NYC Administrative Code Title 28, Chapter 7 New York City Building Code, part 14 of 33
Section BC 1208 to Section BC 1509: 26 sections.
Section BC 1208. Interior Space Dimensions
1208.1 Minimum room widths.
Habitable spaces, other than a kitchen, shall be not less than 8 feet (2438.4 mm) in any plan dimension. Kitchens and kitchenettes shall have a clear passageway of not less than 3 feet (914.4 mm) between counter fronts and appliances or counter fronts and walls.
Exceptions:
1. A room that complies with the requirements for natural light and natural ventilation and in addition has an unobstructed opening of not less than 60 square feet (5.6 m 2 ) into an immediately adjoining room shall be not less than 7 feet (2133.6 mm) in any plan dimension.
2. A habitable dining space that complies with the requirements for natural light and natural ventilation may be less than 8 feet (2438.4 mm) in any plan dimension.
3. One-half the number of bedrooms in a dwelling unit containing 3 or more bedrooms shall be not less than 7 feet (2133.6 mm) in any plan dimension.
4. A room in a group R-1 dwelling or sleeping unit shall be not less than 6 feet (1828.8 mm) in any plan dimension.
1208.2 Minimum ceiling heights.
Habitable rooms and spaces shall have a ceiling height of not less than 8 feet (2438.4 mm). Occupiable spaces and corridors shall have a ceiling height of not less than 7 feet 6 inches (2286 mm). Bathrooms, toilet rooms, kitchens in other than Group I-1 and R occupancies, kitchenettes in Group I-1 or R occupancies, storage rooms and laundry rooms shall have a ceiling height of not less than 7 feet (2133.6 mm). All measurements shall be taken from the finished floor to the finished underside of the ceiling or ceiling beams.
Exceptions:
1. In one- and two-family dwellings, beams or girders spaced not less than 4 feet (1220 mm) on center may project not more than 6 inches (152.4 mm) below the required ceiling height, provided that a clear height of 7 feet (2133.6 mm) is maintained.
2. Habitable rooms in basements of one- or two-family dwellings, including any projecting beams, shall have a ceiling height of not less than 7 feet (2133.6 mm).
3. Habitable rooms in basements of multiple dwellings may have as many as four beams crossing the ceiling if none of the beams exceeds 12 inches (304.8 mm) in width or extends below the ceiling more than 6 inches (152.4 mm).
4. Spaces above and below a mezzanine, other than habitable spaces, shall have a ceiling height of not less than 7 feet (2133.6 mm).
1208.2.1 Furred ceiling.
Any room with a furred ceiling shall be required to have the minimum ceiling height in two-thirds of the area thereof, but in no case shall the height of the furred ceiling be less than 7 feet (2133.6 mm).
Exception: Minimum ceiling heights of habitable rooms and spaces shall be not less than established in Section 1208.2.
1208.3 Room area.
Minimum net floor areas of rooms shall be in accordance with Sections 1208.3.1 and 1208.3.2
1208.3.1 Habitable rooms and spaces.
Every habitable room or space shall have not less than 80 square feet (7.4 m 2 ) in net floor area.
Exceptions:
1. A room that complies with the requirements for natural light and natural ventilation and in addition has an unobstructed opening of not less than 60 square feet (5.6 m 2 ) into an immediately adjoining room shall have not less than 70 square feet (6.5 m 2 ) of net floor area.
2. A habitable dining space, as defined by the New York City Housing Maintenance Code, that complies with the requirements for natural light and natural ventilation may have less than 80 square feet (7.4 m 2 ) of net floor area.
3. A room in a Group R-1 dwelling unit shall have not less than 60 square feet (5.6 m 2 ) of net floor area.
1208.3.2 Dwelling units.
In a dwelling unit, at least one habitable room shall have not less than 150 square feet (13.9 m 2 ) of net floor area.
Exception: Group R-1 dwelling or sleeping units.
1208.3.2.1 Single room occupancy of a single room.
Where a single room within a dwelling unit is used for single room occupancy, as such term is used in Section 27-2074(e) of the New York City Housing Maintenance Code, such room shall have not less than 150 square feet (13.9 m 2 ) of net floor area.
1208.3.2.2 Single room occupancy of a suite of rooms.
Where two or more rooms, joined together and separated from all other rooms within a dwelling unit, are used for single room occupancy, as such term is used in Section 27-2074(e) of the New York City Housing Maintenance Code, at least one of such separated rooms shall have not less than 150 square feet (13.9 m 2 ) of net floor area.
1208.4 Reserved.
Section BC 1209. Access to Unoccupied Spaces
1209.1 Crawl spaces.
Crawl spaces shall be provided with not fewer than one access opening that shall be not less than 18 inches by 24 inches (457.2 mm by 609.6 mm). All crawl spaces shall have a minimum clear height of 18 inches (457.2 mm).
1209.2 Attic spaces.
An opening not less than 20 inches by 30 inches (508 mm by 762 mm) shall be provided to any attic area having a clear height of over 30 inches (762 mm). Clear headroom of not less than 30 inches (762 mm) shall be provided in the attic space at or above the access opening.
1209.3 Mechanical appliances.
Access to mechanical appliances installed in under-floor areas, in attic spaces and on roofs or elevated structures shall be in accordance with the New York City Mechanical Code.
Section BC 1210. Toilet and Bathroom Requirements
1210.1 Required fixtures.
The number and type of plumbing fixtures provided in any occupancy shall comply with the New York City Plumbing Code.
1210.2 Finish materials.
Walls, floors and partitions in toilet and bathrooms shall comply with Sections 1210.2.1 through 1210.2.4.
1210.2.1 Floors and wall bases.
In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches (101.6 mm).
Exception: Group I-1, R-1 and R-2 occupancies shall have a vertical base that extends upward onto walls at least 6 inches (152.4 mm).
1210.2.2 Walls and partitions.
Walls and partitions within 2 feet (609.6 mm) of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet (1220 mm) above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Exceptions:
1. Dwelling units.
2. Toilet rooms that are not accessible to the public and that have not more than one water closet.
Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture.
1210.2.3 Showers.
Shower compartments and walls above bathtubs with installed shower heads shall be finished with a smooth, nonabsorbent surface to a height not less than 72 inches (1828.8 mm) above the drain inlet.
1210.2.4 Waterproof joints.
Built-in tubs with showers shall have waterproof joints between the tub and adjacent wall.
1210.3 Privacy.
Privacy at water closets and urinals shall be provided in accordance with Sections 1210.3.1 and 1210.3.2.
1210.3.1 Water closet compartment.
Each water closet utilized by the public or employees shall occupy a separate compartment with walls or partitions and a door enclosing the fixtures for privacy.
Exceptions:
1. Water closet compartments shall not be required in a single-occupant toilet room with a lockable door.
2. Toilet rooms located in child day care facilities and containing two or more water closets shall be permitted to have one water closet without an enclosing compartment.
3. This provision is not applicable to toilet areas located within Group I-3 occupancy housing areas.
1210.3.2 Urinal partitions.
Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The walls or partitions shall begin at a height not more than 12 inches (304.8 mm) from and extend not less than 60 inches (1524 mm) above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal not less than 18 inches (457.2 mm) or to a point not less than 6 inches (152.4 mm) beyond the outermost front lip of the urinal measured from the finished backwall surface, whichever is greater.
Exceptions:
1. Urinal partitions shall not be required in a single-occupant or family or assisted-use toilet room with a lockable door.
2. Toilet rooms located in child day care facilities and containing two or more urinals shall be permitted to have one urinal without partitions.
1210.4 Toilet rooms.
Toilet rooms shall not open directly into a room used for the preparation of food for service to the public. In multiple dwellings no toilet room or bathroom shall open onto any kitchen or kitchenette.
Section BC 1211. Kitchens and Kitchenettes
1211.1 Sleeping.
No kitchen or kitchenette shall be occupied for sleeping purposes.
1211.2 Kitchenettes in multiple dwellings.
Except at entrances thereto, every kitchenette in a multiple dwelling shall be surrounded by partitions extending from floor to ceiling, and/or by a soffit dropped 1 foot (304.8 mm) from the ceiling.
Section BC 1212. Rodentproofing
1212.1 General.
Rodentproofing shall be in accordance with Appendix F.
Section BC 1213. Refuse and Recyclable Storage
1213.1 General.
Multiple dwellings shall comply with Section 81 of the New York State Multiple Dwelling Law and Section 27-2021 of the New York City Housing Maintenance Code. In Group R-2 occupancies, space shall be provided for the storage of refuse and recyclables as a common accessory space. The location of such refuse and recyclables storage space shall be clearly identified on the construction documents and configured to permit separate unobstructed access by building personnel to stored refuse and recyclables. Such refuse and recyclables storage space shall be a minimum of 1.5 square feet (0.140 m 2 ) per dwelling unit, or a minimum of 350 square feet (32.516 m 2 ), whichever is less, for the storage of collected refuse and recyclables.
Exceptions:
1. In multiple dwellings required to have a compactor in accordance with Section 1213.2, such refuse and recyclables storage space shall be, in addition to space required for equipment or circulation, a minimum of 1.0 square foot (0.094 m 2 ) per dwelling unit, or a minimum of 350 square feet (32.516 m 2 ), whichever is less, for the storage of collected refuse and recyclables.
2. Refuse and recyclables storage space shall not be required in multiple dwellings equipped with a chute system that provides for source separation of refuse and recyclable materials without cross contamination and an integrated mechanical system to transport such materials off-site that has been approved by the commissioner.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2012/060.
1213.1.1 Interior space.
Where an interior room is provided for the storage of refuse and recyclables, such room shall be completely enclosed by construction that has a fire-resistance rating of not less than 2 hours, with self-closing opening protectives having a fire protection rating of not less than 1 1/2 hours.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2012/060.
1213.1.2 Exterior space.
Where space is provided on the exterior of a building for the storage of refuse and recyclables, such refuse and recyclables storage space shall include a minimum of 4 square feet (0.372 m 2 ) in addition to the space per dwelling unit required by Section 1213.1, shall be clearly identified on the construction documents, and shall not be located in the public right-of-way.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2012/060.
1213.2 Compactor.
A refuse compacting system shall be provided in multiple dwellings in Group I-1 or R-2 occupancy that are four or more stories in height and contain 12 or more dwelling units, and in buildings of any size occupied as a Group R-1 multiple dwelling. Such system shall be located within a refuse storage room constructed in accordance with Section 1213.1 or in a refuse chute termination room constructed in accordance with Section 713.13.4. The floor within such room shall be constructed of concrete and shall be sloped to a floor drain connected to the building sewer. A hose connection shall be provided within such room.
1213.3 Refuse chute.
A multiple dwelling that is five or more stories in height and that contains 9 or more dwelling units shall be provided with a refuse chute, chute access rooms, and refuse chute termination room constructed in accordance with Section 713.13. A minimum of 5 square feet (0.470 m 2 ) of floor area within each refuse chute access room shall be provided for the temporary holding of recyclables. Such floor area shall be clearly identified on the construction documents. In Group I-1 and R-1 occupancies, access to the chute access room shall be permitted to be restricted to employees provided that separate refuse storage rooms are located on each story for general occupant use.
Exceptions:
1. In buildings without an elevator, floor area within refuse chute access rooms for the temporary holding of recyclables is not required.
2. In buildings equipped with separate chutes designated for refuse, for paper and cardboard, and for metal, glass and plastic, and in buildings equipped with a chute system that provides for source separation of recyclable materials without cross contamination, floor area within refuse chute access rooms for the temporary holding of recyclables is not required. Chutes for designated recyclable materials shall be constructed in accordance with Section 713.13 of this code.
3. The refuse chute and the occupant use storage rooms shall not be required in transient hotels meeting the following requirements:
3.1 the refuse is removed from rooms by a daily cleaning service, with the staff using a service elevator that is not accessed by hotel guests;
3.2 the building is of Type I or Type II construction; or
3.3 a compactor and refuse storage room is provided in accordance with Section 1213.2.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2012/060.
1213.3.1 Refuse Chute Access Room Floor and Wall Base Finish Materials.
Refuse chute access rooms shall have a smooth, hard and nonabsorbent surface. The intersection of such floors with walls shall have a smooth, hard and nonabsorbent vertical base that extends upward onto the walls at least 4 inches (101.6 mm).
Section BC 1301. General
1301.1 Scope.
This chapter governs the design and construction of buildings for energy efficiency.
1301.1.1 Criteria.
Buildings shall be designed and constructed in accordance with the New York City Energy Conservation Code.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/085.
Section BC 1401. General
1401.1 Scope.
The provisions of this chapter shall establish the minimum requirements for exterior: walls; wall coverings; wall openings; windows and doors; architectural trim; balconies; projections; and other appendages.
1401.2 Construction documents.
Construction documents for exterior wall coverings required to be tested in accordance with NFPA 285 pursuant to this code shall include the following data and information:
1. Design documentation of the NFPA 285 tested assembly from the manufacturer shall be included in the construction documents. This shall include section and elevation drawings that identify materials and components of the tested assembly, including panel sizes and joint locations. All components used in the tested assembly shall be clearly identified. Material thicknesses, relative locations of components and offsets shall be fully dimensioned.
2. Information shall be provided for verification in accordance with Sections 1705.16 and 1705.20 special inspections.
3. A certification by the applicant that "Any deviation which occurs during the course of installation will be evaluated and approved by the applicant of record or registered design professional. No deviation shall be approved that would result in an assembly that would otherwise fail to pass the acceptance criteria of NFPA 285."
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
Section BC 1402. Definitions
1402.1 Definitions.
The following terms are defined in Chapter 2:
ADHERED MASONRY VENEER.
ANCHORED MASONRY VENEER.
BACKING.
BIRD FRIENDLY MATERIAL.
BIRD HAZARD INSTALLATIONS.
CURTAIN WALL.
EXTERIOR INSULATION AND FINISH SYSTEMS (EIFS).
EXTERIOR INSULATION AND FINISH SYSTEMS (EIFS) WITH DRAINAGE.
EXTERIOR WALL.
EXTERIOR WALL COVERING.
EXTERIOR WALL ENVELOPE.
FENESTRATION.
FIBER-CEMENT SIDING.
FLY-THROUGH CONDITIONS.
HIGH-PRESSURE DECORATIVE EXTERIOR-GRADE COMPACT LAMINATE (HPL).
METAL COMPOSITE MATERIAL (MCM).
METAL COMPOSITE MATERIAL (MCM) SYSTEM.
POLYPROPYLENE SIDING.
PORCELAIN TILE.
VENEER.
VINYL SIDING.
WATER-RESISTIVE BARRIER.
(Am. L.L. 2020/015, 1/10/2020, eff. 1/10/2021)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2020/015.
Section BC 1403. Performance Requirements
1403.1 General.
The provisions of this section shall apply to exterior walls, exterior wall coverings and components thereof.
1403.2 Weather protection.
Exterior walls shall provide the building with a weather-resistant exterior wall envelope. The exterior wall envelope shall include flashing, as described in Section 1405.4. The exterior wall envelope shall be designed and constructed in such a manner as to prevent the accumulation of water within the wall assembly by providing a water-resistive barrier behind the exterior veneer, as described in Section 1404.2, and a means for draining water that enters the assembly to the exterior. Protection against condensation shall be provided as required.
Exceptions:
1. A weather-resistant exterior wall envelope shall not be required over concrete and masonry walls designed to resist water penetration and detrimental effects from freeze/thaw cycling and in accordance with Chapters 19 and 21 of this code, as applicable.
2. Compliance with the requirements for a means of drainage, and the requirements of Sections 1404.2 and 1405.4 of this code, shall not be required for an exterior wall envelope that has been demonstrated through testing to resist wind-driven rain, including joints, penetrations and intersections with dissimilar materials, in accordance with ASTM E 331 under the following conditions:
2.1. Exterior wall envelope test assemblies shall include at least one opening, one control joint, and where required one wall/eave interface and one wall sill. Tested openings and penetrations shall be representative of the intended end-use configuration.
2.2. Exterior wall envelope test assemblies shall be at least 4 feet by 8 feet (1220 mm by 2438.4 mm) in size.
2.3. Exterior wall envelope assemblies shall be tested at a minimum differential pressure of 6.24 pounds per square foot (psf) (0.297 kN/m 2 ) for a duration of 2 hours. The exterior wall envelope assemblies shall also be tested at a minimum differential pressure not less than 20 percent of the positive design wind load as calculated per Chapter 16, or 15 pounds per square foot (psf) (0.718 kN/m 2 for a duration of 15 minutes.
