NYC Administrative Code Title 28, Chapter 7 New York City Building Code, part 23 of 33
Section BC 2407 to Section BC 3007: 43 sections.
Section BC 2407. Glass In Handrails and Guards
2407.1 Materials.
Glass used as structural balustrade panels and in-fill panels in railings shall be laminated glass constructed of fully tempered or heat-strengthened glass and shall comply with Category II or CPSC 16 CFR Part 1201 or Class A of ANSI Z97.1. For all glazing types, the minimum nominal thickness shall be 1/4 inch (6.4 mm).
Exception: For Group R-3 occupancies, single fully tempered glass complying with Category II of CPSC 16 CFR Part 1201 or Class A of ANSI Z97.1 shall be permitted to be used in handrails and guardrails where there is no walking surface beneath them or the walking surface is permanently protected from the risk of falling glass.
2407.1.1 Loads.
The panels and their support system shall be designed to withstand the loads specified in Section 1607.8. Glass guard elements shall be designed using a factor of safety of four.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
2407.1.2 Support and framing.
Support and framing of glass used in handrails and guards shall comply with the requirements of Sections 2403.2 and 2403.3. In glass structural balustrade systems, each handrail or guard section shall be supported by no fewer than three glass balusters or shall be otherwise supported to remain in place should one baluster panel fail. Glass balusters shall not be installed without an attached handrail or guard.
Exception: An attached top rail or handrail is not required when panels are tested to remain in place as a barrier following impact or glass breakage in accordance with ASTM E2353, and designed to withstand the loads specified in Section 1607.8.
2407.1.3 Parking garages.
Glazing materials shall not be installed in handrails or guards in parking garages except for pedestrian areas not exposed to impact from vehicles.
2407.1.4 Glazing in wind-borne debris regions.
Glazing installed in in-fill panels or balusters in wind-borne debris regions shall comply with the following:
2407.1.4.1 Balusters and in-fill panels.
Glass installed in exterior railing in-fill panels or balusters shall be laminated glass complying with Category II of CPSC 16 CFR Part 1201 or Class A of ANSI Z97.1.
2407.1.4.2 Glass supporting top rail.
When the top rail is supported by glass, the assembly shall be tested according to the impact requirements of Section 1609.1.2. The top rail shall remain in place after impact.
Section BC 2408. Glazing In Athletic Facilities
2408.1 General.
Glazing in athletic facilities and similar uses subject to impact loads, which forms whole or partial wall sections or which is used as a door or part of a door, shall comply with this section.
2408.2 Racquetball and squash courts.
Glazing in racquetball, squash courts and similar athletic facilities subject to impact loads shall comply with this section.
2408.2.1 Testing.
Test methods and loads for individual glazed areas in racquetball and squash courts subject to impact loads shall conform to those of CPSC 16 CFR Part 1201 or ANSI Z97.1, with impacts being applied at a height of 59 inches (1499 mm) above the playing surface to an actual or simulated glass wall installation with fixtures, fittings and methods of assembly identical to those used in practice.
Glass walls shall comply with the following conditions:
1. A glass wall in a racquetball or squash court, or similar use subject to impact loads, shall remain intact following a test impact.
2. The deflection of such walls shall be not greater than 1 1/2-inches (38 mm) at the point of impact for a drop height of 48 inches (1219 mm).
Glass doors shall comply with the following conditions:
1. Glass doors shall remain intact following a test impact at the prescribed height in the center of the door.
2. The relative deflection between the edge of a glass door and the adjacent wall shall not exceed the thickness of the wall plus 1/2 inch (12.7 mm) for a drop height of 48 inches (1219 mm).
2408.3 Gymnasiums and basketball courts.
Glazing in multipurpose gymnasiums, basketball courts and similar athletic facilities subject to human impact loads shall comply with Category II of CPSC 16 CFR Part 1201 or Class A of ANSI Z97.1.
