NYC Administrative Code Title 28, Chapter 7 New York City Building Code, part 3 of 33
Section BC 301 to Section BC 406: 18 sections.
Section BC 301. General
301.1 Scope.
The provisions of this chapter shall control the classification of all buildings and structures, and spaces therein, as to use and occupancy.
Section BC 302. Classification
302.1 General.
Structures or portions of structures shall be classified with respect to occupancy in one or more of the groups listed below. A room or space that is intended to be occupied at different times for different purposes shall comply with all of the requirements that are applicable to each of the purposes for which the room or space will be occupied. Structures with multiple occupancies or uses shall comply with Section 508. Where a structure, or portion thereof, is proposed for a purpose that is not specifically provided for in this code, such structure, or portion thereof, shall be classified in the group that the occupancy most nearly resembles, according to the fire safety and relative hazard involved, and as approved by the commissioner.
1. Assembly (see Section 303): Groups A-1, A-2, A-3, A-4 and A-5
2. Business (see Section 304): Group B
3. Educational (see Section 305): Group E
4. Factory and Industrial (see Section 306): Groups F-1 and F-2
5. High Hazard (see Section 307): Groups H-1, H-2, H-3, H-4 and H-5
6. Institutional (see Section 308): Groups I-1, I-2, I-3 and I-4
7. Mercantile (see Section 309): Group M
8. Residential (see Section 310): Groups R-1, R-2 and R-3
9. Storage (see Section 311): Groups S-1 and S-2
10. Utility and Miscellaneous (see Section 312): Group U For a listing of occupancy group classifications that corresponds with uses listed in the New York City Zoning Resolution, refer to department rules.
For a listing of occupancy group classifications that corresponds with uses listed in the New York City Zoning Resolution, refer to department rules.
Section BC 303. Assembly Group A
303.1 Assembly Group A.
Assembly Group A occupancy includes, among others, the use of a building or structure or a portion thereof, excluding a dwelling unit, for the gathering of any number of persons for purposes such as civic, social or religious functions, recreation, food or drink consumption, awaiting transportation, or similar group activities; or when occupied by 75 persons or more for educational or instructional purposes.
303.1.1 Definitions.
The following term is defined in Chapter 2:
PLACE OF ASSEMBLY.
303.1.2 Buildings and nonaccessory tenant spaces.
A building or nonaccessory tenant space used for assembly purposes with an occupant load of fewer than 75 persons shall be classified as a Group B occupancy, except that the number of plumbing fixtures for such a building or space is permitted to be calculated in accordance with the requirements for assembly occupancies.
303.1.3 Accessory assembly spaces.
A room or space used for assembly purposes with an occupant load of fewer than 75 persons and accessory to another occupancy shall be classified as a Group B occupancy or as part of that occupancy, except that the number of plumbing fixtures for such a room or space is permitted to be calculated in accordance with the requirements for assembly occupancies. Assembly occupancies shall include the following:
303.2 Assembly Group A-1.
Group A-1 occupancy includes assembly uses, usually with fixed seating, intended for the production and viewing of the performing arts or motion pictures including, but not limited to:
Motion picture theaters
Symphony and concert halls
Television and radio studios admitting an audience
Theaters
303.3 Assembly Group A-2.
Group A-2 occupancy includes assembly uses intended for food and/or drink consumption including, but not limited to:
Banquet halls
Cabarets
Casinos (gaming areas)
Nightclubs, including dance halls
Restaurants, cafeterias (except as provided for in A-3), and similar dining facilities
Restaurants
Taverns and bars
303.4 Assembly Group A-3.
Group A-3 occupancy includes assembly uses intended for worship, recreation or amusement and other assembly uses not classified elsewhere in Group A including, but not limited to:
Amusement arcades
Art galleries
Bowling alleys
Cafeterias for children up to and including the 12th grade
Classrooms and instructional rooms with 75 persons or more; such rooms with fewer than 75 persons shall be classified as Group B or E
Community halls
Courtrooms
Custodial care facilities with 75 or more persons, providing care to persons over the age of 2, where no more than four occupants are incapable of responding to an emergency situation without physical assistance from staff
Dance studio or instruction (not including food or drink consumption)
Exhibition halls
Funeral parlors
Gymnasiums (without spectator seating)
Indoor swimming pools (without spectator seating)
Indoor tennis courts (without spectator seating)
Lecture halls
Museums
Places of religious worship (Houses of worship)
Pool and billiard parlors
School auditoriums
Waiting areas in transportation terminals
303.5 Assembly Group A-4.
Group A-4 occupancy includes assembly uses intended for viewing of indoor sporting events and activities with spectator seating including, but not limited to:
Arenas
Skating rinks
Swimming pools
Tennis courts
303.6 Assembly Group A-5.
Group A-5 occupancy includes assembly uses intended for participation in or viewing outdoor activities including, but not limited to:
Amusement park structures
Bleachers
Grandstands
Stadiums
303.7 Certificate of Operation.
A Certificate of Operation shall be required, as per Section 28-117.1, for the following assembly occupancies:
1. Indoor assembly occupancies used or intended for use by 75 persons or more, including open spaces at 20 feet (6096 mm) or more above or below grade plane, such as roofs or roof terraces.
2. Outdoor assembly occupancies used and intended for use by 200 persons or more.
Section BC 304. Business Group B
304.1 Business Group B.
Business Group B occupancy includes, among others, the use of a building or structure, or a portion thereof, for office, professional, service-type transactions, or for conducting public or civic services, including the incidental storage of records and accounts and the incidental storage of limited quantities of stocks of goods for office use or purposes. Business Group B occupancies shall include, but not be limited to, the following:
Airport traffic control towers
Ambulatory care facilities
Animal hospitals, kennels, pounds, veterinary clinics and pet shops
Banks
Barber and beauty shops
Civic administration offices
Clinic-outpatient, including group medical centers, and neighborhood family care centers
Custodial care facilities with fewer than 75 persons, providing care to persons over the age of 2, where no more than four occupants are incapable of responding to an emergency situation without physical assistance from staff
Dry cleaning and laundries; pick-up and delivery stations and self-service
Educational occupancies for students above the 12th grade, where not classified in Group A. Such occupancy may be used occasionally for educational purposes offered to children through the 12th grade
Electronic data processing
Laboratories; nonproduction testing and research, as per Section 427
Libraries when not classified in Group E
Motor vehicle showrooms
Offices
Post offices
Photocopying and printing shops using electronic printing equipment
Professional services (architects, attorneys, dentists, physicians, engineers, etc.)
Radio and television stations not admitting an audience
Telephone exchanges
Training and skill development not in a school or academic program (this shall include, but not be limited to, tutoring centers, martial arts studios, gymnastics and similar uses regardless of the ages served, and where not classified as a Group A occupancy)
(Am. L.L. 2015/078, 9/2/2015 , eff. 12/31/2015 )
304.2 Definitions.
The following terms are defined in Chapter 2:
AMBULATORY CARE FACILITY.
CLINIC, OUTPATIENT.
Section BC 305. Educational Group E
305.1 Educational Group E.
Educational Group E occupancy includes, among others, the use of a building or structure, or a portion thereof, by five or more persons at any one time for educational purposes offered to children through the 12th grade and where no more than two children are under the age of 2, including but not limited to, the following:
Academies
Day care facilities where no more than two children are under the age of 2
Libraries accessory to Group E occupancies
Schools
Exceptions:
1. Classrooms and instructional rooms with 75 or more persons shall be classified as Group A-3.
2. Day care services provided within a dwelling unit as described in Section 310.
3. Custodial care facilities with up to 30 children under the age of 2 are permitted to be classified as Group E when the rooms where such children are cared for are located on the level of exit discharge and each of these child care rooms has an exit door directly to the exterior.
305.2 Reserved.
Section BC 306. Factory Group F
306.1 Factory Industrial Group F.
Factory Industrial Group F occupancy includes, among others, the use of a building or structure, or a portion thereof, for assembling, disassembling, fabricating, finishing, manufacturing, packaging, repair, cleaning, laundering or processing operations that are not classified as a Group H hazardous occupancy. Factory Industrial Group F occupancy also includes certain mechanical and/or electrical equipment rooms in accordance with Section 306.3.
306.2 Moderate-hazard factory industrial, Group F-1.
Factory industrial uses that are not classified as Factory Industrial F-2 Low Hazard shall be classified as F-1 Moderate Hazard and shall include, but not be limited to, the following:
Aircraft (manufacturing, not to include repair)
Aircraft repairs
Automobiles and other motor vehicles, manufacturing
Automobiles and other motor vehicles, repairs
Bakeries
Beverages; over 16-percent alcohol content
Boats
Boat repairs
Brooms or brushes
Canvas or similar fabric
Carpets and rugs
Carpets and rugs, cleaning, using or storing solvents having a flash point between 100°F (38°C) and 138.2°F (59°C) (Tag closed cup)
Clothing
Disinfectants
Dry cleaning and dyeing using or storing solvents having a flash point between 100°F (38°C) and 138.2°F (59°C) (Tag closed cup)
Electric generation plants
Electrical substations
Engines (including rebuilding)
Food processing, except meat slaughtering or preparation of fish for packing
Food processing establishments and commercial kitchens not adjoining a restaurant, cafeteria or similar dining facilities
Furniture
Hemp products
Jute products
Laboratories; for production (moderate-hazard), that may involve the synthesis or storage of materials that constitute a physical or health hazard in quantities below those found in Tables 307.1(1) and 307.1(2)
Leather products
Metals; finishing, plating, grinding, sharpening, polishing, cleaning, rustproofing, heat treatment, or similar processes
Millwork (sash and door)
Motion pictures filming (without spectators)
Musical instruments
Optical goods
Paper mills or products
Photographic film
Plastic products
Printing or publishing
Recreational vehicles
Refuse incineration
Shoes
Soaps and detergents
Textiles
Tobacco
Trailers
Upholstering
Wood; distillation
Woodworking (cabinet) using no more than 2 quarts (1.9 L) per day or storing no more than 20 gallons (75.7 L) of paint, varnish, lacquer or shellac
306.3 Low-hazard factory industrial, Group F-2.
Factory industrial uses that involve the cleaning, laundering, fabrication or manufacturing of noncombustible materials that during finishing, packing or processing do not involve a significant fire hazard shall be classified as F-2 occupancies and shall include, but not be limited to, the following:
Appliances
Athletic equipment
Automobile laundries
Automobile wrecking establishments
Beverages; up to and including 16-percent alcohol content; bottling works
Beverages; non-alcoholic
Bicycles
Brick and masonry
Business machines
Cameras and photo equipment
Carpets and rugs, cleaning, using or storing solvents having a flash point above 138.2°F (59°C) (Tag closed cup)
Ceramic products
Commercial kitchens adjoining restaurants, cafeterias (including those classified in Group A-3), or similar dining facilities
Construction and agricultural machinery
Dry cleaning and dyeing using or storing solvents having a flash point above 138.2°F (59°C) (Tag closed cup)
Electronics
Food processing; meat slaughtering or preparation of fish for packing
Foundries
Glass products
Gypsum
Ice
Laboratories; for production (low-hazard), that may involve the synthesis or storage of materials that constitute a physical or health hazard in quantities below those found in Tables 307.1(1) and 307.1(2)
Laundries
Machinery
Mechanical and/or electrical equipment rooms that are neither identified as incidental uses in Table 509 nor classified as the occupancy within which they are located per section 508.1
Metal products (fabrication and assembly), not including flammable metals and alloys listed in Section 307
Plastic products; non-flammable
Printing; incidental to primary use, area not exceeding 2,000 square feet (185.8 m 2 )
Television filming (without spectators)
306.4 Location restrictions.
Locations of spaces classified in Factory Group F may be restricted within a building containing a Group R occupancy pursuant to Section 510.8.
Section BC 307. High-Hazard Group H
307.1 High-hazard Group H.
High-hazard Group H occupancy includes, among others, the use of a building or structure, or a portion thereof, that involves the manufacturing, processing, generation or storage of materials that constitute a physical or health hazard in quantities in excess of those allowed in control areas complying with Section 414, based on the maximum allowable quantity limits for control areas set forth in Tables 307.1(1) and 307.1(2). Hazardous occupancies are classified in Groups H-1, H-2, H-3, H-4 and H-5 and shall be in accordance with this section, the requirements of Section 415 and the New York City Fire Code.
307.1.1 Uses other than Group H.
An occupancy that stores, uses or handles hazardous materials as described in one or more of the following items shall not be classified as Group H, but shall be classified as the occupancy that it most nearly resembles.
1. Buildings and structures occupied for the application of flammable finishes, provided that such buildings or areas conform to the requirements of the New York City Fire Code and Section 416 of this code.
2. Wholesale and retail sales and storage of flammable and combustible liquids in mercantile occupancies conforming to the New York City Fire Code.
3. Closed piping system containing flammable or combustible liquids or gases utilized for the operation of machinery or equipment.
4. Cleaning establishments that utilize combustible liquid solvents having a flash point of 140°F (60°C) or higher in closed systems employing equipment listed by an approved testing agency, provided that this occupancy is separated from all other areas of the building by 1-hour fire barriers constructed in accordance with Section 707 or 1-hour horizontal assemblies constructed in accordance with Section 711, or both.
5. Cleaning establishments that utilize a liquid solvent having a flash point at or above 200°F (93°C).
6. Liquor stores and distributors without bulk storage.
7. Refrigeration systems.
8. The storage or utilization of materials for agricultural purposes on the premises.
9. Stationary batteries utilized for facility emergency or standby power, uninterruptable power supply or telecommunication facilities, provided that the batteries are provided with safety venting caps and ventilation is provided in accordance with the New York City Mechanical Code.
10. Corrosive personal or household products in their original packaging used in retail display.
11. Commonly used corrosive building materials.
12. Buildings and structures occupied for aerosol storage shall be classified as Group S-1, provided that such buildings conform to the requirements of the New York City Fire Code.
13. Display and storage of nonflammable solid and nonflammable or noncombustible liquid hazardous materials in quantities not exceeding the maximum allowable quantity per control area in Group M or S occupancies complying with Section 414.2.5.
14. The storage of black powder, smokeless propellant and small arms primers in Groups M and R-3 and special industrial explosive devices in Groups B, F, M and S, provided such storage conforms to the quantity limits and requirements prescribed in the New York City Fire Code.
15. Laboratories for nonproduction testing, research, experimental, instructional or educational purposes, in compliance with Section 427.