2.4. The exterior wall envelope design shall be considered to resist wind-driven rain where the results of testing indicate that water did not penetrate the test assembly including control joints in the exterior wall envelope, joints at the perimeter of openings or intersections of terminations with dissimilar materials.
3. Exterior insulation and finish systems (EIFS) complying with Section 1408.4.1.
1403.3 Structural.
Exterior wall envelope, and the associated openings, shall be designed and constructed to resist safely the superimposed loads required by Chapter 16.
1403.4 Fire resistance.
Exterior wall envelope shall be fire-resistance rated as required by other sections of this code with opening protection as required by Chapter 7.
1403.5 Vertical and lateral flame propagation.
Exterior walls that contain foam plastic insulation including exterior insulation and finish systems (EIFS), metal composite material (MCM) systems, high-pressure decorative exterior-grade compact laminates (HPL), and fiber-reinforced polymer (FRP) shall be tested in accordance with and comply with the acceptance criteria of NFPA 285. Foam plastic insulation assemblies and FRP shall be tested in accordance with Section 2603.5.5. MCM systems shall be tested in accordance with Section 1407.11. HPL systems shall be tested in accordance with Section 1409.11. Approved NFPA 285 tested assembly design documentation shall be included on the submitted construction documents complying with Section 1401.2. Deviation from the NFPA 285 tested design shall be approved by the registered design professional and additional documentation shall be provided if requested by the department. Combustible exterior wall coverings shall comply with Section 1406 of this code.
Exception: Fiber-reinforced polymer (FRP) where permitted by Section 2613.5 not to be tested.
1403.5.1 Exterior walls with water-resistive barriers.
Exterior walls on buildings of Type I, II, III, or IV construction that are greater than 40 feet (12 192 mm) in height above grade plane and contain a combustible water-resistive barrier shall be tested in accordance with and comply with the acceptance criteria of NFPA 285. For the purposes of this section, fenestration products and flashing of fenestration products and water-resistive barrier flashing and accessories at other locations, including through wall flashings and attachment accessories, shall not be considered part of the water-resistive barrier.
Exceptions:
1. Walls in which the water-resistive barrier is the only combustible component and the exterior wall has a wall covering of brick, concrete, stone, terra cotta, stucco or steel with minimum thicknesses in accordance with Table 1405.2 of this code.
2. Walls in which the water-resistive barrier is the only combustible component and the water-resistive barrier has a peak heat release rate of less than 150 kW/m2 (203.9 hp/m 2 ), a total heat release of less than 20 MJ/m2 (18 956 BTU/m 2 ) and an effective heat of combustion of less than 18 MJ/kg (17 060 BTU/lb) as determined in accordance with ASTM E 1354 and has a flame spread index of 25 or less and a smoke-developed index of 450 or less as determined in accordance with ASTM E 84 or UL 723. The ASTM E 1354 test shall be conducted on specimens at the thickness intended for use, in the horizontal orientation and at an incident radiant heat flux of 50 kW/m 2 .
1403.6 Flood resistance.
For buildings in flood hazard areas, the exterior wall envelope extending below the design flood elevation shall be resistant to water damage and shall comply with Appendix G.
1403.7 Thermal and condensation resistance.
The exterior wall envelope shall be designed and constructed for thermal and condensation resistance as necessary to meet the requirements of the New York City Energy Conservation Code.
1403.8 Bird friendly materials.
Bird friendly materials shall be required in accordance with Sections 1403.8.1 through 1403.8.4.
(L.L. 2020/015, 1/10/2020, eff. 1/10/2021)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2020/015.
1403.8.1 Exterior wall envelope.
The exterior wall envelope, and any associated openings, shall be constructed with bird friendly materials up to 75 feet (22 860 mm) above grade. Materials other than bird friendly materials shall not exceed an aggregate of 10 square feet (0.93 m 2 ) within any 10 feet (3048 mm) by 10 feet (3048 mm) square area of exterior wall below 75 feet (22 860 mm) above grade.
Exceptions:
1. Where ground floor transparency is required by the New York City Zoning Resolution, transparent bird friendly material with a UV-reflective pattern and a maximum threat factor of 27 shall be provided.
2. In areas of special flood hazard and shaded X-Zones where flood resistant glazing is proposed and ground floor transparency is required by the New York City Zoning Resolution, transparent bird friendly material with a UV-reflective pattern and a maximum threat factor of 36 shall be provided.
(L.L. 2020/015, 1/10/2020, eff. 1/10/2021)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2020/015.
1403.8.2 Bird hazard installations.
Bird hazard installations shall be constructed of bird friendly materials regardless of their height above grade.
(L.L. 2020/015, 1/10/2020, eff. 1/10/2021)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2020/015.
1403.8.3 Fly-through conditions.
Fly-through conditions located 75 feet (22 860 mm) or less above grade shall be constructed with bird friendly materials.
(L.L. 2020/015, 1/10/2020, eff. 1/10/2021)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2020/015.
1403.8.4 Adjacency to green roofs.
The exterior wall envelope, and any associated openings, installed adjacent to a green roof system on the same building shall be constructed with bird friendly materials up to 12 feet (3657.6 mm) above the walking surface.
(L.L. 2020/015, 1/10/2020, eff. 1/10/2021)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2020/015.
1403.9 Air barrier.
The exterior wall envelope shall be designed and constructed with an air barrier as necessary to meet the requirements of the New York City Energy Conservation Code and this code.
Section BC 1404. Materials
1404.1 General.
Materials used for the construction of exterior walls shall comply with the provisions of this section. Materials not prescribed herein shall be permitted, provided that any such alternative has been approved.
1404.2 Water-resistive barrier.
Not fewer than one layer of No. 15 asphalt felt complying with ASTM D 226 for Type 1 felt or other approved materials shall be attached to the studs or sheathing, with flashing as described in Section 1405.4 of this code, in such a manner as to provide a continuous water-resistive barrier behind the exterior wall veneer. Combustible water-resistive barriers shall comply with special inspection requirements of Chapter 17 of this code.
1404.3 Wood.
Exterior walls of wood construction shall be designed and constructed in accordance with Chapter 23.
1404.3.1 Basic hardboard.
Basic hardboard shall conform to the requirements of ANSI A135.4.
1404.3.2 Hardboard siding.
Hardboard siding shall conform to the requirements of ANSI A135.6 and, where used structurally, shall be so identified by the label of an approved agency.
1404.4 Masonry.
Exterior walls of masonry construction shall be designed and constructed in accordance with this chapter and Chapter 21. Masonry units, mortar and metal accessories used in anchored and adhered veneer shall meet the physical requirements of Chapter 21. The backing of anchored and adhered veneer shall be of concrete, masonry, steel framing or wood framing. Continuous insulation meeting the applicable requirements of this code shall be permitted between the backing and the masonry veneer.
1404.5 Metal.
Exterior walls constructed of cold-formed steel, structural steel or aluminum shall be designed in accordance with Chapters 20 and 22, as applicable.
1404.5.1 Aluminum siding.
Aluminum siding shall conform to the requirements of AAMA 1402.
1404.5.2 Cold-rolled copper.
Copper shall conform to the requirements of ASTM B 370.
1404.5.3 Lead-coated copper.
Lead-coated copper shall conform to the requirements of ASTM B 101.
1404.6 Concrete.
Exterior walls of concrete construction shall be designed and constructed in accordance with Chapter 19.
1404.7 Glass-unit masonry.
Exterior walls of glass-unit masonry shall be designed and constructed in accordance with Chapter 21.
1404.8 Plastics.
Plastic panel, apron or spandrel walls as defined in this code shall not be limited in thickness, provided that such plastics and their assemblies conform to the requirements of Chapter 26 and other applicable requirements of this chapter, and are constructed of approved weather-resistant materials of adequate strength to resist the wind loads for cladding specified in Chapter 16.
1404.9 Vinyl siding.
Vinyl siding shall be certified and labeled as conforming to the requirements of ASTM D 3679 by an approved agency.
1404.10 Fiber-cement siding.
Fiber-cement siding shall conform to the requirements of ASTM C 1186, Type A or ISO 8336, Category A, and shall be so identified on labeling listing an approved agency.
1404.11 Exterior insulation finish system (EIFS).
EIFS shall be designed and constructed in accordance with Section 1408.
1404.12 Polypropylene siding.
Polypropylene siding shall be certified and labeled as conforming to the requirements of ASTM D 7254 and those of Section 1404.12.1 or 1404.12.2 of this code by an approved agency. Polypropylene siding shall be installed in accordance with manufacturer's instructions and the requirements of Section 1405.18 of this code. Polypropylene siding shall be secured to the building so as to provide weather protection for the exterior walls of the building.
1404.12.1 Flame spread index.
The certification of the flame spread index shall be accompanied by a test report stating that all portions of the test specimen ahead of the flame front remained in position during the test in accordance with ASTM E 84 or UL 723.
1404.12.2 Distance between adjacent buildings.
The distance between a building with polypropylene siding and the adjacent building shall be not less than 10 feet (3048 mm).
1404.13 Foam plastic insulation.
Foam plastic insulation used in exterior wall covering assemblies shall comply with Chapter 26 and be fireblocked in accordance with Section 718.2.6.1.
Section BC 1405. Installation of Wall Coverings
1405.1 General.
Exterior wall coverings shall be designed and constructed in accordance with the applicable provisions of this section. Installations not prescribed herein shall be permitted, provided that such alternative has been approved. Installations shall be in accordance with approved construction documents where a permit is required. Installations of exterior wall coverings shall comply with the special inspection requirements of Chapter 17.
1405.2 Weather protection.
The exterior wall envelope shall provide weather protection for the building. The materials of the minimum nominal thickness specified in Table 1405.2 shall be acceptable as approved weather coverings.
Exception: Weather coverings not meeting the minimum nominal thicknesses specified in Table 1405.2 shall be permitted provided such alternative has been approved.
Table 1405.2 Minimum Thickness of Weather Coverings
Covering Type Minimum Thickness (inches) Adhered masonry veneer* 0.25 Aluminum siding 0.019 Anchored masonry veneer 2.625 Asbestos-cement boards 0.125 Asbestos shingles 0.156 Cold-rolled copper d 0.0216 nominal Copper shingles d 0.0162 nominal Exterior plywood (with sheathing) 0.313 Exterior plywood (without sheathing) See Section 2304.6 Fiber-cement lap siding 0.25 c Fiber-cement panel siding 0.25 c Fiberboard siding 0.5 Glass-fiber reinforced concrete panels 0.375 Hardboard siding c 0.25 High-yield copper d 0.0162 nominal Lead-coated copper d 0.0216 nominal Lead-coated high-yield copper 0.0162 nominal Marble slabs 1 Particleboard (with sheathing) See Section 2304.6 Particleboard (without sheathing) See Section 2304.6 Porcelain tile 0.25 Steel (approved corrosion resistant) 0.0149 Stone (cast artificial, anchored) 1.5 Stone (natural) 2 Structural glass 0.344 Stucco or exterior cement plaster Three-coat work over: Metal plaster base 0.875 b Unit masonry 0.625 b Cast-in-place or precast concrete 0.625 b Two-coat work over: Unit masonry 0.5 b Cast-in-place or precast concrete 0.375 b Terra cotta (anchored) 1 Terra cotta (adhered) 0.25 Vinyl siding 0.035 Wood shingles 0.375 Wood siding (without sheathing) a 0.5
For SI: 1 inch = 25.4 mm, 1 ounce = 28.35 g, 1 square foot = 0.093 m 2 .
a. Wood siding of thicknesses less than 0.5 inch shall be placed over sheathing that conforms to Section 2304.6.
b. Exclusive of texture.
c. As measured at the bottom of decorative grooves.
d. 16 ounces per square foot for cold-rolled copper and lead-coated copper, 12 ounces per square foot for copper shingles, high-yield copper and lead-coated high-yield copper.
* Veneer units in this group shall be of an approved type and not be greater than 2 inches in thickness.
1405.3 Vapor retarders.
Vapor retarders as described in Section 1405.3.3 shall be provided based on an approved design using accepted engineering practice for hygrothermal analysis.
1405.3.1 Reserved.
1405.3.2 Reserved.
1405.3.3 Material vapor retarder class.
The vapor retarder class shall be based on the manufacturer's certified testing or a tested assembly. The following shall be deemed to meet the class specified:
Class I: Sheet polyethylene, non-perforated aluminum foil with a perm rating of less than or equal to 0.1.
Class II: Kraft-faced fiberglass batts or paint with a perm rating greater than 0.1 and less than or equal to 1.0.
Class III: Latex or enamel paint with a perm rating of greater than 1.0 and less than or equal to 10.0.
1405.3.4 Minimum clear airspaces and vented openings for vented cladding.
For the purposes of this section, vented cladding shall include the following minimum clear airspaces:
1. Vinyl lap or horizontal aluminum siding applied over a weather-resistive barrier as specified in this chapter.
2. Brick veneer with a clear airspace as specified in this code.
3. Other approved vented claddings.
1405.4 Flashing.
Flashing shall be installed in such a manner so as to prevent moisture from entering the wall or to redirect moisture to the exterior. Flashing shall be installed where required at the perimeters of exterior door and window assemblies, penetrations and terminations of exterior wall assemblies, exterior wall intersections with roofs, chimneys, porches, decks, balconies and similar projections and at built-in gutters and similar locations where moisture could enter the wall. Flashing with projecting flanges shall be installed on both sides and the ends of copings, under sills and continuously above projecting trim.
1405.4.1 Exterior wall pockets.
In exterior walls of buildings or structures, wall pockets or crevices in which moisture can accumulate shall be avoided or protected with caps or drips, or other approved means shall be provided to prevent water damage.
1405.4.2 Masonry.
Flashing and weep holes in anchored veneer shall be located in the first course of masonry above finished ground level above the foundation wall or slab, and other points of support, including structural floors, shelf angles and lintels where anchored veneers are designed in accordance with Section 1405.6.
1405.5 Wood veneers.
Wood veneers on exterior walls of buildings of Type I, II, III and IV construction shall be not less than 1-inch (25.4 mm) nominal thickness, 0.438-inch (11.1 mm) exterior hardboard siding or 0.375-inch (9.5 mm) exterior-type wood structural panels or particleboard and shall conform to the following:
1. The veneer shall not exceed 40 feet (12190 mm) in height above grade. Where fire-retardant-treated wood is used, the height shall not exceed 60 feet (18290 mm) in height above grade.
2. The veneer is attached to or furred from a noncombustible backing that is fire-resistance rated as required by other provisions of this code.
3. Where open or spaced wood veneers (without concealed spaces) are used, they shall not project more than 24 inches (609.6 mm) from the building wall.
1405.6 Anchored masonry veneer.
Anchored masonry veneer shall comply with the provisions of Sections 1405.6, 1405.7, 1405.8 and 1405.9 and Sections 12.1 and 12.2 of TMS 402, as modified by Chapter 21 of this code.
1405.6.1 Tolerances.
Anchored masonry veneers in accordance with Chapter 14 are not required to meet the tolerances in Article 3.3 F1 of TMS 602.
1405.6.2 Seismic requirements.
Anchored masonry veneer located in Seismic Design Category C or D shall conform to the requirements of Section 12.2.2.10 of TMS 402, as modified by Chapter 21 of this code
1405.7 Stone veneer.
Anchored stone veneer units not exceeding 10 inches (254 mm) in thickness shall be anchored directly to masonry, concrete or to stud construction by one of the following methods:
1. With concrete or masonry backing, anchor ties shall be not less than 0.1055-inch (2.68 mm) corrosion-resistant wire, or approved equal, formed beyond the base of the backing. The legs of the loops shall be not less than 6 inches (152.4 mm) in length bent at right angles and laid in the mortar joint, and spaced so that the eyes or loops are 12 inches (304.8 mm) maximum on center in both directions. There shall be provided not less than a 0.1055-inch (2.68 mm) corrosion-resistant wire tie, or approved equal, threaded through the exposed loops for every 2 square feet (0.2 m 2 ) of stone veneer. This tie shall be a loop having legs not less than 15 inches (381 mm) in length, so bent that the tie will lie in the stone veneer mortar joint. The last 2 inches (50.8 mm) of each wire leg shall have a right-angle bend. One-inch (25.4 mm) minimum thickness of cement grout shall be placed between the backing and the stone veneer.
