NYC Administrative Code Title 28, Chapter 7 New York City Building Code, part 30 of 33
Section BC G107 to Section BC H117: 40 sections.
Section BC G107. Periodic, Progress and Special Inspection Requirements
G107.1 General.
Periodic, progress and special inspections shall be performed in accordance with this section. All work applications, regardless of the scope of work, shall be subject to the progress and special inspection requirements of Sections G107.2 through G107.4.
G107.2 All work applications other than new buildings, horizontal enlargements and substantial improvements.
All work applications other than new buildings, horizontal enlargements and substantial improvements, shall be subject to the following special inspection:
1. Flood zone compliance special inspection. Prior to sign-off of work, a special inspector or special inspection agency shall inspect during the course of construction and certify that: "the structure was constructed" or "alterations were performed," "with methods and practices that minimize flood damage and that are in accordance with approved plans, and with any applicable provisions of Appendix G of the New York City Building Code and ASCE 24."
G107.3 New buildings, horizontal enlargements and substantial improvements.
All applications for new buildings, horizontal enlargements or substantial improvements shall be subject to the following inspections:
1. Elevation progress inspection. Upon placement of the lowest floor, including the basement (for flood zone purposes), an engineer or licensed professional surveyor shall inspect the site and verify the elevation of such lowest floor. The inspection report verifying the elevation shall be submitted to the department prior to further vertical construction. The commissioner shall be permitted to issue a stop work order if such inspection report is not submitted.
2. Flood zone compliance special inspection. Prior to sign-off of work, a special inspector or special inspection agency shall inspect during the course of construction and certify that: "the structure was constructed" or "alterations were performed," "with methods and practices that minimize flood damage and that are in accordance with approved plans, and with any applicable provisions of Appendix G of the New York City Building Code and ASCE 24."
3. Final elevation required items. Prior to the sign-off of the flood zone compliance special inspection, the special inspector or special inspection agency shall verify that the following required items have been submitted to the department, as applicable:
3.1. Elevation certificate. The elevation certificate shall be made utilizing FEMA Form 086-0-33 titled, "Elevation Certificate", and shall be signed by a registered design professional or surveyor.
3.2. Dry floodproofing certificate. The dry floodproofing certificate shall be made utilizing FEMA Form 086-0-34 titled, "Floodproofing Certificate", and shall be signed by a registered design professional.
G107.4 Flood shield inspection.
Where flood shields or other flood control devices are installed as part of a dry floodproofing system in buildings and structures that are nonresidential (for flood zone purposes), the special inspector or special inspection agency responsible for the flood zone compliance special inspection shall inspect the shields or devices in their stored positions or locations, witness their activation or transportation to their installed positions, and witness their deactivation or transportation back to their stored locations. The special inspector or special inspection agency shall also confirm the installation of signage required by ASCE 24, Section 6.2.3, Item 3.
G107.5 Periodic inspections of dry floodproofing systems.
Covered buildings, as described in Section 28-324 of the Administrative Code, shall be subject to periodic inspections for dry floodproofing systems in accordance with Sections G107.5.1 and G107.5.2.
G107.5.1 Annual inspection of dry floodproofing system.
An inspection of the dry floodproofing system shall be conducted annually in accordance with Section 28-324.2 of the Administrative Code.
G107.5.2 Triennial full scale deployment inspection.
A full-scale deployment inspection shall be conducted every three years in accordance with Section 28-324.3 of the Administrative Code.
Section BC G201. Definitions
G201.1 Definitions.
This section contains terms defined elsewhere in this code, and terms with definitions that are specific to this appendix.
G201.1.1 Terms defined elsewhere in this code.
The following terms are defined in Chapter 2:
500-YEAR FLOOD ELEVATION.
A-ZONE.
BASE FLOOD.
BASE FLOOD ELEVATION.
BASEMENT (FOR FLOOD ZONE PURPOSES).
BREAKAWAY WALL.
COASTAL A-ZONE.
COASTAL HIGH-HAZARD AREA.
DESIGN FLOOD ELEVATION.
FLOOD or FLOODING.
FLOOD-DAMAGE-RESISTANT MATERIALS.
FLOOD HAZARD AREA.
FLOOD INSURANCE RATE MAP (FIRM).
FLOOD INSURANCE STUDY (FIS).
FLOODPROOFING, DRY.
FLOODPROOFING, WET.
FLOODWAY.
LOWEST FLOOR.
NATIONAL GEODETIC VERTICAL DATUM (NGVD).
NONRESIDENTIAL (FOR FLOOD ZONE PURPOSES).
NORTH AMERICAN VERTICAL DATUM (NAVD).
PATIENT CARE AREA (FOR FLOOD ZONE PURPOSES).
RESIDENTIAL (FOR FLOOD ZONE PURPOSES).
SAND DUNES.
SHADED X-ZONE.
SPECIAL FLOOD HAZARD AREA.
SUBSTANTIAL DAMAGE.
SUBSTANTIAL IMPROVEMENT.
V-ZONE.
G201.1.2 Definitions specific to this appendix.
The following words and terms shall, for the purposes of this appendix, have the meanings shown herein:
DEVELOPMENT. Any man-made change to improved or unimproved real estate, including but not limited to, buildings or other structures, temporary structures, temporary or permanent storage of materials, mining, dredging, filling, grading, paving, excavations or drilling operations and other land-disturbing activities.
EXISTING CONSTRUCTION. See "Pre-FIRM development."
EXISTING STRUCTURE. See "Pre-FIRM development."
FLOOD DESIGN CLASS. A classification of buildings and other structures for determination of flood loads and conditions, and determination of minimum elevation requirements on the basis of risk associated with unacceptable performance.
FUNCTIONALLY DEPENDENT FACILITY. A facility that cannot be used for its intended purpose unless it is located or carried out in close proximity to water. The term includes only docking facilities, port facilities that are necessary for loading and unloading of cargo or passengers and shipbuilding and ship repair facilities, but does not include long-term storage or related manufacturing, sales or service facilities.
HISTORIC STRUCTURE. Any structure that meets one of the following criteria:
1. Listed individually in the National Register of Historic Places;
2. Certified by the Secretary of the U.S. Department of the Interior as meeting the requirements for individual listing in the National Register;
3. Certified or preliminarily determined by the Secretary of the U.S. Department of the Interior to be contributing to the historical significance of a registered historic district or a district preliminarily determined by the Secretary of the U.S. Department of the Interior to qualify as a registered historic district;
4. Individually listed or preliminarily determined to be eligible for listing in the New York State Register of Historic Places; or
5. Individually listed as a landmark by the NYC Landmarks Preservation Commission. Location within a historic district does not alone qualify as being an individually listed landmark.
LETTER OF MAP AMENDMENT (LOMA). An official amendment to the FIRM, issued and approved by the Federal Emergency Management Agency (FEMA), removing structures or tax lots or portions of tax lots from special flood hazard areas, resulting from a demonstration that the pre-FIRM ground elevations are at or above the base flood elevation.
LETTER OF MAP REVISION BASED ON FILL (LOMR-F). An official amendment to the FIRM, issued and approved by the Federal Emergency Management Agency (FEMA), removing structures or tax lots or portions of tax lots from special flood hazard areas, resulting from the post-FIRM placement of compacted fill, such that the new ground elevation is at or above the base flood elevation.
LETTER OF MAP REVISION (LOMR). An official amendment to the FIRM, issued and approved by the Federal Emergency Management Agency (FEMA), removing or adding structures or tax lots or portions of tax lots from special flood hazard areas, which generally results from physical measures implemented that affect the hydrologic or hydraulic characteristics of a flooding source and thus result in the modification of the existing regulatory floodway, the effective base flood elevations, or the special flood hazard area.
MANUFACTURED HOME. A structure that is transportable in one or more sections, built on a permanent chassis, designed for use with or without a permanent foundation when attached to the required utilities, and constructed to the Federal Mobile Home Construction and Safety Standards and rules and regulations promulgated by the U.S. Department of Housing and Urban Development. The term also includes mobile homes, park trailers, travel trailers and similar transportable structures that are placed on a site for 180 consecutive days or longer.
MANUFACTURED HOME PARK OR SUBDIVISION. A parcel (or contiguous parcels) of land divided into two or more manufactured home lots for rent or sale.
MARKET VALUE OF STRUCTURE. The price that a buyer is willing, but is not under any duty, to pay for a particular structure to an owner who is willing, but not obligated, to sell, exclusive of the value of the land, or of other buildings or structures on the same tax lot. The market value of a structure shall be determined in accordance with rules promulgated by the commissioner.
NEW CONSTRUCTION. See "Post-FIRM development."
POST-FIRM DEVELOPMENT. Any development that is not pre-FIRM development.
POST-FIRM STRUCTURE. See "Post-FIRM development."
PRE-FIRM DEVELOPMENT. Any development:
1. Completed prior to November 16, 1983;
2. Under construction on November 16, 1983, provided that the start of construction was prior to said date; or
3. Completed on or after November 16, 1983, but that:
3.1. Was not located within a special flood hazard area at the start of construction; and
3.2. Is now located within a special flood hazard area as a result of a subsequent change to the FIRM.
PRE-FIRM STRUCTURE. See "Pre-FIRM development."
RECREATIONAL VEHICLE. A vehicle that is built on a single chassis, 400 square feet (37.16 m 2 ) or less when measured at the largest horizontal projection, designed to be self-propelled or permanently towable by a light-duty truck, and designed primarily not for use as a permanent dwelling but as temporary living quarters for recreational, camping, travel or seasonal use. A recreational vehicle is ready for highway use if it is on its wheels or jacking system, is attached to the site only by quick disconnect-type utilities and security devices and has no permanently attached additions.
START OF CONSTRUCTION. The date of permit issuance for: (i) post-FIRM developments; (ii) substantial improvements to pre-FIRM structures; and (iii) those pre-FIRM developments that, at the time of permit issuance, were not within a special flood hazard area but that, prior to completion, were within a special flood hazard area as a result of map change; provided the actual commencement of construction, repair, reconstruction, rehabilitation, addition, placement or other improvement is within 180 days after the date of permit issuance and such construction activity is not thereafter suspended or abandoned for 180 days or more. For the purposes of this definition:
1. The actual commencement of construction means the first placement of permanent construction of a building (including a manufactured home or prefabricated building) on a site, such as the pouring of a slab or footings, installation of pilings or construction of columns.
2. Permanent construction does not include land preparation (such as clearing, excavation, grading or filling), the installation of streets or walkways, excavation for a basement (for flood zone purposes), footings, piers or foundations, the erection of temporary forms or the installation of accessory buildings such as garages or sheds not occupied as dwelling units or not part of the main building.
3. For a substantial improvement, the actual commencement of construction means the first alteration of any wall, ceiling, floor or other structural part of a building, regardless of whether that alteration affects the external dimensions of the building.
VARIANCE. A grant of relief from the requirements of this appendix, which permits construction in a manner otherwise prohibited by this appendix.
Section BC G301. Construction Standards
G301.1 All developments.
To the extent required by Section G102.1, all developments, including but not limited to utility installation, site improvements, placement of prefabricated buildings and manufactured homes, new building construction, alterations and repairs, shall be designed and constructed to resist the effects of flood hazards and flood loads in accordance with this appendix and ASCE 24.
G301.1.1 Multiple flood zones.
For a structure that is located in more than one zone (for instance both an A-Zone and an X-Zone, or both an A-Zone and a V-Zone), the provisions associated with the most restrictive zone shall apply to the entire structure.
G301.2 Design requirements and load combinations.
Any construction subject to the requirements of Section G102.1 shall be designed and constructed to resist the loads and load combinations specified in Chapter 16.
Section BC G302. Subdivisions
G302.1 General.
Any subdivision proposal, including proposals for manufactured home parks and subdivisions, or other proposed new development within a special flood hazard area shall be reviewed to verify all of the following:
1. All such proposals are consistent with the need to minimize flood damage.
2. All public utilities and facilities, such as sewer, gas, electric and water systems, are located and constructed to minimize or eliminate flood damage.
3. Adequate drainage is provided to reduce exposure to flood hazards.
G302.2 Subdivision requirements.
The following requirements shall apply in the case of any proposed subdivision, including proposals for manufactured home parks and subdivisions, any portion of which lies within a special flood hazard area:
1. The special flood hazard area, including floodways, coastal high-hazard areas and coastal A-Zones, as appropriate, shall be delineated on tentative and final subdivision plats.
2. Base flood elevations shall be shown on tentative and final subdivision plats.
3. Building lots shall be provided with adequate buildable area, in accordance with the New York City Zoning Resolution, outside the floodway.
4. The design criteria for utilities and facilities set forth in this appendix and appropriate New York City Construction Codes shall be met.
Section BC G303. Site Improvement
G303.1 Development in floodways.
Development or land-disturbing activity shall not be authorized in the floodway unless it has been demonstrated through hydrologic and hydraulic analyses performed in accordance with standard engineering practice, and prepared by a registered design professional, that the proposed encroachment will not result in any increase in the base flood level, in accordance with Section G103.5.
