter.

2306.2.2.3 Indoor storage.

It shall be unlawful to store liquid motor fuel in aboveground tanks indoors.

2306.2.3 Aboveground tanks located outdoors, at grade.

Outdoor storage of combustible liquid motor fuel in aboveground tanks at a fleet motor fuel-dispensing facility shall comply with the requirements set forth in FC 2306.2.3.1 through 2306.2.3.6.

2306.2.3.1 Tank design and construction.

Only protected aboveground tanks shall be used.

2306.2.3.2 Tank capacity.

The capacity of each tank shall not exceed 10,000 gallons (37 850 L). Not more than a total of 10,000 gallons (37 850 L) of liquid motor fuel shall be stored aboveground at any facility. The total storage capacity at a facility in both aboveground and underground tanks shall not exceed 40,000 gallons (15 140 L) of liquid motor fuel. Each tank shall have a separate fill line and a separate vent line that are separate from the fill and vent lines of other tanks.

Exception: When approved, individual tanks may exceed 10,000 gallons (37 850 L) but shall not exceed 12,000 gallons (45 420 L).

2306.2.3.3 Tank base support.

Tanks shall be placed on an approved base slab. The surface of such base slab shall be a minimum of 6 inches (152 mm) above the level of the surrounding area to permit visual inspection. Tanks shall be adequately supported and anchored to the base slab to withstand uplifting by surface water and flooding.

2306.2.3.4 Tank connections.

Tank connections shall be designed and located in accordance with FC 2306.2.1.4.

2306.2.3.5 Liquid level-indicating devices.

Tanks shall be provided with an approved liquid level-indicating device in accordance with FC 2306.2.1.5.

2306.2.3.6 Tank overfill alarm.

Tanks shall be provided with an approved overfill alarm in accordance with FC 2306.2.1.6.

2306.2.4 Location requirements for aboveground tanks at fleet motor fuel-dispensing facilities.

Tanks shall be located in accordance with FC Table 2306.2.4 and as follows:

1. A minimum of 25 feet (7620 mm) from a subway grating, entrance or exit.

2. At a location that will not obstruct or interfere with any means of egress or department access.

3. Tanks shall not be installed under electrical transmission lines, bridges, or public highways.

FC Table 2306.2.4 Minimum Separation Requirements for Aboveground Tanks at Fleet Motor Fuel-Dispensing Facilities

Class of Liquid and Tank Type Individual Tank Capacity (gallons) Minimum Distance from Nearest Building (feet) Minimum Distance from Lot Line (feet) Minimum Distance from Public Street or Private Road (feet) Minimum Distance Between Tanks (feet) Liquid motor fuel tanks 4000 Greater than 4000 15 25 15 25 15 15 3 3

For SI: 1 foot = 304.8 mm, 1 gallon = 3.785 L.

2306.3 Security.

Aboveground tanks for the storage of liquid motor fuel shall be safeguarded in an approved manner from public access or unauthorized entry.

2306.4 Physical protection.

Posts complying with the requirements of FC 312 or other approved means shall be provided to protect aboveground tanks against impact by a motor vehicle unless the tank is listed as a protected aboveground tank with vehicle impact protection.

2306.5 Secondary containment.

Aboveground tanks shall be provided with diking in accordance with FC Chapter 57. Diking is not required for listed secondary containment tanks. The secondary containment systems shall be monitored either visually or automatically. Enclosed secondary containment systems shall be provided with emergency venting in accordance with FC 2306.6.2.5.

2306.6 Piping, valves, fittings and ancillary equipment for use with liquid motor fuel.

The design, fabrication, assembly, testing and inspection of piping, valves, fittings and ancillary equipment for use with liquid motor fuel shall be in accordance with FC Chapter 57 except as otherwise specified in FC 2306.6.1 through 2306.6.3, and FC 2306.9 and 2306.10.

2306.6.1 Protection from damage.

Piping shall be located such that it is protected from physical damage and designed to accommodate settlement, vibration, expansion or contraction.

2306.6.2 Piping, valves, fittings and ancillary equipment for aboveground tanks.

Piping, valves, fittings and ancillary equipment for aboveground tanks shall comply with the requirements of FC 2306.6.2.1 through 2306.6.2.11.

2306.6.2.1 Tank openings.

Tank openings for aboveground tanks shall be through the top only. There shall be no openings except those necessary to inspect, fill, empty and vent the tank.

2306.6.2.2 Fill-pipe connections.

The fill-pipe for aboveground tanks shall be provided with a means for making a direct connection to the cargo tank's fuel-delivery hose so that liquid motor fuel is not exposed to the open air during the filling operation. Operator safety equipment for the filling operation shall be provided in accordance with OSHA regulations. Where any portion of the fill-pipe exterior to the tank extends below the level of the top of the tank, a check valve, a dry break coupling and a quick closing valve shall be installed at the fill connection. Tank fill connections from a remote location are prohibited.

2306.6.2.3 Overfill protection.

Overfill protection shall be provided for aboveground storage tanks. Overfill prevention devices shall be designed to withstand the pressure generated by the cargo tank discharge pump and shall automatically shut off the flow into the tank when the tank is not more than 95 percent full.

2306.6.2.4 Siphon prevention.

An approved antisiphon method shall be provided in the piping system to prevent flow of liquid motor fuel by siphon action.

2306.6.2.5 Emergency relief venting.

Aboveground storage tanks, tank compartments and enclosed secondary containment spaces shall be provided with emergency relief venting in accordance with FC Chapter 57.

2306.6.2.6 Spill containers.

Aboveground tank spill containers having a capacity of not less than 5 gallons (19 L) shall be provided for each fill connection. Spill containers shall be noncombustible and shall be fixed to the tank and equipped with a manual drain valve that drains into the primary tank.

2306.6.2.7 Piping material construction.

Piping shall be of a minimum Schedule 40 steel construction.

2306.6.2.8 Compatibility.

Piping, fittings, components and joint compounds shall be mutually compatible, and compatible with diesel fuel and other commonly-used combustible liquid motor fuels, including the additives commonly used in such combustible motor fuels. Joint compounds shall be listed and approved.

2306.6.2.9 Pressure relief devices.

Where liquid motor fuel may become trapped between shutoff valves and/or check valves, affected piping sections shall be provided with pressure-relief devices that will discharge the pressure generated by thermal expansion back into the tank.

2306.6.2.10 Vent piping.

Each tank shall be provided with a separate unobstructed vent line, without any trap or device that causes excessive back pressure, and shall be maintained unobstructed at all times.

2306.6.2.11 Vent termination.

Vent outlets shall discharge outdoors and upward. The discharge point shall be no less than 15 feet (4572 mm) above the adjacent ground level and no less than 10 feet (3048 mm) from the nearest building opening.

2306.6.3 Piping, valves, fittings and ancillary equipment for underground tanks.

Piping, valves, fittings and ancillary equipment for underground tanks shall comply with the requirements of FC Chapter 57 and NFPA 30A, except as otherwise provided in FC 2306.6.3.1, 2306.6.3.2 and 2306.10.

2306.6.3.1 Piping design and construction.

Piping, including vent piping, shall be of a minimum Schedule 40 steel construction. Approved nonmetallic piping, such as fiberglass-reinforced plastic or other equivalent corrosion-resistant material, may be installed underground.

2306.6.3.2 Underground tank piping.

Piping shall be installed underground, except for the vertical riser of the vent.

2306.6.3.3 Compatibility.

Piping, fittings, components and joint compounds shall be mutually compatible, and compatible with gasoline, diesel fuel, methanol and other commonly-used liquid motor fuels, including the additives commonly used in such liquid motor fuels. Joint compounds shall be listed and approved.

2306.7 Fuel-dispensing systems for liquid motor fuel.

The design and installation of liquid motor fuel-dispensing systems shall be in accordance with FC 2306.7.1 through 2306.7.9.2.4. Alcohol-blended motor fuel-dispensing systems shall additionally comply with FC 2306.7.10.

2306.7.1 Listed equipment.

Electrical equipment, dispensers, hose, nozzles and submersible or subsurface pumps used in liquid motor fuel storage and dispensing systems shall be listed and approved.

2306.7.2 Fixed pumps required.

Liquid motor fuel shall be transferred only from the top of the tank by means of fixed pumps designed and equipped to allow control of the flow and prevent leakage or accidental discharge.

2306.7.2.1 Aboveground tank dispenser.

Only one vehicle may be fueled at a time. Fuel dispensing from a location remote from the tank may be allowed when approved by the commissioner.

2306.7.2.2 Pump sumps.

Pump sumps shall be compatible with the liquid motor fuel, liquid-tight, and accessible for inspection. Prefabricated pump sumps shall be approved.

2306.7.3 Mounting of dispensers.

Dispensing devices, except those installed on top of a protected aboveground tank that qualifies as vehicle-impact resistant, shall be protected against physical damage by mounting on a concrete island 6 inches (152 mm) or more in height, or shall otherwise be suitably protected in accordance with FC 312. Dispensing devices shall be installed and securely fastened to their mounting surface in accordance with the dispenser manufacturer's instructions. Dispensing devices installed indoors shall be located in an approved position not in a direct line with vehicular traffic.

2306.7.3.1 Protection of floor openings in indoor facilities.

Openings in floors beneath liquid motor fuel-dispensing facilities located indoors shall be sealed.

2306.7.3.2 Dispenser pans.

An approved dispenser pan that is compatible with the liquid motor fuel shall be installed beneath a dispenser. The dispenser pan shall be liquid-tight, accessible for inspection, no larger than necessary, and installed solely for the purpose of collecting any liquid motor fuel leaking from the dispenser. The dispenser pan shall not be used to collect liquid motor fuel discharged from defective piping. The dispenser pan shall be backfilled up to not less than 6 inches (152 mm) above any nonmetallic piping and shall not interfere with the operation of any safety device.

2306.7.4 Dispenser emergency valve.

An approved automatic emergency shutoff valve designed to close in the event of a fire or impact shall be properly installed in the liquid supply line at the base of each dispenser supplied by a remote pump. The valve shall be installed so that the shear groove is flush with or within 1/2 inch (12.7 mm) of the top of the concrete dispenser island and there is clearance provided for maintenance purposes around the valve body and operating parts. The valve shall be installed at the liquid supply line inlet of each overhead-type dispenser. Where installed, a vapor return line located inside the dispenser housing shall have a shear section or approved flexible connector for the liquid supply line emergency shutoff valve to function. Emergency shutoff valves shall be installed and maintained in accordance with the manufacturer's instructions, tested at the time of initial installation and tested at least yearly thereafter in accordance with FC 2305.2.2.

2306.7.5 Dispenser hose.

Dispenser hoses shall be a maximum of 18 feet (5486 mm) in length unless otherwise approved. Dispenser hoses shall be listed and approved. When not in use, hoses shall be reeled, racked or otherwise protected from damage. The length of the dispensing hose shall be such that at least 1 inch (25 mm) clearance between the hose and the ground is maintained when the nozzle is rested on its bracket. Dispensing hoses installed at aviation facilities, marine liquid motor fuel-dispensing facilities, and fleet liquid motor fuel-dispensing facilities shall be of an approved length.

2306.7.5.1 Breakaway devices.

Dispenser hoses shall be equipped with a listed emergency breakaway device designed to retain liquid on both sides of a breakaway point. Such devices shall be installed and maintained in accordance with the manufacturer's instructions. Where hoses are attached to hose-retrieving mechanisms, the emergency breakaway device shall be located between the hose nozzle and the point of attachment of the hose-retrieval mechanism to the hose.

2306.7.6 Fuel delivery nozzles.

A listed automatic-closing-type hose nozzle valve without a latch-open device shall be provided for dispensers used for dispensing liquid motor fuel, except that a nozzle valve with a latch-open device may be installed and used at the following automotive liquid motor fuel-dispensing facilities:

1. Full-service automotive liquid motor fuel-dispensing facilities.

2. Fleet automotive liquid motor fuel-dispensing facilities.

3. Dispensing of diesel fuel at self-service automotive liquid motor fuel-dispensing facilities.

2306.7.6.1 Special requirements for nozzles.

Where dispensing of liquid motor fuel is performed, a listed automatic-closing-type hose nozzle valve shall be used that incorporates all of the following features:

1. When the flow of product is normally controlled by devices or equipment other than the hose nozzle valve, the hose nozzle valve shall not be capable of being opened unless the delivery hose is pressurized. If pressure to the hose is lost, the nozzle shall close automatically.

Exception: Vapor recovery nozzles incorporating insertion interlock devices designed to achieve shutoff on disconnect from the vehicle fill pipe.

2. The hose nozzle shall be designed such that the nozzle is retained in the fill pipe during the filling operation.

3. The system shall include listed equipment with a feature that causes or requires the closing of the hose nozzle valve before the product flow can be resumed or before the hose nozzle valve can be replaced in its normal position in the dispenser.

2306.7.6.2 Control device.

A control device shall be provided that will allow a liquid motor fuel pump to operate only when the dispensing nozzle is removed from its bracket on the dispenser and the switch on the dispenser is manually activated. The flow of liquid motor fuel shall automatically stop when the switch is deactivated or the nozzle returned to its bracket.

2306.7.7 Leak detection.

Underground liquid motor fuel storage and dispensing systems shall be provided with a leak detection system in accordance with the following:

1. The leak detection system shall provide continuous monitoring of the tank's interstitial space.

2. The leak detection system shall provide continuous monitoring of liquid motor fuel pump sumps. Activation of the leak detection system shall cause shutdown of the liquid motor fuel pumps.

3. The leak detection system shall provide continuous monitoring of dispenser pans. Activation of the leak detection system shall cause shutdown of the affected dispenser or liquid motor fuel pump supplying such dispenser.

4. Primary discharge piping shall be provided with an automatic line leak detector. Activation of such leak detector shall cause shutdown of the liquid motor fuel pump or significantly restrict the product flow.

5. The leak detection system shall have an alarm panel in a supervised location on the premises; trigger both an audible and visible local alarm; be capable of producing hardcopy printouts of all tests and/or leak notification reports; operate on low voltage; and be intrinsically safe for a liquid motor fuel environment.

6. Leak detection systems shall be listed and approved.

2306.7.8 Gravity and pressure dispensing.

Liquid motor fuel shall not be dispensed by gravity from tanks, drums, barrels or similar containers. Liquid motor fuel shall not be dispensed by a device operating through pressure within a storage tank, drum or container.

2306.7.9 Vapor-recovery and vapor-processing systems.

Stage I vapor-recovery and vapor-processing systems, when required by the New York State Department of Environmental Conservation, shall be installed in accordance with FC 2306.7.9 and the regulations of the New York State Department of Environmental Conservation, and shall be approved.

2306.7.9.1 Vapor-balance systems.

Vapor-balance systems shall comply with the requirements of FC 2306.7.9.1.1 through 2306.7.9.1.5.

2306.7.9.1.1 Dispensing devices.

Dispensing devices incorporating provisions for vapor recovery shall be listed and labeled. When existing listed or labeled dispensing devices are modified for vapor recovery, such modifications shall be listed by report by a nationally recognized testing laboratory. The listing by report shall contain a description of the component parts used in the modification and the recommended method of installation on specific dispensers. Such report shall be made available for inspection by any department representative. Means shall be provided to shut down fuel dispensing in the event the vapor return line becomes blocked.

2306.7.9.1.2 Vapor-return line closeoff.

An approved method shall be provided to close off the vapor return line from dispensers when the product is not being dispensed.

2306.7.9.1.3 Piping.

Piping in vapor-balance systems shall be in accordance with FC 5703.6 and 5704.2. Nonmetallic piping shall be installed in accordance with the manufacturer's installation instructions. Vapor return piping shall be installed in a manner that drains back to the tank, without sags or traps in which liquid can become trapped. If necessary, because of grade, condensate tanks are allowed in vapor return piping. Condensate tanks shall be designed and installed so that they can be drained without opening.