2. With wood stud backing, a 2-inch by 2-inch (50.8 mm by 50.8 mm) 0.0625-inch (1.59 mm) zinc-coated or nonmetallic coated wire mesh with two layers of water-resistive barrier in accordance with Section 1404.2 shall be applied directly to wood studs spaced not more than 16 inches (406.4 mm) on center. On studs, the mesh shall be attached with 2-inch (50.8 mm) long corrosion-resistant steel wire furring nails at 4 inches (101.6 mm) on center providing a minimum 1.125-inch (28.58 mm) penetration into each stud and with 8d (0.120 in. diameter) annular threaded nails at 8 inches (203.2 mm) on center into top and bottom plates or with equivalent wire ties. There shall be not less than a 0.1055-inch (2.68 mm) zinc-coated or nonmetallic coated wire, or approved equal, attached to the stud with not smaller than an 8d (0.120 in. diameter) annular threaded nail for every 2 square feet (0.2 m 2 ) of stone veneer. This tie shall be a loop having legs not less than 15 inches (381 mm) in length, so bent that the tie will lie in the stone veneer mortar joint. The last 2 inches (50.8 mm) of each wire leg shall have a right-angle bend. One-inch (25.4 mm) minimum thickness of cement grout shall be placed between the backing and the stone veneer.
3. With cold-formed steel stud backing, a 2-inch by 2-inch (50.8 mm by 50.8 mm) 0.0625-inch (1.59 mm) zinc-coated or nonmetallic coated wire mesh with two layers of water-resistive barrier in accordance with Section 1404.2 shall be applied directly to steel studs spaced at not more than 16 inches (406.4 mm) on center. The mesh shall be attached with corrosion-resistant #8 self-drilling, tapping screws at 4 inches (101.6 mm) on center, and at 8 inches (203.2 mm) on center into top and bottom tracks or with equivalent wire ties. Screws shall extend through the steel connection not fewer than three exposed threads. There shall be not less than a 0.1055-inch (2.68 mm) corrosion-resistant wire, or approved equal, attached to the stud with not smaller than a #8 self-drilling, tapping screw extending through the steel framing not fewer than three exposed threads for every 2 square feet (0.2 m 2 ) of stone veneer. This tie shall be a loop having legs not less than 15 inches (381 mm) in length, so bent that the tie will lie in the stone veneer mortar joint. The last 2 inches (50.8 mm) of each wire leg shall have a right-angle bend. One inch (25.4 mm) minimum thickness of cement grout shall be placed between the backing and the stone veneer. The cold-formed steel framing members shall have a minimum bare steel thickness of 0.0428 inches (1.087 mm).
1405.8 Slab-type veneer.
Anchored slab-type veneer units not exceeding 2 inches (50.8 mm) in thickness shall be anchored directly to masonry, concrete or light-frame construction. For veneer units of marble, travertine, granite or other stone units of slab form, ties of corrosion-resistant dowels in drilled holes shall be located in the middle third of the edge of the units, spaced not more than 24 inches (609.6 mm) apart around the periphery of each unit with not less than four ties per veneer unit. Units shall not exceed 20 square feet (1.9 m 2 ) in area. If the dowels are not tight fitting, the holes shall be drilled not more than 0.063 inch (1.6 mm) larger in diameter than the dowel, with the hole countersunk to a diameter and depth equal to twice the diameter of the dowel in order to provide a tight-fitting key of cement mortar at the dowel locations where the mortar in the joint has set. Veneer ties shall be corrosion-resistant metal capable of resisting, in tension or compression, a force equal to two times the weight of the attached veneer. If made of sheet metal, veneer ties shall be not smaller in area than 0.0336 by 1 inch (0.853 by 25.4 mm) or, if made of wire, not smaller in diameter than 0.1483-inch (3.76 mm) wire.
1405.9 Terra cotta.
Anchored terra cotta or ceramic units not less than 1 inch (25.4 mm) thick shall be anchored directly to masonry, concrete or stud construction. Terra cotta or ceramic unit anchorage shall be engineered to transfer loads to stable backup walls utilizing not less than two non-corrosive anchors per unit.
1405.10 Adhered masonry veneer.
Adhered masonry veneer shall comply with the applicable requirements in this section and Sections 12.1 and 12.3 of TMS 402, as modified by Chapter 21 of this code.
1405.10.1 Exterior adhered masonry veneer.
Exterior adhered masonry veneer shall be installed in accordance with the manufacturer's instructions and Section 1405.10.
1405.10.1.1 Water-resistive barriers.
Water-resistive barriers shall be installed as required in Section 2510.6.
1405.10.1.2 Flashing.
Flashing shall comply with this section and the applicable requirements of Section 1405.4.
1405.10.1.2.1 Flashing at foundation.
A corrosion-resistant screed or flashing of a minimum 0.019-inch (0.48 mm) or 26 gage galvanized or plastic with a minimum vertical attachment flange of 3 1/2 inches (88.9 mm) shall be installed to extend not less than 1 inch (25.4 mm) below the foundation plate line on exterior stud walls in accordance with Section 1405.4. The water-resistive barrier shall lap over the exterior of the attachment flange of the screed or flashing.
1405.10.1.3 Clearances.
On exterior stud walls, adhered masonry veneer shall be installed not less than 4 inches (101.6 mm) above the earth, or not less than 2 inches (50.8 mm) above paved areas, or not less than 1/2 inch (12.7 mm) above exterior walking surfaces that are supported by the same foundation that supports the exterior wall.
1405.10.1.4 Adhered masonry veneer installed with lath and mortar.
Exterior adhered masonry veneer installed with lath and mortar shall comply with the following.
1405.10.1.4.1 Lathing.
Lathing shall comply with the requirements of Section 2510.
1405.10.1.4.2 Scratch coat.
A nominal 1/2-inch (12.7 mm) thick layer of mortar complying with the material requirements of Sections 2103 and 2512.2 shall be applied, encapsulating the lathing. The surface of this mortar shall be scored horizontally, resulting in a scratch coat.
1405.10.1.4.3 Adhering veneer.
The masonry veneer units shall be adhered to the mortar scratch coat with a nominal 1/2-inch (12.7 mm) thick setting bed of mortar complying with Sections 2103 and 2512.2 applied to create a full setting bed for the back of the masonry veneer units. The masonry veneer units shall be worked into the setting bed resulting in a nominal 3/8-inch (9.5 mm) setting bed after the masonry veneer units are applied.
1405.10.1.5 Adhered masonry veneer applied directly to masonry and concrete.
Adhered masonry veneer applied directly to masonry or concrete shall comply with the applicable requirements of Section 1405.10, and with the requirements of Section 1405.10.1.4 or 2510.7.
1405.10.1.6 Cold weather construction.
Cold weather construction of adhered masonry veneer shall comply with the requirements of Sections 2104 and 2512.4.
1405.10.1.7 Hot weather construction.
Hot weather construction of adhered masonry veneer shall comply with the requirements of Section 2104.
1405.10.2 Exterior adhered masonry veneers – porcelain tile.
Adhered units shall not exceed 5/8 inch (15.8 mm) thickness and 24 inches (609.6 mm) in any face dimension nor more than 3 square feet (0.28 m 2 ) in total face area and shall not weigh more than 9 pounds psf (0.43 kN/m 2 ). Porcelain tile shall be adhered to an approved backing system.
1405.10.3 Interior adhered masonry veneers.
Interior adhered masonry veneers shall have a maximum weight of 20 psf (0.958 kg/m 2 ) and shall be installed in accordance with Section 1405.10. The supporting members shall be designed to limit deflection to 1/600 of the span of the supporting members.
1405.11 Metal veneers.
Veneers of metal shall be fabricated from approved corrosion-resistant materials or shall be protected front and back with porcelain enamel, or otherwise be treated to render the metal resistant to corrosion. Such veneers shall be not less than 0.0149-inch (0.378 mm) nominal thickness sheet steel mounted on wood or metal furring strips or approved sheathing on light-frame construction.
1405.11.1 Attachment.
Exterior metal veneer shall be securely attached to the supporting masonry or framing members with corrosion-resistant fastenings, metal ties or by other approved devices or methods. The spacing of the fastenings or ties shall not exceed 24 inches (609.6 mm) either vertically or horizontally, but where units exceed 4 square feet (0.4 m 2 ) in area there shall be not less than four attachments per unit. The metal attachments shall have a cross-sectional area not less than provided by W 1.7 wire. Such attachments and their supports shall be designed and constructed to resist the wind loads as specified in Section 1609 for components and cladding.
1405.11.2 Weather protection.
Metal supports for exterior metal veneer shall be protected by painting, galvanizing or by other approved coating or treatment. Wood studs, furring strips or other wood supports for exterior metal veneer shall be approved pressure-treated wood or protected as required in Section 1403.2. Joints and edges exposed to the weather shall be caulked with approved durable waterproofing material or by other approved means to prevent penetration of moisture.
1405.11.3 Backup.
Masonry backup shall not be required for metal veneer unless required by the fire-resistance requirements of this code.
1405.11.4 Grounding.
Grounding of metal veneers on buildings shall comply with the requirements of the New York City Electrical Code and Chapter 27 of this code.
1405.12 Thin exterior structural glass veneer.
The area of a single section of thin exterior structural glass veneer shall not exceed 10 square feet (0.93 m 2 ) where that section is not more than 15 feet (4572 mm) above the level of the sidewalk or grade level directly below, and shall not exceed 6 square feet (0.56 m 2 ) where it is more than 15 feet (4572 mm) above that level. In no event shall thin exterior structural glass veneer be installed more than 35 feet (10 668 mm) above the level of the sidewalk or grade level directly below.
1405.12.1 Length and height.
The length or height of any section of thin exterior structural glass veneer shall not exceed 48 inches (1220 mm).
1405.12.2 Thickness.
The thickness of thin exterior structural glass veneer shall be not less than 0.344 inch (8.7 mm).
1405.12.3 Application.
Thin exterior structural glass veneer shall be set only after backing is thoroughly dry and after application of an approved bond coat uniformly over the entire surface of the backing so as to effectively seal the surface. Glass shall be set in place with an approved mastic cement in sufficient quantity so that at least 50 percent of the area of each glass unit is directly bonded to the backing by mastic not less than 1/4 inch (6.4 mm) thick and not more than 5/8 inch (15.9 mm) thick. The bond coat and mastic shall be evaluated for compatibility and shall bond firmly together.
1405.12.4 Installation at sidewalk level.
Where thin exterior structural glass veneer extends to a sidewalk surface, each section shall rest in an approved metal molding, and be set at least 1/4 inch (6.4 mm) above the highest point of the sidewalk. The space between the molding and the sidewalk shall be thoroughly caulked and made water tight.
1405.12.4.1 Installation above sidewalk level.
Where thin exterior structural glass veneer is installed above the level of the top of a bulkhead facing, or at a level more than 36 inches (914.4 mm) above the sidewalk level, the mastic cement binding shall be supplemented with approved nonferrous metal shelf angles located in the horizontal joints in every course. Such shelf angles shall be not less than 0.0478 inch (1.2 mm) thick and not less than 2 inches (50.8 mm) long and shall be spaced at approved intervals, with not less than two angles for each glass unit. Shelf angles shall be secured to the wall or backing with expansion bolts, toggle bolts or by other approved methods.
1405.12.5 Joints.
Unless otherwise specifically approved by the commissioner, abutting edges of thin exterior structural glass veneer shall be ground square. Mitered joints shall not be used except where specifically approved for wide angles. Joints shall be uniformly buttered with an approved jointing compound and horizontal joints shall be held to not less than 0.063 inch (1.6 mm) by an approved nonrigid substance or device. Where thin exterior structural glass veneer abuts nonresilient material at sides or top, expansion joints not less than 1/4 inch (6.4 mm) wide shall be provided.
1405.12.6 Mechanical fastenings.
Thin exterior structural glass veneer installed above the level of the heads of show windows and veneer installed more than 12 feet (3657.6 mm) above sidewalk level shall, in addition to the mastic cement and shelf angles, be held in place by the use of fastenings at each vertical or horizontal edge, or at the four corners of each glass unit. Fastenings shall be secured to the wall or backing with expansion bolts, toggle bolts or by other methods. Fastenings shall be so designed as to hold the glass veneer in a vertical plane independent of the mastic cement. Shelf angles providing both support and fastenings shall be permitted.
1405.12.7 Flashing.
Exposed edges of thin exterior structural glass veneer shall be flashed with overlapping corrosion-resistant metal flashing or equivalent and caulked with a waterproof compound in a manner to effectively prevent the entrance of moisture between the glass veneer and the backing.
1405.13 Exterior windows and doors.
Windows and doors installed in exterior walls shall conform to the testing and performance requirements of Section 1709.5.
1405.13.1 Installation.
Windows and doors shall be installed in accordance with the manufacturer's instructions. Fastener size and spacing shall be provided in such instructions and shall be calculated based on maximum loads and spacing used in the tests.
1405.13.2 Windows in Group R-2 and R-3 occupancies.
Windows in Group R-2 and R-3 occupancies shall comply with Sections 1015.9 and 1015.8, respectively.
1405.13.3 Windows in R-2 Occupancy.
Windows in R-2 occupancy shall be subject to any applicable requirements of the New York City Department of Health and Mental Hygiene with regard to window guards.
1405.14 Vinyl siding.
Vinyl siding conforming to the requirements of this section and complying with ASTM D 3679 shall be permitted on exterior walls of buildings located in areas where the allowable stress design speed V asd , as determined in accordance with Section 1609.3.1, does not exceed 100 miles per hour (44.7 m/s) and the building height is less than or equal to 40 feet (12 192 mm) in Exposure C. Where construction is located in areas where the allowable stress design speed V asd , as determined in accordance with Section 1609.3.1, exceeds 100 miles per hour (44.7 m/s), or building heights are in excess of 40 feet (12 192 mm), tests or calculations showing compliance with Chapter 16 of this code shall be submitted. Vinyl siding shall be secured to the building so as to provide weather protection for the exterior walls of the building.
1405.14.1 Application.
The siding shall be applied over sheathing or materials listed in Section 2304.6. Siding shall be applied to conform to the water-resistive barrier requirements in Section 1403. Siding and accessories shall be installed in accordance with the manufacturer's instructions. Unless otherwise specified in the manufacturer's instructions, nails used to fasten the siding and accessories shall have a minimum 0.313-inch (7.9 mm) head diameter and 1/8-inch (3.18 mm) shank diameter. The nails shall be corrosion resistant and shall be long enough to penetrate the studs or nailing strip at least 3/4 inch (19.1 mm). For cold-formed steel light-frame construction, corrosion-resistant fasteners shall be used. Screw fasteners shall penetrate the cold-formed steel framing at least three exposed threads. Other fasteners shall be installed in accordance with the manufacturer's instructions. Where the siding is installed horizontally, the fastener spacing shall not exceed 16 inches (406.4 mm) horizontally and 12 inches (304.8 mm) vertically. Where the siding is installed vertically, the fastener spacing shall not exceed 12 inches (304.8 mm) horizontally and 12 inches (304.8 mm) vertically.
1405.15 Cement plaster.
Cement plaster applied to exterior walls shall conform to the requirements specified in Chapter 25.
1405.16 Fiber-cement siding.
Fiber-cement siding complying with Section 1404.10 shall be permitted on exterior walls of Type I, II, III, IV and V construction for wind pressure resistance or wind speed exposures as indicated by the manufacturer's listing and label and the installation instructions. Where specified, the siding shall be installed over sheathing or materials listed in Section 2304.6 and shall be installed to conform to the water-resistive barrier requirements in Section 1403. Siding and accessories shall be installed in accordance with the manufacturer's instructions. Unless otherwise specified in the the manufacturer's instructions, nails used to fasten the siding to wood studs shall be corrosion-resistant round head smooth shank and shall be long enough to penetrate the studs at least 1 inch (25.4 mm). For cold-formed steel light-frame construction, corrosion-resistant fasteners shall be used. Screw fasteners shall penetrate the cold-formed steel framing at least three exposed full threads. Other fasteners shall be installed in accordance with the manufacturer's instructions.
