NYC Administrative Code Title 28, Chapter 7 New York City Building Code, part 32 of 33

Chapter K2 to Section BC Q104: 13 sections.

Chapter K2. Modifications to ASME B20.1/2015, Safety Standard for Conveyors and Related Equipment

Open this section

K201.1 General.

As referenced in Section 3001.2 of this code, the provisions of ASME B20.1-2015 shall be modified in accordance with this appendix. The section numbers correlate to those in the referenced ASME standard. Refer to the rules of the department for any subsequent additions, modifications or deletions that may have been made to this standard in accordance with Section 28-103.19 of the Administrative Code.

4 DEFINITIONS

Delete and revise the definition "Conveyor, vertical reciprocating" in Section 4 to read as follows:

CONVEYOR, VERTICAL RECIPROCATING. A permanent reciprocating power or gravity-actuated unit (not designed to carry passengers or an operator) that receives objects on a carrier and transmits these objects vertically between two or more levels.

6 SPECIFIC SAFETY STANDARDS SECTION 6.1

BELT CONVEYORS: FIXED IN PLACE

Delete Section 6.1 in its entirety.

SECTION 6.2 GUARDING OF BUCKET CONVEYORS

Delete Section 6.2 in its entirety.

SECTION 6.3 SAFETY CONSIDERATIONS FOR CHAIN CONVEYORS

Delete Section 6.3 in its entirety.

SECTION 6.4 EN MASSE CONVEYORS

Delete Section 6.4 in its entirety.

SECTION 6.5 FLIGHT AND APRON CONVEYORS: BULK MATERIAL

Delete Section 6.5 in its entirety.

SECTION 6.6 INCLINED RECIPROCATING CONVEYORS

Delete Section 6.6 in its entirety.

SECTION 6.7 LIVE ROLLER CONVEYORS: BELT OR CHAIN DRIVEN

Delete Section 6.7 in its entirety.

SECTION 6.8 MOBILE CONVEYORS

Delete Section 6.8 in its entirety.

SECTION 6.9 SAFETY CONSIDERATIONS FOR PORTABLE CONVEYORS, EXTENDABLE BELT CONVEYORS, AND CAR UNLOADERS

Delete Section 6.9 in its entirety.

SECTION 6.10 SAFETY CONSIDERATIONS FOR PUSHER BAR CONVEYORS

Delete Section 6.10 in its entirety.

SECTION 6.11 ROLLER AND WHEEL CONVEYORS

Delete Section 6.11 in its entirety.

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

SECTION 6.12 SAFETY CONSIDERATIONS FOR SCREW CONVEYORS

Delete Section 6.12 in its entirety.

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

SECTION 6.13 SAFETY CONSIDERATIONS FOR SHUTTLE CONVEYERS, BELT TRIPPERS, AND TRANSFER CARS

Delete Section 6.13 in its entirety.

SECTION 6.14 SKIP HOISTS: BULK MATERIAL

Delete Section 6.14 in its entirety.

SECTION 6.15 SLAT CONVEYORS AND ROLLER SLAT CONVEYORS

Delete Section 6.15 in its entirety.

SECTION 6.16 SUSPENDED VERTICAL TRAY CONVEYORS

Delete Section 6.16 in its entirety.

SECTION 6.17 TOW CONVEYORS

Delete and revise the title of Section 6.17 to read as follows:

SECTION 6.17 TOW CONVEYORS (SHOPPING CAR CONVEYORS)

6.17.2 Tow Conveyors: Public use intended.

Delete and revise Section 6.17.2.2 and add new Section 6.17.2.3 to Section 6.17.2 read as follows:

6.17.2.2 Guarding. Where a parted chain, cable, belt, tow pin, or other linkage would permit a runaway condition on an incline or decline, anti-runway/backstop devices shall be provided.

6.17.2.3 Periodic inspections and tests. Tow conveyors shall be subject to periodic inspections and tests including acceptance, category 1 and category 5.

SECTION 6.18 TROLLEY CONVEYORS AND POWER AND FREE CONVEYORS

Delete Section 6.18 in its entirety.

SECTION 6.19 VERTICAL ARTICULATED CONVEYORS

Delete Section 6.19 in its entirety.

SECTION 6.20 VERTICAL CHAIN-OPPOSED SHELF TYPE CONVEYORS

Delete Section 6.20 in its entirety.

SECTION 6.21 VERTICAL RECIPROCATING CONVEYORS

6.21.1 Safety considerations.

Add new Subsections (d), (e), (f), (g), (h), (i), (j) and (k) to Section 6.21.1 to read as follows:

(d) Travel distance shall be limited to less than 22 860 mm (75 ft) with a maximum of four landings served.

(e) Where fire-resistant construction is required by the Building Code, conveyor(s) shall be enclosed in a fire-rated hoistway.

(f) Access at landings shall be a restricted area for authorized personnel with no public access.

(g) Where there is accessible space under the hoistway, the conveyor and counterweight shall be equipped with a safety device designed to stop and hold the conveyor and counterweight independent of the hoisting or driving mechanism and shall comply with A17.1 rules 2.6 and 2.1.2.3.

(h) The operating device shall not be located inside the conveyor enclosure and must be external to the hoistway at each landing served.

(i) The system shall incorporate a position indicator at each floor landing to register the location of the conveyor.

(j) The rated-load capacity shall not be less than 239 kg/m 2 (49 lbs. per sq ft).

(k) The rated speed shall not exceed 406 mm/sec (80 FPM).

6.21.2 Guarding.

6.21.2 Delete and revise Subsections (b), (c) and (d) of Section 6.21.2 to read as follows:

(b) The conveyor housing shall be equipped with doors or an equivalent means at each manual landing and unloading station, arranged so that they can be opened only when the carrier is present and stopped at that level and such that the carrier cannot be actuated until they are closed. This requirement is typically satisfied by use of a mechanical locking device, which is actuated by the motion of the carrier, and an electrical switch indicating that the door is closed and locked.

(1) The unlocking mechanism must be mounted on the carrier.

(2) This requirement shall be satisfied by the use of an interlock as required by ASME A17.1, Section 2.12.2.

(c) Vertical reciprocating conveyors designed to automatically receive and discharge material shall have interlocked doors as in (b) or, as an alternative, be guarded by a suitable enclosure extending from the path of the moving carrier.

(d) Where the application requires that personnel walk onto the carrier to load or unload material, the carriers shall be provided with a conveyor enclosure securely fastened to the conveyor platform. The enclosure walls shall be of solid, grille or perforated construction; and shall be of such strength and support that when subjected to a leaning or falling rated load on the conveyor, the enclosure walls will not deflect or deform in a way that reduces running clearances to less than 13 mm (0.5 in.). Enclosure entrance(s) shall be provided with solid doors or gates; and shall guard the full width opening with a minimum height of 2030 mm (80 in.). Grille or perforated portions of conveyor enclosures and entrance gates shall reject a ball 38 mm (1.5 in.) in diameter.

Add new Section 6.21.3 to read as follows:

6.21.3 Periodic testing.

(a) All conveyors shall be inspected and tested as per Table N1 of ASME A17.1 as modified by Chapter K1 of this appendix.

(b) All safety devices shall be tested on all tests. A static full load shall be performed every five years to ensure that the conveyor holds the load.

SECTION 6.22 MATERIAL ENCAPSULATING CONVEYORS

Delete Section 6.22 in its entirety.

Delete and revise the title of "Mandatory Appendix I" to read as follows:

NON-MANDATORY APPENDIX I SPECIFICATIONS FOR DESIGN, INSTALLATION COMMISSIONING, AND PERIODIC INSPECTION OF VERTICAL RECIPROCATING CONVEYORS

Chapter K3. Modifications to ASME A17.3-2015, Safety Code for Existing Elevators and Escalators

Open this section

K301.1 Retroactive requirements for existing elevators and escalators.

As referenced in Section 3001.2 of this code, the provisions of ASME A17.3-2015 shall be modified in accordance with this appendix and are applicable to all existing elevators and escalators. The section numbers correlate to those in the referenced ASME standard. Refer to the rules of the department for any subsequent additions, modifications or deletions that may have been made to this standard in accordance with Section 28-103.19 of the Administrative Code.

PART I INTRODUCTION

SECTION 1.1 SCOPE

1.1.2 Equipment not covered by this code.

Delete and revise subsection (ee) to read as follows:

Equipment not covered by this code. Equipment not covered by this code includes, but is not limited to, the following:

(ee) limited-use/limited-application elevators within the scope of ASME A17.1, except for section 3.10.12 of this code, where such limited-use/limited-application elevators shall achieve compliance by January 1, 2027

SECTION 1.5 ALTERATIONS, MAINTENANCE, AND INSPECTIONS AND TESTS

1.5 Delete and revise Section 1.5 to read as follows:

Existing installations shall conform to the following requirements of ASME A17.1–2013:

(a) Requirements 8.10, Acceptance Inspections and Tests; and 8.11, Periodic Inspections and Tests

(b) Requirements 8.6, Maintenance, Repair, and Replacement; and 8.7, Alterations

In addition, existing installations shall conform to Sections 1007.4, 1607.8.1, 3001.2, 3001.4, 3002.5, and 3003.2 of the New York City Building Code.

PART II HOISTWAYS AND RELATED CONSTRUCTION FOR ELECTRIC ELEVATORS

SECTION 2.1 HOISTWAYS

2.1.1 Hoistway construction.

Delete Section 2.1.1 in its entirety.

2.1.2 Windows in hoistway enclosures.

Delete and revise Section 2.1.2 to read as follows:

2.1.2 Windows in hoistway enclosures. Every hoistway-window opening ten (10) stories or fewer above a thoroughfare, and every such window opening three (3) stories or fewer above the roof of an adjacent building, shall be guarded by one of the following:

(a) Vertical bars at least 5/8 inch (16 mm) in diameter or equivalent, spaced not more than 10 inches (254 mm) apart, permanently and securely fastened in place; or

(b) Metal-sash windows having solid-section steel muntins of not less than 1/8 inch (3.2 mm) thickness, spaced not more than 8 inch (203 mm) apart.

Exterior hoistway-windows shall be marked with the word "SHAFTWAY" in red letters at least 6 inches (152 mm) high on a white background.

2.1.4 Pipes, air ducts, and wiring.

Delete Section 2.1.4 in its entirety.

2.1.5 Counterweight guards.

Delete Section 2.1.5 in its entirety.

SECTION 2.2 MACHINE ROOMS AND MACHINERY SPACES

2.2.5 Pipes, air ducts, and wiring.

Delete Section 2.2.5 in its entirety.

SECTION 2.4 CLEARANCES AND RUNBYS

Delete Section 2.4 in its entirety.

SECTION 2.5 PROTECTION OF SPACES BELOW HOISTWAYS

Delete and revise Section 2.5 to read as follows:

Where the space below the hoistway is not permanently secured against access, the following requirements shall be conformed to:

(a) The cars and counterweights shall be provided with spring or oil buffers.

(b) Car and counterweight buffer supports shall be of sufficient strength to withstand without permanent deformation the impact resulting from buffer engagement of the car plus the rated load or the counterweight with an empty car at the following speeds:

(1) Governor tripping speed where the safety is governor operated;

(2) One hundred and twenty-five (125) percent of the rated speed where the safety is not governor operated.

SECTION 2.6 HOISTWAY ENTRANCES

2.6.3 Hoistway-door vision panels.

Delete and revise Section 2.6.3 to read as follows:

2.6.3 Hoistway-door vision panels. Hoistway-door vision panels must be protected by protective grills made of number sixteen (16) gage stainless or galvanized steel in accordance with the following specifications:

(a) Grills shall be sized to fit within or over the vision panel frame and completely cover the vision panel opening in the elevator, car doors and hoistway doors.

(b) Grills and vision panel frames shall be secured by means of non-reversible screws or other tamper proof fasteners.

(c) Grills shall contain openings that shall reject a ball 0.75 inch (19 mm) in diameter.

(d) All cut edges shall be deburred.

(e) The provisions of this section shall apply to both new and existing passenger cars. Requirements for such grills may be waived if certification is submitted that such elevator is operated manually or twenty-four (24) hour doorman service is provided. A security guard shall not be considered doorman service.

(f) For the purpose of this subparagraph, a vandal resistant 0.25 inch (6 mm) polycarbonate sheet, such as Lexan, in two (2) layers, one (1) on each side of the required wire glass, may be used in lieu of the metal protective.

2.6.4 Door hangers.

Delete Section 2.6.4 in its entirety.

