NYC Administrative Code Title 28, Chapter 7 New York City Building Code, part 5 of 33
Section BC 426 to Section BC 704: 20 sections.
Section BC 426. Combustible Dusts, Grain Processing and Storage
426.1 Combustible dusts, grain processing and storage.
The provisions of Sections 426.1.1 through 426.1.7 shall apply to buildings in which materials that produce combustible dusts are stored or handled. Buildings that store or handle combustible dusts shall comply with the applicable provisions of NFPA 61, NFPA 69, NFPA 85, NFPA 120, NFPA 484, NFPA 654, NFPA 655 and NFPA 664 and the New York City Fire Code.
426.1.1 Type of construction and height exceptions.
Buildings shall be constructed in compliance with the height, number of stories and area limitations specified in Sections 504 and 506; except that where erected of Type I or II construction, the heights and areas of grain elevators and similar structures shall be unlimited, and where of Type IV construction, the maximum building height shall be 65 feet (19 812 mm) and except further that, in isolated areas, the maximum building height of Type IV structures shall be increased to 85 feet (25 908 mm).
426.1.2 Grinding rooms.
Every room or space occupied for grinding or other operations that produce combustible dusts in such a manner that the room or space is classified as a Group H-2 occupancy shall be enclosed with fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. The fire-resistance rating of the enclosure shall be not less than 2 hours where the area is not more than 3,000 square feet (279 m 2 ), and not less than 4 hours where the area is greater than 3,000 square feet (279 m 2 ).
426.1.3 Conveyors.
Conveyors, chutes, piping and similar equipment passing through the enclosures of rooms or spaces shall be constructed dirt tight and vapor tight, and be of approved noncombustible materials complying with Chapter 30.
426.1.4 Explosion control.
Explosion control shall be provided as specified in the New York City Fire Code, or spaces shall be equipped with the equivalent mechanical ventilation complying with the New York City Mechanical Code.
426.1.5 Grain elevators.
Grain elevators, malt houses and buildings for similar occupancies shall not be located within 30 feet (9144 mm) of interior lot lines or structures on the same lot, except where erected along a railroad right-of-way.
426.1.6 Coal pockets.
Coal pockets located less than 30 feet (9144 mm) from interior lot lines or from structures on the same lot shall be constructed of not less than Type IB construction. Where more than 30 feet (9144 mm) from interior lot lines, or where erected along a railroad right-of-way, the minimum type of construction of such structures not more than 65 feet (19 812 mm) in building height shall be Type IV.
426.1.7 Tire rebuilding.
Buffing operations shall be located in a room separated from the remainder of the building housing the tire rebuilding or tire recapping operation by a 1-hour fire barrier.
Exception: Buffing operations are not required to be separated where all of the following conditions are met:
1. Buffing operations are equipped with an approved continuous automatic water-spray system directed at the point of cutting action;
2. Buffing machines are connected to particle-collecting systems providing a minimum air movement of 1,500 cubic feet per minute (cfm) (0.71 m 3 /s) in volume and 4,500 feet per minute (fpm) (23 m/s) in-line velocity; and
3. The collecting system shall discharge the rubber particles to an approved outdoor noncombustible or fire-resistant container, which is emptied at frequent intervals to prevent overflow.
Section BC 427. Non-Production Chemical Laboratories
427.1 General.
The provisions of this section shall govern the design, construction and chemical quantity limitations of buildings and portions thereof occupied or designed to be occupied as a nonproduction laboratory. Nonproduction laboratories shall be classified into occupancy groups in accordance with Section 427.5. The provisions of this section shall not apply to production laboratories classified in Occupancy Group F or H.
427.2 Standards.
Except as otherwise provided in this section, nonproduction laboratories shall meet the design, construction and chemical quantity limitation requirements for laboratory unit fire hazard Class D, as set forth in NFPA 45 as modified by the New York City Fire Code, and the New York City Mechanical Code. The storage arrangement, handling and use of chemicals within nonproduction laboratories and accessory storage rooms, and the operation and maintenance of nonproduction laboratories shall comply with the requirements of the New York City Fire Code, and the rules of the Fire Commissioner.
427.3 Prohibitions.
It shall be unlawful in any nonproduction laboratory to:
1. Store or use any explosive.
2. Store or use any unclassified detonable organic peroxide, detonable pyrophoric material, detonable unstable (reactive) material or detonable water-reactive material.
3. Store or use any Class 4 unstable (reactive) material.
4. Store or use any Class 4 oxidizing material.
5. Store or use any flammable gas below grade.
427.4 Definitions specific to this section.
The following terms shall, for the purposes of this section, have the meanings shown herein:
LABORATORY BUILDING. A structure consisting wholly or principally of one or more laboratory units.
LABORATORY CHEMICAL. A material with a health, flammability, or instability hazard rating of 2, 3, or 4 as defined in NFPA 704.
LABORATORY, NONPRODUCTION. A building or portion thereof wherein chemicals or gases are used or synthesized on a nonproduction basis for testing, research, experimental, instructional or educational purposes.
LABORATORY UNIT. An enclosed space of a minimum 1-hour fire-rated construction, designed or used as a nonproduction laboratory. Laboratory units may include one or more separate laboratory work areas, and accessory storage rooms or spaces within or contiguous with the laboratory unit, such as offices and lavatories.
STORAGE CABINET. A cabinet designed and constructed in accordance with UL 1275, and used for the storage of not more than 60 gallons (227 L) of flammable and combustible liquids.
STORAGE ROOM. A room where laboratory chemicals or gases are stored and not otherwise used or synthesized.
427.5 Classification.
Buildings or portions thereof occupied as a nonproduction laboratory may be classified as a Group B occupancy provided they comply with the provisions of Section 427. Nonproduction laboratories not in compliance with the provisions of Section 427.7 for laboratory chemical quantity limitations shall be classified as Group H occupancy.
427.5.1 Accessory use nonproduction laboratories.
Accessory use nonproduction laboratories occupying an area not more than 10 percent of the area of the story in which such laboratories are located and not exceeding the tabular values in Sections 504 and 506 for the allowable height or area for such use shall be classified according to the main occupancy. Such accessory nonproduction laboratories shall comply with the provisions of Section 427.
427.6 Fire protection.
Fire protection systems in nonproduction laboratories shall be provided in accordance with Section 427.6.1 through 427.6.3.
427.6.1 Sprinkler system.
Laboratory units shall be provided throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. The entire building shall be provided throughout with an automatic sprinkler system when the aggregate floor area of all laboratory units within any building exceeds 20,000 square feet (1858 m 2 ).
427.6.2 Standpipe and hose system.
In all nonproduction laboratory buildings that are two or more stories above or below the grade level (level of exit discharge), standpipes shall be installed in accordance with Section 905.2.
427.6.3 Fire alarm system.
A manual fire alarm system shall be installed in accordance with Section 907.2.2, 907.2.3, or 907.2.6, as applicable.
427.7 Quantity limitations.
Quantity limitations in nonproduction laboratories shall be provided in accordance with Section 427.7.1 through 427.7.10.
427.7.1 Flammable and combustible liquids.
The density and total quantity of flammable and combustible liquids allowed within a laboratory unit, outside of storage rooms, shall comply with Table 9.1.1(A) of NFPA 45, as modified by the New York City Fire Code, for laboratory unit fire hazard Class D.
Exceptions: The following exceptions apply to other than educational or instructional laboratories:
1. The density of flammable and combustible liquids allowed within a laboratory unit may be increased to those set forth in Table 9.1.1(A) of NFPA 45, as modified by the New York City Fire Code, for laboratory unit fire hazard Class B provided the total quantity of flammable and combustible liquid, including any in storage cabinets or safety cans, does not exceed 25 gallons (95 L).
2. The density of flammable and combustible liquids allowed within a laboratory unit may be increased to those set forth in Table 9.1.1(A) of NFPA 45, as modified by the New York City Fire Code, for laboratory unit fire hazard Class B provided the total quantity of flammable and combustible liquid, including any in storage cabinets or safety cans, does not exceed 30 gallons (114 L) and the walls, floors and ceilings of the laboratory unit are separated from all adjoining areas by 2-hour fire- rated construction.
3. Based on a density of 1 gallon per 100 square feet (3.7 85 L per 9.3 m 2 ) of area, the quantity of flammable and combustible liquid allowed within a laboratory unit, excluding quantities in storage cabinets or safety cans, may be increased to 100 gallons (379 L), and the total quantities of flammable and combustible liquids, including quantities in storage cabinets or safety cans, may be increased to 200 gallons (757 L) provided the walls, floors and ceilings of the laboratory unit are separated from all adjoining areas by 2-hour fire- rated construction.
427.7.2 Flammable solids.
The total quantity of flammable solids allowed within a laboratory unit, excluding any quantities in a storage room, shall not exceed 10 pounds (4.5 kg).
Exception: The total quantity of flammable solids allowed within a laboratory unit that is provided with walls, floors and ceilings that separate the laboratory unit from all adjoining areas by 2-hour fire-rated construction shall not exceed 15 pounds (6.8 kg).
427.7.3 Oxidizers and organic peroxides.
The total quantity of solid and liquid oxidizers and organic peroxides combined allowed within a laboratory unit, excluding any quantities in a storage room, shall not exceed 40 pounds (18 kg), provided not more than 2 pounds (0.908 kg) of which are Class 3 oxidizers and 1 pound (0.454 kg) of which is Class I organic peroxides.
Exception: The total quantity of solid and liquid oxidizers and organic peroxides combined allowed within a laboratory unit that is provided with walls, floors and ceilings that separate the laboratory unit from all adjoining areas by 2-hour fire-rated construction shall not exceed 50 pounds (23 kg), provided not more than 2 pounds (0.908 kg) of which are Class 3 oxidizers and 1 pound (0.454 kg) of which are Class I organic peroxides.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
427.7.4 Unstable (reactive).
The total quantity of unstable (reactive) material allowed within a laboratory unit, excluding any quantities in a storage room, shall not exceed 6 pounds (2.7 kg), provided not more than 1 pound (0.454 kg) of which is Class 3 unstable (reactive).
Exception: The total quantity of unstable (reactive) material allowed within a laboratory unit that is provided with walls, floors and ceilings that separate the laboratory unit from all adjoining areas by 2-hour fire-rated construction shall not exceed 12 pounds (5.4 kg), provided not more than 1 pound (0.454 kg) of which is Class 3 unstable (reactive).
427.7.5 Water reactive material.
The total quantity of water reactive material allowed within a laboratory unit, excluding any quantities in a storage room, shall not exceed 2.5 pounds (1.1 kg).
Exception: The total quantity of water-reactive material allowed within a laboratory unit that is provided with walls, floors and ceilings that separate the laboratory unit from all adjoining areas by 2-hour fire-rated construction shall not exceed 5 pounds (2.3 kg).
427.7.6 Pyrophoric material.
The total quantity of solid or liquid pyrophoric material allowed within a laboratory unit, excluding any quantities in a storage room, shall not exceed 0.5 pounds (0.227 kg).
Exception: The total quantity of pyrophoric material allowed within a laboratory unit that is provided with walls, floors and ceilings that separate the laboratory unit from all adjoining areas by 2-hour fire-rated construction shall not exceed 1 pound (0.454 kg).
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
427.7.7 Highly toxic material.
The total quantity of solid or liquid highly toxic material allowed within a laboratory unit, excluding any quantities in a storage room, shall not exceed 5 pounds (2.27 kg).
427.7.8 Toxic material.
The total quantity of solid or liquid toxic material allowed within a laboratory unit, excluding any quantities in a storage room, shall not exceed 250 pounds (113.4 kg).
427.7.9 Corrosive material.
The total quantity of solid or liquid corrosive material allowed within a laboratory unit, excluding any quantity in a storage room, shall not exceed 250 gallons (946 L).
427.7.10 Hazardous gases.
The storage, handling and use of hazardous gases, including highly toxic, toxic, corrosive, and asphyxiant gases, within a laboratory unit shall be in accordance the New York City Fire Code, including quantities permitted and oxygen sensors.
427.8 Storage room classification.
Storage rooms for laboratory chemicals accessory to a laboratory unit shall be classified as Occupancy Group S-1 provided they comply with the provisions of Section 427.9. Storage rooms not in compliance with the provisions of Section 427.9 for laboratory chemical quantity limitations shall be classified as a Group H occupancy.
427.9 Storage rooms.
In addition to the quantities allowed within a laboratory unit by Section 427.7, laboratory chemicals that are accessory to a laboratory unit may be stored, whether outside of or entirely within a laboratory unit, in dedicated storage rooms complying with all of the following:
1. Storage room capacity shall be limited to a maximum of 300 gallons (1136 L) of laboratory chemicals, not to exceed 5 gallons per square foot (0.125 L/m 2 ) of floor area.
2. Flammable gas storage rooms shall be limited to 2,500 standard cubic feet (71 standard cubic m) of flammable gas.
3. Storage rooms shall be enclosed by a minimum of 2-hour rated fire barriers.
4. Storage rooms shall be equipped with a continuously operated ventilation system that provides at least 6 changes of air per hour and vents to the outdoors.
5. Each entrance to the storage room shall be provided with a minimum 1 1/2-hour rated self-closing fire door.
6. Each entrance to the storage room shall be provided with a sill at the doorway, except that no sill shall be required in storage rooms containing only flammable gases.
7. Storage rooms shall be equipped with an automatic sprinkler system providing at least one sprinkler for each 90 square feet (8.4 m 2 ) or portion thereof.
8. Laboratory chemicals that are incompatible with each other shall not be stored in the same storage room unless in compliance with the New York City Fire Code for separation of incompatible materials.