1405.16.1 Panel siding.
Fiber-cement panels shall comply with the requirements of ASTM C 1186, Type A, minimum Grade II or ISO 8336, Category A, minimum Class 2. Panels shall be installed with the long dimension either parallel or perpendicular to framing. Vertical and horizontal joints shall occur over framing members and shall be protected with sealant, battens or flashing. Alternatively, vertical or horizontal joints shall be shiplap or otherwise designed to comply with Section 1403.2 of this code. Panel siding shall be installed with fasteners in accordance with the manufacturer's instructions.
1405.16.2 Lap siding.
Fiber-cement lap siding having a maximum width of 12 inches (304.8 mm) shall comply with the requirements of ASTM C 1186, Type A, minimum Grade II or ISO 8336, Category A, minimum Class 2. Lap siding shall be lapped a minimum of 1 1/4 inches (32 mm) and lap siding not having tongue-and-groove end joints shall have the ends protected with caulking, covered with an H-section joint cover, located over a strip of flashing or shall be otherwise designed to comply with Section 1403.2 of this code. Lap siding courses shall be installed with the fastener heads exposed or concealed in accordance with the manufacturer's instructions.
1405.17 Fastening.
Weather boarding and wall coverings shall be securely fastened with aluminum, copper, zinc, zinc-coated or other approved corrosion-resistant fasteners in accordance with the nailing schedule in Table 2304.10.1 or the manufacturer's instructions. Shingles and other weather coverings shall be attached with appropriate standard-shingle nails to furring strips securely nailed to studs, or with approved mechanically bonding nails, except where sheathing is of wood not less than 1-inch (25.4 mm) nominal thickness or of wood structural panels as specified in Table 2308.6.3(3).
1405.18 Polypropylene siding.
Polypropylene siding conforming to the requirements of this section and complying with Section 1404.12 shall be limited to exterior walls of Type VB construction located in areas where the wind speed specified in Chapter 16 does not exceed 100 miles per hour (44.7 m/s) and the building height is less than or equal to 40 feet (12 192 mm) in Exposure C. Where construction is located in areas where the basic wind speed exceeds 100 miles per hour (44.7 m/s), or building heights are in excess of 40 feet (12 192 mm), tests or calculations showing compliance with Chapter 16 shall be submitted. Polypropylene siding shall be installed in accordance with the manufacturer's instructions. Polypropylene siding shall be secured to the building so as to provide weather protection for the exterior walls of the building.
Section BC 1406. Combustible Materials on the Exterior Side of Exterior Walls
1406.1 General.
Section 1406 shall apply to exterior wall coverings, exterior balconies and similar projections, bay and oriel windows, decks, porches, porticos, entranceways, and storm enclosures constructed of combustible materials. Combustible water-resistive barriers complying with Section 1403.5.1 shall be permitted in exterior wall coverings. Fireblocking shall be installed in accordance with Section 1406.2.3. Existing building retrofits utilizing combustible exterior wall coverings shall also comply with Section 1406.5. Combustible exterior wall coverings shall be subject to the special inspection requirements of Section 1705.16.
1406.2 Combustible exterior wall coverings.
Combustible exterior wall coverings, including architectural trim, shall comply with this section.
Exceptions:
1. Plastics complying with Chapter 26.
2. Metal composite materials (MCM) complying with Section 1407.
3. High-pressure decorative exterior-grade compact laminates (HPL) complying with Section 1409.
1406.2.1 Type I, II, III and IV construction.
In buildings of Type I, II, III and IV construction, exterior wall coverings shall be permitted to be constructed of combustible materials in accordance with Section 1406.2.1.1, subject to the following limitations:
1. Combustible exterior wall coverings shall not exceed 10 percent of an exterior wall surface area on any given story. Such combustible exterior wall covering shall not be permitted on exterior walls where the fire separation distance is 5 feet (1524 mm) or less.
2. Combustible exterior wall coverings shall be limited to 40 feet (12 192 mm) in height above grade plane.
3. Combustible exterior wall coverings constructed of fire-retardant-treated wood complying with Section 2303.2 for exterior installation shall not be limited in wall surface area where the fire separation distance is 5 feet (1524 mm) or less and shall be permitted up to 60 feet (18 288 mm) in height above grade plane, regardless of the fire separation distance.
4. Wood veneers shall comply with Section 1405.5.
5. Combustible exterior wall coverings shall not be permitted on buildings of Type IV construction utilizing CLT or SCL complying with Section 602.4.
6. Combustible exterior wall coverings shall not be permitted at exterior balconies in accordance with Section 1406.3.
1406.2.1.1 Ignition resistance.
Where permitted by Section 1406.2.1 of this code, combustible exterior wall coverings shall be tested in accordance with NFPA 268.
Exceptions: The following materials are not required to be tested in accordance with NFPA 268. However, such materials shall comply with all other provisions of Section 1406 of this code.
1. Wood or wood-based products.
2. Other combustible materials covered with an exterior weather covering other than vinyl sidings included in and complying with the thickness requirements of Table 1405.2 of this code.
3. Aluminum having a minimum thickness of 0.019 inch (0.48 mm).
1406.2.1.1.1 Fire separation 5 feet or less.
Where installed on exterior walls having a fire separation distance of 5 feet (1524 mm) or less, combustible exterior wall coverings shall not exhibit sustained flaming as defined in NFPA 268.
1406.2.1.1.2 Fire separation greater than 5 feet.
For fire separation distances greater than 5 feet (1524 mm), any exterior wall covering shall be permitted that has been exposed to a reduced level of incident radiant heat flux in accordance with the NFPA 268 test method without exhibiting sustained flaming. The minimum fire separation distance required for the exterior wall covering shall be determined from Table 1406.2.1.1.2 of this code based on the maximum tolerable level of incident radiant heat flux that does not cause sustained flaming of the exterior wall covering.
Table 1406.2.1.1.2 Minimum Fire Separation for Combustible Exterior Wall Coverings
Fire Separation Distance (feet) Tolerable Level Incident Radiant Heat Energy (kW/m 2 ) Fire Separation Distance (feet) Tolerable Level Incident Radiant Heat Energy (kW/m 2 ) 5 12.5 16 5.9 6 11.8 17 5.5 7 11.0 18 5.2 8 10.3 19 4.9 9 9.6 20 4.6 10 8.9 21 4.4 11 8.3 22 4.1 12 7.7 23 3.9 13 7.2 24 3.7 14 6.7 25 3.5 15 6.3
For SI: 1 foot = 304.8 mm, 1 Btu/H 2 × °F = 0.0057 kW/m 2 × K.
1406.2.2 Location.
Combustible exterior wall coverings located along the top of exterior walls shall be completely backed up by the exterior wall and shall not extend over or above the top of the exterior walls.
1406.2.3 Fireblocking.
Exterior wall coverings shall be fireblocked in accordance with Section 718.2.6.
1406.3 Exterior balconies and similar projections.
Exterior wall covering on walls abutting balconies, and cladding on the sides and underside of balconies, shall be constructed of noncombustible materials. Exterior walls abutting balconies shall be noncombustible up to 12 feet (3657.6 mm) above the walking surface or to the underside of the balcony above, whichever is less. On cantilevered balconies, the exterior wall abutting the balcony, plus 3 feet (914.4 mm) on each side, shall be constructed of noncombustible materials. On recessed and semirecessed balconies, the exterior walls abutting the balconies shall be constructed of noncombustible materials.
Exception: Combustible exterior wall coverings shall be allowed on balconies in Type V construction with a fire separation distance greater than or equal to 5 feet (1524 mm).
1406.4 Bay and oriel windows, decks, porches, porticos, entranceways, and storm enclosures.
Bay and oriel windows, decks, porches, porticos, entranceways and storm enclosures shall conform to the type of construction required for the building to which they are attached, including required fire rating, unless otherwise modified by the requirements of this section. For the purposes of this section, such structures shall be referred to as, "appendages".
Exception: Plastic complying with Chapter 26.
1406.4.1 Appendages on Type I and II construction.
Appendages on buildings of Type I or II construction shall be constructed of noncombustible materials. However, on buildings not more than three stories or 40 feet (12 192 mm) in height, whichever is less, fire-retardant-treated wood shall be permitted.
1406.4.2 Appendages on Type III, IV and VA construction.
Appendages on buildings of Type III, IV and VA construction may be constructed of combustible materials, provided that all the following conditions are met:
1. Such building does not exceed three stories or 40 feet (12 192 mm) in height, whichever is less.
2. The main use or dominant occupancy of such building is classified in Occupancy Group R-2 or R-3.
3. The appendage has an exterior separation on all exposed sides of at least 15 feet (4572 mm), measured from the outermost surface of the appendage, except that appendages with exposed sides protected by minimum 1-hour fire-rated construction extending at least 36 inches (914.4 mm) above the highest combustible horizontal surface may be located up to a minimum distance of 36 inches (914.4 mm) from any property line.
4. The appendage is so constructed that its removal or destruction will not reduce the structural stability or fire-resistive integrity of the building.
5. The appendage has a superficial area not exceeding 150 square feet (13.9 m 2 ) when viewed from directly above and is included in the area limitations of Table 503* for the entire building.
* Editor's note: As set forth in L.L. 2021/126; Table 503 was deleted by L.L. 2021/126.
6. The appendage is not higher than the sills of the second-story windows.
7. The vertical surface area of the combustible portions of the appendage does not exceed 10 percent of the total wall area (windows excluded) of the building.
8. For enclosed appendages, the roof of the appendage has a class A roof covering, and the soffit or ceiling covering the combustible roof framing shall have a minimum 1-hour fire-resistance rating.
Exception: Appendages constructed of fire-retardant-treated wood, on buildings not exceeding 3 stories or40 feet (12 192 mm) in height, whichever is less, need not comply with Items 2 through 8.
1406.4.3 Appendages on Type VB construction.
Appendages may be constructed of combustible materials on buildings of construction Type VB.
1406.5 Retrofit of existing buildings.
Combustible materials shall not be permitted for use at the outermost surface of the exterior wall covering for exterior envelope retrofits of existing nonsprinklered buildings over 75 feet (22 860 mm), unless the following conditions are satisfied:
1. The outermost surface of the combustible exterior wall covering shall be interrupted by a noncombustible material at least 3 feet (914.4 mm) high between the top of one opening and the bottom of the opening immediately above to form a continuous band across building elevations.
2. On walls without openings, a 3 feet (914.4 mm) high noncombustible band shall interrupt the outermost surface of the combustible exterior wall covering at least every 15 feet (4572 mm) vertically.
Section BC 1407. Metal Composite Materials (MCM)
1407.1 General.
The provisions of this section shall govern the materials, construction and quality of metal composite materials (MCM) for use as exterior wall coverings in addition to other applicable requirements of Chapters 14 and 16.
1407.1.1 Plastic core.
The plastic core of the MCM shall not contain foam plastic insulation as defined in Section 202.
1407.1.2 Prohibited locations.
The use of MCM in exterior wall coverings is subject to the following limitations:
1. MCM is prohibited in exterior wall coverings in Type IV construction utilizing cross-laminated timer (CLT) or structural composite lumber (SCL) complying with Section 602.4.
2. MCM is prohibited in exterior wall coverings at exterior balconies in accordance with Section 1406.3.
1407.2 Exterior wall finish.
MCM used as exterior wall finish or as elements of bay and oriel windows to provide cladding or weather resistance shall comply with Sections 1407.4 through 1407.16.
1407.3 Architectural trim and embellishments.
MCM used as architectural trim or embellishments shall comply with Sections 1407.7 through 1407.14.
1407.4 Structural design.
MCM systems shall be designed and constructed to resist wind loads as required by Chapter 16 for components and cladding.
1407.5 Approval.
Results of approved tests or an engineering analysis shall be submitted to the commissioner to verify compliance with the requirements of Chapter 16 for wind loads.
1407.6 Weather resistance.
MCM systems shall comply with Section 1403 and shall be designed and constructed to resist wind and rain in accordance with this section and the manufacturer's installation instructions.
1407.7 Durability.
MCM systems shall be constructed of approved materials that maintain the performance characteristics required in Section 1407 for the duration of use.
1407.8 Fire-resistance rating.
Where MCM systems are used on exterior walls required to have a fire-resistance rating in accordance with Section 705, evidence shall be submitted to the commissioner that the required fire-resistance rating is maintained.
Exception: MCM systems not containing foam plastic insulation, which are installed on the outer surface of a fire-resistance-rated exterior wall in a manner such that the attachments do not penetrate through the entire exterior wall assembly, shall not be required to comply with this section.
1407.9 Surface-burning characteristics.
MCM shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 450 when tested as an assembly in the maximum thickness intended for use in accordance with ASTM E 84 or UL 723.
1407.10 Thermal barriers.
MCM shall be separated from the interior of a building by an approved thermal barrier consisting of 5/8-inch (15.9 mm) Type X gypsum wallboard or equivalent thermal barrier material that will limit the average temperature rise of the unexposed surface to not more than 250°F (12 1°C) after 20 minutes of fire exposure in accordance with the standard time-temperature curve of ASTM E 119 or UL 263. The thermal barrier shall be installed in accordance with criteria established by testing in accordance with UL 1715, where the thermal barrier shall remain in place for 20 minutes.
1407.11 Full-scale tests.
All MCM systems shall be tested in accordance with, and comply with, the acceptance criteria of NFPA 285. Such testing shall be performed on the MCM system with the MCM in the maximum thickness intended for use, including any required fireblocking. Approved NFPA 285 tested assembly design documentation of the MCM system shall be included on the submitted construction documents complying with Section 1401.2 of this code. Deviation from the NFPA 285 tested design shall be approved by the registered design professional and additional documentation shall be provided if requested by the department.
1407.12 Reserved.
1407.13 Foam plastic insulation.
MCM systems containing foam plastic insulation shall also comply with the requirements of Section 2603.
1407.14 Labeling.
MCM shall be labeled in accordance with this code and Section 28-113 of the Administrative Code.
1407.15 Special inspection.
MCM shall be subject to special inspection in accordance with Chapter 17.
1407.16 Fireblocking.
MCM installations shall be fireblocked in accordance with Section 718.2.6.1.
Section BC 1408. Exterior Insulation and Finish Systems (EIFS)
1408.1 General.
The provisions of this section shall govern the materials, construction and quality of exterior insulation and finish systems (EIFS) for use as exterior wall coverings in addition to other applicable requirements of Chapters 7, 14, 16, 17 and 26.
1408.1.1 Prohibited locations.
The use of EIFS containing foam plastic insulation in exterior wall coverings is subject to the following limitations:
1. EIFS containing foam plastic insulation is prohibited in exterior wall coverings in Type IV construction utilizing cross-laminated timer (CLT) or structural composite lumber (SCL) complying with Section 602.4.
2. EIFS containing foam plastic insulation is prohibited in exterior wall coverings at exterior balconies in accordance with Section 1406.3.
1408.2 Performance characteristics.
EIFS shall be constructed such that it meets the performance characteristics required in ASTM E 2568.
1408.3 Structural design.
The underlying structural framing and substrate shall be designed and constructed to resist loads as required by Chapter 16.
1408.4 Weather resistance.
EIFS shall comply with Section 1403 and shall be designed and constructed to resist environmental conditions in accordance with this section, the approved construction documents and manufacturer's installation instructions.
1408.4.1 EIFS with drainage.
EIFS with drainage shall have an average minimum drainage efficiency of 90 percent when tested in accordance the requirements of ASTM E 2273 and is required on framed walls of Type V construction, Residential Group R occupancies.
1408.4.1.1 Water-resistive barrier.
For EIFS with drainage, the water-resistive barrier shall comply with Section 1404.2 of this code or ASTM E 2570.
1408.5 Installation.
Installation of the EIFS and EIFS with drainage shall be in accordance with the EIFS manufacturer's instructions and this section.
1408.6 Special inspections.
EIFS installations shall comply with the provisions of Chapter 17.
1408.7 Fireblocking.
EIFS installations containing foam plastic insulation shall be fireblocked in accordance with Section 718.2.6.1.
1408.8 Foam plastic insulation.
EIFS installations containing foam plastic insulation shall be tested and comply with the requirements of Section 2603.
1408.9 Thermal barrier.
EIFS installations containing foam plastic insulation shall be separated from the interior of a building in accordance with Section 2603.5.2.
Section BC 1409. High-Pressure Decorative Exterior-Grade Compact Laminates (HPL)
1409.1 General.
The provisions of this section shall govern the materials, construction and quality of High-Pressure Decorative Exterior-Grade Compact Laminates (HPL) for use as exterior wall coverings in addition to other applicable requirements of Chapters 14 and 16.