2.6.7 Bottom guides.

Delete and revise Section 2.6.7 to read as follows:

2.6.7 Bottom guides. Existing elevators in occupancy groups R-1, R-2 and E shall comply with the following requirements:

(a) The bottom of each horizontally sliding hoistway elevator door panel shall be equipped with bottom guiding members and bottom safety retainers.

(1) The bottom of each horizontally sliding hoistway door panel shall be guided by two or more members as described in ASME A17.1 Section 2.11.11.6.

(2) Safety Retainers - The bottom of each horizontally sliding hoistway elevator door panel shall be provided with a means of retaining the door panel in position if the primary guiding means fail, and preventing displacement of the bottom of the door panel by not more than 0.75 inch (19 mm) into the hoistway. Such retainers shall be installed on the bottom, shaft-side of each door panel, shall be fabricated of at least twelve (12) gage stainless or galvanized steel, and shall engage the corresponding sill member by not less than 0.375 inch (9.5 mm).

Exception: New elevator doors installed under the 1996/1997 or later editions of ASME A17.1 as modified by Chapter K1 of this Appendix.

(b) The door panels shall be structurally sound and in such condition that the guide(s) and retainer(s) may be securely attached.

(1) At least one (1) bottom guide shall be installed near each end of every door panel.

(2) A safety retainer(s) totaling at least 8 inches (203 mm) in length shall be installed between the two (2) outermost guides.

(3) On smaller sized door panels, where due to the width of the door panel, the space between the two (2) outermost bottom guides would be less than 8 inches (203 mm), then either:

(i) The length of the retainer may be reduced to a minimum of 4 inches (102 mm); or

(ii) When only one (1) bottom guide is provided near the center of the door, a 4 inches (102 mm) retainer shall be installed on each side of the bottom guide. If the space between the bottom guide and the edge of the door is less than four inches, the length of the retainer may be reduced to the amount of the space between the bottom guide and the edge of the door.

Exception: New elevator entrance frames and doors installed under the 1996/1997 or later editions of ASME A17.1 as modified by Chapter K1 of this appendix.

SECTION 2.7 HOISTWAY-DOOR LOCKING DEVICES, PARKING DEVICES, AND ACCESS

2.7.4 Access to hoistway.

Delete Section 2.7.4 in its entirety.

2.7.5 Restricted opening of hoistway doors and/or car doors on passenger elevators.

Delete and revise the title of Section 2.7.5 to read as follows:

2.7.5 Restricted opening of hoistway doors and/or car doors on automatic passenger elevators. Automatic passenger elevators shall comply by January 1, 2027.

Add new Section 2.7.7 to read as follows:

2.7.7 Locks on elevators and elevator hoistway doors. All elevators shall comply by January 1, 2027.

In all buildings, no switch, lock or device of any kind shall be installed on any floor on or above the street floor on any passenger elevator car or hoistway sliding door. Freight elevators, and passenger elevators with swing-type hoistway doors, are permitted to have locks provided that they are openable by the city-wide standard key 2642 and the New York City Fire Department Standard 1620 key.

SECTION 2.8 POWER OPERATION OF DOORS AND GATES

2.8.1 Kinetic energy and force limitations for power-operated horizontally sliding doors.

Add new Subsection (3) to Section 2.8.1(a):

(3) See Nonmandatory Appendix G of A17.2-204 for door closing time guidelines.

PART III MACHINERY AND EQUIPMENT FOR ELECTRIC ELEVATORS

SECTION 3.3 CAR FRAMES AND PLATFORMS

3.3.1 Car platforms.

Delete Section 3.3.1 in its entirety.

SECTION 3.4 CAR ENCLOSURES

3.4.1 Car enclosures.

Delete Section 3.4.1 in its entirety.

3.4.2 Car doors and gates.

Delete and revise Section 3.4.2 to read as follows:

3.4.2 Car doors and gates. Passenger and loft elevators shall comply with subsections (a) and (b) of this section.

(a) Doors, gates, and electric contacts. Cars shall have a car door or gate provided at each entrance equipped with a car door or gate electric contact. Car doors and/or gates shall conform to the following requirements:

(1) Be positively opened by a lever or other device attached to and operated by the door or gate.

(2) Be maintained in the open position by the action of gravity or by a restrained compression spring, or both, or by positive mechanical means.

(3) Not be readily accessible.

(b) Car-door interlock. A car-door interlock shall be required for

(1) Car doors of elevators where the clearance between the loading side of the car platform and hoistway enclosure exceeds the maximum specified in 2.4.1.

(2) Car doors of elevators that face an unenclosed portion of the hoistway during the travel of the car.

(c) Closed position of car doors or gates. Car doors or gates shall be considered to be in the closed position under the following conditions:

(1) For horizontally sliding doors or gates, when the clear open space between the leading edge of the door or gate and the nearest face of the jamb does not exceed 2 in. (51 mm) except where car doors are provided with a car-door interlock(s), 0.375 in. (10 mm)

(2) For vertically sliding counterweighted doors or gates, when the clear open space between the leading edge of the door or gate and the car platform sill does not exceed 2 in. (51 mm)

(3) For horizontally sliding center-opening doors, or vertically sliding biparting counterbalanced doors, when the door panels are within 2 in. (51 mm) of contact with each other, except where horizontally sliding center-opening car doors are provided with a car-door interlock(s), 0.375 in. (10 mm)

(d) Collapsible gates. Collapsible car gates shall conform to the following requirements:

(1) Collapsible car gates shall not be power opened to a distance exceeding one-third (1/3) of the clear gate opening, and in no case more than 10 inches (254 mm).

(2) When fully closed (extended position), gates shall reject a ball 3 inches (76 mm) in diameter for passenger elevators and 4.5 inches (114 mm) for freight elevators.

(3) Gates shall have at least every fourth vertical member guided at the top and every second vertical member guided at the bottom.

(4) Handles of manually operated collapsible gates nearest the car operating device on elevators operated from the car only shall be so located that the nearest handle is not more than 48 inches (1.22 m) from the car operating device when the gate is closed (extended position), and not more than 48 inches (1.22 m) above the car floor. Gate handles shall be provided with finger guards.

3.4.4 Emergency exits.

Delete Section 3.4.4 in its entirety.

3.4.5 Car illumination.

Delete and revise Section 3.4.5 to read as follows:

3.4.5 Car illumination.

(a) Interiors of cars shall be provided with an electric light or lights. Not less than two (2) lamps shall be provided.

(b) The minimum illumination at the car threshold, with the door closed, shall not be less than:

(1) For passenger elevators: 5 fc (54 lux).

(2) For freight elevators: 2 1/2 fc (27 lux).

(c) Light control switches are not required, but if provided they shall be located in or adjacent to the operating device in the car. In elevators having automatic operation, they shall be of the key-operated type or located in a fixture with a locked cover.

(d) Top of car light fixtures shall be provided with a non-key-operated switch in or adjacent to the fixture.

SECTION 3.5 SAFETIES

3.5.1 Car safeties.

Delete Section 3.5.1 in its entirety.

3.5.2 Counterweight safeties.

Delete Section 3.5.2 in its entirety.

3.5.3 Safeties to stop ascending cars or counterweights prohibited.

Delete Section 3.5.3 in its entirety.

3.5.4 Application and release of safeties.

Delete Section 3.5.4 in its entirety.

3.5.5 Maximum permissible movement of governor rope to operate the safety mechanism.

Delete Section 3.5.5 in its entirety.

3.5.6 Rail lubricants and lubrication plate.

Delete and revise Section 3.5.6 to read as follows:

3.5.6 Rail lubricants. Rail lubricants or coatings that will reduce the holding power of the safety or prevent its functioning as required shall not be used.

SECTION 3.6 SPEED GOVERNORS

Delete Section 3.6 in its entirety.

SECTION 3.8 DRIVING MACHINES AND SHEAVES

3.8.1 General requirement.

Delete Section 3.8.1 in its entirety.

3.8.2 Winding drum machines.

Delete and revise Subsection (b) of Section 3.8.2 to read as follows:

(b) Final terminal stopping devices for winding drum machines shall consist of a stopping switch located on the driving machine (machine final) and a stopping switch located in the hoistway and operated by cams attached to the car.

(1) Stopping switches, located on and operated by the driving machine, shall not be driven by chains, ropes, or belts. The opening of these contacts shall occur before or concurrent with the opening of the final terminal stopping switch.

(2) Driving machines equipped with an alternating current motor and alternating current brake or a direct current motor and direct-current brake shall have the final terminal stopping and machine stop device contacts installed in the operating circuits. The occurrence of a single ground or the failure of any single magnetically operated switch, contactor, or relay shall not render any final terminal stopping device ineffective.

Add new Subsection 3.8.4.1 to read as follows:

3.8.4.1 Single plunger brakes.

(a) All existing traction elevators with single plunger brakes must comply with either of the following by January 1, 2027:

(1) Alteration of single plunger assemblies to dual-plunger type, or

(2) Compliance with Unintended Car Movement Protection as specified by Section 2.19.2 of ASME A17.1.

(b) Notwithstanding any inconsistent provision of chapter 1 of title 28 of the Administrative Code, the work required to comply with this section may not be performed without a permit from the department.

SECTION 3.9 TERMINAL STOPPING DEVICES

3.9.1 Normal terminal stopping devices.

Delete Section 3.9.1 in its entirety.

3.9.2 Final terminal stopping devices.

Delete and revise Section 3.9.2 to read as follows:

3.9.2 Final terminal stopping devices. Upper and lower final terminal electro-mechanical stopping devices shall be provided and arranged to prevent movement of the car by the normal operating devices in either direction of travel after the car has passed a terminal landing. Final terminal stopping devices shall be located as follows:

(a) Winding drum driving machines. Elevators having winding drum machines shall have stopping switches on the machines and also installed in the hoistway and operated by cams attached to the car. Final limit switches and brackets shall be permanently secured and pinned.

(b) Traction driving machines. Elevators having traction driving machines shall have stopping switches installed in the hoistway and operated by cams attached to the car. Final limit switches and brackets shall be permanently secured and pinned.

SECTION 3.10 OPERATING DEVICES AND CONTROL EQUIPMENT

3.10.1 Types of operating devices.

Delete Section 3.10.1 in its entirety.

3.10.3 Top-of-car operating devices.

Delete Section 3.10.3 in its entirety.

3.10.4 Electrical protective devices.

Delete and revise Section 3.10.4 to read as follows:

3.10.4 Electrical protective devices.

Electrical protective devices shall be provided in accordance with the following:

(a) Slack-rope switch. Winding drum machines shall be provided with a slack-rope device equipped with a slack-rope switch of the enclosed manually reset type that shall cause the electric power to be removed from the elevator driving machine motor and brake if the suspension ropes become slack.

(b) Compensating rope sheave switch. Compensating rope sheaves shall be provided with a compensating rope sheave switch or switches mechanically opened by the compensating rope sheave before the sheave reaches its upper or lower limit of travel to cause the electric power to be removed from the elevator driving machine motor and brake.

(c) Broken rope, tape, or chain switches used in connection with machine room normal terminal stopping switches. Broken rope, tape, or chain switches conforming to the requirements of Section 3.6.1 shall be provided in connection with normal terminal stopping devices located in machine rooms of traction elevators. Such switches shall be opened by a failure of the rope, tape or chain.

(d) Car-safety mechanism switch. A switch shall be required where a car safety is provided.

(e) Final terminal stopping devices. Final terminal stopping devices shall be provided for every elevator.

(f) Emergency terminal speed limiting device. Where reduced stroke oil buffers are provided, emergency terminal speed limiting devices are required.

(g) Motor generator overspeed protection. Means shall be provided to cause the electric power to be removed automatically from the elevator driving machine motor and brake should a motor generator set, driven by a direct current motor, overspeed excessively.

(h) Motor field sensing means. Where direct current is supplied to an armature and shunt field of an elevator driving machine motor, a motor field current sensing means shall be provided, which shall cause the electric power to be removed from the motor armature and brake unless current is flowing in the shunt field of the motor.

A motor field current sensing means is not required for static control elevators provided with a device to detect an overspeed condition prior to, and independent of, the operation of the governor overspeed switch. This device shall cause power to be removed from the elevator driving machine motor armature and machine brake.

(i) Buffer switches for oil buffers used with type C car safeties. Oil level and compression switches shall be provided for all oil buffers used with Type C safeties.

(j) Hoistway door interlocks or hoistway door electric contacts. Hoistway door interlocks or hoistway door electric contacts shall be provided for all elevators.

(k) Car door or gate electric contacts. Car door or gate electric contacts shall be provided for all elevators with car doors or gates.