9. Storage rooms shall not open directly to an exit or any enclosed exit access component.
10. The floor of any storage room storing flammable gases shall be located at or above grade.
427.10 Ventilation.
Nonproduction laboratories shall be ventilated in accordance with Section 408 of the New York City Mechanical Code.
Section BC 428. Uses and Occupancies Involving Radioactive Materials and Radiation-Producing Equipment
428.1 Scope.
This section shall apply to the construction, alteration, and use of buildings or spaces for radioactive materials and radiation-producing equipment.
428.2 City, state and federal regulations.
In addition to the requirements of this section, occupancies involving radioactive materials and radiation-producing equipment shall also comply with applicable requirements of the New York City Health Code, and applicable state and federal regulations.
428.3 Laboratories.
All laboratories utilizing radioactive materials or radiation-producing equipment required to register under the requirements of the New York City Health Code shall comply with the requirements of Sections 428.3.1 through 428.3.7.
428.3.1 Construction.
All buildings in which such laboratories occur shall be of Type I or II construction.
428.3.2 Floors.
All floors shall comply with the fire resistance requirements for the class of construction, and provide the degree of radioactive resistance required by applicable city, state, and federal regulations. A finished material shall be applied to provide a continuous nonporous surface, which may be readily removed.
4285.3.3 Interior finish.
All insulation of acoustical treatments and interior partitions shall be of noncombustible material. Walls and ceilings shall have nonporous finishes of Class A rating.
428.3.4 Sprinkler protection.
Automatic sprinkler protection complying with the construction provisions of Chapter 9 of the New York City Building Code shall be provided, and such protection shall be designed for the type of combustible materials wherever such material is used, and for the radioactive material that may be expected to melt, vaporize, or oxidize under fire conditions. Laboratory equipment susceptible to damage from water or other materials used in the sprinkler system may be shielded by hoods except when the equipment provides a source of combustion. Where sprinkler protection uses water, or small water-spray installations are used to fight small isolated fires, floors shall be provided with drainage so that water may be carried to retention tanks for later disposal as required by the New York City Health Code when contamination of the water is to be anticipated.
428.3.5 Electrical controls.
Electrical controls and equipment shall be installed in accordance with the requirements of the New York City Electrical Code.
428.3.6 Ventilation.
Exhaust air from areas in which radioactive materials are used or stored shall be exhausted to the outdoors in such manner as not to create a health hazard, and shall not be recirculated to other areas of the building. Air pressure in rooms in which radioactive materials are used or stored shall be maintained below the air pressure of adjoining rooms, so that there is no flow of radioactive gases or dusts into adjoining rooms.
428.3.6.1 Ducts.
Ducts shall be of sheet steel of not less than No. 16 manufacturers' standard gauge or of other equivalent noncombustible material having a melting point above 1800°F (982°C). Exhaust ducts within the building, on the discharge side of the fan, shall be welded airtight. Exhaust ducts within the building, on the suction side of the fan, shall have laps in the direction of airflow with smoke-tight joints, and shall be subjected to a smoke test in accordance with the requirements for chimneys in the New York City Mechanical Code. Access hatches with tight-closing covers shall be provided for cleaning and for fire-fighting in the exhaust system ducts.
428.3.6.2 Fume hoods.
Fume hoods shall be exhausted to the outdoors. Controls for hood fans shall be interlocked so that contaminated air cannot be drawn into any space from a hood where the exhaust fan is not in operation.
428.3.6.3 Fans.
Fan equipment other than the impeller and impeller housing shall be located outside the exhaust stream.
428.3.6.4 Exhaust.
When the degree of contamination of the exhaust stream exceeds the concentration limits permitted by the health code, the duct system shall be equipped with devices to decontaminate the air to a safe level before discharging to the outdoor air.
428.3.7 Plumbing.
Drainage lines from sinks used for radioactive wastes shall be without traps, and shall lead to retention tanks when required by the provisions of the New York City Health Code.
428.4 Radiation machines.
Radiation machines or particle accelerators, linear accelerators, cyclotrons, synchrotons, betatrons, or bevatrons shall be located only in buildings of Type I or II construction; however, this requirement shall not apply to conventional medical, dental, research, or industrial x-ray machines of less than one million-volt capacity.
428.5 Storage.
Radioactive materials shall be stored in sealed containers. When required by the commissioner to avoid too concentrated an exposure within any one space, radioactive materials shall be stored in vaults designed in accordance with the radiation shielding or other requirements for the materials to be stored, and with the requirements of Sections 428.5.1 through 428.5.3.
428.5.1 Fire protection.
When any materials are subject to melting, vaporization, or oxidation under fire conditions, the storage vaults shall be constructed of walls having a fire-resistance rating of at least 4 hours, and the vaults shall be equipped with automatic sprinklers complying with the construction requirements of Chapter 9 and shall be vented through devices to decontaminate the air to a safe level.
428.5.2 Doors.
Doors opening into storage vaults shall meet shielding requirements and have a fire-protection rating of not less than 3 hours.
428.5.3 Bins, shelving, partitions and pallets.
All bins, shelving, partitions, and pallets in storage vaults shall be of noncombustible materials. Other methods of storage permitted by the health department or applicable state and federal regulations, such as storage under water, may be used.
Section BC 501. General
501.1 Scope.
The provisions of this chapter control the height and area of structures hereafter erected and additions to existing structures, including separation of occupancies.
501.2 Address identification.
Buildings shall be provided with address numbers or letters in accordance with section 3-505 of the Administrative Code and the rules issued thereunder by the borough president of the borough in which the property is located. Except as otherwise provided by the rules of the borough president in which the property is located, characters shall be a minimum 4 inches (102 mm) high and a minimum of 0.5 inch (12.7 mm) wide. They shall be installed on a contrasting background and be plainly visible from the street or road fronting the property. Where access is by means of a private road and the building address cannot be viewed from the public way, an appropriately placed monument, pole or sign or any other means authorized by the borough president of the borough in which the property is located shall be used to identify the structure.
501.3 Fire Department access.
Access shall be provided to the Fire Department in accordance with Sections 501.3.1 and 501.3.2.
501.3.1 Frontage.
Every building, exclusive of accessory buildings, shall have at least 8 percent of the total perimeter of the building adjoining a street or frontage space. For the purposes of this section, building perimeter shall be measured at that story having the maximum enclosed floor area; and buildings provided with a front yard or front setback no deeper than 30 feet (9144 mm) in compliance with the New York City Zoning Resolution shall be considered as adjoining the street or frontage space.
501.3.2 Building access.
Provisions shall be made for access by the Fire Department to every building in accordance with the New York City Fire Code and Section 903.2.11.1 of this code. In addition, multiple dwellings shall comply with Section 54 of the New York State Multiple Dwelling Law, as applicable.
Section BC 502. Definitions
502.1 Definitions.
The following terms are defined in Chapter 2:
AREA, BUILDING.
BASEMENT.
CELLAR.
COMBINED HEAT AND POWER SYSTEMS.
EQUIPMENT PLATFORM.
FIRE LANE.
FRONTAGE SPACE.
GRADE PLANE.
HEIGHT, BUILDING.
MEZZANINE.
STORY.
STORY ABOVE GRADE PLANE.
Section BC 503. General Building Height and Area Limitations
503.1 General.
Unless otherwise specifically modified in Chapter 4, building height, number of stories and building area shall not exceed the limits specified in Sections 504 and 506, based on the type of construction as determined by Section 602, and the occupancies as determined by Section 302, except as modified hereafter in this chapter. Building height, number of stories and building area provisions shall be applied independently. Each portion of a building separated by one or more fire walls complying with Section 706 shall be considered to be a separate building.
503.1.1 Special industrial occupancies.
Buildings and structures of Type I and II construction designed to house special industrial processes that require large areas and unusual building heights to accommodate craneways or special machinery and equipment, including, among others, rolling mills; structural metal fabrication shops and foundries; or the production and distribution of electric, gas or steam power, shall be exempt from the building height, number of stories and building area limitations specified in Sections 504 and 506. Mezzanines within such buildings or structures shall comply with Section 505.2. Documents and plans describing the special industrial processes shall be submitted to the commissioner for approval.
503.1.2 Buildings on the same tax lot.
Two or more buildings on the same tax lot and under the same ownership and control shall be regulated as separate buildings, or, at the option of the owner, shall be considered as portions of one building where the building height, number of stories of each building and the aggregate building area of the combined buildings are within the limitations specified in Sections 504 and 506. The provisions of this code applicable to the aggregate building shall be applicable to each building.
503.1.3 Type I construction.
Buildings of Type I construction permitted to be of unlimited tabular building heights and areas are not subject to the special requirements that allow unlimited area buildings in Section 507 or unlimited building height in Sections 503.1.1 and 504.3 or increased building heights and areas for other types of construction.
Section BC 504. Building Height and Number of Stories
504.1 General.
The height, in feet, and the number of stories of a building shall be determined based on the type of construction, occupancy classification and whether there is an automatic sprinkler system installed throughout the building.
Exception: The building height of one-story aircraft hangars, aircraft paint hangars and buildings used for the manufacturing of aircraft shall not be limited where the building is provided with an automatic sprinkler system or automatic fire-extinguishing system in accordance with Chapter 9 and is entirely surrounded by public ways or yards not less in width than one and one-half times the building height.
504.1.1 Unlimited area buildings.
The height of unlimited area buildings shall be designed in accordance with Section 507.
504.1.2 Special provisions.
The special provisions of Section 510 permit the use of special conditions that are exempt from, or modify, the specific requirements of this chapter regarding the allowable heights of buildings based on the occupancy classification and type of construction, provided the special condition complies with the provisions specified in Section 510.
504.2 Mixed occupancy.
In a building containing mixed occupancies in accordance with Section 508, no individual occupancy shall exceed the height and number of story limits specified in Section 504 for the applicable occupancies.
504.3 Height in feet and number of stories.
The maximum height, in feet, of a building shall not exceed the limits specified in Table 504.3. The maximum number of stories of a building shall not exceed the limits specified in Table 504.4.
Exceptions:
1. Rooftop structures including but not limited to roof tanks and their supports, ventilating, air conditioning, combined heat and power systems and similar building service equipment, bulkheads, penthouses, greenhouses, chimneys, and parapet walls 4 feet (1219 mm) or less in height shall not be included in the building height of the building or considered an additional story unless the aggregate area of all such structures, exclusive of any solar thermal and solar (photovoltaic) collectors and/or panels and their supporting equipment, exceeds 33 1/3 percent of the area of the roof of the building upon which they are erected. Rooftop structures shall be constructed in accordance with Section 1510.
2. Solar thermal and solar electric (photovoltaic) collectors and/or panels and their supporting equipment that exceed 33 1/3 percent of the area of the roof of the building upon which they are erected shall not be included in the height of a building or considered an additional story.
3. Noncombustible steeples, minarets, spires, domes, cupolas and other similar architectural elements, not used for occupancy or storage, shall not be included in the building height of the building or considered an extra story, and may be unlimited in height.
Table 504.3 a Allowable Building Height in Feet above Grade Plane
Occupancy Classification See Footnotes Type of Construction Type I Type II Type III Type IV j Type V A B i A B A B HT A B A-1 NS b, c UL 160 65 55 65 55 65 50 40 S UL 420 85 75 85 75 85 70 60 A-2 NS b, c UL 160 65 55 65 55 65 50 40 S UL 420 85 75 85 75 85 70 60 A-3 NS b, c UL 160 65 55 65 55 65 50 40 S UL 420 85 75 85 75 85 70 60 A-4 NS b, c UL 160 65 55 65 55 65 50 40 S UL 420 85 75 85 75 85 70 60 A-5 NS b, c UL 160 65 55 65 55 65 50 40 S UL 420 85 75 85 75 85 70 60 B NS b, c UL 160 65 55 65 55 65 50 40 S UL 420 85 75 85 75 85 70 60 E NS b, c UL 160 65 55 65 55 65 50 40 S UL 420 85 75 85 75 85 70 60 F-1 NS b, c UL 160 65 55 65 55 65 50 40 S UL 180 85 75 85 75 85 70 60 F-2 NS b, c UL 160 65 55 65 55 65 50 40 S UL 420 85 75 85 75 85 70 60 H-1 S UL 160 65 55 65 55 65 50 NP H-2 f S UL 160 65 55 65 55 65 50 40 H-3 f S UL 160 65 55 65 55 65 50 40 H-4 S UL 180 85 75 85 75 85 70 60 H-5 S UL 160 65 55 65 55 65 50 40 I-1 S13D 60 60 60 NP 60 55 60 NP NP S13R S UL 420 85 85 75 85 NP NP I-2 S UL 180 85 55 65 55 65 50 NP I-3 S UL 180 85 75 85 75 85 70 NP I-4 NS b, c UL 160 65 55 65 55 65 50 40 S UL 420 85 75 85 75 85 70 60 M NS b, c UL 160 65 55 65 55 65 50 40 S UL 420 85 75 85 75 85 70 60 R-1 S13R 60 60 60 NP 60 NP 60 NP NP S UL 420 85 85 85 R-2 S13R 60 60 60 NP 60 60 60 NP NP S UL 420 85 85 75 85 R-3 NS b, c UL 160 65 55 65 55 65 50 g, h 40 g S13D 60 60 60 60 60 55 60 S13R 60 60 g, h 60 g S UL 420 85 75 85 75 85 70 g, h S-1 NS b, c UL 160 65 55 65 55 65 50 40 S UL 180 85 75 85 75 85 70 60 S-2 d, e NS b, c UL 160 65 55 65 55 65 50 40 S UL 420 85 75 85 75 85 70 60 U e NS b, c UL 160 65 55 65 55 65 50 40 S UL 180 85 75 85 75 85 70 60
= Not permitted in Fire District = Not permitted in Fire District without sprinklers
For SI: 1 foot = 304.8 mm.