Table 307.1(1) Maximum Allowable Quantity per Control Area of Hazardous Materials Posing a Physical Hazard a, j, m, n, q
Material Class Group When the Maximum Allowable Quantity Is Exceeded q Storage b Use-Closed Systems b Use-Open Systems b Solid Pounds (cubic feet) Liquid Gallons (pounds) Gas SCF Solid Pounds (cubic feet) Liquid gallons (pounds) Gas SCF Solid Pounds (cubic feet) Liquid gallons (pounds) Combustible Liquid c, i, r II IIIA IIIB H-2 or H-3 H-2 or H-3 Not Applicable Not Applicable 120 d, e 330 d, e 13,200 e, f Not Applicable Not Applicable 120 d 330 d 13,200 f Not Applicable Not Applicable 30 d 80 d 3,300 f Combustible fiber Loose Baled s H-3 (100) (1,000) Not Applicable Not Applicable (100) (1,000) Not Applicable Not Applicable (20) (200) Not Applicable Cryogenics Flammable Not Applicable H-2 Not Applicable 45 d Not Applicable Not Applicable 45 d Not Applicable Not Applicable 10 d Cryogenics Oxidizing Not Applicable H-3 Not Applicable 45 d Not Applicable Not Applicable 45 d Not Applicable Not Applicable 10 d Explosives Division 1.1 Division 1.2 Division 1.3 Division 1.4 Division 1.4G Division 1.5 Division 1.6 H-1 H-1 H-1 or H-2 H-3 H-3 H-1 H-1 1 e, g 1 e, g 5 e, g 50 e, g 125 d, e, l 1 e, g 1 d, e, g (1) e, g (1) e, g (5) e, g (50) e, g Not Applicable (1) e, g Not Applicable Not Applicable 0.25 g 0.25 g 1 g 50 g Not Applicable 0.25 g Not Applicable (0.25) g (0.25) g (1) g (50) g Not Applicable (0.25) g Not Applicable Not Applicable 0.25 g 0.25 g 1 g Not Applicable Not Applicable 0.25 g Not Applicable (0.25) g (0.25) g (1) g Not Applicable Not Applicable (0.25) g Not Applicable Flammable gas Gaseous Liquefied H-2 Not Applicable Not Applicable (150) d, e 1,000 d, e Not Applicable Not Applicable Not Applicable (150) d, e 1,000 d, e Not Applicable Not Applicable Not Applicable Flammable liquids c, k IA o IB and IC H-2 or H-3 Not Applicable 30 d, e 120 d, e Not Applicable Not Applicable 30 d 120 d Not Applicable Not Applicable 10 d 30 d Combination Flammable liquid (IA o , IB, IC) Not Applicable H-2 or H-3 Not Applicable 120 d, e, h Not Applicable Not Applicable 120 d, h Not Applicable Not Applicable 30 d, h Flammable solid s Not Applicable H-3 Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Pigs, ingots, billets, heavy castings 1,000 d, e 1,000 d 1,000 d Light castings, light metallic products 125 d, e 125 d 25 d Scraps, shavings, powders, dusts 1 d, e 1 d 1 d All others 125 d, e 125 d 25 d Inert Gas Gaseous Liquefied Not Applicable Not Applicable Not Applicable Not Limited Not Applicable Not Applicable Not Limited Not Applicable Not Applicable Cryogenic Inert Not Applicable Not Applicable Not Applicable Not Applicable Not Limited Not Applicable Not Applicable Not Limited Not Applicable Not Applicable Organic peroxide p Unclassified Detonable I II III IV V H-1 H-2 H-3 H-3 Not Applicable Not Applicable 1 e, g 5 d, e 50 d, e 125 d, e Not Limited Not Limited (1) e, g (5) d, e (50) d, e (125) d, e Not Limited Not Limited Not Applicable 0.25 g 1 d 50 d 125 d Not Limited Not Limited (0.25) g (1) d (50) d (125) d Not Limited Not Limited Not Applicable 0.25 g 1 d 10 d 25 d Not Limited Not Limited (0.25) g (1) d (10) d (25) d Not Limited Not Limited Oxidizer 4 3 k 2 1 H-1 H-2 H-3 H-3 1 g 10 d, e 250 d, e 4,000 e, f (1) e, g (10) d, e (250) d, e (4,000) e, f Not Applicable 0.25 g 2 d 250 d 4,000 f (0.25) g (2) d (250) d (4,000) f Not Applicable 0.25 g 2 d 50 d 1,000 f (0.25) g (2) d (50) d (1,000) f Oxidizing gas Gaseous Liquefied H-3 Not Applicable Not Applicable (150) d, e 1,500 d, e Not Applicable Not Applicable Not Applicable (150) d, e 1,500 d, e Not Applicable Pyrophoric material p detonable Not Applicable H-1 1 e, g (1) e, g 10 e, g 0.25 g (0.25) g 2 e, g 0 0 Pyrophoric material nondetonable Not Applicable H-2 4 e, g (4) e, g 50 e, g 1 g (1) g 10 e, g 0 0 Unstable (reactive) p detonable 4 3 H-1 H-1 1 e, g 1 e, g (1) e, g (1) e, g 10 e, g 10 e, g 0.25 g 0.25 g (0.25) g (0.25) g 2 e, g 2 e, g 0.25 g 0.25 g (0.25) g (0.25) g Unstable (reactive) nondetonable 4 3 2 1 H-1 H-1 or H-2 H-3 Not Applicable 1 e, g 5 d, e 50 d, e Not Limited (1) e, g (5) d, e (50) d, e Not Limited 10 e, g 50 d, e 250 d, e 750 d, e 0.25 g 1 d 50 d Not Limited (0.25) g (1) d (50) d Not Limited 2 e, g 10 d, e 250 d, e Not Limited 0.25 g 1 d 10 d Not Limited (0.25) g (1) d (10) d Not Limited Water-reactive detonable p 3 2 H-1 H-1 1 e, g 1 e, g (1) e, g (1) e, g Not Applicable 0.25 g 0.25 g (0.25) g (0.25) g Not Applicable 0.25 g 0.25 g (0.25) g (0.25) g Water-reactive nondetonable 3 2 1 H-2 H-3 Not Applicable 5 d, e 50 d, e Not Limited (5) d, e (50) d, e Not Limited Not Applicable 5 d 50 d Not Limited (5) d (50) d Not Limited Not Applicable 1 d 10 d Not Limited (1) d (10) d Not Limited
For SI: 1 cubic foot = 0.028 m 3 , 1 pound = 0.454 kg, 1 gallon = 3.785 L.
a. For use of control areas, see the New York City Fire Code and Section 414.2 of this code .
b. The aggregate quantity in storage, handling and use shall not exceed the quantity listed for storage.
c. The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited providing the liquids are packaged in individual containers not exceeding 1.3 gallons. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics containing not more than 50 percent by volume of water-miscible liquids with the remainder of the solutions not being flammable shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons.
d. Maximum allowable quantities, except for liquefied petroleum gas and flammable liquid motor fuel, shall be increased 100 percent in buildings protected throughout by a sprinkler system. Where Note e also applies, the increase for both notes shall be applied accumulatively.
e. Maximum allowable quantities, except for liquefied petroleum gas and flammable liquid motor fuel, shall be increased 100 percent when stored in approved storage cabinets, gas cabinets, exhausted enclosures or listed safety cans. Listed safety cans shall be in accordance with the New York City Fire Code . Where Note d also applies, the increase for both notes shall be applied accumulatively.
f. Quantities shall not be limited in a building protected throughout by a sprinkler system.
g. Allowed only in buildings protected throughout by a sprinkler system.
h. Containing not more than the maximum allowable quantity per control area of Class IA, Class IB or Class IC flammable liquids.
i. The maximum allowable quantity shall not apply to fuel oil storage that complies with the requirements of Section 1305 of the New York City Mechanical Code .
j. Quantities shown in the table in parentheses have the units shown in parentheses at the head of the column.
k. A maximum quantity of 200 pounds of solid or 20 gallons of liquid Class 3 oxidizers is allowed when such materials are necessary for maintenance and operation of equipment when the storage containers and the manner of storage are approved.
l. Reserved.
m. For gallons of liquids, divide the amount in pounds by 10 in accordance with the New York City Fire Code .
n. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with the New York City Fire Code .
o. For purposes of this table, gasoline and other flammable liquid motor fuels are classified as a Class IA flammable liquid.
p. Unclassified detonable organic peroxides, detonable pyrophoric materials, detonable unstable (reactive) materials and detonable water-reactive materials shall be treated as explosives for purposes of storage, handling and use in accordance with the New York City Fire Code.
q. The maximum allowable quantities shall be limited by the New York City Fire Code for non-production laboratories classified as Occupancy Group B.
r. For storage of flammable and combustible liquids in Group M occupancy, see the New York City Fire Code.
s. Densely-packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class.
Table 307.1(2) Maximum Allowable Quantity per Control Area of Hazardous Material Posing a Health Hazard a, b, c, i, j
Material Storage d Use-Closed Systems d Use-Open Systems d Solid pounds Liquid gallons (pounds) e, f Gas SCF e (pounds) Solid pounds e Liquid gallons (pounds) e Gas SCF e (pounds) Solid pounds e Liquid gallons (pounds) e Corrosive 5,000 500 Gaseous 810 f Liquefied (150) h 5,000 500 Gaseous 810 f Liquefied (150) h 1,000 100 Highly toxic 10 (10) h Gaseous 20 g Liquefied (4) g, h 10 (10) h Gaseous 20 g Liquefied (4) g, h 3 (3) h Toxic 500 (500) h Gaseous 810 f Liquefied (150) f, h 500 (500) h Gaseous 810 f Liquefied (150) f, h 125 (125) h
For SI: 1 cubic foot = 0.028 m 3 , 1 pound = 0.454 kg, 1 gallon = 3.785 L.
a. For use of control areas, see the New York City Fire Code and Section 414.2 of this code
b. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics, containing not more than 50 percent by volume of water-miscible liquids and with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons.
c. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with the New York City Fire Code .
d. The aggregate quantity in storage, handling and use shall not exceed the quantity listed for storage.
e. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1. Where Note f also applies, the increase for both notes shall be applied accumulatively.
f. Maximum allowable quantities may be increased 100 percent when stored in approved storage cabinets, gas cabinets or exhausted enclosures as specified in the New York City Fire Code . Where Note e also applies, the increase for both notes shall be applied accumulatively.
g. Allowed only when stored in approved exhausted gas cabinets or exhausted enclosures as specified in the New York City Fire Code .
h. Quantities shown in the table in parenthesis have the units shown in parenthesis at the head of the column.
i. For gallons of liquids, divide the amount in pounds by 10 in accordance with the New York City Fire Code .
j. The maximum allowable quantities shall be limited by Section 427 for chemical laboratories classified as Occupancy Group B and operating as nonproduction facilities for testing, research, experimental, instructional or education purposes.
307.1.2 Hazardous materials.
Hazardous materials in any quantity shall conform to the requirements of this code, including Section 414 of this code, and the New York City Fire Code.
307.2 Definitions.
The following terms are defined in Chapter 2:
AEROSOL.
Level 1.
Level 2.
Level 3.
BALED COTTON.
BALED COTTON, DENSELY PACKED.
BARRICADE.
Artificial barricade.
Natural barricade.
BOILING POINT.
CLOSED SYSTEM.
COMBUSTIBLE DUST.
COMBUSTIBLE FIBERS.
COMBUSTIBLE LIQUID.
Class II.
Class IIIA.
Class IIIB.
COMPRESSED GAS.
CONTROL AREA.
CORROSIVE MATERIAL.
CRYOGENIC FLUID.
DAY BOX.
DEFLAGRATION.
DETONATION.
DISPENSING.
EXPLOSION.
EXPLOSIVE.
High explosive.
Low explosive.
Mass-detonating explosives.
UN/DOTn Class 1 explosives.
Division 1.1.
Division 1.2.
Division 1.3.
Division 1.4.
Division 1.5.
Division 1.6.
FIREWORKS.
Fireworks, 1.3G.
Fireworks, 1.4G.
FLAMMABLE GAS.
FLAMMABLE LIQUEFIED GAS.
FLAMMABLE LIQUID.
Class IA.
Class IB.
Class IC.
FLAMMABLE MATERIAL.
FLAMMABLE SOLID.
FLASH POINT.
HANDLING.
HAZARDOUS MATERIALS.
HEALTH HAZARD.
HIGHLY TOXIC MATERIAL.
INCOMPATIBLE MATERIALS.
INERT GAS.
OPEN SYSTEM.
ORGANIC PEROXIDE.
Class I.
Class II.
Class III.
Class IV.
Class V.
Unclassified detonable.
OXIDIZER.
Class 4.
Class 3.
Class 2.
Class 1.
OXIDIZING GAS.
PHYSICAL HAZARD.
PYROPHORIC MATERIAL.
PYROTECHNIC MATERIAL.
STANDARD CUBIC FEET (SCF).
TOXIC MATERIAL.
UNSTABLE (REACTIVE) MATERIAL.
Class 4.
Class 3.
Class 2.
Class 1.
WATER-REACTIVE MATERIAL.
Class 3.
Class 2.
Class 1.
307.3 High-hazard Group H-1.
Buildings and structures containing materials that pose a detonation hazard shall be classified as Group H-1. Such materials shall include, but not be limited to, the following:
Detonable pyrophoric materials
Explosives:
Division 1.1
Division 1.2
Division 1.3
Division 1.4
Division 1.5
Division 1.6
Organic peroxides, unclassified detonable
Oxidizers, Class 4
Unstable (reactive) materials, Class 3 detonable and Class 4
307.3.1 Occupancies containing explosives not classified as H-1.
The following occupancies containing explosive materials shall be classified as follows:
1. Division 1.3 explosive materials that are used and maintained in a form where either confinement or configuration will not elevate the hazard from a mass fire to mass explosion hazard shall be allowed in H-2 occupancies.
2. Articles, including articles packaged for shipment, that are not regulated as a Division 1.4 explosive under Bureau of Alcohol, Tobacco, Firearms and Explosives regulations, or unpackaged articles used in process operations that do not propagate a detonation or deflagration between articles shall be allowed in H-3 occupancies.
No part of this section shall be construed to authorize the manufacture, storage, sale or use of explosives, including fireworks, if otherwise prohibited by the New York City Fire Code and unless in compliance with the requirements of the New York City Fire Code.
307.4 High-hazard Group H-2.
Buildings and structures containing materials that pose a deflagration hazard or a hazard from accelerated burning shall be classified as Group H-2. Such materials shall include, but not be limited to, the following:
Class I, II or IIIA flammable or combustible liquids that are used or stored in normally open containers or systems, or in closed containers or systems pressurized at more than 15 pounds per square inch gauge (103.4 kPa)
Combustible dusts where manufactured, generated or used in such a manner that the concentration and conditions create a fire or explosion hazard based on information prepared in accordance with Section 414.1.3
Cryogenic fluids, flammable
Flammable gases
Organic peroxides, Class I
Oxidizers, Class 3, that are used or stored in normally open containers or systems, or in closed containers or systems pressurized at more than 15 pounds per square inch gauge (103 kPa)
Pyrophoric liquids, solids and gases, nondetonable
Unstable (reactive) materials, Class 3, nondetonable
Water-reactive materials, Class 3, nondetonable
No part of this section shall be construed to authorize an LPG-distribution facility if otherwise prohibited by the New York City Fire Code.