G303.2 Coastal high-hazard areas and coastal A-Zones.
In coastal high-hazard areas and coastal A-Zones:
1. New buildings, not including substantial improvements, shall only be authorized landward of the reach of mean high tide.
2. The use of fill for structural support of buildings is prohibited.
G303.3 Sewer facilities.
All new or replaced sanitary sewer facilities, private sewage treatment plants (including all pumping stations and collector systems) and on-site waste disposal systems shall be designed in accordance with Chapter 7, ASCE 24, to minimize or eliminate infiltration of floodwaters into the facilities and discharge from the facilities into floodwaters, or impairment of the facilities and systems.
G303.4 Water facilities.
All new or replacement water facilities shall be designed in accordance with the provisions of Chapter 7, ASCE 24, to minimize or eliminate infiltration of floodwaters into the systems.
G303.5 Storm drainage.
Storm drainage shall be designed to convey the flow of surface waters to minimize or eliminate damage to persons or property and shall meet the requirements of ASCE 24.
G303.6 Streets and sidewalks.
Streets and sidewalks shall be designed to minimize potential for increasing or aggravating flood levels and shall meet the requirements of Section G303.8.
G303.7 Retaining walls and driveways.
Retaining walls shall be designed in accordance with Section 1807. Retaining walls and driveways shall meet the requirements of Section G303.8.
G303.8 Grading and fill.
In flood hazard areas, grading and/or fill shall not be approved:
1. Unless such fill is placed, compacted and sloped to minimize shifting, slumping and erosion during the rise and fall of flood water and, as applicable, wave action, in accordance with ASCE 24 and Section 1804 of this code.
2. In floodways, unless it has been demonstrated through hydrologic and hydraulic analyses performed by an engineer in accordance with standard engineering practice that the proposed grading or fill, or both will not result in any increase in the flood levels during the occurrence of the design flood, in accordance with Section G103.5.
3. In coastal A-Zones and coastal high-hazard areas, unless such fill is conducted and or placed to avoid diversion of water and waves towards any building or structure.
Section BC G304. Post-FIRM Construction, Horizontal Enlargements and Substantial Improvements
G304.1 A-Zone construction standards.
In addition to the requirements of ASCE 24, the following standards shall apply to post-FIRM construction, horizontal enlargements and substantial improvements located within A-Zones, other than Coastal A-Zones.
G304.1.1 Residential.
For buildings or structures that are residential (for flood zone purposes), all post-FIRM new buildings, horizontal enlargements and substantial improvements shall comply with the applicable requirements of this appendix and ASCE 24, and shall be elevated as follows:
1. Lowest floor. The lowest floor, including the basement (for flood zone purposes), shall be elevated to or above the design flood elevation specified in ASCE 24, Table 2-1;
2. Enclosures below the design flood elevation. Enclosed spaces below the design flood elevation specified in ASCE 24, Table 2-1, shall be useable solely for parking of vehicles, building access, storage, or crawlspace, and shall be wet floodproofed in accordance with ASCE 24. Breakaway walls are not required in A-Zones;
2.1. A restrictive declaration noting the above restriction shall be filed with the City Register or County Clerk, and the City Register File Number (CRFN) shall be identified in the permit application and on the certificate of occupancy.
3. Under-floor spaces. The finished ground level of an under-floor space, such as a crawl space, shall be equal to or higher than the outside finished ground level on at least one side;
4. Materials. Only flood-damage-resistant materials and finishes shall be utilized below the design flood elevation specified in ASCE 24, Table 5-1;
5. Utilities and equipment. Utilities and attendant equipment shall be located at or above the design flood elevation specified in ASCE 24, Table 7-1, or with the exception of the items below, shall be constructed so as to prevent water from entering or accumulating within the components during conditions of flooding in accordance with ASCE 24.
5.1 Fire protection systems and equipment. The following fire protection systems and equipment shall be located at or above the design flood elevation specified in ASCE 24, Table 7-1, except that where the system or equipment or portion thereof serves only spaces located below such design flood elevation, the system or equipment or portion thereof may be located at or above such design flood elevation:
5.1.1. Sprinkler control valves that are not outside stem and yoke valves;
5.1.2. Fire standpipe control valves that are not outside stem and yoke valves;
5.1.3. Sprinkler booster pumps and fire pumps;
5.1.4. Dry pipe valve-related electrically operated alarm appurtenances;
5.1.5. Alarm control panels for water and non-water fire extinguishing systems;
5.1.6. Alarm control panels for sprinkler systems, pre-action sprinkler systems, deluge sprinkler systems, and combined dry pipe and pre-action sprinkler systems;
5.1.7. Electrically operated waterflow detection devices serving sprinkler systems and
5.1.8. Air compressors serving sprinkler systems and pre-action sprinkler systems.
5.2 Fire alarm systems and components. Where a zoning indicator panel is provided at the main building entrance in accordance with Section 907.6.3.1 of this code and such panel is located at or below 5 feet (1524 mm) above the design flood elevation specified in ASCE 24, Table 7-1, at least one secondary zoning indicator panel complying with the following requirements shall be provided:
5.2.1. The secondary zoning indicator panel, associated controls, power supplies and means of transferring control shall be provided at least 5 feet (1524 mm) above the design flood elevation specified in ASCE 24, Table 7-1, in a location accessible to responding Fire Department personnel and approved by the department and the Fire Department and
5.2.2. Where the secondary zoning indicator panel or associated controls are only operable upon transfer of control from another zoning indicator panel, such transfer shall be by a means that is approved by the Fire Department.
5.3 Fuel-oil piping systems. The following requirements shall apply to fuel-oil piping systems, as defined by Section 202 of the New York City Mechanical Code:
5.3.1. Fill piping that does not terminate in a watertight terminal approved by the department shall terminate at least 3 feet (914 mm) above the design flood elevation specified in ASCE 24, Table 7-1 and
5.3.2. Normal vent piping and emergency vent piping shall terminate at least 3 feet (914 mm) above the design flood elevation specified in ASCE 24, Table 7-1.
5.4 Plumbing systems and components. The structure shall comply with the following requirements:
5.4.1. Relief vents and fresh air intakes. Relief vents and fresh air intakes serving building traps in accordance with Section 1002.6 of the New York City Plumbing Code shall be carried above grade and shall terminate in a screened outlet that is located outside of the building and at or above the design flood elevation specified in ASCE 24, Table 7-1 and
5.4.2. Reduced pressure zone backflow preventers.
5.4.2.1. Primary reduced pressure principle backflow preventers complying with the requirements of the Department of Environmental Protection shall be located at or above the design flood elevation specified in ASCE 24, Table 7.1.
5.4.2.2. Secondary reduced pressure principle backflow preventers complying with Section 608.13.2 of the New York City Plumbing Code and backflow preventers with intermediate atmospheric vents complying with Section 608.13.3 of the New York City Plumbing Code shall be located at or above the design flood elevation specified in ASCE 24, Table 7-1.
5.4.3. Relief vents for gas service, equipment, and appliance pressure regulators. Relief vents for gas service, equipment, and appliance pressure regulators complying with the New York City Fuel Gas Code shall be located at or above the design flood elevation specified in ASCE 24, Table 7.1.
6. Certifications. Applications shall contain applicable certifications in accordance with Section G104.5; and
7. Special inspections. Special inspections shall be as required by Section G107.
G304.1.2 Nonresidential.
For buildings or structures that are nonresidential (for flood zone purposes), all post-FIRM new buildings, horizontal enlargements and substantial improvements shall comply with the applicable requirements of this appendix and ASCE 24, and shall comply with either of the following:
1. Elevation option. The structure shall comply with Items 1 through 7 of Section G304.1.1; or
2. Dry floodproofing option. The structure shall comply with the following:
2.1. Elevation of dry floodproofing. The structure shall be dry floodproofed to or above the design flood elevation specified in ASCE 24, Table 6-1;
2.2. Dwelling units, patient care areas (for flood zone purposes) and sleeping areas. Where dwelling units, patient care areas (for flood zone purposes) or spaces intended to be used by persons for sleeping purposes are located in a building utilizing the dry floodproofing option, the following additional requirements shall be met:
2.2.1. All rooms and spaces within dwelling units, patient care areas (for flood zone purposes) and all spaces intended to be used by persons for sleeping purposes shall be located at or above the design flood elevation;
2.2.2. A restrictive declaration noting the above restriction shall be filed with the City Register or County Clerk, and the City Register File Number (CRFN) shall be identified in the permit application and on the certificate of occupancy.
2.3. Utilities and equipment. Utilities and attendant equipment shall be located within the dry floodproofed enclosure, or may be located outside the dry floodproofed enclosure provided that they are located at or above the design flood elevation specified in ASCE 24, Table 7-1 or are constructed so as to prevent water from entering or accumulating within the components during conditions of flooding in accordance with ASCE 24.
2.3.1 Additional requirements. Notwithstanding the above, utilities and attendant equipment, listed in Items 5.1 through 5.4 of Section G304.1.1, shall not be located in dry floodproofed enclosures and shall be elevated in accordance with Section G304.1.1.
2.4. Fire department connections. Dry floodproofing measures including temporary shields, stairs and ramps shall be located and arranged so as to allow hose lines to be attached to the inlets of fire department connections without interference in accordance with Section 6.4.5 of NFPA 14, as modified by Appendix Q of this code.
2.5. Certifications. Applications shall contain applicable certifications in accordance with Section G104.3.2; and
2.6. Special inspections. Special inspections shall be as required by Section G107.
G304.2 Coastal high-hazard area construction standards.
In addition to the requirements of ASCE 24, the following standards shall apply to post-FIRM construction, horizontal enlargements and substantial improvements located within coastal high-hazard area.
1. Foundation. The lowest floor shall be elevated on adequately anchored pilings or columns and securely anchored to such piles or columns to prevent flotation, collapse and lateral movement resulting from wind and flood loads acting simultaneously on all building components, and other load requirements of Chapter 16 and this appendix.
2. Lowest horizontal member. The lowest portion of the lowest horizontal structural member of the lowest floor (excluding the pilings or columns) shall be at or above the design flood elevation specified in ASCE 24, Table 4-1.
3. Below the lowest horizontal member. Spaces below the lowest horizontal member shall be either:
3.1. Free of obstructions; or
3.2. Enclosed with breakaway walls providing unconditioned space useable solely for parking of vehicles, building access, storage or crawl space. Such breakaway walls shall:
3.2.1. Be of an open lattice type construction only;
3.2.2. Meet the load requirements of Section 5.3.3 of ASCE 7; and
3.2.3. Meet the additional requirements of ASCE 24.
4. Materials. Only flood-damage-resistant materials and finishes shall be utilized below the design flood elevation specified in ASCE 24, Table 5-1;
5. Utilities and equipment. Utilities and attendant equipment shall be located at or above the design flood elevation specified in ASCE 24, Table 7-1, or shall be constructed so as to both resist the wave action and prevent water from entering or accumulating within the components during conditions of flooding in accordance with ASCE 24;
5.1. Additional requirements. The structure shall comply with Items 5.1 through 5.4 of Section G304.1.1.
6. Prohibitions. The following shall be prohibited in coastal high-hazard areas:
6.1. Development, including land disturbing activities, seaward of the reach of mean high tide;
6.2. Use of fill for structural support of buildings; and
6.3. Man-made alterations of sand dunes that would increase potential damage to buildings.
7. Certifications. Applications shall contain applicable certifications in accordance with Section G104.2.3; and
8. Special inspections. Special inspections shall be as required by Section G107.
G304.3 Coastal A-Zone construction standards.
In addition to the requirements of ASCE 24, all post-FIRM new buildings, horizontal enlargements and substantial improvements in a Coastal A-Zone shall comply with the coastal high-hazard area construction standards of Section G304.2.
Exceptions: The following structural systems shall be permitted in a Coastal A-Zone:
1. Wave-resisting stem wall foundation. Stem walls supporting a floor system above, and backfilled with soil or gravel to the underside of the floor system, shall be permitted in Coastal A-Zones. The design and construction of the shallow foundation system shall comply with the following:
1.1. The underside of such floor system shall be located at or above the design flood elevation specified in ASCE 24, Table 4-1.
1.2. Stem walls enclosing areas below the design flood elevation shall not be permitted. Stem walls shall be designed to transfer all vertical and lateral forces to the slab above and to the foundation elements below;
1.3. The design shall consider all forces resulting from flooding, including wave action, debris impact, erosion, and local scour;
1.4. The design shall consider all forces resulting from soil pressure behind the walls, including the effect of hydrostatic loads, and all live and dead surcharge loads from the slab above;
1.5. Flood openings shall not be required in stem walls constructed in accordance with this section;
1.6. Where soils are susceptible to erosion and local scour, stem walls shall be supported by deep footings;
1.7. Shallow foundations including spread footing, mat and raft foundations shall be designed to prevent sliding, uplift, or overturning when exposed to the combination of loads in ASCE 24, Section 1.6.2.