Note: UL = Unlimited; NP = Not permitted; NS = Buildings not equipped throughout with an automatic sprinkler system; S = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3.
a. See the following sections for general exceptions to Table 504.3:
1. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter.
2. Section 506.3, Allowable area increase due to frontage.
3. Section 507, Unlimited area building.
b. See Section 903.2 for the minimum thresholds for protection by an automatic sprinkler system for specific occupancies.
c. The NS value is only for use in buildings not required by this code to be equipped throughout with an automatic sprinkler system.
d. For open parking structures, see Section 406.5.
e. For private garages, see Section 406.3.
f. See Section 415.8 for limitations.
g. See Exception 9 of Section D105.1 for allowances of Type VA and VB construction for R-3 occupancies.
h. See Exception 12 of Section D105.1 for allowances of Type VA construction and height limitations for R-3 occupancies in Lower Density Growth Management Areas.
i. See Section 403.2.1 for additional requirements for high-rise buildings.
j. Type IV construction utilizing cross-laminated timber or structural composite lumber shall be sprinklered where required by Section 903.2.13.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2011/020.
504.4 Number of stories.
The maximum number of stories of a building shall not exceed the limits specified in Table 504.4.
Table 504.4 a, b Allowable Number of Stories above Grade Plane
Occupancy Classification See Footnotes Type of Construction Type I Type II Type III Type IV i Type V A B A B A B HT A B A-1 NS b, c UL UL 6 3 6 3 6 3 2 S UL UL 7 4 7 4 7 4 3 A-2 NS b, c UL UL 6 3 6 3 6 3 2 S UL UL 7 4 7 4 7 4 3 A-3 NS b, c UL UL 6 3 6 3 6 3 2 S UL UL 7 4 7 4 7 4 3 A-4 NS b, c UL UL 6 3 6 3 6 3 2 S UL UL 7 4 7 4 7 4 3 A-5 NS b, c UL UL UL UL UL UL 6 UL UL S UL UL UL UL UL UL 7 UL UL B NS b, c UL UL 6 3 6 3 6 3 2 S UL UL 7 4 7 4 7 4 3 E NS b, c UL UL 4 3 4 3 6 3 2 S UL UL 5 4 5 4 7 4 3 F-1 NS b, c UL 6 5 3 5 2 5 3 2 S UL 7 6 4 6 3 6 4 3 F-2 NS b, c UL UL 6 3 6 3 6 3 2 S UL UL 7 4 7 4 7 4 3 H-1 S 1 1 1 1 1 1 1 1 NP H-2 f S UL 3 2 1 2 1 2 1 1 H-3 f S UL 6 4 2 4 2 4 2 1 H-4 S UL 8 6 4 6 4 6 4 3 H-5 S 3 3 3 3 3 3 3 3 2 I-1 S13D 6 6 6 NP 4 3 4 NP NP S13R UL UL 5 4 5 S UL UL 7 NP I-2 S UL 7 5 4 5 3 5 3 NP I-3 S UL 5 5 4 5 3 5 4 NP I-4 NS b, c UL UL 3 3 3 3 3 2 2 S UL UL 4 4 4 4 4 3 3 M NS b, c UL UL 6 3 6 3 6 3 2 S UL UL 7 4 7 4 7 4 3 R-1 S13R 6 6 6 NP 6 NP 6 NP NP S UL UL 7 NP 7 NP 7 NP NP R-2 S13R 6 6 6 NP 6 4 6 NP NP S UL UL 7 NP 7 7 NP NP R-3 NS b, c X X X X X X X 3 g, h 3 g S13D 6 6 6 3 6 3 6 S13R 4 4 4 g, h 4 g S UL UL 7 7 7 S-1 NS b, c UL 6 5 3 4 3 4 3 2 S UL 7 6 4 5 4 5 4 3 S-2 d, e NS b, c UL UL 6 3 6 4 6 3 2 S UL UL 7 4 7 5 7 4 3 U e NS b, c UL 5 4 2 3 2 4 2 1 S UL 6 5 3 4 3 5 3 2
= Not permitted in Fire District = Not permitted in Fire District without sprinklers X = Number of stories in nonsprinklered 1- & 2-family buildings shall be limited by Section 903.2.8
Note: UL = Unlimited; NP = Not Permitted; NS = Buildings not equipped throughout with an automatic sprinkler system; S = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3.
a. See the following sections for general exceptions to Table 504.4.
1. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter.
2. Section 506.3, Allowable area increase due to frontage.
3. Section 507, Unlimited area building.
b. See Section 903.2 for the minimum thresholds for protection by an automatic sprinkler system for specific occupancies.
c. The NS value is only for use in buildings not required by this code to be equipped throughout with an automatic sprinkler system.
d. For open parking structures, see Section 406.5.
e. For private garages, see Section 406.3.
f. See Section 415.8 for limitations.
g. See Exception 9 of Section D105.1 for allowances of Type VA and VB construction for R-3 occupancies.
h. See Exception 12 of Section D105.1 for allowances of Type VA construction and height limitations for R-3 occupancies in Lower Density Growth Management Areas.
i. Type IV construction utilizing cross-laminated timber or structural composite lumber shall be sprinklered where required by Section 903.2.13.
Section BC 505. Mezzanines and Equipment Platforms
505.1 General.
Mezzanines shall comply with Section 505.2. Equipment platforms shall comply with Section 505.3.
505.2 Mezzanines.
A mezzanine or mezzanines in compliance with Section 505.2 shall be considered a portion of the story below. Such mezzanines shall not contribute to either the building area or number of stories as regulated by Section 503.1. The area of the mezzanine shall be included in determining the fire area. The clear height above and below the mezzanine floor construction shall be not less than 7 feet (2134 mm).
Exception: The clear height of habitable spaces above or below mezzanines within dwelling units shall be not less than 8 feet (2438 mm).
505.2.1 Area limitation.
The aggregate area of a mezzanine or mezzanines within a room or space shall be not greater than one-third of the floor area of that room or space in which they are located. The enclosed portions of a room or space shall not be included in determining the permissible floor area of the mezzanine. In determining the allowable mezzanine area, the area of the mezzanine shall not be included in the floor area of the room in which it is contained.
Where a room contains both a mezzanine and an equipment platform, the aggregate area of the two raised floor levels shall be not greater than two-thirds of the floor area of that room or space in which they are located.
Exceptions:
1. The aggregate area of mezzanines in buildings and structures of Type I or II construction for special industrial occupancies in accordance with Section 503.1.1 shall be not greater than two-thirds of the area of the room in which the mezzanines are located.
2. The aggregate area of a mezzanine or mezzanines within a dwelling unit shall not exceed one-third of the net floor area of such dwelling unit, whether or not portions of such dwelling unit are enclosed. The area of the mezzanine shall not contribute to the determination of the floor area of the dwelling unit in which it is contained.
505.2.2 Means of egress.
Each occupant of a mezzanine shall have access to at least two independent means of egress where the common path of egress travel exceeds the limitations of Section 1006.2. Where a stairway provides a means of exit access from a mezzanine, the maximum travel distance includes the distance traveled on the stairway measured in the plane of the tread nosing. Accessible means of egress shall be provided in accordance with Section 1009.
Exception: A single means of egress shall be permitted in accordance with Section 1006.2.
505.2.3 Openness.
A mezzanine shall be open and unobstructed to the room in which such mezzanine is located except for walls or railings not more than 42 inches (1067 mm) in height, columns and posts.
Exceptions:
1. Mezzanines or portions thereof are not required to be open to the room in which the mezzanines are located, provided that the occupant load of the aggregate area of the enclosed space is not greater than 10.
2. A mezzanine having two or more means of egress is not required to be open to the room in which the mezzanine is located, if at least one of the means of egress provides direct access to an exit located on the mezzanine level.
3. Mezzanines or portions thereof are not required to be open to the room in which the mezzanines are located, provided that the aggregate floor area of the enclosed space is not greater than 10 percent of the mezzanine area.
4. In industrial facilities, mezzanines used for control equipment are permitted to be glazed on all sides.
5. A mezzanine having two or more means of egress shall not be required to be open to the room in which the mezzanine is located in occupancies, other than Groups H and I, that comply with Items 5.1 through 5.4.
5.1. Such occupancy is no more than two stories above grade plane,
5.2. Such occupancy is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1,
5.3. An approved fire alarm system is installed throughout the entire building or structure in which such occupancy is located, and
5.4. Notification appliances are installed throughout the mezzanine in accordance with NFPA 72.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
505.3 Equipment platforms.
Equipment platforms in buildings shall not be considered as a portion of the floor below. Such equipment platforms shall not contribute to either the building area or the number of stories as regulated by Section 503.1. The area of the equipment platform shall not be included in determining the fire area in accordance with Section 903. Equipment platforms shall not be a part of any mezzanine and such platforms and the walkways, stairways, alternating tread devices and ladders providing access to an equipment platform shall not serve as a part of the means of egress from the building.
505.3.1 Area limitation.
The aggregate area of all industrial equipment platforms within a room shall be not greater than two-thirds of the area of the room in which they occur. Where an equipment platform is located in the same room as a mezzanine, the area of the mezzanine shall be determined by Section 505.2.1 and the combined aggregate area of the equipment platforms and mezzanines shall be not greater than two-thirds of the room in which they are located.
505.3.2 Fire suppression.
Where located in a building that is required to be protected by an automatic sprinkler system, equipment platforms shall be fully protected by sprinklers above and below the platform, where required by the standards referenced in Section 903.3.
505.3.3 Guards.
Equipment platforms shall have guards where required by Section 1015.2.
Section BC 506. Building Area Modifications
506.1 General.
The floor area of a building shall be determined based on the type of construction, occupancy classification, whether there is an automatic sprinkler system installed throughout the building and the amount of building frontage on public way or open space.
506.1.1 Unlimited area buildings.
Unlimited area buildings shall be designed in accordance with Section 507.
506.1.2 Special provisions.
The special provisions of Section 510 permit the use of special conditions that are exempt from, or modify, the specific requirements of this chapter regarding the allowable areas of buildings based on the occupancy classification and type of construction, provided the special condition complies with the provisions specified in Section 510.
506.1.3 Basement and cellar.
A single basement or cellar need not be included in the total allowable building area, provided such basement or cellar does not exceed the area permitted for a building with no more than one story above grade plane.
506.2 Allowable area determination.
The allowable area of a building shall be determined in accordance with the applicable provisions of Sections 506.2.1 through 506.2.4, and Section 506.3.