2306.7.9.1.3.1 Removal of piping.

The owner shall be responsible for notifying the department, in writing, upon decommissioning of the piping in vapor-balance system. Such notification shall include the location of the facility and the name, address and telephone number of the contractor who performed the removal.

2306.7.9.1.4 Flexible joints and shear joints.

Flexible joints shall be installed in accordance with FC 5703.6.9. An approved shear joint shall be rigidly mounted and connected by a union in the vapor return piping at the base of each dispensing device. The shear joint shall be mounted flush with the top of the surface on which the dispenser is mounted.

2306.7.9.1.5 Testing.

Vapor return lines and vent piping shall be tested in accordance with FC 2306.9.

2306.7.9.2 Vapor-processing systems.

Vapor-processing systems shall comply with the requirements of FC 2306.7.9.2.1 through 2306.7.9.2.4.

2306.7.9.2.1 Equipment.

Equipment in vapor-processing systems, including hose nozzle valves, vapor pumps, flame arresters, fire checks or systems for prevention of flame propagation, controls and vapor-processing equipment, shall be individually listed for the intended use in a specified manner. Vapor-processing systems that introduce air into the underground piping or storage tanks shall be provided with equipment for prevention of flame propagation that has been tested and listed as suitable for the intended use.

2306.7.9.2.2 Location.

Vapor-processing equipment shall be located at or above grade. Sources of ignition shall be located not less than 50 feet (15 240 mm) from fuel-transfer areas and not less than 18 inches (457 mm) above tank fill openings and tops of dispenser islands. Vapor-processing units shall be located not less than 10 feet (3048 mm) from the nearest building or structure or lot line.

Exception: Where the required distances to buildings or structures, lot lines or fuel-transfer areas cannot be obtained, means shall be provided to protect equipment against fire exposure. Acceptable means shall include:

1. Approved protective enclosures, which extend at least 18 inches (457 mm) above the equipment, constructed of fire-resistant or noncombustible materials; and

2. Fire protection using an approved water-spray system.

2306.7.9.2.2.1 Location and safeguards.

Vapor-processing equipment shall be located a minimum of 20 feet (6096 mm) from dispensing devices. Processing equipment shall be protected against physical damage by guardrails, curbs, protective enclosures or fencing. Where approved protective enclosures are used, approved means shall be provided to ventilate the volume within the enclosure to prevent pocketing of flammable vapors. Where a downslope exists toward the location of the vapor-processing unit from a fuel-transfer area, the commissioner may require additional separation by distance and height.

2306.7.9.2.3 Installation.

Vapor-processing units shall be securely mounted on concrete, masonry or structural steel supports on concrete or other noncombustible foundations. Vapor-recovery and vapor-processing equipment is allowed to be installed on roofs when approved.

2306.7.9.2.4 Piping.

Piping in a mechanical-assist system shall be in accordance with FC 5703.6.

2306.7.10 Alcohol-blended motor fuel-dispensing equipment.

Dispensers, hoses, nozzles, breakaway fittings, swivels, flexible connectors, dispenser emergency shutoff valves, vapor recovery systems and pumps used in alcohol-blended motor fuel storage and dispensing systems shall be compatible with such fuels and shall be listed or approved for such purpose.

2306.8 Fire extinguishing system for dispensing area.

Where flammable liquid motor fuel is dispensed at an automotive liquid motor fuel-dispensing facility, the dispensing area shall be provided with a dry chemical fire extinguishing system designed and installed in accordance with FC 904.6, and the following requirements:

1. The fire extinguishing system shall be designed to provide overhead protection of the dispenser area encompassed by a circle formed by the fully extended hose and nozzle on each fuel dispenser and both ends of the dispenser island.

2. The extinguishing agent containers shall be equipped with indicators to show whether the system is fully charged. Indicators shall be positioned to be easily read from grade.

3. The installation, alteration, testing and repair of the fire extinguishing system, including any maintenance or modification of the system, shall be performed by a person possessing a master fire suppression piping contractor license issued by the Department of Buildings and trained and knowledgeable in the installation, operation and maintenance of the specific fire extinguishing system.

4. Dispensers shall not be operated when the fire extinguishing system has discharged or is inoperative, except as authorized in writing by the department. The motor fuel-dispensing facility certified attendant shall immediately notify the department of system discharge or inoperability.

5. Fire extinguishing systems shall be inspected and tested in accordance with FC 2306.9.

6. Fire extinguishing systems at fleet automotive liquid motor fuel-dispensing facilities shall be monitored by an approved central station company.

2306.9 Inspection and testing.

Inspection and testing required by FC 2306.9.1 through 2306.9.7 shall be conducted at the owner's risk by his or her representative before a representative of the department.

2306.9.1 Initial tank test.

Underground and aboveground tanks shall be tested hydrostatically at 15 pounds per square inch (psig) (103.4 kPa), or one and one-half times the maximum anticipated static head pressure, whichever is greater, for the inner tank, and pneumatically or hydrostatically at 5 pounds per square inch (psig) (34.5 kPa) for the annular space (secondary containment tank). When a pneumatic test is allowed, an inert gas shall be used; however, air may be used if the tank or piping system does not contain any liquid motor fuel or combustible vapor. Test pressure shall be maintained for a sufficient time to complete visual inspection, but not less than 1 hour. A tank shall be deemed to have passed the test if it shows no evidence of leakage or permanent deformation.

2306.9.2 Initial piping test.

Prior to backfill, primary piping shall be tested hydrostatically to one and one-half times the maximum anticipated operating pressure, but not less than 15 pounds per square inch (psig) (103.4 kPa). After backfill and installation of the top slab, discharge piping shall be tested hydrostatically at one and one-half times the maximum anticipated pressure, but not less than 50 pounds per square inch (psig) (345 kPa). Secondary containment piping (annular space) shall be tested pneumatically at 5 pounds per square inch (psig) (34.5 kPa) utilizing an inert gas; however, air may be used if the tank system or piping system does not contain any liquid motor fuel or combustible vapor. Hydrostatic test pressure shall be maintained for sufficient time to complete visual inspection but not less than 1 hour. The test shall show that there is no evidence of leakage. Test pressure for aboveground tank piping shall be at one and one-half times the maximum anticipated operating pressure but not less than 100 pounds per square inch (psig) (690 kPa).

2306.9.3 Leak detection functionality test.

Leak detection systems shall be inspected and tested at the time of installation in accordance with the rules. Leak detection systems monitoring liquid motor fuel storage systems shall be tested at least once every 2 years by a person holding a certificate of license. Such test shall confirm that all leak detection equipment and associated alarms are in good working order.

2306.9.4 Fire extinguishing system test.

A performance test of the fire extinguishing system shall be performed at the time of installation in accordance with the approved design and installation documents, and such procedures as may be prescribed by the commissioner. Fire extinguishing systems shall be tested at least once every 5 years. The test shall be in accordance with procedures prescribed by the commissioner.

2306.9.5 Emergency tank and piping system test.

The commissioner may require that a tank and piping system be precision tested or pressure tested in accordance with this section to determine the condition of the tank or piping. Storage systems that may contain liquid motor fuel or combustible vapor shall not be tested pneumatically.

2306.9.6 Periodic tank and piping test.

Any existing underground single-walled liquid motor fuel storage tank previously approved by the department or any existing underground tank that is not provided with a leak detection system meeting the requirements of FC 2306.7.7 shall be precision tested at least once every 5 years.

2306.9.7 Pouring concrete and backfilling.

The pouring of concrete for the base and top slab, the backfilling of tank and piping, and the construction of the top slab support shall be witnessed by a representative of the department at time of installation.

2306.10 Installation of underground tank and piping systems.

The installation of tank and piping systems shall be in accordance with FC Chapter 57, except as otherwise specified in this section.

1. Tanks shall be located so that the forces from building foundations and support loads are not transmitted to the tanks. The distance from any part of a tank to the nearest wall of any basement, pit, cellar or any property line shall not be less than 3 feet (914 mm). Tanks shall not be placed less than 20 feet (6096 mm) from a subway wall.

2. Tanks shall be installed so that the highest point of the tank is not less than 2 feet (609.6 mm) below the level of the lowest cellar floor of any building within a radius of 10 feet (3048 mm) from the tank. No tank shall be located under a sidewalk or beyond the property line of the liquid motor fuel-dispensing faility.

3. Tanks shall be placed on a 12-inch (305-mm) thick base slab approved by the Department of Buildings, or installed in such other manner as may be approved by the Commissioner of Buildings, and secured against flotation. The system used for anchoring the tank shall not damage the tank or its coating.

4. Tanks shall be placed on a bed of approved backfill material in accordance with manufacturer's specifications. The backfill material shall evenly and completely support the bottom quadrant of the tank. The backfill material shall be carefully placed along the bottom, under the sides and under the end caps or heads of the tank, by shoveling and tamping. Backfilling shall then be completed in 12-inch (305-mm) lifts placed uniformly around the tank. Provision shall be made, consistent with site conditions, to prevent the migration of backfill.

5. Tanks shall be covered with a reinforced concrete slab not less than 8 inches (203 mm) thick, which shall extend not less than 12 inches (305 mm) beyond the horizontal outlines of the tank. The support of the top slab shall be of a design approved by the Department of Buildings.

6. Fill, suction and discharge piping shall be encased in 4 inches (102 mm) of concrete or covered by a minimum of 18 inches (457 mm) of manufacturer-approved backfill, or covered by 4 inches (102 mm) of manufacturer-approved backfill and an 8-inch (203-mm) reinforced concrete slab.

7. Not more than 40,000 gallons (151 400 L) of liquid motor fuel shall be stored at any facility, including liquid motor fuel stored in aboveground tanks.

8. Tanks containing identical products may be wet-manifolded provided that the total aggregate capacity of such tanks does not exceed 12,000 gallons (45 420 L) of liquid motor fuel, and each tank is provided with its own submersible pump.

9. Tank connections shall be designed and located so as to:

9.1. Minimize the maneuvering necessary to position a cargo tank to make the delivery.

9.2. Minimize obstructing a public right of way or motorists' view of roadways, or impeding the movement of motor vehicles or pedestrians, during deliveries.

9.3. Provide connections by means of approved liquid- and vapor-tight connections.

10. Tanks installed underground indoors shall be provided with an approved liquid level-indicating device. Liquid level-indicating devices shall be designed and constructed to prevent the escape of liquid or vapor and shall be approved.

11. Test wells shall be prohibited in tanks located underground indoors. Unused tank openings shall be permanently sealed at the tank to prevent removal of plugs or covers.

12. Secondary containment piping shall be required on all nonmetallic product-carrying pipes except direct fill lines, suction lines or siphon lines containing only one check valve located at the highest point of the line.

13. Underground piping shall have a slope of not less than 1/8 inch per foot (10.4 mm per meter) pitched toward the tank and shall be installed so as to facilitate initial and periodic testing.

14. Flexible joints shall be installed in accordance with FC 5703.6.9.

15. Each underground motor fuel storage tank shall be provided with a separate unobstructed vent line without any trap or device that causes excessive back pressure.

16. Vent piping shall be installed not less than 12 inches (305 mm) below the finished surface measured from the point where the piping rises vertically and shall slope toward the tank.

17. Vent outlets shall discharge outdoors and upward. The discharge point shall be no less than 15 feet (4572 mm) above the adjacent ground level and no less than 10 feet (3048 mm) from the nearest building opening.

18. An approved overfill prevention device shall be provided to prevent overfilling. When installed in diesel fuel tanks, such overfill prevention device shall be designed to withstand the pressure generated by the cargo tank discharge pump and shall automatically shut off the flow into the tank when the tank is not more than 95 percent full.

19. Each tank shall be provided with one fill connection only, unless approved. Each tank fill connection shall be provided with a catchment basin with a capacity of at least 15 gallons (56.8 L). The contents of the catchment basin shall be automatically drained into the tank without overfilling the tank after the transfer from the cargo tank is completed provided, however, that if the Stage II vapor recovery system approved for the tank does not allow for the installation of an automatic drain, a manual drain may be installed.

20. Where the discharging piping leak detector required by FC 2306.7.7(4) does not cause shutdown of the liquid motor fuel pump, secondary containment piping shall be provided.

2306.11 Spill control.

Provision shall be made to prevent liquids spilled during dispensing operations from flowing into buildings, by grading driveways, raising doorsills or other approved means.

Section FC 2307. Design and Installation Requirements for Biodiesel Motor Fuel

Open this section

2307.1 General.

Biodiesel motor fuel shall be stored and dispensed in motor fuel storage and dispensing systems designed and installed in accordance with this section.

2307.2 Biofuel content.

The amount of biofuel content in biodiesel motor fuel shall not exceed 20 percent, except as authorized by the department.

2307.3 Aboveground storage.

Biodiesel motor fuel may be stored and dispensed in protected aboveground tanks in accordance with FC 2306.2.3.1.

2307.4 Design and installation.

The design of motor fuel storage and dispensing systems used for biodiesel motor fuel shall be in accordance with FC Chapter 23.

2307.5 Change of tank contents.

Any motor fuel storage and dispensing system that is to be used for biodiesel, which was previously used for other types of motor fuel, shall comply with the requirements of FC 5704.2.1.

Section FC 2308. Compressed Natural Gas Motor Fuel-Dispensing Facilities

Open this section

2308.1 General.

CNG motor fuel-dispensing facilities shall be designed, installed, operated and maintained in accordance with NFPA 52 except as otherwise specified in this section and FC 2301.

2308.1.1 Prohibitions.

It shall be unlawful to:

1. Operate a self-service marine CNG motor fuel-dispensing facility.

2. Fill a portable container, other than permanently mounted fuel containers on CNG-powered vehicles, except outdoors at a utility-operated facility.

2308.1.2 Supervision of dispensing operations.

The dispensing of CNG at CNG motor fuel-dispensing facilities shall be supervised by a certified attendant as set forth in FC 2301.7.

2308.1.3 Maintenance.

Maintenance of CNG motor fuel-dispensing systems shall be conducted under the personal supervision of a person holding a CNG fueling facility maintenance certificate of fitness.

2308.1.4 Lighting.

Dispensing areas shall be well lighted whenever dispensing is being conducted.

2308.1.5 Dispensing area signage.

Durable signs shall be conspicuously posted in dispensing areas in CNG motor fuel-dispensing facilities in compliance with the requirements of FC 2308.1.5.1 through 2308.1.5.3.

2308.1.5.1 Operating instructions.

A sign setting forth dispenser operating instructions shall be posted on every dispenser. Such sign shall also indicate the location of the emergency shutdown switches required by FC 2308.7.

2308.1.5.2 CNG dispensing warning sign.

A warning sign that reads as follows shall be posted on or immediately adjacent to each dispenser:

1. No smoking.

2. Shut off engine.

2308.1.5.3 Emergency procedures.

A sign setting forth emergency procedures that reads as follows shall be posted in the dispensing area, or other location designated in this section:

IN CASE OF FIRE, LEAK OR EMERGENCY: ACTIVATE EMERGENCY CNG SHUTDOWN DIRECT VEHICLE OCCUPANTS TO EXIT VEHICLES AND LEAVE AREA IMMEDIATELY KEEP ALL PERSONS AWAY FROM THE AREA. NOTIFY THE FIRE DEPARTMENT (CALL 911) (FACILITY ADDRESS) (indicate address, with cross-street reference ).

2308.1.6 Emergency telephone.

A telephone not requiring a coin to operate or another approved, clearly identified means to notify the department, shall be provided at the facility in an approved location.

2308.1.7 Electrical equipment.

Electrical wiring and equipment shall be suitable for the location in which they are installed and shall be in accordance with FC 605, NFPA 52 and the Electrical Code.

2308.1.8 Audible and visible alarms.

All audible and visible alarms required by this section shall actuate at a supervised location on the premises that assures immediate response.

2308.1.9 Smoking and open flames.

It shall be unlawful to smoke or use or maintain an open flame in any area where CNG motor fuel is compressed, stored or dispensed.