307.5 High-hazard Group H-3.
Buildings and structures containing materials that readily support combustion or that pose a physical hazard shall be classified as Group H-3. Such materials shall include, but not be limited to, the following:
Class I, II or IIIA flammable or combustible liquids that are used or stored in normally closed containers or systems pressurized at 15 pounds per square inch gauge (103 kPa) or less
Combustible fibers, other than densely packed baled cotton, where manufactured, generated or used in such a manner that the concentration and conditions create a fire or explosion hazard based on information prepared in accordance with Section 414.1.3
Cryogenic fluids, oxidizing
Flammable solids
Organic peroxides, Class II and III
Oxidizers, Class 1 and 2
Oxidizing gases
Unstable (reactive) materials, Class 2
Water-reactive materials, Class 2, nondetonable
307.6 High-hazard Group H-4.
Buildings and structures containing materials that are health hazards shall be classified as Group H-4. Such materials shall include, but not be limited to, the following:
Corrosives
Highly toxic materials
Toxic materials
307.7 High-hazard Group H-5.
Semiconductor fabrication facilities and comparable research and development areas in which hazardous production materials (HPM) are used and the aggregate quantity of materials is in excess of those listed in Tables 307.1(1) and 307.1(2) shall be classified as Group H-5. Such facilities and areas shall be designed and constructed in accordance with Section 415.11.
307.8 Multiple hazards.
Buildings and structures containing a material or materials representing hazards that are classified in one or more of Groups H-1, H-2, H-3 and H-4 shall conform to the code requirements for each of the occupancies so classified.
Section BC 308. Institutional Group I
308.1 Institutional Group I.
Institutional Group I occupancy includes, among others, the use of a building or structure, or a portion thereof, in which care or supervision is provided to persons who are or are not capable of self-preservation without physical assistance or in which persons are detained for penal or correctional purposes or in which the liberty of the occupants is restricted. Institutional occupancies shall be classified as Group I-1, I-2, I-3 or I-4.
308.2 Definitions.
This section contains provisions for definitions of terms defined elsewhere in this code as well as the terms with definitions specific to this section.
308.2.1 Terms defined elsewhere in this code.
The following terms are defined in Chapter 2:
24-HOUR BASIS.
CARE SUITE.
INCAPABLE OF SELF-PRESERVATION.
308.2.2 Definitions specific to this section.
The following words and terms shall, for the purposes of this section, have the meanings shown herein:
CHILD CARE FACILITIES. Facilities that provide care on a 24-hour basis to more than 5 children, under the age of 2.
DETOXIFICATION FACILITIES. Facilities that serve patients who are provided treatment for substance abuse on a 24-hour basis and who are incapable of self-preservation or who are harmful to themselves or others.
HOSPITALS AND PSYCHIATRIC CENTERS. Buildings or portions thereof used on a 24-hour basis for the medical, psychiatric, obstetrical or surgical treatment of inpatients who are incapable of self-preservation.
NURSING HOMES. Nursing homes are long-term care facilities on a 24-hour basis, including both intermediate care facilities and skilled nursing facilities, serving more than five persons and any of the persons are incapable of self-preservation.
308.3 Institutional Group I-1.
Institutional Group I-1 occupancy shall include buildings, structures or parts thereof housing persons, on a 24-hour basis, who because of age, mental disability or other reasons, live in a supervised residential environment that provides personal care services. The occupants are capable of self-preservation and capable of responding to an emergency situation without physical assistance from staff. Such occupancy shall be subject to the New York State Multiple Dwelling Law. This group shall include, but not be limited to, the following:
Adult homes, where occupants are capable of self-preservation (see Section 308.3.1)
Alcohol and drug abuse rehabilitation centers
Assisted living facilities
Community Residences or Intermediate Care Facilities (see Section 308.3.2)
Congregate care facilities
Convalescent facilities
Enriched housing, where occupants are capable of self-preservation (see Section 308.3.1)
Halfway houses
Overnight facilities for children where all supervised occupants are under the age of 18, with no more than two children under the age of 2
Residential care facilities
Social rehabilitation facilities
308.3.1 Adult homes and enriched housing.
Adult homes and enriched housing facilities operated pursuant to and meeting the additional construction requirements of Section 460 of the New York State Social Services Law and regulations of the New York State Department of Health offering care on a 24-hour basis to persons capable of self-preservation, in the same building, shall be classified as Group I-1.
Exception: Such a facility offering supervised care on a 24-hour basis for no more than 16 occupants capable of self preservation, in the same building, may be classified in Group R in accordance with Section 310.
308.3.2 Community Residences or Intermediate Care Facilities.
Community Residences or Intermediate Care Facilities, operated pursuant to and meeting the additional construction requirements of the New York State Mental Hygiene Law and applicable regulations of the New York State Office of Mental Health and Office for People with Developmental Disabilities shall be classified as Group I-1.
Exceptions: Such facilities limited to 14 residents capable of self-preservation and three staff members per dwelling unit shall be classified as:
1. Group R-1, where such facility does not occupy more than two dwelling units in a residential building classified as R-1 of Type I or II construction, or one dwelling unit in any other type of construction, and occupied on a transient basis; or
2. Group R-2 where such facility does not occupy more than two dwelling units in a residential building classified R-2 of Type I or II construction, or one dwelling unit in any other type of construction, and occupied on a long-term basis; or
3. Group R-3 where the number of dwelling units in the building does not exceed two.
308.4 Institutional Group I-2.
Institutional Group I-2 shall include buildings and structures used for medical, surgical, psychiatric, nursing or personal care on a 24-hour basis or overnight of more than two children under the age of 2, or more than three persons who are not capable of self-preservation and not capable of responding to an emergency situation without physical assistance from staff. This group shall include, but not be limited to, the following:
Adult homes, where occupants are not capable of self-preservation (see Section 308.4.1)
Child care facilities
Community Residences or Intermediate Care Facilities, where occupants are not capable of self preservation, operated pursuant to and meeting the additional construction requirements of the New York State Mental Hygiene Law and applicable regulations of the New York State Office of Mental Health and Office for people with Developmental Disabilities
Detoxification facilities
Exception: Such a facility offering care on a 24-hour basis for three or fewer persons who are not capable of self-preservation may occupy not more than one dwelling unit in a Group R occupancy.
Enriched Housing, where occupants are not capable of self-preservation (see Section 308.4.1)
Hospitals
Nursing homes
Psychiatric centers where patients are not under restraint
308.4.1 Adult homes and enriched housing.
Adult homes and enriched housing facilities operated pursuant to and meeting the additional construction requirements of Section 460 of the New York State Social Services Law and regulations of the New York State Department of Health offering care on a 24-hour basis to persons not capable of self-preservation, in the same building, shall be classified as Group I-2.
308.5 Institutional Group I-3.
Institutional Group I-3 occupancy shall include buildings and structures that are inhabited by more than five persons who are under restraint or security. A Group I-3 facility is occupied by persons who are generally incapable of self-preservation due to security measures not under the occupants' control. This group shall include, but not be limited to, the following:
Correctional centers
Detention centers
Jails
Prerelease centers
Prisons
Psychiatric centers where patients are under restraint
Reformatories
Buildings of Group I-3 shall be classified as one of the occupancy conditions specified in Sections 308.5.1 through 308.5.5.
308.5.1 Condition 1.
This occupancy condition shall include buildings in which free movement is allowed from sleeping areas, and other spaces where access or occupancy is permitted, to the exterior via means of egress without restraint. A Condition 1 facility is permitted to be constructed as Group R.
308.5.2 Condition 2.
This occupancy condition shall include buildings in which free movement is allowed from sleeping areas and any other occupied smoke compartment to one or more other smoke compartments. Egress to the exterior is impeded by locked exits.
308.5.3 Condition 3.
This occupancy condition shall include buildings in which free movement is allowed within individual smoke compartments, such as within a residential unit comprised of individual sleeping units and group activity spaces, where egress is impeded by remote controlled release of means of egress from such a smoke compartment to another smoke compartment.
308.5.4 Condition 4.
This occupancy condition shall include buildings in which free movement is restricted from an occupied space. Remote-controlled release is provided to permit movement from sleeping units, activity spaces and other occupied areas within the smoke compartment to other smoke compartments.
308.5.5 Condition 5.
This occupancy condition shall include buildings in which free movement is restricted from an occupied space. Staff-controlled manual release is provided to permit movement from sleeping units, activity spaces and other occupied areas within the smoke compartment to other smoke compartments.
308.6 Institutional Group I-4.
Institutional Group I-4 occupancy shall include custodial care facilities providing care to more than two children under the age of 2, or to more than four persons over the age of 2 who are not capable of responding to an emergency situation without physical assistance from the staff. Such occupancy shall include, but not be limited to, adult custodial care facilities and day nurseries.
Exceptions:
1. Custodial care facility as described in Section 303.
2. Custodial care facility as described in Section 304.
3. Custodial care facility as described in Exception 3 of Section 305.1.
4. Such facility providing care within a dwelling unit as described in Section 310.
5. Such facility providing care to children under the age of 2 in religious houses of worship during religious functions.
Section BC 309. Mercantile Group M
309.1 Mercantile Group M.
Mercantile Group M occupancy includes, among others, the use of a building or structure or a portion thereof for the display and sale of merchandise, and involves stocks of goods, wares or merchandise incidental to such purposes and accessible to the public. Mercantile occupancies shall include, but not be limited to, the following:
Department stores
Drug stores
Markets
Motor fuel-dispensing facilities
Retail or wholesale stores
Sales rooms
309.2 Quantity of hazardous materials.
The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials stored or displayed in a single control area of a Group M occupancy shall not exceed the quantities in Table 414.2.5(1).
Section BC 310. Residential Group R
310.1 Residential Group R.
Residential Group R includes, among others, the use of a building or structure, or a portion thereof, for dwelling or sleeping purposes when not classified as an Institutional Group I. Buildings containing 3 or more dwelling units shall be subject to the New York State Multiple Dwelling Law. Residential occupancies shall be classified as Groups R-1, R-2, or R-3.
310.2 Definitions.
The following terms are defined in Chapter 2:
APARTMENT.
APARTMENT, STUDENT.
BOARDER (ROOMER, LODGER).
CONGREGATE LIVING UNIT.
CUSTODIAL CARE FACILITY.
DWELLING.
DWELLING, MULTIPLE.
DWELLING, ONE-FAMILY.
DWELLING, TWO-FAMILY.
DWELLING UNIT.
FAMILY.
GROUP HOME.
PERSONAL CARE SERVICE.
RESIDENTIAL CARE/ASSISTED LIVING FACILITIES.
ROOMING HOUSE.
SLEEPING UNIT.
TRANSIENT.
310.3 Residential Group R-1.
Residential Group R-1 occupancies shall include:
1. Residential buildings or spaces occupied, as a rule, transiently, for a period less than 30 days, as the more or less temporary abode of individuals or families who are lodged with or without meals, including, but not limited to, the following:
Class B multiple dwellings as defined in Section 27-2004 of the New York City Housing Maintenance Code and Section 4 of the New York State Multiple Dwelling Law, where not classified in Group I-1.
Club houses
Hotels (transient)
Motels (transient)
Rooming houses (boarding houses – transient)
Settlement houses
Vacation timeshares
2. College or school student dormitories, except for student apartments classified as an R-2 occupancy
3. Congregate living units owned and operated by a government agency or not-for-profit organization, where the number of occupants in the dwelling unit exceeds the limitations of a family as defined, including, but not limited to, the following:
Adult homes or enriched housing with 16 or fewer occupants requiring supervised care within the same building on a 24-hour basis
Fraternity and sorority houses
Homeless shelters
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
310.4 Residential Group R-2.
Residential Group R-2 occupancies shall include buildings or portions thereof containing sleeping units or more than two dwelling units that are occupied for permanent residence purposes as defined in subparagraph (a) of paragraph 8 of subdivision a of Section 27-2004 of the New York City Housing Maintenance Code. Such occupancy shall be subject to the New York State Multiple Dwelling Law. This group shall include, but not be limited to, the following:
Adult homes or enriched housing with 16 or fewer occupants requiring supervised care on a 24-hour basis in the same building, provided that the number of occupants per dwelling unit does not exceed the definition of a family
Apartment houses
Apartment hotels (nontransient)
Class A multiple dwellings as defined in Section 27-2004 of the New York City Housing Maintenance Code and Section 4 of the New York State Multiple Dwelling Law, where not classified in Group I, including the following:
1. Dwelling units where the resident of the unit provides custodial care to no more than four persons on less than a 24-hour basis and not overnight, where not classified in Group I.
2. Dwelling units where the resident of the unit provides child custodial care as a family day care home registered with the New York City Department of Health and Mental Hygiene in accordance with the New York State Social Services Law, with no more than six children between the ages of 2 and 13, or with no more than five children if any are under the age of 2, receiving supervised care on less than a 24-hour basis and not overnight, where not classified in Group I.
Convents and monasteries with more than 20 occupants in the building
Student apartments
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
310.5 Residential Group R-3.
Residential Group R-3 occupancies shall include buildings or portions thereof containing no more than 2 dwelling units, occupied, as a rule, for shelter and sleeping accommodation on a long-term basis for a month or more at a time, and are not classified in Group R-1, R-2 or I. This group shall include, but not be limited to, the following:
Convents and monasteries with 20 or fewer occupants in the building
Group homes
One- and two-family dwellings, including the following:
1. Dwelling units where the resident of the unit provides custodial care to no more than four persons on less than a 24-hour basis and not overnight.
2. Dwelling units where the resident of the unit provides child custodial care as a family day care home registered with the New York City Department of Health and Mental Hygiene in accordance with the New York State Social Services Law for three to six children for more than three hours per day per child but less than 24 hours per day. A family day care provider may, however, care for seven or eight children at any one time if no more than six of the children are less than school age and such children receive services only during the periods set forth in the New York State Social Services Law.
3. Dwelling units where the resident of the unit provides child custodial care as a group family day care home registered with the New York City Department of Health and Mental Hygiene in accordance with the New York State Social Services Law for seven to 12 children of all ages for more than three hours a day per child but less than 24 hours per day. There may be an additional four children if such children are of school age and such children receive services only during the periods set forth in the New York State Social Services Law.
Section BC 311. Storage Group S
311.1 Storage Group S.
Storage Group S occupancy includes, among others, the use of a building or structure, or a portion thereof, for storage, such as for warehouses, storage rooms, freight depots and distribution centers, when not classified as a hazardous occupancy.
311.1.1 Accessory storage spaces.
A room or space used for storage purposes that is less than 100 square feet (9.3 m 2 ) in area and accessory to another occupancy shall be classified as part of that occupancy. The aggregate area of such rooms or spaces shall not exceed the allowable area limits of Section 508.2.3.