2. Wave-resisting dry floodproofing wall and foundation system. Buildings that are nonresidential (for flood zone purposes) and that are located in Coastal A-Zones shall be permitted to be dry floodproofed in accordance with Section G304.1.2. Such structure shall be dry floodproofed to or above the design flood elevation specified in ASCE 24, Table 6-1. Flood zone compliance plans shall include calculations demonstrating that the foundation and building, including flood shields if provided, will resist the wave action, including the combination of loads in ASCE 24, Section 1.6, to or above the design flood elevation.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
G304.4 Construction standards for shaded X-Zones.
In shaded X-Zones, flood design class 4 buildings, as defined in ASCE 24, Table 1-1, shall comply with the requirements of this appendix and the applicable provisions of ASCE 24 for A-Zone construction.
G304.4.1 Alterations to certain flood design class 4 buildings.
Where existing emergency vehicle garages and fire, rescue, ambulance, and police stations located within shaded X-Zones are undergoing either a substantial improvement or an increase in the degree of noncompliance as such term is described in Item 10 of Section G102.1, they shall comply with this appendix to the maximum extent practicable as described in Sections G304.4.1.1 through G304.4.1.4.
G304.4.1.1 Existing emergency vehicle garages and fire, rescue, ambulance, and police stations to remain.
Where an existing emergency vehicle garage or fire, rescue, ambulance, or police station building is undergoing substantial improvement or an increase in the degree of noncompliance, such existing emergency vehicle storage area shall be permitted to be located below the design flood elevation, provided such space is wet floodproofed in accordance with ASCE 24 and an emergency action plan is filed with the department in accordance with ASCE 24, Section 6.2.3. Such emergency action plan shall include actionable directives for the relocation of such emergency vehicles in advance of a flood event.
G304.4.1.2 Equipment within existing emergency vehicle garages and fire, rescue, ambulance, and police stations.
Where an existing emergency vehicle garage or fire, rescue, ambulance, or police station building is undergoing substantial improvement or an increase in the degree of noncompliance, equipment necessary to support operations of such facilities may be located below the design flood elevation where elevation of such equipment to the design flood elevation is physically unfeasible. Such equipment shall be elevated to the maximum extent practicable.
G304.4.1.3 Conversion of space below the design flood elevation.
Conversion of existing nonoccupiable space to occupiable space without such space being in full compliance with this appendix shall be prohibited.
G304.4.1.4 Subgrade spaces to remain.
Where an existing emergency vehicle garage or fire, rescue, ambulance, or police station building is undergoing substantial improvement or an increase in the degree of noncompliance, the existing subgrade space shall be provided with a sump pump system, designed to be fully submerged and remain operational post-flood-event to remove flood waters after a storm surge has receded. Such pump system shall be designed with the pump controller located above the design flood elevation and all electrical wiring below the design flood elevation shall be listed and marked for use with a submersible pump. The pump system shall be connected to a standby power source, which shall be elevated above the design flood elevation.
G304.5 Additional construction standards with respect to connections for temporary external generators, boilers and chillers.
In addition to the other requirements of this appendix, connections for temporary external generators, boilers and chillers shall be provided in accordance with Sections G304.5.1 through G304.5.4.
G304.5.1 Group I-1 and adult homes, enriched housing, community residences and intermediate care facilities.
An occupancy that is classified as Group I-1, or that is an adult home, enriched housing, community residence or intermediate care facility and classified as Group R pursuant to an exception to Section 308.3.1 or 308.3.2, shall comply with the following requirements:
1. Connections for temporary external generators. Electrical connections shall be provided allowing for the connection of temporary external generators capable of providing power for at least 72 hours for, at a minimum, the following systems:
1.1. Exit signs and means of egress illumination required by Chapter 10 and serving such occupancy;
1.2. Fire alarm systems serving such occupancy;
1.3. For buildings having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access, at least one elevator that serves all floors; and
1.4. Lighting in such occupancy, sufficient to maintain illumination in accordance with Section 1205.3, for (i) spaces primarily used for the provision of medical services to persons, including, but not limited to, consultation, evaluation, monitoring and treatment services and (ii) spaces intended to be used by persons for sleeping purposes.
Exception: Connections for temporary external generators shall not be required for buildings with emergency or standby power systems that are permanently installed above the design flood elevation specified in Table 7-1 of ASCE 24 and capable of providing power for at least 72 hours to the systems identified in Item 1 of Section G304.5.1. Natural gas shall be a permitted fuel supply.
2. Flood protection for temporary external generator connections. Electrical connections installed in accordance with Item 1 of Section G304.5.1 shall be located at or above the design flood elevation specified in Table 7-1 of ASCE 24.
3. Emergency connection plan. Prior to sign-off of work by the department, a plan shall be submitted to the department that identifies how the temporary external generators will be connected and capable of providing power for the occupancy in accordance with Item 1 of Section G304.5.1 within 72 hours after failure of the normal power supply.
G304.5.2 Group I-2 hospitals.
An occupancy that is a Group I-2 hospital shall comply with the following requirements:
1. Connections for temporary external generators. Electrical connections shall be provided allowing for the connection of temporary external generators capable of providing power for at least 72 hours for, at a minimum, the following systems:
1.1. All electrical services serving such occupancy for which emergency or standby power must be provided in accordance with any other applicable local, state or federal law or rule; and
1.2. Air conditioning and cooling systems serving such occupancy, sufficient to maintain temperature and humidity in accordance with Section 1204, for (i) spaces primarily used for the provision of medical services to persons, including, but not limited to, consultation, evaluation, monitoring and treatment services and (ii) spaces intended to be used by persons for sleeping purposes.
Exception: Connections for temporary external generators shall not be required for buildings that have emergency or standby power systems that are permanently installed above the design flood elevation specified in Table 7-1 of ASCE 24 and capable of providing power for at least 72 hours to the systems identified in Item 1 of Section G304.5.2. Natural gas shall be a permitted fuel supply.
2. Connections for temporary external boilers and chillers. Where boiler and chiller plants are located below the design flood elevation specified in Table 7-1 of ASCE 24 and serve (i) spaces primarily used for the provision of medical services to persons, including, but not limited to, consultation, evaluation, monitoring and treatment services or (ii) spaces intended to be used by persons for sleeping purposes, connections shall be provided to allow for the connection of temporary external boilers and chillers capable of maintaining temperature and humidity for such spaces in accordance with Section 1204 for at least 72 hours.
3. Flood protection for temporary external generator, boiler and chiller connections. Electrical connections installed in accordance with Item 1 of Section G304.5.2 and connections installed in accordance with Item 2 of Section G304.5.2 shall be located at or above the design flood elevation specified in Table 7-1 of ASCE 24.
4. Emergency connection plan. Prior to sign-off of work by the department, the following shall be submitted to the department:
4.1. For an occupancy required to comply with Item 1 of Section G304.5.2, a plan that identifies how the temporary external generators will be connected and capable of providing power for the occupancy in accordance with such item within 72 hours after failure of the normal power supply; and
4.2. For an occupancy required to comply with Item 2 of Section G304.5.2, a plan that identifies how the temporary external boilers and chillers will be connected and capable of maintaining temperature and humidity for specified spaces in accordance with Section 1204 within 72 hours after failure of the primary boiler and chiller plants.
G304.5.3 Group I-2 nursing homes.
An occupancy that is a Group I-2 nursing home shall comply with Section G304.5.2.
Exception: Such occupancy is not required to comply with Items 1.2, 2 and 4.2 of Section G304.5.2.
G304.5.4 Group I-2 occupancies, other than hospitals and nursing homes.
A Group I-2 occupancy, other than a hospital or a nursing home, shall comply with Section G304.5.1.
Section BC G305. Manufactured Homes
G305.1 Elevation.
All new and replacement manufactured homes shall be prohibited in coastal high-hazard areas. Within A-Zones, all new, replaced or substantially improved manufactured homes shall be elevated such that the lowest floor of the manufactured home is elevated to or above the design flood elevation as specified in ASCE 24, Table 2-1.
G305.2 Foundations.
Within A-Zones, all new and replacement manufactured homes, including substantial improvement of existing manufactured homes, shall be placed on a permanent, reinforced foundation that is designed in accordance with ASCE 24.
G305.3 Anchoring.
Manufactured homes shall be securely anchored to an adequately anchored foundation system to resist flotation, collapse and lateral movement. Methods of anchoring are authorized to include, but are not limited to, use of over-the-top or frame ties to ground anchors. This requirement is in addition to applicable state and local anchoring requirements for resisting wind forces.
G305.4 Protection of mechanical equipment and outside appliances.
Mechanical equipment and outside appliances shall be elevated to or above the design flood elevation.
Exception: Where such equipment and appliances are designed and installed to prevent water from entering or accumulating within their components and the systems are constructed to resist hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy, during the occurrence of flooding up to the elevation required by ASCE 24, Table 2-1, the systems and equipment shall be permitted to be located below the elevation required by ASCE 24, Table 2-1. Electrical wiring systems shall be permitted below the design flood elevation provided they conform to the provisions of the New York City Electrical Code.
G305.5 Enclosures.
Fully enclosed areas below elevated manufactured homes shall comply with the requirements of Section G304.1.1, Item 2.
Section BC G306. Recreational Vehicles
G306.1 Placement prohibited.
The placement of recreational vehicles shall not be authorized in coastal high-hazard areas or in floodways.
G306.2 Temporary placement in A-Zones.
Recreational vehicles in A-Zones shall be fully licensed and ready for highway use, and shall be placed on a site for less than 180 consecutive days.
G306.3 Permanent placement.
Recreational vehicles in A-Zones that are not fully licensed and ready for highway use, or that are to be placed on a site for 180 or more consecutive days, shall meet the requirements of Section G305 for manufactured homes.
Section BC G307. Tanks
G307.1 Underground tanks.
Underground tanks in special flood hazard areas shall be designed, constructed, installed, and anchored to prevent flotation, collapse and lateral movement resulting from hydrostatic loads, including the effects of buoyancy, during conditions of flooding to the design flood elevation, in accordance with ASCE 24.
G307.2 Above-ground tanks.
Editor's note: this section has been amended by L.L. 2026/012, 1/3/2026, eff. 1/1/2028.
Above-ground tanks in special flood hazard areas shall be:
1. Elevated to or above the design flood elevation specified in ASCE 24, Table 7-1; or
2. Designed, constructed, installed, and anchored to prevent flotation, collapse and lateral movement resulting from hydrodynamic and hydrostatic loads, including the effects of buoyancy, during conditions of flooding to the design flood elevation, in accordance with ASCE 24.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2026/012.
G307.3 Tank inlets and vents.
Editor's note: this section has been amended by L.L. 2026/012, 1/3/2026, eff. 1/1/2028.
In special flood hazard areas, tank inlets, fill openings, outlets and vents shall be:
1. Installed at or above the design flood elevation specified in ASCE 24, Table 7-1, or designed to prevent the inflow of floodwater and outflow of the contents of the tanks during conditions of flooding to the design flood elevation, in accordance with ASCE 24; and
2. Anchored to prevent lateral movement resulting from hydrodynamic and hydrostatic loads, including the effects of buoyancy, during conditions of flooding to the design flood elevation, in accordance with ASCE 24.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2026/012.
G307.4 Additional fuel-oil storage capacity.
Fuel-oil storage capacity in special flood hazard areas and shaded X-Zones shall comply with the following:
1. In special flood hazard areas, fuel oil on the lowest story having its floor above the applicable design flood elevation shall be limited to 3,000 gallons (11 356 L) and no storage tank may exceed the lesser of 1,500 gallons (5678 L) or the quantity of fuel-oil needed to operate the emergency or standby generator(s) served by such tank for 24 hours and
2. In shaded X-Zones, fuel oil on the lowest story having its floor above the 500-year flood elevation shall be limited to 3,000 gallons (11 356 L) and no storage tank may exceed the lesser of 1,500 gallons (5678 L) or the quantity of fuel-oil needed to operate the emergency or standby generator(s) served by such tank for 24 hours.
G307.4.1 Additional requirements.
Where fuel-oil storage capacity exceeds the quantity set forth in Section 1305.11.1.3 of the New York City Mechanical Code, the fuel-oil storage shall comply with Sections G307.4.1.1 and G307.4.1.2 in addition to Section 1305 of the New York City Mechanical Code.
G307.4.1.1 Vault.
Each fuel-oil storage tank shall be separately enclosed in a vault complying with all of the following requirements:
1. The walls, floor, and top of such vault shall have a fire-resistance rating of not less than 3 hours;
2. The walls of such vault shall be bonded to the floor of such vault;
3. The top and walls of such vault shall be independent of the building structure;
4. An exterior building wall having a fire-resistance rating of not less than 3 hours shall be permitted to serve as a wall of such vault; and
5. The vault shall be located in a dedicated room or area of the building that is separated vertically and horizontally from other areas of the building by construction having a fire-resistance rating of not less than 2 hours.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
G307.4.1.2 Extinguishing system.
Fuel-oil storage shall be protected with an alternative automatic fire-extinguishing system complying with Section 904.