Section BC 2409. Glass in Walkways, Elevator Hoistways and Elevator Cars
2409.1 Glass walkways.
Glass installed as floors, landings, stairs and in similar locations shall be designed and engineered by a registered design professional and the design shall include the applicable provisions of ASTM E 2751 and the load requirements of Chapter 16. Such assemblies shall comply with the fire-resistance rating and marking requirements of this code where applicable.
2409.2 Glass in elevator hoistway enclosures.
Glass in elevator hoistway enclosures and hoistway doors shall be laminated glass conforming to ANSI Z97. 1 or CPSC 16 CFR Part 1201 and ASME A17.1, as modified by Appendix K of this code.
2409.2.1 Fire-resistance-rated hoistways.
Glass installed in hoistways and hoistway doors where the hoistway is required to have a fire-resistance rating shall also comply with Section 716.
2409.3 Visions panels in elevator hoistway doors.
Glass in vision panels in elevator hoistway doors shall be permitted to be any transparent glazing material not less than 1/4 inch (6.4 mm) in thickness conforming to Class A in accordance with ANSI Z97.1 or Category II in accordance with CPSC 16 CFR Part 1201. Glass in vision panels in elevator hoistway doors shall also comply with ASME A17.1, Section 2.11.7, as modified by Appendix K of this code for additional requirements.
2409.4 Glass in elevator cars.
Glass in elevator cars shall be in accordance with ASME A17.1 section 2.14.1.8, as modified by Appendix K.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
2409.4.1 Glass types.
Glass in elevator car enclosures, glass elevator car doors and glass used for lining walls and ceilings of elevator cars shall be laminated glass conforming to Class A in accordance with ANSI Z97. 1 or Category II in accordance with CPSC 16 CFR Part 1201. See ASME A17.1, as modified by Appendix K of this code for additional requirements.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
Section BC 2410. Marking of Transparent Doors and Fixed Adjacent Transparent Sidelites
2410.1 Requirement.
Transparent doors and fixed adjacent sidelites shall be marked in accordance with Sections 2410.3 through 2410.4.
Exceptions:
1. One- and two-family dwellings.
2. Fixed adjacent transparent sidelites 20 inches (508 mm) or less in width with opaque stiles at least 1 3/4 inches (44 mm) in width.
3. Where the ground, floor or equivalent surface area in the path of approach to a fixed adjacent transparent sidelite from either side for a minimum distance of 3 feet (914 mm) from such sidelite is so arranged, constructed or designed as to deter persons from approaching such sidelite or a permanent barrier is installed in the path of approach, provided that:
3.1. Decorative pools, horticultural planting or similar installations shall be considered as indicating that the ground, floor or equivalent surface area is not a path of approach.
3.2. Planters, benches and similar barriers which are securely fastened to the floor or wall to prevent their removal shall be considered as blocking the path of approach provided they shall be not less than 18 inches (457 mm) in height from the ground, floor or equivalent surface and extend across at least 2/3 of the total width of the glazed area of the sidelight.
4. Fixed adjacent transparent sidelites which are supported by opaque sill and wall construction of at least 18 inches (457 mm) above the ground, floor or equivalent surface immediately adjacent.
5. Display windows in any establishment, building or structure which fall within the definition of a sidelite if the top of the supporting sill and wall construction is not less than 18 inches (457 mm) above the ground, floor or equivalent surface immediately adjacent and the interior area is occupied with merchandise or similar displays to clearly indicate to the public that it is not a means of ingress or egress.
6. Opaque door pulls or push bars extending across at least two-thirds of the total width of the glazed area.
2410.2 Locations.
Transparent doors and fixed adjacent transparent sidelites shall be marked in two areas on the glass surface. One such area shall be located at least 30 inches (762 mm) but not more than 36 inches (914 mm) above the ground, floor or equivalent surface below the door or sidelite, and the other at least 60 inches (1524 mm) but not more than 66 inches (1676 mm) above the ground, floor or equivalent surface below the door or sidelite.