Exception: Welding, cutting or similar hot work may be conducted for emergency repair, alteration or installation work, providing that all necessary safety precautions are taken, and all required department permits and authorization from the holder of a certificate of fitness for CNG station maintenance have been obtained.

2308.1.10 Records of incidents.

Records shall be kept of all incidents including fire, leak, device, equipment or system failure, out-of-service fire protection, alarm, or safety system, and of all equipment maintenance. Such records shall be kept in a bound log book or other recordkeeping approved by the department, maintained on the premises for a minimum of 4 years.

2308.1.11 Self-service CNG motor fuel-dispensing facilities.

Self-service CNG motor fuel-dispensing facilities shall be designed, installed, operated and maintained in compliance with the requirements of FC 2308.1.11.1 through 2308.1.11.5.

2308.1.11.1 Duties of certified attendant.

The certified attendant's primary function shall be to supervise, observe and monitor the dispensing of CNG. The certified attendant shall prevent the dispensing of CNG into portable containers, control sources of ignition, take immediate action upon a fire, leak or other emergency and be ready to use a portable fire extinguisher. Nothing in this section shall be construed to prohibit a certified attendant from engaging in activities directly related to the sale of CNG motor fuel, such as the collection of money or processing of credit cards.

2308.1.11.2 Self-service dispensers.

Approved self-service devices, equipment and systems such as, but not limited to, card-operated and remote-preset types, are allowed at CNG motor fuel-dispensing facilities. The certified attendant shall set the dispensing devices in the "off" position when not in use if such dispensing device can be activated without the certified attendant's knowledge.

2308.1.11.3 Monitoring of dispensing.

A control booth shall be located on the premises of every self-service CNG motor fuel-dispensing facility. The control booth shall be an interior or exterior enclosure to which the public has no access. The certified attendant shall be present within the control booth while dispensing operations are conducted. The control booth shall be designed and located so that the certified attendant stationed therein shall have a full, unobstructed clear view of dispensing operations, except that mirrors and/or an approved closed-circuit television installation may be provided to afford the certified attendant a clear view of dispensing operations when the view from the control booth is partially or temporarily obstructed. For purposes of this section, the "clear" view provided by a closed-circuit television installation shall mean that the image on the monitor shall be of such brightness and resolution as to allow ready identification of individuals and easy observation of activities at all times of day. Audible and visible alarms required by this section shall actuate within the control booth. A properly labeled manual switch that activates the emergency shut down device shall be located within the control booth. A console that controls the self-service CNG motor fuel dispensers shall be provided within the control booth and within 5 feet (1524 mm) of the emergency shutdown device manual switch.

2308.1.11.4 Two-way voice communication.

A two-way voice communication system shall be installed to provide contact between the control booth and each dispensing island.

2308.1.11.5 Signage.

The signage required by FC 2308.1.5 shall be posted in the dispensing area of a self-service motor fuel-dispensing facility, except that the emergency procedures sign required by FC 2308.1.5.3 shall be posted in the control booth.

2308.1.12 Fleet CNG motor fuel-dispensing facilities.

Fleet CNG motor fuel-dispensing facilities shall be designed, installed, operated and maintained in compliance with the requirements of FC 2308.1.12.1 through 2308.1.12.3.

2308.1.12.1 Inspection of dispensing areas.

The certified attendant responsible for supervision of the dispensing of CNG at a fleet motor fuel-dispensing facility shall inspect the dispensing area on a periodic basis in accordance with the rules to ensure that the facility is being maintained in accordance with this chapter and the rules. The certified attendant shall notify the owner and make any other notifications required by this code if there is any evidence that the facility is not in good working order. A record of such inspections and notifications shall be maintained at the premises in accordance with FC 107.7.

2308.1.12.2 Duties of fleet personnel.

Employees or other persons working for the owner of a fleet CNG fuel-dispensing facility whose duties involve the dispensing of CNG shall be trained and knowledgeable in such dispensing in compliance with the requirements of this code and the rules.

2308.1.12.3 Quantity limits.

Dispensing equipment used at fleet CNG motor fuel-dispensing facilities shall be programmed or set to limit uninterrupted CNG delivery to an approved amount and require a manual action to resume delivery.

2308.1.13 Full-service CNG motor fuel-dispensing facilities.

Full-service CNG motor fuel-dispensing facilities shall be operated and maintained in compliance with the requirements of FC 2308.1.13.1.

2308.1.13.1 Duties of certified attendant.

The certified attendant at a full-service CNG motor fuel-dispensing facility shall personally supervise the dispensing of motor fuel into vehicles by facility personnel. The certified attendant shall conduct a visual inspection of the dispensing area on a daily basis to monitor the condition of such installation. The certificate of fitness holder shall notify the owner and make any other notifications required by this code if there is any evidence that the installation is not in good working order. A record of such inspections and notifications shall be maintained at the premises in accordance with FC 107.7.

2308.2 Design, installation and testing requirements.

Devices, equipment and systems used for the compression, storage and dispensing of CNG shall be designed, approved, listed and/or tested in accordance with FC 2308.2.1 through 2308.2.7.

2308.2.1 Approved equipment.

Containers, vessels, compressors, pressure regulators, pressure relief valves and other pressure relief devices and piping used for CNG shall be approved.

2308.2.2 Listed equipment.

Hoses, hose connections, dispensers, gas detection systems and electrical equipment used for CNG shall be listed. Vehicle-fueling connections shall be listed and labeled.

2308.2.3 Vehicle fueling hose.

Vehicle fueling hose shall be compatible with CNG and shall withstand a pressure of at least four times the service pressure. Hoses shall be of retractable design and shall be protected against physical damage. Hoses shall be tested for leaks with a noncorrosive solution or equivalent leak detection method at least annually by a certified attendant and shall be replaced if damaged. Records of required inspections and testing shall be kept in a bound log book or other approved recordkeeping, maintained on the premises for a minimum of 4 years.

2308.2.4 Initial container testing.

Prior to placing containers and pressure vessels in CNG service, evidence of container and pressure vessel pressure tests shall be submitted to the department demonstrating compliance with the requirements of NFPA 52.

2308.2.5 Gas piping.

All CNG system gas piping shall be tested by a qualified person in accordance with NFPA 52 at the owner's risk and before a representative of the department prior to placing the system in service. Required tests shall begin at the downstream side of the remote manual shutdown valve.

2308.2.6 Filters and dryers.

Filters and dryers used at CNG motor fuel-dispensing facilities shall be rated for the service and pressure intended and shall be tested in accordance with the gas piping test requirements set forth in FC 2308.2.5.

2308.2.7 Safety devices.

Upon installation, all automatic safety devices intended to cause equipment shutdown shall be tested at the owner's risk by his or her representative before a representative of the department.

2308.3 Location of dispensing operations and equipment.

CNG motor fuel-dispensing facilities shall be located at a site operated by a natural gas utility, or other approved location.

2308.3.1 Location on property.

In addition to the requirements of FC 2303.1 and NFPA 52, compression, storage and dispensing devices, equipment and systems shall be installed as follows:

1. Aboveground, and not beneath power lines.

2. At least 10 feet (3048 mm) from the nearest building, lot line, public street, private road, sidewalk, or source of ignition.

Exception: Dispensing equipment need not be separated from canopies that are constructed in accordance with the construction codes, including the Building Code, and which provide weather protection for the dispensing equipment.

3. At least 25 feet (7620 mm) from the nearest rail of any railroad track and 50 feet (15240 mm) or more from the nearest rail of any railroad main track or any railroad or transit line where power for train propulsion is provided by an outside electrical source such as third rail or overhead catenary.

4. At least 50 feet (15 240 mm) from the vertical plane below the nearest overhead wire of a trolley bus line.

2308.3.2 Rooftop operations.

Rooftop dispensing shall be in accordance with FC 2308.3.2.1 through 2308.3.2.3.

2308.3.2.1 Roof construction.

The roof of the building or structure shall be of noncombustible construction.

2308.3.2.2 Compressor and discharge piping.

The compressor shall be located on the roof and the discharge piping shall not enter the building or structure.

2308.3.2.3 Height.

The building or structure shall be 75 feet (22 860 mm) or less in height.

2308.4 Reserved.

2308.5 Pressure regulators.

Pressure regulators shall be designed and installed or protected so that their operation will not be affected by the elements (freezing rain, sleet, snow or ice), mud or debris. The protection is allowed to be an integral part of the regulator.

2308.6 Manual valves.

Gas supply piping to equipment shall be provided with a remote, readily accessible manual shutoff valve of the fast-closing, quarter-turn type. Manual valves shall be located so as to minimize the risk of physical damage and minimize being rendered inoperable as a result of freezing.

2308.6.1 Location.

Manual valves shall be located within the boundary of the facility and as follows:

1. Not less than 25 feet (7620 mm) from the compressor for compressors rated for 300 standard cubic feet per minute (8.5 m 3 /min) or less.

2. Not less than 75 feet (22 860 mm) from the compressor for compressors rated for greater than 300 standard cubic feet per minute (8.5 m 3 /min).

2308.7 Emergency shutdown switches.

An approved, clearly identified and readily accessible emergency shutdown switch shall be provided at an approved location. The switch, upon activation, shall automatically and immediately shut off the power supply to the compressor and close valves between the gas supply and the compressor and between the storage tanks and the dispensers. Such emergency shutdown switches for outdoor CNG dispensers shall be located within 75 feet (22 860 mm) of, but not less than 25 feet (7620 mm) from, the fuel dispensers. For interior fuel-dispensing operations, such emergency shutdown switches shall be installed at an approved location. An additional automatic emergency shutdown switch shall be provided in the compressor area for both indoor and outdoor compressors. An approved sign shall be posted on or immediately adjacent to such switches and shall read: EMERGENCY CNG SHUTOFF. Such emergency shutdown switch shall be of a type that is manually resettable.

2308.7.1 Compressor shutdown devices.

Each compressor shall be equipped with an automatic shutdown device that will shut down the compressor in the event of low suction pressure, high suction pressure, high motor temperature, high discharge pressure or high discharge temperature.

2308.7.2 Gas detection system.

Indoor compressing, storage and dispensing areas shall be provided with a combustible gas detection alarm system meeting the standards of the construction codes, including the Building Code. Such system shall activate a local audible and visible alarm at 20 percent of the LEL and automatically shut off gas supply at 50 percent of the LEL, with simultaneous transmission of an alarm to the department by an approved central station company. The automatic shutoff valve shall be located upstream from the confined high-pressure piping and shall be installed underground or otherwise protected from exposure to fire in an approved manner.

2308.7.3 Heat detection system.

Indoor compressing, storage and dispensing areas shall be provided with a closed-circuit heat detection system utilizing approved heat detection devices and equipment designed to automatically activate a local audible and visible alarm with simultaneous transmission to an approved central station, activate a fire extinguishing system over the area or enclosure, and shut off the gas supply to the compressor and dispenser. The automatic shutoff valve shall be installed underground or be otherwise protected from exposure to fire in an approved manner.

2308.7.3.1 Outdoor heat detection system.

Outdoor compressing, storage and dispensing shall be provided with a closed-circuit heat detection system designed utilizing approved heat detection devices and equipment designed to automatically activate a local audible and visible alarm and shut off the gas supply to the compressor and dispenser. The automatic shutoff valve shall be installed underground or otherwise protected from exposure to fire in an approved manner.

2308.7.3.2. Outdoor storage exceeding 35,000 SCF (991.1 m3).

For outdoor CNG storage exceeding 35,000 SCF (991.1 m 3 ) located within 25 feet (7620 mm) of a building or structure, activation of the heat detection system shall simultaneously transmit an alarm to an approved central station.

2308.7.4 Fire extinguishing systems and appliances.

Indoor compressing, storage and dispensing areas shall be protected throughout by a fire extinguishing system.

2308.7.4.1 Fire extinguishing system periodic testing.

A performance test of the non-water fire extinguishing system and the dispensing facility emergency shutdown system shall be conducted at least once every 5 years. The test shall be conducted at the owner's risk by his or her representative before a representative of the department.

2308.7.4.2 Portable fire extinguishers.

Portable fire extinguishers shall be provided adjacent to the CNG motor fuel-dispensing facility in the number and size specified by NFPA 52 and FC 906.

2308.8 Discharge of CNG from motor vehicle fuel storage containers.

The discharge of CNG from motor vehicle fuel containers for the purposes of maintenance, container certification, calibration of dispensers or other activities shall be in accordance with FC 2308.8.1 through 2308.8.1.2.

2308.8.1 Methods of discharge.

The discharge of CNG from motor vehicle fuel containers shall be accomplished through a closed transfer system in accordance with FC 2308.8.1.1 or an approved method of atmospheric venting in accordance with FC 2308.8.1.2.

2308.8.1.1 Closed transfer system.

Documentation of the procedure for discharging the container shall be provided to the commissioner for approval. The procedure shall include the actions the operator will take in the event of a low-pressure or high-pressure natural gas release during the discharging activity. A schematic design document illustrating the arrangement of piping, regulators and equipment settings, and their relation to the location of the compressor, storage vessels and emergency shutdown devices, shall be provided to the commissioner for approval.

2308.8.1.2 Atmospheric venting.

Atmospheric venting of CNG shall comply with the requirements of FC 2308.8.1.2.1 through 2308.8.1.2.6.

2308.8.1.2.1 Plans and specifications.

A schematic design document illustrating the location of the vessel support, piping, the method of grounding and bonding, and other requirements specified herein or requested by the department shall be provided to the commissioner for approval.

2308.8.1.2.2 Container stability.

A method of rigidly supporting the container during the venting of CNG shall be provided. The selected method shall provide not less than two points of support and shall prevent the horizontal and lateral movement of the container. The system shall be designed to prevent the movement of the container based on the highest gas-release velocity through valve orifices at the container's rated pressure and volume. The structure or appurtenance shall be constructed of noncombustible materials.

2308.8.1.2.3 Separation.

The structure or appurtenance used for stabilizing the container shall be separated from other equipment or features as set forth in FC Table 2308.8.1.2.3.

FC Table 2308.8.1.2.3 Separation Distance for Atmospheric Venting of CNG

Equipment or Feature Minimum Separation (feet) Buildings 25 Building openings 25 Lot lines 15 Public street or private roads 15 Vehicles 25 CNG compressor and storage containers 25 CNG dispensers 25

For SI: 1 foot = 304.8 mm.

2308.8.1.2.4 Grounding and bonding.

The structure or appurtenance used for supporting the container shall be grounded in accordance with the Electrical Code. The container valve shall be bonded prior to the commencement of venting operations.

2308.8.1.2.5 Vent tube.

A vent tube that will divert the gas flow to the atmosphere shall be installed on the container prior to commencement of the venting and purging operation. The vent tube shall be constructed of pipe or tubing materials approved for use with CNG in accordance with FC Chapter 53. The vent tube shall be capable of dispersing the gas a minimum of 10 feet (3048 mm) above grade level. The vent tube shall not be provided with a rain cap or other feature that would limit or obstruct the gas flow. At the connection fitting of the vent tube and the CNG container, a listed bi-directional detonation flame arrester shall be provided.

2308.8.1.2.6 Signage.

Approved "No Smoking" signs complying with the requirements of FC 310 shall be conspicuously posted within 10 feet (3048 mm) of the container support structure or appurtenance. Approved CONTAINER SHALL BE BONDED signs shall be posted on the container support structure or appurtenance.

2308.9 Residential and other vehicle fueling appliance facilities.

The compressing and dispensing of CNG by a vehicle fueling appliance shall be in accordance with FC 2308.9.1 through 2308.9.4.

2308.9.1 Residential fueling appliance facilities.

The compressing and dispensing of CNG at a residential fueling appliance facility shall be in accordance with NFPA 52 and this chapter, except that such facilities shall be exempt from the requirements of FC 2308.3.1(2) with regard to the distance to the nearest building, and FC 2308.7 through 2308.7.4.