311.2 Moderate-hazard storage, Group S-1.
Storage Group S-1 occupancies are buildings occupied for storing any flammable or combustible materials that are likely to permit the development and production of fire with moderate rapidity including, but not limited to, storage of the following:
Aerosols, Levels 2 and 3
Aircraft hangar (storage and repair)
Bags; cloth, burlap and paper
Bamboos and rattan
Baskets
Belting; canvas and leather
Books and paper in rolls or packs
Boots and shoes
Buttons, including cloth covered, pearl or bone
Cardboard and cardboard boxes
Clothing, woolen wearing apparel
Cordage
Dry boat storage (indoor, not accessory to Group R)
Furniture
Furs
Glues, mucilage, pastes and size
Grains
Horns and combs, other than celluloid
Leather
Linoleum
Lumber
Photo engravings
Resilient flooring
Silks
Soaps
Sugar
Tires, bulk storage of
Tobacco, cigars, cigarettes and snuff
Upholstery and mattresses
Wax candles
311.3 Low-hazard storage, Group S-2.
Storage Group S-2 occupancies include, among others, buildings used for the storage of noncombustible materials such as products on wood pallets or in paper cartons with or without single thickness divisions; or in paper wrappings. Such products are permitted to have a negligible amount of plastic trim, such as knobs, handles or film wrapping. Group S-2 storage uses shall include, but not be limited to, storage of the following:
Asbestos
Beverages up to and including 16-percent alcohol in metal, glass or ceramic containers
Cement in bags
Chalk and crayons
Dairy products in nonwaxed coated paper containers
Dry cell batteries
Electrical coils
Electrical motors
Empty cans
Food products
Foods in noncombustible containers
Fresh fruits and vegetables in nonplastic trays or containers
Frozen foods
Glass
Glass bottles, empty or filled with noncombustible liquids
Gypsum board
Inert pigments
Ivory
Meats
Metal cabinets
Metal desks with plastic tops and trim
Metal parts
Metals
Mirrors
Oil-filled and other types of distribution transformers
Parking garages, open or enclosed
Porcelain and pottery
Stoves
Talc and soapstones
Washers and dryers
Section BC 312. Utility and Miscellaneous Group U
312.1 General.
Buildings and structures of an accessory character and miscellaneous structures not classified in any specific occupancy shall be constructed, equipped and maintained to conform to the requirements of this code commensurate with the fire and life hazard incidental to their occupancy. Group U shall include, but not be limited to, the following:
Carports
Fences more than 6 feet (1829 mm) in height
Private garages as per Section 406.1
Retaining walls
Sheds or greenhouses accessory to Group R-3 occupancies, that are: freestanding, less than 120 square feet (11.15 m 2 ) in area, not permanently affixed to the ground, and used for household goods or items associated with the garden or lawn. Any other shed shall be classified as either S-1 or S-2.
Tanks
Towers
Section BC 401. Scope
401.1 Detailed use and occupancy requirements.
In addition to the occupancy and construction requirements in this code, the provisions of this chapter apply to the special uses and occupancies described herein.
Section BC 402. Covered Mall and Open Mall Buildings
402.1 Applicability.
The provisions of this section shall apply to buildings or structures defined herein as covered or open mall buildings not exceeding three floor levels at any point nor more than three stories above grade plane. Except as specifically required by this section, covered and open mall buildings shall meet applicable provisions of this code.
Exceptions:
1. Foyers and lobbies of Groups B, R-1 and R-2 are not required to comply with this section.
2. Buildings need not comply with the provisions of this section where they fully comply with other applicable provisions of this code.
402.1.1 Occupancy classification.
A mall in compliance with the provisions of this section shall be classified as occupancy Group M.
402.1.2 Open space.
A covered mall building and attached anchor buildings and parking garages shall be surrounded on all sides by a permanent open space of not less than 60 feet (18 288 mm). An open mall building and anchor buildings and parking garages adjoining the perimeter line shall be surrounded on all sides by a permanent open space of not less than 60 feet (18 288 mm).
Exception: The permanent open space of 60 feet (18 288 mm) shall be permitted to be reduced to not less than 40 feet (12 192 mm), provided the following requirements are met:
1. The reduced open space shall not be allowed for more than 75 percent of the perimeter of the covered mall building and anchor buildings or of the perimeter line of the open mall building and anchor buildings;
2. The exterior wall facing the reduced open space shall have a fire-resistance rating of not less than three hours;
3. Openings in the exterior wall facing the reduced open space shall have opening protectives with a fire protection rating of not less than three hours; and
4. Group E, H, I or R occupancies are not located within the covered or open mall building or anchor buildings.
402.1.3 Open mall building perimeter line.
For the purpose of this code, a perimeter line shall be established. The perimeter line shall encircle all buildings and structures that comprise the open mall building and shall encompass any open-air interior walkways, open-air courtyards or similar open-air spaces. The perimeter line shall define the extent of the open mall building. Anchor buildings and parking structures shall be outside of the perimeter line and are not considered as part of the open mall building.
402.2 Definitions.
This section contains terms defined elsewhere in this code, and terms with definitions that are specific to this section.
402.2.1 Terms defined elsewhere in this code.
The following terms are defined in Chapter 2:
ANCHOR BUILDING.
COVERED MALL BUILDING.
Mall.
Open mall.
Open mall building.
402.2.2 Definitions specific to this section.
The following terms shall, for the purposes of this section, have the meanings shown herein:
FOOD COURT. A Public seating area located in the mall that serves adjacent food preparation tenant spaces.
GROSS LEASABLE AREA. The total floor area designed for tenant occupancy and exclusive use. The area of tenant occupancy is measured from the centerlines of joint partitions to the outside of the tenant walls. All tenant areas, including areas used for storage, shall be included in calculating gross leasable area.
402.3 Fire protection plan.
A fire protection plan shall be provided to the Fire Department pursuant to Article 109 of Title 28.
(Am. L.L. 2018/195, 12/1/2018, eff. 5/30/2019)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2018/195.
402.4 Construction.
The construction of covered and open mall buildings, anchor buildings and parking garages associated with a mall building shall comply with Sections 402.4.1 through 402.4.3.
402.4.1 Area and types of construction.
The building area and type of construction of covered mall or open mall buildings, anchor buildings and parking garages shall comply with this section.
402.4.1.1 Covered and open mall buildings.
Covered and open mall buildings shall be of Type I, II or IV construction. The height of covered mall buildings of Type IIB construction shall be limited to one story. The areas of covered mall buildings or open mall buildings shall not be limited provided that the covered mall building or open mall building and attached anchor buildings and parking garages are surrounded on all sides by a permanent open space in accordance with Section 402.1.2.
402.4.1.2 Anchor buildings.
Anchor buildings shall be of Type I, II or IV construction. The height of anchor buildings, of Type IIB construction, shall be limited to one story. The allowable height and area of anchor buildings greater than three stories in height shall comply with Section 503, as modified by Sections 504 and 506.
402.4.1.3 Parking garage.
The building area and building height of any parking garage, open or enclosed, shall be based on the type of construction as required by Sections 406.5 and 406.6, respectively.
402.4.2 Fire-resistance-rated separation.
Fire-resistance-rated separation is not required between tenant spaces and the mall. Fire-resistance-rated separation is not required between a food court and adjacent tenant spaces or the mall.
402.4.2.1 Tenant separations.
Each tenant space shall be separated from other tenant spaces by a fire partition complying with Section 708. A tenant separation wall is not required between any tenant space and the mall.
402.4.2.2 Anchor building separation.
An anchor building shall be separated from the covered or open mall building by fire walls complying with Section 706.
Exceptions:
1. Anchor buildings of not more than three stories above grade that have an occupancy classification of the same uses permitted as tenants of the covered mall building shall be separated by 2-hour fire-resistance-rated fire barriers complying with Section 707. Openings between such buildings and the mall need not be protected.
2. The exterior walls of anchor buildings separated from an open mall building by an open mall shall comply with Table 602.
402.4.2.3 Parking garages.
An attached garage for the storage of passenger vehicles having a capacity of not more than nine persons and open parking garages shall be considered as a separate building where it is separated from the covered or open mall building or anchor building by not less than 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. Parking garages, open or enclosed, which are separated from covered mall buildings, open mall buildings or anchor buildings, shall comply with the provisions of Table 602. Pedestrian walkways and tunnels that connect garages to the mall buildings or anchor buildings shall be constructed in accordance with Section 3104.
402.4.3 Open mall construction.
Floor assemblies in, and roof assemblies over, the open mall of an open mall building shall be open to the atmosphere for not less than 20 feet (9096 mm), measured perpendicular from the face of the tenant spaces on the lowest level, from edge of balcony to edge of balcony on upper floors and from edge of roof line to edge of roof line. The openings within, or the unroofed area of, an open mall shall extend from the lowest/grade level of the open mall through the entire roof assembly. Balconies on upper levels of the mall shall not project into the required width of the opening.
402.4.3.1 Pedestrian walkways.
Pedestrian walkways connecting balconies in an open mall shall be located not less than 20 feet (9096 mm) from any other pedestrian walkway.
402.5 Automatic sprinkler system.
Covered and open mall buildings and buildings connected shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, which shall comply with all of the following:
1. The automatic sprinkler system shall be complete and operative throughout occupied space in the mall building prior to occupancy of any of the tenant spaces. Unoccupied tenant spaces shall be similarly protected unless provided with approved alternative protection.
2. Sprinkler protection for the mall of a covered mall building shall be controlled independently from that provided for tenant spaces or anchor buildings.
3. Sprinkler protection for the tenant spaces of an open mall building shall be controlled independently from that provided for anchor buildings.
4. Sprinkler protection shall be provided beneath exterior circulation balconies located adjacent to an open mall.
5. Where tenant spaces are supplied by the same system, they shall be independently controlled.
Exception: An automatic sprinkler system shall not be required in spaces or areas of open parking garages separated from the covered or open mall building in accordance with Section 402.4.2.3 and constructed in accordance with Section 406.5.
402.6 Interior finishes and features.
Interior finishes within the mall and installations within the mall shall comply with Sections 402.6.1 through 402.6.4.
402.6.1 Interior finish.
Interior wall and ceiling finishes within the mall of a covered mall building and within the exits of covered or open mall buildings shall have a minimum flame spread index and smoke-developed index of Class B in accordance with Chapter 8. Interior floor finishes shall meet the requirements of Section 804.
402.6.2 Kiosks.
Kiosks and similar structures (temporary or permanent) located within the mall of a covered mall building or within the perimeter line of an open mall building shall meet the following requirements:
1. Combustible kiosks or other similar structures shall not be located within a covered or open mall unless constructed of any of the following materials:
1.1. Fire-retardant-treated wood complying with Section 2303.2.
1.2. Foam plastics having a maximum heat release rate not greater than 100 kW (105 Btu/h) when tested in accordance with the exhibit booth protocol in UL 1975 or when tested in accordance with NFPA 289 using the 20 kW ignition source.
1.3. Aluminum composite material (ACM) having a flame spread index of not more than 25 and a smoke-developed index of not more than 450 when tested as an assembly in the maximum thickness intended for use in accordance with ASTM E 84 or UL 723.
2. Covered kiosks or similar covered structures located within the covered mall building shall be provided with an approved automatic sprinkler system and detection devices where required by the New York City Fire Code and Section 903.3.3 of this code.
3. The horizontal separation between kiosks or groupings thereof and other similar structures within the mall shall be not less than 20 feet (6096 mm).
4. Each kiosk or similar structure or groupings thereof shall have an area not greater than 300 square feet (28 m 2 ).
402.6.3 Children's play structures.
Children's play structures located within the mall of a covered mall building or within the perimeter line of an open mall building shall comply with Section 424. The horizontal separation between children's play structures, kiosks and similar structures within the mall shall be not less than 20 feet (6096 mm).
402.6.4 Plastic signs.
Plastic signs affixed to the storefront of any tenant space facing a mall or open mall shall be limited as specified in Sections 402.6.4.1 through 402.6.4.5.
402.6.4.1 Area.
Plastic signs shall be not more than 20 percent of the wall area facing the mall.
402.6.4.2 Height and width.
Plastic signs shall be not greater than 36 inches (914 mm) in height, except that where the sign is vertical, the height shall be not greater than 96 inches (2438 mm) and the width shall be not greater than 36 inches (914 mm).
402.6.4.3 Location.
Plastic signs shall be located not less than 18 inches (457 mm) from adjacent tenants.
402.6.4.4 Plastics other than foam plastics.
Plastics other than foam plastics used in signs shall be light-transmitting plastics complying with Section 2606.4 or shall have a self-ignition temperature of 650°F (343°C) or greater when tested in accordance with ASTM D 1929, and a flame spread index not greater than 75 and smoke-developed index not greater than 450 when tested in the manner intended for use in accordance with ASTM E 84 or UL 723 or meet the acceptance criteria of Section 803.1.2.1 when tested in accordance with NFPA 286.
402.6.4.4.1 Encasement.
Edges and backs of plastic signs in the mall shall be fully encased in metal.
402.6.4.5 Foam plastics.
Foam plastics used in signs shall have flame-retardant characteristics such that the sign has a maximum heat-release rate of 150 kilowatts when tested in accordance with UL 1975 or when tested in accordance with NFPA 289 using the 20 kW ignition source, and the foam plastics shall have the physical characteristics specified in this section. Foam plastics used in signs installed in accordance with Section 402.6.4 shall not be required to comply with the flame spread and smoke-developed indices specified in Section 2603.3.
402.6.4.5.1 Density.
The density of foam plastics used in signs shall be not less than 20 pounds per cubic foot (pcf) (320 kg/m 3 ).
402.6.4.5.2 Thickness.
The thickness of foam plastic signs shall be not greater than 1/2 inch (12.7 mm).
402.7 Emergency systems.
Covered and open mall buildings, anchor buildings and associated parking garages shall be provided with emergency systems complying with Sections 402.7.1 through 402.7.5.
402.7.1 Standpipe system.
Covered and open mall buildings shall be equipped throughout with a standpipe system as required by Section 905.3.3.
402.7.2 Smoke control.
Where a covered mall building contains an atrium, a smoke control system shall be provided in accordance with Section 404.5.
402.7.3 Emergency power.
Covered mall buildings greater than 50,000 square feet (4645 m 2 ) in area and open mall buildings greater than 50,000 square feet (4645 m 2 ) within the established perimeter line shall be provided with emergency power that is capable of operating the emergency voice/alarm communication system in accordance with Section 2702.
402.7.4 Emergency voice/alarm communication system.
Where the total floor area is greater than 50,000 square feet (4645 m 2 ) within either a covered mall building or within the perimeter line of an open mall building, an emergency voice/alarm communication system shall be provided. Emergency voice/alarm communication systems serving a mall, required or otherwise, shall be accessible to the fire department. The systems shall be provided in accordance with Section 907.5.2.2.
402.7.5 Fire Department access to equipment.
Rooms or areas containing controls for air-conditioning systems, automatic fire-extinguishing systems, automatic sprinkler systems or other detection, suppression or control elements shall be identified for use by the Fire Department.