1409.1.1 Prohibited locations.
The use of HPL in exterior wall coverings is subject to the following limitations:
1. HPL is prohibited in exterior wall coverings in Type IV construction utilizing cross-laminated timer (CLT) or structural composite lumber (SCL) complying with Section 602.4.
2. HPL is prohibited in exterior wall coverings at exterior balconies and shall comply with Section 1406.3.
1409.2 Exterior wall finish.
HPL used as exterior wall covering or as elements of bay and oriel windows to provide cladding or weather resistance shall comply with Sections 1409.4 through 1409.16.
1409.3 Architectural trim and embellishments.
HPL used as architectural trim or embellishments shall comply with Sections 1409.7 through 1409.14.
1409.4 Structural design.
HPL systems shall be designed and constructed to resist wind loads as required by Chapter 16 for components and cladding.
1409.5 Approval.
Results of approved tests or an engineering analysis shall be submitted to the commissioner to verify compliance with the requirements of Chapter 16 for wind loads.
1409.6 Weather resistance.
HPL systems shall comply with Section 1403 and shall be designed and constructed to resist wind and rain in accordance with this section and the manufacturer's instructions.
1409.7 Durability.
HPL systems shall be constructed of approved materials that maintain the performance characteristics required in Section 1409 for the duration of use.
1409.8 Fire-resistance rating.
Where HPL systems are used on exterior walls required to have a fire-resistance rating in accordance with Section 705, evidence shall be submitted to the commissioner that the required fire-resistance rating is maintained.
Exception: HPL systems not containing foam plastic insulation that are installed on the outer surface of a fire-resistance-rated exterior wall in a manner such that the attachments do not penetrate through the entire exterior wall assembly shall not be required to comply with this section.
1409.9 Surface-burning characteristics.
HPL shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 450 when tested in the minimum and maximum thicknesses intended for use in accordance with ASTM E 84 or UL 723.
1409.10 Thermal barriers.
HPL shall be separated from the interior of a building by an approved thermal barrier consisting of 5/8-inch (15.9 mm) Type X gypsum wallboard or equivalent thermal barrier material that will limit the average temperature rise of the unexposed surface to not more than 250°F (121°C) after 20 minutes of fire exposure in accordance with the standard time temperature curve of ASTM E 119 or UL 263. The thermal barrier shall be installed in accordance with criteria established by testing performed in accordance with UL 1715, where the thermal barrier shall remain in place for 20 minutes.
1409.11 Full-scale tests.
All HPL systems shall be tested in accordance with, and comply with, the acceptance criteria of NFPA 285. Such testing shall be performed on the HPL system with the HPL in the minimum and maximum thicknesses intended for use, including any required fireblocking. Approved NFPA 285 tested assembly design documentation of the HPL system shall be included on the submitted construction documents complying with Section 1401.2 of this code. Deviation from the NFPA 285 tested design shall be approved by the registered design professional and additional documentation shall be provided if requested by the department.
1409.12 Reserved.
1409.13 Foam plastic insulation.
HPL systems containing foam plastic insulation shall also comply with the requirements of Section 2603.
1409.14 Labeling.
HPL shall be labeled in accordance with this code and Article 113 of Title 28 of the Administrative Code.
1409.15 Special inspection.
HPL shall be subject to the special inspection requirements of Chapter 17.
1409.16 Fireblocking.
HPL installations shall be fireblocked in accordance with Section 718.2.6.1.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
Section BC 1410. Plastic Composite Decking
1410.1 Plastic composite decking.
Exterior deck boards, stair treads, handrails and guardrail systems constructed of plastic composites, including plastic lumber, shall comply with Section 2612.
Section BC 1501. General
1501.1 Scope.
The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies, and rooftop structures.
Section BC 1502. Definitions
1502.1 Definitions.
The following terms are defined in Chapter 2:
AGGREGATE.
BALLAST.
BUILDING-INTEGRATED PHOTOVOLTAIC (BIPV) PRODUCT.
BUILT-UP ROOF COVERING.
BULKHEAD.
CONTAINER GARDEN.
GREEN ROOF SYSTEM.
INTERLAYMENT.
MECHANICAL EQUIPMENT SCREEN.
METAL ROOF PANEL.
METAL ROOF SHINGLE.
MODIFIED BITUMEN ROOF COVERING.
PENTHOUSE.
PHOTOVOLTAIC MODULE.
PHOTOVOLTAIC PANEL.
PHOTOVOLTAIC PANEL SYSTEM.
PHOTOVOLTAIC SHINGLES.
POSITIVE ROOF DRAINAGE.
RADIANT BARRIER.
REROOFING.
ROOF ASSEMBLY.
ROOF COVERING.
ROOF COVERING SYSTEM.
ROOF DECK.
ROOF RECOVER.
ROOF REPAIR.
ROOF REPLACEMENT.
ROOF VENTILATION.
ROOFTOP STRUCTURE.
SCUPPER.
SINGLE-PLY MEMBRANE.
SUSTAINABLE ROOFING ZONE.
UNDERLAYMENT.
VEGETATIVE ROOF.
(Am. L.L. 2019/094, 5/19/2019, eff. 11/15/2019; Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
Section BC 1503. Weather Protection
1503.1 General.
Roof decks shall be covered with approved roof coverings secured to the building or structure in accordance with the provisions of this chapter. Roof coverings shall be designed and installed in accordance with this code and the manufacturer's instructions such that the roof covering shall serve to protect the building or structure.
1503.2 Flashing.
Flashing shall be installed in such a manner so as to prevent moisture entering the wall and roof through joints in copings, through moisture-permeable materials and at intersections with parapet walls and other penetrations through the roof plane.
1503.2.1 Locations.
Flashing shall be installed at wall and roof intersections, at gutters, wherever there is a change in roof slope or direction and around roof openings. Where flashing is of metal, the metal shall be corrosion resistant with a thickness of not less than 0.019 inch (0.483 mm) (No. 26 galvanized sheet).
1503.3 Coping.
Parapet walls shall be properly coped with noncombustible, weatherproof materials of a width no less than the thickness of the parapet wall.
1503.4 Roof drainage.
Design and installation of roof drainage systems shall comply with Chapter 11 of the New York City Plumbing Code and this section.
1503.4.1 Secondary (emergency overflow) drains or scuppers.
Where roof drains are required, secondary (emergency overflow) roof drains or scuppers shall be provided where the roof perimeter construction extends above the roof in such a manner that water will be entrapped if the primary drains allow buildup for any reason. The installation and sizing of secondary (emergency overflow) drains, leaders and conductors shall comply with Chapter 11 of the New York City Plumbing Code, as applicable.
1503.4.2 Scuppers.
When scuppers are used for secondary (emergency overflow) roof drainage, the quantity, size, location and inlet elevation of the scuppers shall be sized to prevent the depth of ponding water from exceeding that for which the roof was designed as determined by Section 1611.1. Scuppers shall not have an opening dimension of less than 4 inches (101.6 mm). The flow through the primary system shall not be considered when locating and sizing scuppers.
1503.4.3 Gutters.
Gutters placed on the outside of buildings shall be of noncombustible, corrosion-resistant material in accordance with Chapter 11 of the New York City Plumbing Code. Gutters and vertical sections of exterior leaders shall be adequately anchored. Gutters and leaders installed more than 15 feet (4572 mm) above grade shall be designed to resist loads in accordance with Chapter 16 of this code.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
1503.5 Attic and rafter ventilation.
Intake and exhaust vents shall be provided in accordance with Section 1203.2 and the vent product's manufacturer's instructions.
1503.6 Crickets and saddles.
A cricket or saddle shall be installed on the ridge side of any chimney or penetration greater than 30 inches (762 mm) wide as measured perpendicular to the slope. Cricket or saddle coverings shall be sheet metal or of the same material as the roof covering.
Exception: Unit skylights installed in accordance with Section 2405.5 and flashed in accordance with the manufacturer's instructions shall be permitted to be installed without a cricket or saddle.
Section BC 1504. Performance Requirements
1504.1 Wind resistance of roofs.
Roof decks and roof coverings shall be designed for wind loads in accordance with Chapter 16 and Sections 1504.2, 1504.3 and 1504.4.
1504.1.1 Wind resistance of asphalt shingles.
Asphalt shingles shall be tested in accordance with ASTM D 7158. Asphalt shingles shall meet the classification requirements of Table 1504.1.1 of this code for the appropriate maximum wind speed. Asphalt shingle packaging shall bear a label to indicate compliance with ASTM D 7158 and the required classification in Table 1504.1.1 of this code.
Exception: Asphalt shingles that are not included in the scope of ASTM D 7158 shall be tested and labeled to indicate compliance with ASTM D 3161 and the required classification in Table 1504.1.1 of this code.
Table 1504.1.1 Classification of Asphalt Shingles
Maximum Allowable Stress Design Wind Speed, V asd Maximum Basic Design Wind Speed, V, from Table 1609.3 ASTM D 7158 a Classification ASTM D 3161 Classification 88 110 D, G or H A, D or F 94 117 G or H A, D or F 102 127 G or H F 106 132 G or H F
1504.2 Wind resistance of clay and concrete tile.
Wind loads on clay and concrete tile roof coverings shall be in accordance with Section 1609.
1504.2.1 Testing.
Testing of concrete and clay roof tiles shall be in accordance with Sections 1504.2.1.1 and 1504.2.1.2.
1504.2.1.1 Overturning resistance.
Concrete and clay roof tiles shall be tested to determine their resistance to overturning due to wind in accordance with SBCCI SSTD 11 and this chapter.
1504.2.1.2 Wind tunnel testing.
Where concrete and clay roof tiles do not satisfy the limitations in Chapter 16 of this code for rigid tile, a wind tunnel test shall be used to determine the wind characteristics of the concrete or clay tile roof covering in accordance with SBCCI SSTD 11 and this chapter.
1504.3 Wind resistance of nonballasted roofs.
Roof coverings installed on roofs in accordance with Section 1507 that are mechanically attached or adhered to the roof deck shall be designed to resist the design wind load pressures for components and cladding in accordance with Section 1609.
1504.3.1 Other roof systems.
Built-up, modified bitumen, fully adhered or mechanically attached single-ply roof systems, metal panel roof systems applied to a solid or closely fitted deck and other types of membrane roof coverings shall be tested in accordance with FM 4474, UL 580 or UL 1897.
1504.3.2 Structural metal panel roof systems.
Where the metal roof panel functions as the roof deck and roof covering and it provides both weather protection and support for loads, the structural metal panel roof system shall comply with this section. Structural standing-seam metal panel roof systems shall be tested in accordance with ASTM E 1592 or FM 4474. Structural through-fastened metal panel roof systems shall be tested in accordance with FM 4474, UL 580 or ASTM E 1592.
Exceptions:
1. Metal roofs constructed of cold-formed steel shall be permitted to be designed and tested in accordance with the applicable referenced structural design standard in Section 2210.1.
2. Metal roofs constructed of aluminum shall be permitted to be designed and tested in accordance with the applicable referenced structural design standard in Section 2002.1.
1504.4 Ballasted low-slope roof systems.
Ballasted low-slope (roof slope < 2:12) single-ply roof system coverings installed in accordance with Sections 1507.12 and 1507.13 shall be designed in accordance with ANSI/SPRI RP-4 and Section 1504.8 of this code.
1504.5 Edge securement for low-slope roofs.
Low-slope membrane roof systems metal edge securement, except gutters, shall be designed and installed for wind loads in accordance with Chapter 16 and tested for resistance in accordance with Test Methods RE-1, RE-2 and RE-3 of ANSI/SPRI/FM 4435 ES-1, except the basic design wind speed V shall be determined in accordance with Chapter 16 of this code.
1504.6 Physical properties.
Roof coverings installed on low-slope roofs (roof slope < 2:12) in accordance with Section 1507 shall demonstrate physical integrity over the working life of the roof based upon 2,000 hours of exposure to accelerated weathering tests conducted in accordance with ASTM G 152, ASTM G 155 or ASTM G 154. Those roof coverings that are subject to cyclical flexural response due to wind loads shall not demonstrate any significant loss of tensile strength for unreinforced membranes or breaking strength for reinforced membranes when tested as herein required.
1504.7 Impact resistance.
Roof coverings installed on low-slope roofs (roof slope < 2:12) in accordance with Section 1507 shall resist impact damage based on the results of tests conducted in accordance with ASTM D 3746, ASTM D 4272, CGSB 37-GP-52M or the "Resistance to Foot Traffic Test" in Section 5.5 of FM 4470.
1504.8 Surfacing and ballast materials.
Aggregate, gravel or crushed stone shall not be used as surfacing for roof coverings.
1504.9 Reflectance.
Roof coverings on roofs or setbacks with slope equal to or less than two units vertical in 12 units horizontal (17 percent) shall have:
1. a minimum initial solar reflectance of 0.7 in accordance with ASTM C1549 or ASTM E 1918, and a minimum thermal emittance of 0.75 as determined in accordance with ASTM C1371 or ASTM E 408; or
2. a minimum SRI of 82 as determined in accordance with ASTM E 1980.
Roof coverings on roofs or setbacks with slope greater than two units vertical in 12 units horizontal (17 percent) shall have:
1. A minimum initial solar reflectance of 0.25 in accordance with ASTM C 1549 or ASTM E 1918, and a minimum thermal emittance of 0.75 as determined in accordance with ASTM C 1371 or ASTM E 408; or
2. A minimum SRI of 39 as determined in accordance with ASTM E 1980.
Exceptions:
1. Terraces on setbacks comprising less than 25 percent of the area of the largest floor plate in the building.
2. Any portion of a roof covered by a green roof system, including such a system with agricultural plantings, in compliance with Section 1507.16 of this code.
3. Any portion of a roof used as outdoor recreation space by the occupants of the building that is landscaped, covered by wood decking or covered with a walking surface or other protective surface, provided that such walking surface or protective surface has a minimum initial solar reflectance of 0.3 as determined in accordance with ASTM C 1549 or ASTM E 1918.
4. Ballasted roofs, provided that the ballast has a minimum initial solar reflectance of 0.2 as determined in accordance with ASTM C 1549 or ASTM E 1918.
5. Any portion of a roof that is under mechanical equipment, flush mounted solar panels lying directly on the roof surface, duckboarding, decking, platform, roof tank, cooling tower or any other rooftop structure or equipment exempted by rule by the commissioner.
6. Any roof or portion of a roof composed of glass, metal, clay or concrete tile or plastic/rubber intended to simulate clay or concrete tile, wood, or slate.
7. Any portion of a roof used by a school or daycare center as a playground for children.
8. Any roof, if the amount of rooftop space not subject to exceptions 1 through 7 is in the aggregate less than 100 square feet.
(Am. L.L. 2019/094, 5/19/2019, eff. 11/15/2019)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2011/021.
Section BC 1505. Fire Classification
1505.1 General.
Roof assemblies shall be divided into the classes defined below. Class A, B and C roof assemblies and roof coverings required to be listed by this section shall be tested in accordance with ASTM E 108 or UL 790. In addition, fire-retardant-treated wood roof coverings shall be tested in accordance with ASTM D 2898. The minimum roof coverings installed on buildings shall comply with Table 1505.1 of this code based on the type of construction of the building.
Exception: Skylights and sloped glazing that comply with Chapter 24 or Section 2610 of this code.
Table 1505.1 a, b Minimum Roof Covering Classification for Types of Construction
IA IB IIA IIB IIIA IIIB IV VA VB B B B B B B B B C b
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m 2
a. Unless otherwise required due to the location of the building within a fire district in accordance with Section D102.2.3 in Appendix D.
b. Buildings that are not more than two stories above grade plane and having not more than 6,000 square feet (557.4 m 2 ) of projected roof area and where there is a minimum 10-foot fire-separation distance from the leading edge of the roof to a lot line on all sides of the building, except for street fronts or public ways, shall be permitted to have roofs of No. 1 cedar or redwood shakes and No. 1 shingles in accordance with Section 1505.6.
1505.2 Class A roof assemblies.
Class A roof assemblies are those that are effective against severe fire test exposure. Class A roof assemblies and roof coverings shall be listed and identified as Class A by an approved testing agency. Class A roof assemblies shall be permitted for use in buildings or structures of all types of construction.