2308.9.2 Nonresidential fueling appliance facilities.

The compressing and dispensing of CNG at a nonresidential fueling appliance facility shall be in accordance with NFPA 52 and this chapter, except that such facilities shall be exempt from FC 2308.3.1(2) with regard to the distance to the nearest building, and FC 2308.7 through 2308.7.4.

2308.9.3 Prohibitions.

It shall be unlawful to:

1. Fill or store any containers, other than permanently mounted fuel containers on CNG-powered vehicles.

2. Compress and dispense CNG indoors.

2308.9.4 Supervision.

The operation of a vehicle fueling appliance facility shall be under the personal supervision of a certified attendant.

2308.10 Mobile CNG motor fuel compression, storage and dispensing.

A mobile CNG motor fuel compression, storage and/or dispensing system may be used to fuel vehicle-mounted containers as approved by the commissioner and subject to such conditions as the commissioner may prescribe consistent with public safety.

Section FC 2309. Hydrogen Motor Fuel-Dispensing and Generating Facilities

Open this section

2309.1 General.

Hydrogen motor fuel-dispensing and generating facilities shall be designed, installed, operated and maintained in accordance with this section and FC Chapters 53, 55 and 58, as applicable.

2309.1.1 Prohibition.

It shall be unlawful to:

1. Maintain or operate a self-service hydrogen motor fuel-dispensing facility.

2. Maintain or operate a marine hydrogen motor fuel-dispensing facility.

3. Fill a container with hydrogen, other than containers permanently mounted on a powered industrial truck or a hydrogen-powered motor vehicle and used for motive power as set forth in FC 5801.5(1).

4. Generate, compress, store or dispense hydrogen indoors, except for gaseous hydrogen in hydrogen fuel gas rooms in accordance with FC 5808.

2309.1.2 Supervision.

The dispensing of hydrogen at hydrogen motor fuel-dispensing facilities shall be conducted by or under the personal supervision of a certified attendant in accordance with FC 2301.7.

2309.1.2.1 Inspection of dispensing area.

The certified attendant at a hydrogen motor fuel-dispensing facility responsible for supervision of the dispensing of hydrogen shall inspect the dispensing area on a daily basis to ensure that the facility is being maintained in accordance with this chapter and the rules. The certified attendant shall notify the owner and make any other notifications required by this code if there is any evidence that the facility is not in good working order. A record of such inspections and notifications shall be maintained at the premises in accordance with FC 107.7.

2309.1.2.2 Duties of fleet personnel.

Employees or other persons working for the owner of a fleet hydrogen motor fuel-dispensing facility whose duties involve the dispensing of hydrogen shall be trained and knowledgeable in such dispensing in compliance with the requirements of this code and the rules.

2309.1.3 Maintenance.

Maintenance of hydrogen motor fuel-dispensing facilities shall be conducted under the personal supervision of a person holding a hydrogen fueling-facility maintenance certificate of fitness.

2309.1.4 Lighting.

Dispensing areas shall be well lighted whenever dispensing is conducted.

2309.1.5 Dispensing area signage.

Durable signs shall be conspicuously posted in dispensing areas in hydrogen motor fuel-dispensing facilities in compliance with the requirements of FC 2309.1.5.1 through 2309.1.5.4.

2309.1.5.1 Operating instructions.

A sign setting forth dispenser operating instructions shall be posted on every dispenser. Such sign shall also indicate the location of the emergency shutdown valves and emergency shutdown controls required by FC 2309.7.3 and 2309.7.4.

2309.1.5.2 Hydrogen dispensing warning sign.

A warning sign that reads as follows shall be posted on or immediately adjacent to each dispenser:

1. No smoking.

2. Shut off engine.

2309.1.5.3 Emergency procedures.

A sign setting forth emergency procedures that reads as follows shall be posted in the dispensing area, or other location designated in this section:

IN CASE OF FIRE, LEAK OR EMERGENCY: ACTIVATE EMERGENCY SHUTDOWN DIRECT VEHICLE OCCUPANTS TO EXIT VEHICLES AND LEAVE AREA IMMEDIATELY KEEP ALL PERSONS AWAY FROM THE AREA NOTIFY THE FIRE DEPARTMENT (CALL 911) (FACILITY ADDRESS) (indicate address, with cross-street reference ).

2309.1.5.4 Canopy top hydrogen storage.

An approved sign having 2-inch (51-mm) block letters shall be conspicuously posted at approved locations on the exterior of any canopy structure when gaseous hydrogen compression and storage equipment is located on top of such canopy reading "CANOPY TOP HYDROGEN STORAGE."

2309.1.6 Emergency telephone.

A telephone not requiring a coin to operate or another approved, clearly identified means to notify the department, shall be provided on the site in an approved location.

2309.2 Equipment.

Equipment used for the generation, compression, storage or dispensing of hydrogen shall be designed for hydrogen motor fuel in accordance with this section.

2309.2.1 Approved equipment.

Containers and tanks; pressure relief devices, including pressure valves, hydrogen vaporizers, pressure regulators, and piping used for gaseous hydrogen systems shall be designed and constructed in accordance with FC Chapters 53, 55 and 58.

2309.2.2 Listed or approved equipment.

Hoses, hose connections, compressors, hydrogen generators, dispensers, detection systems and electrical equipment used for hydrogen shall be listed or approved for use with hydrogen. Hydrogen motor fueling connections shall be listed and labeled or approved for use with hydrogen.

2309.2.3 Electrical equipment.

Electrical wiring and equipment shall be suitable for the location in which they are installed and shall be in accordance with the Electrical Code.

2309.3 Location.

In addition to the requirements of FC 2303.1, generation, compression, storage and dispensing equipment shall be located in accordance with this section.

2309.3.1 Outdoors.

Generation, compression, storage or dispensing equipment shall be allowed outdoors only in accordance with FC Chapter 58 and NFPA 2.

2309.3.2 Gaseous hydrogen storage.

Storage of gaseous hydrogen shall be in accordance with FC Chapters 53 and 58 and NFPA 2.

2309.3.3 Liquefied hydrogen storage.

Storage of liquefied hydrogen shall be in accordance with FC Chapters 55 and 58 and NFPA 2.

2309.3.4 Canopy tops.

Gaseous hydrogen compression and storage equipment located on top of motor fuel-dispensing facility canopies shall be in accordance with FC Chapters 53 and 58 , the Fuel Gas Code and this section.

2309.3.4.1 Construction.

Canopies shall be constructed in accordance with the motor fuel-dispensing facility canopy requirements of Chapter 4 of the Building Code and the following:

1. The canopy shall meet or exceed Type I construction requirements.

2. Operations located under canopies shall be limited to fueling only.

3. The canopy shall be constructed in a manner that prevents the accumulation of hydrogen gas.

2309.3.4.2 Fire extinguishing systems.

Fuel-dispensing areas under canopies shall be protected throughout by a sprinkler system. The design of the sprinkler system shall not be less than that required for Extra Hazard Group 2 occupancies. Operation of the sprinkler system shall activate the emergency functions of this section.

2309.3.4.3 Emergency discharge.

Operation of the sprinkler system shall activate an automatic emergency discharge system, which will discharge the hydrogen gas from the equipment on the canopy top through the vent pipe system.

2309.3.4.4 Emergency shutdown control.

Operation of the sprinkler system shall activate the emergency shutdown control required by FC 2309.7.4.

2309.4 Canopies.

Dispensing equipment need not be separated from canopies of Type I or II construction that are constructed in a manner that prevents the accumulation of hydrogen gas and in accordance with Chapter 4 of the Building Code.

2309.5 Weather protection.

Generation, compression, storage or dispensing equipment shall be allowed under weather protection in accordance with the requirements of Chapter 4 of the Building Code and FC 5004.13. The weather protection shall be constructed in a manner that prevents the accumulation of hydrogen gas.

2309.6 Overpressure protection.

Dispensing systems shall be equipped with an overpressure protection device set at 140 percent of the service pressure of the fueling nozzle it supplies.

2309.7 Safety precautions.

Safety precautions at hydrogen motor fuel-dispensing and generating facilities shall be in accordance with this section.

2309.7.1 Protection from vehicles.

Guard posts or other approved means shall be provided to protect hydrogen storage systems and use areas subject to vehicular damage in accordance with FC 312.

2309.7.2 Vehicle fueling pad.

The motor vehicle shall be fueled on noncoated concrete or other approved paving material having a resistance not exceeding 1 megohm as determined by the methodology specified in EN 1081.

2309.7.3 Emergency shutoff valves.

A manual emergency shutoff valve shall be provided at a clearly visible, accessible and approved location, to shut down the flow of gas from the hydrogen supply to the piping system.

2309.7.4 Emergency shutdown controls.

In addition to the manual emergency shutoff valve required by FC 2309.7.3, a remotely located, manually activated emergency shutdown control shall be provided. An emergency shutdown control shall be located within 75 feet (22 860 mm) of, but not less than 25 feet (7620 mm) from, dispensers and hydrogen generators.

2309.7.5 System requirements.

Activation of the emergency shutdown control shall automatically shut down the power supply to all hydrogen storage, compression and dispensing equipment; shut off natural gas or other fuel supply to the hydrogen generator; and close valves between the main supply and the compressor and between the storage containers and dispensing equipment.

2309.8 Defueling procedure.

The defueling, purging or other discharge of gaseous hydrogen from hydrogen motor fuel supply systems, including tanks and piping, shall be conducted in accordance with FC Chapters 53 and 58 and NFPA 2. Documentation setting forth the procedure for discharging the storage container shall be submitted to the department for review in connection with the approval of the hydrogen motor fuel storage and dispensing system installation. The written procedure shall address the actions the operator shall take in the event of a low-pressure or high-pressure hydrogen release during gaseous hydrogen discharge.

Exception: Discharges limited to the fuel supply piping from the fuel storage tank to the engine compartment on a motor vehicle or powered industrial truck.

Section FC 2310. Marine Liquid Motor Fuel-Dispensing Facilities

Open this section

2310.1 General.

The construction of marine liquid motor fuel-dispensing facilities shall be in accordance with the construction codes, including the Building Code, and NFPA 30A. The installation, inspection, testing, maintenance and operation of a liquid motor fuel storage and dispensing system at marine liquid motor fuel-dispensing facilities shall be in accordance with this chapter governing automotive liquid motor fuel-dispensing facilities, except that full-service marine liquid motor fuel-dispensing facilities do not require a fire extinguishing system for the dispensing area.

2310.1.1 Prohibited facility.

It shall be unlawful to operate a self-service marine liquid motor fuel-dispensing facility.

2310.2 Storage and handling.

The storage and handling of liquid motor fuel at marine liquid motor fuel-dispensing facilities shall be in accordance with FC 2310.2.1 through 2310.2.3.

2310.2.1 Class I, II or IIIA liquid storage.

Class I, II or IIIA liquids stored indoors used for marine liquid motor fuel-dispensing facilities shall be stored in approved containers. Storage of Class I liquids shall not exceed 10 gallons (38 L).

2310.2.2 Dispensing from portable containers.

No marine vessel or watercraft shall be fueled from a portable container while indoors.

2310.2.3 Heating equipment.

Heating equipment installed in liquid motor fuel storage or dispensing areas shall comply with the requirements of FC 2301.6.

2310.3 Dispensing.

The dispensing of liquid motor fuel at marine liquid motor fuel-dispensing facilities shall comply with the requirements of FC 2310.3.1 through 2310.3.4.

2310.3.1 General.

Unless another use has been approved, piers, docks or wharves at marine liquid motor fuel-dispensing facilities shall be used exclusively for the dispensing or transfer of liquid motor fuel to or from marine vessel, watercraft, except that transfer of essential ship stores is allowed.

2310.3.1.1 Flexible metallic piping.

Where there is a need to provide flexibility in piping to allow for motion of a pier or dock, flexible metallic piping of an approved length and design may be installed and used in compliance with NFPA 30A. All flexible metallic piping or other flexible hose connections authorized by this section shall be inspected for proper operation at least once a year by a certificate of license holder. A record of such inspection shall be kept in a bound log book or other approved form of recordkeeping, and maintained on the premises for a minimum of 4 years.

2310.3.2 Supervision.

The dispensing of liquid motor fuel at marine liquid motor fuel-dispensing facilities shall be conducted by or under the personal supervision of a certified attendant as set forth in FC 2301.7.

2310.3.3 Hoses and nozzles.

Dispensing of liquid motor fuel into the fuel tanks of marine vessels and watercraft shall be by means of an approved-type hose equipped with a listed automatic-closing nozzle without a latch-open device. Hoses used for dispensing or transferring liquid motor fuel, when not in use, shall be reeled, racked or otherwise protected from mechanical damage.

2310.3.4 Portable containers.

Liquid motor fuel dispensing into portable containers shall be performed in accordance with FC 2304.1.7, except that portable containers that are approved and used as the fuel tank for marine vessels or watercraft may be of a capacity not greater than 5 1/2 gallons (20.8 L).

2310.4 Fueling of marine vehicles at other than approved marine liquid motor fuel-dispensing facilities.

It shall be unlawful to fuel floating marine vessels and watercraft with liquid motor fuel at other than a marine liquid motor fuel-dispensing facility, except fueling of marine vessels and watercraft performed by off-shore fueling vessels approved by the United States Coast Guard.

2310.5 Fire prevention.

Marine liquid motor fuel-dispensing facilities shall comply with the requirements of FC 2310.5.1 through 2310.5.7.

2310.5.1 Housekeeping.

Marine motor fuel-dispensing facilities shall be maintained in a neat and orderly manner. Accumulations of rubbish or waste oils in excessive amounts are prohibited. Rubbish and other combustible waste shall be regularly removed from the premises and disposed of lawfully.

2310.5.2 Spills.

Spills of liquid motor fuel near or in the water shall be reported immediately to the department and other governmental agencies requiring such reporting.

2310.5.3 Rubbish containers.

Metal containers with tight-fitting or self-closing metal lids shall be provided for the temporary storage of rubbish or other combustible waste.

2310.5.4 Marine vessel and watercraft mooring.

When marine vessels and watercraft are being fueled at a fuel dock, no other marine vessel or watercraft shall be made fast to the marine vessel or watercraft being fueled or to the fuel dock. The dispensing hose shall not cross one marine vessel or watercraft to reach another.

2310.5.5 Sources of ignition.

Any activity or operation involving the use of open flames, arc- or spark-producing devices shall not be performed at marine motor fuel-dispensing facilities or within 50 feet (15 240 mm) of the dispensing facilities, including piers, docks or wharves, except where approved by the commissioner. Dispensing shall not be conducted at such pier, dock or wharf during the course of such emergency repairs.

2310.5.5.1 Smoking.

It shall be unlawful to smoke, use or maintain an open flame within 50 feet (15 240 mm) of fueling operations. "No Smoking" signs complying with the requirements of FC 310 shall be conspicuously posted throughout the premises. Such signs shall have letters of not less than 4 inches (102 mm) in height with a background of contrasting color.

2310.5.6 Preparation of tanks for fueling.

Marine vessel and watercraft owners and operators shall not offer their marine vessel or watercraft for fueling unless the tanks being filled are properly vented to dissipate fumes to the outdoors.

2310.5.7 Warning signs.

Warning signs shall be prominently displayed at the face of each pier, dock or wharf at such elevation as to be clearly visible from the decks of marine vessels and watercraft being fueled. Such signs shall have letters not less than 3 inches (76 mm) in height on a background of contrasting color bearing the following or approved equivalent wording:

WARNING NO SMOKING – STOP ENGINE WHILE FUELING, SHUT OFF ELECTRICITY. DO NOT START ENGINE UNTIL AFTER BELOW DECK SPACES ARE VENTILATED.

2310.6 Fire protection.

Marine liquid motor fuel-dispensing facilities shall comply with the requirements of FC 2310.6.1 through 2310.6.4, and the construction codes, including the Building Code.