402.8 Means of egress.
Covered mall buildings, open mall buildings and each tenant space within a mall building shall be provided with means of egress as required by this section and this code. Where there is a conflict between the requirements of this code and the requirements of Sections 402.8.1 through 402.8.8, the requirements of Sections 402.8.1 through 402.8.8 shall apply.
402.8.1 Mall width.
For the purpose of providing required egress, malls are permitted to be considered as corridors but need not comply with the requirements of Section 1005.1 of this code where the width of the mall is as specified in this section.
402.8.1.1 Minimum width.
The aggregate clear egress width of the mall in either a covered or open mall building shall be not less than 20 feet (6096 mm). The mall width shall be sufficient to accommodate the occupant load served. No portion of the minimum required aggregate egress width shall be less than 10 feet (3048 mm) measured to a height of 8 feet (2438 mm) between any projection of a tenant space bordering the mall and the nearest kiosk, vending machine, bench, display opening, food court or other obstruction to means of egress travel.
402.8.2 Occupant load.
The calculated occupant load used to determine the required number of means of egress shall be in accordance with this section.
402.8.2.1 Occupant load of tenant spaces.
The occupant load permitted in any individual tenant space in a covered mall building shall be determined in accordance with Chapter 10. Means of egress requirements for individual tenant spaces shall be based on the occupant load thus determined.
402.8.2.2 Occupant load of mall.
In determining required means of egress of the mall, the total occupant load in the mall shall include the occupant load attributed to the mall as determined by Section 402.8.2.3, plus the occupant load of the food court as determined by Section 402.8.2.5, if any.
402.8.2.3 Occupant load formula.
To determine the occupant load attributed to the mall, the gross leasable area (square feet), excluding any food court and anchor buildings, shall be divided by the occupant load factor (OLF) value determined by Equation 4-1.
OLF = (0.00007)(GLA) + 25 (Equation 4-1)
where:
OLF = The occupant load factor (square feet per person).
GLA = The gross leasable area (square feet).
Exception: Tenant spaces attached to a covered mall building but with a means of egress system that is totally independent of the covered mall building shall not be considered as gross leasable area for determining the required means of egress for the covered mall building.
402.8.2.4 OLF range.
The occupant load factor (OLF) is not required to be less than 30 and shall not exceed 50.
402.8.2.5 Food courts.
The occupant load of a food court shall be determined in accordance with Section 1004 and shall be added to the occupant load of the mall.
402.8.2.6 Anchor buildings.
The occupant load of anchor buildings opening into the mall shall not be included in computing the total number of occupants for the covered mall building.
402.8.3 Number of means of egress.
The required number of means of egress shall be determined in accordance with this section.
402.8.3.1 Number of means of egress within tenant spaces.
Wherever the distance of travel to the mall from any location within a tenant space used by persons other than employees exceeds 75 feet (22 860 mm) or the tenant space exceeds an occupant load of 74, no fewer than two means of egress shall be provided.
402.8.3.2 Number of means of egress from the mall.
The number of means of egress from the mall shall be determined in accordance with Chapter 10 and shall be based upon an occupant load calculated in accordance with Section 402.8.2.
402.8.4 Arrangements of means of egress.
Means of egress shall be arranged in accordance with this section.
402.8.4.1 Anchor building means of egress.
Required means of egress for anchor buildings shall be provided independently from the mall means of egress system. The occupant load of anchor buildings opening into the mall shall not be included in determining means of egress requirements for the mall. The path of egress travel of malls shall not exit through anchor buildings. Malls terminating at an anchor building where no other means of egress has been provided shall be considered as a dead-end mall.
402.8.4.2 Tenant spaces requiring more than one means of egress.
Where more than one means of egress is required from an individual tenant space as determined by Chapter 10, not more than 50 percent of the occupant load shall discharge into the mall.
402.8.4.3 Large assembly occupancy.
Assembly occupancies with an occupant load of 500 or more shall be so located in the covered mall building such that their entrance will be immediately adjacent to a principal entrance to the mall and shall have not less than one-half of their required means of egress opening directly to the exterior of the covered mall building.
402.8.5 Distance to exits.
Within each individual tenant space in a covered or open mall building, the distance of travel from any point to an exit or entrance to the mall shall be not greater than 200 feet (60 960 mm). The distance of travel from any point within a mall of a covered mall building to an exit shall be not greater than 200 feet (60 960 mm). The maximum distance of travel from any point within an open mall to the perimeter line of the open mall building shall be not greater than 200 feet (60 960 mm).
402.8.6 Access to exits.
Where more than one exit is required, they shall be so arranged that it is possible to travel in either direction from any point in a mall of a covered mall building to separate exits or from any point in an open mall of an open mall building to two separate locations on the perimeter line, provided neither location is an exterior wall of an anchor building or parking garage. The width of an exit passageway or corridor from a mall shall be not less than 66 inches (1676 mm).
Exception: Access to exits is permitted by way of a dead-end mall that does not exceed a length equal to twice the width of the mall measured at the narrowest location within the dead-end portion of the mall.
402.8.6.1 Exit passageway enclosures.
Where exit passageway enclosures provide a secondary means of egress from a tenant space, doors to the exit passageway enclosures shall be minimum 1-hour fire doors with panic hardware. Such doors shall be self-closing and be so maintained or shall be automatic closing by smoke detection.
402.8.7 Service areas fronting on exit passageways.
Mechanical rooms, electrical rooms, building service areas and service elevators are permitted to open directly into exit passageways provided that the exit passageway is separated from such rooms by fire barriers providing the same fire-resistance rating as required for the exit passageway. Door swings from these rooms shall not project into the minimum width of such exit passageways.
402.8.8 Security grilles and doors.
Horizontal sliding or vertical security grilles or doors that are a part of a required means of egress shall conform to the following:
1. Doors and grilles shall remain in the full open position during the period of occupancy by the general public.
2. Doors or grilles shall not be brought to the closed position when there are 10 or more persons occupying spaces served by a single exit or 50 or more persons occupying spaces served by more than one exit.
3. The doors or grilles shall be openable from within without the use of any special knowledge or effort where the space is occupied.
4. Where two or more exits are required, not more than one-half of the exits shall be permitted to include either a horizontal sliding or vertical rolling grille or door.
Section BC 403. High-Rise Buildings
403.1 Applicability.
High-rise buildings shall comply with Sections 403.2 through 403.8.
Exception: The provisions of Sections 403.2 through 403.8 shall not apply to the following buildings and structures:
1. Air traffic control towers in accordance with Section 412.3.
2. Buildings occupied entirely by Group R-3 classification.
3. Open parking garages in accordance with Section 406.5.
4. The portion of a building containing a Group A-5 occupancy in accordance with Section 303.6.
5. Special industrial occupancies in accordance with Section 503.1.1.
6. Buildings with:
6.1. A Group H-1 occupancy;
6.2. A Group H-2 occupancy in accordance with Section 415.8, 415.9.2, 415.9.3 or 426.1; or
6.3. A Group H-3 occupancy in accordance with Section 415.8.
403.2 Construction.
The construction of high-rise buildings shall comply with the provisions of Sections 403.2.1 through 403.2.4.
403.2.1 Types of construction.
The following modifications to the minimum fire-resistance rating of the building elements in Table 601 shall be as follows:
1. High rise buildings 420 feet (128 m) or greater in building height shall be constructed of Type IA construction.
2. For high rise buildings not greater than 420 feet (128 m) in building height, and constructed to meet the fire-resistance rating requirements of Type IB or IIA construction, the required fire-resistance rating of columns supporting floors shall be constructed to meet Type IA construction.
403.2.2 Seismic considerations.
For seismic considerations, see Chapter 16.
403.2.3 Structural integrity of interior exit stairways and elevator hoistway enclosures.
For all high-rise buildings, exit enclosures for interior exit stairways and elevator hoistway enclosures shall comply with Sections 403.2.3.1 through 403.2.3.4.
Exception: Where fire-resistance rating is not required by this code for the enclosure or portions thereof.
403.2.3.1 Wall assembly.
The wall assemblies making up the enclosures for interior exit stairways and elevator hoistway enclosures shall meet or exceed Soft Body Impact Classification Level 2 as measured by the test method described in ASTM C 1629 / C 1629M.
403.2.3.2 Wall assembly materials.
The face of the wall assemblies making up the enclosures for interior exit stairways and elevator hoistway enclosures that are not exposed to the interior of the enclosures for interior exit stairways or elevator hoistway enclosure shall be constructed in accordance with one of the following methods:
1. The wall assembly shall incorporate no fewer than two layers of impact-resistant construction board each of which meets or exceeds Hard Body Impact Classification Level 2 as measured by the test method described in ASTM C 1629 / C 1629M.
2. The wall assembly shall incorporate no fewer than one layer of impact-resistant construction material that meets or exceeds Hard Body Impact Classification Level 3 as measured by the test method described in ASTM C 1629 / C 1629M.
3. The wall assembly incorporates multiple layers of any material, tested in tandem, that meets or exceeds Hard Body Impact Classification Level 3 as measured by the test method described in ASTM C 1629 / C 1629M.
403.2.3.3 Concrete and masonry walls.
Concrete or masonry walls shall be deemed to satisfy the requirements of Sections 403.2.3.1 and 403.2.3.2.
403.2.3.4 Other wall assemblies.
Any other wall assembly that provides impact resistance equivalent to that required by Sections 403.2.3.1 and 403.2.3.2 for Hard Body Impact Classification Level 3, as measured by the test method described in ASTM C 1629 / C 1629M, shall be permitted.
403.2.4 Sprayed fire-resistant materials (SFRM).
The bond strength of the SFRM installed throughout the building shall be in accordance with Table 403.2.4.
Table 403.2.4 Minimum Bond Strength
Height of Building a SFRM Minimum Bond Strength Up to 420 feet 430 psf Greater than 420 feet 1,000 psf
For SI: 1 foot = 304.8 mm, 1 pound per square foot (psf) = 0.0479 kW/m 2 .
a. Above the lowest level of fire department vehicle access.
403.3 Automatic sprinkler system.
Buildings and structures shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 and a secondary water supply where required by Section 403.3.3.
403.3.1 Number of sprinkler risers and system design.
Each sprinkler system zone in buildings that are more than 300 feet (91 440 mm) in building height shall be supplied by no fewer than two risers. Each riser shall supply sprinklers on alternate floors. If more than two risers are provided for a zone, sprinklers on adjacent floors shall not be supplied from the same riser.
403.3.1.1 Riser location.
Sprinkler risers shall be placed in interior exit stairways and ramps that are remotely located in accordance with Section 1007.1.
403.3.2 Water supply to required fire pumps.
Required fire pumps shall be provided with water supplies in accordance with Section 905.2 and NFPA 14 as modified by Appendix Q of this code.
403.3.3 Secondary on-site water supply.
A secondary on-site water supply equal to the hydraulically calculated sprinkler demand, including the hose stream requirement, shall be provided for high-rise buildings in Seismic Design Category C or D as determined by this code, and in any high-rise building with occupied floors located more than 500 feet (152 m) above the lowest level of fire department vehicle access. The secondary on-site water supply shall have a duration of not less than 30 minutes as determined by the occupancy hazard classification in accordance with NFPA 13 as modified by Appendix Q of this code.
403.3.4 Fire pump room.
Fire pumps shall be located in rooms protected in accordance with Section 913.2.1.
403.4 Emergency systems.
The detection, alarm and emergency systems of high-rise buildings shall comply with Sections 403.4.1 through 403.4.8.
403.4.1 Smoke detection.
Smoke detection shall be provided in accordance with Section 907.2.13.1.
403.4.2 Fire alarm systems.
A fire alarm system shall be provided in accordance with Section 907.2.13.
403.4.3 Standpipe system.
A high-rise building shall be equipped with a standpipe system as required by Section 905.3.
403.4.4 Emergency voice/alarm communication system.
An emergency voice/alarm communication system shall be provided in accordance with Section 907.5.2.2.
403.4.5 Emergency responder radio coverage.
Emergency responder radio coverage shall be provided in accordance with the New York City Fire Code and Section 907.2.13.2 of this code.
403.4.6 Fire command.
A fire command center complying with Section 911 shall be provided in a location approved by the Fire Department.
403.4.7 Post-fire smoke purge.
A post-fire smoke purge system shall be installed in accordance with Section 917.
403.4.8 Standby and emergency power.
A standby power system complying with Section 2702 and Section 3003 shall be provided for the standby power loads specified in Section 403.4.8.3. An emergency power system complying with Section 2702 shall be provided for the emergency power loads specified in Section 403.4.8.4.
403.4.8.1 Equipment room.
If the standby or emergency power system includes a generator set inside a building, the system shall be located in a separate room in accordance with Section 2702.1.2.2.
403.4.8.2 Fuel line piping protection.
Fuel lines supplying a generator set inside a building shall comply with Section 1305.9 of the New York City Mechanical Code.
403.4.8.3 Standby power systems.
A standby power system complying with Section 2702 shall be provided for standby power loads specified in Sections 403.4.8.3.1 and 403.4.8.3.2. Fuel sources for generators shall be in accordance with Section 2702.1.1.
403.4.8.3.1 Standby power loads in occupancies other than Group R-2.
In buildings of any occupancy group other than Group R-2, the following are classified as standby power loads:
1. Power and lighting for fire command center required by Section 403.4.6;
2. Ventilation and automatic fire detection equipment for smokeproof enclosures;
3. Elevators, in accordance with Section 3003; and
4. Stair pressurization systems when provided.
403.4.8.3.2 Standby power loads in Group R-2 occupancies.
Group R-2 occupancies in buildings greater than 125 feet (38 100 mm) in height shall be required to provide a standby power system to support the following loads:
1. Power and lighting for fire command center required by Section 403.4.6;
2. Ventilation and automatic fire detection equipment for smokeproof enclosures;
3. At least one elevator serving all floors, or one elevator per bank where different banks serve different portions of the building; and
4. Stair pressurization systems when provided.
403.4.8.4 Emergency power systems.
An emergency power system complying with Section 2702 shall be provided for emergency power loads specified in Sections 403.4.8.4.1 and 403.4.8.4.3. Fuel sources for generators shall be in accordance with Section 2702.1.1.
403.4.8.4.1 Emergency power loads in occupancies other than Group R-2.
In buildings of any occupancy group other than Group R-2, the following are classified as emergency power loads:
1. Exit signs and means of egress illumination required by Chapter 10;
2. Elevator car lighting;
3. Emergency voice/alarm communications systems, including Fire Department in-building Auxiliary Radio Communication systems (ARCs);
4. Automatic fire detection systems;
5. Fire alarm systems; and
6. Electrically powered fire pumps, including manual fire pumps, automatic fire pumps, and sprinkler booster pumps.
403.4.8.4.2 Emergency power loads in Group R-2 occupancies.
Group R-2 occupancies in buildings greater than 125 feet (38 100 mm) in height shall be required to provide an emergency power system to support the following loads:
1. Exit signs and means of egress illumination required by Chapter 10;
2. Emergency voice communications systems, including Fire Department in-building Auxiliary Radio Communication systems (ARCs); and
3. Electrically powered fire pumps, unless electrical power to the motor is taken ahead of the main from the street side of the house service switch.