Exceptions:
1. Class A roof assemblies include those with coverings of brick, masonry, or an exposed concrete roof deck.
2. Class A roof assemblies also include ferrous or copper shingles or sheets, metal sheets and shingles, clay or concrete roof tile or slate installed on noncombustible decks or ferrous, copper or metal sheets installed without a roof deck on noncombustible framing.
3. Class A roof assemblies include minimum 16 ounce per square foot (0.0416 kg/m 2 ) copper sheets installed over combustible decks.
4. Class A roof assemblies include slate installed over ASTM D 226, Type II underlayment over combustible decks.
1505.3 Class B roof assemblies.
Class B roof assemblies are those that are effective against moderate fire-test exposure. Class B roof assemblies and roof coverings shall be listed and identified as Class B by an approved testing agency.
1505.4 Class C roof assemblies.
Class C roof assemblies are those that are effective against light fire-test exposure. Class C roof assemblies and roof coverings shall be listed and identified as Class C by an approved testing agency.
1505.5 Construction of sloping roofs.
Roofs having a slope of more than 60 degrees (1.05 rad) to the horizontal shall be constructed of material having the same fire-resistance rating as required for an exterior nonbearing wall of the building of which it is a part. When the slope is 60 degrees (1.05 rad) or less to the horizontal, the sloping roof shall be constructed as required for the roof of the building. Where the back of a false mansard is exposed to the outdoors, the back shall be covered with noncombustible material or with roof covering as required for the roof of the building.
1505.6 Fire-retardant-treated wood shingles and shakes.
Fire-retardant-treated wood shakes and shingles shall be treated by impregnation with chemicals by the full-cell vacuum-pressure process, in accordance with AWPA C1. Each bundle shall be marked to identify the manufactured unit and the manufacturer, and shall also be labeled to identify the classification of the material in accordance with the testing required in Section 1505.1, the treating company and the quality control agency.
1505.7 Special purpose roofs.
Special purpose wood shingle or wood shake roofing shall conform to the grading and application requirements of Section 1507.8 or Section 1507.9. In addition, an underlayment of 5/8 inch (15.9 mm) Type X water-resistant gypsum backing board or gypsum sheathing shall be placed under minimum nominal 1/2-inch (12.7 mm) thick wood structural panel solid sheathing or 1-inch (25.4 mm) nominal spaced sheathing.
1505.8 Building-integrated photovoltaic products.
Building-integrated photovoltaic products installed as the roof covering shall be tested, listed and labeled for fire classification in accordance with Section 1505.1.
1505.9 Photovoltaic panels and modules.
Rooftop-mounted photovoltaic panel systems shall be tested, listed and identified with a fire classification in accordance with UL 1703. The fire classification shall comply with Table 1505.1 of this code based on the type of construction of the building.
1505.10 Roof gardens and landscaped roofs.
Roof gardens and landscaped roofs shall comply with Section 1507.16.
Section BC 1506. Materials
1506.1 Scope.
The requirements set forth in this section shall apply to the application of roof-covering materials specified herein. Roof coverings shall be applied in accordance with this chapter and the manufacturer's instructions. Installation of roof coverings shall comply with the applicable provisions of Section 1507.
1506.2 Material specifications and physical characteristics.
Roof-covering materials shall conform to the applicable standards listed in this chapter. In the absence of applicable standards or where materials are of questionable suitability, testing by an approved agency shall be required by the commissioner to determine the character, quality and limitations of application of the materials.
1506.3 Product identification.
Roof-covering materials shall be delivered in packages bearing the manufacturer's identifying marks and approved testing agency labels required in accordance with Section 1505. Bulk shipments of materials shall be accompanied with the same information issued in the form of a certificate or on a bill of lading by the manufacturer.
Section BC 1507. Requirements for Roof Coverings
1507.1 Scope.
Roof coverings shall be applied in accordance with the applicable provisions of this section and the manufacturer's instructions.
1507.2 Asphalt shingles.
The installation of asphalt shingles shall comply with the provisions of this section.
1507.2.1 Deck requirements.
Asphalt shingles shall be fastened to solidly sheathed decks.
1507.2.2 Slope.
Asphalt shingles shall only be used on roof slopes of two units vertical in 12 units horizontal (17-percent slope) or greater. For roof slopes from two units vertical in 12 units horizontal (17-percent slope) up to four units vertical in 12 units horizontal (33-percent slope), double underlayment application is required in accordance with Section 1507.2.8.
1507.2.3 Underlayment.
Unless otherwise noted, required underlayment shall conform to ASTM D 226, Type I, ASTM D 4869, Type I, or ASTM D 6757.
1507.2.4 Self-adhering polymer modified bitumen sheet.
Self-adhering polymer modified bitumen sheet shall comply with ASTM D 1970.
1507.2.5 Asphalt shingles.
Asphalt shingles shall comply with ASTM D 225 or ASTM D 3462.
1507.2.6 Fasteners.
Fasteners for asphalt shingles shall be galvanized, stainless steel, aluminum or copper roofing nails, minimum 12-gage (0.105-inch (2.67 mm)) shank with a minimum 3/8 inch-diameter (9.5 mm) head, of a length to penetrate through the roofing materials and a minimum of 3/4 inch (19.1 mm) into the roof sheathing. Where the roof sheathing is less than 3/4 inch (19.1 mm) thick, the nails shall penetrate through the sheathing. Fasteners shall comply with ASTM F 1667.
1507.2.7 Attachment.
Asphalt shingles shall have the minimum number of fasteners required by the manufacturer, but not less than four fasteners per strip shingle or two fasteners per individual shingle. Where the roof slope exceeds 21 units vertical in 12 units horizontal (21:12), shingles shall be installed as required by the manufacturer.
1507.2.8 Underlayment application.
For roof slopes from two units vertical in 12 units horizontal (17-percent slope), up to four units vertical in 12 units horizontal (33-percent slope), underlayment shall be two layers applied in the following manner. Apply a minimum 19-inch (482.6 mm) wide strip of underlayment felt parallel with and starting at the eaves, fastened sufficiently to hold in place. Starting at the eave, apply 36-inch (914.4 mm) wide sheets of underlayment overlapping successive sheets 19 inches (482.6 mm) and fastened sufficiently to hold in place. Distortions in the underlayment shall not interfere with the ability of the shingles to seal. For roof slopes of four units vertical in 12 units horizontal (33-percent slope) or greater, underlayment shall be one layer applied in the following manner. Underlayment shall be applied shingle fashion, parallel to and starting from the eave and lapped 2 inches (50.8 mm), fastened only as necessary to hold in place. Distortions in the underlayment shall not interfere with the ability of the shingles to seal.
1507.2.8.1 Ice barrier.
An ice barrier that consists of at least two layers of underlayment cemented together or of a self-adhering polymer modified bitumen sheet shall be used in lieu of normal underlayment and extend from the lowest edges of all roof surfaces to a point at least 24 inches (609.6 mm) inside the exterior wall line of the building.
Exception: Detached accessory structures that contain no conditioned floor area.
1507.2.9 Flashings.
Flashing for asphalt shingles shall comply with this section. Flashing shall be applied in accordance with this section and the asphalt shingle manufacturer's instructions.
1507.2.9.1 Base and cap flashing.
Base and cap flashing shall be installed in accordance with the manufacturer's instructions. Base flashing shall be of either corrosion-resistant metal of minimum nominal 0.019-inch (0.483 mm) thickness or mineral-surfaced roll roofing weighing a minimum of 77 pounds per 100 square feet (3.76 kg/m 2 ). Cap flashing shall be corrosion-resistant metal of minimum nominal 0.019-inch (0.483 mm) thickness.
1507.2.9.2 Valleys.
Valley linings shall be installed in accordance with the manufacturer's instructions before applying shingles. Valley linings of the following types shall be permitted:
1. For open valleys (valley lining exposed) lined with metal, the valley lining shall be at least 24 inches (609.6 mm) wide and of any of the corrosion-resistant metals in Table 1507.2.9.2.
2. For open valleys, valley lining of two plies of mineral-surfaced roll roofing complying with ASTM D 3909 or ASTM D 6380 shall be permitted. The bottom layer shall be 18 inches (457.2 mm) and the top layer a minimum of 36 inches (914.4 mm) wide.
3. For closed valleys (valleys covered with shingles), valley lining of one ply of smooth roll roofing complying with ASTM D 6380, and at least 36 inches (914.4 mm) wide or types as described in Item 1 or 2 above shall be permitted. Self-adhering polymer modified bitumen underlayment complying with ASTM D 1970 shall be permitted in lieu of the lining material.
Table 1507.2.9.2 Valley Lining Material
Material Minimum Thickness Gage Weight Aluminum 0.024 in. — — Cold-rolled copper 0.0216 in. — ASTM B 370, 16 oz. per square ft. Copper — — 16 oz. Galvanized steel 0.0179 in. 26 (zinc-coated G90) — High-yield copper 0.0162 in. — ASTM B 370, 12 oz. per square ft. Lead — — 2.5 pounds Lead-coated copper 0.0216 in. — ASTM B 101, 16 oz. per square ft. Lead-coated high-yield copper 0.0162 in. — ASTM B 101, 12 oz. per square ft. Painted terne — — 20 pounds Stainless steel — 28 — Zinc alloy 0.027 in. — —
For SI: 1 inch = 25.4 mm, 1 pound = 0.454 kg, 1 ounce = 28.35 g, 1 square foot = 0.0929 m 2 .
1507.2.9.3 Drip edge.
A drip edge shall be provided at eaves and rake edges of shingle roofs. Adjacent segments of the drip edge shall be lapped a minimum of 2 inches (50.8 mm). The vertical leg of drip edges shall be a minimum of 1 1/2 inches (38.1 mm) in width and shall extend a minimum of 1/4 inch (6.4 mm) below sheathing. The drip edge shall extend back on the roof a minimum of 2 inches (50.8 mm). Underlayment shall be installed over drip edges along eaves. Drip edges shall be installed over underlayment along rake edges. Drip edges shall be mechanically fastened a maximum of 12 inches (304.8 mm) on center.
1507.3 Clay and concrete tile.
The installation of clay and concrete tile shall comply with the provisions of this section.
1507.3.1 Deck requirements.
Concrete and clay tile shall be installed only over solid sheathing or spaced structural sheathing boards.
1507.3.2 Deck slope.
Clay and concrete roof tile shall be installed on roof slopes of 2 1/2 units vertical in 12 units horizontal (21-percent slope) or greater. For roof slopes from 2 1/2 units vertical in 12 units horizontal (21-percent slope) to four units vertical in 12 units horizontal (33-percent slope), double underlayment application is required in accordance with Section 1507.3.3.
1507.3.3 Underlayment.
Unless otherwise noted, required underlayment shall conform to: ASTM D 226, Type II; ASTM D 2626 or ASTM D 6380, Class M mineral-surfaced roll roofing.
1507.3.3.1 Low-slope roofs.
For roof slopes from 2 1/2 units vertical in 12 units horizontal (21-percent slope), up to four units vertical in 12 units horizontal (33-percent slope), underlayment shall be a minimum of two layers applied as follows:
1. Starting at the eave, a 19-inch (482.6 mm) strip of underlayment shall be applied parallel with the eave and fastened sufficiently in place.
2. Starting at the eave, 36-inch (914.4 mm) wide strips of underlayment felt shall be applied overlapping successive sheets 19 inches (482.6 mm) and fastened sufficiently in place.
1507.3.3.2 High-slope roofs.
For roof slopes of four units vertical in 12 units horizontal (33-percent slope) or greater, underlayment shall be a minimum of one layer of underlayment felt applied shingle fashion, parallel to, and starting from the eaves and lapped 2 inches (50.8 mm), fastened only as necessary to hold in place.
1507.3.4 Clay tile.
Clay roof tile shall comply with ASTM C 1167.
1507.3.5 Concrete tile.
Concrete roof tile shall comply with ASTM C 1492.
1507.3.6 Fasteners.
Tile fasteners shall be corrosion resistant and not less than 11 gage, 5/16-inch (8.0 mm) head, and of sufficient length to penetrate the deck a minimum of 3/4 inch (19.1 mm) or through the thickness of the deck, whichever is less. Attaching wire for clay or concrete tile shall be not less than 0.083 inch (2.1 mm). Perimeter fastening areas include three tile courses but not less than 36 inches (914.4 mm) from either side of hips or ridges and edges of eaves and gable rakes.
1507.3.7 Attachment.
Clay and concrete roof tiles shall be fastened in accordance with Table 1507.3.7.
Table 1507.3.7 Clay and Concrete Tile Attachment a, b, c
General – Clay or Concrete Roof Tile Maximum Nominal Design Wind Speed, V asd f (mph) Mean roof height (feet) Roof slope £ 3:12 Roof slope 3:12 and over 85 0 - 60 One fastener per tile. Flat tile without vertical laps, two fasteners per tile. Two fasteners per tile. Only one fastener on slopes of 7:12 and less for tiles with installed weight exceeding 7.5 lbs./sq. ft. having a width no greater than 16 inches. 100 0 - 40 100 > 40 - 60 The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved clips. All rake tiles shall be nailed with two nails. The nose of all ridge, hip and rake tiles shall be set in a bead of roofer's mastic. 110 0 - 60 The fastening system shall resist the wind forces in Section 1609.5.3. 120 0 - 60 The fastening system shall resist the wind forces in Section 1609.5.3. 130 0 - 60 The fastening system shall resist the wind forces in Section 1609.5.3. All > 60 The fastening system shall resist the wind forces in Section 1609.5.3. Interlocking Clay or Concrete Roof Tile with Projecting Anchor Lugs d, e (Installations on spaced/solid sheathing with battens or spaced sheathing) Maximum Nominal Design Wind Speed, V asd f (mph) Mean roof height (feet) Roof slope < 5:12 Roof slope 5:12 < 12:12 Roof slope 12:12 and over 85 0 - 60 Fasteners are not required. Tiles with installed weight less than 9 lbs./sq. ft. require a minimum of one fastener per tile. One fastener per tile every other row. All perimeter tiles require one fastener. Tiles with installed weight less than 9 lbs./sq. ft. require a minimum of one fastener per tile. One fastener required for every tile. Tiles with installed weight less than 9 lbs./sq. ft. require a minimum of one fastener per tile. 100 0 - 40 100 > 40 - 60 The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved clips. All rake tiles shall be nailed with two nails The nose of all ridge, hip and rake tiles shall be set in a bead of roofers' mastic. 110 0 - 60 The fastening system shall resist the wind forces in 1609.5.3. 120 0 - 60 The fastening system shall resist the wind forces in 1609.5.3. 130 0 - 60 The fastening system shall resist the wind forces in 1609.5.3. All > 60 The fastening system shall resist the wind forces in 1609.5.3. Interlocking Clay or Concrete Roof Tile with Projecting Anchor Lugs (Installations on solid sheathing without battens) Maximum Nominal Design Wind Speed, V asd f (mph) Mean roof height (feet) All roof slopes 85 0 - 60 One fastener per tile. 100 0 - 40 One fastener per tile. 100 > 40 - 60 The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved clips. All rake tiles shall be nailed with two nails The nose of all ridge, hip and rake tiles shall be set in a bead of roofers' mastic. 110 0 - 60 The fastening system shall resist the wind forces in 1609.5.3. 120 0 - 60 The fastening system shall resist the wind forces in 1609.5.3. 130 0 - 60 The fastening system shall resist the wind forces in 1609.5.3. All > 60 The fastening system shall resist the wind forces in 1609.5.3.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 4.882kg/m 2 .
a. Minimum fastener size. Corrosion-resistant nails not less than No. 11 gage with 5/16-inch head. Fasteners shall be long enough to penetrate into the sheathing 3/4 inch or through the thickness of the sheathing, whichever is less. Attaching wire for clay and concrete tile shall not be smaller than 0.083 inch.
b. Snow areas. A minimum of two fasteners per tile are required or battens and one fastener.
c. Roof slopes greater than 24:12. The nose of all tiles shall be securely fastened.
d. Horizontal battens. Battens shall be not less than 1 inch by 2 inch nominal. Provisions shall be made for drainage by a minimum of 1/8-inch riser at each nail or by 4-foot-long battens with at least a 1/2-inch separation between battens. Horizontal battens are required for slopes over 7:12.
e. Perimeter fastening areas include three tile courses but not less than 36 inches from either side of hips or ridges and edges of eaves and gable rakes.
f. V asd shall be determined in accordance with Section 1609.3.1.