G307.5 Elevation of certain tanks and containers serving flood design class 4 buildings.
The following tanks and containers shall be located at or above the design flood elevation specified in ASCE 24, Table 7-1, when serving flood design class 4 buildings. Such tanks and containers must be designed to maintain service to such structure during flood conditions and shall comply with Section 9.7 of ASCE 24:
1. Medical and compressed gas storage tanks, oxygen tanks, and other cryogenic system storage tanks;
2. Hazardous material storage tanks;
3. Stationary compressed gas containers;
4. Stationary cryogenic containers and
5. Stationary flammable gas storage containers.
Section BC G308. Other Building Work
G308.1 Garages and accessory structures.
Garages and accessory structures shall be designed and constructed in accordance with ASCE 24, Section 9.4.
G308.2 Fences.
Fences in floodways that may block the passage of floodwaters, such as stockade fences and wire mesh fences, shall meet the requirement of Section G103.5.
G308.3 Oil derricks.
Oil derricks located in special flood hazard areas shall be designed in conformance with ASCE 24.
G308.4 Retaining walls, sidewalks and driveways.
Retaining walls, sidewalks and driveways shall meet the requirements of Sections G303.6 and G303.7.
G308.5 Swimming pools.
Swimming pools shall be designed and constructed in accordance with ASCE 24. Above-ground swimming pools, on-ground swimming pools and in-ground swimming pools that involve placement of fill in floodways shall also meet the requirements of Section G103.5.
G308.6 Decks, porches, and patios.
Decks, porches and patios shall be designed and constructed in accordance with ASCE 24.
G308.7 Nonstructural concrete slabs in coastal high-hazard areas and coastal A-Zones.
In coastal high-hazard areas and coastal A-Zones, nonstructural concrete slabs used as parking pads, enclosure floors, landings, decks, walkways, patios and similar nonstructural uses are permitted beneath or adjacent to buildings and structures provided that the concrete slabs shall be constructed in accordance with ASCE 24, Section 9.3.
G308.8 Roads and watercourse crossings in regulated floodways.
Roads and watercourse crossings that encroach into regulated floodways, including roads, bridges, culverts, low-water crossings and similar means for vehicles or pedestrians to travel from one side of a watercourse to the other, shall meet the requirement of Section G103.5.
G308.9 Temporary flood shields.
Temporary flood shields shall be permitted in accordance with Section 6.2.3 of ASCE 24. Temporary flood shields shall be located and arranged so as to allow hose lines to be attached to the inlets of fire department connections without interference in accordance with Section 6.4.5 of NFPA 14 as modified by Appendix Q. Where temporary flood shields extend beyond the property line, Section 3202 for permitted encroachments into the public right-of-way shall apply.
G308.10 Temporary stairs and ramps.
Temporary stairs and ramps shall comply with the requirements of Sections G308.10.1 and G308.10.2. Temporary stairs and ramps shall be located and arranged so as to allow hose lines to be attached to the inlets of fire department connections without interference in accordance with Section 6.4.5 of NFPA 14, as modified by Appendix Q. Where temporary stairs and ramps extend beyond the property line, Section 3202 for permitted encroachments into the public right-of-way shall apply.
G308.10.1 Evacuated buildings.
Temporary stairs and ramps shall be permitted to provide elevated ingress and egress in compliance with Item 3 of Section 6.2.2 of ASCE 24 for buildings or portions of buildings that are planned to be evacuated during design flood conditions, except for maintenance and emergency personnel, provided that such temporary stairs and ramps shall not be permitted to serve as a required means of egress for a dwelling unit or for any area described in Item 2.2.1 of Section G304.1.2 required to be located at or above the design flood elevation.
G308.10.2 Existing buildings.
Temporary stairs and ramps for an existing building or portions thereof shall be permitted to provide elevated ingress and egress in compliance with Item 3 of Section 6.2.2 of ASCE 24, including as a required means of egress for dwelling units or for areas described in Item 2.2.1 of Section G304.1.2 required to be located at or above the design flood elevation, where such temporary stairs and ramps comply with Sections 1009 and 1010.
G308.11 Alterations to pre-FIRM buildings involving flood protective works.
Where alterations to pre-FIRM buildings within the flood hazard area, other than substantial improvements or horizontal enlargements, include the installation of flood protective works, compliance with ASCE 24, Section 6.2.2 shall be required. Flood protective works shall be located and arranged so as to allow hose lines to be attached to the inlets of fire department connections without interference in accordance with Section 6.4.5 of NFPA 14, as modified by Appendix Q of this code.
Section BC G309. Temporary Structures and Temporary Storage
G309.1 Temporary structures.
Temporary structures shall be erected for a period of less than 180 days. Temporary structures shall be anchored to prevent flotation, collapse or lateral movement resulting from hydrostatic loads, including the effects of buoyancy, during conditions of the base flood. Fully enclosed temporary structures shall have flood openings that are in accordance with ASCE 24 to allow for the automatic entry and exit of floodwaters.
G309.2 Temporary storage.
Temporary storage includes storage of goods and materials for a period of fewer than 180 days. Stored materials shall not include hazardous materials.
G309.3 Floodway encroachment.
Temporary structures and temporary storage in floodways shall meet the requirements of Section G103.5.
Section BC G310. Utility and Miscellaneous Group U
G310.1 Utility and miscellaneous Group U.
Section G310 shall govern utility and miscellaneous Group U, including buildings that are accessory in character and miscellaneous structures not classified in any specific occupancy in this code, including, but not limited to, agricultural buildings, aircraft hangars (accessory to a one- or two-family residence), barns, carports, fences more than 6 feet (1829 mm) high, grain silos (accessory to a residential occupancy), greenhouses, livestock shelters, private garages, retaining walls, sheds, stables and towers.
G310.2 Flood loads.
Utility and miscellaneous Group U buildings and structures, including substantial improvement of such buildings and structures, shall be anchored to prevent flotation, collapse or lateral movement resulting from flood loads, including the effects of buoyancy, during conditions of the design flood.
G310.3 Elevation.
Utility and miscellaneous Group U buildings and structures, including substantial improvement of such buildings and structures, shall be elevated such that the lowest floor, including basement, is elevated to or above the design flood elevation specified in ASCE 24, unless otherwise permitted to comply with requirements of Section 9.4 of ASCE 24.
G310.4 Enclosures below design flood elevation.
Fully enclosed areas below the design flood elevation shall be constructed in accordance with Section G304.
G310.5 Flood-damage-resistant materials.
Flood-damage-resistant materials shall be used below the design flood elevation.
G310.6 Protection of mechanical, plumbing and electrical systems.
Mechanical, plumbing and electrical systems, including plumbing fixtures, shall be elevated to or above the design flood elevation.
Exception: Electrical systems, equipment and components; heating, ventilating, air conditioning and plumbing appliances; plumbing fixtures, duct systems and other service equipment shall be permitted to be located below the design flood elevation provided that they are designed and installed in compliance with Section G304.1.2, Item 2.3 and other applicable flood-resistant construction requirements of this code.
Electrical wiring systems shall be permitted to be located below the design flood elevation provided they conform to the provisions of the New York City Electrical Code and Section 7.2 of ASCE 24.
Section BC G311. Hazardous Substances
G311.1 Hazardous substances.
Portable containers located in the flood hazard area that store hazardous substances, as defined in Section 41-03 of Title 15 of the Rules of the City of New York, shall comply with Section 41-14 of Title 15 of the Rules of the City of New York.
Section BC G312. Retroactive Requirements
G312.1 General.
Notwithstanding any other provision of the New York City Construction Codes, the provisions of this section shall apply retroactively to all buildings and structures specified herein.
G312.2 Connections for temporary external generators.
The following buildings shall be provided with connections for temporary external generators in accordance with Sections G304.5.1 through G304.5.4, as applicable, by January 1, 2033, and a report detailing compliance with such requirements shall be filed with the department in accordance with Section G312.2.2 by such date:
1. Buildings whose main use or dominant occupancy is Group I-1 and that are located in a special flood hazard area;
2. Buildings whose main use or dominant occupancy is an adult home, enriched housing, community residence or intermediate care facility that is classified as occupancy Group R pursuant to an exception to Section 308.3.1 or 308.3.2 and that are located in a special flood hazard area;
3. Buildings whose main use or dominant occupancy is Group I-2 hospital and that are located in a special flood hazard area or shaded X-Zone;
4. Buildings whose main use or dominant occupancy is Group I-2 nursing home and that are located in a special flood hazard area; and
5. Buildings whose main use or dominant occupancy is Group I-2, other than hospitals and nursing homes, and that are located in a special flood hazard area.
G312.2.1 Modification to the flood hazard area.
Where the special flood hazard area or shaded X-Zone is modified on or after the effective date of this section, any building identified in Section G312.2 and newly identified as being within such modified special flood hazard area or shaded X-Zone shall, no later than 20 years following the adoption of such modification, comply with the retroactive requirements of Section G312.2. The owner of such building shall, no later than 20 years following the adoption of such modification, file with the department a report detailing compliance with such requirements in accordance with Section G312.2.2.
G312.2.2 Report of compliance.
The owner of a building required to comply with the provisions of Section G312.2 shall file with the department, by January 1, 2033, a report prepared by a registered design professional or licensed master electrician (i) certifying that the requirements of Section G312.2 have been satisfied and detailing how such requirements were satisfied or (ii) certifying that the building met or was altered to meet the provisions of any applicable exception in Sections G304.5.1 or G304.5.2.
G312.2.3 Filing.
The department may promulgate rules establishing filing fees for the review and examination of such reports.
G312.3 Connections for temporary external boilers and chillers.
Buildings whose main use or dominant occupancy is Group I-2 hospital and that are located in a flood hazard area shall be provided with connections for temporary external boilers and chillers in accordance with Section G304.5.2 by January 1, 2033, and a report detailing compliance with such requirements shall be filed with the department in accordance with Section G312.3.2 by such date.
G312.3.1 Modification to the flood hazard area.
Where the special flood hazard area or shaded X-Zone is modified on or after the effective date of this section, any building whose main use or dominant occupancy is Group I-2 hospital and that is newly identified as being within such modified special flood hazard area or shaded X-Zone shall comply with the retroactive requirements of Section G312.3 no later than 20 years following the adoption of such modification. The owner of such building shall file with the department a report detailing compliance with such requirements in accordance with Section 312.3.2 no later than 20 years following the adoption of such modification.
G312.3.2 Report of compliance.
The owner of a building required to comply with the provisions of Section G312.3 shall file with the department, by January 1, 2033, a report prepared by a registered design professional (i) certifying that the requirements of Section G312.3 have been satisfied and detailing how such requirements were satisfied or (ii) certifying that any boiler and chiller plants that serve the spaces specified in Item 2 of Section G304.5.2 are located at or above the design flood elevation specified in Table 7-1 of ASCE 24.
G312.3.3 Filing.
The department may promulgate rules establishing filing fees for the review and examination of such reports.
Section BC G401. Referenced Standards
G401.1 General.
This section lists the standards that are referenced in various sections of this appendix. The standards are listed herein by the promulgating agency of the standard, the standard identification, the effective date and title and the section or sections of this document that reference the standard.
G401.2 Subsequent additions, modifications, or deletions.
Refer to the rules of the department for any subsequent additions, modifications or deletions t may have been made to these standards in accordance with Section 28-103.19 of the Administrative Code.
G401.3 Applicability.
The application of the referenced standards shall be as specified in Section G105.1.
Section BC G402. Standards
ASCE 7-16 Minimum Design Loads and Associated Criteria for Buildings and Other Structures G104.2.3.2, G304.2 ASCE 24-14* * As modified in Section G501. Flood Resistant Design and Construction G101.3, G102.1, G103.1, G104.2.1, G104.2.3.1, G104.2.3.2, G107.2, G107.3, G107.4, G301.1, G303.3, G303.4, G303.5, G303.8, G304.1, G304.1.1, G304.1.2, G304.2, G304.3, G304.4, G304.4.1.1, G304.5.1, G305.1, G305.2, G305.4, G307.1, G307.2, G307.3, G307.5, G308.1, G308.3, G308.5, G308.6, G308.7, G308.9, G308.10.1, G308.10.2, G308.11, G309.1, G310.3, G310.6, G312.3.2 FEMA FIS 360497 Flood Insurance Study, Community Number 360497, Revised September 5, 2007; Federal Emergency Management Agency G102.2, G102.2.1, G102.2.2, G102.3.1.1, G103.3.2 FEMA PFIS 360497 Preliminary Flood Insurance Study, Issued December 5, 2013, Community Number 360497, Federal Emergency Management Agency G102.2.1, G102.2.2, G102.3.1.1, G102.3.2.1 FEMA FIRMs 360497 Flood Insurance Rate Map, Community Number 360497, Panel Numbers 1 through 0457, Revised September 5, 2007; Federal Emergency Management Agency, with the following Letters of Map Revision: Letter of Map Revision effective September 29, 2008, FEMA case # 08-02-0948P, revising FIRM panel 0111 and Letter of Map Revision effective April 18, 2018, FEMA case # 17-02-1503P, revising FIRM panels 0092F, 0094F, 0111F, and 0113F. G102.2, G102.2.2, G102.3, G102.3.1, G102.3.2, G103.3.1, G103.3.2 FEMA PFIRMs 360497 Preliminary Flood Insurance Rate Map, Community Number 360497, Issued December 5, 2013; Revised January 30, 2015, as applicable; Federal Emergency Management Agency G102.2.1, G102.2.2, G102.3.1.1, G102.3.2.1 FEMA FORM 086-0-34 Floodproofing Certificate; Federal Emergency Management Agency G107.3 FEMA FORM 086-0-33 Elevation Certificate; Federal Emergency Management Agency G107.3 HUD 24 CFR Part 3280-08 Manufactured Home Construction and Safety Standards, 2008 G201.1.2 NFPA 14-16* * As modified in Appendix Q. Standard for the Installation of Standpipe and Hose Systems G304.1.2, G308.9, G308.10, G308.11
Section BC G501. Modifications to Referenced Standards
G501.1 Amendments to ASCE 24-14.