Exception. The use of horizontal separation bars, muntin bars or other equivalent bars at least one and one-half inches in vertical dimension that extend across the total width of the glazed area and are located at least 40 inches (1016 mm) but not more than 50 inches (1270 mm) above the bottom of the door or sidelite is permitted in lieu of markings.
2410.3 Design.
The marking design shall be at least 4 inches (102 mm) in diameter if circular or 4 inches (102 mm) in its least dimension if elliptical or polygonal, or shall be at least 12 inches (305 mm) in horizontal dimension if the marking is less than 4 inches (102 mm) in its least dimension. In no event shall the vertical dimension of any marking including lettering be less than 1 1/2 inches (38 mm) in height.
2410.4 Materials.
Markings may be comprised of, but are not limited to:
1. Muntin bars, separation bars or other equivalent bars;
2. Chemical etching;
3. Sandblasting;
4. Adhesive strips;
5. Decals; or
6. Paint, gilding or other opaque marking materials.
Section BC 2501. General
2501.1 Scope.
Provisions of this chapter shall govern the materials, design, construction and quality of gypsum board, gypsum panel products, lath, gypsum plaster, cement plaster, cement board and reinforced gypsum concrete.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2014/013.
2501.2 Performance.
Lathing, plastering, gypsum board and gypsum panel product construction shall be done in the manner and with the materials specified in this chapter and the referenced standards listed in Chapter 35. When fire protection is required, such construction shall also comply with the provisions of Chapter 7.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
2501.3 Other materials.
Other approved wall or ceiling coverings shall be permitted to be installed in accordance with the recommendations of the manufacturer and the approval of the commissioner.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
Section BC 2502. Definitions
2502.1 Definitions.
The following terms are defined in Chapter 2:
CEMENT BOARD.
CEMENT PLASTER.
EXTERIOR SURFACES.
GYPSUM BOARD.
GYPSUM PANEL PRODUCTS.
GYPSUM PLASTER.
GYPSUM VENEER PLASTER.
INTERIOR SURFACES.
WEATHER-EXPOSED SURFACES.
WIRE BACKING.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2014/013.
Section BC 2503. Reserved
BetaNYC's copy has no text for this section. Read Section BC 2503 at American Legal Publishing.
Section BC 2504. Vertical and Horizontal Assemblies
2504.1 Scope.
The following requirements shall be met where construction involves gypsum board, gypsum panel products or lath and plaster in vertical and horizontal assemblies.
2504.1.1 Wood framing.
Wood supports for lath, gypsum board or gypsum panel products, as well as wood stripping or furring, shall be not less than 2 inches (51 mm) nominal thickness in the least dimension.
Exception: The minimum nominal dimension of wood furring strips installed over solid backing shall be not less than 1 inch by 2 inches (25 mm by 51 mm).
2504.1.2 Studless partitions.
The minimum thickness of vertically erected studless solid plaster partitions of 3/8-inch (9.5 mm) and 3/4-inch (19.1 mm) rib metal lath, 1/2-inch-thick (12.7 mm) gypsum lath, gypsum board or gypsum panel product shall be 2 inches (51 mm).
Section BC 2505. Shear Wall Construction
2505.1 Resistance to shear (wood framing).
Wood-frame shear walls sheathed with gypsum board, gypsum panel products or lath and plaster shall be designed and constructed in accordance with Section 2306.3 and are permitted to resist wind and seismic loads. Walls resisting seismic loads shall be subject to the limitations in Section 12.2.1 of ASCE 7.
2505.2 Resistance to shear (steel framing).
Cold-formed steel-frame shear walls sheathed with gypsum board or gypsum panel products and constructed in accordance with the materials and provisions of Section 2211.1.1 are permitted to resist wind and seismic loads. Walls resisting seismic loads shall be subject to the limitations in Section 12.2.1 of ASCE 7.
Section BC 2506. Gypsum Board and Gypsum Panel Product Materials
2506.1 General.
Gypsum board, gypsum panel products and accessories shall be identified by the manufacturer's designation to indicate compliance with the appropriate standards referenced in this section and stored to protect such materials from the weather.