(l) Normal terminal stopping devices. Normal terminal stopping devices shall be provided for every elevator.

(m) Car side emergency exit electric contact. An electric contact shall be provided on every car side emergency exit door.

(n) Electric contacts for hinged car platform sills. Hinged car platform sills, where provided, shall be equipped with electric contacts.

(o) Emergency stop switch. On all elevators, an emergency stop switch shall be provided in the car, and located in or adjacent to each car operating panel. When open (i.e. the "stop position"), this switch shall cause the electric power to be removed from the elevator driving-machine motor and brake. Emergency stop switches shall:

(1) Be of the manual open and close type;

(2) Have a red operating handle or buttons;

(3) Be conspicuously and permanently marked "STOP" and indicate the "STOP" and "RUN" positions; and

(4) When open, cause an audible signaling device to sound.

(p) Stop switch in pit. A stop switch, conforming to the following requirements shall be provided in the pit of every elevator. The switch shall be located adjacent to the normal pit access. The switch shall cause the electric power to be removed from the elevator driving machine motor and brake and shall:

(1) Be of the manual open and close type;

(2) Have a red operating handle or buttons;

(3) Be conspicuously and permanently marked "STOP" and indicate the "STOP" and "RUN" positions; and

(4) Be positively opened mechanically and its opening shall not be solely dependent on a spring.

(q) Buffer switches for gas spring return oil buffers. A buffer switch shall be provided for gas spring return oil buffers that will cause electric power to be removed from the elevator driving machine motor and brake if the plunger is not within 0.5 inch (13 mm) of the fully extended position.

3.10.5 Power supply line disconnecting means.

Delete Section 3.10.5 in its entirety.

3.10.11 Reserved for Future Use.

Delete and revise Section 3.10.11 to read as follows:

3.10.11 Signal system on car switch elevators.

Elevators with car switch operations shall be provided with a signal system by means of which signals can be given from any landing whenever the elevator is desired at the landing.

3.10.12 System to Monitor and Prevent Automatic Operation of the Elevator With Faulty Door Contact Circuits.

Delete and revise Section 3.10.12 to read as follows:

3.10.12 System to monitor and prevent automatic operation of passenger and freight elevators with faulty door contact circuits.

All automatic passenger and freight elevators shall comply with this section by January 1, 2020. Means shall be provided to monitor the position of power-operated car doors that are mechanically coupled with the landing doors or power-operated car doors with manually operated swing-type hall doors, while the car is in the landing zone, in order

(a) to prevent the operation of the car if the car door is not closed (see Section 3.4.2(c) of ASME A17.3), regardless whether the portion of the circuits incorporating the car-door contact or the interlock contact of the landing door coupled with car door, or both, are closed or open, except as permitted under any of the following conditions:

(1) by a car-leveling or truck-leveling device;

(2) when a hoistway access switch is operated;

(3) when the top-of-car inspection operation utilizing a car door by-pass or hoistway-door bypass switch is activated;

(4) when on any mode of inspection operation; and

(b) to prevent, except as permitted by inspection operation, the power closing of the doors if the car door is fully open and any of the following conditions exist:

(1) the car-door contact is closed or the portion of the circuit, incorporating this contact is bypassed;

(2) the interlock contact of the landing door that is coupled to the opened car door is closed or the portion of the circuit, incorporating this contact is bypassed, except when operating during Firefighters' Service Phase II;

Exception: For swing-type door operation, the locking (secondary) contacts shall be monitored.

(3) the car-door contact and the interlock contact of the door that is coupled to the opened car door are closed, or the portions of the circuits incorporating these contacts are bypassed.

SECTION 3.11 EMERGENCY OPERATION AND SIGNALING DEVICES

3.11.1 Car emergency signaling devices.

Delete and revise Section 3.11.1 to read as follows:

3.11.1 Car emergency signaling devices. In all buildings, the elevator(s) shall be provided with the following:

(a) If installed, altered, or both under ASME A17.1–2003 or earlier edition, as modified by Chapter K, Appendix K1

(1) An audible signaling device, operable from the emergency stop switch, when provided, and from a switch marked "ALARM" that is located in or adjacent to each car operating panel. The signaling device shall be located inside the building and audible inside the car and outside the hoistway. One signaling device shall be permitted to be used for a group of elevators.

(2) If the audible signaling device, or the means of two-way communication, or both, are normally connected to the building power supply, they shall automatically transfer to a source of emergency power within 10 seconds after the normal power supply fails. The power source shall be capable of providing for the operation of the audible signaling device for at least 1 hour, and the means of two-way communication for at least 4 hours.

(3) In buildings in which a building attendant (building employee, watchman, etc.) is not continuously available to take action when the required emergency signal is operated, the elevators shall be provided with a means within the car for communicating with or signaling to a service that is capable of taking appropriate action when a building attendant is not available.

(4) An emergency power system shall be provided conforming to the requirements of (a)(3) of this section.

(b) If installed, altered, or both under ASME A17.1–2013 or later editions as modified by Chapter K, Appendix K1, the emergency communications system shall comply with Section 2.27 of the ASME A17.1 Code under which it was installed or altered.

3.11.3 Firefighters' service.

Delete and revise Section 3.11.3 to read as follows:

3.11.3 Firefighters' service operation in existing elevators. Firefighters' service operation shall be installed in accordance with the New York City Building Code in all existing elevators serving any of the following:

(a) High rise buildings or buildings classified in Occupancy Group M except existing R-2.

(b) All buildings or buildings classified in Occupancy Group A, B, E, I, or R-1 (except for "residential hotels," as such term is defined by the commissioner pursuant to rules and regulations).

SECTION 3.12 SUSPENSION MEANS AND THEIR CONNECTIONS

3.12.1 Suspension means.

Delete Section 3.12.1 in its entirety.

PART IV HYDRAULIC ELEVATORS

SECTION 4.2 MECHANICAL EQUIPMENT

Delete Section 4.2 in its entirety.

SECTION 4.3 DRIVING MACHINES

4.3.2 Plunger stops.

Delete and revise Section 4.3.2 to read as follows:

4.3.2 Plunger stops. Plungers shall be provided with solid metal stops and/or other means to prevent the plunger from traveling beyond the limits of the cylinder. Stops shall be so designed and constructed as to stop the plunger from maximum speed in the up direction under full pressure without damage to the connection to the driving machine, plunger, plunger connection, couplings, plunger joints, cylinder, cylinder connecting couplings or any other parts of the hydraulic system.

4.3.3 Hydraulic elevators.

Delete and revise Section 4.3.3 to read as follows:

4.3.3 Hydraulic elevators. Hydraulic elevators that have any portion of the cylinder buried in the ground and that do not have a double cylinder or a cylinder with a safety bulkhead shall:

(a) Have the cylinder replaced with a double cylinder or a cylinder with a safety bulkhead protected from corrosion by one or more of the following methods:

(1) Monitored cathodic protection;

(2) A coating to protect the cylinder from corrosion that will withstand the installation process;

(3) By a protective plastic casing immune to galvanic or electrolytic action, salt water, and other known underground conditions; or

(b) Be provided with a device meeting the requirements of Section 3.5 or a device arranged to operate in the down direction at an overspeed not exceeding one hundred twenty-five (125) percent of rated speed. The device shall mechanically act to limit the maximum car speed to the buffer striking speed, or stop the elevator car with rated load with a deceleration not to exceed 32.2 ft/s 2 (9.8 m/s 2 ), and shall not automatically reset. Actuation of the device shall cause power to be removed from the pump motor and control valves until manually reset; or

(c) Have other means acceptable to the department to protect against unintended movement of the car as a result of uncontrolled fluid loss.

SECTION 4.5 TANKS

4.5.2 Pressure tanks.

Delete Section 4.5.2 in its entirety.

SECTION 4.7 OPERATING DEVICES AND CONTROL EQUIPMENT

4.7.2 Top-of-car operating devices.

Delete Section 4.7.2 in its entirety.

4.7.3 Anticreep leveling devices.

Delete Section 4.7.3 in its entirety.

4.7.4 Electrical protective devices.

Delete and revise Section 4.7.4 to read as follows:

4.7.4 Electrical protective devices. Electrical protective devices conforming to the requirements of Section 3.10.4, where they apply to hydraulic elevators, shall be provided and operate as follows:

(a) The following devices shall prevent operation of the elevator by the normal operating device and also the movement of the car in response to the anticreep leveling device:

(1) stop switches in the pit

(2) stop switches on top of the car

(3) car side emergency exit door electric contacts, where such doors are provided

(b) The following devices shall prevent the operation of the elevator by the normal operating device, but the anticreep leveling device where provided, shall remain operative:

(1) emergency stop switches in the car

(2) broken rope, tape, or chain switches on normal terminal stopping devices when such devices are located in the machine room or overhead space

(3) hoistway-door interlocks or hoistway-door electric contacts

(4) car door or gate electric contacts

(5) hinged car platform sill electric contacts

(6) in-car stop switch, where permitted by subsection 3.10.4(t)

4.7.5 Power supply line disconnecting means.

Delete Section 4.7.5 in its entirety.

4.7.7 Control and operating circuit requirements.

Delete and revise Section 4.7.7 to read as follows:

4.7.7 Control and operating circuit requirements. Control and operating circuits shall conform to the requirements of Sections 3.10.9 and 3.10.12.

SECTION 4.8 ADDITIONAL REQUIREMENTS FOR COUNTERWEIGHTED HYDRAULIC ELEVATORS

Delete Section 4.8 in its entirety.

SECTION 4.9 ADDITIONAL REQUIREMENTS FOR ROPED HYDRAULIC ELEVATORS

Delete Section 4.9 in its entirety.

PART V ESCALATORS

SECTION 5.1 CONSTRUCTION

5.1.4 Antislide device.

Delete and revise Section 5.1.4 to read as follows:

5.1.4 Antislide device.

On high deck balustrades, antislide devices shall be provided on decks or combination of decks when the outer edge of the deck is greater than 12 inches (305 mm) from the centerline of the handrail or on adjacent escalators when the distance between centerline of the handrails is greater than 16 inches (406 mm).

These devices shall consist of raised objects fastened to the decks, not closer than 4 inches (102 mm) to the handrail and spaced not greater than 78 inches (2000 mm) apart. The height shall be not less than 0.75 inches (19 mm). There shall be no sharp corners or edges.

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

5.1.7 Step risers.

Delete Section 5.1.7 in its entirety.

5.1.8 Slotting of step treads.

Delete Section 5.1.8 in its entirety.

5.1.11 Step/skirt performance index.

Delete Section 5.1.11 in its entirety.

SECTION 5.3 OPERATING AND SAFETY DEVICES

5.3.1 Starting switches.

Delete and revise Section 5.3.1 to read as follows:

5.3.1 Starting devices. In every new and existing escalator, starting devices shall be provided with the combination of a starting switch and a starting button. The escalator shall be started only after the activation of both the switch and the button.

(a) Starting switch. Starting switches shall be of continuous pressure spring return type and shall be operated by a cylinder-type lock having five-pin, five-disc or five-tumbler combination. Starting switches shall be of three-position type and shall be clearly marked as follows:

NORMAL. A central position for the key entry and spring return position.

START-UP. A right side position for starting the escalator in the upward direction.

START-DOWN. A left side position for starting the escalator in the downward direction.

(b) Starting Button. Starting buttons shall be of the constant pressure type and located within 6 inches (152 mm) from the starting switch. They shall be clearly marked "Starting Button".

(c) Cover Plate. A locked, transparent cover plate that can be opened by the starting key and clearly marked "For Start Only" shall protect the starting devices.

(d) Location of starting devices. Starting devices shall be located at the top and bottom of the escalator on the right side-facing newel.

NOTE: The starting key shall be kept on the premises at all times and shall only be accessible to persons authorized to start escalators. It shall also be made available to the commissioner or the commissioner's representatives.

5.3.2 Emergency stop buttons.

Delete and revise Section 5.3.2 to read as follows:

5.3.2 Emergency stop buttons location. A red stop button shall be visibly located at the top and bottom landings on the right side-facing the escalator. Remote stop buttons are prohibited, except that any escalator connected to an automatic fire alarm system shall gradually stop the escalator at a rate not greater than 3 ft per sec 2 (0.91 m/s 2 ) upon the activation of such system.