403.4.8.4.3 Emergency power loads in Group R-2 occupancies 125 feet or less in height.
Group R-2 occupancies in buildings 125 feet (38 100 mm) or less in height shall be required to provide an emergency power system to support the following loads:
1. Emergency voice communications systems in buildings containing Group R-2 occupancies in accordance with Section 907.5.2.2 of this code, or where otherwise provided. Batteries in accordance with the New York City Electrical Code are permitted to serve as the secondary power supply for such systems.
2. Fire Department in-building Auxiliary Radio Communication systems (ARCs) in buildings containing Group R-2 occupancies in accordance with Section 916.3 of this code, or where otherwise provided. Batteries in accordance with the New York City Electrical Code are permitted to serve as the secondary power supply for such systems.
403.5 Means of egress and evacuation.
The means of egress in high-rise buildings shall comply with Sections 403.5.1 through 403.5.6.
403.5.1 Remoteness of interior exit stairways.
Required interior exit stairways shall be separated by a distance not less than 30 feet (9144 mm) or not less than 1/4 of the length of the maximum overall diagonal dimension of the building or area to be served, whichever is less. The distance shall be measured in a straight line between the nearest points of the enclosure surrounding the interior exit stairways. In buildings with three or more interior exit stairways, no fewer than two of the interior exit stairways shall comply with this section. Stairs sharing any common wall, floors, ceilings, scissor stair assemblies, or other enclosures shall be counted as one interior exit stairway.
Exception: Group R-2 occupancies.
403.5.2 Additional exit stairway.
For buildings other than Group R-2 that are more than 420 feet (128 m) in building height, one additional exit stairway meeting the requirements of Sections 1011 and 1023 shall be provided in addition to the minimum number of exits required by Section 1006.3. The total width of any combination of remaining exit stairways with one exit stairway removed shall not be less than the total width required by Section 1005.1. Stairs sharing any common wall, floors, ceilings, scissor stair assemblies, or other enclosures shall not be considered the additional exit stairway required by this section.
Exceptions: An additional exit stairway shall not be required to be installed in any of the following instances:
1. In buildings where all passenger elevators for general public use and all other elevators used for occupant self-evacuation comply with Sections 3008.1 through 3008.11;
2. In buildings where all of the following conditions are met:
2.1. The commissioner has approved a timed egress analysis establishing the egress time it would take for a full building evacuation, utilizing the stairs required by Section 1006 and the additional stair that would have been required pursuant to Section 403.5.2;
2.2. The commissioner has approved a timed egress analysis establishing the egress time it would take for a full building evacuation, utilizing the combination of the stairs required by Section 1006 and elevators used for occupant self-evacuation as follows:
2.2.1. Such analysis need only utilize a number of designated elevators designed for occupant self-evacuation necessary to demonstrate an evacuation time that is less than the time established in Exception 2.1; and
2.2.2. Every bank of passenger elevators for general public use shall be served by at least one such designated elevator;
2.3. All elevators in the building that either are passenger elevators for general public use or are used for occupant self-evacuation shall comply with Sections 3008.1 through 3008.11. However, the standby power generating equipment required by Section 3008.9 need only be sized to satisfy the loads required to simultaneously operate those elevators identified in the timed egress analysis described in Exception 2.2.
The minimum number of exits required by Section 1006 are all at least 25 percent wider than the exit width required by Chapter 10. The increase in the stair width shall not be utilized in the timed egress analyses required by Exceptions 2.1 and 2.2.
403.5.3 Stairway door operation.
Doors opening into interior stair enclosures shall not be locked from either side. However, a door locked from the stair side may be permitted provided that such door is equipped with an automatic fail safe system for opening in the event of the activation of any automatic fire detection system, or when any elevator recall is activated, or when any signal is received from the fire command center. Such door shall be deemed as openable from the stair side. Stair reentry signs shall be posted throughout the stairway indicating that reentry is provided only during fire emergencies. Such signs shall be in accordance with Section 1031.4.2.
Exception: In schools classified as Group E occupancies that require "lockdown drills" as per Section 807 of the New York State Education Law, stairway egress doors from occupied spaces are permitted to be locked from the side opposite the egress side for the duration of the lockdown drill, provided they are openable from the occupied side for egress and are unlocked upon directions from the school administrative personnel following the completion of the lockdown drill.
403.5.3.1 Stairway communication system.
A telephone or other two-way communications system connected to an approved constantly attended station shall be provided at not less than every fifth floor in each stairway where the doors to the stairway are locked in accordance with Section 403.5.3.
403.5.4 Smokeproof enclosures.
Every required interior exit stairway serving floors more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access shall comply with Sections 909.20 and 1023.11
Exception: Smokeproof enclosures are not required in occupancy Group R-2 unless provided pursuant to Exception 2 of Section 917.1.
403.5.5 Luminous egress path markings.
Luminous egress path markings shall be provided in accordance with Section 1025 and Appendix S.
Exception: Egress paths serving Group R-2.
403.5.6 Emergency escape and rescue.
Emergency escape and rescue openings specified in Section 1030 are not required.
403.6 Elevators.
Elevator installation and operation in high-rise buildings shall comply with Chapter 30 and Sections 403.6.1 and 403.6.2.
403.6.1 Fire service access elevator.
In buildings with an occupied floor more than 120 feet (36 576 mm) above the lowest level of fire department vehicle access, a minimum of one fire service access elevator shall be provided in accordance with Section 3007.
403.6.2 Occupant evacuation elevators.
Where installed in accordance with Section 3008, passenger elevators for general public use shall be permitted to be used for occupant self-evacuation.
403.6.3 Elevator lobbies.
Elevator lobbies shall be provided in accordance with Sections 3006.1.1 and 3006.1.2.
403.7 Outdoor air intakes.
For high-rise buildings, outdoor air intakes serving spaces above the second story and serving spaces greater than 10,000 square feet (929 m 2 ) of floor area shall be located in accordance with Section 401.5 of the New York City Mechanical Code.
Exception: Group R-2 occupancy.
403.8 Open web steel joists.
The use of open web steel joists shall be prohibited in high-rise buildings until the commissioner promulgates rules establishing minimum acceptable fireproofing methods.
Section BC 404. Atriums
404.1 General.
In other than Group H occupancies, and where permitted by Section 712.1.7, the provisions of Sections 404.1 through 404.10 shall apply to buildings or structures containing vertical openings defined as "atriums".
404.1.1 Definitions.
The following term is defined in Chapter 2:
ATRIUM.
404.2 Use.
The floor of the atrium shall not be used for other than low fire hazard uses and only approved materials and decorations in accordance with the New York City Fire Code shall be used in the atrium space.
Exception: The atrium floor area is permitted to be used for any approved use where the individual space is provided with an automatic sprinkler system in accordance with Section 903.3.1.1.
404.3 Automatic sprinkler protection.
An approved automatic sprinkler system shall be installed throughout the entire building.
Exceptions:
1. That area of a building adjacent to or above the atrium need not be sprinklered provided that portion of the building is separated from the atrium portion by not less than 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711 or both.
2. Where the ceiling of the atrium is more than 55 feet (16 764 mm) above the floor, sprinkler protection at the ceiling of the atrium is not required.
404.4 Fire alarm system.
A fire alarm system shall be provided in accordance with Section 907.2.14.
404.5 Smoke control.
A smoke control system shall be installed in accordance with Section 909.
Exception: In other than Groups I-1 and I-2, and covered mall buildings containing an atrium pursuant to Section 402.7.2, smoke control is not required for atriums that connect only two stories.
404.6 Enclosure of atriums.
Atrium spaces shall be separated from adjacent spaces by a 1-hour fire barrier constructed in accordance with Section 707 or a horizontal assembly constructed in accordance with Section 711, or both.
Exceptions:
1. A fire barrier is not required where a glass or glass-block wall forming a smoke partition is provided. The glass or glass-block wall shall comply with all of the following:
1.1. Automatic sprinklers are provided along both sides of the separation wall and doors, or on the room side only if there is not a walkway on the atrium side. The sprinklers shall be located between 4 inches and 12 inches (102 mm and 305 mm) away from the glass and at intervals along the glass not greater than 6 feet (1829 mm). The sprinkler system shall be designed so that the entire surface of the glass is wet upon activation of the sprinkler system without obstruction;
1.2. The glass wall shall be installed in a gasketed frame in a manner that the framing system deflects without breaking (loading) the glass before the sprinkler system operates; and
1.3. Where glass doors are provided in the glass wall, they shall be either self-closing or automatic-closing.
2. The adjacent spaces of any three floors of the atrium shall not be required to be separated from the atrium where such spaces are accounted for in the design of the smoke control system.
404.7 Standby power.
Equipment required to provide smoke control shall be provided with standby power in accordance with Section 909.11.
404.8 Interior finish.
The interior finish of walls and ceilings of the atrium shall be not less than Class B with no reduction in class for sprinkler protection.
404.9 Exit access travel distance.
Exit access travel distance for areas open to an atrium shall comply with the requirements of this section.
404.9.1 Egress not through the atrium.
Where required access to the exits is not through the atrium, exit access travel distance shall comply with Section 1017.
404.9.2 Exit access travel distance at the level of exit discharge.
Where the path of egress travel is through an atrium space, exit access travel distance at the level of exit discharge shall be determined in accordance with Section 1017.
404.9.3 Exit access travel distance at other than the level of exit discharge.
Where the path of egress travel is not at the level of exit discharge from the atrium, that portion of the total permitted exit access travel distance that occurs within the atrium shall be not greater than 200 feet (60 960 mm).
404.10 Interior exit stairways.
A maximum of 50 percent of interior exit stairways are permitted to egress through an atrium on the level of exit discharge in accordance with Section 1028.
Section BC 405. Underground Buildings and Spaces
405.1 General.
The provisions of Sections 405.2 through 405.9 apply to building spaces having a floor level used for human occupancy more than 30 feet (9144 mm) below the finished floor of the lowest level of exit discharge.
Exceptions: The provisions of Section 405 are not applicable to the following buildings or portions of buildings:
1. One- and two-family dwellings, sprinklered in accordance with Section 903.3.1.3.
2. Parking garages provided with automatic sprinkler systems in compliance with Section 405.3.
3. Fixed guideway transit systems.
4. Grandstands, bleachers, stadiums, arenas and similar facilities.
5. Where the lowest story is the only story that would qualify the building as an underground building and has an area not greater than 1,500 square feet (139 m 2 ) and has an occupant load less than 10.
6. Pumping stations and other similar mechanical spaces intended only for limited periodic use by service or maintenance personnel.
405.2 Construction requirements.
The underground portion of the building shall be of Type I construction.
405.3 Automatic sprinkler system.
The highest level of exit discharge serving the underground portions of the building and all levels below shall be equipped with an automatic sprinkler system installed in accordance with Section 903.3.1.1. Water-flow switches and control valves shall be supervised in accordance with Section 903.4.
405.4 Compartmentation.
Compartmentation shall be in accordance with Sections 405.4.1 through 405.4.3.
405.4.1 Number of compartments.
A building having a floor level more than 60 feet (18 288 mm) below the finished floor of the lowest level of exit discharge shall be divided into no fewer than two compartments of approximately equal size. Such compartmentation shall extend through the highest level of exit discharge serving the underground portions of the building and all levels below.
Exception: The lowest story need not be compartmented where the area is not greater than 1,500 square feet (139 m 2 ) and has an occupant load of less than 10.
405.4.2 Compartment separation.
The separation between the two compartments shall be of minimum 2-hour fire barrier wall construction that shall extend from floor slab to floor deck above. Penetrations between the two compartments shall be limited to plumbing and electrical piping and conduit that are firestopped in accordance with Section 714. Doorways shall be protected by fire door assemblies that are automatic-closing by smoke detection in accordance with Section 716.5.9.3 and are installed in accordance with NFPA 105 and Section 716.5.3 of this code. Where provided, each compartment shall have an air supply and an exhaust system independent of the other compartments.
405.4.3 Elevators.
Where elevators are provided, each compartment shall have direct access to an elevator. Where an elevator serves more than one compartment, an elevator lobby shall be provided and shall be separated from each compartment by a 2-hour fire barrier wall. Doors shall be gasketed, have a drop sill, and be automatic-closing by smoke detection in accordance with Section 716.5.9.3.
405.5 Smoke control system.
A smoke control system shall be provided in accordance with Sections 405.5.1 and 405.5.2.
405.5.1 Control system.
A smoke control system is required to control the migration of products of combustion in accordance with Section 909 and the provisions of this section. Smoke control shall restrict movement of smoke to the general area of fire origin and maintain means of egress in a usable condition.
405.5.2 Compartment smoke control system.
Where compartmentation is required, each compartment shall have an independent smoke control system. The system shall be automatically activated and capable of manual operation in accordance with Sections 907.2.18 and 907.2.19.
405.6 Fire alarm systems.
A fire alarm system shall be provided where required by Sections 907.2.18 and 907.2.19.
405.7 Means of egress.
Means of egress shall be in accordance with Sections 405.7.1 and 405.7.2.
405.7.1 Number of exits.
Each floor level shall be provided with no fewer than two exits. Where compartmentation is required by Section 405.4, each compartment shall have no fewer than one exit and shall also have no fewer than one exit access doorway into the adjoining compartment.
405.7.2 Smokeproof enclosure.
Every required stairway serving floor levels more than 30 feet (9144 mm) below its level of exit discharge shall comply with the requirements for a smokeproof enclosure as provided in Section 1023.11.
405.8 Standby power.
A standby power system complying with Section 2702 shall be provided for the standby power loads specified in Section 405.8.1. An emergency power system complying with Section 2702 shall be provided for the emergency power loads specified in Section 405.8.2.
405.8.1 Standby power loads.
The following loads are classified as standby power loads:
1. Smoke control system.
2. Ventilation and automatic fire detection equipment for smokeproof enclosures.
3. Fire pumps.
4. Elevators, as required in Section 3003; and
5. Stair pressurization systems when provided.
405.8.2 Emergency power loads.
The following loads are classified as emergency power loads:
1. Emergency voice/alarm communications systems, including Fire Department in-building Auxiliary Radio Communication systems (ARCs) provided where required or installed voluntarily in accordance with Section 916;
2. Fire alarm systems;
3. Automatic fire detection systems;
4. Elevator car lighting; and
5. Means of egress and exit sign illumination as required by Chapter 10.
405.9 Standpipe system.
The underground building shall be equipped throughout with a standpipe system in accordance with Section 905.
Section BC 406. Motor Vehicle-Related Occupancies
406.1 General.
Motor-vehicle-related occupancies shall comply with Sections 406.1 through 406.8.