The following amendments are hereby made to the applicable sections of ASCE 24-14. Refer to the rules of the department for any subsequent additions, modifications or deletions that may have been made to this standard in accordance with Section 28-103.19 of the Administrative Code.
Section 1.1. Section 1.1 (Scope) is amended by deleting the sentence "In addition to the requirements of this section (see Fig. 1-2):" and Items 1 through 4, and by adding the following paragraph to read as follows:
In addition to the requirements of this section, the applicability of this standard is as provided for in Section G102.1 of the New York City Building Code, Appendix G.
Section 1.1. Figure 1-2 (Application of Chapters) of Section 1.2. Delete.
Section 1.1.1. A new Section 1.1.1 is added to read as follows:
1.1.1 High-risk flood hazard areas. Notwithstanding any other provision in this standard, no special flood hazard area in New York City shall be classified as alluvial fan area, flash flood area, mudslide area, ice jam and debris area, erosion-prone area, high-velocity flow area.
Section 1.2. Section 1.2 (Definitions) is amended by modifying only the following definitions to read as follows:
Breakaway wall – As defined in Section G201 of the New York City Building Code, Appendix G.
Design flood elevation – The applicable elevation specified in Table 2-1, 4-1, 5-1, 6-1, or 7-1, depending on the flood design classification designated in Table 1-1.
High-risk flood hazard area – An area designated as a coastal high-hazard area, being those areas identified on the FIRM as a V-Zone or Coastal A-Zone.
Nonresidential – Defined as Nonresidential (for flood zone purposes) in Section G201 of the New York City Building Code, Appendix G.
Residential – Defined as Residential (for flood zone purposes) in Section G201 of the New York City Building Code, Appendix G.
Section 1.4.3. Table 1-1 of Section 1.4.3 (Classification of Structures) is amended to read as follows:
Table 1-1 Flood Design Class of Buildings and Structures
Use of Occupancy of Buildings and Structures Flood Design Class Buildings and structures that normally are unoccupied and pose minimal risk to the public or minimal disruption to the community should they be damaged or fail due to flooding. Flood Design Class 1 includes: 1. certain temporary structures that are in place for less than 180 days, 2. accessory storage buildings and minor storage facilities, 3. small structures used for parking of vehicles, and 4. certain agricultural structures. a 1 Buildings and structures that pose a moderate risk to the public or moderate disruption to the community should they be damaged or fail due to flooding, except those listed as Flood Design Classes 1, 3, and 4. Flood Design Class 2 includes the vast majority of buildings and structures that are not specifically assigned another Flood Design Class, including most residential, commercial, and industrial buildings. 2 Buildings and structures that pose a high risk to the public or significant disruption to the community should they be damaged, be unable to perform their intended functions after flooding, or fail due to flooding. Flood Design Class 3 includes: 1. buildings and structures in which 300 or more persons may assemble in one place, such as theaters, lecture halls, and religious institutions with large areas used for worship; 2. museums; 3. community centers and other recreational facilities; 4. athletic facilities with seating for spectators; 5. elementary schools, secondary schools, and buildings with college or adult education classrooms; 6. jails, correctional facilities, and detention facilities; 7. healthcare facilities not having surgery or emergency treatment capabilities; 8. care facilities where residents have limited mobility or ability, including nursing homes but not including care facilities for five or fewer persons; 9. preschool and child care facilities not located in one- and two-family dwellings; 10. buildings and structures associated with power generating stations, water and sewage treatment plants, telecommunication facilities, and other utilities which, if their operations were interrupted by a flood, would cause significant disruption in day-to-day life or significant economic losses in a community; and 11. buildings and other structures not included in Flood Design Class 4 (including but not limited to facilities that manufacture, process, handle, store, use, or dispose of such substances as hazardous fuels, hazardous chemicals, hazardous waste, or explosives) containing toxic or explosive substances where the quantity of the material exceeds a threshold quantity established by the authority having jurisdiction and is sufficient to pose a threat to the public if released. b 3 Buildings and structures that contain essential facilities and services necessary for emergency response and recovery, or that pose a substantial risk to the community at large in the event of failure, disruption of function, or damage by flooding. Flood Design Class 4 includes: 1. group I-2 occupancies having surgery or emergency treatment facilities; 2. fire, rescue, ambulance, and police stations and emergency vehicle garages; 3. designated emergency shelters; 4. designated emergency preparedness, communication, and operation centers and other facilities required for emergency response; 5. power generating stations and other public utility facilities required in emergencies; 6. structures containing highly toxic materials as defined by Section 307 where the quantity of the material exceeds the maximum allowable quantities of Table 307.1(2); 7. critical aviation facilities such as control towers, air traffic control centers, and hangars for aircraft used in emergency response; 8. ancillary structures such as communication towers, electrical substations, fuel or water storage tanks, or other structures necessary to allow continued functioning of a Flood Design Class 4 facility during and after an emergency; 9. buildings and other structures having critical national defense functions; and 10. water storage facilities and pump structures required to maintain water pressure for fire suppression. 4
a. Certain agricultural structures may be exempt from some of the provisions of this standard; see Section C1.4.3.
b. Buildings and other structures containing toxic, highly toxic, or explosive substances shall be eligible for assignment to a lower Flood Design Class if it can be demonstrated to the satisfaction of the authority having jurisdiction by a hazard assessment as described in Section 1.5.3 of Minimum Design Loads for Buildings and Other Structures that a release of the substances is commensurate with the risk associated with that Flood Design Class.
Section 2.3. Table 2-1 of Section 2.3 (Elevation Requirements) is amended to read as follows:
Table 2-1 Minimum Elevation of the Top of Lowest Floor Flood Hazard Areas Other than Coastal High-Hazard Areas a , Coastal A-Zones a
Flood Design Class b Minimum Elevation of Lowest Floor, Relative to Base Flood Elevation (BFE) or Design Flood Elevation (DFE) 1 c DFE = BFE + 2 ft 2 d DFE = BFE + 2 ft 3 d DFE = BFE + 2 ft 4 d DFE = BFE + 2 ft, or 500-year flood elevation, whichever is higher
a. Minimum elevations shown in Table 2-1 do not apply to Coastal High-Hazard Areas and Coastal A-Zones (see Table 4-1). Minimum elevations shown in Table 2-1 apply to other high risk flood hazard areas unless specific elevation requirements are given in Section 3 of this standard.
b. See Table 1-1 for Flood Design Class descriptions.
c. Flood Design Class 1 structures shall be allowed below the minimum elevation where the structure is permitted to be wet floodproofed in accordance with the requirements of Section 6.3.1 and is wet floodproofed in accordance with Section 6.3.2.
d. For nonresidential buildings and nonresidential portions of mixed-use buildings, the lowest floor shall be allowed below the minimum elevation if the structure meets the floodproofing requirements of Section 6.2.
Section 4.4. Table 4-1 of Section 4.4 (Elevation Requirements) is amended to read as follows:
Table 4-1 Minimum Elevation of Bottom of Lowest Supporting Horizontal Structural Member of Lowest Floor – Coastal High-Hazard Areas and Coastal A-Zones
Flood Design Class a Minimum Elevation, Relative to Base Flood Elevation (BFE) or Design Flood Elevation (DFE) 1 DFE = BFE + 2 ft 2 DFE = BFE + 2 ft 3 DFE = BFE + 2 ft 4 DFE = BFE + 2 ft, or 500-year flood elevation, whichever is higher
a See Table 1-1 for Flood Design Class descriptions.
Section 4.6.1. Section 4.6.1 (Breakaway Walls) is amended by adding the following sentence: All breakaway walls enclosing spaces below the DFE in coastal high-hazard area shall be open lattice, and not solid, with such enclosed spaces constructed as unconditioned per the New York State Energy Conservation Construction Code.
Section 5.1. Table 5-1 of Section 5.1 (Materials, General) is amended to read as follows:
Table 5-1 Minimum Elevation Below which Flood-Damage-Resistant Materials Shall Be Used
Flood Design Class a Minimum Elevation in Flood Hazard Areas, Other than Coastal High-hazard Areas and Coastal A-zones, Relative to Design Flood Elevation (DFE) Minimum Elevation in Coastal High-hazard Areas and Coastal A-zones, Relative to Design Flood Elevation (DFE) 1 DFE = BFE + 2 ft DFE = BFE + 2 ft 2 DFE = BFE + 2 ft DFE = BFE + 2 ft 3 DFE = BFE + 2 ft DFE = BFE + 3 ft 4 DFE = BFE + 2 ft, or 500-year flood elevation, whichever is higher DFE = BFE + 3 ft, or 500-year flood elevation, whichever is higher
a See Table 1-1 for Flood Design Class descriptions.
Section 5.2.6. Section 5.2.6 (Finishes) shall be amended to read as follows:
5.2.6 Finishes and other materials. Interior and exterior finishes, as well as any materials not otherwise provided for in Sections 5.2.1 through 5.2.5, shall be flood damage-resistant materials in accordance with FEMA Technical Bulletin 2/August 2008, Flood Damage-Resistant Materials Requirement for Buildings Located in Special Flood Hazard Areas, or shall be required to be approved by the authority having jurisdiction.
Section 6.2. Table 6-1 of Section 6.2 (Dry Floodproofing) is amended to read as follows:
Table 6-1 Minimum Elevation of Floodproofing – Flood Hazard Areas Other Than Coastal High-Hazard Areas a
Flood Design Class b Minimum Elevation of Floodproofing c Relative to Design Flood Elevation (DFE) 1 DFE = BFE + 2 ft 2 d DFE = BFE + 2 ft 3 DFE = BFE + 2 ft 4 DFE = BFE + 2 ft, or 500-year flood elevation, whichever is higher
a. Dry floodproofing is not allowed in Coastal High-Hazard Areas.
b. See Table 1-1 for Flood Design Class descriptions.
c. Wet or dry floodproofing shall extend to the same level.
d. Dry floodproofing shall not be permitted (i) in buildings that are "residential for flood zone purposes"; (ii) for certain systems and equipment as provided for in Section G304.1.2, Item 2.3.1 of the New York City Building Code; and (iii) for dwelling units and spaces directly accessed from dwelling units in buildings that are "nonresidential for flood zone purposes".
Section 6.2.1. (Dry Floodproofing Limitations) is amended to add the following exceptions:
Exceptions:
1. Upon special application to the commissioner, the department may authorize dry floodproofing for designs that demonstrate resistance to flood velocities exceeding 5 ft/s while meeting the other limitations of this standard.
2. Dry floodproofing shall be permitted in Coastal A-Zones, provided:
2.1 such dry floodproofing complies with the requirements of Appendix G of the New York City Building Code; and
2.2 where flood velocities adjacent to the structure exceed 5 ft/s, the commissioner has authorized the dry floodproofing in accordance with Exception 1.