5.3.7 Skirt obstruction device.

Delete and revise the title of Section 5.3.7 to read as follows:

5.3.7 Skirt obstruction and deflector devices.

Add new Section 5.3.7.1 to read as follows:

5.3.7.1 Means shall be provided to cause the electric power to be removed from the escalator driving machine motor and brake if an object becomes caught between the step and the skirt as the step approaches the upper combplate, intermediate device or lower combplate. On units having a run of 20 feet (6.1 m) or more, intermediate devices shall be provided on both sides of the escalator with devices located at intervals of 10 feet (3.05 m) or less. The activation of intermediate devices shall stop the escalator at a rate not greater than 3 ft per sec 2 (0.91 m/s 2 ) in the direction of travel. The upper and lower skirt obstruction device shall be located so that the escalator will stop before that object reaches the combplate. The activation of any skirt device shall stop the escalator with any load up to full brake rated load with the escalator running.

Add new Section 5.3.7.2 to read as follows:

5.3.7.2 Skirt deflector devices, in accordance with 6.1.3.3.10 of A17.1, 2013, shall be provided no later than January 1, 2025.

Add new Section 5.3.13 to read as follows:

5.3.13 Comb-step stop device. A device shall be provided that will cause the opening of the power circuit to the escalator driving machine motor and brake where a resultant vertical force not greater than 60 lbf (268 N) in the upward direction is applied at the center of the front of the comb-plate.

PART VI DUMBWAITERS

Delete Part VI in its entirety.

PART VII HAND ELEVATORS

Add new Section 7.0 to read as follows:

SECTION 7.0 EXISTING HAND POWERED FREIGHT ELEVATORS

Existing hand powered freight elevators shall not be subject to the provisions of this section. However, adequate protection of landing openings shall be provided by hinged or sliding doors which shall remain locked at all times except when the freight elevator is in use. Auxiliary gates not less than 36 inches (914 mm) in height, substantially constructed and secured in place, of wood or metal, or equivalent metal chains shall be installed. Such gates or chains may be arranged to lift vertically, to slide horizontally, or to swing. No part of any gate or chain shall project into the freight elevator shaft. Gates may be operated automatically or manually.

SECTION 7.1 HOISTWAY, HOISTWAY ENCLOSURES, AND RELATED CONSTRUCTION

Delete Section 7.1 in its entirety.

SECTION 7.2 MACHINERY AND EQUIPMENT

Delete Section 7.2 in its entirety.

PART VIII SIDEWALK ELEVATORS

SECTION 8.1 HOISTWAY, HOISTWAY ENCLOSURES, AND MACHINE ROOMS

Delete Section 8.1 in its entirety.

SECTION 8.2 MACHINERY AND EQUIPMENT

8.2.2 Buffers and bumpers.

Delete Section 8.2.2 in its entirety.

8.2.3 Counterweights.

Delete Section 8.2.3 in its entirety.

8.2.4 Car frames and platforms.

Delete Section 8.2.4 in its entirety.

8.2.5 Bow-irons and stanchions.

Delete Section 8.2.5 in its entirety.

8.2.6 Car enclosures and car doors and gates.

Delete Section 8.2.6 in its entirety.

8.2.7 Car and counterweight safeties and governors.

Delete Section 8.2.7 in its entirety.

8.2.8 Capacity and loading.

Delete Section 8.2.8 in its entirety.

8.2.9 Driving machines and sheaves.

Delete Section 8.2.9 in its entirety.

8.2.10 Terminal stopping devices.

Delete Section 8.2.10 in its entirety.

8.2.11 Locking devices for hinged swinging doors or vertically lifting covers in sidewalks or other areas exterior to the building.

Delete Section 8.2.11 in its entirety.

8.2.12 Requirements for electrical wiring and electrical equipment.

Delete Section 8.2.12 in its entirety.

8.2.13 Clearance between loading side of car platforms and hoistway enclosures.

Delete Section 8.2.13 in its entirety.

8.2.14 Operating devices and control equipment of sidewalk elevator.

Delete and revise Section 8.2.14 to read as follows:

8.2.14 Operating devices and control equipment of sidewalk elevator. The operation of power sidewalk elevators through openings in the sidewalk, or through openings in other exterior areas that are accessible to the public, and that are protected by hinged doors or vertically lifting covers, shall conform to the following:

(a) The elevator shall be operated in both the up and down directions through the opening, only from the sidewalk or other exterior area. The operation shall be by means of:

(1) Key-operated continuous-pressure type up and down switches; or

(2) Continuous-pressure-type up-and-down operating buttons on the free end of a detachable, flexible cord 5 feet (1.52 m) or less in length.

(b) Key-operated switches shall be of continuous pressure spring return type, and shall be operated by a cylinder-type lock having not less than a five-pin or five-disk combination with the key removable only when the switch is in the "OFF" position.

(c) Key-operated switches and plug receptacles for flexible cords shall be mounted in weatherproof boxes with covers installed above the sidewalk or other area on the side of the building wall, located 18 inches (457 mm) or less horizontally from one side of the opening.

(d) Operating buttons may be provided in the elevator car and at any landing below the top landing, provided that such buttons shall operate the car only when the bow-iron or stanchions are not in contact with the doors or covers in the sidewalk of other exterior area.

(e) When the bow-iron or stanchions are in contact with the doors or covers at the sidewalk or other exterior area, it shall be possible to operate the car only by means of either the key switches or the continuous-pressure type up-and-down buttons on the free end of the flexible cord specified in Section 8.2.14(a)(1).

(f) Flexible cords and operating keys shall not be left where they are accessible to unauthorized persons for operation of the elevator.

PART IX MOVING WALKS

SECTION 9.2 PROTECTION OF SUPPORTS AND MACHINE SPACES AGAINST FIRE

Delete and revise the title of Section 9.2.2 to read as follows:

9.2.1 Protection required.

SECTION 9.3 CONSTRUCTION REQUIREMENTS

Delete and revise subsection (a) of Section 9.3.3.4 to read as follows:

9.3.3.4 Skirt panels. Where skirt panels are provided

(a) the clearance between each side of the treadway and the adjacent skirt panel shall be not more than 0.188 inches (4.8 mm).

SECTION 9.6 OPERATING AND SAFETY DEVICES

9.6.2 Starting switch.

Delete and revise Section 9.6.2 to read as follows:

9.6.2 Starting devices. In every new and existing moving walk, starting devices shall be provided with the combination of a starting switch and a starting button. The moving walk shall be started only after the activation of both the switch and the button.

(a) Starting Switch. Starting switches shall be of continuous pressure spring return type and shall be operated by a cylinder-type lock having five-pin, five-disc or five-tumbler combination. Starting switches shall be of three-position type and shall be clearly marked as follows:

NORMAL. A central position for the key entry and spring return position.

START-UP. A right-side position for starting the moving walks in the upward direction.

START-DOWN. A left-side position for starting the moving walks in the downward direction.

(b) Starting Button. Starting buttons shall be of the constant pressure type and located within 6 inches (152 mm) from the starting switch. They shall be clearly marked "Starting Button".

(c) Cover Plate. A locked, transparent cover plate that can be opened by the starting key and clearly marked "For Start Only" shall protect the starting devices.

(d) Location of starting devices. Starting devices shall be located at top and bottom of the moving walk on the right-side facing newel.

NOTE: The starting key shall be kept on the premises at all times and shall only be accessible to persons authorized to start moving walks. It shall also be made available to the commissioner or the commissioner's representatives.

9.6.3 Emergency stop buttons.

Delete and revise Section 9.6.3 to read as follows:

9.6.3 Emergency stop buttons location. A red stop button shall be visibly located at the top and bottom landings on the right side facing the moving walk. Remote stop buttons are prohibited, except that any moving walk connected to an automatic fire alarm system shall gradually stop the moving walk at a rate not greater than 3 ft/sec 2 (0.91 m/s 2 ) upon the activation of such system.

Add new Section 9.6.14 to read as follows:

9.6.14 Comb-plate stop device. A device shall be provided that will cause the opening of the power circuit to the moving walk driving-machine motor and brake when a resultant vertical force not greater than 60 lbf (268 N) in the upward direction is applied at the center of the front of the comb-plate.

PART X PRIVATE RESIDENCE ELEVATORS

Delete and revise Part X Scope to read as follows:

SCOPE

This Part applies to power elevators that are limited in size, capacity, rise, and speed and are installed in or at a private residence. This Part also applies to similar elevators installed in buildings as a means of access to private residences within such buildings provided the elevators are so installed that they are not accessible to the general public or to other occupants in the building.

NOTE: This Part has been developed to provide a minimum standard of safety for private residence elevators. These elevators are installed for the convenience of those persons who are unable to use stairways. Private residence elevators, while they are usually installed in single-family dwellings, may be installed within a separate apartment in a multiple dwelling where they are not accessible to the general public or to other occupants of the building. It is frequently necessary to install such elevators in open stairwells, as the construction of the building may not provide space for an enclosed hoistway.

Since the size, speed, load, rise, and use are limited, it is possible to provide an adequate level of safety without requiring the equipment to meet the standards in other parts of the Code. Equipment installed for use by the general public is subjected to much more severe and frequent service.

Although private residences are usually exempt from routine inspections, this Code will provide a basis for evaluation of existing equipment during resale or exchange of property. It will also be useful when an "installation placed out of service" is returned to use.

It should be noted that the rules of this Part of the Code do not apply to all power elevators installed in private residences, but only to those that meet the definition for "private residence elevator." All other elevators in private residences are required to comply with all the rules of the other parts of this Code.

All residential elevators shall comply with the following by November 7, 2023.

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

SECTION 10.1 HOISTWAY, HOISTWAY ENCLOSURES, AND RELATED CONSTRUCTION

Section 10.1.1 Hoistway enclosure construction.

Delete Section 10.1.1 in its entirety.

Section 10.1.2 Pits.

Delete Section 10.1.2 in its entirety.

Section 10.1.3 Top car clearance.

Delete Section 10.1.3 in its entirety.

Section 10.1.4.4 Locking devices for hoistway doors and gates.

Delete Section 10.1.4.4 in its entirety.

Section 10.1.4.5 Opening of hoistway doors or gates.

Delete Section 10.1.4.5 in its entirety.

Section 10.1.4.6 Hangers and stops for hoistway sliding doors.

Delete Section 10.1.4.6 in its entirety.

Section 10.1.4.7 Access to the hoistway for emergency purposes.

Delete Section 10.1.4.7 in its entirety.

Section 10.1.5 Pipes in hoistways.

Delete Section 10.1.5 in its entirety.

Section 10.1.6 Horizontal car clearances.

Delete Section 10.1.6 in its entirety.

Section 10.1.7 Guarding of suspension means.

Delete Section 10.1.7 in its entirety.

SECTION 10.2 CARS

Delete Section 10.2 in its entirety.

SECTION 10.3 COUNTERWEIGHTS

Delete Section 10.3 in its entirety.

SECTION 10.4 SAFETIES AND GOVERNORS

Delete Section 10.4 in its entirety.

SECTION 10.5 CAR AND COUNTERWEIGHT GUIDE RAILS AND FASTENINGS

Delete Section 10.5 in its entirety.

SECTION 10.6 CAR AND COUNTERWEIGHT BUFFERS

Delete Section 10.6 in its entirety.

SECTION 10.7 DRIVING MACHINES, SHEAVES, AND THEIR SUPPORTS

Delete Section 10.7 in its entirety.

SECTION 10.8 TERMINAL STOPPING DEVICES

Delete Section 10.8 in its entirety.

SECTION 10.9 OPERATING DEVICES AND CONTROL EQUIPMENT

10.9.1 Type of Operation.

Delete Section 10.9.1 in its entirety.

10.9.2 Control and Operating Circuit Requirements.

Delete Section 10.9.2 in its entirety.

10.9.3 Key Operated Switches.

Delete Section 10.9.3 in its entirety.

10.9.5 Phase Reversal and Failure Protection.

Delete Section 10.9.5 in its entirety.

10.9.7 Slack Rope and Slack Chain Devices for Winding Drum and Roller Chain Type Driving Machines.

Delete Section 10.9.7 in its entirety.

SECTION 10.10 EMERGENCY SIGNAL DEVICES

Delete and revise Section 10.10 to read as follows:

10.10.1 Emergency signal. A telephone connected to a central telephone exchange shall be permanently installed in the car and an emergency signaling device operable from inside the car and audible outside the hoistway shall be provided. The telephone must have the capability of calling outside to contact emergency personnel.

SECTION 10.11 LIMITATION OF LOAD, SPEED, AND RISE

Delete Section 10.11 in its entirety.

SECTION 10.12 MARKING PLATES

Delete Section 10.12 in its entirety.

SECTION 10.13 SUSPENSION MEANS

Delete Section 10.13 in its entirety.

Section BC M101. General

Open this section

M101.1 General.

The provisions of this appendix contain supplementary requirements for the design and construction of one- and two-family dwellings not more than three stories in height.