Table 506.2 a Allowable Area Factor ( A t = NS, S1, S13D, S13R, or SM, as applicable) in Square Feet
Occupancy Classification See Footnotes Type of Construction Type I Type II Type III Type IV i Type V A B A B A B HT A B A-1 NS b, c UL UL 17,500 10,500 14,700 5,600 15,000 8,400 5,500 S1 UL UL 52,500 31,500 44,100 16,800 45,000 25,200 16,500 SM UL UL 35,000 21,000 29,400 11,200 30,000 16,800 11,000 A-2 NS b, c UL UL 17,500 9,500 14,000 5,600 15,000 8,400 5,500 S1 UL UL 52,500 28,500 42,000 16,800 45,000 25,200 16,500 SM UL UL 35,000 19,000 28,000 11,200 30,000 16,800 11,000 A-3 NS b, c UL UL 17,500 9,500 14,000 5,600 15,000 8,400 5,500 S1 UL UL 52,500 28,500 42,000 16,800 45,000 25,200 16,500 SM UL UL 35,000 19,000 28,000 11,200 30,000 16,800 11,000 A-4 NS b, c UL UL 17,500 9,500 14,000 5,600 15,000 8,400 5,500 S1 UL UL 52,500 28,500 42,000 16,800 45000 25,200 16,500 SM UL UL 35,000 19,000 28,000 11,200 30,000 16,800 11,000 A-5 NS b, c UL UL UL UL UL UL UL UL UL S1 SM B NS b, c UL UL 37,500 10,500 28,500 5,600 36,000 8,400 5,500 S1 UL UL 112,500 31,500 85,500 16,800 108,000 25,200 16,500 SM UL UL 75,000 21,000 57,000 11,200 72,000 16,800 11,000 E NS b, c UL UL 26,000 10,500 23,500 5,600 25,500 8,400 5,500 S1 UL UL 78,000 31,500 70,500 16,800 76,500 25,200 16,500 SM UL UL 52,000 21,000 47,000 11,200 51,000 16,800 11,000 F-1 NS b, c UL UL 12,500 7,500 7,500 3,000 10,000 3,000 1,000 S1 UL UL 37,500 22,500 22,500 9,000 30,000 9,000 3,000 SM UL UL 25,000 15,000 15,000 6,000 20,000 6,000 2,000 F-2 NS b, c UL UL 37,500 10,500 28,500 5,600 30,000 8,400 5,500 S1 UL UL 112,500 31,500 85,500 16,800 90,000 25,200 16,500 SM UL UL 75,000 21,000 57,000 11,200 60,000 16,800 11,000 H-1 NS b, c 21,000 16,500 11,000 7,500 9,500 7,000 10,500 7,500 NP S1 H-2 f NS b, c 21,000 16,500 11,000 7,500 9,500 7,000 10,500 7,500 3,000 S1 SM H-3 f NS b, c UL 60,000 26,500 14,000 17,500 13,000 25,000 10,000 5,000 S1 SM H-4 NS b, c UL UL 37,500 17,500 28,500 17,500 36,000 18,000 6,500 S1 UL UL 112,500 52,500 85,500 52,500 108,000 54,000 19,500 SM UL UL 75,000 35,000 57,000 35,000 72,000 36,000 13,000 H-5 NS b, c UL UL 37,500 23,000 28,500 19,000 36,000 18,000 9,000 S1 UL UL 112,500 69,000 85,500 57,000 108,000 54,000 27,000 SM UL UL 75,000 46,000 57,000 38,000 72,000 36,000 18,000 I-1 NS b, c UL UL 19,000 NP 16,500 5,600 18,000 NP NP S13D UL UL 19,000 NP 16,500 5,600 18,000 NP NP S1 UL UL 57,000 49,500 16,800 54,000 NP NP SM UL UL 38,000 NP 33,000 11,200 36,000 NP NP I-2 NS b, c UL UL 7,000 3,500 5,000 1,200 6,500 2,000 NP S1 UL UL 21,000 10,500 15,000 3,600 19,500 6,000 NP SM UL UL 14,000 7,000 10,000 2,400 13,000 4,000 NP I-3 NS b, c UL UL 7,000 3,500 5,000 1,200 6,500 2,000 NP S1 UL UL 21,000 10,500 15,000 3,600 19,500 6,000 NP SM UL UL 14,000 7,000 10,000 2,400 13,000 4,000 NP I-4 NS b, c UL UL 26,500 9,500 23,500 5,600 25,500 8,400 5,500 S1 UL UL 79,500 28,500 70,500 16,800 76,500 25,200 16,500 SM UL UL 53,000 19,000 47,000 11,200 51,000 16,800 11,000 M NS b, c UL UL 21,500 7,500 18,500 5,600 14,000 8,400 5,500 S1 UL UL 64,500 22,500 55,500 16,800 42,000 25,200 16,500 SM UL UL 43,000 15,000 37,000 11,200 28,000 16,800 11,000 R-1 NS b, c UL UL UL NP 24,000 NP 20,500 NP NP S13R S1 UL UL UL NP 72,000 NP 61,500 NP NP SM UL UL UL NP 48,000 NP 41,000 NP NP R-2 NS b, c UL UL UL NP 24,000 5,600 20,500 NP NP S13R S1 UL UL UL NP 72,000 16,800 61,500 NP NP SM UL UL UL NP 48,000 11,200 41,000 NP NP R-3 NS b, c UL UL 17,500 10,500 14,700 5,600 30,000 8,400 g, h 5,500 g S13D 5,600 S13R S1 UL UL 52,500 31,500 44,100 16,800 90,000 8,400 g, h 5,500 g SM UL UL 35,000 21,000 29,400 11,200 60,000 S-1 NS b, c UL 48,000 12,000 7,500 7,500 7,500 7,500 5,000 1,000 S1 UL 144,000 36,000 22,500 22,500 22,500 22,500 15,000 3,000 SM UL 96,000 24,000 15,000 15,000 15,000 15,000 10,000 2,000 S-2 d, e NS b, c UL UL 15,000 10,000 10,000 8,500 10,000 8,400 5,500 S1 UL UL 45,000 30,000 30,000 25,500 30,000 25,200 16,500 SM UL UL 30,000 20,000 20,000 17,000 20,000 16,800 11,000 U e NS b, c UL 35,000 19,000 8,500 14,000 8,500 18,000 9,000 5,500 S1 UL 105,000 57,000 25,500 42,000 25,500 54,000 27,000 16,500 SM UL 70,000 38,000 17,000 28,000 17,000 36,000 18,000 11,000
= Not permitted in Fire District = Not permitted in Fire District without sprinklers
Note: UL = Unlimited; NP = Not permitted.
For SI: 1 square foot = 0.0929 m 2 .
NS = Buildings not equipped throughout with an automatic sprinkler system; S1 = Buildings a maximum of one story above grade plane equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; SM = Buildings two or more stories above grade plane equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3.
a. See the following sections for general exceptions to Table 506.2.
1. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter.
2. Section 506.3, Allowable area increase due to frontage.
3. Section 507, Unlimited area building.
b. See Section 903.2 for the minimum thresholds for protection by an automatic sprinkler system for specific occupancies.
c. The NS value is only for use in buildings not required by this code to be equipped throughout with an automatic sprinkler system.
d. For open parking structures, see Section 406.5.
e. For private garages, see Section 406.3.
f. See Section 415.8 for limitations.
g. See Exception 9 of Section D105.1 for allowances of Type VA and VB construction for R-3 occupancies.
h. See Exception 12 of Section D105.1 for allowances of Type VA construction for R-3 occupancies in Lower Density Growth Management Areas.
i. Type IV construction utilizing cross-laminated timber or structural composite lumber shall be sprinklered where required by Section 903.2.13.
506.2.1 Single-occupancy, one-story buildings.
The allowable area of a single-occupancy building with no more than one story above grade plane shall be determined in accordance with Equation 5-1:
A a = A t + (NS × I f ) (Equation 5-1)
where:
A a = Allowable area (square feet).
A t = Tabular allowable area factor (NS, S1, S13D or S13R value, as applicable) in accordance with Table 506.2.
NS = Tabular allowable area factor in accordance with Table 506.2 for nonsprinklered building (regardless of whether the building is sprinklered).
I f = Area increase factor due to frontage (percent) as calculated in accordance with Section 506.3.
506.2.2 Mixed-occupancy, one-story buildings.
The allowable area of a mixed-occupancy building with no more than one story above grade plane shall be determined in accordance with the applicable provisions of Section 508.1 based on Equation 5-1 for each applicable occupancy.
506.2.2.1 Group H-2 or H-3 mixed occupancies.
For a building containing Group H-2 or H-3 occupancies, the allowable area shall be determined in accordance with Section 508.4.2, with the sprinkler system increase applicable only to the portions of the building not classified as Group H-2 or H-3.
506.2.3 Single-occupancy, multistory buildings.
The allowable area of a single-occupancy building with more than one story above grade plane shall be determined in accordance with Equation 5-2:
A a = [A t + (NS × I f )] × S a (Equation 5-2)
where:
A a = Allowable area (square feet).
A t = Tabular allowable area factor (NS, S13D, S13R or SM value, as applicable) in accordance with Table 506.2.
NS = Tabular allowable area factor in accordance with Table 506.2 for a nonsprinklered building (regardless of whether the building is sprinklered).
I f Area factor increase due to frontage (percent) as calculated in accordance with Section 506.3.
S a Actual number of building stories above grade plane, not to exceed three. For buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2, use the actual number of building stories above grade plane, not to exceed four.
No individual story shall exceed the allowable area (Aa) as determined by Equation 5-2 using the value of S a = 1.
506.2.4 Mixed-occupancy, multistory buildings.
Each story of a mixed-occupancy building with more than one story above grade plane shall individually comply with the applicable requirements of Section 508.1. For buildings with more than three stories above grade plane, the total building area shall be such that the aggregate sum of the ratios of the actual area of each story divided by the allowable area of such stories, determined in accordance with Equation 5-3 based on the applicable provisions of Section 508.1, shall not exceed three.
A a = [A t + (NS × I f )] (Equation 5-3)
where:
A a = Allowable area (square feet).
A t = Tabular allowable area factor (NS, S13D, S13R or SM value, as applicable) in accordance with Table 506.2.
NS = Tabular allowable area factor in accordance with Table 506.2 for a nonsprinklered building (regardless of whether the building is sprinklered).
I f = Area factor increase due to frontage (percent) as calculated in accordance with Section 506.3.
Exception: For buildings designed as separated occupancies under Section 508.4 and equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2, the total building area shall be such that the aggregate sum of the ratios of the actual area of each story divided by the allowable area of such stories determined in accordance with Equation 5-3 based on the applicable provisions of Section 508.1, shall not exceed four.
506.2.4.1 Group H-2 or H-3 mixed occupancies.
For a building containing Group H-2 or H-3 occupancies, the allowable area shall be determined in accordance with Section 508.4.2, with the sprinkler system increase applicable only to the portions of the building not classified as Group H-2 or H-3.
506.3 Frontage increase.
Area factor increase shall be determined in accordance with Sections 506.3.1 through 506.3.3.
506.3.1 Minimum percentage of perimeter.
To qualify for an area factor increase based on frontage, a building shall have not less than 25 percent of its perimeter on a public way or open space. Such open space shall be either on the same zoning lot or dedicated for public use and shall be accessed from a street or approved fire lane.
506.3.2 Minimum frontage distance.
To qualify for an area factor increase based on frontage, the public way or open space adjacent to the building perimeter shall have a minimum distance (W) of 20 feet (6096 mm) measured at right angles from the building face to any of the following:
1. The closest interior tax lot line.
2. The entire width of a street, alley or public way.
3. The exterior face of an adjacent building on the same tax lot.
Where the value of W is greater than 30 feet (9144 mm), a value of 30 feet (9144 mm) shall be used in calculating the building area increase based on frontage, regardless of the actual width of the public way or open space. Where the value of W varies along the perimeter of the building, the calculation performed in accordance with Equation 5-5 shall be based on the weighted average calculated in accordance with Equation 5-4.
W = (L 1 × w 1 + L 2 × w 2 + L 3 × w 3 …)/F (Equation 5-4)
where:
W = (Width: weighted average) = Calculated width of public way or open space (feet).
L n = Length of a portion of the exterior perimeter wall.
w n = Width (³ 20 feet) of a public way or open space associated with that portion of the exterior perimeter wall.
F = Building perimeter that fronts on a public way or open space having a width of 20 feet (6096 mm) or more.
Exception: Where a building meets the requirements of Section 507, as applicable, except for compliance with the minimum 60-foot (18 288 mm) public way or yard requirement, and the value of W is greater than 30 feet (9144 mm), the value of W shall not exceed 60 feet (18 288 mm).
506.3.3 Amount of increase.
The area factor increase based on frontage shall be determined in accordance with Equation 5-5:
I f = (F/P - 0.25) W/30 (Equation 5-5)
where:
I f = Area increase factor due to frontage.
F = Building perimeter that fronts on a public way or open space having minimum distance of 20 feet (6096 mm).
P = Perimeter of entire building (feet).
W = Width of public way or open space (feet) in accordance with Section 506.3.2.
Section BC 507. Unlimited Area Buildings
507.1 General.
The area of buildings of the occupancies and configurations specified in Sections 507.1 through 507.18 shall not be limited, except that only one cellar or one basement shall be permissible.
507.1.1 Accessory occupancies.
Accessory occupancies shall be permitted in unlimited area buildings in accordance with the provisions of Section 508.2, otherwise the requirements of Sections 507.3 through 507.18 shall be applied, where applicable.
507.2 Measurement of open spaces.
Where Sections 507.3 through 507.18 require buildings to be surrounded and adjoined by public ways and yards, those open spaces shall be determined as follows:
1. Yards shall be measured from the building perimeter in all directions to the closest interior lot lines or to the exterior face of an opposing building located on the same tax lot, as applicable.
2. Where the building fronts on a public way, the entire width of the public way shall be used.
507.2.1 Reduced open space.
The public ways or yards of 60 feet (18 288 mm) in width required in Sections 507.3, 507.4, 507.5 and 507.6 shall be permitted to be reduced to not less than 40 feet (12 192 mm) in width provided all of the following requirements are met:
1. The reduced width shall not be allowed for more than 75 percent of the perimeter of the building.
2. The exterior walls facing the reduced width shall have a fire-resistance rating of not less than 3 hours.
3. Openings in the exterior walls facing the reduced width shall have opening protectives with a fire protection rating of not less than 3 hours.
507.3 Nonsprinklered, one-story buildings.
The area of a Group F-2 or S-2 building no more than one story in height, of other than Type V construction, shall not be limited when the building is surrounded and adjoined on all sides by public ways or yards not less than 60 feet (18 288 mm) in width.
507.4 Sprinklered, one-story buildings.
The area of a Group A-4 building no more than one story in height above grade plane of other than Type V construction, or the area of a Group B, F, M or S building no more than one story in height of any construction type, shall not be limited where the building is provided with an automatic sprinkler system throughout in accordance with Section 903.3.1.1 and is surrounded and adjoined on all sides by public ways or yards not less than 60 feet (18 288 mm) in width.
Exceptions:
1. In Group F-2 and S-2 occupancies, one-story rack storage facilities of Type II construction that are not accessible to the public shall not be limited in height provided that such buildings conform to the requirements of the New York City Fire Code, and Sections 507.4 and 903.3.1.1 of this code.
2. The automatic sprinkler system shall not be required in areas occupied for indoor participant sports, such as tennis, skating, swimming and equestrian activities, in occupancies in Group A-4, provided that both of the following criteria are met:
2.1. Exit doors directly to the outside are provided for occupants of the participant sports areas.
2.2. The building is equipped with a fire alarm system with manual fire alarm boxes installed in accordance with Section 907.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2008/026.
507.4.1 Mixed occupancy buildings with Groups A-1 and A-2.
Group A-1 and A-2 occupancies of other than Type V construction shall be permitted within mixed occupancy buildings of unlimited area complying with Section 507.4, provided all of the following criteria are met:
1. Group A-1 and A-2 occupancies are separated from other occupancies as required for separated occupancies in Section 508.4.4 with no reduction allowed in the fire-resistance rating of the separation based upon the installation of an automatic sprinkler system.
2. Each area of the portions of the building used for Group A-1 or A-2 occupancies shall not exceed the maximum allowable area permitted for such occupancies in Section 503.1.
3. Exit doors from Group A-1 and A-2 occupancies shall discharge directly to the exterior of the building.
507.5 Sprinklered, two story buildings.
The area of a Group B, F, M or S building no more than two stories in height shall not be limited when the building is provided with an automatic sprinkler system in accordance with Section 903.3.1.1 throughout, and is surrounded and adjoined on all sides by public ways or yards not less than 60 feet (18 288 mm) in width.