Section 6.2.2. Item 1 of Section 6.2.2 (Dry Floodproofing Requirements) is amended to read as follows:
1. Be designed and constructed so that any area below the applicable elevation specified in Table 6-1, together with attendant utilities, equipment, and sanitary facilities, is flood resistant with walls that are substantially impermeable to the passage of water. Where acceptable to the commissioner, fixed flood-resistant glazing systems may be used when tested and designed to be within walls substantially impermeable to water. Walls, floors, and flood shields shall be designed and constructed to resist hydrostatic, hydrodynamic, and other flood-related loads, including the effects of buoyancy resulting from flooding to the elevation listed in Table 6-1;
Section 6.2.2. Item 3 of Section 6.2.2 (Dry Floodproofing Requirements) is amended to read as follows:
3. Provide egress and ingress, where a means of egress is required by Chapter 10 of the New York City Building Code, to such dry floodproofed areas of structures in accordance with Item 3.1, 3.2 or 3.3, or a combination thereof, where permitted, as follows:
3.1 Egress and ingress not blocked by shields. Means of egress shall be elevated to or above the applicable DFE specified in Table 6-1, capable of providing human ingress and egress during the design flood between the dry floodproofed area to the exterior, without being blocked by flood shields or flood control devices; or
3.2 Egress and ingress blocked by shields not serving dwelling units. Where a means of egress required by Chapter 10 of the New York City Building Code that does not serve a dwelling unit is to be blocked by flood shields or flood control devices, an alternate means of egress shall be provided capable of providing human ingress and egress during the design flood between the dry floodproofed area to the exterior. The alternate means of egress shall comprise of: (i) a door providing ingress and egress opening directly to the exterior at or above the DFE, and such door shall be permitted to be accessed by steps or ramps; or (ii) a means of egress leading to an exterior exit door not blocked by shields or which is constructed as a wet floodproofed enclosure where discharging below the DFE, and such means of egress shall be permitted to be accessed by stairs and ramps. In either case, such alternate means of egress shall also comply with Items 3.2.1 through 3.2.6:
3.2.1 Alternate Means of Egress Entrance. The alternate means of egress entrance door, or directional signage to such alternate means of egress entrance door shall be readily visible and identifiable within a direct line of sight to a person approaching the blocked egress door(s). The path of travel from the blocked egress door to the alternate means of egress entrance shall be unobstructed with a travel distance of not more than 40 ft as measured from the blocked means of egress. Directional signage to the alternate means of egress shall be installed on the exit door blocked by flood shields prior to flood condition and removed during non-flood conditions.
3.2.2 Travel Distance. The path of travel from the alternate means of egress entrance door leading to the exterior of the building shall not exceed 100 ft.
3.2.3 Temporary Stairs, Ramps and Platforms. For buildings or portions of buildings that are planned to be evacuated during the design flood condition and pre-FIRM buildings, temporary stairs and ramps shall be permitted to serve as an alternate means of egress if their only purpose is to provide supplemental egress and ingress during conditions of flooding subject to the limitations of Section G308.10 of the New York City Building Code.
3.2.3.1 Doors. Any door opening directly onto such temporary stairs or platforms shall be secured during non-flood conditions to prevent use when such temporary stairs and ramps are in storage.
3.2.3.2 Signage. Directional signage to an egress utilizing temporary stairs, ramps or platforms shall be removed to prevent accidental operation during non-flood conditions.
3.2.4 Visibility from outside. Permanent signage affixed to the outside of flood shields or flood control devices that block the egress door shall provide directions to first responders or other personnel seeking to locate the path into the space from the exterior.
3.2.5 Compliance with egress requirements. Such alternate means of egress shall meet all requirements of Chapter 10 of the New York City Building Code for a required means of egress, including, travel distances, hardware and signage. Where an alternate means of egress may be used as a means of egress at any time other than a flood event, temporary stairs and ramps shall not be permitted.
Exceptions for buildings or portions of buildings that are planned to be evacuated during the design flood conditions:
1. Such alternate means of egress shall not be required to comply with occupant load calculations of the New York City Building Code if its only purpose is to provide supplemental egress and ingress during conditions of flooding.
2. The alternate means of egress may serve more than one required exit provided that the travel distances to and within the alternate means of egress comply with Item 3.2.1 and Item 3.2.2 from each required means of egress that is blocked by flood shields or flood control devices.
3.2.6 Accessibility. The alternate means of egress shall not be required to comply with Chapter 11 of the New York City Building Code if its only purpose is to provide supplemental egress and ingress during conditions of flooding, unless the structure is intended for occupancy during the design flood.
3.3 Egress and ingress blocked by shields serving dwelling units. For each means of egress required by Chapter 10 of the New York City Building Code that serves a dwelling unit and is to be blocked by flood shields or flood control devices, at least one alternate means of egress shall be provided capable of providing human ingress and egress during the design flood between the dry floodproofed area to the exterior. The alternate means of egress shall comprise either an elevated door opening directly to the exterior of the building arranged in accordance with Section 3.3.1 or an enclosure that incorporates wet floodproofing and is arranged in accordance with Section 3.3.2.
3.3.1 Elevated door. Where an elevated door is provided, such door shall be capable of providing human ingress and egress during the design flood. The elevated door shall open directly to the exterior of the building and shall be located in close proximity to the required means of egress to the exterior that is to be blocked by flood shields or flood control devices as follows:
3.3.1.1 Face of door. The face of the elevated door itself, and not merely its directional signage, shall be arranged so it is clearly visible to a person approaching the blocked egress door(s).
3.3.1.2 Elevation of door. Such door(s) shall be elevated to or above the applicable DFE specified in Table 6-1.
3.3.1.3 Compliance with egress requirements. Such door shall meet all New York City Building Code requirements for a required means of egress to the exterior of the structure including hardware and signage.
3.3.1.4 Accessibility. Such door may be accessed by open steps and shall not be required to comply with Chapter 11 of the New York City Building Code if its only purpose is to provide supplemental egress and ingress during conditions of flooding and to provide emergency egress at other times.
3.3.2 Enclosure that incorporates wet floodproofing. Where an enclosure which is partially wet floodproofed is used to provide alternate means of egress, such means of egress shall be capable of providing human ingress and egress during the design flood and shall be located in close proximity to the required means of egress to the exterior that is to be blocked by flood shields or flood control devices as follows:
3.3.2.1 Face of door to enclosure. The face of the door to the enclosure, and not merely its directional signage, shall be arranged so it is clearly visible to a person approaching the blocked egress door(s).
3.3.2.2 Wet floodproofing within an enclosure. Wet floodproofed portions of the enclosure shall be designed to comply with Section 6.3 and resist all flood related loads while prohibiting infiltration of floodwater to dry floodproofed spaces within the building.
3.3.2.3 Travel Distance. The path of travel from the alternate means of egress entrance door to the door leading to the exterior of the building shall not exceed 25 ft.
3.3.2.4 Compliance with egress requirements. The entrance and exit door shall meet all requirements of Chapter 10 of the New York City Building Code for a required means of egress to the exterior of the structure including hardware and signage.
Section 6.2.3. Section 6.2.3 (Limits on Human Intervention) is amended to read as follows:
Section 6.2.3 Limits on Human Intervention. Dry floodproofing measures that require human intervention to activate or implement prior to or during a flood, including temporary stairs or ramps, shall be permitted only when all of the following conditions are satisfied:
1. The flood warning time (alerting potential flood victims of a pending flood situation) shall be a minimum of 12 h unless the community operates a flood warning system and implements an emergency plan to ensure safe evacuation of flood hazard areas, in which case human intervention is allowed only if the community can provide a minimum flood warning time equal to or longer than the cumulative time:
(a) to notify persons responsible for installation of floodproofing measures,
(b) for responsible persons to travel to structure to be floodproofed,
(c) to install, activate, or implement floodproofing measures, and
(d) to evacuate all occupants from the flood hazard area.
2. All removable shields or covers for openings such as windows, doors, and other openings in walls and temporary stairs or ramps shall be designed to resist flood loads specified in Section 1.6.
3. Where removable shields or temporary stairs or ramps are to be used, a flood emergency plan shall be approved by the authority having jurisdiction and shall specify, at a minimum, the following information: storage locations of the shields and temporary stairs and ramps; the method of installation and removal; conditions activating installation and removal; maintenance of shields and attachment devices and temporary stairs and ramps; periodic practice of installing and removing shields and temporary stairs and ramps; testing sump pumps and other drainage measures; and inspecting necessary material and equipment to activate or implement floodproofing. The flood emergency plan shall be posted permanently in at least two conspicuous locations within the structure.
4. Where removable shields or temporary stairs or ramps are to be used, they shall be stored on site within a building or within a secured, weather-resistant enclosure. Off-site storage shall be prohibited for buildings required to comply with Section G304.
5. Where removable shields or temporary stairs or ramps are proposed as per Section G304, periodic inspections, including a triennial full scale deployment, shall be conducted in accordance with Article 324 of the Administrative Code.*
* Editor's note: As set forth in L.L. 2021/126; correct cite is Article 324 of Chapter 3 of Title 28 of the Administrative Code.
Section 7.1. Table 7-1 of Section 7.1 (General) is amended to read as follows:
Table 7-1 Minimum Elevation of Attendant Utilities and Equipment
Flood Design Class a Locate Attendant Utilities and Equipment Above b Minimum Elevation in Flood Hazard Areas, Other than Coastal High-Hazard Areas and Coastal A-Zones, Relative to Design Flood Elevation (DFE) Minimum Elevation in Coastal High-Hazard Areas and Coastal A-Zones, Relative to Design Flood Elevation (DFE) 1 DFE = BFE + 2 ft DFE = BFE + 2 ft 2 DFE = BFE + 2 ft DFE = BFE + 2 ft 3 DFE = BFE + 2 ft DFE = BFE + 3 ft 4 DFE = BFE + 2 ft, or 500-year flood elevation, whichever is higher DFE = BFE + 3 ft, or 500-year flood elevation, whichever is higher
a. See Table 1-1 for Flood Design Class descriptions.
b. Locate attendant utilities and equipment above elevations shown unless otherwise provided in Chapter 7 of ASCE 24.
Section 7.2.4. Section 7.2.4 (Panelboards, Disconnect Switches, and Circuit Breakers) is amended to read as follows:
7.2.4 Panelboards, Disconnect Switches, and Circuit Breakers. The panelboards, load centers, main disconnect switches, all service disconnecting means, and all circuit breakers shall be located above and be accessible from the elevation specified in Table 7-1, or within a dry floodproofed enclosure, except where prohibited by the New York City Building Code. Panelboards, load centers, main disconnect switches, all service disconnecting means, and circuit breakers shall be located no more than 6 feet 7 inches (2 m) above the floor, or a platform shall be installed to provide access.
Section 7.3.3. Section 7.3.3 is amended to read as follows:
7.3.3 Plumbing Systems Installed Below Minimum Elevations. Plumbing systems and components, including plumbing fixtures, shall be elevated above the elevation specified in Table 7-1. Where plumbing systems and components have openings below the elevation specified in Table 7-1, the openings shall be protected with automatic backwater valves or other automatic backflow devices. Devices shall be installed in each line that extends below the DFE to prevent release of sewage into floodwaters and to prevent infiltration by floodwaters into the plumbing. Redundant devices requiring human intervention shall be permitted. Plumbing systems shall be provided with backwater valves in the building drain at its point of exit from the building and downstream of the building trap.
Section 7.3.4. Section 7.3.4 is amended to read as follows:
7.3.4 Sanitary Systems. Sanitary systems shall be designed to minimize infiltration of flood waters into the systems and discharges from the systems into floodwaters. Vents and openings shall be above the elevation specified in Table 7-1. Sanitary system storage tanks shall be designed, constructed, installed, and anchored to resist at least 1.5 times the potential buoyant and other flood forces acting on an empty tank during design flood conditions. Tanks and piping shall be installed to resist local scour and erosion. Sanitary systems shall be provided with backwater valves at the point of exit from the building and downstream of the building trap. Sanitary systems that must remain operational during or immediately after the design flood or lesser floods shall be equipped with a sealed storage tank that is sized to store at least 150% of the anticipated sewage flow associated with occupancy during flood conditions and during subsequent periods of saturated soil when sewage will not percolate.
Section 7.5.2. A new section 7.5.2 is added to read as follows:
7.5.2 Elevator signage. Where there is potential for an elevator cab to descend below the elevation specified in Table 7-1 into a wet floodproofed space, the elevator shall be equipped with controls that will prevent the cab from descending into floodwaters. Permanent, durable, and washable signage shall be placed in the elevator cab and in the elevator lobby on any story subject to flooding, stating that "In the event of flooding, water sensors in the elevator shaft will prevent the elevator from descending to (description of story, e.g., ground floor, first floor, parking level, etc.) and will automatically cause the elevator to rise to (description of story, e.g., second floor, mezzanine, etc.)."
Section 8.1. Section 8.1 (General) is amended to read as follows:
8.1 General. Stairways and ramps, including stairs and ramps pursuant to Section G308.10 of the New York City Building Code, that are located below the elevations specified in Tables 2-1 and 4-1 shall be designed and constructed to:
1. Resist flood-related loads specified in Section 1.6 and minimize transfer of flood-related loads to the structure and structure foundation; or
2. Break away during design flood conditions without causing damage to the structure, including the foundation; or
3. Use materials that conform to Chapter 5 for those portions of stairways and ramps that are located below the elevations specified in Tables 2-1 and 4-1, including items such as gates and doors.
In flood hazard areas other than Coastal High-Hazard Areas and Coastal A-Zones, enclosures for stairways and ramps that extend below the elevations specified in Table 2-1 shall conform to the requirements for enclosures in Section 2.7. In Coastal High-Hazard Areas and Coastal A-Zones, enclosures for stairways and ramps that extend below the elevations specified in Table 4-1 shall conform to the requirements for enclosures in Section 4.6.
Elevators shall conform to the requirements of Section 7.5.