1507.3.8 Application.
Tile shall be applied according to the manufacturer's instructions, based on the following:
1. Climatic conditions.
2. Roof slope.
3. Underlayment system.
4. Type of tile being installed.
1507.3.9 Flashing.
At the juncture of the roof vertical surfaces, flashing and counterflashing shall be provided in accordance with the manufacturer's instructions, and where of metal, shall not be less than 0.019-inch (0.48 mm) (No. 26 galvanized sheet gage) corrosion-resistant metal. The valley flashing shall extend at least 11 inches (279 mm) from the centerline each way and have a splash diverter rib not less than 1 inch (24.5 mm) high at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (101.6 mm). For roof slopes of three units vertical in 12 units horizontal (25-percent slope) and over, the valley flashing shall have a 36-inch (914.4 mm) wide underlayment of either one layer of Type I underlayment running the full length of the valley, or a self-adhering polymer-modified bitumen sheet complying with ASTM D 1970, in addition to other required underlayment. For slopes under seven units vertical in 12 units horizontal (58-percent slope), the metal valley flashing underlayment shall be solid cemented to the roofing underlayment or a self-adhering polymer modified bitumen sheet shall be installed.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2014/051.
1507.4 Metal roof panels.
The installation of metal roof panels shall comply with the provisions of this section.
1507.4.1 Deck requirements.
Metal roof panel roof coverings shall be applied to a solid or closely fitted deck, except where the roof covering is specifically designed to be applied to spaced supports.
1507.4.2 Deck slope.
The minimum slope for metal roof panels shall comply with the following:
1. The minimum slope for lapped, nonsoldered seam metal roof panels without applied lap sealant shall be three units vertical in 12 units horizontal (25-percent slope).
2. The minimum slope for lapped, nonsoldered seam metal roof panels with applied lap sealant shall be one-half vertical unit in 12 units horizontal (4-percent slope). Lap sealants shall be applied in accordance with the manufacturer's instructions.
3. The minimum slope for standing-seam metal roof panel systems shall be one-quarter unit vertical in 12 units horizontal (2-percent slope).
1507.4.3 Material standards.
Metal-sheet roof covering systems that incorporate supporting structural members shall be designed in accordance with Chapter 22. Metal-sheet roof coverings installed over structural decking shall comply with Table 1507.4.3(1). The materials used for metal-sheet roof coverings shall be naturally corrosion resistant or provided with corrosion resistance in accordance with the standards and minimum thicknesses shown in Table 1507.4.3(2).
Table 1507.4.3(1) Metal Roof Coverings
Roof Covering Type Standard Application Rate/Thickness Aluminum ASTM B 209, 0.024 inch minimum thickness for roll-formed panels and 0.019 inch minimum thickness for press-formed shingles. Aluminum-zinc alloy coated steel ASTM A 792 AZ 50 Cold-rolled copper ASTM B 370 minimum 16 oz./sq. ft. and 12 oz./sq. ft. high yield copper for metal-sheet roof covering systems: 12 oz./sq. ft. for preformed metal shingle systems. Copper 16 oz./sq. ft. for metal-sheet roof-covering systems; 12 oz./sq. ft. for pre-formed metal shingle systems. Galvanized steel ASTM A 653 G-90 zinc-coated a Hard lead 2 lbs / sq. ft Lead-coated copper ASTM B 101 Prepainted steel ASTM A 755 Soft lead 3 lbs./sq. ft Stainless steel ASTM A 240, 300 Series Alloys Steel ASTM A 924 Terne and terne-coated stainless Terne coating of 40 lbs. per double base box, field painted where applicable in accordance with manufacturer's instructions. Zinc 0.027 inch minimum thickness; 99.995% electrolytic high grade zinc with alloy additives of copper (0.08% - 0.20%), titanium (0.07% - 0.12%) and aluminum (0.015%).
For SI: 1 ounce per square foot = 0.305 kg/m 2 , 1 pound per square foot = 4.882 kg/m 2 , 1 inch = 25.4 mm, 1 pound = 0.454 kg.
a. For Group U buildings, the minimum coating thickness for ASTM A 653 galvanized steel roofing shall be G-60.
Table 1507.4.3(2) Minimum Corrosion Resistance
Material Standard 55% Aluminum-zinc alloy coated steel ASTM A 792 AZ 50 5% Aluminum alloy-coated steel ASTM A 875 GF60 Aluminum-coated steel ASTM A 463 T2 65 Galvanized steel ASTM A 653 G-90 Prepainted steel ASTM A 755 a
a. Paint systems in accordance with ASTM A 755 shall be applied over steel products with corrosion resistant coatings complying with ASTM A 792, ASTM A 875, ASTM A 463 or ASTM A 653.
1507.4.4 Attachment.
Metal roof panels shall be secured to the supports in accordance with the approved manufacturers' fasteners. In the absence of manufacturer recommendations, the following fasteners shall be used:
1. Galvanized fasteners shall be used for steel roofs.
2. Copper, brass, bronze, copper alloy or 300 series stainless-steel fasteners shall be used for copper roofs.
3. Stainless-steel fasteners are acceptable for all types of metal roofs.
4. Aluminum fasteners are acceptable for aluminum roofs attached to aluminum supports.
1507.5 Metal roof shingles.
The installation of metal roof shingles shall comply with the provisions of this section.
1507.5.1 Deck requirements.
Metal roof shingles shall be applied to a solid or closely fitted deck, except where the roof covering is specifically designed to be applied to spaced sheathing.
1507.5.2 Deck slope.
Metal roof shingles shall not be installed on roof slopes below three units vertical in 12 units horizontal (25-percent slope).
1507.5.3 Underlayment.
Underlayment shall comply with ASTM D 226, Type I or ASTM D 4869.
1507.5.4 Ice barrier.
An ice barrier that consists of at least two layers of underlayment cemented together or of a self-adhering polymer-modified bitumen sheet, shall be used in lieu of normal underlayment and extend from the ' lowest edges of all roof surfaces to a point at least 24 inches (610 mm) inside the exterior wall line of the building.
Exception: Detached accessory structures that contain no conditioned floor area.
1507.5.5 Material standards.
Metal roof shingle roof coverings shall comply with Table 1507.4.3(1). The materials used for metal-roof shingle roof coverings shall be naturally corrosion resistant or provided with corrosion resistance in accordance with the standards and minimum thicknesses specified in the standards listed in Table 1507.4.3(2).
1507.5.6 Attachment.
Metal roof shingles shall be secured to the roof in accordance with the manufacturer's instructions.
1507.5.7 Flashing.
Roof valley flashing shall be of corrosion-resistant metal of the same material as the roof covering or shall comply with the standards in Table 1507.4.3(1). The valley flashing shall extend at least 8 inches (203.2 mm) from the centerline each way and shall have a splash diverter rib not less than 3/4 inch (19.1 mm) high at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (101.6 mm). The metal valley flashing shall have a 36-inch (914.4 mm) wide underlayment directly under it consisting of either one layer of underlayment running the full length of the valley or a self-adhering polymer-modified bitumen sheet complying with ASTM D 1970, in addition to underlayment required for metal roof shingles. For slopes under seven units vertical in 12 units horizontal (58-percent slope), the metal valley flashing underlayment shall be solid cemented to the roofing underlayment or a self-adhering polymer modified bitumen sheet shall be installed.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2014/051.
1507.6 Mineral-surfaced roll roofing.
The installation of mineral-surfaced roll roofing shall comply with this section.
1507.6.1 Deck requirements.
Mineral-surfaced roll roofing shall be fastened to solidly sheathed roofs.
1507.6.2 Deck slope.
Mineral-surfaced roll roofing shall not be applied on roof slopes below one unit vertical in 12 units horizontal (8-percent slope).
1507.6.3 Underlayment.
Underlayment shall comply with ASTM D 226, Type I or ASTM D 4869.
1507.6.4 Ice barrier.
An ice barrier that consists of at least two layers of underlayment cemented together or of a self-adhering polymer-modified bitumen sheet, shall be used in lieu of normal underlayment and extend from the lowest edges of all roof surfaces to a point at least 24 inches (609.6 mm) inside the exterior wall line of the building.
Exception: Detached accessory structures that contain no conditioned floor area.
1507.6.5 Material standards.
Mineral-surfaced roll roofing shall conform to ASTM D 3909 or ASTM D 6380.
1507.7 Slate shingles.
The installation of slate shingles shall comply with the provisions of this section.
1507.7.1 Deck requirements.
Slate shingles shall be fastened to solidly sheathed roofs.
1507.7.2 Deck slope.
Slate shingles shall only be used on slopes of four units vertical in 12 units horizontal (4:12) or greater.
1507.7.3 Underlayment.
Underlayment shall comply with ASTM D 226, Type II or ASTM D 4869, Type III or IV.
1507.7.4 Ice barrier.
An ice barrier that consists of at least two layers of underlayment cemented together or of a self-adhering polymer-modified bitumen sheet, shall extend from the lowest edges of all roof surfaces to a point at least 24 inches (609.6 mm) inside the exterior wall line of the building.
Exception: Detached accessory structures that contain no conditioned floor area.
1507.7.5 Material standards.
Slate shingles shall comply with ASTM C 406.
1507.7.6 Application.
Minimum headlap for slate shingles shall be in accordance with Table 1507.7.6 Slate shingles shall be secured to the roof with two fasteners per slate.
Table 1507.7.6 Slate Shingle Headlap
Slope Headlap (inches) 4:12 < slope < 8:12 4 8:12 < slope < 20:12 3 slope ³ 20:12 2
For SI: 1 inch = 25.4 mm.
1507.7.7 Flashing.
Flashing and counterflashing shall be made with sheet metal. Valley flashing shall be a minimum of 15 inches (381 mm) wide. Valley and flashing metal shall be a minimum uncoated thickness of 0.0179-inch (0.455 mm) zinc-coated G90. Chimneys, stucco or brick walls shall have a minimum of two plies of felt for a cap flashing consisting of a 4-inch (101.6 mm) wide strip of felt set in plastic cement and extending 1 inch (25.4 mm) above the first felt and a top coating of plastic cement. The felt shall extend over the base flashing 2 inches (50.8 mm).
1507.8 Wood shingles.
The installation of wood shingles shall comply with the provisions of this section and Table 1507.8.
Table 1507.8 Wood Shingle and Shake Installation
Roof Item Wood Shingles Wood Shakes 1. Roof slope Wood shingles shall be installed on slopes of not less than three units vertical in 12 units horizontal (3:12). Wood shakes shall be installed on slopes of not less than four units vertical in 12 units horizontal (4:12). 2. Deck requirement Temperate climate Shingles shall be applied to roofs with solid or spaced sheathing. Where spaced sheathing is used, sheathing boards shall be not less than 1" × 4" nominal dimensions and shall be spaced on centers equal to the weather exposure to coincide with the placement of fasteners. Shakes shall be applied to roofs with solid or spaced sheathing. Where spaced sheathing is used, sheathing boards shall be not less than 1" × 4" nominal dimensions and shall be spaced on centers equal to the weather exposure to coincide with the placement of fasteners. When1" × 4" spaced sheathing is installed at 10 inches, boards must be installed between the sheathing boards. Ice forming along the eaves causing a backup of water. Solid sheathing required. Solid sheathing is required. 3. Interlayment No requirements. Interlayment shall comply with ASTM D 226, Type 1. 4. Underlayment Temperate climate Underlayment shall comply with ASTM D 226, Type 1. Underlayment shall comply with ASTM D 226, Type 1. Ice forming along the eaves causing a backup of water. An ice barrier that consists of at least two layers of underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall extend from the eave's edge to a point at least 24 inches inside the exterior wall line of the building. An ice barrier that consists of at least two layers of underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall extend from the lowest eave's edge of all roof surfaces to a point at least 24 inches inside the exterior wall line of the building. 5. Application Attachment Fasteners for wood shingles shall be hot-dipped galvanized or Type 304 (Type 316 for coastal areas) stainless steel with a minimum penetration of 0.75 inch into the sheathing. For sheathing less than 0.5 inch thick, the fasteners shall extend through the sheathing. Fasteners for wood shakes shall be hot-dipped galvanized or Type 304 (Type 316 for coastal areas) with a minimum penetration of 0.75 inch into the sheathing. For sheathing less than 0.5 inch thick, the fasteners shall extend through the sheathing. No. of fasteners Two per shingle. Two per shake. Exposure Weather exposures shall not exceed those set forth in Table 1507.8.7 Weather exposures shall not exceed those set forth in Table 1507.9.8 Method Shingles shall be laid with a side lap of not less than 1.5 inches between joints in courses, and no two joints in any three adjacent courses shall be in direct alignment. Spacing between shingles shall be 0.25 to 0.375 inch. Shakes shall be laid with a side lap of not less than 1.5 inches between joints in adjacent courses. Spacing between shakes shall not be less than 0.375 inch or more than 0.625 inch for shakes and taper sawn shakes of naturally durable wood and shall be 0.25 to 0.375 inch for preservative-treated taper sawn shakes. Flashing In accordance with Section 1507.8.8. In accordance with Section 1507.9.9.
For SI: 1 inch = 25.4 mm, °C = ((°F) - 32)/1.8.
1507.8.1 Deck requirements.
Wood shingles shall be installed on solid or spaced sheathing. Where spaced sheathing is used, sheathing boards shall be not less than 1-inch by 4-inch (25.4 mm by 101.6 mm) nominal dimensions and shall be spaced on centers equal to the weather exposure to coincide with the placement of fasteners.
1507.8.1.1 Solid sheathing required.
Solid sheathing is required.
1507.8.2 Deck slope.
Wood shingles shall be installed on slopes of not less than three units vertical in 12 units horizontal (25-percent slope).
1507.8.3 Underlayment.
Underlayment shall comply with ASTM D 226, Type I or ASTM D 4869.
1507.8.4 Ice barrier.
An ice barrier that consists of at least two layers of underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall be used in lieu of normal underlayment and extend from the ' lowest edges of all roof surfaces to a point at least 24 inches (609.6 mm) inside the exterior wall line of the building.
Exception: Detached accessory structures that contain no conditioned floor area.
1507.8.5 Material standards.
Wood shingles shall be of naturally durable wood and comply with the requirements of Table 1507.8.5.
Table 1507.8.5 Wood Shingle Material Requirements
Material Applicable Minimum Grades Grading Rules Wood shingles of naturally durable wood 1, 2 or 3 CSSB
CSSB = Cedar Shake and Shingle Bureau
1507.8.6 Attachment.
Fasteners for wood shingles shall be corrosion resistant with a minimum penetration of 3/4 inch (19.1 mm) into the sheathing. For sheathing less than 1/2 inch (12.7 mm) in thickness, the fasteners shall extend through the sheathing. Each shingle shall be attached with a minimum of two fasteners.
1507.8.7 Application.
Wood shingles shall be laid with a side lap not less than 1 1/2 inches (38.1 mm) between joints in adjacent courses, and not be in direct alignment in alternate courses. Spacing between shingles shall be 1/4 to 3/8 inches (6.4 to 9.5 mm). Weather exposure for wood shingles shall not exceed that set in Table 1507.8.7.
Table 1507.8.7 Wood Shingle Weather Exposure and Roof Slope
Roofing Material Length (inches) Grade Exposure (inches) 3:12 pitch to < 4:12 4:12 pitch or steeper Shingles of naturally durable wood 16 No. 1 No. 2 No. 3 3.75 3.5 3 5 4 3.5 18 No. 1 No. 2 No. 3 4.25 4 3.5 5.5 4.5 4 24 No. 1 No. 2 No. 3 5.75 5.5 5 7.5 6.5 5.5
For SI: 1 inch = 25.4 mm.
1507.8.8 Flashing.
At the juncture of the roof and vertical surfaces, flashing and counterflashing shall be provided in accordance with the manufacturer's instructions, and where of metal, shall be not less than 0.019-inch (0.48 mm) (No. 26 galvanized sheet gage) corrosion-resistant metal. The valley flashing shall extend at least 11 inches (279 mm) from the centerline each way and have a splash diverter rib not less than 1 inch (25.4 mm) high at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (101.6 mm). For roof slopes of three units vertical in 12 units horizontal (25-percent slope) and over, the valley flashing shall have a 36-inch (914.4 mm) wide underlayment of either one layer of Type I underlayment running the full length of the valley or a self-adhering polymer-modified bitumen sheet complying with ASTM D 1970, in addition to other required underlayment. For slopes under seven units vertical in 12 units horizontal (58-percent slope), the metal valley flashing underlayment shall be solid cemented to the roofing underlayment or a self-adhering polymer modified bitumen sheet shall be installed.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2014/051.