507.6 Group A buildings.
The area of a Group A-1, A-2, A-3, or A-4 building of Type IIA, IIIA or IV construction shall not be limited where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. The area of a one-story, Group A-3 building used as a house of worship, community hall, dance hall, exhibition hall, gymnasium, lecture hall, indoor swimming pool or tennis court of Type IIB construction shall not be limited when all of the following criteria are met:
1. The building shall not have a stage other than a platform.
2. The building shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
3. The assembly floor shall be located at or within 21 inches (533 mm) of street or grade level and all exits are provided with ramps complying with Section 1012.1 to the street or grade level.
4. The building shall be surrounded and adjoined on all sides by public ways or yards not less than 60 feet (18 288 mm) in width.
507.7 Reserved.
507.8 Group H occupancies.
Group H-2, H-3 and H-4 fire occupancies shall be permitted in unlimited area buildings containing Group F or S occupancies in accordance with Sections 507.4 and 507.5 and the provisions of Sections 507.8.1 through 507.8.4.
507.8.1 Allowable area.
The aggregate floor area of Group H occupancies located in an unlimited area building shall not exceed 10 percent of the area of the building and shall not exceed the area limitations for the Group H occupancies as specified in Section 506 based on the perimeter of each Group H floor area that fronts on a public way or open space.
507.8.1.1 Located within the building.
The aggregate floor area of Group H occupancies not located at the perimeter of the building shall not exceed 25 percent of the area limitations for the Group H occupancies as specified in Section 506.
507.8.1.1.1 Liquid use, dispensing and mixing rooms.
Liquid use, dispensing and mixing rooms having a floor area of not more than 500 square feet (46.5 m 2 ) need not be located on the outer perimeter of the building where they are in accordance with the New York City Fire Code and NFPA 30.
507.8.1.1.2 Liquid storage rooms.
Liquid storage rooms having a floor area of not more than 1,000 square feet (93 m 2 ) need not be located on the outer perimeter where they are in accordance with the New York City Fire Code and NFPA 30.
507.8.1.1.3 Spray paint booths.
Spray paint booths that comply with the New York City Fire Code need not be located on the outer perimeter.
507.8.2 Located on building perimeter.
Except as provided for in Section 507.8.1.1, Group H occupancies shall be located on the perimeter of the building. In Group H-2 and H-3 occupancies, not less than 25 percent of the perimeter of such occupancies shall be an exterior wall.
507.8.3 Occupancy separations.
Group H occupancies shall be separated from the remainder of the unlimited area building and from each other in accordance with Table 508.4.
507.8.4 Height limitations.
For two-story, unlimited area buildings, Group H occupancies shall not be located more than one story above grade plane unless permitted based on the allowable height and number of stories and feet as set forth in Section 504 based on the type of construction of the unlimited area building.
507.9 Unlimited mixed occupancy buildings with Group H-5.
The area of a Group B, F, H-5, M or S building no more than two stories above grade plane shall not be limited where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, and is surrounded and adjoined by public ways or yards not less than 60 feet (18 288 mm) in width, provided all of the following criteria are met:
1. Buildings containing Group H-5 occupancy shall be of Type I or II construction.
2. Each area used for Group H-5 occupancy shall be separated from other occupancies as required in Sections 415.11 and 508.4.
3. Each area used for Group H-5 occupancy shall not exceed the maximum allowable area permitted for such occupancies in Section 503.1 including modifications of Section 506.
Exception: Where the Group H-5 occupancy exceeds the maximum allowable area, the Group H-5 shall be subdivided into areas that are separated by 2-hour fire barriers.
507.10 Aircraft paint hangar.
The area of a Group H-2 aircraft paint hangar no more than one story above grade plane shall not be limited where such aircraft paint hangar complies with the provisions of Section 412.6 and is surrounded and adjoined by public ways or yards not less in width than one and one-half times the building height.
507.11 Group E buildings.
The area of a Group E building of Type IIA, IIIA or IV construction shall not be limited where the building is protected throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1. The area of a one-story Group E building of Type IIB construction shall not be limited when the following criteria are met:
1. Each classroom shall have not less than two means of egress, with one of the means of egress being a direct exit to the outside of the building complying with Section 1022.
2. The building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
3. The building is surrounded and adjoined on all sides by public ways or yards not less than 60 feet (18 288 mm) in width.
507.12 Motion picture theaters.
In buildings of Type II, IIIA and IV construction, the area of a motion picture theater located on the first story above grade plane shall not be limited when the building is provided with an automatic sprinkler system throughout in accordance with Section 903.3.1.1 and is surrounded and adjoined on all sides by public ways or yards not less than 60 feet (18 288 mm) in width.
507.13 Covered and open mall buildings and anchor buildings.
The area of covered and open mall buildings and anchor buildings not exceeding three stories in height that comply with Section 402 shall not be limited
507.14 Group B buildings.
Notwithstanding the provisions of Sections 507.3 and 507.4, the area of a Group B building of Type IIA, IIIA or IV construction shall not be limited where the building is protected throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1.
507.15 Group F-2 buildings.
Notwithstanding the provisions of Sections 507.3 and 507.4, the area of a Group F-2 building of Type IIA, IIIA or IV construction shall not be limited where the building is protected throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1.
507.16 Group M buildings.
Notwithstanding the provisions of Sections 507.3 and 507.4, the area of a Group M building of Type IIA, IIIA or IV construction shall not be limited where the building is protected throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1.
507.17 Group R buildings.
The area of Group R-1 and R-2 buildings of Type IIA, IIIA or IV construction shall not be limited where the building is protected throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2, as applicable.
507.18 Group S-2 buildings.
Notwithstanding the provisions of Sections 507.3 and 507.4, the area of a Group S-2 building of Type IB, IIA, IIIA or IV construction shall not be limited where the building is protected throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1.
Section BC 508. Mixed Use and Occupancy
508.1 General.
Each portion of a building shall be individually classified in accordance with Section 302.1. Where a building contains more than one occupancy group, the building or portion thereof shall comply with the applicable provisions of Sections 508.2, 508.3 or 508.4, or a combination of these sections.
Exceptions:
1. Occupancies separated in accordance with Section 510.
2. Where required by Table 415.6.2, areas of Group H-1, H-2 and H-3 occupancies shall be located in a detached building or structure.
3. Where identified in Table 509, rooms or spaces shall be treated as incidental uses.
4. Where not identified in Table 509, mechanical and/or electrical equipment rooms shall be permitted to be classified as the occupancy within which they are located, or at the option of the applicant, classified as Group F-2 occupancy in accordance with Section 306.3.
5. Commercial kitchens classified as Group F-2 need not be separated by fire separations from adjoining dining spaces, provided that the conditions of Items 5.1, 5.2, and 5.3 are met:
5.1. The cooking equipment is vented directly to the outdoors;
5.2. A draft curtain of noncombustible material, at least 24 inches (609 mm) down from the ceiling, is provided to separate the opening between the cooking facilities and the dining spaces; and
5.3. A fire protection system is installed and located as set forth in Item 5.3.1 or 5.3.2.
5.3.1. A fire protection system in accordance with Sections 903 and 904 is installed within the cooking facilities. Additionally, sprinkler heads protecting the opening between the cooking facilities and the dining spaces shall be located within 24 inches (609 mm) of the curtain on the cooking facilities side; or
5.3.2. A fire protection system in accordance with Section 903 is located along any opening between the cooking facilities and the dining space on the cooking facilities side, with sprinkler heads located within 24 inches (609 mm) of the opening and, if the opening is more than 60 inches (1524 mm) wide, the sprinkler heads are spaced not more than 48 inches (1219 mm) on center.
Where the conditions of Items 5.1, 5.2, and 5.3 cannot be satisfied, such commercial kitchen shall be separated from adjoining dining spaces in accordance with Table 508.4, footnote f.
508.2 Accessory occupancies.
Accessory occupancies are those occupancies that are ancillary to the main occupancy of the building or portion thereof. Accessory occupancies shall comply with the provisions of Sections 508.2.1 through 508.2.4.
508.2.1 Occupancy classification.
Accessory occupancies shall be individually classified in accordance with Section 302.1. The requirements of this code shall apply to each portion of the building based on the occupancy classification of that space.
508.2.2 Allowable building height.
The allowable height and number of stories of the building containing accessory occupancies shall be in accordance with Section 504 for the main occupancy of the building.
508.2.3 Allowable building area.
The allowable area of the building shall be based on the applicable provisions of Section 506 for the main occupancy of the building. Aggregate accessory occupancies shall not occupy more than 10 percent of the building area of the story in which they are located and shall not exceed the tabular values for nonsprinklered buildings in Table 506.2 for each such accessory occupancy.
Exceptions:
1. The following accessory occupancies are permitted to occupy more than 10 percent of the floor area of the story in which they are located:
1.1. Accessory assembly areas having a floor area less than 750 square feet (69.7 m 2 ).
1.2. Assembly areas that are accessory to Group E occupancies.
1.3. Accessory religious educational rooms and religious auditoriums with occupant loads of less than 100.
2. Rooms or spaces within Group H-2, H-3, H-4 or H-5 occupancy shall not be considered accessory occupancies and shall be treated as separated occupancies.
508.2.4 Separation of occupancies.
No separation is required between accessory occupancies and the main occupancy.
Exceptions:
1. Group H-2, H-3, H-4 and H-5 occupancies shall be separated from all other occupancies in accordance with Section 508.4.
2. Separated tenancies in accordance with the requirements of Section 510.10.
508.3 Nonseparated occupancies.
Buildings or portions of buildings that comply with the provisions of this section shall be considered as nonseparated occupancies.
508.3.1 Occupancy classification.
Nonseparated occupancies shall be individually classified in accordance with Section 302.1. The requirements of this code shall apply to each portion of the building based on the occupancy classification of that space. In addition, the most restrictive provisions of Chapter 9 that apply to the nonseparated occupancies shall apply to the total nonseparated occupancy area. Where nonseparated occupancies occur in a high-rise building, the most restrictive requirements of Section 403 that apply to the nonseparated occupancies shall apply throughout the high-rise building.
508.3.2 Allowable building area and height.
The allowable building area and height of the building or portion thereof shall be based on the most restrictive allowances for the occupancy groups under consideration for the type of construction of the building in accordance with Section 503.1.
508.3.3 Separation.
No separation is required between nonseparated occupancies.
Exceptions:
1. Group H-2, H-3, H-4 and B-5 occupancies shall be separated from all other occupancies in accordance with Section 508.4.
2. Separated tenancies in accordance with Section 510.10.
3. Commercial kitchens shall be separated in accordance with Section 508.1, Exception 5.
508.4 Separated occupancies.
Buildings or portions of buildings that comply with the provisions of this section shall be considered as separated occupancies.
Table 508.4 Required Separation of Occupancies (Hours)
Occupancy A, E I-1 a , I-3, I-4 I-2 Ra F-2, S-2 b , U B c F-1 M S-1 H-1 H-2 H-3, H-4 H-5 S NS S NS S NS S NS S NS S NS S NS S NS S NS S NS S NS S NS S NS A, E N N 1 2 2 NP 1 2 N f 1 f 1 2 1 2 1 2 1 2 NP NP 3 4 2 3 2 NP I-1 a , I-3, I-4 – – N N 2 NP 1 NP 1 2 1 2 1 2 1 2 1 2 NP NP 3 NP 2 NP 2 NP I-2 – – – – N N 2 NP 2 NP 2 NP 2 NP 2 NP 2 NP NP NP 3 NP 2 NP 2 NP R a – – – – – – N N 1 c 2 c 1 2 1 2 1 2 1 2 NP NP 3 NP 2 NP 2 NP F-2, S-2 b , U – – – – – – – – N N 1 2 1 2 1 2 1 2 NP NP 3 4 2 3 2 NP B e – – – – – – – – – – N N 2 3 1 2 2 3 NP NP 2 3 1 2 1 NP F-1 – – – – – – – – – – – – N N 2 3 2 3 NP NP 2 3 1 2 1 NP M – – – – – – – – – – – – – – N N 2 3 NP NP 2 3 1 2 1 NP S-1 – – – – – – – – – – – – – – – – N N NP NP 2 3 1 2 1 NP H-1 – – – – – – – – – – – – – – – – – – N NP NP NP NP NP NP NP H-2 – – – – – – – – – – – – – – – – – – – – N NP 1 NP 1 NP H-3, H-4 – – – – – – – – – – – – – – – – – – – – – – 1 d NP 1 NP H-5 – – – – – – – – – – – – – – – – – – – – – – – – N NP
S = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.
NS = Buildings not equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.
N = No separation requirement.
NP = Not permitted.
a. See Section 420.
b. The required separation from areas used only for private or pleasure vehicles shall be reduced by 1 hour but to not less than 1 hour.
c. See Section 406.3.4.
d. Separation is not required between occupancies of the same classification.
e. See Section 422.2 for ambulatory care facilities.
f. A commercial kitchen in Group F-2 that does not comply with Section 508.1, Exception 5 shall be separated from adjoining dining spaces with 1-hour fire separation where the dining spaces are equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1, and separated with 2-hour fire separation where the dining spaces is not equipped throughout with an automatic sprinkler system.
508.4.1 Occupancy classification.
Separated occupancies shall be individually classified in accordance with Section 302.1. Each separated space shall comply with this code based on the occupancy classification of that portion of the building.
508.4.2 Allowable building area.
In each story, the building area shall be such that the sum of the ratios of the actual building area of each separated occupancy divided by the allowable building area of each separated occupancy shall not exceed 1.