406.2 Definitions.
The following terms are defined in Chapter 2:
CARPORT.
DIRECT CURRENT FAST CHARGING STATION.
ELECTRIC VEHICLE LOAD MANAGEMENT SYSTEM.
ELECTRIC VEHICLE SUPPLY EQUIPMENT (EVSE).
LEVEL 2 CHARGING STATION.
MECHANICAL-ACCESS OPEN PARKING GARAGE.
OPEN PARKING GARAGE.
PRIVATE GARAGE.
RAMP-ACCESS OPEN PARKING GARAGE.
(Am. L.L. 2024/055, 4/6/2024, eff. 12/21/2025)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2024/055.
406.3 Private garages and carports.
Private garages and carports shall comply with Sections 406.3.1 through 406.3.5.
406.3.1 Classification.
Private garages and carports shall be classified as Group U occupancy.
406.3.2 Clear height.
In private garages and carports, the clear height in vehicle and pedestrian traffic areas shall be not less than 7 feet (2134 mm). Vehicle and pedestrian areas accommodating van-accessible parking shall comply with Section 1106.5.
406.3.3 Floor construction.
Private garage and carport floors shall be of concrete or equivalent noncombustible material that will not absorb flammable liquids. The area of floor used for parking of vehicles shall be sloped to facilitate the movement of liquids to a drain. The sills of all door openings connecting a dwelling unit to a private garage shall be raised at least 4 inches (102 mm) above the floor level of the garage.
Exception: Asphalt surfaces shall be permitted at ground level in carports.
406.3.3.1 Ramps.
Ramps shall have a gradient not exceeding one in seven, with nonslip surfaces, and shall be located entirely within the property line. However, upon application to the commissioner, steeper gradients may be accepted, but in no event greater than one in three.
406.3.4 Separation.
Separations shall comply with the following:
1. The private garage shall be separated from the dwelling unit and its attic area by means of a minimum 1-hour fire-rated construction. Garages beneath habitable rooms shall be separated from all habitable rooms above by not less than 1-hour fire-rated construction. Openings from a private garage directly into a room used for sleeping purposes shall not be permitted.
2. No air used for heating, cooling, or ventilation shall be circulated through private garages to dwelling areas.
3. A separation is not required between a Group R-3 occupancy and a carport, provided the carport does not have any enclosed areas above.
4. For free standing private garages where the fire separation distance from the nearest exterior wall is less than 5 feet, such exterior walls shall have a fire-resistance rating not less than one hour.
406.3.5 Automatic garage door openers.
Automatic garage door openers, if provided, shall be listed in accordance with UL 325.
406.4 Public parking garages.
Parking garages, other than private parking garages, shall be classified as public parking garages and shall comply with the provisions of Sections 406.4.2 through 406.4.10 and shall be classified as either an open parking garage or an enclosed parking garage. Open parking garages shall also comply with Section 406.5. Enclosed parking garages shall also comply with Section 406.6. See Section 510 for special provisions for parking garages.
406.4.1 Clear height.
The clear height of each floor level in vehicle and pedestrian traffic areas shall be not less than 7 feet (2134 mm). Vehicle and pedestrian areas accommodating van-accessible parking shall comply with Section 1106.5.
406.4.2 Guards.
Guards shall be provided in accordance with Section 1015. Guards serving as vehicle barrier systems shall comply with Sections 406.4.3 and 1015.
406.4.3 Vehicle barrier systems.
Vehicle barriers not less than 2 feet 9 inches (835 mm) in height shall be placed where the vertical distance from the floor of a drive lane or parking space to the ground or surface directly below is greater than 1 foot (305 mm). Vehicle barriers shall comply with the loading requirements of Section 1607.9.
Exception: Vehicle barriers are not required in vehicle storage compartments in a mechanical access parking garage.
406.4.4 Ramps.
Ramps shall have a gradient not exceeding one in seven, with non-slip surfaces. A level landing having a minimum dimension of 20 feet (6096 mm) shall be provided at the discharge point of all ramps at the street level, within the property line. Ramps used for the movement of motor vehicles need not be enclosed when serving tiers above grade. Vehicle ramps may serve as part of a means of egress in accordance with Section 1006.4.
406.4.5 Floor surface.
Parking surfaces shall be of concrete or similar noncombustible and nonabsorbent materials. The area of floor used for parking of vehicles shall be sloped to facilitate the movement of liquids to a drain.
Exceptions:
1. Asphalt parking surfaces shall be permitted at ground level.
2. Floors of Group S-2 parking garages shall not be required to have a sloped surface.
406.4.6 Separation.
Parking garages shall be separated from other occupancies in accordance with Section 508.1.
406.4.7 Special hazards.
Connection of a parking garage with any room in which there is a fuel-fired appliance shall be by means of a vestibule providing a two-doorway separation. Such vestibule and doorway shall be minimum 1-hour rated construction.
Exception: A single door shall be allowed provided the sources of ignition in the appliance are not less than 18 inches (457 mm) above the floor.
406.4.8 Attached to rooms.
Openings from a parking garage directly into a room used for sleeping purposes shall not be permitted.
406.4.9 Fire-fighter aisles.
In any parking garage or lot, one or more aisles, at least 24 inches (610 mm) in width, shall be provided to permit access by fire fighting personnel to all parts of the garage or lot. There shall not be more than three rows of parked motor vehicles between aisles.
406.4.10 Electric vehicle supply equipment (EVSE).
A new parking garage and a parking garage in an existing structure undergoing such significant alterations as established by the department by rule shall be capable of supporting EVSE in accordance with this section. At least 20 percent of the parking spaces of the garage shall be equipped with level 2 charging stations. At least 60 percent of the parking spaces of the garage shall be capable of supporting EVSE. The installation of 1 direct current fast charging station shall be considered the equivalent of 10 level 2 charging stations, and the installation of direct current fast charging stations shall not be used to satisfy more than 50 percent of the level 2 charging stations required for purposes of compliance with this section. This amount of electrical capacity may be coupled with an electric vehicle load management system to distribute power to a greater percentage of spaces at lower amperage as EVSE penetration increases above 40 percent of parking spaces. All components and work appurtenant thereto, including ventilation system(s), shall be in accordance with the New York City Electrical Code and the New York City Mechanical Code.
Exceptions:
1. The commissioner may waive compliance with this section if the commissioner determines that the parking garage is a temporary facility that will be in service no longer than 3 years.
2. The commissioner, upon consultation with the commissioner of housing preservation and development, shall grant a waiver of the requirements of this section for a parking garage within or appurtenant to a multiple dwelling in which 100 percent of dwelling units are required, pursuant to a federal, state, or local law, rule, or program to be affordable for tenants or owners where the occupant’s income relative to the area median income does not exceed a fixed percentage or percentages, and that is subject to an actual or anticipated agreement with a federal, state, or local governmental entity for the purposes of providing affordable housing in a given locality or region.
3. The commissioner of citywide administrative services may waive or adjust compliance with this section for parking garages on city owned or leased real property or the New York city housing authority may waive or adjust compliance with respect to real property owned or leased by such authority where such commissioner or authority, as applicable, determines that the installation of EVSE to the extent required by this section is not feasible for budgetary, operational, or programmatic reasons with respect to the ongoing citywide installation of EVSE or with respect to the issuance of a license or lease to a private person or entity to operate a parking garage.
4. The commissioner may waive or adjust compliance with this section if the commissioner finds that, upon submission of evidence from the owner, the provisions present an undue hardship resulting from technical infeasibility, including but not limited to:
4.1. The parking garage utilizes equipment that enables vehicles to be parked vertically and the owner demonstrates that such vertical parking would make the use of EVSE infeasible, provided an adjustment may be granted so that only spaces where EVSE could feasibly be used will be required to do so to the maximum extent practicable to meet the requirements under this section; or
4.2. The owner provides evidence that compliance with this section would compromise the structural integrity of the parking garage.
(Am. L.L. 2024/055, 4/6/2024, eff. 12/21/2025)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2013/130 and L.L. 2024/055.
406.5 Open parking garages.
Open parking garages shall comply with Sections 406.5.1 through 406.5.11.
406.5.1 Construction.
Open parking garages shall be of Type I, II or IV construction. Open parking garages shall meet the design requirements of Chapter 16. For vehicle barriers, see Section 406.4.3.
406.5.2 Openings.
For natural ventilation purposes, the exterior side of the structure shall have uniformly distributed openings on two or more sides. The area of such openings in exterior walls on a tier shall be not less than 20 percent of the total perimeter wall area of each tier. The aggregate length of the openings considered to be providing natural ventilation shall be not less than 40 percent of the perimeter of the tier. Interior walls shall be not less than 20 percent open with uniformly distributed openings.
Exception: Openings are not required to be distributed over 40 percent of the building perimeter where the required openings are uniformly distributed over two opposing sides of the building.
406.5.2.1 Openings below grade.
Where openings below grade provide required natural ventilation, the outside horizontal clear space shall be 1 1/2 times the depth of the opening. The width of the horizontal clear space shall be maintained from grade down to the bottom of the lowest required opening.
406.5.3 Uses.
Mixed uses shall be allowed in the same building as an open parking garage subject to the provisions of Sections 402.4.2.3, 406.5.11, 508.1, 510.3, 510.4 and 510.7.
406.5.4 Area and height.
Area and height of open parking garages shall be limited as set forth in Chapter 5 for Group S-2 occupancies.
Table 406.5.4 Open Parking Garages Area and Height
Type of Construction Area Per Tier (square feet) Height (in tiers) Ramp Access Mechanical Access Automatic Sprinkler System No Yes 1A Unlimited Unlimited Unlimited Unlimited IB Unlimited 12 tiers 12 tiers 18 tiers IIA 50,000 10 tiers 10 tiers 15 tiers IIB 50,000 8 tiers 8 tiers 12 tiers IV 50,000 4 tiers 4 tiers 4 tiers
For SI: 1 square foot = 0.0929 m 2 .
406.5.4.1 Single use.
Where the open parking garage is used exclusively for the parking or storage of private motor vehicles, with no other uses in the building, the area and height shall be permitted to comply with Table 406.5.4.
Exception: The grade-level tier is permitted to contain an office, waiting and toilet rooms having a total combined area of not more than 1,000 square feet (93 m 2 ). Such area need not be separated from the open parking garage.
In open parking garages having a spiral or sloping floor, the horizontal projection of the structure at any cross section shall not exceed the allowable area per parking tier. In the case of an open parking garage having a continuous spiral floor, each 9 feet 6 inches (2896 mm) of height, or portion thereof, shall be considered a tier.
The clear height of a parking tier shall be not less than 7 feet (2134 mm), except that a lower clear height is permitted in mechanical-access open parking garages where approved by the commissioner.
406.5.5 Area and height increases.
The allowable area and height of open parking garages shall be increased in accordance with the provisions of this section. Garages with sides open on three-fourths of the building's perimeter are permitted to be increased by 25 percent in area and one tier in height. Garages with sides open around the entire building's perimeter are permitted to be increased by 50 percent in area and one tier in height. For a side to be considered open under the above provisions, the total area of openings along the side shall not be less than 50 percent of the interior area of the side at each tier and such openings shall be equally distributed along the length of the tier. For purposes of calculating the interior area of the side, the height shall not exceed 7 feet (2134 mm).
Allowable tier areas in Table 406.5.4 shall be increased for open parking garages constructed to heights less than the table maximum. The gross tier area of the garage shall not exceed that permitted for the higher structure. No fewer than three sides of each such larger tier shall have continuous horizontal openings not less than 30 inches (762 mm) in clear height extending for not less than 80 percent of the length of the sides and no part of such larger tier shall be more than 200 feet (60 960 mm) horizontally from such an opening. In addition, each such opening shall face a street or yard accessible to a street with a width of not less than 30 feet (9144 mm) for the full length of the opening, and standpipes shall be provided in each such tier.
Open parking garages of Type II construction, with all sides open, shall be unlimited in allowable area where the building height does not exceed 75 feet (22 860 mm). For a side to be considered open, the total area of openings along the side shall be not less than 50 percent of the interior area of the side at each tier and such openings shall be equally distributed along the length of the tier. All portions of tiers shall be within 200 feet (60 960 mm) horizontally from such openings or other natural ventilation openings as defined in Section 406.3.3.1. These openings shall be permitted to be provided in courts with a minimum dimension of 20 feet (6096 mm) for the full width of the openings.
406.5.6 Fire separation distance.
Exterior walls and openings in exterior walls shall comply with Tables 601 and 602. The distance from an adjacent property line shall be determined in accordance with Table 602 and Section 705.
406.5.7 Means of egress.
Open parking garages shall meet the means of egress requirements of Chapter 10. However, where no persons other than parking attendants are permitted, required exit stairways shall not be less than 36 inches (914 mm) wide.
406.5.8 Standpipes.
Standpipes shall be installed where required by the provisions of Section 905.
406.5.9 Enclosure of vertical openings.
Enclosure shall not be required for vertical openings.
406.5.10 Ventilation.
Openings specified in Section 406.5.2 shall satisfy natural ventilation requirements. Additional mechanical ventilation shall not be required.
406.5.11 Prohibitions.
The following uses and alterations are not permitted:
1. Vehicle repair work.
2. Parking of commercial vehicles, buses, trucks and similar vehicles.
3. Partial or complete closing of required openings in exterior walls by tarpaulins or any other means.
4. Dispensing of fuel.
406.6 Enclosed parking garages.
Parking garages and portions thereof that do not meet the definition of open parking garages shall be classified as an enclosed parking garage and shall meet the requirements of this section.
406.6.1 Heights and areas.
Enclosed parking garages shall be limited to the allowable heights and areas specified in Chapter 5. Permitted roof parking shall not be considered as a separate story.
406.6.2 Ventilation.
A mechanical ventilation system shall be provided in accordance with the New York City Mechanical Code.
406.6.3 Automatic sprinkler system.
Automatic sprinkler systems and standpipes shall be installed in accordance with the provisions of Section 903. An automatic dry sprinkler system may be installed in unheated garages.
406.6.4 Means of egress.
Enclosed parking garages shall meet the means of egress requirements of Chapter 10.
406.7 Motor fuel-dispensing facilities.
Motor fuel-dispensing facilities shall be designed and constructed in accordance with the New York City Fire Code and Sections 406.7.1 through 406.7.3 of this code.
406.7.1 Vehicle fueling pad.
The vehicle shall be fueled on noncoated concrete or other approved paving material having a resistance not exceeding 1 megohm as determined by the methodology in CEN 1081.
406.7.2 Canopies.
Canopies under which fuels are dispensed shall have a clear, unobstructed height of not less than 14 feet (4267 mm) to the lowest projecting element in the vehicle drive-through area. Canopies and their supports over pumps shall be of noncombustible materials. However, panels constructed of light-transmitting plastic materials shall be permitted to be installed in canopies erected over motor vehicle fuel-dispensing station fuel dispensers, provided the panels are located not less than 10 feet (3048 mm) from any building on the same property and face yards or streets not less than 40 feet (12 192 mm) in width on the other sides. The aggregate areas of plastics shall be not greater than 1,000 square feet (93 m 2 ). The maximum area of any individual panel shall shall be not greater than 100 square feet (9.3 m 2 ).