Section 9.4.1. The second sentence of the first paragraph of Section 9.4.1 (Attached Garages, Carports, and Accessory Storage Structures) is amended to read as follows:
Wet floodproofed garages and carports are permitted below elevations specified in Table 2-1 provided the lowest level of the garage, carport or accessory storage structure is at or above grade on at least one side, the garage, carport or accessory storage structure walls meet the opening requirements of Section 2.7, and the lowest level of the garage, carport or accessory storage structure is not classified as a "lowest floor" pursuant to Appendix G of the New York City Building Code.
Section 9.7. The first sentence of Section 9.7 (Tanks) is amended to read as follows:
Tanks and tank inlets, fill openings, outlets, and vents shall terminate in accordance with Section G307.3 of the New York City Building Code or where located below the design flood elevation, shall be designed, constructed, installed, and anchored to resist all flood-related and other loads, including the effects of buoyancy, during flooding up to and including the design flood and without release of contents into floodwaters or infiltration of floodwaters into the tanks.
(Am. L.L. 2021/043, 4/18/2021, eff. 4/18/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/043.
Section BC G601. Reserved
BetaNYC's copy has no text for this section. Read Section BC G601 at American Legal Publishing.
Section BC G701. Reserved
BetaNYC's copy has no text for this section. Read Section BC G701 at American Legal Publishing.
Section BC G801. Reserved
BetaNYC's copy has no text for this section. Read Section BC G801 at American Legal Publishing.
Section BC G901. Reserved
BetaNYC's copy has no text for this section. Read Section BC G901 at American Legal Publishing.
Section BC G1001. Reserved
BetaNYC's copy has no text for this section. Read Section BC G1001 at American Legal Publishing.
Section BC G1101. Reserved
BetaNYC's copy has no text for this section. Read Section BC G1101 at American Legal Publishing.
Section BC H101. General
H101.1 General.
An outdoor sign shall not be erected in a manner that would confuse or obstruct the view of or interfere with exit signs required by Chapter 10 of this code or with official traffic signs, signals or devices. Signs and sign support structures, together with their supports, braces, guys and anchors, shall be kept in repair and in proper state of preservation. The display surfaces of signs shall be kept neatly painted or posted at all times. No sign shall project beyond the street line except as permitted by Chapter 32 of this code.
H101.2 Signs exempt from permits.
The signs specified in Section 28-105.4.5 of the Administrative Code are exempt from the requirements to obtain a permit before erection. The changing of moveable parts of an approved sign that is designed for such changes, or the repainting or repositioning of display matter shall not be deemed an alteration requiring a separate permit.
Section BC H102. Definitions
H102.1 Definitions.
The following terms are defined in Chapter 2:
COMBINATION SIGN.
DISPLAY SIGN.
ELECTRIC SIGN.
FILM SIGN.
GROUND SIGN.
MONOPOLE SIGN.
POLE SIGN.
PROJECTING SIGN.
ROOF SIGN.
SIGN.
SIGN STRUCTURE.
TEMPORARY SIGN.
WALL SIGN.
Section BC H103. Location
H103.1 Location restrictions.
Signs shall not be erected, constructed or maintained so as to obstruct any fire escape or any window or door or opening used as a means of egress or so as to prevent free passage from one part of a roof to any other part thereof. A sign shall not be attached in any form, shape or manner to a fire escape or exterior stair, nor be placed in such manner as to interfere with any opening required for natural light or natural ventilation.
H103.2 Fire Department access.
Signs erected to cover doors or windows required by Section 501.3.2 for Fire Department access to existing buildings shall be provided with access panels to such openings.
Section BC H104. Identification
H104.1 Identification.
Every outdoor advertising display sign hereafter erected, constructed or maintained, for which a permit is required, shall be marked and identified in accordance with Section 28-502.5 of the Administrative Code and as required elsewhere in this appendix.
Section BC H105. Design and Construction
H105.1 General requirements.
Signs shall be designed and constructed to comply with the provisions of this code for use of materials, loads and stresses.
H105.2 Permits, drawings and specifications.
Where a permit is required, as provided in Chapter 1, construction documents shall be required. These documents shall show the dimensions, material and required details of construction, including loads, stresses and anchors. It is the responsibility of the property owner to have every sign for which a permit is required inspected at least once every calendar year.
H105.3 Wind load.
Signs shall be designed and constructed to withstand wind pressure as provided for in Chapter 16 of this code.
H105.4 Seismic load.
Signs shall be designed to meet seismic requirements of Chapter 16 of this code.
H105.5 Working stresses.
In outdoor advertising display signs, the allowable working stresses shall conform to the requirements of Chapter 16 of this code. The working stresses of wire rope and its fastenings shall not exceed 25 percent of the ultimate strength of the rope or fasteners.
Exceptions:
1. The allowable working stresses for steel and wood shall be in accordance with the provisions of Chapters 22 and 23 of this code.
2. The working strength of chains, cables, guys or steel rods shall not exceed one-fifth of the ultimate strength of such chains, cables, guys or steel.
H105.6 Attachment.
Signs attached to masonry, concrete or steel shall be safely and securely fastened by means of metal anchors, bolts or approved expansion screws of sufficient size and anchorage to safely support the loads applied.
Section BC H106. Electrical
H106.1 Illumination.
A sign shall not be illuminated by other than electrical means, and electrical devices and wiring shall be installed in accordance with the requirements of the New York City Electrical Code. Any open spark or flame shall not be used for display purposes unless specifically approved.
H106.1.1 Internally illuminated signs.
Wiring for electric lighting shall be entirely enclosed in the sign cabinet with a clearance of not less than 2 inches (51 mm) from the facing material.
H106.2 Electrical service.
Signs that require electrical service shall comply with the New York City Electrical Code.
H106.3 Material limitations.
All sign structures for signs requiring electric service shall be constructed of noncombustible materials, except as permitted by Section H107.
H106.4 Projecting reflectors.
Lighting reflectors may project beyond the top or face of all signs provided that every part of such reflector is at least 10 feet (3048 mm) above the ground or sidewalk level. Reflectors shall be constructed, attached, and maintained so that they shall not be, or become, a hazard to the public.
Section BC H107. Material Limitations
H107.1 Use of combustibles.
In all signs required to be constructed of noncombustible materials pursuant to the provisions of Sections H109 through H116, the following materials may be used for moldings, cappings, nailing blocks, letters and latticing, or other purely ornamental features of signs, unless otherwise directed by the commissioner: wood, approved plastic or plastic veneer panels as provided for in Chapter 26 of this code, or other materials of combustible characteristics similar to wood. In all signs permitted to be constructed of combustible materials pursuant to the provisions of Sections H107 through H116, wood and other materials of combustible characteristics similar to wood shall be permitted, pursuant to the provisions of Sections H109 through H116, on the display surface without limit, except that approved plastic shall be limited in area by the provisions of Section H107.1.3.
H107.1.1 Approved plastic materials.
Plastic materials which burn at a rate no faster than 2.5 inches per minute (64 mm/s) when tested in accordance with ASTM D 635 shall be deemed approved plastics and can be used as the display surface material and for the letters, decorations and facings on signs, subject to the area limitations of Sections H107.1.2 through H107.1.3.
Exception: Flexible vinyl signs shall comply with the requirements of Section H114.
H107.1.2 Plastic area limitations for internally illuminated signs.
Except as provided for in Sections 402.14 and 2611 of this code, approved plastic used on the display surface of internally illuminated signs shall be permitted up to 200 square feet (18.6 m 2 ) in area on signs required to be of noncombustible construction and on signs permitted to be of combustible construction.
H107.1.3 Plastic area limitations for all other signs.
Approved plastic used on the display surface of ground signs, walls signs, roof signs, projecting signs, and marquee signs shall be limited in area as provided by Sections H107.1.3.1 through H107.1.3.4.
H107.1.3.1 Plastic area limitations on noncombustible ground signs and wall signs.
On ground signs and wall signs required to be constructed of noncombustible materials, if the display surface does not exceed 150 square feet (13.9 m 2 ), the entire display surface shall be permitted to be covered by approved plastic. If the area of a display surface exceeds 150 square feet (13.9 m 2 ), the area occupied or covered by approved plastics shall be limited to 150 square feet (13.9 m 2 ) plus 50 percent of the difference between 150 square feet (13.9 m 2 ) and the total area of display surface. The area of plastic on a display surface shall not in any case exceed 1,050 square feet (97.5 m 2 ), unless approved by the commissioner.
H107.1.3.2 Plastic area limitations on combustible ground signs and wall signs.
On ground signs and wall signs permitted to be constructed of combustible materials, if the display surface does not exceed 300 square feet (27.9 m 2 ), 50 percent of the display surface shall be permitted to be covered by approved plastic. If the area of a display surface exceeds 300 square feet (27.9 m 2 ), the area occupied or covered by approved plastics shall be limited to 150 square feet (13.9 m 2 ) plus 25 percent of the difference between 150 square feet (13.9 m 2 ) and the total area of display surface. The area of plastic on a display surface shall not in any case exceed 575 square feet (53.4 m 2 ), unless approved by the commissioner.
H107.1.3.3 Plastic area limitations on noncombustible roof signs, projecting signs, and marquee signs.
On roof signs, projecting signs, and marquee signs required to be constructed of noncombustible materials, if the display surface does not exceed 150 square feet (13.9 m 2 ), the entire display surface shall be permitted to be covered by approved plastic. If the area of a display surface exceeds 150 square feet (13.9 m 2 ), the area occupied or covered by approved plastics shall be limited to 150 square feet (13.9 m 2 ) plus 25 percent of the difference between 150 square feet (13.9 m 2 ) and the total area of display surface. The area of plastic on a display surface shall not in any case exceed 575 square feet (53.4 m 2 ), unless approved by the commissioner.
H107.1.3.4 Plastic area limitations on combustible roof signs.
On roof signs permitted to be constructed of combustible materials, if the display surface does not exceed 1,000 square feet (92.9 m 2 ), 25 percent of the display surface shall be permitted to be covered by approved plastic. If the area of a display surface exceeds 1,000 square feet (92.9 m 2 ), the area occupied or covered by approved plastics shall be limited to 250 square feet (23.2 m 2 ) plus 10 percent of the difference between 250 square feet (23.2 m 2 ) and the total area of display surface. The area of plastic on a display surface shall not in any case exceed 350 square feet (32.5 m 2 ), unless approved by the commissioner.
H107.2 Glass panels.
Glass panels used in display areas of signs shall be designed in accordance with Chapter 24 of this code.
Section BC H108. Animated Devices
H108.1 Fail-safe device.
Signs that contain moving sections or ornaments shall have fail-safe provisions to prevent the section or ornament from releasing and falling or shifting its center of gravity more than 15 inches (381 mm). The fail-safe device shall be in addition to the mechanism and the mechanism's housing that operate the movable section or ornament. The fail-safe device shall be capable of supporting the full dead weight of the section or ornament when the moving mechanism releases.
Section BC H109. Ground Signs
H109.1 Materials.
Ground signs erected inside the fire districts shall be constructed entirely of noncombustible materials and the facings of such signs shall be of noncombustible materials, except as permitted by Section H107. Outside the fire districts, the structure of ground signs exceeding 25 feet (7620 mm) in height above grade, or exceeding 2,500 square feet (232 m 2 ) in display area, shall be constructed of noncombustible materials, and the facing of such signs shall be noncombustible, except as permitted by Section H107.
H109.2 Required clearance.
The bottom coping of every ground sign shall be not less than 3 feet (914 mm) above the ground or street level, which space can be filled with platform decorative trim or light wooden construction.
H109.3 Wood anchors and supports.
Where wood anchors or supports are embedded in the soil, the wood shall be pressure treated with an approved preservative.
Section BC H110. Roof Signs
H110.1 Materials.
Roof signs erected inside the fire districts shall be constructed entirely of noncombustible materials and the facings of such signs shall be of noncombustible materials, except as permitted by Section H107. Outside of the fire districts, the structure of roof signs exceeding 65 feet (19 812 mm) in height above grade, or exceeding 1,500 square feet (139 m 2 ) in display area, shall be constructed of noncombustible materials and the facings of such signs shall be of noncombustible materials, except as permitted by Section H107.
H110.2 Required clearance.
Roof signs shall be constructed so as to provide a clear space of at least 7 feet (2134 mm) between the roof and the lowest part of the sign, and at least 5 feet (1524 mm) between the vertical supports thereof.
H110.3 Location.
Roof signs shall be set back a minimum of 6 feet (1829 mm) from the face of the walls of the building on which they are erected.
H110.4 Bearing plates.
The bearing plates of roof signs shall distribute the load directly to or upon masonry walls, steel roof girders, columns or beams. The building shall be designed to avoid overstress of these members.
H110.5 Reserved.
Section BC H111. Wall Signs
H111.1 Materials.
Wall signs erected inside the fire districts shall be constructed entirely of noncombustible materials, and the facings of such signs shall be of noncombustible materials, except as permitted by Section H107. Outside of the fire districts, the structure of wall signs exceeding 500 square feet (46 m 2 ) in display area shall be constructed of noncombustible materials, and the facings of such signs shall be of noncombustible materials, except as permitted in Section H107.
