NYC Administrative Code § 27-863.01 Chimney limitations and tests
No solid fuel fireplace, fireplace stove or room heater shall be installed or altered unless connected to a chimney which complies with the limitations and testing requirements set forth in table 15-6.1.
TABLE 15-6.1 Chimney Limitations and Tests for Solid Fuel Fireplaces, Fireplace Stoves and Room Heaters
Occupancy Reference Standard Test Standard Temperature Number of Tests J-2 & J-3 limited to 40 feet and three stories RS 15-15 UL 127, as Modified 1700°F 1 test J-2 & J-3 limited RS 15-9 UL 103HT 2100°F – 10 min. 3 tests to 75 feet RS 15-12 ULC 629M 2100°F – 30 min. 3 tests All other occupancies and all buildings greater than 75 feet in height RS 15-10 UL 959 2000°F to Equilibrium and 2300°F – 30 min. 1 test 3 tests Table 15-6 of Subdivision (c) of Section 27-863 and Section 27-861 No Standard Unlisted High Temp. Chimney with Required Thickness Listed in Table 15-6 No test
Note: Chimneys accepted pursuant to reference standard RS 15-10 or Table 15-6 may be used in lieu of chimneys accepted pursuant to reference standards RS 15-9, RS 15-12 and RS 15-15.Chimneys accepted pursuant to reference standards RS 15-9 or RS 15-12 may be used in lieu of chimneys accepted pursuant to reference standard RS 15-15.