508.4.3 Allowable height.
Each separated occupancy shall comply with the building height limitations based on the type of construction of the building in accordance with Section 503.1.
Exception: Special provisions of Section 510 shall permit occupancies at building heights other than provided in Section 503.1.
508.4.4 Separation.
Individual occupancies shall be separated from adjacent occupancies in accordance with Table 508.4.
Exception: Fire separations of Group H and I-2 occupancies shall not be permitted any reductions in fire-resistance ratings.
508.4.4.1 Construction.
Required separations shall be fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both, so as to completely separate adjacent occupancies.
Section BC 509. Incidental Uses
509.1 General.
Incidental uses listed in Table 509 and located within single occupancy or mixed occupancy buildings shall comply with the provisions of this section. Incidental uses are ancillary functions associated with a given occupancy that generally pose a greater level of risk to that occupancy and are limited to those uses listed in Table 509.
Exception: Incidental uses within and serving a dwelling unit are not required to comply with this section.
Table 509 c Incidental Uses
Room or Area Separation and/or Protection Furnace room where any piece of equipment is over 350,000 Btu per hour input 2 hour; or 1 hour and provide automatic sprinkler system a Furnace room where any piece of equipment is 350,000 Btu per hour input or less, except in R-3 occupancy 1 hour or provide automatic sprinkler system a Rooms with a high pressure steam or water boiler that exceeds 350,000 Btu per hour input 2 hour; or 1 hour and provide automatic fire-extinguishing system a Rooms with a high pressure steam or water boiler that is 350,000 Btu per hour input or less 1 hour or provide automatic sprinkler system a Rooms that contain a low pressure steam or water boiler regardless of Btu per hour input 1 hour or provide automatic sprinkler system a, b Refrigerant machinery room 1 hour or provide automatic sprinkler system Hydrogen fuel gas rooms, not classified as Group H 2 hours in all occupancies Incinerator rooms 2 hours and automatic sprinkler system Paint shops, not classified as Group H, located in occupancies other than Group F 2 hours; or 1 hour and provide automatic sprinkler system In Group E occupancies, laboratories and vocational shops not classified as Group H 1 hour or provide automatic sprinkler system In Group I-2 occupancies, laboratories not classified as Group H 1 hour and provide automatic sprinkler system In ambulatory care facilities, laboratories not classified as Group H 1 hour or provide automatic sprinkler system Laundry rooms over 100 square feet 1 hour or provide automatic sprinkler system In Group I-2, laundry rooms over 100 square feet 1 hour Group I-3 cells and Group I-2 patient rooms equipped with padded surfaces 1 hour In Group I-2, physical plant maintenance shops 1 hour In ambulatory care facilities or Group I-2 occupancies, waste and linen collection rooms with containers that have an aggregate volume of 10 cubic feet or greater 1 hour In other than ambulatory care facilities and Group I-2 occupancies, waste and linen collection rooms over 100 square feet 1 hour or provide automatic sprinkler system In ambulatory care facilities or Group I-2 occupancies, storage rooms greater than 100 square feet 1 hour Stationary storage battery systems having an energy capacity greater than the threshold quantity specified in Table 608.9.1.1 of the New York City Fire Code 1 hour in group B, F, M, S and U occupancies; 2 hours in Group A, E, I and R occupancies Rooms containing fire pumps in non-high-rise buildings 2 hours; or 1 hour and provide automatic sprinkler system throughout the building Rooms containing fire pumps in high-rise buildings 2 hours
For SI: 1 square foot = 0.0929 m 2 , 1 pound per square inch (psi) = 6.9 kPa, 1 British thermal unit (Btu) per hour = 0.293 watts, 1 horsepower = 746 watts, 1 gallon = 3.785 L, 1 cubic foot = 0.0283 m 3 .
a. Boilers servicing more than one dwelling unit in Multiple dwellings shall also comply with Section 65 of the New York State Multiple Dwelling Law.
b. Sealed combustion direct vent boilers shall comply with Section 303 of the New York City Mechanical Code and Section 303 of the New York City Fuel Gas Code, as applicable.
c. For mechanical and/or electrical equipment rooms not identified in this table, see Section 508.1.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
509.2 Occupancy classification.
Incidental uses shall not be individually classified in accordance with Section 302.1. Incidental uses shall be included in the building occupancies within which they are located.
509.3 Area limitations.
Incidental uses shall not occupy more than 10 percent of the building in which they are located.
509.4 Separation and protection.
The incidental uses listed in Table 509 shall be separated from the remainder of the building or equipped with an automatic sprinkler system, or both, in accordance with the provisions of that table.
509.4.1 Separation.
Where Table 509 specifies a fire-resistance-rated separation, the incidental uses shall be separated from the remainder of the building by a fire barrier constructed in accordance with Section 707 or a horizontal assembly constructed in accordance with Section 711, or both. Construction supporting 1-hour fire barriers or horizontal assemblies used for incidental use separations in buildings of Type IIB, IIIB and VB construction is not required to be fire-resistance rated unless required by other sections of this code.
509.4.2 Protection.
Where Table 509 permits an automatic sprinkler system without a fire barrier, the incidental uses shall be separated from the remainder of the building by construction capable of resisting the passage of smoke. The walls shall extend from the top of the foundation or floor assembly below to the underside of the ceiling that is a component of a fire-resistance-rated floor assembly or roof assembly above or to the underside of the floor or roof sheathing, deck or slab above. Doors shall be self- or automatic-closing upon detection of smoke in accordance with Section 716.5.9.3. Doors shall not have air transfer openings and shall not be undercut in excess of the clearance permitted in accordance with NFPA 80. Walls surrounding the incidental use shall not have air transfer openings unless provided with smoke dampers in accordance with Section 710.8.
509.4.2.1 Protection limitation.
Except as specified in Table 509 for certain incidental uses, where an automatic sprinkler system is provided in accordance with Table 509, only the space occupied by the incidental use need be equipped with such a system.
Section BC 510. Special Provisions
510.1 General.
The provisions in Sections 510.2 through 510.10 shall permit the use of special conditions that are exempt from, or modify, the specific requirements of this chapter regarding the allowable building heights and areas of buildings based on the occupancy classification and type of construction, provided the special condition complies with the provisions specified in this section for such condition and other applicable requirements of this code. The provisions of Sections 510.2 through 510.8 are to be considered independent and separate from each other.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
510.2 Horizontal building separation allowance.
Buildings shall be considered as separate and distinct from each other for the purpose of determining area limitations, continuity of fire walls, limitation of number of stories and type of construction, where all of the following conditions are met:
1. The buildings are separated with a horizontal floor assembly having a fire-resistance rating of not less than 3 hours.
2. The building below the horizontal assembly is of Type IA construction.
3. Shaft, stairway, ramp or escalator enclosures through the horizontal floor assembly shall have not less than a 2-hour fire-resistance rating with opening protectives in accordance with Section 716.5.
Exception: Where the enclosure walls below the horizontal floor assembly have not less than a 3-hour fire-resistance rating with opening protectives in accordance with Section 716.5, the enclosure walls extending above the horizontal floor assembly shall be permitted to have a 1-hour fire-resistance rating, provided:
1. The building above the horizontal floor assembly is not required to be of Type I construction;
2. The enclosure connects fewer than four stories; and
3. The enclosure opening protectives above the horizontal floor assembly have a fire protection rating of not less than 1 hour.
4. The building or buildings above the horizontal assembly shall be permitted to have multiple Group A occupancy uses, each with an occupant load of less than 300, or Group B, M, R or S occupancies.
5. The building below the horizontal assembly shall be protected throughout by an approved automatic sprinkler system in accordance with Section 903.3.1.1, and shall be permitted to be any occupancy allowed by this code except Group H.
6. The maximum building height in feet (mm) as measured from the grade plane shall not exceed the limits set forth in Section 504.3 for the building having the smaller allowable height as measured from the grade plane.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
510.3 Group S-2 enclosed parking garage with Group S-2 open parking garage above.
A Group S-2 enclosed parking garage with not more than one story above grade plane and located below a Group S-2 open parking garage shall be classified as a separate and distinct building for the purpose of determining the type of construction where all of the following conditions are met:
1. The allowable area of the building shall be such that the sum of the ratios of the actual area divided by the allowable area for each separate occupancy shall not exceed 1.
2. The Group S-2 enclosed parking garage is of Type I or II construction and is at least equal to the fire-resistance requirements of the Group S-2 open parking garage.
3. The height and the number of the tiers of the Group S-2 open parking garage shall be limited as specified in Table 406.5.4.
4. The floor assembly separating the Group S-2 enclosed parking garage and Group S-2 open parking garage shall be protected as required for the floor assembly of the Group S-2 enclosed parking garage. Openings between the Group S-2 enclosed parking garage and Group S-2 open parking garage, except exit openings, shall not be required to be protected.
5. The Group S-2 enclosed parking garage is used exclusively for the parking or storage of private motor vehicles, but shall be permitted to contain an accessory office, waiting room and toilet room having a total area of not more than 1,000 square feet (93 m 2 ) and mechanical equipment rooms incidental to the operation of the building.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
510.4 Parking beneath Group R.
Where a maximum one story above grade plane Group S-2 parking garage, enclosed or open, or combination thereof, of Type I construction or open of Type IV construction, with grade entrance, is provided under a building of Group R, the number of stories to be used in determining the minimum type of construction shall be measured from the floor above such a parking area. The horizontal floor assembly between the parking garage and the Group R above shall comply with the type of construction required for the parking garage and shall also provide a fire-resistance rating not less than the mixed occupancy separation required in Section 508.4.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
510.5 Reserved.
510.6 Group R-2 buildings of Type IIA construction.
The height limitation for buildings of Type IIA construction in Group R-2 shall be increased to nine stories and 100 feet (30 480 mm) where the building is separated by not less than 50 feet (15 240 mm) from any other building on the lot and from lot lines, the exits are segregated in an area enclosed by a 2-hour fire-resistance-rated fire wall and the first floor assembly has a fire-resistance rating of not less than 1 1/2 hours.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
510.7 Open parking garage beneath Groups A, I, B, M and R.
Open parking garages constructed under Groups A, I, B, M and R shall not exceed the height and area limitations permitted under Section 406.5. The height and area of the portion of the building above the open parking garage shall not exceed the limitations in Section 503 for the upper occupancy. The height, in both feet and stories, of the portion of the building above the open parking garage shall be measured from grade plane and shall include both the open parking garage and the portion of the building above the parking garage.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
510.7.1 Fire separation.
Fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711 between the parking occupancy and the upper occupancy shall correspond to the required fire-resistance rating prescribed in Table 508.4 for the occupancies involved. The type of construction shall apply to each occupancy individually, except that structural members, including main bracing within the open parking structure, which is necessary to support the upper occupancy, shall be protected with the more restrictive fire-resistance-rated assemblies of the groups involved as shown in Table 601. Means of egress for the upper occupancy shall conform to Chapter 10 and shall be separated from the parking occupancy by fire barriers having not less than a 2-hour fire-resistance rating as required by Section 707, with self-closing doors complying with Section 716 or horizontal assemblies having not less than a 2-hour fire-resistance rating as required by Section 711, with self-closing doors complying with Section 716. Means of egress from the open parking garage shall comply with Section 406.5.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
510.8 Industrial uses in buildings containing Group R.
No space classified as Factory Industrial Group F shall be located above the second story of any building of Type III, IV or V construction containing a space classified as Residential Group R-1 or R-2.
510.9 Multiple buildings above Group S-2 parking garages.
Where two or more buildings are provided above the horizontal assembly separating a Group S-2 open or closed parking garage from the buildings above in accordance with the special provisions in Sections 510.2, 510.3 or 510.8, the buildings above the horizontal assembly shall be regarded as separate and distinct buildings from each other and shall comply with all other provisions of this code as applicable to each separate and distinct building.
510.10 Separation of different tenancies.
Spaces or dwelling units occupied by different tenants shall be separated by fire barriers having at least 1-hour fire-resistance ratings.
Exceptions:
1. Nonresidential spaces occupied by different tenants located in buildings that are sprinklered throughout.
2. Tenant spaces in covered mall buildings complying with Section 402.
Section BC 601. General
601.1 Scope.
The provisions of this chapter shall control the classification of buildings as to type of construction.
Table 601 Fire-Resistance Rating Requirements for Building Element (hours)
Building Element Type I Type II Type III Type IV i Type V i A B A B A B HT A B Primary structural frame f (see Section 202) 3 a 2 a, j 1 j 0 1 0 HT 1 0 Bearing walls Exterior e, f, g Interior 3 3 a 2 2 a 1 1 0 0 2 1 2 0 2 1/HT 1 1 0 0 Nonbearing walls and partitions Exterior See Table 602 Nonbearing walls and partitions Interior d 0 0 0 0 0 0 See Section 602.4.6 0 0 Floor construction h and associated secondary members (see Section 202) 2 2 1 0 1 0 HT 1 0 Roof construction and associated secondary members (see Section 202) 1 1/2 b, c 1 b, c 1 b, c 0 c 1 b, c 0 HT 1 b, c 0
For SI: 1 foot = 304.8 mm.
a. Roof supports: Fire-resistance ratings of primary structural frame and bearing walls are permitted to be reduced by 1 hour where supporting a roof only.
b. 1. Except in Group F-1, H, M and S-1 occupancies, fire protection of structural members in roof construction shall not be required, including protection of primary structural frame members within any portion of the roof, roof framing and decking where every part of the roof construction is 20 feet or more above any floor immediately below. Fire-retardant-treated wood members shall be allowed to be used for such unprotected members.