Section BC M102. Definitions

Open this section

M102.1 Definitions.

The following terms are defined in Chapter 2:

DWELLING, ONE-FAMILY.

DWELLING, TWO-FAMILY.

Section BC M103. Fire Wall Separation

Open this section

This section has 2 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read Section BC M103 at American Legal Publishing.

M103.1 General.

A fire wall shall be provided between buildings in accordance with Chapter 7. However, attached one- and two-family dwellings of construction Type IIIA, IIIB, VA and VB, where permitted and where each building is not more than three stories in height and not more than 2,100 square feet (195 m 2 ) on a story, may be separated by party walls constructed in accordance with the following and as illustrated in Figures M103(1) and M103(2):

1. If there are three or fewer contiguous attached one- or two-family dwellings, such fire wall shall consist of a solid 1-inch (25 mm) Type X gypsum wall board core covered on each side by a 1/2-inch (12.7 mm) exterior-grade Type X gypsum wall board, followed by a 1-inch (25 mm) air gap on one side. Such assembly shall be constructed between two independently supported load-bearing stud walls. See Figure M103(1).

2. If there are in excess of three contiguous attached one- or two-family dwellings, the fire wall shall be made of concrete and masonry, and constructed in accordance with Section 706.

3. Such wall shall be continuous between foundations and roofs.

4. When roof construction on the same level is combustible on both sides of the party wall, the party wall shall extend through the roof construction to a height of at least 4 inches (102 mm) above the high point of the roof framing unless a minimum of 18 inches (457 mm) of non-combustible roof construction is provided on each side of the party wall.

5. Such party wall shall be made smoke-tight at junctions with exterior walls. In buildings of construction Type VA or VB, exterior walls shall be constructed of noncombustible materials for a distance of at least 18 inches (457 mm) on each side of the party wall, or the party wall shall project at least 12 inches (305 mm) through the exterior wall.

Figure M103(1) Party Wall Vertical Section

Figure M103(2) Party Wall Plan Section

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

Section BC N101. General

Open this section

N101.1 Scope.

The provisions of this appendix shall control the performance standards of assistive listening systems (ALS).

Section BC N102. Induction Loop System

Open this section

N102.1 Induction loop system specifications.

1. Where induction-loop systems are provided for hearing aid purposes, the system performance shall be in accordance with IEC 60118-4:2014.

2. The methods of measuring and specifying the performance of system components shall be in accordance with IEC 62489-1:2010, as specified in IEC 60118-4:2014.

3. All electrical wiring installations shall be in accordance with the New York City Electrical Code.

N102.2 Capital projects.

City funded projects shall provide induction-loop systems pursuant to Section 224.3 of the New York City Charter.

Section BC N103. Infra-Red System

Open this section

N103.1 Infra-red system specifications.

1. If the ambient infra-red light (generally caused by other infra-red light-generating devices or direct sunlight) produces interference, it is recommended that, unless the interfering infra-red light can be reduced, infra-red systems not be considered.

2. Given an input signal to the transmitter at the levels specified in Item 6 over a minimum frequency range of 200 Hz to 8,000 Hz, the measured frequency response of the output signal generated by the receiver and transducer over that range shall not vary by more than +/- 5 decibels from the value at 1,000 Hz. In actual usage, graphic equalization of the output signal is allowed.

3. Given an input signal to the transmitter at the levels specified in Item 6, the minimum signal-to-noise ratio of the output generated by the receiver and transducer shall be 35 decibels at all frequencies specified in Item 2.

4. Given an input signal of 1,000 Hz to the transmitter at a level sufficient to produce the minimum signal-to-noise ratio specified in Item 3, the harmonic distortion produced by the receiver and transducer shall not be more than 5 percent.

5. Given a 1,000 Hz sinusoidal input signal at the levels specified in Item 6, the following are the possible transducers:

5.1. If using a neckloop as an output transducer, generate a magnetic field strength of at least 150 mA/meter. The peak field strength shall not exceed 600 mA/meter. Measurements shall be made at the geometric center of the plane of the neckloop.

5.2. If using a silhouette as an output transducer, generate a magnetic field strength of at least 50 mA/meter (the peak field strength shall not exceed 200 mA/meter). Measurements shall be made at a distance of 10 centimeters from the silhouette.

5.3. If using a miniature earphone as an output transducer, generate a sound pressure level of at least 80 decibels. The maximum high-frequency average sound pressure level shall not exceed 130 decibels.

5.4. If a direct input cable is used between the output of the receiver and the input of a hearing aid boot or shoe, generate a minimum voltage range of 2 mV to 800 mV and match a boot/shoe input impedance of 50 ohms or greater. The plugs at either end shall be molded 2-pin, 3-pin and/or 3.5-millimeter mini-plug (stereo or mono).

6. The system must have inputs capable of accepting signals at line level and microphone level and must be capable of interfacing with existing public address systems or stand-alone.

7. The minimum light level of the transmitted infra-red carrier signal must be sufficient so that a receiver can produce the specifications in Items 2, 3, 4 and 5 at any point within the user area.

8. Any stand-alone devices powered by 110-120 volt AC used as part of the system must be tested by an approved laboratory.

9. All electrical wiring installations shall be in accordance with the New York City Electrical Code.

Section BC N104. FM System

Open this section

N104.1 FM system specifications.

1. If an ambient FM signal (generally caused by other agencies on the same frequency or major power supplies) produces interference, it is recommended that, unless the frequency can be changed, an FM system not be considered.

2. Given an input signal to the transmitter at the levels specified in Item 6 over a minimum frequency range of 100 Hz to 8,000 Hz, the measured frequency response of the output signal generated by the receiver and a transducer over that range shall not vary by more than +/- 5 decibels from the value at 1,000 Hz. In actual usage, graphic equalization of the output signal is allowed.

3. Given an input signal to the transmitter at the levels specified in Item 6, the minimum signal-to-noise ratio of the output generated by the receiver and transducer shall be 35 decibels at all frequencies specified in Item 2.

4. Given an input signal to the transmitter at 1,000 Hz. at a level sufficient to produce the minimum signal-to-noise ratio specified in Item 3, the total harmonic distortion between the input signal and the program signal produced by the receiver and transducer shall not be more than 10 percent.

5. Given a 1,000 Hz. sinusoidal input signal at the levels specified in Item 6, the following are among the possible transducers:

5.1. If using a neckloop as an output transducer, generate a magnetic field strength of at least 150 mA/meter. The peak field strength shall not exceed 600 mA/meter. Measurements shall be made at the geometric center of the plane of the neckloop.

5.2. If using a silhouette as an output transducer, generate a magnetic field strength of at least 50 mA/meter. The peak field strength shall not exceed 200 mA/meter. Measurements shall be made at a distance of 10 centimeters from the silhouette.

5.3. If using a miniature earphone as an output transducer, generate a sound pressure level of at least 80 decibels. The maximum high-frequency average sound pressure level shall not exceed 130 decibels.

5.4. If a direct input cable is used between the output of the receiver and the input of a hearing aid boot or shoe, generate a minimum voltage range of 2 mV to 800 mV and match a boot/shoe input impedance of 50 ohms or greater. The plugs at either end shall be molded 2-pin, 3-pin and/or 3.5-millimeter mini-plug (stereo or mono).

6. The system must have inputs capable of accepting signals at line level and microphone level and must be capable of interfacing with existing public address systems or stand-alone.

7. The minimum sensitivity of the receiver shall be at least 2 mV at 12 decibel SINAD. The maximum RF signal generated by the transmitter shall not exceed 8,000 mV/meter at 30 meters.

8. Any stand-alone devices powered by 110-120 volt AC used as part of the system must be tested by an approved laboratory.

9. All electrical wiring installations shall be in accordance with the New York City Electrical Code.

10. The frequencies used by the transmitter should be in compliance with applicable FCC rules.

Section BC Q101. Scope

Open this section

Q101.1 Scope.

This appendix provides the modifications to the nationally recognized standards NFPA 13, NFPA 13D, NFPA 13R, NFPA 14, NFPA 20, NFPA 72, and NFPA 92, governing the installation and maintenance requirements of automatic sprinkler systems, standpipe and hose systems, fire pumps, fire alarms, and smoke control systems. Where a referenced publication has been modified for the City of New York as by the New York City Building Code and the New York City Fire Code, every reference to such publication shall be deemed to include all such modifications.

Section BC Q102. Installation of Sprinkler Systems

Open this section

Q102.1 General.

Sprinkler systems, where required by this code, shall be installed in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems, 2016 edition, modified for New York City as follows. Refer to the rules of the department for any subsequent additions, modifications or deletions that may have been made to this standard in accordance with Section 28-103.19 of the Administrative Code.

Chapter 1 Administration No changes.

Chapter 2 Referenced Publications

2.1 Add at end the following: "Where a referenced publication has been modified for the City of New York by the New York City Building Code or the rules of the Department of Buildings, every reference to such publication shall be deemed to include all such modifications. Where the edition of a publication referenced within this standard differs from the edition provided for the same standard in Chapter 35 of the New York City Building Code, the edition provided for in Chapter 35 of the New York City Building Code shall govern."

Chapter 3 Definitions No changes.

Chapter 4 General Requirements No changes.

Chapter 5 Classification of Occupancies and Commodities No changes.

Chapter 6 System Components and Hardware

6.3.1.1.1 Delete after the word wall and replace with the following: "in accordance with the New York City Plumbing Code."

Add the following at the end of section 6.3.9.1.1: "The use of pipe or tube other than that described above must involve consideration of many factors, including but not limited to the following:

1. Pressure rating.

2. Beam strength (hangers).

3. Corrosion (chemical and electrolytic).

4. Resistance to failure when exposed to elevated temperatures.

5. Methods of joining (strength, permanence, fire hazard).

6. Availability of fittings (for sprinkler outlets and proper routings).

7. Physical characteristics relating to integrity during earthquakes.

8. Toxicity.

9. Combustibility.

10. Movement during sprinkler operation (water distribution)."

Add Section 6.3.9.9 Non-metallic piping and fittings are permitted to be used only in Group R occupancies 6 stories or less in height.

6.7.1.3 Delete.

6.7.3 Delete.

Add Section 6.8.2.2.3 The alarm apparatus for a dry-pipe system shall also consist of approved low and high air pressure alarm attachments to the dry-pipe valve.

6.8.5 Change "8.16.2.6" to "8.17.1.9".

Chapter 7 System Requirements

7.1.5 Delete.

7.1.5.1 Delete.

Add 7.2.6.3.4 to read as follows: "High / Low air pressure in the system shall be monitored so that either condition sends a supervisory signal. Such signal shall trigger an audible notification signal and shall report to a supervising station if the system is required otherwise to do so."

7.2.6.8.3 Delete and replace with the following: "High / Low air pressure in the system shall be monitored so that either condition sends a supervisory signal. Such signal shall trigger an audible notification signal and shall report to a supervising station if the system is required otherwise to do so."

7.6.3.1 Delete.

Figure 7.6.3.1 Delete.

7.6.3.2 Add the following sentence at the end: "Backflow prevention device relief discharge shall be piped to a safe location.

7.9 Delete entire section, including subsections.

Chapter 8 Installation Requirements

8.2.1 Delete the first sentence and replace with the following: "The maximum floor area on any one floor to be protected by a single riser from a control and alarm device shall be as follows:"

8.15.3.2.1 Delete the words after "is" and replace with the following: "permanently blocked off so that storage cannot occur."

8.15.4.1* Delete the reference to 8.15.4.4 and add the following at the end: "when required by other sections of this standard or the New York City Building Code."

8.15.4.4 Delete.

8.15.5.3 Delete the words "in NFPA 101, or the applicable building code" and replace with the following: "in accordance with the New York City Building Code."

8.15.5.4* Delete the words "in elevator machine rooms or".

8.15.7.4 Delete.

8.15.7.5 Delete.

8.15.8.1.2 Delete all words after and including "as defined".

8.15.8.2* Delete and replace with the following: "Closets and Pantries. Sprinklers are not required in clothes closets, linen closets, and pantries within:

(1) Dwelling units in hotels and motels where the area of the closet or pantry does not exceed 24 square feet (2.2 m), the least dimension does not exceed 3 feet (0.9 m), and the walls and ceilings are surfaced with noncombustible or limited-combustible materials; and

(2) Dwelling units in Group R occupancies other than hotels and motels where the area of the closet or pantry does not exceed 12 square feet (1.1 m), the room or space upon which the closet or pantry opens is equipped with sprinklers designed to afford protection to the opening of the closet or pantry, and the walls and ceilings of the closet or pantry are surfaced with noncombustible or limited-combustible materials."