2310.6.1 Standpipe hose stations.

Fire hose, when required, shall be provided and enclosed within a cabinet, and hose stations shall be labeled: FIRE HOSE – EMERGENCY USE ONLY.

2310.6.2 Obstruction of fire protection equipment.

Materials shall not be placed or stored on a pier, dock or wharf in such a manner as to obstruct access to firefighting equipment or piping system control valves.

2310.6.3 Access.

Where the pier, dock or wharf is accessible to vehicular traffic, an unobstructed roadway to the shore end of the pier, dock or wharf shall be maintained for access by fire apparatus.

2310.6.4 Portable fire extinguishers.

One portable fire extinguisher in accordance with FC 906 having a minimum rating of 40-B:C shall be provided on the pier, dock or wharf within 25 feet (7620 mm) of the head of the gangway to the pier, dock or wharf. If the certified attendant's office is within 25 feet (7620 mm) of the gangway or is on the pier, dock or wharf, the fire extinguisher may be provided therein.

Section FC 2311. Repair Garages

Open this section

2311.1 General.

Repair garages shall comply with the requirements of this section and the construction codes, including the Building Code. Repair garages for vehicles that use more than one type of fuel shall comply with the applicable requirements of this section for each type of fuel used. Where a repair garage also includes a motor fuel-dispensing facility, the fuel-dispensing operation shall comply with the requirements of this chapter for motor fuel-dispensing facilities.

2311.1.1 Supervision of defueling operations.

The defueling of liquid motor fuel from the fuel tank of a motor vehicle shall be supervised in accordance with FC 2301.8.

2311.1.2 Supervision of repair garages for vehicles fueled by lighter-than-air motor fuels.

The defueling of motor fuel from the fuel tank of a motor vehicle fueled by lighter-than-air motor fuel, and the refueling of such vehicles, shall be conducted by or under the personal supervision of a person holding a certificate of fitness.

2311.2 Storage and use of flammable and combustible liquids.

The storage and use of flammable and combustible liquids in repair garages shall comply with the requirements of FC Chapter 57 and FC 2311.2.1 through 2311.2.4.

2311.2.1 Cleaning of parts.

Cleaning of parts shall be conducted in listed and approved parts-cleaning machines in accordance with FC Chapter 57.

2311.2.2 Waste oil, motor oil and other Class IIIB liquids.

Waste oil, motor oil and other Class IIIB liquids, including crankcase drainings shall be stored in approved tanks or containers, which are allowed to be stored and dispensed from inside repair garages.

2311.2.2.1 Tanks storing waste oil.

For tanks of a capacity of 500 gallons (1893 L) or less, the fill connection may be located indoors provided that discharge of vapor from the fill port is prevented from entering the building or structure during and after filling. An automatic spring-loaded vertical check valve in the fill line or other device designed to prevent vapors from escaping shall be provided. The fill line shall be capped immediately after filling.

2311.2.3 Draining and disposal of liquids and oil-soaked waste.

Garage floor drains, where provided, shall drain to approved oil separators or traps discharging to a sewer in accordance with the construction codes, including the Plumbing Code. Contents of oil separators, traps and floor drainage systems shall be collected at sufficiently frequent intervals and removed from the premises to prevent oil from being carried into the sewers. Crankcase drainings and liquids shall not be dumped into sewers, streams or on the ground, but shall be stored in approved tanks or containers in accordance with FC Chapter 57 until removed from the premises. Self-closing metal cans shall be used for oily waste.

2311.2.3.1 Draining of liquid motor fuel tanks.

Portable equipment used for defueling and refueling shall be listed and labeled and shall have fuel storage tanks not exceeding 65 gallons (246 L). Stationary systems for defueling and refueling, shall be approved by the department.

2311.2.4 Spray finishing.

Spray finishing with flammable or combustible liquids shall comply with the requirements of FC Chapter 24.

2311.3 Sources of ignition.

Sources of ignition shall not be located within 18 inches (457 mm) of the floor and shall comply with the requirements of FC Chapters 3 and 35.

2311.3.1 Equipment.

Appliances and equipment installed in a repair garage shall comply with the requirements of the construction codes, including the Building Code, the Mechanical Code and the Electrical Code.

2311.3.2 Smoking.

Smoking is prohibited in repair garages.

2311.4 Below grade areas.

Pits and other work areas below grade in repair garages shall comply with the requirements of FC 2311.4.1 through 2311.4.3.

2311.4.1 Construction.

Pits and other work areas below grade shall be constructed in accordance with the construction codes, including the Building Code.

2311.4.2 Means of egress.

Pits and other work areas below grade shall be provided with means of egress in accordance with the Building Code.

2311.4.3 Ventilation.

Where Class I liquids are stored or used within a building having a basement or pit wherein flammable vapors could accumulate, the basement or pit shall be provided with mechanical ventilation in accordance with the construction codes, including the Mechanical Code, at a minimum rate of 1.5 cubic feet per minute per square foot (0.008 m 3 /s/m 2 ) to prevent the accumulation of flammable vapors.

2311.5 Reserved.

2311.6 Reserved.

2311.7 Portable fire extinguishers.

Portable fire extinguishers shall be provided in accordance with FC 906.

2311.8 Repair garages for vehicles fueled by lighter-than-air motor fuels.

The repair garage, or the room, booth or area thereof, for the conversion and/or repair of vehicles which use CNG, liquefied natural gas (LNG), hydrogen or other lighter-than-air motor fuels shall be designed, installed, operated and maintained in accordance with FC 2311.8.1 through 2311.8.8.

Exceptions:

1. Repair garages where work is conducted only on vehicles that have been defueled and their systems purged with nitrogen gas, and which will not be re-fueled in the repair garage. Documentation of such purging shall be maintained on the premises and signage conspicuously posted that no lighter-than-air gas fueling shall be conducted in the repair garage.

2. Repair garages where work is not performed on the fuel system and is limited to exchange of parts and maintenance requiring no open flame or welding on the CNG-, LNG-, hydrogen- or other lighter-than-air-fueled motor vehicle.

3. Repair garages for hydrogen-fueled vehicles where work is not performed on the hydrogen storage tank and is limited to the exchange of parts and maintenance requiring no open flame or welding on the hydrogen-fueled vehicle. During the work, the entire hydrogen fuel system shall contain less than 200 cubic feet (5.6 m 3 ) of hydrogen.

4. Repair garages for natural-gas-fueled vehicles where work is not being performed on the fuel storage tank, and is limited to the exchange of parts and maintenance requiring no open flame or welding on the natural-gas-fueled vehicle. During the work, the natural gas in the vehicle fuel tank shall contain a pressure of not more than 250 psi at 70ºF (1724 kPa at 21ºC).

2311.8.1 Construction requirements.

Any room or booth in a repair garage that is used for motor vehicle repair shall be constructed in accordance with the Building Code and FC 2311.8.1.1 and 2311.8.1.2.

2311.8.1.1 Motor vehicle repair spaces.

When motor vehicle repairs are performed in an unenclosed interior space, noncombustible spray curtains shall be provided to restrict the spread of flammable gases.

2311.8.1.2 Below grade areas.

Motor vehicle repair rooms, booths and spaces shall not be constructed in below grade areas.

2311.8.2 Fire protection.

Motor vehicle repair booths or spaces installed in a room or area shall be protected by a sprinkler system as set forth in the Building Code.

2311.8.3 Exhaust ventilation system.

Repair garages used for the repair of vehicles fueled by CNG, LNG or other lighter-than-air motor fuels other than hydrogen shall be provided with an approved mechanical ventilation system designed in accordance with this section and the construction codes, including the Mechanical Code. Repair garages used for the repair of hydrogen-fueled vehicles shall be provided with an approved exhaust ventilation system in accordance with the construction codes, including the Mechanical Code, and Chapter 6 of NFPA 2.

2311.8.3.1 Design.

For indoor locations, air supply inlets and exhaust outlets for mechanical ventilation shall be arranged to provide uniformly distributed air movement with inlets uniformly arranged on walls near floor level and outlets at the high point of the room in walls or the roof. Failure of the ventilation system shall cause the fueling system to shut down. The exhaust ventilation rate shall be not less than 1 cubic foot per minute (0.03 m 3 /minute) per 12 cubic feet (34 m 3 ) of room volume.

2311.8.3.2 Operation.

The mechanical exhaust ventilation system shall operate continuously.

Exceptions:

1. Mechanical exhaust ventilation systems that are interlocked with a gas detection system designed in accordance with FC 2311.8.4.

2. Mechanical exhaust ventilation systems in repair garages that are used only for repair of vehicles fueled by liquid fuels or odorized gases, such as CNG, where the ventilation system is electrically interlocked with the lighting circuit.

2311.8.4 Gas detection system.

Repair garages used for repair of vehicles fueled by CNG, LNG or hydrogen shall be provided with a gas detection system in accordance with FC 908 and 2311.8.4.1 through 2311.8.4.3.

2311.8.4.1 System design.

The gas detection system shall be designed to detect leakage of nonodorized gaseous fuel. Where lubrication or chassis service pits are provided in garages used for repairing nonodorized LNG-fueled vehicles, gas sensors shall be provided in such pits.

2311.8.4.2 System activation.

Activation of the gas detection system alarm shall initiate the following actions:

1. Activation of local audible and visual alarms in approved locations.

2. Deactivation of heating systems located in the repair garage.

3. Activation of the mechanical exhaust ventilation system, where the ventilation system is interlocked with gas detection.

2311.8.4.3 System failure.

Failure of the gas detection system shall automatically deactivate the heating system, activate the mechanical exhaust ventilation system where the system is interlocked with the gas detection system, and transmit a supervisory signal to the control panel and a central station.

2311.8.5 Electrical requirements.

Areas within 18 inches (450 mm) of a ceiling within a motor vehicle repair room or motor vehicle repair booth shall be designed and installed in accordance with the requirements for Class I, Division 2 classified locations, as set forth in the Electrical Code.

Exceptions:

1. Motor vehicle repair rooms with exhaust ventilation of not less than 1 cfm per square foot (0.03 m 3 /minute/m 2 ) of floor area, with suction taken from a point within 18 inches (450 mm) of the highest point in the ceiling in repair garages for vehicles that use CNG, liquefied natural gas (LNG) or other lighter-than-air motor fuels.

2. Motor vehicle repair rooms used for the repair of hydrogen-fueled vehicles that have an approved exhaust ventilation system in accordance with the Mechanical Code and NFPA 2.

2311.8.6 Preparation of vehicles for repair.

For vehicles powered by gaseous fuels, the fuel shutoff valves shall be closed prior to repairing any portion of the vehicle fuel system. Where the fuel system of a vehicle powered by a gaseous fuel has been damaged, the entire fuel system of the vehicle shall be inspected and evaluated for integrity prior to being brought into the repair garage.

2311.8.7 Other requirements.

Repair garages for vehicles fueled by lighter-than-air motor fuels shall comply with the requirements of FC 2311.1.2, 2311.3 and 2311.7 with respect to supervision, sources of ignition and portable fire extinguishers.

2311.8.8 Defueling equipment required at vehicle maintenance and repair facilities.

Repair garages that repair or replace hydrogen fuel systems on hydrogen-fueled vehicles shall have equipment to defuel hydrogen fuel storage tanks. Where work must be performed on a vehicle's fuel storage tank for the purpose of maintenance, repair or cylinder certification, defueling and purging shall be conducted in accordance with FC 2309.8 and NFPA 2.

Section FC 2401. General

Open this section

2401.1 Scope.

This chapter shall govern the following operations, and the design, installation, operation and maintenance of any building, structure or premises wherein such operations are conducted:

1. The application of flammable finishes to articles or materials by means of spray apparatus.

2. The application of flammable finishes by dipping or immersing articles or materials into the contents of tanks, vats or containers of flammable or combustible liquids for coating, finishing, treatment and similar processes.

3. The application of flammable finishes utilizing powder spray guns, electrostatic powder spray guns, fluidized beds or electrostatic fluidized beds to apply combustible powders.

4. Floor finishing operations.

5. The application of flammable finishes consisting of dual-component coatings or Class I or II liquids when applied by brush or roller in quantities exceeding 1 gallon (4 L).

2401.2 Permits.

Permits shall be required as set forth in FC 105.6.

2401.3 General.

Flammable finishing operations governed by this chapter shall be conducted in accordance with this chapter. The buildings and premises in which such flammable finishing operations are conducted shall be designed, installed, operated and maintained in accordance with this chapter.

2401.4 Supervision.

The following finishing operations shall be conducted by or under the personal supervision of a certificate of fitness holder:

1. Spray-finishing and dipping operations.

2. Floor finishing operations requiring a permit.

2401.5 Certificate of approval.

Pre-manufactured spray rooms and pre-manufactured spray booths that circulate heated air shall be of a type for which a certificate of approval has been issued in accordance with this code, or which was previously approved by the Department of Buildings or the Board of Standards and Appeals, unless such approval is amended or repealed by the commissioner.

Section FC 2402. Definitions

Open this section

2402.1 Definitions.

The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.

DETEARING.

DIP TANK.

ELECTROSTATIC FLUIDIZED BED.

FLAMMABLE FINISHES.

FLAMMABLE VAPOR AREA.

FLOOR FINISHING OPERATION.

FLUIDIZED BED.

LIMITED-SPRAYING SPACE.

RESIN APPLICATION AREA.

ROLL COATING.

SPRAY BOOTH.

SPRAY ROOM.

SPRAYING SPACE.

Section FC 2403. Protection of Operations

Open this section

2403.1 General.

Operations covered by this chapter shall be protected as required by this section and the Electrical Code.

2403.2 Sources of ignition.

Protection against sources of ignition shall be provided in accordance with FC 2403.2.1 through 2403.2.8.

2403.2.1 Electrical wiring and equipment.

Electrical wiring and equipment shall comply with the requirements of this chapter and the Electrical Code.

2403.2.1.1 Flammable vapor areas.

Electrical wiring and equipment in flammable vapor areas shall be of an explosion-proof type approved for use in such hazardous locations. Such areas shall be considered to be Class I, Division 1 or Class II, Division 1 hazardous locations in accordance with the Electrical Code.

2403.2.1.2 Areas subject to deposits of residues.

Electrical equipment in flammable vapor areas and drying operations which are subject to splashing or dripping of liquids shall be specifically approved for locations containing deposits of readily ignitable residue and explosive vapors.

Exceptions:

1. Wiring in rigid conduit and threaded boxes or fittings not containing taps, splices or terminal connections.

2. Electrostatic equipment complying with the requirements of FC 2407.

2403.2.1.2.1 Resin application areas.

In resin application areas, electrical wiring and equipment that is subject to deposits of combustible residues shall be listed for such exposure and shall be installed as required for hazardous (classified) locations. Electrical wiring and equipment not subject to deposits of combustible residues shall be installed as required for ordinary hazard locations.

2403.2.1.3 Areas adjacent to spray booths.

Electrical wiring and equipment located outside of, but within 5 feet (1524 mm) horizontally and 3 feet (914 mm) vertically of openings in a spray booth or a spray room shall be approved for Class I, Division 2 or Class II, Division 2 hazardous locations, whichever is applicable.

2403.2.1.4 Areas subject to overspray deposits.

Electrical equipment in flammable vapor areas located such that deposits of combustible residues could readily accumulate thereon shall be specifically approved for locations containing deposits of readily ignitable residue and explosive vapors in accordance with the Electrical Code.

Exceptions:

1. Wiring in rigid conduit and threaded boxes or fittings not containing taps, splices or terminal connections.

2. Equipment complying with the requirements of FC 2404 and 2407 and FC Chapter 30.

2403.2.2 Open flames and sparks.

Open flames and spark-producing devices shall not be located in flammable vapor areas and shall not be located within 20 feet (6096 mm) of such areas unless separated by a permanent partition.

Exception: Drying and baking apparatus complying with the requirements of FC 2404.3.4.2.