2. Except in Group F occupancies subject to regulation under Sections 264(1) and 264(2) of the New York State Labor Law, and in Group I-1, R-1, and R-2 occupancies, in Types I and II construction, fire-retardant-treated wood shall be allowed in buildings including girders and trusses as part of the roof construction when the building is:
i. Type II construction of any height; or
ii. Type I construction two stories or less; or when over two stories, the vertical distance from the upper floor to the roof is 20 feet or more.
c. Except in Group F occupancies subject to regulation under Sections 264(1) and 264(2) of the New York State Labor Law, and in Group I-1, R-1 and R-2 occupancies, heavy timber shall be allowed where a 1-hour or less fire-resistance rating is required.
d. Not less than the fire-resistance rating required by other sections of this code.
e. Not less than the fire-resistance rating based on fire separation distance (see Table 602).
f. Not less than the fire-resistance rating as referenced in Section 704.10.
g. See note g of Table 602.
h. See Section 711.2.4 for additional requirements.
i. Type V construction is not permitted inside fire districts except as provided for in Section D105.1 of Appendix D.
j. See Section 403.2.1 for additional requirements for high-rise buildings and fire-resistance rating of columns in such buildings.
Table 602 Fire-Resistance Rating Requirements for Exterior Walls Based on Fire Separation Distance a, e, g, h, j
Fire Separation Distance = X (feet) Type of Construction Occupancy Group H f Occupancy Group F-1, M, S-1 g, i Occupancy Group A, B, E, F-2, I, R, S-2, U b X < 5 c All 3 2 1 5 £ X < 10 IA Others 3 2 2 1 1 1 10 £ X < 30 IA, IB IIB, VB Others 2 1 1 1 0 1 1 d 0 1 d X ³ 30 All 0 0 0
For SI: 1 foot = 304.8 mm.
a. Load-bearing exterior walls shall also comply with the fire-resistance rating requirements of Table 601.
b. Group U when used as accessory to Group R-3 shall not be required to have a fire-resistance rating where the fire separation distance is 5 feet or more for free standing private garages in compliance with Section 406.1, and when the separation distance is 3 feet or more for other free-standing Group U buildings. For free standing private garages where the fire separation distance is less than 5 feet, refer to Section 406.3.4 for required fire-resistance rating for exterior walls.
c. See Section 706.1.1 for party walls.
d. Open parking garages complying with Section 406 shall not be required to have a fire-resistance rating.
e. The fire-resistance rating of an exterior wall is determined based upon the fire separation distance of the exterior wall and the story in which the wall is located.
f. For special requirements for Group H occupancies, see Section 415.6.
g. Inside the fire district, exterior load bearing walls of Type II buildings shall have a fire-resistance rating not less than prescribed below:
X < 5 2 hours
5 £ X < 10 2 hours
10 £ X < 30 1 hour
X ³ 30 As per Table 602.
h. Inside the fire district, exterior non-load bearing walls of Type II buildings shall have a fire resistance rating not less than prescribed below:
X < 5 As per Table 602
5 £ X < 10 As per Table 602
10 £ X < 30 1 hour
X ³ 30 As per Table 602.
i. For special requirements for Group S aircraft hangars, see Section 412.4.1.
j. Where Table 705.8 permits nonbearing exterior walls with unlimited area of unprotected openings, the required fire-resistance rating for the exterior walls is 0 hours.
Section BC 602. Construction Classification
602.1 General.
Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. The building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire-resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection of openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Buildings constructed or altered inside the fire district shall further comply with Appendix D.
602.1.1 Minimum requirements.
A building or portion thereof shall not be required to conform to the details of a type of construction higher than that type which meets the minimum requirements based on occupancy even though certain features of such a building actually conform to a higher type of construction. Classification shall be that of the minimum requirement unless all of the requirements for the higher type of construction are met.
Exception: Portions of buildings that cantilever over an adjacent building or tax lot shall also comply with the fire-resistance ratings of Section 705.12.
602.2 Types I and II.
Types I and II construction are those types of construction in which the building elements listed in Table 601 are of noncombustible materials, except as permitted in Section 603 and elsewhere in this code.
602.3 Type III.
Type III construction is that type of construction in which the exterior walls are of noncombustible materials and the interior building elements are of any material permitted by this code. Fire-retardant-treated wood framing complying with Section 2303.2 shall be permitted within exterior wall assemblies of a 2-hour rating or less.
Exceptions:
1. In Group I-1, R- 1, and R-2 occupancies, all exterior walls, fire walls, exit passageways, and shaft enclosures shall be noncombustible.
2. In Group F occupancies subject to Section 270(1) of the New York State Labor Law, all exterior wall assemblies and all structural elements shall meet the requirements for a "fireproof building" as such term is defined in Section 264 of such law.
3. Inside the fire district, exterior load-bearing walls shall be constructed of noncombustible material.
4. Inside the fire district, exterior nonload-bearing walls may be constructed with fire-retardant-treated wood complying with Section 2303.2 where the building is equipped throughout with an automatic sprinkler system in accordance with Sections 903.3.1.1 through 903.3.1.3, unless otherwise prohibited by Exception 1 or 2 above.
602.4 Type IV.
Type IV construction is that type of construction in which the exterior walls are of noncombustible materials or other materials permitted by Section 602.4.1 or 602.4.2, and the interior building elements are of solid wood, glue-laminated timber, heavy timber (HT), structural composite lumber (SCL), or cross-laminated timber (CLT) without concealed spaces. The minimum dimensions for permitted materials including solid timber, glued-laminated timber, SCL, and CLT and details of Type IV construction shall comply with the provisions of Section 2304.11 and this section. Interior walls and partitions not less than 1-hour fire-resistance rating or heavy timber complying with Section 2304.11.2.2 shall be permitted. Buildings of Type IV construction utilizing SCL or CLT shall be equipped throughout with an automatic sprinkler system where required by Section 903.2.13. In buildings of Type IV construction utilizing SCL or CLT, a fire watch shall be maintained in accordance with Section 901.7.2 of the New York City Fire Code and Section 3303.3 of this code.
Exceptions:
1. In Group I-1, R-1, and R-2 occupancies, all exterior walls, fire walls, exit passageways, and shaft enclosures shall be noncombustible.
2. In Group F occupancies subject to Section 270(1) of the New York State Labor Law, all exterior wall assemblies and all structural elements shall meet the requirements for a "fireproof building" as defined in Section 264 of such law.
3. Inside the fire district, exterior load-bearing walls shall be constructed of noncombustible material.
4. Inside the fire district, exterior nonbearing walls may be constructed with fire-retardant-treated wood complying with Section 2303.2 where the building is equipped throughout with an automatic sprinkler system in accordance with Sections 903.3.1.1 through 903.3.1.3, unless otherwise prohibited by Exception 1 or 2 above.
5. Inside the fire district, exterior nonbearing walls are permitted to be constructed with cross-laminated timber (CLT) complying with Section 602.4.2 of this code, unless otherwise prohibited by Exception 1 or 2 above.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
602.4.1 Fire-retardant-treated wood in exterior walls.
Fire-retardant-treated wood framing and sheathing complying with Section 2303.2 shall be permitted within exterior wall assemblies not less than 6 inches (152.4 mm) in thickness with a 2-hour rating or less.
602.4.2 Cross-laminated timber in exterior walls.
Cross-laminated timber (CLT) complying with Section 2303.1.4 shall be permitted within exterior wall assemblies not less than 6 inches (152.4 mm) in thickness with a 2-hour rating or less, provided the exterior surface of the cross-laminated timber (CLT) is protected by one of the following:
1. Fire-retardant-treated wood sheathing complying with Section 2303.2 and not less than 15/32 inch (11.9 mm) thick;
2. Type X gypsum board not less than 5/8 inch (15.9 mm) thick; or
3. A noncombustible material.
602.4.3 Exterior structural members.
Where a horizontal separation of 20 feet (6096 mm) or more is provided, wood columns and arches conforming to heavy timber sizes in accordance with Section 2304.11 shall be permitted to be used externally.
Exception: Where prohibited by Exceptions 1, 2 or 3 of Section 602.4.
602.5 Type V.
Type V construction is that type of construction in which the structural elements, exterior walls and interior walls are of any materials permitted by this code. Type V construction shall not be permitted inside the fire district unless otherwise permitted by Section D105.1.
Exception: In Group F occupancies subject to Section 270(1) of the New York State Labor Law, all exterior wall assemblies and all structural elements shall meet the requirements for a "fireproof building" as defined in Section 264 of such law.
Section BC 603. Combustible Material in Types I and II Construction
603.1 Allowable materials.
Combustible materials shall be permitted in buildings of Type I or II construction in the following applications and in accordance with Sections 603.1.1 through 603.1.3.
1. Fire-retardant-treated wood, complying with Section 2303.2, shall be permitted in:
1.1. Nonbearing interior partitions where the required fire-resistance rating is 1 hour or less.
Exception: Public corridors and exits shall be constructed of noncombustible materials.
1.2. Roof construction as permitted in Table 601, Note b.
2. Thermal and acoustical insulation, other than foam plastics, having a flame spread index of not more than 25.
Exceptions:
1. Insulation placed between two layers of noncombustible materials without an intervening airspace shall be allowed to have a flame spread index of not more than 100.
2. Insulation installed between a finished floor and solid decking without intervening airspace shall be allowed to have a flame spread index of not more than 200.
3. Foam plastics in accordance with Chapter 26.
4. Roof coverings that have an A or B classification as defined in Section 1505.
5. Interior floor finish and floor covering materials installed in accordance with Section 804.
6. Millwork such as doors, door frames, window sashes and frames.
7. Interior wall and ceiling finishes installed in accordance with Sections 801 and 803.
8. Trim installed in accordance with Section 806.
9. Where not installed greater than 15 feet (4572 mm) above grade, show windows, nailing or furring strips and wooden bulkheads below show windows, including their frames, aprons and show cases.
10. Finish flooring installed in accordance with Section 805.
11. Partitions dividing portions of stores, offices or similar places occupied by one tenant only and that do not establish a corridor serving an occupant load of 30 or more shall be permitted to be constructed of fire-retardant-treated wood, 1-hour fire-resistance-rated construction or of wood panels or similar light construction up to 6 feet (1828.8 mm) in height.
12. Stages and platforms constructed in accordance with Sections 410.3 and 410.4, respectively.
13. Combustible exterior wall coverings, balconies and similar projections and bay or oriel windows in accordance with Chapter 14.
14. Blocking such as for handrails, millwork, cabinets and window and door frames.
15. Light-transmitting plastics as permitted by Chapter 26.
16. Mastics and caulking materials applied to provide flexible seals between components of exterior wall construction.
17. Exterior plastic veneer installed in accordance with Section 2605.2.
18. Nailing or furring strips as permitted by Section 803.13.
19. Heavy timber as permitted by Note c to Table 601 and Sections 602.4.3.
20. Aggregates, component materials and admixtures as permitted by Section 703.2.2.
21. Sprayed fire-resistant materials and intumescent and mastic fire-resistant coatings, determined on the basis of fire resistance tests in accordance with Section 703.2 and installed in accordance with Sections 1705.14 and 1705.15, respectively.
22. Materials used to protect penetrations in fire-resistance-rated assemblies in accordance with Section 714.
23. Materials used to protect joints in fire-resistance-rated assemblies in accordance with Section 715.
24. Materials allowed in the concealed spaces of buildings of Types I and II construction in accordance with Section 718.5.
25. Materials exposed within plenums complying with Section 602 of the New York City Mechanical Code.
26. Bleachers, grandstands, and folding and telescopic seating within an assembly space in accordance with Section 1029.1.1 of this code.
603.1.1 Ducts.
The use of nonmetallic ducts shall be permitted where installed in accordance with the limitations of the New York City Mechanical Code.
603.1.2 Piping.
The use of combustible piping materials shall be permitted where installed in accordance with the limitations of the New York City Mechanical Code and the New York City Plumbing Code.
603.1.3 Electrical.
The use of electrical wiring methods with combustible insulation, tubing, raceways and related components shall be permitted where installed in accordance with the limitations of the New York City Electrical Code.
Section BC 701. General
701.1 Scope.
The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated construction separation of adjacent spaces to safeguard against the spread of fire and smoke within a building and the spread of fire to or from buildings.
701.2 Multiple use fire assemblies.
Fire assemblies that serve multiple purposes in a building shall comply with all of the requirements that are applicable for each of the individual fire assemblies.
Section BC 702. Definitions
702.1 Definitions.
The following terms are defined in Chapter 2:
ANNULAR SPACE.
BUILDING ELEMENT.
CEILING RADIATION DAMPER.
COMBINATION FIRE/SMOKE DAMPER.
CONCEALED SPACES.
DAMPERS, TYPES OF.
DRAFTSTOP.
F RATING.
FIRE BARRIER.
FIRE DAMPER.
FIRE DOOR.
FIRE DOOR ASSEMBLY.
FIRE PARTITION.
FIRE PROTECTION RATING.
FIRE-RATED GLAZING.
FIRE RESISTANCE.
FIRE-RESISTANCE RATING.
FIRE-RESISTANT JOINT SYSTEM.
FIRE SEPARATION DISTANCE.
FIRE WALL.
FIRE WINDOW ASSEMBLY.
FIREBLOCKING.
FIRESTOPPING.
FLOOR FIRE DOOR ASSEMBLY.
HORIZONTAL ASSEMBLY.
JOINT.
L RATING.
MEMBRANE PENETRATION.
MEMBRANE PENETRATION FIRESTOP.
MEMBRANE-PENETRATION FIRESTOP SYSTEM.
MINERAL FIBER.
MINERAL WOOL.
PENETRATION FIRESTOP.
SELF-CLOSING.
SHAFT.