8.15.9 Add the following after the word "closets": "without solid doors".

8.15.16 Delete.

8.15.20.4.4 Delete and replace with the following: "In altering existing sprinkler systems which contain 3/4-inch (19 mm) pipe, the existing 3/4-inch (19 mm) pipe shall be removed and replaced with pipe having a minimum diameter of 1-inch (25 mm) except as provided for in 8.15.20.4.1, 8.15.20.4.2, 8.15.20.4.3 and 8.15.20.4.5."

Add 8.15.20.4.5 "Where nipples used are less than 1 in. (25 mm) diameter, nipples shall be schedule 80 and no longer than shoulder length."

8.15.20.5.4 Delete and replace with the following: "Where nipples used are less than 1 in. (25 mm) diameter, nipples shall be schedule 80 and no longer than shoulder length."

8.15.23.3 Delete.

8.15.26 Delete and replace with the following: "Sprinkler Interior Protected Glazing. Where sprinklers are used in combination with glazing as an alternative to a required fire-rated wall or window assembly, the sprinkler-protected assembly shall be approved by the commissioner and shall comply with the following:

"(1) Sprinklers shall be listed as specific application window sprinklers unless standard spray sprinklers are specifically permitted by the commissioner."

"(2) Sprinklers shall be supplied by a wet-pipe system."

"(3) Where the assembly is required to be protected from both sides, sprinklers shall be installed on both sides of the glazing."

"(4) The use of sprinkler protected glazing shall be limited to non-load-bearing walls."

"(5) The water supply duration for the design area that includes the window sprinklers shall not be less than the required rating of the assembly."

Add 8.16.1.1.1.4 to read as follows: "An approved indicating shutoff valve may be used in lieu of an O.S.&Y. gate valve wherever referred to in these modifications except such valve shall not be part of the pressure reducing valve. The indicator shall be readily visible from the floor."

Add 8.16.1.1.1.5 to read as follows: "A connection from public water system shall not extend into or through a building unless such connection is under the control of an outside indicator post or O.S.&Y. gate or under the control of an inside O.S.&Y. gate valve located near the outside wall of the building."

Add 8.16.1.1.1.6 to read as follows: "All gate valves controlling water supplied for sprinklers shall be located where readily accessible and when necessary, permanent ladders, clamped treads on risers, chains and wheels, or other accepted means shall be provided."

Add 8.16.1.1.1.7 to read as follows: "Floor control valves shall be provided where required or in special cases where area or height or number of tenants is excessive, both in manufacturing and mercantile buildings, or where contents are more than ordinarily susceptible to damage. Floor valves shall be located where they are readily accessible. They are to be O.S.&Y. or indicating type located ahead of the inlet of any pressure reducing valve."

Add 8.16.1.1.1.8 to read as follows: "Valves controlling sprinkler supplied from the standpipe system shall be listed for standpipe service in the pressure zone in which it is installed. They shall be O.S.&Y. or indicating valves, and shall be located ahead of the inlet of any pressure reducing valve installed."

8.16.1.1.2.2 Delete and replace with the following: "Floor control valves in high-rise buildings shall comply with 8.16.1.1.2.1(1) or 8.16.1.1.2.1(2)."

8.16.1.1.2.5 Delete.

8.16.1.1.3.5 Delete and replace with the following: "Where there is one water supply connection a check valve shall be installed. Such check valve may be a swing check, alarm check, an approved fire meter or an approved detector check."

Add 8.16.1.1.3.6 to read as follows: "Where a system having only one dry-pipe valve is supplied with city water and Fire Department connection, it will be satisfactory to install the main check valve in the water supply connection in a vertical position immediately inside of the building after the main indicating valve."

Add 8.16.1.1.3.7 to read as follows: "Check valves on tank or pump connections, when located underground, may be placed inside of buildings and at a safe distance from the tank riser or pump, except in cases where the building is entirely of one fire area, in which case the check valve may be located over-head in the lowest level."

Add 8.16.1.1.4.5 to read as follows: "Where either a wet or dry pipe sprinkler system is supplied by city water and a Fire Department connection and has more than one riser with O.S.&Y. gate valve in each, and the whole system is controlled by one outside post indicator valve, the main check valve in the water supply connection may be installed immediately inside building. If the supply is controlled by an underground gate valve with a Department of Environmental Protection standard curb, roadway or sidewalk flush box, the main check valve in the water supply connection shall be installed immediately after the O.S.&Y. gate valve inside the building."

Add 8.16.1.1.4.6 to read as follows: "A gate valve shall be installed on each side of each check valve under conditions other than described in 8.16.1.1.4.1, 8.16.1.1.4.2, 8.16.1.1.4.3 and 8.16.1.1.4.4. However, this shall not apply to two-way Fire Department check valves."

Add 8.16.1.1.4.7 to read as follows: "In a city connection serving as one source of supply, the city valve in the connection may serve as one of the required gate valves. An O.S.&Y. valve or an indicator post valve shall be installed on the systems (water supply) side of the check valve."

8.16.1.1.5 Delete and replace with the following: "Where a gravity tank is located on a tower in the yard, the gate valve on the tank side of the check valve shall be of O.S.&Y. type; the other shall be either an O.S.&Y. valve or other listed indicating valve. Where a gravity tank is located on a building, both gate valves shall be the O.S.&Y. type; and all fittings inside the buildings, except the drain tee fill line, and heater connections, shall be under the control of a gate valve."

8.16.1.2.4 Delete all words after and including the word "unless."

8.16.1.2.5 Delete all words after and including the word "at."

Add 8.16.1.3.4 to read as follows: "Where sprinklers are supplied from a yard main, a listed outside indicator post gate valve shall be placed in the connecting pipe at a safe distance from the building. Indicator post valves shall be located not less than 40 feet (12 192 mm) from buildings; but where necessary to place a valve close to a building, it shall be located at a blank part of the wall."

Add 8.16.1.3.5 to read as follows: "When a building has no basement, and an outside post indicator control cannot be furnished, a short post indicator may be installed in a horizontal position in riser with handwheel projecting outside of wall."

Add 8.16.1.4.2.7 to read as follows: "Pits for underground valves, except those located at the base of a tank riser, are described in the Standard for Outside Protection (ANSI/NFPA No. 24-2010). For pits protecting valves located at the base of a tank riser, refer to 8.15.1.4.2.6."

8.16.2.3.2 Add at the end the following: "unless the system is installed utilizing schedule 40 steel piping for sizes 1" to 6" and a minimum of schedule 30 steel piping for sizes 8" and larger."

Table 8.16.2.4.2 Delete and replace with the following:

TABLE 8.16.2.4.2 SECTIONAL OR FLOOR VALVE SIZE MINIMUM SIZE OF DRAIN CONNECTION Up to 2 in. 1 in. 2 1/2 in. to 4 in. 1 1/4 in. 5 in. and larger 2 in.

8.16.4.1.5 Delete.

8.16.6 Delete.

Add 8.17.1.5.3 to read as follows: "Identification signs shall be provided for outside alarm devices. The sign shall be located near the device in a conspicuous position and shall be worded as follows: "SPRINKLER FIRE ALARM –WHEN BELL RINGS NOTIFY FIRE DEPARTMENT OR POLICE"."

8.17.1.6 Add at end a new item 4 as follows: "(4) Refer to NFPA 72 for further requirements."

Add 8.17.1.8 to read as follows: "Dry Pipe System Alarms."

Add 8.17.1.8.1 to read as follows: "The alarm apparatus for a dry-pipe system shall consist of approved low and high air pressure alarm attachments as well as waterflow pressure type alarm attachments to the dry-pipe valve. When a dry-pipe valve is located on the system side of an alarm valve, the actuating device of the alarms for the dry-pipe valve may be connected to the alarms on the wet-pipe system."

Add 8.17.1.9 to read as follows: "Drains for Alarm Devices."

Add 8.17.1.9.1 to read as follows: "Where vents are necessary for satisfactory electric alarm switch operations, such vents shall be properly piped to a drain."

Add 8.17.1.9.2 to read as follows: "Drains from alarm devices shall be so arranged that there will be no danger of freezing, and so that there will be no overflowing at the alarm apparatus, at domestic connections or elsewhere with the sprinkler drains wide open and under pressure."

Add 8.17.1.9.3 to read as follows: "Drain from retarding chamber and electric alarm switch shall be permitted to discharge through an open cone and be run separate from main system drains to a safe and visible point of free discharge or to sewer or ground drain. Drain from water-motor-operated alarm device may run separately to sewer or ground drain or may be connected to drain from retarding chamber at a point between such sewer and a check valve on this drain, a union or plug being inserted in the drain from the alarm device to permit inspection. Where checks are used, they shall be so located as to have the equivalent of at least a four-foot (1219 mm) head and shall not be installed in a vertical position."

Add 8.17.1.9.4 to read as follows: "Where drains are conveyed to a sewer, a proper trap shall be provided."

Add 8.17.1.9.5 to read as follows: "Where it is necessary to drain alarm valves outside the wall, an open discharge cone shall be provided inside to break the pipe line so that cold air will not conduct directly into the retarding chamber. Alternately, all drains shall have at least 4 feet (1219 mm) of pipe beyond the valves, in a warm area."

8.17.2.2 Delete items 1 –3 and add the following:

"(1) Systems with sprinklered areas not exceeding 2000 square feet (186 m 2 )."

"(2) Systems containing 36 or fewer sprinkler heads except as otherwise required by other sections of this referenced standard."

8.17.2.3 Delete items 1 –3 and add the following:

"(1) Minimum size of two-way Fire Department connection is 5 inches (127 mm) except for two-way Fire Department connections supplying a single system with a riser smaller than 5 inches (127 mm) where a 4 inch (102 mm) two-way Fire Department connection may be used."

8.17.2.4.6 Delete.

Add 8.17.4.2.1.1 to read as follows: "This test pipe shall be not less than 1-inch in diameter, located in the upper story, and the connection shall be permitted to be piped from the end of the most remote branch line. The discharge shall be at a point where it can be readily observed. In locations where it is not practical to terminate the test pipe outside the building, the test pipe may terminate in a drain. In such case, the test connection shall be made using a sight test connection containing a smooth bore corrosion resistant orifice giving a flow equivalent to one sprinkler. The test valve shall be located at an accessible point, and not over seven feet above the floor. The control valve on the test connection shall be located at a point not exposed to freezing."

8.17.5 Delete.

Chapter 9 Hanging, Bracing, and Restraint of System Piping

9.2.1.3.3 Delete all subsections and replace with the following:

"9.2.1.3.3.1 Listed flexible hose fittings and their anchoring components intended for use in installations connecting the sprinkler system piping to sprinklers shall be rigidly fixed to the building structure at the sprinkler end of the flexible hose, independent of the ceiling suspension and support system in accordance with ASTM C 635, Section 3.1.1.10, as modified by Appendix R of the New York City Building Code."

9.3.4.11 Delete.

9.3.4.11.1 Delete.

Chapter 10 Underground Requirements

10.10.1 Delete and replace with the following: "The installing contractor shall perform all required inspections and acceptance tests in accordance with this chapter prior to scheduling an inspection."

Figure 10.10.1 Delete.

Chapter 11 Design Approaches

11.1.4.2* Delete and replace with the following: "The minimum water supply requirements for a pipe schedule designed sprinkler system shall be per the requirements of 11.2.2. The minimum water supply requirement for a hydraulically calculated sprinkler system shall be the calculated sprinkler system demand only, for the duration indicated in Table 11.2.3.1.2. Where gravity tanks are used as the supply or a portion of the supply to a hydraulically designed sprinkler system, it shall not be required to balance the calculated sprinkler flow and pressure demand to the outlet pressure of the gravity tank for the calculation of the water supply duration. The total water supply required shall be the product of the calculated system flow only, multiplied by the required water supply duration."

Add 11.1.4.2.1 to read as follows: "In fully sprinklered buildings, where an Automatic Wet Standpipe System is not required by Section 905 of the New York City Building Code, the storage capacity of the fire reserve in the tank supplying water to the sprinkler system shall be as required for the sprinkler demand, at a minimum."

11.1.6 Delete.

Add 11.2.2.10 to read as follows: "Where the water supply to a system sized in accordance with the pipe sizing schedules is taken from a water storage tank, the adequacy of the tank capacity shall be verified with a hydraulic calculation."

Table 11.2.3.1.2 Delete hose stream allowances.

11.2.3.1.5.2 (10) Delete.