406.7.2.1 Canopies used to support gaseous hydrogen systems.
Where flammable compressed gases are permitted by the New York City Fire Code to be located on the roof of a canopy that is used to shelter dispensing operations, such canopy shall be in accordance with the following:
1. The canopy shall meet or exceed Type I construction requirements.
2. Operations located under canopies shall be limited to refueling only.
3. The canopy shall be constructed in a manner that prevents the accumulation of hydrogen gas.
406.7.3 Storage tanks.
Motor fuel storage tanks shall be installed below ground, except as authorized by the rules of the Fire Department. The installation and venting of storage tanks shall be in accordance with the rules of the Fire Department and the requirements of the New York City Fire Code. Storage tanks installed below ground shall comply with the following:
1. The top of the storage tanks shall be at least 24 inches (below finished grade and at least 24 inches (610 mm) below the level of any cellar or basement floor within 10 feet (3048 mm) of the tanks.
2. Storage tanks shall be located so that the forces from any building foundation and support loads are not transmitted to the tanks. The distance from any part of a storage tank to the nearest wall of any basement, pit or cellar, or from any property line that may be built upon, shall not be less than 36 inches (914 mm).
3. Storage tanks shall be covered with a structurally supported reinforced concrete slab at least 8 inches (203 mm) thick, extending at least 12 inches (305 mm) beyond the horizontal outlines of the storage tanks, and placed over a cover of suitable clean backfill material. Such slab shall be designed and reinforced in accordance with ACI 318. All concrete shall have a minimum compressive strength of 4,000 pounds per square inch (27 580 kPa) at 28 days.
4. Storage tanks shall be placed on a 12-inch (305 mm) thick concrete base slab or installed in such other manner, secured against flotation, and approved by the department.
406.8 Repair garages.
Repair garages shall be constructed in accordance with the New York City Fire Code and Sections 406.8.1 through 406.8.6 of this code. This occupancy shall not include motor fuel-dispensing facilities, as regulated in Section 406.7.
406.8.1 Mixed uses.
Mixed uses shall be allowed in the same building as a repair garage subject to the provisions of Section 508.1.
406.8.2 Ventilation.
Repair garages shall be mechanically ventilated in accordance with the New York City Mechanical Code. The ventilation system shall be controlled at the entrance to the garage.
406.8.3 Floor surface.
Repair garage floors shall be of concrete or similar noncombustible and nonabsorbent materials.
Exception: Slip-resistant, nonabsorbent, interior floor finishes having a critical radiant flux not more than 0.45 W/cm 2 , as determined by NFPA 253, shall be permitted.
406.8.4 Heating equipment.
Heating equipment shall be installed in accordance with the New York City Mechanical Code.
406.8.5 Gas detection system.
Repair garages used for the repair of vehicles fueled by CNG, LNG, or hydrogen, shall be provided with an approved flammable gas-detection system.
406.8.5.1 System design.
The flammable gas-detection system shall be listed or approved and shall be calibrated to the types of fuels or gases used by vehicles to be repaired. The gas detection system shall be designed to activate when the level of flammable gas exceeds 25 percent of the lower flammable limit (LFL). Gas detection shall be provided in lubrication or chassis service pits of repair garages used for repairing nonodorized LNG-fueled vehicles.
406.8.5.1.1 Gas detection system components.
Gas detection system control units shall be listed and labeled in accordance with UL 864 or UL 2017. Gas detectors shall be listed and labeled in accordance with UL 2075 for use with the gases and vapors being detected.
406.8.5.2 Operation.
Activation of the gas detection system shall result in all of the following:
1. Initiation of distinct audible and visual alarm signals in the repair garage.
2. Deactivation of all heating systems located in the repair garage.
3. Activation of the mechanical ventilation and exhaust system, where the system is interlocked with gas detection.
406.8.5.3 Failure of the gas detection system.
Failure of the gas detection system shall result in the deactivation of the heating system, activation of the mechanical ventilation system where the system is interlocked with the gas detection system and cause a trouble signal to sound in an approved location.
406.8.6 Automatic sprinkler system.
A repair garage shall be equipped with an automatic sprinkler system in accordance with Section 903.2.4.2.
406.9 Open Parking Lots.
The provisions of this section shall govern the construction of open parking lots and to all such existing premises hereafter enlarged or changed in location.
406.9.1 Definitions.
The following term is defined in Chapter 2:
OPEN PARKING LOT.
406.9.2 Permit required.
Any premise intended to be occupied for the storage or sale of motor vehicles on an open parking lot shall require an application to be filed with the department in order to obtain a Certificate of Occupancy. Such Certificate of Occupancy shall indicate the maximum number of vehicles to be accommodated and the type of vehicle, whether private passenger or commercial, to be stored. An application for or including an open parking lot shall be accompanied by a plan exhibiting the following:
1. Dimensions of the lot and its location in relation to adjoining streets;
2. Any structure(s) existing or to be erected on the plot;
3. The relative elevations of the parking area, curbs and adjoining yards or courts;
4. Structures, retaining walls, and open spaces on adjoining premises;
5. Retaining walls to be built;
6. Location and dimensions of curb cuts, driveways, and enclosures;
7. Drainage diagram;
8. Specification of surfacing material;
9. Parking stall layout with dimensions;
10. Analysis exhibiting compliance with the New York City Zoning Resolution; and
11. Other information as may be requested by the commissioner.
A copy of the plan or diagram approved by the department shall be kept on the premises. Certified, reduced size, legible copies may be used for this purpose. When an attendant's shelter is provided on the parking lot, the Certificate of Occupancy issued shall be posted and maintained under glass in the shelter.
406.9.3 Locations prohibited.
All vehicular activities associated with the operation of open parking lots shall be entirely within the property lines of the premises. Vehicles shall not be permitted to encroach upon the sidewalks. No motor vehicle may be stored or parked in any location where it would obstruct a required window or required exit of any adjacent building.
406.9.4 Surfacing.
All driveways, parking stalls, and open spaces used for the parking or storage of motor vehicles shall be surfaced with concrete asphalt, or equivalent durable, dustless material.
406.9.4.1 Drainage.
Open parking lots shall be graded and maintained such that no drainage will flow onto abutting sidewalks and adjoining properties.
406.9.4.2 Non-porous surfaces.
Where the surface paving of an open parking lot is non-porous, such lot shall be drained as required by the New York City Plumbing Code.
406.9.4.3 Resurfacing.
Resurfacing of existing open parking lots shall comply with this section.
406.9.5 Curbs and bumpers.
Open parking lots shall be completely separated from adjoining premises and public sidewalks by curbs or bumpers of concrete, masonry, steel, heavy timber, or other similar and equally substantial materials, and shall be securely anchored so as to stop motor vehicles. Curbs and bumpers shall be at least 8 inches (203 mm) high and 8 inches (203 mm) wide.
406.9.5.1 Openings.
Openings in required perimeter curbs and bumpers shall be permitted only for drainage, for motor vehicle entrances and exits, and for pedestrian entrances and exits. The width of an opening for motor vehicle access shall not exceed the length of the curb cut, not including the lengths of the splays. When an opening for pedestrian access is adjacent to a motor vehicle access opening, the two openings shall be separated by a permanent and substantial post. In no case shall any pedestrian entrance or exit exceed 5 feet (1524 mm) in width.
406.9.6 Accessory uses and occupancies.
Parking lot offices, attendant shelters, storage facilities, and similar structures used in conjunction with open parking lots may be provided as an accessory use and shall comply with the applicable code provisions. Such accessory structures may be constructed of combustible materials subject to the limitations of Section D105.1 of Appendix D.
406.9.6.1 Motor fuel-dispensing facilities.
Motor fuel-dispensing facilities, accessory to open parking lots, shall comply with the requirements of the New York City Fire Code and Section 406.8 of this code. Motor fuel pumps shall be located at least 30 feet (9144 mm) from any parking space or interior lot line.
406.9.7 Special provisions applicable to large open parking lots.
Open parking lots storing ten or more motor vehicles shall also be subject to the special provisions of this section.
406.9.7.1 Curbs and bumpers.
Bumpers shall be situated not less than 1 foot (305 mm) from the perimeter edge of the open parking lot where vehicles are parked parallel to such perimeter edge, and not less than 4 feet (1219 mm) from the perimeter edge where vehicles are parked perpendicular to such perimeter edge. Openings shall be limited as provided for in Section 406.9.5.1.
Exception: A steel guardrail or other substantial barrier designed in accordance with the provisions of Section 1607.9, that will prevent any part of a vehicle from extending across a property line, may be accepted in lieu of bumpers.
406.9.7.2 Screen enclosures.
Open parking lots shall provide a perimeter screen enclosure as per this section unless otherwise required by the New York City Zoning Resolution. Such screen enclosure may be constructed as a masonry wall, woven wire fence, iron picket fence, or uniformly painted fence of fire-resistant material at least 4 feet (1219 mm) high, but not more than 8 feet (2438 mm) above finished grade, subject to the limitations of Section 3111. Such enclosures shall completely separate the lot from adjoining premises and public sidewalks. Openings shall be limited as provided for in Section 406.9.5.1.
Exception: Screening shall not be required for any portion of the lot adjacent to an existing wall located at the lot line.
406.9.7.3 Illumination.
Open parking lots operating between 6 p.m. and 6 a.m. shall be adequately illuminated to a minimum of 1 footcandle measured at grade level, distributed over the entire area. Illumination provided with reflectors or floodlights shall be arranged such that the illumination is directed downward and away from adjacent premises.
406.9.7.4 Fire fighter aisles.
In any open parking lot, one or more aisles, at least 24 inches (610 mm) in width, shall be provided to permit access by fire-fighting personnel to all parts of the garage or lot. There shall not be more than three rows of parked motor vehicles between aisles.
406.9.8 Electric vehicle supply equipment (EVSE).
A new open parking lot and an existing open parking lot on the same tax lot or appurtenant to a building owned by the same owner of such open parking lot undergoing such significant alterations as established by the department by rule shall be capable of supporting and be equipped with EVSE in accordance with this section. A minimum of 20 percent of the parking spaces in such an open parking lot shall be equipped with level 2 charging stations. At least 60 percent of the parking spaces of the lot shall be capable of supporting EVSE. The installation of 1 direct current fast charging station shall be considered the equivalent of 10 level 2 charging stations, and the installation of direct current fast charging stations shall not be used to satisfy more than 50 percent of the level 2 charging stations required for purposes of compliance with this section. This amount of electrical capacity may be coupled with an electric vehicle load management system to distribute power to a greater percentage of spaces at lower amperage as EVSE penetration increases above 40 percent of parking spaces. All components and work appurtenant thereto, including ventilation system(s), shall be in accordance with the New York City Electrical Code and the New York City Mechanical Code.
Exceptions:
1. The commissioner may waive compliance with this section if the commissioner determines that the open parking lot is a temporary facility that will be in service no longer than 3 years.
2. The commissioner, upon consultation with the commissioner of housing preservation and development, shall grant a waiver of the requirements of this section for a parking garage within or appurtenant to a multiple dwelling in which 100 percent of dwelling units are required, pursuant to a federal, state, or local law, rule, or program to be affordable for tenants or owners where the occupant’s income relative to the area median income does not exceed a fixed percentage or percentages, and that is subject to an actual or anticipated agreement with a federal, state, or local governmental entity for the purposes of providing affordable housing in a given locality or region.
3. The commissioner of citywide administrative services may waive or adjust compliance with this section for parking lots on city owned or leased real property or the New York city housing authority may waive or adjust compliance with respect to real property owned or leased by such authority where such commissioner or authority, as applicable, determines that the installation of EVSE to the extent required by this section is not feasible for budgetary, operational, or programmatic reasons with respect to the ongoing citywide installation of EVSE or with respect to the issuance of a license or lease to a private person or entity to operate a parking lot.
4. The commissioner may waive or adjust compliance with this section if the commissioner finds that, upon submission of evidence from the owner, the provisions present an undue hardship resulting from technical infeasibility, including but not limited to:
4.1. The open parking lot utilizes equipment that enables vehicles to be parked vertically and the owner demonstrates that such vertical parking would make the use of EVSE infeasible, provided an adjustment may be granted so that only spaces where EVSE could feasibly be used will be required to do so to the maximum extent practicable to meet the requirements under this section; or
4.2. The owner provides evidence that a waiver or adjustment is necessary in order to comply with Appendix G.
(Am. L.L. 2024/055, 4/6/2024, eff. 12/21/2025)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2013/130 and L.L. 2024/055.
406.10 Curb cuts and driveways.
Except where specifically provided for in the New York City Zoning Resolution, all curb cuts and driveways shall be constructed in accordance with Sections 406.10.1 and 406.10.2. All sidewalks and driveways or portions thereof that are structurally supported shall be designed for loads prescribed in Chapter 16.
406.10.1 Curb cuts.
For the purpose of this section, a curb cut shall include all splays when determining the total length of cut curb. All curb cuts shall comply with the following requirements:
1. The aggregate length of curb cuts shall not exceed 60 percent of any street frontage 100 feet (30 480 mm) or less in length. No single curb cut shall exceed 30 feet (9144 mm) in length, and there shall not be more than two curb cuts on any street frontage 100 feet (30 480 mm) or less in length. The minimum distance between two curb cuts shall be 5 feet (1524 mm).
2. For each 50 feet (15 240 mm) of street frontage length over 100 feet (30 480 mm), an additional curb cut no greater than 30 feet (9144 mm) in length may be permitted.
3. No curb cut shall commence within 8 feet (2438 mm) of a side lot line.
Exceptions:
1. For open parking lots on corner lots and on lots with street frontage length of 50 feet (15 240 mm) or less, the curb cut may commence no less than 30 inches (762 mm) from the side lot line.
2. In open or enclosed parking garages where a level landing having a minimum dimension of 20 feet (6096 mm) is provided at the discharge point of all ramps at the street level within the property line, the curb cut may commence no less than 30 inches (762 mm) from a side lot line.
4. No curb cut, including splays, shall be less than 10 feet (3048 mm) in length.
406.10.2 Driveways.
Driveways serving passenger vehicles shall be a minimum of 8 feet (2438 mm) in width and shall not exceed the length of the curb cut, not including the lengths of the splays. For all other motor vehicles, the minimum width of driveways shall be 10 feet (3048 mm). Portions of the driveway located between the curb line and the lot line shall be paved in accordance with the requirements of the Department of Transportation for the construction of sidewalks.
406.11 Battery-powered industrial trucks, equipment and mobility devices.
Buildings or portions thereof that contain or store battery-powered industrial trucks, equipment and mobility devices shall be designed and constructed in accordance with Section 309.3 of the New York City Fire Code.