1507.9 Wood shakes.
The installation of wood shakes shall comply with the provisions of this section and Table 1507.8.
1507.9.1 Deck requirements.
Wood shakes shall only be used on solid or spaced sheathing. Where spaced sheathing is used, sheathing boards shall be not less than 1-inch by 4-inch (25.4 mm by 101.6 mm) nominal dimensions and shall be spaced on centers equal to the weather exposure to coincide with the placement of fasteners. Where 1-inch by 4-inch (25.4 mm by 101.6 mm) spaced sheathing is installed at 10 inches (254 mm) on center, additional 1-inch by 4-inch (25.4 mm by 101.6 mm) boards shall be installed between the sheathing boards.
1507.9.1.1 Solid sheathing required.
Solid sheathing is required in areas where the average daily temperature in January is 25°F (-4°C) or less or where there is a possibility of ice forming along the eaves causing a backup of water.
1507.9.2 Deck slope.
Wood shakes shall only be used on slopes of not less than four units vertical in 12 units horizontal (33-percent slope).
1507.9.3 Underlayment.
Underlayment shall comply with ASTM D 226, Type I or ASTM D 4869.
1507.9.4 Ice barrier.
An ice barrier that consists of at least two layers of underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall be used in lieu of normal underlayment and extend from the lowest edges of all roof surfaces to a point at least 24 inches (609.6 mm) inside the exterior wall line of the building.
Exception: Detached accessory structures that contain no conditioned floor area.
1507.9.5 Interlayment.
Interlayment shall comply with ASTM D 226, Type I.
1507.9.6 Material standards.
Wood shakes shall comply with the requirements of Table 1507.9.6.
Table 1507.9.6 Wood Shake Material Requirements
Material Minimum Grades Applicable Grading Rules Wood shakes of naturally durable wood 1 CSSB Taper sawn shakes of naturally durable wood 1 or 2 CSSB Preservative-treated shakes and shingles of naturally durable wood 1 CSSB Fire-retardant-treated shakes and shingles of naturally durable wood 1 CSSB Preservative-treated taper sawn shakes of Southern pine treated in accordance with AWPA U1 (Commodity Specification A, Use Category 3B and Section 5.6) 1 or 2 TFS
CSSB = Cedar Shake and Shingle Bureau.
TFS = Forest Products Laboratory of the Texas Forest Services.
1507.9.7 Attachment.
Fasteners for wood shakes shall be corrosion resistant with a minimum penetration of 3/4 inch (19.1 mm) into the sheathing. For sheathing less than 1/2 inch (12.7 mm) in thickness, the fasteners shall extend through the sheathing. Each shake shall be attached with a minimum of two fasteners.
1507.9.8 Application.
Wood shakes shall be laid with a side lap not less than 1 1/2 inches (38.1 mm) between joints in adjacent courses. Spacing between shakes in the same course shall be 3/8 to 5/8 inches (9.5 to 15.9 mm) for shakes and taper sawn shakes of naturally durable wood and shall be 1/4 to 3/8 inch (6.4 to 9.5 mm) for preservative taper sawn shakes. Weather exposure for wood shakes shall not exceed those set in Table 1507.9.8.
Table 1507.9.8 Wood Shake Weather Exposure and Roof Slope
Roofing Material Length (inches) Grade Exposure (inches) 4:12 Pitch or Steeper Shakes of naturally durable wood 18 No. 1 7.5 24 No. 1 10 a Preservative-treated taper sawn shakes of Southern yellow pine 18 No. 1 7.5 24 No. 1 10 18 No. 2 5.5 24 No. 2 7.5 Taper sawn shakes of naturally durable wood 18 No. 1 7.5 24 No. 1 10 18 No. 2 5.5 24 No. 2 7.5
For SI: 1 inch = 25.4 mm.
a. For 24-inch by 0.375-inch handsplit shakes, the maximum exposure is 7.5 inches.
1507.9.9 Flashing.
At the juncture of the roof and vertical surfaces, flashing and counterflashing shall be provided in accordance with the manufacturer's instructions, and where of metal, shall be not less than 0.019-inch (0.48 mm) (No. 26 galvanized sheet gage) corrosion-resistant metal. The valley flashing shall extend at least 11 inches (279 mm) from the centerline each way and have a splash diverter rib not less than 1 inch (25.4 mm) high at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (101.6 mm). For roof slopes of three units vertical in 12 units horizontal (25-percent slope) and over, the valley flashing shall have a 36-inch (914.4 mm) wide underlayment of either one layer of Type I underlayment running the full length of the valley or a self-adhering polymer-modified bitumen sheet complying with ASTM D 1970, in addition to other required underlayment. For slopes under seven units vertical in 12 units horizontal (58-percent slope) the metal valley flashing underlayment shall be solidly cemented to the roofing underlayment or a self-adhering polymer-modified bitumen sheet shall be installed.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2014/051.
1507.10 Built-up roofs.
The installation of built-up roofs shall comply with the provisions of this section.
1507.10.1 Slope.
Built-up roofs shall have a slope designed and built to provide positive roof drainage.
1507.10.2 Material standards.
Built-up roof covering materials shall comply with UL 55A or the standards in Table 1507.10.2 of this code.
Table 1507.10.2 Built-Up Roofing Material Standards
Material Standard Standard Acrylic coating used in roofing ASTM D 6083 Aggregate surfacing ASTM D 1863 Asphalt adhesive used in roofing ASTM D 3747 Asphalt cements used in roofing ASTM D 3019; D 2822; D 4586 Asphalt-coated glass fiber base sheet ASTM D 4601 Asphalt coatings used in roofing ASTM D 1227; D 2823; D 2824; D 4479 Asphalt glass felt ASTM D 2178 Asphalt primer used in roofing ASTM D 41 Asphalt-saturated and asphalt-coated organic felt base sheet ASTM D 2626 Asphalt-saturated organic felt (perforated) ASTM D 226 Asphalt used in roofing ASTM D 312 Coal-tar cements used in roofing ASTM D 4022; D 5643 Coal-tar saturated organic felt ASTM D 227 Coal-tar pitch used in roofing ASTM D 450; Type I or II Coal-tar primer used in roofing, dampproofing and waterproofing ASTM D 43 Glass mat, coal tar ASTM D 4990 Glass mat, venting type ASTM D 4897 Mineral-surfaced inorganic cap sheet ASTM D 3909 Thermoplastic fabrics used in roofing ASTM D 5665, D 5726
1507.11 Modified bitumen roofing.
The installation of modified bitumen roofing shall comply with the provisions of this section.
1507.11.1 Slope.
Modified bitumen membrane roofs shall have a slope designed and built to provide positive roof drainage.
1507.11.2 Material standards.
Modified bitumen roof coverings shall comply with CGSB 37-GP-56M, ASTM D 6162, ASTM D 6163, ASTM D 6164, ASTM D 6222, ASTM D 6223, ASTM D 6298 or ASTM D 6509.
1507.12 Thermoset single-ply roofing.
The installation of thermoset single-ply roofing shall comply with the provisions of this section.
1507.12.1 Slope.
Thermoset single-ply membrane roofs shall have a slope designed and built to provide positive roof drainage.
1507.12.2 Material standards.
Thermoset single-ply roof coverings shall comply with ASTM D 4637, ASTM D 5019 or CGSB 37-GP-52M.
1507.12.3 Ballasted thermoset low-slope roofs.
Ballasted thermoset low-slope roofs (roof slope < 2:12) shall be installed in accordance with this section and Section 1504.4, and subject to the limitations of Section 1504.8.
1507.13 Thermoplastic single-ply roofing.
The installation of thermoplastic single-ply roofing shall comply with the provisions of this section.
1507.13.1 Slope.
Thermoplastic single-ply membrane roofs shall have a slope designed and built to provide positive roof drainage.
1507.13.2 Material standards.
Thermoplastic single-ply roof coverings shall comply with ASTM D 4434, ASTM D 6754, ASTM D 6878 or CAN/CGSB 37-54.
1507.13.3 Ballasted thermoplastic low-slope roofs.
Ballasted thermoplastic low-slope roofs (roof slope < 2:12) shall be installed in accordance with this section and Section 1504.4, and subject to the limitations of Section 1504.8.
1507.14 Sprayed polyurethane foam roofing.
The installation of sprayed polyurethane foam roofing shall comply with the provisions of this section.
1507.14.1 Slope.
Sprayed polyurethane foam roofs shall have a slope designed and built to provide positive roof drainage.
1507.14.2 Material standards.
Spray-applied polyurethane foam insulation shall comply with Type III or IV as defined in ASTM C 1029.
1507.14.3 Application.
Foamed-in-place roof insulation shall be installed in accordance with the manufacturer's instructions. A liquid-applied protective coating that complies with Table 1507.14.3 shall be applied no less than 2 hours nor more than 72 hours following the application of the foam.
Table 1507.14.3 Protective Coating Material Standards
Material Standard Standard Acrylic coating ASTM D 6083 Silicone coating ASTM D 6694 Moisture-cured polyurethane coating ASTM D 6947
1507.14.4 Foam plastics.
Foam plastic materials and installation shall comply with Chapter 26.
1507.15 Liquid-applied roofing.
The installation of liquid-applied roofing shall comply with the provisions of this section.
1507.15.1 Slope.
Liquid-applied roofing shall have a slope designed and built to provide positive roof drainage.
1507.15.2 Material standards.
Liquid-applied roofing shall comply with ASTM C 836, ASTM C 957, ASTM D 1227 or ASTM D 3468, ASTM D 6083, ASTM D 6694 or ASTM D 6947.
1507.16 Vegetative roofs, roof gardens and landscaped roofs.
Vegetative roofs, roof gardens and landscaped roofs shall comply with the provisions of this section and New York City Fire Code.
1507.16.1 Design standards.
Vegetative roofs, roof gardens and landscaped roofs shall comply with ANSI/SPRI RP-14 and ANSI/SPRI VF-1, or with FM DS 1-35.
Exceptions: The aggregate area of landscaping materials or growth media or both on any single roof level of a building or structure is 250 square feet (23.2 m 2 )or less.
1. The roof area is 22 feet (6705.6 mm) or less from grade.
2. The vegetative roof system is a container garden.
1507.16.2 Roof structure.
The roof structure shall comply with Chapter 16 for the design of the vegetative roofs, roof gardens and landscaped roofs.
1507.16.3 Roof covering.
Roof covering shall comply with Section 1507.10, 1507.11, 1507.12, 1507.13 or 1507.15.
1507.16.4 Slope.
The roofing membrane shall have a design slope in accordance with the roof covering utilized. Overburden shall be installed to prevent slippage.
1507.16.5 Structural fire resistance.
The structural frame and roof construction supporting the load imposed upon the roof by the vegetative roof, roof gardens or landscaped roofs shall comply with the requirements of Table 601.
1507.17 Photovoltaic shingles.
The installation of photovoltaic shingles shall comply with the provisions of this section.
1507.17.1 Deck requirements.
Photovoltaic shingles shall be applied to a solid or closely fitted deck, except where the shingles are specifically designed to be applied over spaced sheathing.
1507.17.2 Deck slope.
Photovoltaic shingles shall not be installed on roof slopes less than three units vertical in 12 units horizontal (25-percent slope).
1507.17.3 Underlayment.
Unless otherwise noted, required underlayment shall conform to ASTM D 226, ASTM D 4869 or ASTM D 6757.
1507.17.4 Underlayment application.
Underlayment shall be applied shingle fashion, parallel to and starting from the eave, lapped 2 inches (50.8 mm) and fastened sufficiently to hold in place.
1507.17.4.1 High wind attachment.
Underlayment applied in areas subject to high winds (V asd greater than 110 mph (49.1 m/s) as determined in accordance with Section 1609.3.1) shall be applied with corrosion-resistant fasteners in accordance with the manufacturer's instructions. Fasteners shall be applied along the overlap at not more than 36 inches (914.4 mm) on center. Underlayment installed where V asd is not less than 120 mph (53.6 m/s) shall comply with ASTM D 226, Type II, ASTM D 4869, Type IV or ASTM D 6757. The underlayment shall be attached in a grid pattern of 12 inches (304.8 mm) between side laps with a 6-inch (152.4 mm) spacing at the side laps. Underlayment shall be applied in accordance with Section 1507.2.8 except all laps shall be a minimum of 4 inches (101.6 mm). Underlayment shall be attached using metal or plastic cap nails with a head diameter of not less than 1 inch (25.4 mm) with a thickness of not less than 32-gage (0.0134 inch (0.34 mm)) sheet metal. The cap nail shank shall be a minimum of 12 gage (0.105 inch (2.67 mm)) with a length to penetrate through the roof sheathing or a minimum of 3/4 inch (19.1 mm) into the roof sheathing.
Exception: As an alternative, adhered underlayment complying with ASTM D 1970 shall be permitted.
1507.17.4.2 Ice barrier.
An ice barrier that consists of at least two layers of underlayment cemented together or of a self-adhering polymer modified bitumen sheet shall be used instead of normal underlayment and extend from the lowest edges of all roof surfaces to a point not less than 24 inches (609.6 mm) inside the exterior wall line of the building.
Exception: Detached accessory structures that contain no conditioned floor area.
1507.17.5 Fasteners.
Fasteners for photovoltaic shingles shall be galvanized, stainless steel, aluminum or copper roofing nails, minimum 12-gage (0.105 inch (2.67 mm)) shank with a minimum 3/8-inch (9.5 mm) diameter head, of a length to penetrate through the roofing materials and a minimum of 3/4 inch (19.1 mm) into the roof sheathing. Where the roof sheathing is less than 3/4 inch (19.1 mm) thick, the nails shall penetrate through the sheathing. Fasteners shall comply with ASTM F 1667.
1507.17.6 Material standards.
Photovoltaic shingles shall be listed and labeled in accordance with UL 1703.
1507.17.7 Attachment.
Photovoltaic shingles shall be attached in accordance with the manufacturer's instructions.
1507.17.8 Wind resistance.
Photovoltaic shingles shall be tested in accordance with procedures and acceptance criteria in ASTM D 3161. Photovoltaic shingles shall comply with the classification requirements of Table 1504.1.1 of this code for the appropriate maximum nominal design wind speed. Photovoltaic shingle packaging shall bear a label to indicate compliance with the procedures in ASTM D 3161 and the required classification from Table 1504.1.1 of this code.
Section BC 1508. Roof Insulation
1508.1 General.
The use of above-deck thermal insulation shall be permitted provided such insulation is covered with an approved roof covering and passes the tests of NFPA 276 or UL 1256 when tested as an assembly.
Exceptions:
1. Foam plastic roof insulation shall conform to the material and installation requirements of Chapter 26 of this code.
2. Where a concrete roof deck is used and the above-deck thermal insulation is covered with an approved roof covering.
1508.1.1 Cellulosic fiberboard.
Cellulosic fiberboard roof insulation shall conform to the material and installation requirements of Chapter 23.
1508.2 Material standards.
Above-deck thermal insulation board shall comply with the standards in Table 1508.2.
Table 1508.2 Material Standards for Roof Insulation
Material Standard Cellular glass board ASTM C 552 Composite boards ASTM C 1289, Type III, IV, V or VI Expanded polystyrene ASTM C 578 Extruded polystyrene ASTM C 578 Fiber-reinforced gypsum board ASTM C 1278 Glass-faced gypsum board ASTM C 1177 Mineral fiber insulation board ASTM C 726 Perlite board ASTM C 728 Polyisocyanurate board ASTM C 1289, Type I or II Wood fiberboard ASTM C 208
Section BC 1509. Radiant Barriers Installed above Deck
1509.1 General.
A radiant barrier installed above a deck shall comply with Sections 1509.2 through 1509.4.
1509.2 Fire testing.
Radiant barriers shall be permitted for use above decks where the radiant barrier is covered with an approved roof covering and the system consisting of the radiant barrier and the roof covering complies with the requirements of either FM 4550 or UL 1256.
1509.3 Installation.
The low emittance surface of the radiant barrier shall face the continuous airspace between the radiant barrier and the roof covering.
1509.4 Material standards.
A radiant barrier installed above a deck shall comply with ASTM C 1313/1313M.