Add 11.2.3.2.3.4 to read as follows: "Reductions in the size of the calculated area of operation shall not be taken for the use of quick response sprinklers in the design of systems in existing buildings employing fixed duration stored water supplies of less than 5,000 gallons."

Chapter 12 General Requirements for Storage

12.2 Delete.

12.7.2 Delete the following: "the hose stream allowance and".

12.7.4 Delete the following: "adding the hose stream allowance from 12.8 to".

12.8 Delete the following: "Hose Stream Allowance and".

12.8.4 Delete.

12.8.5 Delete.

12.8.6 Delete the following: "adding the hose stream allowance from Table 12.8.6 to".

Table 12.8.6 Remove the column(s) titled "Hose Stream Allowance" and all of its corresponding requirements.

12.12.1.2 Delete the following: "existing with a hose stream demand of at least 250 gpm (950 L/min)".

Chapter 13 Protection of Miscellaneous and Low-Piled Storage

13.1.2 Delete.

Table 13.2.1 Remove the column(s) titled "Inside Hose" and all of its corresponding requirements.

Chapter 14 Protection for Palletized, Solid-Piled, Bin Box, Shelf, or Back-to-Back Shelf Storage of Class I through Class IV Commodities

14.3.4 Delete the following: "Hose stream allowance and".

Chapter 15 Protection for Palletized, Solid-Piled, Bin Box, Shelf, or Back-to-Back Shelf Storage of Plastic and Rubber Commodities No changes.

Chapter 16 Protection of Rack Storage of Class I Through Class IV Commodities

Table 16.3.3.1 Remove Hose Stream Allowance Requirements.

Chapter 17 Protection of Rack Storage of Plastic and Rubber Commodities

17.3.1.17 Delete the following: "adding the hose stream allowance from Table 17.3.1.17 to".

Table 17.3.1.17 Delete.

Chapter 18 Protection of Rubber Tire Storage

18.3 Delete the following: "hose streams".

Chapter 19 Protection of Roll Paper

19.1.1.1 Delete the following: "plus the hose stream allowance".

Chapter 20 Special Designs of Storage Protection

20.3.1 Delete the following: "with 500 GPM (1900 L/min) hose stream allowance".

20.3.2 Delete the following: "with 500 GPM (1900 L/min) hose stream allowance".

20.3.3 Delete the following: "with 500 GPM (1900 L/min) hose stream allowance".

20.3.4 Delete the following: "with 500 GPM (1900 L/min) hose stream allowance".

20.3.5 Delete the following: "with 500 GPM (1900 L/min) hose stream allowance".

20.3.6 Delete the following: "with 500 GPM (1900 L/min) hose stream allowance".

20.4.1.1 Delete the following: "plus a minimum of 500 gpm (1900 L/min) for hose streams".

20.4.1.2 Delete the following: "and hose streams".

Table 20.5.6.2 Remove the row(s) titled "Hose Allowance" and all of its corresponding requirements.

Chapter 21 Alternative Sprinkler System Designs for Chapters Through 20

21.1.7(5) Delete.

21.4 Delete the following: "Hose Stream Allowance and".

21.4.1 Delete the following: "adding the hose stream allowance from Table 21.4.1 to".

Table 21.4.1 Remove the column(s) titled "Hose Stream Allowance" and all of its corresponding requirements.

Chapter 22 Special Occupancy Requirements

Add 22.1.1.3 to read as follows: "The application of the requirements of this chapter are subject to the approval of the Fire Commissioner."

22.12.1.2 Delete.

22.12.1.3 Delete the following: "to augment hand hose streams".

22.13.1 Delete the following: "plus an allowance of 1,000 gpm (63 L/sec) for hand hose streams for not less than 2 hours".

22.15.2.2.1 Gravity Waste and Linen Chutes. Add the following after the heading: "Sprinklers shall be provided in chute vestibules on all floors; if no vestibule exists, sprinklers shall be provided above chute doors and shall be located no more than 1-foot (25 mm) horizontally from face of chute door. All building service chute sprinkler systems shall be provided with a local water flow and valve supervisory alarm with supervising station annunciation. In high rise buildings where sprinklers in chutes are supplied by a chute riser(s), such riser(s) shall be zoned to coincide with the zoning of the standpipe riser(s)."

22.15.2.2.1.5 Delete.

22.21.1.7.3 Delete.

22.21.7.4 Delete the following: "plus the hose stream demand specified in 22.21.1.7.3".

22.25.1.4 Delete the following: "plus a minimum of 500 gpm (1893 L/min) for hose streams".

22.26.1.2 Delete the following: "plus hose stream demand".

22.26.1.2.1 Delete.

22.27.1.1(1) Delete the following: "500 gpm (1892.5 L/min) for manual hose streams plus".

22.28.1(2)(a) Delete the following: "500 gpm (1892.5 L/min) for manual hose streams plus".

Table 22.37.1.4.4.1(B) Remove the row titled "hose stream demand" and all of its corresponding requirements.

Table 22.37.1.4.4.3 Remove the row titled "hose stream demand" and all of its corresponding requirements.

Chapter 23 Plans and Calculations

23.1.3(35) Delete the following: "and the water required for hose streams both inside and outside."

23.3.2(9) Delete "inside hose".

23.3.4(3) Delete and renumber (4) to (3).

23.3.5.2(16) Delete "inside hose."

23.3.5.3(3) Delete and renumber (4) and (5) to (3) and (4), respectively.

23.3.5.5(4) Delete.

23.4.4.2.5 Delete "not including hose stream allowance".

Chapter 24 Water Supplies

24.1.1 Add the following at the end of the section:

"(a) Two automatic sources of water supply shall be provided for sprinklers in:"

"(1) Buildings classified in occupancy group H."

"(2) Buildings classified in occupancy group M when the area on one floor exceeds 20,000 square feet (1858 m 2 )."

"(3) Buildings classified in occupancy group A-1 with stages larger than 1,000 square feet (93 m 2 ) in floor area or with a stage height greater than 40 feet (15 240 mm)."

"(b) The domestic water supply may be used to supply any sprinklers required by Section 903 of the New York City Building Code when installed in buildings classified in occupancy groups B, E, I and R, and not classified as a high-rise building, provided that all the requirements stated in subdivision (d) of this section are met."

"(c) The domestic water supply may be used to supply water to sprinklers in cooling towers if provision is made to automatically stop the use of water through the domestic supply lines and provided that all of the requirements stated in subdivision (d) of this section are met."

"(d) When the domestic water is used to supply sprinklers as permitted in subdivisions (b) and (c) of this section, all of the following conditions shall be met:"

"(1) The domestic water supply line from the tank or street supply shall be at least the size of the sprinkler line and the capacity available shall be at least equal to the capacity required for the sprinklers."

"(2) The domestic water supply line from the tank or street shall have the required pressure as provided in this referenced standard."

"(3) The domestic water supply line shall be of non ferrous material except when the domestic water supply is four inches (102 mm) or more."

"(4) An O.S.&Y. valve or other listed valve having visual indication, and sealed open, shall be installed in the sprinkler supply branch, or such other valve arrangement as may be provided in this referenced standard and in referenced standards NFPA 13R or NFPA 13D as modified for New York City, as applicable."

"(5) The pipe connecting the domestic water supply and the sprinkler control valve shall be of nonferrous material and not less than twelve inches (305 mm) long."

"(6) The number of heads in each fire section shall not exceed six, except that the number of heads in each fire section may exceed six in buildings classified in occupancy group R-2, or R-3 not exceeding six stories or 75 feet (22 860 mm) in height and in spaces classified in occupancy group R-2, or R-3 in buildings not exceeding six stories or 75 feet (22 860 mm) in height, provided that no more than three heads are supplied from any one domestic water riser."

"(7) The connection shall be made at the supply or riser side of any domestic branch control valves."

"(8) In connection with the above conditions, the number of fire sections having 6 or fewer heads may be unlimited; and the installation of alarms in branches supplying fire sections shall be at the option of the owner, except that such alarms shall be provided where required by referenced standards NFPA 13R and NFPA 13D as modified for New York City."

"(9) A check valve shall be installed on the sprinkler supply branch."

24.1.3.2(1) Delete the words "or Class II Standpipes".

Add 24.2.3.1 to read as follows: "Combined Use. In light hazard occupancies with only limited ordinary hazard areas, an automatic fire pump serving the lower 300 feet (91 440 mm) of the standpipe system may be used as the primary supply to the sprinkler system, provided that an automatic switching secondary power supply is available to drive the pump, where secondary power is required by other provisions of this code, and that the pump is fully supervised as to pump running and power loss. The supervisory attachments shall be directly connected to an office where maintenance personnel are in attendance twenty-four hours a day; or, in lieu thereof, the supervisory attachment may be directly connected to the supervising station of an approved operating fire alarm company."

Add 24.2.3.2 to read as follows: "In hydraulically designed sprinkler systems supplied from a gravity tank, the pressure may be increased by means of an automatic, special service fire pump. The pump shall be sized to satisfy the water supply requirements of this section and the New York City Building Code and shall be arranged with a bypass to permit the portion of the system so supplied to be served by the system's two-way Fire Department connections.

If the pump is not supplied from the street side of the building service switch, the electrical service and pump operation shall be fully supervised and an automatic switching secondary power supply provided to drive the pumps, where secondary power is required by other provisions of this code."

Add 24.2.3.3 to read as follows: "Wiring for Fire Pumps. When the fire pump feeder conductors are routed through the building(s), they shall be enclosed by 2 inches (51 mm) of concrete or an assembly that has a minimum of 2-hour fire resistive rating. Wiring for all fire and sprinkler pumps shall be in accordance with the New York City Electrical Code."

Add 24.2.3.4 to read as follows: "Sprinkler Booster Pumps. Where the pressure from the city water main is insufficient to comply with the requirements of this referenced standard, but is sufficient to provide at least 5 PSI (34 kPa) at the highest level of sprinklers as determined by test, an automatic, electrically driven pump installed for the purpose of boosting or increasing the city water pressure in the sprinkler system may be used subject to the following requirements:"

"(a) Pumps shall be of approved centrifugal type, capable of delivering at least 200 gpm (757 L/m), and shall be capable of supplying the calculated flow and pressure demand of the sprinkler system."

"(b) Pumps shall be maintained under approved automatic control with closed circuit supervisory attachment. The supervisory attachments shall be directly connected to an office where maintenance personnel are in attendance twenty-four hours a day; or, in lieu thereof, the supervisory attachment may be directly connected to the supervising station of an approved operating fire alarm company. The supervisory alarm services shall be arranged so as to provide positive indication at an approved central office or sprinkler alarm panel board that the pump has operated or that the source of electrical supply has failed."

"(c) Such pumps shall also comply with the applicable provisions of this referenced standard and the New York City Building Code pertaining to fire pumps, except that only one water supply shall be required."

"(d) Power to such pumps shall be supplied from the street side of the building service switch. Secondary power shall be provided where required by other provisions of this code."

"(e) If a secondary power supply is provided to drive the pump and such power supply is automatic switching, the 5 psi (34 kPa) requirement in 23.2.2.4 and the requirements of paragraph (d), for power to be supplied from the street side of the building service switch, may be waived."

24.2.4.1 through 24.2.4.3, including all subsections Delete.

Add 24.2.4.1 to read as follows: "A pressure tank providing water supply in accordance with Table 11.2.2.1 or section 11.2.3 is an acceptable water supply source. The total available quantity of water in pressure tanks need not exceed 15,000 gallons (56 781 L) when there is a secondary source of water supply available from a gravity tank or a street connection. The maximum gross capacity of a single pressure tank shall be 9,000 gallons (34 069 L) and shall include the needed extra capacity to fill dry-pipe or preaction systems when installed."

Add 24.2.4.1.1 to read as follows: "Each tank shall be kept at a maximum of 2/3 full of water and a minimum of 1/3 full of air maintained under a minimum pressure of 75 psig (517 kPa). The water-to-air ratio shall be so proportioned and the tank so located that a minimum pressure of 15 psig (103 kPa) will be available on the highest line of sprinklers below the main roof when all the water has been discharged from the tank."

Add 24.2.4.1.2 to read as follows: "The tank supports shall be designed on the basis of a full tank. The tanks shall be supplied with water through a fixed pipe, independent of the sprinkler piping and at least 2 inch (51 mm) in size. The water supply shall be capable of supplying the tank at a rate of at least 65 gpm (4 L/s) without decreasing the pressure in the tank. The tank shall have a fixed water level plate on the end of the tank opposite the gage glass, or equivalent devices, to indicate the level of the water in the tank."