2403.2.3 Hot surfaces.

Heated surfaces having a temperature sufficient to ignite vapors shall not be located in flammable vapor areas. Space-heating appliances, steam pipes or hot surfaces in flammable vapor areas shall be located such that they are not subject to accumulation of deposits of combustible residues.

Exception: Drying apparatus complying with the requirements of FC 2404.3.4.2.

2403.2.4 Equipment enclosures.

Equipment or apparatus that is capable of producing sparks or particles of hot metal that would fall into a flammable vapor area shall be totally enclosed.

2403.2.5 Grounding.

Metal parts of spray booths, exhaust ducts and piping systems conveying Class I or II liquids shall be electrically grounded in accordance with the Electrical Code. Metallic parts located in resin application areas, including but not limited to exhaust ducts, ventilation fans, spray application equipment, workpieces and piping, shall be electrically grounded.

2403.2.6 Smoking prohibited.

It shall be unlawful to smoke in flammable vapor areas and hazardous material storage rooms associated with flammable finishing operations. "No Smoking" signs complying with the requirements of FC 310 shall be conspicuously posted in such areas.

2403.2.7 Hot work warning signs.

Welding, cutting and other hot work operations shall not be conducted in or adjacent to flammable vapor areas. Durable signs bearing the following warning shall be conspicuously posted in the vicinity of flammable vapor areas and flammable finishing material storage rooms:

NO WELDING THE USE OF WELDING OR CUTTING EQUIPMENT IN OR NEAR THIS AREA IS DANGEROUS BECAUSE OF FIRE AND EXPLOSION HAZARDS.

2403.2.8 Powered industrial trucks.

Powered industrial trucks used in electrically classified areas shall be listed for such use.

2403.3 Storage, handling and use of flammable and combustible liquids.

Flammable and combustible liquids shall be stored, handled and used in accordance with this section and FC Chapter 57.

2403.3.1 Use.

Containers supplying spray nozzles shall be of a closed type or provided with metal covers which are kept closed. Containers not resting on floors shall be on noncombustible supports or suspended by wire cables. Containers supplying spray nozzles by gravity flow shall not exceed 10 gallons (37.9 L) in capacity.

2403.3.2 Valves.

Containers and piping to which a hose or flexible connection is attached shall be provided with a shutoff valve at the connection. Such valves shall be kept shut when hoses are not in use.

2403.3.3 Pumped liquid supplies.

Where flammable or combustible liquids are supplied to spray nozzles by positive displacement pumps, pump discharge lines shall be provided with an approved relief valve discharging to pump suction or a safe detached location.

2403.3.4 Liquid transfer.

Where a flammable liquid is transferred from one portable container to another, a bond shall be provided between the two containers. At least one container shall be grounded. Piping systems for Class I and Class II liquids shall be permanently grounded.

2403.3.5 Class I liquids as solvents.

Class I liquids used as solvents shall be used in spray gun and equipment cleaning machines which have been listed and approved for the purpose or shall be used in spray booths or spray rooms in accordance with FC 2403.3.5.1 and 2403.3.5.2.

2403.3.5.1 Listed devices.

Cleaning machines for spray guns and equipment shall not be located in areas open to the public and shall be separated from ignition sources in accordance with their listings or by a distance of 3 feet (914 mm), whichever is greater. The quantity of solvent used in a machine shall not exceed the design capacity of the machine.

2403.3.5.2 Within spray booths and spray rooms.

Mechanical ventilation equipment shall be operated when solvents are used for cleaning spray nozzles and auxiliary equipment and for a period of time thereafter to allow for the exhaust of the vapors within spray booths and spray rooms.

2403.3.6 Class II and Class III liquids.

Solvents used outside of spray booths, spray rooms or listed and approved spray gun and equipment cleaning machines shall be restricted to Class II and Class III liquids.

2403.4 Operations and maintenance.

Flammable vapor areas, exhaust fan blades and exhaust ducts shall be kept free from the accumulation of deposits of combustible residues. Where excessive residue accumulates in such areas, spraying operations shall be discontinued until the accumulation is removed from such areas and properly disposed of.

2403.4.1 Tools.

Scrapers, spuds and other tools used for cleaning purposes shall be constructed of non-sparking materials.

2403.4.2 Residue.

Residue removed during cleaning and debris contaminated with residue shall be immediately removed from the premises and disposed of lawfully.

2403.4.3 Waste cans.

Approved metal waste cans equipped with self-closing lids shall be provided wherever rags or waste are impregnated with finishing material. Such rags and waste shall be deposited therein immediately after being utilized. The contents of waste cans shall be properly disposed of at the end of each work shift and at least once daily.

2403.4.4 Solvent recycling.

Solvent distillation equipment used to recycle and clean dirty solvents shall comply with the requirements of FC 5705.4.

Section FC 2404. Spray Finishing

Open this section

2404.1 General.

Spraying operations involving the use of flammable or combustible liquids in continuous or intermittent processes shall be conducted in accordance with this section and FC 2403 and 2407, as applicable.

2404.2 Location.

Except in Group A, E, I and R occupancies, spraying operations shall be conducted in a spray room or a spray booth complying with the applicable requirements of FC 2404.3, unless the extent of such operations allows them to be conducted in a limited-spraying space in accordance with FC 2404.5. In Group A, E, I and R occupancies, spray-finishing operations shall be conducted in a spray room in compliance with the applicable requirements of FC 2404.3.

Exceptions:

1. Approved automobile undercoating spray operations and spray-on automotive lining operations, utilizing liquids having a flashpoint above 140ºF (60°C), when conducted in areas with approved natural or mechanical ventilation.

2. The application of resin in the manufacturing of reinforced plastics in accordance with FC 2409.

2404.2.1 Below grade areas.

Spray rooms and spray booths shall not be located in basements, cellars or other areas below grade.

2404.3 Design and installation.

Spray rooms and spray booths shall be designed and installed in compliance with the requirements of FC 2404.3.1 through 2404.3.7, as applicable.

2404.3.1 Construction of spray rooms.

Spray rooms shall be designed and installed in compliance with the requirements of the Building Code and Mechanical Code, including vertical and horizontal separation from other spaces. Spray rooms shall additionally comply with the requirements of this section.

2404.3.2 Construction of spray booths.

Spray booths shall be designed and installed in compliance with the requirements of the Building Code and Mechanical Code, NFPA 33 and this section.

2404.3.2.1 Materials.

Spray booths shall be constructed of approved noncombustible materials. Aluminum shall not be used. Where walls or ceiling assemblies are constructed of sheet metal, single-skin assemblies shall be no thinner than 0.0478 inch (18 gauge) (1.2 mm) and each sheet of double-skin assemblies shall be no thinner than 0.0359 inch (20 gauge) (0.9 mm). Structural sections of spray booths may be sealed with latex-based or similar caulks and sealants. The interior surfaces of spray booths shall be smooth and shall be constructed so as to permit the free passage of exhaust air from all parts of the interior and to facilitate washing and cleaning, and shall be designed to confine residues within the booth.

2404.3.2.2 Clear space.

Spray booths shall be installed so that all parts of the booth are readily accessible for cleaning and other maintenance. A clear space of not less than 3 feet (914 mm) shall be maintained on all sides of the spray booth.

Exception: A clear space of less than 3 feet (914 mm) may be maintained from an interior partition, wall or floor/ceiling assembly with a fire-resistance-rating of not less than 1 hour, or an exterior wall or roof assembly of a noncombustible wall or roof.

2404.3.2.3 Size.

The aggregate area of spray booths in a building shall not exceed the lesser of 10 percent of the area of any floor of the building or the floor area allowed for a Group H-2 occupancy by the Building Code, as set forth in Table 503 of the Building Code, excluding any area increases allowed by Section 506 of the Building Code. The area of an individual spray booth in a building shall not exceed the lesser of the aggregate size limit or 1,500 square feet (139 m 2 ).

Exception: A single spray booth not exceeding 500 square feet (46 m 2 ) is allowed irrespective of the results of the required calculations.

2404.3.2.4 Waterwash spray booths.

Waterwash spray booths shall be of an approved design so as to prevent excessive accumulation of deposits in ducts and residue at duct outlets. Such booths shall be arranged so that air and overspray are drawn through a continuously flowing water curtain before being exhausted outdoors.

2404.3.2.5 Means of egress.

Means of egress doors from pre-manufactured spray booths shall not be less than 30 inches (762 mm) in width by 80 inches (2032 mm) in height.

2404.3.3 Fire protection.

Spray rooms and spray booths shall be protected by a fire extinguishing system. Such fire extinguishing system shall also protect exhaust plenums, exhaust ducts and both sides of dry filters when such filters are used.

2404.3.3.1 Automated spraying operations.

The fire extinguishing system for each spray room or spray booth designed for automatic spraying operations shall be equipped with an interlock in accordance with FC 2404.3.5(7) and with a manual shutdown device. Such manual shutdown device shall be located within the path of emergency egress from such spray room or spray booth, shall be readily accessible to personnel supervising the spraying operation, and when activated, shall initiate the same functions as the automatic interlock.

2404.3.4 Drying operations.

Spray rooms and spray booths shall not be used for drying operations that could cause an increase in the surface temperature of the spray room or spray booth, unless such operations are conducted in compliance with the requirements of FC 2404.3.4.1, 2404.3.4.2 and 2404.3.5.

2404.3.4.1 Spraying procedure.

The spraying procedure shall use low-volume spray application.

2404.3.4.2 Drying and baking apparatus.

Fixed drying and baking apparatus shall comply with the requirements of this chapter and the applicable provisions of FC Chapter 30. When recirculation ventilation is provided in accordance with FC 2404.3.7.1, the heating system shall not be within the recirculation air path.

2404.3.5 Interlocks.

The spraying apparatus, drying apparatus and ventilating system for the spray room or spray booth shall be equipped with interlocks designed to automatically:

1. prevent operation of spraying apparatus while drying operations are in progress.

2. prevent the operation of the drying apparatus until the spray room or spray booth has been purged of vapors for a period of at least 3 minutes.

3. shut down the drying apparatus in the event that the ventilation system fails to operate within the spray room or spray booth during the drying process.

4. shut down the drying apparatus if the air temperature within the spray room or spray booth exceeds 200°F (93°C).

5. prevent the spraying operation unless the ventilation system is in operation.

6. shut down the spraying operation in a spray booth equipped with a filter roll when the filter roll fails to automatically advance when the air velocity falls below the minimum design level.

7. shut down the spraying operation, drying operation and workpiece conveyors into and out of the flammable vapor area, and notify the building fire alarm system, upon activation of the fire extinguishing systems protecting an automated spraying operation.

2404.3.6 Illumination.

Only fixed luminaires protected by a glass panel shall be utilized as a source of illumination in spray rooms and spray booths. Such luminaires and glass panels shall comply with the requirements of FC 2404.3.6.1 through 2404.3.6.3, as applicable.

2404.3.6.1 Glass panels.

Panels for light fixtures or for observation shall be of heat-treated glass, wired glass or hammered-wire glass, and shall be sealed to confine vapor, gas, fume, mists or dust to the flammable vapor area. Panels for luminaires shall be separated from the luminaire to prevent the surface temperature of the panel from exceeding 200°F (93°C).

2404.3.6.2 Exterior luminaires.

Luminaires approved for use in ordinary hazard locations may be used when the luminaire is attached to an exterior wall or ceiling of a spray room or spray booth, but is separated and protected from the flammable vapor area by a vapor-tight glass panel. Such luminaires shall be serviced exclusively from outside the flammable vapor area.

2404.3.6.3 Integral luminaires.

Luminaires approved for use in hazardous locations shall be used when the luminaire is an integral part of the walls or ceiling of a spray room or spray booth. Such luminaires shall be listed for use in Class I, Division 2 or Class II, Division 2 locations, as applicable. Such luminaires may be serviced from inside the flammable vapor area.

2404.3.7 Ventilation.

Mechanical ventilation of flammable vapor areas shall be provided in accordance with Chapter 5 of the Mechanical Code and this section.

2404.3.7.1 Recirculation.

Air exhausted from spraying operations shall not be recirculated, except as authorized by the Mechanical Code.

2404.3.7.2 Prohibition.

Makeup air and flammable vapor area exhaust systems shall not be interlocked with the fire alarm system. The ventilation system shall remain in operation upon activation of the building fire alarm system.

Exception: Where the type of fire extinguishing system used requires that ventilation be discontinued, makeup air and exhaust systems shall shut down and dampers shall close.

2404.3.7.3 Filters.

Spray rooms and spray booths shall be provided with exhaust filters. Air intake filters are not required, but if part of a spray room or spray booth wall or ceiling assembly shall be listed as Class I or Class II in accordance with UL 900.

2404.3.7.3.1 Supports.

Supports and holders for filters shall be constructed of noncombustible materials.

2404.3.7.3.2 Attachment.

Overspray collection filters shall be readily removable and accessible for cleaning or replacement.

2404.3.7.3.3 Monitoring air velocity.

One or more devices shall be provided to monitor the air velocity of the air being exhausted from a spray room or spray booth and to provide an indication, alarm or system shutdown if the required velocity is not being maintained. The device monitoring the air flow shall visually display the pressure of the exhausted air, activate an alarm and/or shut down the spraying operation.

2404.4 Operation and maintenance.

Facilities in which spraying operations and drying operations are conducted shall be operated and maintained in compliance with the requirements of this section.

2404.4.1 Spraying of incompatible materials.

Spray rooms and spray booths shall not be utilized for spraying operations utilizing alternating incompatible materials, unless all deposits of one material are removed from the room or booth and exhaust ducts, and dry filters replaced, prior to spraying with the incompatible material.

2404.4.2 Filter disposal.

Discarded exhaust filters shall be immediately removed from the spray room or spray booth and disposed of in accordance with FC 304.3.1.

2404.4.3 Sprinkler head protection.

Sprinkler heads installed in spraying spaces shall be protected in an approved manner from accumulation of residue from spraying operations. Sprinkler heads shall be inspected at least once per week and cleaned as needed. Bags used as a protective covering shall be of 0.003-inch-thick (0.076-mm-thick) polyethylene or cellophane or shall be of thin paper. Sprinkler heads contaminated by overspray particles shall be replaced with new sprinkler heads.

2404.4.4 Floor protection.

Combustible floor construction in spraying spaces shall be covered by an approved, noncombustible, nonsparking material, except that combustible coverings, such as thin paper or plastic and strippable coatings, may be utilized over the noncombustible, nonsparking floor covering material on combustible floors, and on noncombustible floors, to facilitate cleaning operations in spraying spaces.

2404.4.5 Portable electric lamps.

Portable electric lamps shall not be stored or used in the flammable vapor area.

Exception: Portable electric lamps of a type approved for hazardous locations may be used to provide additional lighting for cleaning or maintenance in such areas.

2404.4.6 Portable infrared apparatus.

Portable electrical equipment located within 18 inches (457 mm) of floor level shall be approved for Class I, Division 2, hazardous locations. Metallic parts of drying apparatus shall be electrically bonded and grounded. During spraying operations, portable drying apparatus and electrical connections and wiring thereto shall not be located within spray booths, spray rooms or other spraying space.

2404.4.7 Continuous ventilation.

Mechanical ventilation shall be kept in operation at all times while spraying operations are being conducted and for a sufficient time thereafter to allow vapors from drying coated articles and finishing material residue to be exhausted.

2404.4.8 Obstruction of exhaust ventilation.

Articles being sprayed shall be positioned in a manner that does not obstruct collection of overspray.

2404.4.9 Hazardous and combustible material storage.

The clear space around spray booths pursuant to FC 2404.3.2.2 shall be kept free of hazardous material and combustible material storage.

2404.4.10 Portable fire extinguishers.

Spraying spaces shall be provided with portable fire extinguishers for an extra (high) hazard occupancy in accordance with FC 906.