H111.2 Exterior wall mounting details.
Wall signs attached to exterior walls of solid masonry, concrete or stone shall be safely and securely attached by means of metal anchors, bolts or expansion screws of not less than 3/8 inch (9.5 mm) diameter and shall be embedded at least 5 inches (127 mm). Wood blocks shall not be used for anchorage, except in the case of wall signs attached to buildings with walls of wood. A wall sign shall not be supported by anchorages secured to an unbraced parapet wall.
H111.3 Extension.
Wall signs shall not extend above the top of the wall, nor beyond the ends of the wall to which the signs are attached unless such signs conform to the requirements for roof signs, projecting signs or ground signs.
Section BC H112. Projecting Signs
H112.1 Materials.
Projecting signs shall be constructed entirely of noncombustible materials, and the facings of such signs shall be of noncombustible materials, except as permitted by Section H107.
H112.2 Attachment.
Projecting signs shall be securely attached to a building or structure by metal supports such as bolts, anchors, chains, guys or steel rods. Supports shall be secured to a bolt or expansion screw that will develop the strength of the supporting chains, guys or steel rods, with a minimum 5/8-inch (15.9 mm) bolt or lag screw, by an expansion shield. Turn buckles shall be placed in chains, guys or steel rods supporting projecting signs. Staples or nails shall not be used to secure any projecting sign to any building or structure. The dead load of projecting signs not parallel to the building or structure and the load due to wind pressure shall be supported with chains, guys or steel rods having net cross-sectional dimension of not less than 3/8 inch (9.5 mm) diameter. Such supports shall be erected or maintained at an angle of at least 45 degrees (0.78 rad) from the horizontal to resist the dead load and at angle of 45 degrees (0.78 rad) or more with the face of the sign to resist the specified wind pressure. If such projecting sign exceeds 30 square feet (2.8 m 2 ) in one facial area, there shall be provided at least two such supports on each side not more than 8 feet (2438 mm) apart to resist the wind pressure.
H112.3 Wall mounting details.
Chains, cables, guys or steel rods used to support the live or dead load of projecting signs are permitted to be fastened to solid masonry walls with expansion bolts or by machine screws in iron supports, but such supports shall not be attached to an unbraced parapet wall. Where the supports must be fastened to walls made of wood, the supporting anchor bolts must go through the wall and be plated or fastened on the inside in a secure manner.
H112.4 Height limitation.
A projecting sign shall not be erected on the wall of any building so as to project above the roof or cornice wall or above the roof level where there is no cornice wall; except that a sign erected at a right angle to the building, the horizontal width of which sign is perpendicular to such a wall and does not exceed 24 inches (610 mm), is permitted to be erected to a height not exceeding 5 feet (1524 mm) above the roof or cornice wall or above the roof level where there is no cornice wall. A sign attached to a corner of a building and parallel to the vertical line of such corner shall be deemed to be erected at a right angle to the building wall.
Exception: On buildings 35 feet (10 668 mm) high or less, projecting signs, not exceeding 24 inches (610 mm) in width, may be erected to a maximum height of 40 feet (12 192 mm) above grade but in no case to a height of more than 15 feet (4572 mm) above the main roof level.
H112.5 Additional loads.
Projecting sign structures which will be used to support an individual on a ladder or other servicing device, whether or not specifically designed for the servicing device, shall be capable of supporting the anticipated additional load, but not less than a 100-pound (445 N) concentrated horizontal load and a 300-pound (1334 N) concentrated vertical load applied at the point of assumed or most eccentric loading. The building component to which the projecting sign is attached shall also be designed to support the additional loads.
H112.6 Thickness.
Projecting signs shall be limited in thickness as provided for in Table H112.6.
Table H112.6 Thickness of Projecting Signs
Projection (feet) Maximum Thickness (feet) 5 2 4 2.5 3 3 2 3.5 1 4
For SI: 1 foot = 304.8 mm.
H112.7 Location restrictions.
Projecting signs shall not be erected on buildings located on those streets and avenues listed in Section 3202.2.1.8.
Section BC H113. Marquee Signs
H113.1 Materials.
Marquee signs shall be constructed entirely of noncombustible materials, and the facings of such signs shall be of noncombustible materials, except as provided for in Section H107.
H113.2 Attachment.
Marquee signs shall be attached to approved marquees that are constructed in accordance with Section 3106 of this code and shall be anchored in conformance with the requirements for projecting signs under Section H112.
H113.3 Extension.
No part of a marquee sign shall project above or below the marquee fascia, or beyond the perimeter of the marquee.
Exception. On marquees attached to buildings classified as Occupancy Group A-1, skating rinks in Occupancy Group A-4, or amusement park structures in Occupancy Group A-5, marquee signs may project not more than 8 feet (2438 mm) above nor more than 1 foot (305 mm) below the fascia, provided that the total height of such signs does not exceed 9 feet (2743 mm) and the lowest part of such signs is at least 10 feet (3048 mm) above the ground or sidewalk level. Marquee signs shall not project beyond the horizontal ends of the marquee.
H113.4 Location restrictions.
Marquee signs erected on marquees projecting beyond the street line shall be limited to those occupancy groups and locations provided by Section 3202.2.1.4.5 of this code.
Section BC H114. Flexible Fabric Signs
H114.1 General.
The provisions of this section shall apply to flexible fabric signs and flexible fabric sign structures, including the fabric display area, the restraining framework, and all stiffening and fastening devices.
H114.2 Materials.
Fabric used in flexible fabric signs shall be flame resistant in accordance with NFPA 701 or listed under UL 214.
H114.2.1 Longevity.
The same fabric shall not be used for longer than a 12 month period. The same fabric may be relocated and re-erected within that 12 month period, but in no case shall re-inking of fabrics be permitted.
H114.2.2 Affidavit.
Prior to installation of a flexible fabric sign, an affidavit shall be submitted to the Department in which the sign graphic producer shall attest that the sign was made from noncombustible fabric, flame-resistant fabric tested in accordance with NFPA 701 by a nationally recognized testing entity, or fabric bearing a UL Classification Mark obtained from the manufacturer of the fabric.
H114.2.3 Identification.
The additional requirements set forth in Sections H114.2.3.1 through H114.2.3.2 shall apply:
H114.2.3.1 UL classification decal.
All signs shall bear a decal bearing the UL Classification Mark or name of the testing entity and its listing number on a corner of the face of the fabric. This decal shall be of color(s) contrasting with those of the background of the display, and shall be readable from street or roadway level with the aid of binoculars.
H114.2.3.2 Date of sign erection.
All signs shall bear a decal identifying the date of erection of the flexible sign structure on a corner of the face of the sign fabric. This decal shall be of color(s) contrasting with those of the background of the display, and shall be readable from street or roadway level with the aid of binoculars. If the same fabric is relocated, the existing decal shall remain, and a new decal stating the re-erection date shall be affixed.
H114.2.4 Limitations.
When erected on walls, flexible fabric signs exceeding 500 square feet (46.5 m 2 ) in area shall be of the open weave type, unless backed by means of a wall sign or projecting sign structure supported as provided by Sections H111 and H112.
H114.3 Attachment to exterior walls.
A flexible fabric sign attached to an exterior wall shall be attached in accordance with this section. The sign fabric shall not be placed in front of doors, windows, glass blocks, louvers, grilles, fire escapes, exterior stairs, balconies, marquees, wall recesses or projections unless backed by a wall sign or a projecting sign structure as provided by Sections H111 and H112.
H114.3.1 Load spreader bars.
Load spreader bars comprised of noncombustible materials must be inserted around the entire perimeter of the fabric display area into pockets that are either woven, or heat-welded and stitched seamed. The load spreader bars shall be provided with rounded edges to prevent tearing of the fabric.
H114.3.2 Spring snaps.
As an alternate to load spreader bars, the side hems of the fabric may be equipped with grommets to receive spring snaps. The applicant shall determine the appropriate spacing of grommets. The sides of fabric display areas equipped with grommets may be secured with spring snaps to vertical steel wire rope in lieu of restraining angles. The vertical steel wire rope shall be anchored to the wall or other mounting surface by means of eyebolts spaced at intervals to be determined by the applicant. The ends of the vertical steel wire rope shall be restrained by means of turnbuckles or "J" hooks secured to metal angles.
H114.3.3 Fasteners.
Fasteners shall consist of "J" hooks secured with lock nuts or double nuts to continuous metal restraining angles around the perimeter of the display area. The "J" hooks shall extend through holes in the load spreader bars. The ends of the "J" hooks shall be secured with either safety clips or nuts in order to prevent accidental dislodging of the load spreader bars. In lieu of "J" hooks and restraining angles, the load spreader bars in the pockets along the top edge of the fabric display area may be bolted to steel flat bars.
H114.3.3.1 Metal restraining angles and bars.
For all flexible sign structures, the metal angles and/or steel flat bars shall be secured to the wall or other mounting surface. Angles and/or bars shall not be secured to any parapet or wall unless the applicant has determined that the parapet or wall is capable of resisting the loads imposed on it by the flexible sign structure. Unsatisfactory parapets or walls shall be braced or otherwise reinforced as determined by the applicant, prior to the erection of the flexible sign structure. A wall sign, projecting sign, roof sign or ground sign structure must be capable of resisting the loads imposed on it by the flexible sign structure.
H114.3.4 Tensioning.
Initial tension may be applied mechanically to the fabric display area, but it shall be held in final position by adjusting or tightening the turnbuckles, or the nuts holding the "J" hooks to the restraining angles. Mechanical tensioning devices may not remain attached to the flexible sign, except as permitted by Section H114.4.
H114.4 Attachment to sign structures.
Fabric stretched around any edge of a sign structure shall be protected from any sharp edge that may cut or tear the fabric. The perimeter of the fabric located on the front or rear of a sign structure shall be secured as required by Section H114.3, except that the "J" hooks may be secured directly to the sign structure.
H114.4.1 Tensioning devices.
Opposing ends of a fabric sign stretched around the edges of a sign structure may be secured to each other by means of mechanical tensioning devices behind the sign structure, provided that the open ends for the "S" hooks shall be closed with safety clips. Spring snaps may be used in lieu of "S" hooks. The mechanical tensioning devices shall be fastened to safety wires, placed through the holes in the load spreader bars or grommets, to prevent the devices from falling in the event of loss of tension.
H114.4.2 Limitations.
The length of the fabric or safety wire perpendicular to any edge of the sign structure shall be dimensioned such that in the event of failure of any part of the flexible sign structure, no load spreader bars, mechanical tensioning devices, clamps, or wires will strike any nearby doors, windows, vents, chimneys, grilles, skylights, light fixtures, decorations or other wall appurtenances, or mechanical equipment, nor shall any load spreader bar fall within 10 feet (3048 mm) of grade.
Section BC H115. Portable Signs
H115.1 General.
Portable signs shall conform to requirements for ground, roof, projecting, flat and temporary signs where such signs are used in a similar capacity. The requirements of this section shall not be construed to require portable signs to have connections to surfaces, tie-downs or foundations where provisions are made by temporary means or configuration of the structure to provide stability for the expected duration of the installation.
Section BC H116. Temporary Signs
H116.1 Materials.
Temporary signs less than 500 square feet (46.5 m 2 ) in display area may be constructed of combustible materials. Temporary sign structures, with display area greater than 100 square feet (9.3 m 2 ), shall be constructed of rigid materials with rigid frames.
H116.2 Attachment.
Temporary signs shall be securely attached to the sign structure.
H116.3 Duration.
Temporary signs shall be removed no later than 30 days after erection or as soon as such sign is torn or damaged.
H116.4 Limitations.
Temporary signs constructed of combustible materials shall not extend more than 12 inches (305 mm) over, or into, a street.
Exceptions:
1. When permitted by the Department of Transportation, temporary signs of combustible materials may be suspended from buildings or poles to extend across streets.
2. Temporary signs of combustible materials constructed without a frame may be attached flat against, or suspended from, the fascia of a canopy or marquee, provided that the lowest part of any such sign is at least 9 feet (2743 mm) above the ground or sidewalk level.
Section BC H117. Referenced Standards
H117.1 General.
This section lists the standards that are referenced in various sections of this appendix. The standards are listed herein by the promulgating agency of the standard, the standard identification, the effective date and title and the section or sections of this document that reference the standard.
H117.2 Subsequent additions, modifications, or deletions.
Refer to the rules of the department for any subsequent additions, modifications or deletions that may have been made to these standards in accordance with Section 28-103.19 of the Administrative Code.
H117.3 Applicability.
The application of the referenced standards shall be as specified in Section 102.4.
H117.4 Standards.
ASTM D 635-10 Standard Test Method for Rate of Burning and/or Extent and Time of Burning of Self-Supporting Plastics in a Horizontal Position H107.1.1 NFPA 701-10 Methods of Fire Test for Flame Propagation of Textiles and Films H114.2 UL 214-01 Standard for Tests for Flame Propagation of Fabrics and Films H114.2