Add 24.2.4.1.3 to read as follows: "The air compressor shall be provided with automatic controls for maintaining the air pressure. The capacity of the compressor shall be sufficient to build up the tank pressure to 75 psig (517 kPa) within 3 hr. or less."

Add 24.2.4.1.4 to read as follows: "Pressure tanks shall be provided with closed circuit high and low water and high and low air pressure alarms."

Add 24.2.4.1.5 to read as follows: "Pressure tanks shall be located at or above the top level of sprinklers."

24.2.5 Add at end the following: "If any of the sprinkler heads are supplied from domestic water tanks, the combined water supply in the tank shall be at least 5,000 gallons (18 927 L). Further, the sprinkler water supply shall be taken from the lowest level of the tank."

Add 24.2.5.1 to read as follows: "Combined Use. In A, B, E, I and R Occupancies, with only limited ordinary hazard areas, the sprinkler and standpipe reserve may be common to both. The Reserve shall be sized for the greater demand, in accordance with NFPA 14, 7.10.1.3. For purposes of this section, limited shall be defined as less than 30 percent of the floor area on the given floor. Buildings whose occupancies are more than 85 percent light hazard may have a light hazard water supply, provided the ordinary hazard areas are designed for ordinary hazard requirements with respect to sprinkler spacing and pipe sizing."

Add 24.2.5.2 to read as follows: "Combined standpipe and sprinkler systems may be used in Occupancies A, B, E, F, I, M, R and S. If an automatic fire pump is used as the primary supply, the requirements of 23.2.2.1 shall apply."

Chapter 25 Systems Acceptance

25.1 Delete and replace with the following: "The installing contractor shall inspect and test the installation in accordance with the procedures of this chapter prior to scheduling an inspection."

25.2.1.1 Delete the words "2 hours" and replace with "1 hour".

25.2.1.4.1 Delete the words "2 hours" and replace with "1 hour".

25.2.1.7 Delete the words "150 psi (10.3 bar)" and replace with "200 psi (13.8 bar)".

25.3 Delete entire section, including subsections.

25.3.1 Delete.

25.3.2 Delete.

25.3.3 Delete.

25.3.4 Delete.

25.5.2(5) Delete.

25.6.2 (13) Delete item 13 and renumber remainder of items accordingly.

Chapter 26 Marine Systems No changes.

Chapter 27 System Inspection, Testing, and Maintenance

27.1 Delete and replace with the following: "General. A sprinkler system installed in accordance with this standard shall be properly inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems and the New York City Fire Code, to provide at least the same level of performance and protection as designed."

ANNEXES

The annexes are not a part of the requirements of this Referenced Standard but are included for informational purposes only. These annexes contain explanatory material, numbered to correspond with the applicable text paragraphs. In the event of any conflict between the Annexes and the body of the Referenced Standard, particularly where modifications have been made for New York City, the body of the Referenced Standard will govern.

Annex A Explanatory Material

Annex B Miscellaneous Topics

Annex C Explanation of Test Data and Procedures for Rack Storage

Annex D Sprinkler System Information from the 2012 Edition of the Life Safety Code

Annex E Development of the Design Approach to Conform with SEI/ASCE 7

Annex F Informational References

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

Section BC Q103. Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes

Open this section

Q103.1 General.

Sprinkler systems, where required by this code, shall be installed in accordance with NFPA 13D, Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes, 2016 edition, modified for New York City as follows. Refer to the rules of the department for any subsequent additions, modifications or deletions that may have been made to this standard in accordance with Section 28-103.19 of the Administrative Code.

Chapter 1 Administration No changes.

Chapter 2 Referenced Publications

2.1 Add at end the following: "Where a referenced publication has been modified for the City of New York by the New York City Building Code or the rules of the Department of Buildings, every reference to such publication shall be deemed to include all such modifications. Where the edition of a publication referenced within this standard differs from the edition provided for the same standard in Chapter 35 of the New York City Building Code, the edition provided for in Chapter 35 of the New York City Building Code shall govern."

Chapter 3 Definitions

3.3.11.3 Delete.

3.3.11.7 Delete.

Chapter 4 General Requirements No changes.

Chapter 5 System Components

5.2.2 Add at end the following: "Non-metallic pipe shall be used in wet systems only."

5.2.2.3 Delete.

5.4 Delete.

Chapter 6 Water Supply

6.2 Add the following as item (6):

"(6) A common supply main to the building, serving both sprinklers and domestic uses, may be used if provision is made to prevent flow on the domestic water system upon operation of sprinklers, and closure of the main sprinkler control valve (the house control valve) will shut off the domestic water supply."

6.3 Delete.

Chapter 7 Installation

7.1.1 Delete the words "unless a separate shutoff valve for the sprinkler system is installed in accordance with 7.1.2."

7.1.2 Delete and replace with the following: "Except for the meter set controlling combined domestic water and fire sprinkler systems, sectional control valves and other valves if provided in supply pipes to sprinklers shall be locked open and supervised open by one of the following methods:"

"(a) Supervising station, proprietary or remote station signaling service, or"

"(b) Local signaling service that will cause the sounding of an audible signal."

"Exception: Underground gate valves with roadway boxes need not be supervised."

7.1.3 Delete the words "other than those complying with Section 6.3."

7.6 Add at the end the following: "as modified for New York City."

Chapter 8 Sprinkler Position and Location

8.3.4 Add the following after the word "garages": "provided that at least one sprinkler head is located within 3 feet (914 mm) of any communicating opening between the garage and the dwelling."

8.3.5 Add after the word "attics", the words "without floors".

Chapter 9 Protection from Freezing

9.2.3.1.1 Delete and replace with the following: "Arrangement of supply piping to an anti-freeze system shall be in accordance with NFPA 13-2016 as modified for New York City."

9.2.3.1.2 Delete.

9.2.3.1.3 Delete.

9.2.3.1.4 Delete.

9.2.3.2 Delete.

9.2.3.2.1 Delete.

9.2.3.2.2 Delete.

9.2.3.2.3 Delete.

Chapter 10 Discharge and Hydraulic Calculations

10.4.2.2 Delete the words "unless smaller sizes are permitted by 10.4.2.3."

10.4.2.3 Delete.

Chapter 11 System Acceptance

11.2.1.1 Delete and replace with the following: "Where a Fire Department pumper connection is not provided, the system shall be hydrostatically tested for leakage at 50 psi (344 kPa) above normal system operating pressure and checked visually for leakage at each joint or coupling."

11.2.1.2 Add the following to the end: "As modified for New York City. Dry systems shall also be tested by placing the system under 40 pounds (2.8 bar) air pressure. Any leak that results in a drop in system pressure greater than 2 psi (0.14 bar) in 24 hours shall be corrected. Check for leaks using soapy water brushed on each joint or coupling. Leaks will be shown by the presence of bubbles. This test shall be made prior to concealing of piping."

Chapter 12 Inspection, Testing, and Maintenance

12.1 Add at end the following: "The owner is responsible for the maintenance of the system."

ANNEXES

The annexes are not a part of the requirements of this Referenced Standard but are included for informational purposes only. These annexes contain explanatory material, numbered to correspond with the applicable text paragraphs. In the event of any conflict between the Annexes and the body of the Referenced Standard, particularly where modifications have been made for New York City, the body of the Referenced Standard will govern.

Annex A Explanatory Material

A.5.2.3.2 Delete.

Figure A.6.2(c) Delete the "Fire sprinkler shutoff valve (supervised or lockable)*" shown.

A.6.3 Delete.

Figure A.6.3(a) Delete.

Figure A.6.3(b) Delete.

Figure A.6.3(c) Delete.

Figure A.6.3(d) Delete.

A.10.4.2.3(1) Delete.

Figure A.10.4.2.3(1) Delete.

Annex B Informational References No changes.

Section BC Q104. Installation of Sprinkler Systems in Residential Occupancies

Open this section

Q104.1 General.

Sprinkler systems, where required by this code, shall be installed in accordance with NFPA 13R, Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies, 2016 edition, modified for New York City as follows. Refer to the rules of the department for any subsequent additions, modifications or deletions that may have been made to this standard in accordance with Section 28-103.19 of the Administrative Code.

Chapter 1 Administration

1.1 Delete after the word "including" and replace with the following: "six stories in height in buildings not exceeding 60 ft (18.3 m) in height above grade plane."

1.2.3 Add at end the following: "in accordance with the New York City Building Code."

Chapter 2 Referenced Publications

2.1 Add at end the following: "Where a referenced publication has been modified for the City of New York by the New York City Building Code or the rules of the Department of Buildings, every reference to such publication shall be deemed to include all such modifications. Where the edition of a publication referenced within this standard differs from the edition provided for the same standard in Chapter 35 of the New York City Building Code, the edition provided for in Chapter 35 of the New York City Building Code shall govern."

Chapter 3 Definitions

3.3.6 Delete after the word "walls."

3.3.9 Delete (Use definitions contained in the New York City Building Code).

Chapter 4 General Requirements No changes.

Chapter 5 System Components

5.2.1 Add at the end the following: "Non-metallic pipe shall be used in wet systems only when standpipe is not present."

5.2.11 Add at the end the following: "in accordance with the New York City Plumbing Code."

5.3.2(1) Delete and replace with the following: "Antifreeze systems – Only glycerin type anti-freeze is permitted for use in systems containing non-metallic pipe or fittings."

Chapter 6 Installation

6.5.4 Delete and replace with the following: "Sprinkler Interior Protected Glazing. Where sprinklers are used in combination with glazing as an alternative to a required fire-rated wall or window assembly, the sprinkler-protected assembly shall be approved by the commissioner and shall comply with the following:

"(1) Sprinklers shall be listed as specific application window sprinklers unless standard spray sprinklers are specifically permitted by the commissioner."

"(2) Sprinklers shall be supplied by a wet pipe system."

"(3) Where the assembly is required to be protected from both sides, sprinklers shall be installed on both sides of the glazing."

"(4) The use of sprinkler protected glazing shall be limited to non-load-bearing walls."

"(5) The water supply duration for the design area that includes the window sprinklers shall not be less than the required rating of the assembly."

6.6.6* After the word "attics" add the words: "without floors".

Add 6.6.10 to read as follows: "Location of sprinklers installed in buildings classified in occupancy group R-1 shall be in accordance with the requirements of the New York City Building Code and NFPA 13-2016 as modified for New York City."

6.8.2 Delete and replace with the following: "Except for the meter set controlling combined domestic water and fire sprinkler systems, sectional control valves and other valves if provided in supply pipes to sprinklers shall be locked open and supervised open by one of the following methods:"

"(a) Supervising station, proprietary or remote station signaling service, or"

"(b) Local signaling service that will cause the sounding of an audible signal at a constantly attended point."

"Exception: Underground gate valves with roadway boxes need not be supervised."

6.11 Delete and replace with the following: "Fire Department Connection. Except in buildings classified in occupancy group R-1, at least one 3 in. (76 mm) single inlet Fire Department connection shall be provided and located in accordance with the New York City Building Code. Buildings classified in occupancy group R-1 shall be provided with two-way Fire Department connections in accordance with the referenced standard NFPA 13-2016 as modified for New York City. A Fire Department connection is not required in one-and two-family dwellings."

6.11.1 Delete.

6.11.2 Delete.

6.11.5 Delete.

Chapter 7 Discharge Criteria No changes.

Chapter 8 Plans and Calculations No changes.

Chapter 9 Water Supply

9.3 Add the following as item (5):

"(5) A common supply main to the building, serving both sprinklers and domestic uses, may be used if provision is made to prevent flow on the domestic water system upon operation of sprinklers, and closure of the main sprinkler control valve (the house control valve) will shut off the domestic water supply."

9.6 Delete.

Chapter 10 System Acceptance

10.1.2 Delete.

Figure 10.1.2 Delete.

10.1.3 Delete.

Chapter 11 Care and Maintenance

11.3 Delete and replace with the following: "Sprinkler systems shall be inspected, tested, and maintained in accordance with the New York City Fire Code and with the rules of the Fire Department."

11.4 Delete.

ANNEXES

The annexes are not a part of the requirements of this Referenced Standard but are included for informational purposes only. These annexes contain explanatory material, numbered to correspond with the applicable text paragraphs. In the event of any conflict between the Annexes and the body of the Referenced Standard, particularly where modifications have been made for New York City, the body of the Referenced Standard will govern.

Annex A Explanatory Material

A.1.1 Delete the words "four stories" and replace with the words: "six stories".

A.5.2.12.2 Delete.

A.9.6 Delete.

Table A.9.6(a) Delete.

Table A.9.6(b) Delete.

Annex B Informational References No changes.

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.