2404.5 Limited-spraying spaces.

Spray finishing operations may be conducted in a limited-spraying space when the spraying operations are limited in size and frequency and are conducted in a properly ventilated and electrically wired space in compliance with the requirements of FC 2404.5.1 through 2404.5.5.

2404.5.1 Job size.

The surface area of any workpiece to be sprayed shall not exceed 9 square feet (0.84 m 2 ).

2404.5.2 Frequency.

Spraying operations shall not be of a continuous nature and shall be incidental to the operation of the facility.

2404.5.3 Ventilation.

Positive mechanical ventilation shall be provided in accordance with Chapter 5 of the Mechanical Code. Such system shall meet the requirements of the Mechanical Code for flammable vapor areas. Explosion venting is not required.

2404.5.4 Electrical wiring.

Electrical wiring within 10 feet (3048 mm) of the floor and 20 feet (6096 mm) horizontally of the limited-spraying space shall be designed for Class I, Division 2 locations in accordance with the Electrical Code.

2404.5.5 Portable fire extinguisher.

Limited-spraying space shall be provided with a portable fire extinguisher in accordance with FC 2404.4.10.

Section FC 2405. Dip-Tank Operations

Open this section

2405.1 General.

Dip-tank operations shall be conducted in accordance with this section and FC 2403.

2405.2 Location.

In Group A, I and R occupancies, dip-tank operations shall be conducted in a room designed for that purpose, protected throughout by a sprinkler system, and separated vertically and horizontally from other areas by construction having a fire resistance rating of not less than 2 hours, in accordance with the construction codes, including the Building Code.

2405.3 Design and installation.

Dip tanks shall be designed and installed in compliance with the requirements of FC 2405.3.1 through 2405.3.6.

2405.3.1 Construction.

Except as otherwise provided in FC 2405.4 with respect to hardening and tempering tanks, dip tanks shall be constructed in accordance with this section, and NFPA 34. Dip tanks, including drain boards, shall be constructed of noncombustible material and their supports shall be sturdily constructed of metal, reinforced concrete or masonry.

2405.3.1.1 Overflow.

Dip tanks greater than 150 gallons (568 L) in capacity or 10 square feet (0.93 m 2 ) in liquid surface area shall be equipped with a trapped overflow pipe leading to an approved outdoor location. The bottom of the overflow connection shall not be less than 6 inches (152 mm) below the top of the tank.

2405.3.1.2 Bottom drains.

Dip tanks greater than 500 gallons (1893 L) in liquid capacity shall be equipped with bottom drains that are arranged to automatically and manually drain the tank quickly in the event of a fire unless the viscosity of the liquid at normal atmospheric temperature makes this impractical. Manual operation shall be from a safe, accessible location. Where gravity flow is not practicable, automatic pumps shall be provided. Such drains shall be provided with traps and shall discharge to a closed, vented salvage tank or other approved location.

Exception: Dip tanks containing Class IIIB combustible liquids where the liquids are not heated above room temperature, and the process area is protected throughout by a sprinkler system.

2405.3.2 Dipping liquid temperature control.

Protection against the accumulation of vapors, self-ignition and excessively high temperatures shall be provided for dip tanks in which dipping liquids are heated directly or heated by the surfaces of the object being dipped.

2405.3.3 Dip tank covers.

Dip tank covers, if provided, shall be capable of manual operation and shall be automatic-closing by approved automatic-closing devices designed to operate in the event of fire. Dip tank covers shall be kept closed when tanks are not in use.

2405.3.3.1 Materials.

Dip tank covers shall be constructed of noncombustible material or be of a tin-clad type designed in the same manner as fire doors.

2405.3.3.2 Supports.

Chain or wire rope shall be utilized for cover supports or operating mechanisms.

2405.3.4 Fire protection.

Dip-tank operations shall be protected in compliance with the requirements of FC 2405.3.4.1 and 2405.3.4.2.

2405.3.4.1 Fire extinguishing equipment.

A fire extinguishing system shall be provided for the following dip tanks unless such dip tanks are provided with a dip tank cover in accordance with FC 2405.3.3:

1. Dip tanks less than 150 gallons (568 L) in capacity or 10 square feet (0.93 m 2 ) in liquid surface area.

2. Dip tanks containing a liquid with a flash point below 110°F (43°C), used in such manner that the liquid temperature could equal or be greater than its flash point from artificial or natural causes, and having both a capacity of more than 10 gallons (37.9 L) and a liquid surface area exceeding 4 square feet (0.37 m 2 ).

2405.3.4.2 Fire extinguishing system.

Dip tanks with a capacity of 150 gallons (568 L) or more, or a liquid surface area of 10 square feet (0.93 m 2 ) or more shall be protected by a fire extinguishing system. Such fire extinguishing system shall be designed in accordance with NFPA 34.

2405.3.5 Interlocks.

Dip tanks utilizing a conveyor system shall be arranged such that in the event of fire, the conveyor system shall automatically cease motion and the required tank bottom drains shall open.

2405.3.6 Ventilation.

Mechanical ventilation of flammable vapor areas shall be provided in accordance with Chapter 5 of the Mechanical Code.

2405.4 Hardening and tempering tanks.

Hardening and tempering tanks shall be designed and installed in compliance with the requirements of FC 2405.4.1 through 2405.4.5. Except as provided therein, hardening and tempering tanks shall not be subject to the requirements for dip tanks set forth in FC 2405.

2405.4.1 Construction.

Hardening and tempering tanks shall be constructed in accordance with FC 2405.3.1, 2405.3.1.1, 2405.3.1.2, 2405.3.2 and 2405.3.5.

2405.4.2 Location.

Hardening and tempering tanks located in a room containing an industrial furnace shall be positioned to minimize the ignition risk from such furnace, and such tanks shall not be located on a combustible floor.

2405.4.3 Hoods.

Hardening and tempering tanks shall be provided with a noncombustible hood and vent or other approved ventilation system that terminates outdoors. Such exhaust hood and vent shall serve to provide a path for heat and flames in the event of a fire in the tank. Such vent ducts shall be designed as flues, and clearances shall be maintained from combustible materials to minimize their ignition risk.

2405.4.4 Fire extinguishing system.

Hardening and tempering tanks with a capacity exceeding 500 gallons (1893 L) or a liquid surface area exceeding 25 square feet (2.3 m 2 ) shall be protected by a fire extinguishing system.

2405.4.5 High temperature alarm.

Hardening and tempering tanks shall be equipped with a high-temperature limit switch arranged to sound an alarm when the temperature of the quenching medium reaches 50°F (10°C) below its flash point.

2405.5 Operation and maintenance.

Facilities in which dipping operations are conducted shall be operated and maintained in compliance with the requirements of this section.

2405.5.1 Sources of ignition.

Protection against sources of ignition shall be provided in accordance with FC 2403.2.

2405.5.2 Use of compressed air.

Compressed air shall not be used to fill the tank or agitate tank contents.

2405.5.3 Portable fire extinguishers.

Dip tank rooms and areas shall be provided with portable fire extinguishers complying with the requirements of FC 906 and rated for flammable and combustible liquid fires in extra (high) hazard environments.

2405.6 Flow-coating operations.

Flow-coating operations shall be conducted in compliance with the design, installation, operation and maintenance requirements for dip tanks. For such purposes, the sump and any areas on which paint flows shall be considered to be the area of a dip tank. Finishing products shall be supplied by a gravity tank not exceeding 10 gallons (37.9 L) in capacity or by direct low-pressure pumps arranged to shut down automatically in case of fire by means of approved heat-activated devices.

2405.7 Roll-coating operations.

Roll-coating operations shall comply with the requirements of FC 2405.6. In roll-coating operations utilizing flammable or combustible liquids, sparks from static electricity shall be prevented by electrically bonding and grounding all metallic rotating and other parts of machinery and equipment and by the installation of static collectors or by maintaining a conductive atmosphere such as a high relative humidity.

Section FC 2406. Powder Coating

Open this section

2406.1 General.

Operations using finely ground particles of protective finishing material applied in dry powder form by fluidized bed, electrostatic fluidized bed, powder spray guns or electrostatic powder spray guns shall be conducted in accordance with this section. When stationary electrostatic equipment is utilized, such operations shall additionally be conducted in accordance with FC 2407.

2406.2 Location.

Powder coating operations shall be conducted in spray rooms or spray booths located in accordance with FC 2404.

2406.3 Design and installation.

Powder coating operations shall be conducted in powder coating rooms and powder coating booths designed and installed in compliance with the requirements of this section.

2406.3.1 Construction of powder coating rooms.

Powder coating rooms shall be constructed of noncombustible materials.

2406.3.2 Construction of powder coating booths.

Powder coating booths shall be constructed in accordance with FC 2404.3.2, except that booth assemblies listed for such purpose and constructed in accordance with such listing may be constructed of materials other than as required by FC 2404.3.2.1.

2406.3.3 Fire protection.

Powder coating rooms and booths shall be protected by fire protection systems in accordance with this section.

2406.3.3.1 Fire extinguishing system.

Powder coating rooms and booths shall be protected throughout by a fire extinguishing system.

2406.3.3.2 Flame detection system.

Automated powder coating application equipment shall be protected by an approved, supervised flame detection device capable of detecting the presence of flame within 1/2 second, that shall, upon activation, automatically initiate the following actions:

1. Shut down electrical power and compressed air supply to the powder coating operation, including the conveyor, ventilation, application, transfer and powder collection systems.

2. Close segregation dampers in associated ductwork to interrupt airflows from application equipment to powder collectors.

3. Activate a local alarm audible within the powder coating room or booth and surrounding area.

2406.3.4 Drying, curing and fusion equipment.

Drying, curing and fusion equipment shall comply with the requirements of FC Chapter 30.

2406.3.5 Ventilation.

Exhaust ventilation and powder recovery systems shall be provided in accordance with Chapter 5 of the Mechanical Code.

2406.4 Operation and maintenance.

Facilities in which powder coating operations are conducted shall be operated and maintained in compliance with the requirements of this section.

2406.4.1 Housekeeping.

Powder coating areas, including horizontal surfaces such as ledges, beams, pipes, hoods, booths and floors, shall be kept free from the accumulation of powder coating dusts.

2406.4.2 Cleaning.

Surfaces shall be cleaned in such a manner as to avoid scattering dust or creating a dust cloud. Vacuum cleaning equipment shall be of a type approved for use in a hazardous location.

2406.4.3 Spark-producing metals.

Magnetic separators, filter-type separators, or other approved means shall be installed or used to prevent iron or other spark-producing metals from being introduced into the powders or the powder-coating operation.

2406.4.4 Preheating parts.

The temperature of the parts heated prior to coating shall not exceed the ignition temperature of the powder to be used.

2406.4.5 Sources of ignition.

Protection against sources of ignition shall be provided in accordance with FC 2403.2. Static bonding and grounding or other appropriate precautions shall be taken to minimize the possibility of ignition by static electrical sparks generated by powder transport, application and recovery systems.

2406.4.6 Portable fire extinguishers.

Powder coating rooms and booths shall be provided with portable fire extinguishers complying with the requirements of FC 906 and rated for flammable and combustible liquid fires in extra (high) hazard environments.

Section FC 2407. Electrostatic Spray-Finishing Equipment

Open this section

2407.1 General.

Electrostatic spray-finishing equipment used in connection with paint-spraying and paint-detearing operations shall be of an approved type, and shall be designed, installed, operated and maintained in accordance with this section.

2407.2 Location and clear space.

A space of at least twice the maximum potential sparking distance shall be maintained between the workpiece being painted or deteared and any electrodes, electrostatic atomizing heads or conductors.

Exception: Such distance is not required to be maintained between workpieces and portable electrostatic spray-finishing equipment listed for use in Class I, Division 1 locations.

2407.3 Design and installation.

Electrostatic spray-finishing equipment used in connection with paint-spraying and paint-detearing operations shall be designed and installed in compliance with the requirements of this section.

2407.3.1 Construction.

Electrodes and electrostatic atomizing heads shall be of approved construction, rigidly braced or otherwise supported to prevent movement and insulated from grounding by nonporous and noncombustible insulators.

Exception: Such bracing and insulation is not required to be provided for portable electrostatic spray-finishing equipment listed for use in Class I, Division 1 locations.

2407.3.1.1 Separation.

Electrostatic spray-finishing equipment shall be separated from other areas and operations by means of booths, fencing, railings or other barriers. Fencing, railings or other barriers shall be of conductive material, adequately grounded, and shall be placed not less than 5 feet (1524 mm) from the electrostatic spray-finishing equipment.

Exception: Such barrier and separation distance is not required to be provided for portable electrostatic spray-finishing equipment listed for use in Class I, Division 1 locations.

2407.3.2 Fire protection.

Electrostatic spray finishing operations shall be protected by fire protection systems in compliance with the requirements of this section.

2407.3.2.1 Fire extinguishing system.

Spraying areas shall be protected throughout by a fire extinguishing system complying with FC Chapter 9.

2407.3.2.2 Flame detection system.

Automated liquid electrostatic spray-finishing operation areas shall be protected by the installation of an approved, supervised flame detection system capable of detecting the presence of flame within 1/2 second, which shall, upon activation, automatically initiate the following actions:

1. Shut down electrical power to the electrostatic spray-finishing equipment, including the coating material delivery system and the conveyors into and out of the flammable vapor area, and terminating all spray-finishing operations.

2. Activate a local alarm in the spraying area, and the building fire alarm system if such a system is provided.

2407.3.3 Interlocks.

Electrostatic spray-finishing equipment shall be provided with emergency shut down devices and interlocks in compliance with the requirements of this section.

2407.3.3.1 Emergency shutdown.

Electrostatic spray-finishing equipment shall be equipped with automatic controls operating without time delay to disconnect the power supply to the high-voltage transformer and signal the operator under any of the following conditions:

1. Stoppage of ventilating fans or failure of ventilating equipment from any cause.

2. Stoppage of the conveyor carrying articles past the high-voltage grid.

3. Occurrence of a ground fault or an imminent ground fault at any point of the high-voltage system.

4. Reduction of clearance below that required in FC 2407.2.

2407.3.3.2 Ventilation interlock.

Electrostatic spray-finishing equipment utilizing hand-held sprayers shall be interlocked with the ventilation system for the spraying area so that the equipment cannot be operated unless the ventilating system is in operation.

2407.3.4 Ventilation.

Mechanical ventilation in the flammable vapor area shall be provided in accordance with Chapter 5 of the Mechanical Code.

2407.4 Operation and maintenance.

Facilities in which electrostatic spray-finishing operations are conducted shall be operated and maintained in compliance with the requirements of this section and FC 2403.3 and 2403.4, and FC 2407.4.1 through 2407.4.3.

2407.4.1 Cleaning.

Insulators shall be kept clean and dry. Drip plates and screens upon which paint is deposited shall be removable and shall be regularly removed and cleaned. Grounding connections for the electrostatic spray-finishing equipment shall be regularly cleaned so as to prevent overspray.

2407.4.2 Signage.

Durable signs that provide the following cautions and information shall be conspicuously posted:

1. Designate the process zone as dangerous with respect to fire and accident.

2. Restrict access to qualified personnel only.

3. Indicate the grounding requirements for all electrically conductive objects in the flammable vapor area, including persons working in that area.

4. Indicates the maximum potential sparking distance as set forth in FC 2407.2.

2407.4.3 Sources of ignition.

Transformers, power packs, control apparatus and all other electrical components of the electrostatic spray-finishing equipment, except high-voltage grids and electrostatic atomizing heads and connections, shall be located outside of the flammable vapor area or shall comply with the requirements of FC 2403.2.

Section FC 2408. Organic Peroxides and Dual-Component Coatings

Open this section

2408.1 General.

Spraying operations involving the use of organic peroxides and other dual-component coatings shall be conducted in accordance with this section and FC 2403.

2408.2 Design and construction.

Spraying operations involving the use of organic peroxides and other dual-component coatings shall be conducted in a facility designed and installed in accordance with this section.