SHAFT ENCLOSURE.
SMOKE BARRIER.
SMOKE COMPARTMENT.
SMOKE DAMPER.
SMOKE PARTITION.
SPLICE.
T RATING.
THROUGH-PENETRATION.
THROUGH-PENETRATION FIRESTOP SYSTEM.
Section BC 703. Fire-Resistance Ratings and Fire Tests
703.1 Scope.
Materials prescribed herein for fire resistance shall conform to the requirements of this chapter.
703.2 Fire-resistance ratings.
The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. The fire-resistance rating of penetrations and fire-resistant joint systems shall be determined in accordance with Sections 714 and 715, respectively.
703.2.1 Nonsymmetrical wall construction.
Interior walls and partitions of nonsymmetrical construction shall be tested with both faces exposed to the furnace, and the assigned fire-resistance rating shall be the shortest duration obtained from the two tests conducted in compliance with ASTM E 119 or UL 263. When evidence is furnished to show that the wall was tested with the least fire-resistant side exposed to the furnace, subject to acceptance of the commissioner, the wall need not be subjected to tests from the opposite side (see Section 705.5 of this code for exterior walls).
703.2.2 Combustible components.
Combustible aggregates may be integrated with other materials to form a noncombustible material provided that the entire mixture, in the form in which it is to be used in construction, meets the requirement of this code for noncombustible construction.
703.2.3 Restrained classification.
Fire-resistance-rated assemblies tested under ASTM E 119 or UL 263 shall not be considered to be restrained unless evidence satisfactory to the commissioner is furnished by the registered design professional showing that the construction qualifies for a restrained classification in accordance with ASTM E 119 or UL 263. Restrained construction shall be identified on the construction documents.
703.2.4 Supplemental features.
Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element component or assembly, sufficient data shall be made available to the commissioner to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire-resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating.
703.2.5 Exterior bearing walls.
In determining the fire-resistance rating of exterior bearing walls, compliance with the ASTM E 119 or UL 263 criteria for unexposed surface temperature rise and ignition of cotton waste due to passage of flame or gases is required only for a period of time corresponding to the required fire-resistance rating of an exterior nonbearing wall with the same fire separation distance, and in a building of the same group. Where the fire-resistance rating, determined in accordance with this section, exceeds the fire-resistance rating determined in accordance with ASTM E 119 or UL 263, the fire exposure time period, water pressure and application duration criteria for the hose stream test of ASTM E 119 or UL 263 shall be based on the fire-resistance rating determined in accordance with this section.
703.3 Methods for determining fire resistance.
The application of any of the methods listed in this section shall be based on the fire exposure and acceptance criteria specified in ASTM E 119 or UL 263. The required fire resistance of a building element, component or assembly shall be permitted to be established by any of the following methods or procedures:
1. Fire-resistance designs documented in approved sources.
2. Prescriptive designs of fire-resistance-rated building elements, components or assemblies as prescribed in Section 721 of this code.
3. Calculations in accordance with Section 722 of this code.
4. Engineering analysis based on a comparison of building element, component or assemblies designs having fire-resistance ratings as determined by the test procedures set forth in ASTM E 119 or UL 263.
5. Alternative protection methods as allowed by rules of the department.
703.4 Automatic sprinklers.
Under the prescriptive fire-resistance requirements of this code, the fire-resistance rating of a building element, component or assembly shall be established without the use of automatic sprinklers or any other fire suppression system being incorporated as part of the assembly tested in accordance with the fire exposure, procedures and acceptance criteria specified in ASTM E 119 or UL 263. However, this section shall not prohibit or limit the duties and powers of the commissioner as allowed by Sections 28-103.1.3 and 28-103.3 of Administrative Code.
703.5 Noncombustibility tests.
The tests indicated in Sections 703.5.1 and 703.5.2 shall serve as criteria for acceptance of building materials as set forth in Sections 602.2, 602.3 and 602.4 in Type I, II, III and IV construction. The term "noncombustible" does not apply to the flame spread characteristics of interior finish or trim materials. A material shall not be classified as a noncombustible building construction material if it is subject to an increase in combustibility or flame spread beyond the limitations herein established through the effects of age, fabrication or erection techniques, moisture or other atmospheric conditions.
703.5.1 Elementary materials.
Materials required to be noncombustible shall be tested in accordance with ASTM E 136.
703.5.2 Composite materials.
Materials having a structural base of noncombustible material as determined in accordance with Section 703.5.1 of this code with a surfacing not more than 0.125 inch (3.18 mm) thick that has a flame spread index not greater than 50 when tested in accordance with ASTM E 84 or UL 723 shall be acceptable as noncombustible materials.
703.6 Fire-resistance-rated glazing.
Fire-resistance-rated glazing, when tested in accordance with ASTM E 119 or UL 263 and complying with the requirements of Section 707, shall be permitted. Fire-resistance-rated glazing shall bear a label marked in accordance with Table 716.3 of this code and issued by an approved agency that shall be permanently identified on the glazing.
703.7 Marking and identification.
Where there is a concealed floor, floor-ceiling or attic space, fire walls, fire barriers, fire partitions, smoke barriers and smoke partitions or any other wall required to have protected openings or penetrations shall be effectively and permanently identified with signs or stenciling in the concealed space. Such identification shall:
1. Be located within 15 feet (4572 mm) of the end of each wall and at intervals not exceeding 30 feet (9144 mm) measured horizontally along the wall or partition.
2. Include lettering not less than 3 inches (76.2 mm) in height with a minimum 3/8-inch (9.5 mm) stroke in a contrasting color incorporating the suggested wording, "FIRE AND/OR SMOKE BARRIER – PROTECT ALL OPENINGS."
Section BC 704. Fire-Resistance Rating of Structural Members
704.1 Requirements.
The fire-resistance ratings of structural members and assemblies shall comply with this section and the requirements for the type of construction as specified in Table 601. The fire-resistance ratings shall be not less than the ratings required for the fire-resistance-rated assemblies supported by the structural members.
Exception: Fire barriers, fire partitions, smoke barriers and horizontal assemblies as provided in Sections 707.5, 708.4 and 711.2, respectively.
704.2 Column protection.
Where columns are required to have protection to achieve a fire-resistance rating, the entire column shall be provided individual encasement protection by protecting it on all sides for the full column height, including connections to other structural members, with materials having the required fire-resistance rating. Where the column extends through a ceiling, the encasement protection shall be continuous from the top of the foundation or floor/ceiling assembly below through the ceiling space to the top of the column.
704.3 Protection of the primary structural frame other than columns.
Members of the primary structural frame other than columns that are required to have protection to achieve a fire-resistance rating and support more than one floor or one floor and roof, or support a load-bearing wall or a nonload-bearing wall more than one story high, shall be provided individual encasement protection by protecting them on all sides for the full length, including connections to other structural members, with materials having the required fire-resistance rating.
Exception: Individual encasement protection may be omitted on those exposed sides where the extent of protection is in accordance with the required fire-resistance rating, as determined in Section 703.
704.4 Protection of secondary members.
Secondary members that are required to have protection to achieve a fire-resistance rating shall be protected by individual encasement protection.
704.4.1 Light-frame construction.
Studs and boundary elements that are integral elements in load-bearing walls of light-frame construction shall be permitted to have required fire-resistance ratings provided by the membrane protection provided for the load-bearing wall.
704.4.2 Horizontal assemblies.
Horizontal assemblies are permitted to be protected with a membrane or ceiling where the membrane or ceiling provides the required fire-resistance rating and is installed in accordance with Section 711.
704.5 Truss protection.
The required thickness and construction of fire-resistance-rated assemblies enclosing trusses shall be based on the results of full-scale tests or combinations of tests on truss components or on approved calculations based on such tests that satisfactorily demonstrate that the assembly has the required fire resistance.
704.6 Attachments to structural members.
The edges of lugs, brackets, rivets and bolt heads attached to structural members shall be protected to the highest required fire-resistance rating of the members connected.
704.7 Reinforcing.
Thickness of protection for concrete or masonry reinforcement shall be measured to the outside of the reinforcement, including stirrups, ties and spiral reinforcing ties.
704.8 Embedments and enclosures.
Pipes, wires, conduits, ducts or other service facilities shall not be embedded in the required fire protective covering of a structural member that is required to be individually encased.
Exception: Pipes, wires, and conduits may be installed in the space between the required fire protection and the structural member protected, provided that where such facilities pierce the required fire protection:
1. The area of the penetration does not exceed two percent of the area of the fire protection on any one face,
2. The penetrations are closed off with close-fitting metal escutcheons or plates, and3. the concealed space is firestopped at each story, and
3. The concealed space is firestopped at each story.
704.9 Impact protection.
Where the fire protective covering of a structural member is subject to impact damage from moving vehicles, the handling of merchandise or other activity, the fire protective covering shall be protected by corner guards or by a substantial jacket of metal or other noncombustible material to a height adequate to provide full protection, but not less than 5 feet (1524 mm) from the finished floor.
Exception: Corner protection is not required on concrete columns in open or enclosed parking garages.
704.10 Exterior structural members.
Load-bearing structural members located within the exterior walls or exposed to the outside of a building or structure shall be provided with the highest fire-resistance rating as determined in accordance with the following:
1. As required by Table 601 for the type of building element based on the type of construction of the building;
2. As required by Table 601 for exterior bearing walls based on the type of construction; and
3. As required by Table 602 for exterior walls based on the fire separation distance.
704.11 Bottom flange protection.
Fire protection is not required at the bottom flange of lintels, shelf angles and plates spanning not more than 6 feet 4 inches (1930.4 mm), whether part of the primary structural frame or not, and from the bottom flange of lintels, shelf angles and plates not part of the structural frame, regardless of span.
704.12 Seismic isolation systems.
Fire-resistance ratings for the isolation system shall meet the fire-resistance rating required for the columns, walls or other structural elements in which the isolation system is installed in accordance with Table 601 of this code. Isolation systems required to have a fire-resistance rating shall be protected with approved materials or construction assemblies designed to provide the same degree of fire resistance as the structural element in which the system is installed when tested in accordance with ASTM E 119 or UL 263 (see Section 703.2 of this code).
Such isolation system protection applied to isolator units shall be capable of retarding the transfer of heat to the isolator unit in such a manner that the required gravity load-carrying capacity of the isolator unit will not be impaired after exposure to the standard time-temperature curve fire test prescribed in ASTM E 119 or UL 263 for a duration not less than that required for the fire-resistance rating of the structure element in which the system is installed.
Such isolation system protection applied to isolator units shall be suitably designed and securely installed so as not to dislodge, loosen, sustain damage or otherwise impair its ability to accommodate the seismic movements for which the isolator unit is designed and to maintain its integrity for the purpose of providing the required fire-resistance protection.
704.13 Sprayed fire-resistant materials (SFRM).
Sprayed fire-resistant materials (SFRM) shall comply with Sections 704.13.1 through 704.13.5.
704.13.1 Fire-resistance rating.
The application of SFRM shall be consistent with the fire-resistance rating and the listing, including, but not limited to, minimum thickness and dry density of the applied SFRM, method of application, substrate surface conditions and the use of bonding adhesives, sealants, reinforcing or other materials.
704.13.2 Manufacturer's installation instructions.
The application of SFRM shall be in accordance with the manufacturer's installation instructions. The instructions shall include, but are not limited to, substrate temperatures and surface conditions and SFRM handling, storage, mixing, conveyance, method of application, curing and ventilation.
704.13.3 Substrate condition.
The SFRM shall be applied to a substrate in compliance with Sections 704.13.3.1 through 704.13.3.2.
704.13.3.1 Surface conditions.
Substrates to receive SFRM shall be free of dirt, oil, grease, release agents, loose scale and any other condition that prevents adhesion. The substrates shall also be free of primers, paints and encapsulants other than those fire tested and listed by a nationally recognized testing agency. Primed, painted or encapsulated steel shall be allowed, provided that testing has demonstrated that required adhesion is maintained.
704.13.3.2 Primers, paints and encapsulants.
Where the SFRM is to be applied over primers, paints or encapsulants other than those specified in the listing, the material shall be field tested in accordance with ASTM E 736. Where testing of the SFRM with primers, paints or encapsulants demonstrates that required adhesion is maintained, SFRM shall be permitted to be applied to primed, painted or encapsulated wide flange steel shapes subject to the following conditions:
1. The beam flange width of such shape may not exceed 12 inches (304.8 mm);
2. The column flange width of such shape may not exceed 16 inches (406.4 mm);
3. The beam or column web depth of such shape may not exceed 16 inches (406.4 mm); and
4. The average and minimum bond strength values shall be determined based on a minimum of five bond tests conducted in accordance with ASTM E 736. Bond tests conducted in accordance with ASTM E 736 shall indicate an average bond strength of not less than 80 percent and an individual bond strength of not less than 50 percent, when compared to the bond strength of the SFRM as applied to clean uncoated 1/8-inch (3.2 mm) thick steel plate.
704.13.4 Temperature.
A minimum ambient and substrate temperature of 40° F (4.44° C) shall be maintained during and for not fewer than 24 hours after the application of the SFRM, unless the manufacturer's instructions allow otherwise.
704.13.5 Finished condition.
The finished condition of SFRM applied to structural members or assemblies shall not, upon complete drying or curing, exhibit cracks, voids, spalls, delamination or any exposure of the substrate. Surface irregularities of SFRM shall be deemed acceptable.
704.14 Fire retardant or intumescent coatings on mass timber.
Fire retardant or intumescent coatings shall not be used to achieve the required fire-resistance rating on structural elements composed of heavy timber members including, but not limited to, glued-laminated members, cross laminated timber (CLT) or structural composite lumber (SCL).