2408.2.1 Construction.

Spraying operations shall be conducted in spray booths complying with the requirements of FC 2404.3.2.

2408.2.2 Fire extinguishing systems.

Spray booths shall be protected throughout by a sprinkler system.

2408.2.3 Equipment.

Spray guns and related equipment shall be of a type manufactured for such use.

2408.2.4 Pressure tanks.

Separate pressure vessels and inserts shall be used for the application of the resin and the organic peroxide, and shall not be interchanged. Organic peroxide pressure tank inserts shall be constructed of stainless steel or polyethylene.

2408.3 Operation and maintenance.

Facilities in which spraying operations involving the use of organic peroxides and other dual-component coatings are conducted shall be operated and maintained in compliance with the requirements of this section and FC 2403.3 and 2403.4, and FC 2408.3.1 through 2408.3.8.

2408.3.1 Contamination prevention.

Organic peroxide initiators shall not be contaminated with foreign substances.

2408.3.2 Spilled material.

Spilled organic peroxides shall be promptly removed so there are no residues. Spilled material absorbed by using a noncombustible absorbent shall be promptly removed from the premises and disposed of lawfully.

2408.3.3 Residue control.

Materials shall not be contaminated by dusts and overspray residues resulting from the sanding or spraying of finishing materials containing organic peroxides.

2408.3.4 Handling.

Handling of organic peroxides shall be conducted in a manner that avoids shock and friction that produces decomposition and violent reaction hazards.

2408.3.5 Mixing.

Organic peroxides shall not be mixed directly with accelerators or promoters.

2408.3.6 Personnel qualifications.

Personnel working with organic peroxides and dual-component coatings shall be specifically trained to work with these materials.

2408.3.7 Storage.

The storage of organic peroxides shall be in accordance with FC Chapter 62.

2408.3.8 Sources of ignition.

Only nonsparking tools shall be used in areas where organic peroxides are stored, mixed or applied.

Section FC 2409. Indoor Manufacturing of Reinforced Plastics

Open this section

2409.1 General.

Indoor manufacturing processes involving spray or hand application of reinforced plastics and using more than 5 gallons (19 L) of resin in a 24-hour period shall be conducted in accordance with this section and FC 2408.

2409.2 Design and installation.

Indoor manufacturing processes involving spray or hand application of reinforced plastics shall be conducted in a facility designed and installed in compliance with the requirements of this section.

2409.2.1 Fire protection.

Resin application areas shall be protected throughout by a sprinkler system. The sprinkler system design shall not be less than that required for Ordinary Hazard, Group 2, with a minimum design area of 3,000 square feet (279 m 2 ). Where the materials or storage arrangements are required by other regulations to be provided with a higher level of sprinkler system protection, the higher level of sprinkler system protection shall be provided.

2409.2.2 Ventilation.

Mechanical ventilation shall be provided in resin application areas in accordance with Chapter 5 of the Mechanical Code. The ventilation rate shall be adequate to maintain the concentration of flammable vapors in the resin application area at or below 25 percent of the lower flammable limit (LFL).

Exception: Mechanical ventilation is not required for buildings that are unenclosed for at least 75 percent of the perimeter.

2409.2.2.1 Local ventilation.

Local ventilation shall additionally be provided inside of workpieces where personnel will be under or inside of the workpiece.

2409.2.3 Sources of ignition.

Sources of ignition in resin application areas shall comply with the requirements of FC 2403.2.

2409.3 Operation and maintenance.

Facilities in which indoor manufacturing processes involving spray or hand application of reinforced plastics are conducted shall be operated and maintained in compliance with the requirements of this section and FC 2403.3 and 2403.4.

2409.3.1 Handling of excess catalyzed resin.

A noncombustible, open-top container shall be provided for disposal of excess catalyzed resin. Excess catalyzed resin shall be drained into the container while still in the liquid state. Enough water shall be provided in the container to maintain a minimum 2-inch (51-mm) water layer over contained resin.

2409.3.2 Control of overchop.

In areas where chopper guns are used, exposed wall and floor surfaces shall be covered with paper, polyethylene film or other approved material to allow for removal of overchop. Overchop shall be allowed to cure for not less than 4 hours prior to removal of the wall and floor coverings. Used coverings shall be placed in a noncombustible container and removed from the premises.

2409.3.3 Storage and use of hazardous materials.

Storage and use of organic peroxides shall be in accordance with FC 2408 and FC Chapter 62. Storage and use of flammable and combustible liquids shall be in accordance with FC Chapter 57. Storage and use of unstable (reactive) materials shall be in accordance with FC Chapter 66.

Section FC 2410. Floor Finishing Operations

Open this section

2410.1 Scope.

All floor finishing operations using Class I or Class II liquids shall be conducted in accordance with FC 2410.1.1 and 2410.1.2. Floor finishing operations exceeding 168 square feet (15.6 m 2 ) and using Class I or Class II liquids shall additionally be conducted in accordance with FC 2410.2 through 2410.5.

2410.1.1 Prohibitions.

It shall be unlawful to:

1. Use flammable floor finishing products with a flash point below 80°F (27°C) indoors.

2. Smoke, use or maintain open flames, including torches, in rooms or other indoor areas in which floor finishing products are being stored and/or in which floor finishing operations are being conducted.

3. Conduct floor finishing operations in rooms or other indoor areas occupied by anyone other than the individuals engaged in such operations.

2410.1.2 General requirements.

All floor finishing operations shall comply with the following requirements:

1. Floor finishing operations shall be conducted in accordance with the manufacturer's instructions for the storage, handling and use of floor finishing products.

2. Flammable or combustible liquids or mixtures, other than floor finishing products, stored, handled or used in connection with floor finishing operations shall be stored, handled or used in accordance with FC Chapter 57.

3. Floor finishing product containers shall be closed when not in use.

4. Empty containers of floor finishing products and all other floor finishing product waste and residue shall be removed from the premises not less than once a day.

5. Gas burners, pilot lights, electrical devices, electronic devices and other sources of ignition in flammable vapor areas shall be shut off prior to commencing work.

6. At least one portable fire extinguisher with a minimum rating of 20-B shall be readily accessible during floor finishing operations. The travel distance to such extinguisher shall not exceed 30 feet (9144 mm).

7. Quantities of floor finishing products at a site shall not exceed the amount necessary for that day's operations. In no circumstance shall such quantity exceed 20 gallons (76 L).

2410.2 Occupancy of premises during operations.

Floor finishing operations shall not be conducted in occupied rooms or other areas. If occupants are allowed to return to the premises in which the floor finishing operations were conducted before the surfaces have dried, fire safety precautions shall be maintained and the occupants shall be given written instructions in regard thereto. Floor finishing operations shall not be conducted in a Group A or Group M occupancy while the premises is open to the public.

2410.3 Sources of ignition.

No electrical equipment or device that is a potential source of ignition of floor finishing product vapors, including switches and outlets, shall be operated during floor finishing operations. Precautions shall be taken prior to commencing work to prevent inadvertent operation of such equipment or devices, such as shutting down electrical power, unplugging equipment and taping over switches and outlets.

2410.4 Mechanical system operation.

Heating, ventilation and air-conditioning systems shall not be operated during floor finishing operations and for the period of time thereafter until the surfaces have dried.

2410.5 Ventilation.

To prevent the accumulation of flammable vapors, mechanical ventilation at a minimum rate of 1 cubic foot per minute per square foot (0.00508 m 3 /s/m 2 ) of the area being surfaced or finished shall be provided. Such ventilation shall be by approved temporary or portable means. Vapors shall be exhausted outdoors. Such ventilation equipment shall be kept in operation while the floor finishing operations are being conducted and for a period of time thereafter to allow for the exhaust of the vapors.

2410.6 Retail sale.

Floor finishing products with a flash point below 80°F (27°C) shall be provided with a conspicuous and durable tag bearing the words, "WARNING: INDOOR USE OF THIS PRODUCT IS PROHIBITED IN NEW YORK CITY." A sign shall be conspicuously posted in the area in which the floor finishing product is displayed, warning that the product is prohibited for indoor use in New York City.

Section FC 2501. General

Open this section

2501.1 Scope.

This chapter shall govern the design, installation, operation and maintenance of facilities in which ethylene gas is used, other than in self-contained equipment, to promote the ripening of fruits, vegetables and other crops.

Exception: Mixtures of ethylene and one or more inert gases in concentrations which prevent the gas from reaching greater than 25 percent of the lower explosive limit (LEL) when released to the atmosphere.

2501.2 Permits.

Permits shall be required as set forth in FC 105.6.

2501.3 Ethylene generators.

Approved ethylene generators shall be operated and maintained in accordance with FC 2506.

2501.4 General.

Facilities using ethylene gas to promote the ripening of fruits, vegetables and other crops shall be designed, installed, operated and maintained in accordance with this chapter.

Section FC 2502. Definitions

Open this section

2502.1 Terms defined in FC Chapter 2.

Terms used in this chapter and defined in FC 202 shall have the meanings set forth therein.

Section FC 2503. Ethylene Gas

Open this section

2503.1 Location.

Ethylene gas shall be discharged only into approved rooms or enclosures designed and constructed for this purpose.

2503.2 Dispensing.

Valves controlling discharge of ethylene shall provide positive and fail-closed control of flow and shall be set to limit the concentration of gas in air below 1,000 parts per million (ppm).

Section FC 2504. Sources of Ignition

Open this section

2504.1 Ignition prevention.

Sources of ignition shall be controlled or protected in accordance with this section and FC Chapter 3.

2504.2 Electrical wiring and equipment.

Electrical wiring and equipment, including luminaires, shall be approved for use in Class I, Division 2, Group C hazardous (classified) locations.

2504.3 Static electricity.

Devices, equipment and systems, including containers and piping, used to dispense ethylene, shall be bonded and grounded to prevent the discharge of static sparks or arcs.

2504.4 Lighting.

Lighting shall be by approved electric lamps or luminaires only.

2504.5 Heating.

Heating shall be by indirect means utilizing low-pressure steam, hot water, or warm air.

Exception: Electric or fuel-fired heaters approved for use in hazardous (classified) locations which are installed and operated in accordance with the Electrical Code, the Mechanical Code or the Fuel Gas Code.

Section FC 2505. Combustible Waste

Open this section

2505.1 Housekeeping.

Empty boxes, cartons, pallets and other combustible waste shall be removed from ripening rooms or enclosures and properly disposed of at the end of each work shift, but at least once a day.

Section FC 2506. Ethylene Generators

Open this section

2506.1 Ethylene generators.

Ethylene generators shall be listed and labeled by an approved testing laboratory and used only in approved rooms in accordance with the ethylene generator manufacturer's instructions. The listing evaluation shall include documentation that the concentration of ethylene gas does not exceed 25 percent of the lower explosive limit (LEL).

2506.2 Ethylene generator rooms.

Ethylene generators shall be used in rooms having a volume of not less than the minimum room size provided for in the manufacturer's specifications and testing laboratory listing, but in no case less than 1,000 cubic feet (28 m 3 ). Rooms shall have air circulation to ensure even distribution of ethylene gas and shall be free from sparks, open flames or other ignition sources.

Section FC 2507. Warning Signs

Open this section

2507.1 Required warning sign.

Approved warning signs identifying the hazard and indicating the danger involved and necessary precautions shall be posted on all doors and entrances to the premises in accordance with FC Chapter 50.

Section FC 2601. General

Open this section

2601.1 Scope.

This chapter shall govern fumigation and insecticidal fogging operations within buildings and structures.

2601.2 Permits.

Permits shall be required as set forth in FC 105.6.

2601.3 General.

Fumigation and insecticidal fogging operations within buildings and structures shall be conducted in accordance with this chapter.

2601.4 Supervision.

Fumigation and insecticidal fogging operations shall be supervised in accordance with FC 2601.4.1 and 2601.4.2.

2601.4.1 Fumigation and insecticidal fogging operation company certificate.

Persons engaged in the business of fumigation and insecticidal fogging operations shall obtain a fumigation and insecticidal fogging operation company certificate.

2601.4.2 Fumigation and insecticidal fogging operations.

Fumigation and insecticidal fogging operations requiring a permit or a company certificate shall be conducted by or under the personal supervision of a person holding a certificate of fitness.

2601.5 Compliance with other provisions of law.

Fumigation and insecticidal fogging operations shall comply with all applicable federal, state and city laws, rules and regulations.

2601.6 Prohibitions.

It shall be unlawful to:

1. Use insecticidal fogging liquids with a flash point below 100°F (38°C).

2. Use carbon disulfide and hydrogen cyanide for fumigation unless conducted on a premises used solely for agriculture.

Section FC 2602. Definitions

Open this section

2602.1 Definitions.

The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.

FUMIGANT.

FUMIGATION.

FUMIGATION AND INSECTICIDAL FOGGING OPERATION COMPANY CERTIFICATE.

INSECTICIDAL FOGGING.

Section FC 2603. Fire Safety Requirements

Open this section

2603.1 General.

Fumigation and insecticidal fogging operations in buildings and structures shall be conducted in compliance with the fire protection and safety requirements of FC 2603.2 through 2603.5.

2603.2 Sources of ignition.

Open flames and similar sources of ignition shall be removed from the space in which fumigation or insecticidal fogging operations are being conducted. Heating, where needed, shall be of an approved type.

2603.2.1 Electricity.

Electricity in any part of the building or structure where operation of switches or electrical devices, equipment and systems could serve as a source of ignition during and for a reasonable time after any fumigation or insecticidal fogging operation shall be shut off.

Exception: Circulating fans that have been specifically designed for utilization in hazardous atmospheres and installed in accordance with the Electrical Code.

2603.2.2 Electronic devices.

Electronic devices, including portable equipment and cellular phones, shall be shut off. Telephone lines shall be disconnected from telephones.

2603.3 Notification.

The department shall be notified in writing at least 48 hours before the building or structure is to be closed in connection with the utilization of any toxic or flammable fumigant. Notification shall give the location of the enclosed space to be fumigated or fogged, the occupancy, the fumigants or insecticides to be utilized, the person or persons responsible for the operation, and the date and time at which the operation will begin. Written notice of any fumigation or insecticidal fogging operation shall be given to all affected occupants of the building, structure or portion thereof in which such operations are to be conducted, with sufficient advance notice to allow all such spaces to be vacated in an orderly manner. Such notice shall inform the occupants as to the purposes and anticipated duration of the fumigation operations.

2603.3.1 Warning signs.

Approved warning signs indicating the danger, type of chemical involved and necessary precautions shall be posted on all doors and entrances to the premises and upon all gangplanks and ladders from the deck, pier or land to the marine vessel or watercraft. Such notices shall be printed in red ink on a white background. Letters in the headlines shall be at least 2 inches (51 mm) in height and shall state the date and time of the operation, the name and address of the person conducting the fumigation or insecticidal fogging, the name of the operator in charge, and a warning stating that the occupied premises shall be vacated at least 1 hour before the operation begins and shall not be reentered until the danger signs have been removed by the proper authorities. Advance notice shall be given to all occupants of the building or structure where fumigation and insecticidal fogging operations are to be conducted to warn of the hazards of such operation.

2603.3.2 Reserved.

2603.3.3 Watchperson.

During the period fumigation is in progress, except when fumigation is conducted in a gas-tight vault or tank, one or more watchpersons shall be provided at each entrance to the space being fumigated to prevent entry into such space until the fumigation is completed and the premises is properly ventilated and safe for occupancy.

2603.4 Wrapping of buildings.

Paper and other similar combustible materials that do not meet the flame propagation performance criteria of NFPA 701 shall not be used to wrap or cover a building in excess of that required for the sealing of cracks, casements and similar openings.

2603.5 Ventilation and cleanup.

At the end of the exposure period, fumigators shall safely and properly ventilate the premises and contents; properly dispose of fumigant containers, residues, debris and other waste materials; and clear obstructions from gas-fired appliance vents.