2506.2 Standards.
Gypsum board and gypsum panel products shall conform to the appropriate standards listed in Table 2506.2 and Chapter 35 and, where required for fire protection, shall conform to the provisions of Chapter 7.
Table 2506.2 Gypsum Board and Gypsum Panel Products Materials and Accessories
Material Standard Abuse resistant non-decorated interior gypsum panel products and fiber-reinforced cement panels ASTM C 1629 Accessories for gypsum board ASTM C 1047 Adhesives for fastening gypsum wallboard ASTM C 557 Cold-formed steel studs and track, structural AISI S200 and ASTM C 955, Section 8 Cold-formed steel studs and track, nonstructural AISI S220 and ASTM C 645, Section 10 Elastomeric joint sealants ASTM C 920 Fiber-reinforced gypsum panels ASTM C 1278 Glass mat gypsum backing panel ASTM C 1178 Glass mat gypsum panel 5 ASTM C 1658 Glass mat gypsum substrate ASTM C 1177 Joint reinforcing tape and compound ASTM C 474; C 475 Nails for gypsum boards ASTM C 514, F 547, F 1667 Steel screws ASTM C 954; C 1002 Standard specification for gypsum board ASTM C 1396 Testing gypsum and gypsum products ASTM C 22; C 472; C 473
2506.2.1 Other materials.
Metal suspension systems for acoustical and lay-in panel ceilings shall conform with Section 808.1.
2506.3 Mold resistance.
Gypsum board or cement board, used in an assembly for the following areas, shall have a mold resistance rating of 10 in accordance with ASTM D 3273:
1. Interior faces of exterior walls of basements, cellars, and other below grade rooms.
2. Walls and ceilings of spaces containing condensers, water tanks, water pumps, and pressure reduction valves.
3. Walls and ceilings of laundry rooms.
4. Portions of walls within 2 feet (610 mm) of kitchen sinks to a height of 4 feet (1219 mm) above the floor.
5. Portions of walls within 2 feet (610 mm) of kitchen stoves to a height of 4 feet (1219 mm) above the floor.
6. Walls of bathrooms that are not solely water closet compartments, other than walls specifically required to be cement board.
7. Walls and ceilings in service sink closets.
8. Portions of walls within 2 feet (610 mm) of mop sinks or service sinks to a height of 4 feet (1219 mm) above the floor.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2014/013.
Section BC 2507. Lathing and Plastering
2507.1 General.
Lathing and plastering materials and accessories shall be marked by the manufacturer's designation to indicate compliance with the appropriate standards referenced in this section and stored in such a manner to protect them from the weather.
2507.2 Standards.
Lathing and plastering materials shall conform to the standards listed in Table 2507.2 and Chapter 35 and, where required for fire protection, shall also conform to the provisions of Chapter 7.
Table 2507.2 Lath, Plastering Materials and Accessories
Material Standard Accessories for gypsum veneer base ASTM C 1047 Blended cement ASTM C 595 Cold-formed steel studs and track, nonstructural AISI S220 and ASTM C 645, Section 10 Cold-formed steel studs and track, structural AISI S200 and ASTM C 955, Section 8 Exterior plaster bonding compounds ASTM C 932 Gypsum casting and molding plaster ASTM C 59 Gypsum Keene's cement ASTM C 61 Gypsum plaster ASTM C 28 Gypsum veneer plaster ASTM C 587 Hydraulic cement ASTM C 1157; C 1600 Interior bonding compounds, gypsum ASTM C 631 Lime plasters ASTM C 5; C 206 Masonry cement ASTM C 91 Metal lath ASTM C 847 Plaster aggregates Sand Perlite Vermiculite ASTM C 35; C 897 ASTM C 35 ASTM C 35 Plastic cement ASTM C 1328 Portland cement ASTM C 150 Steel screws ASTM C 1002; C 954 Welded wire lath ASTM C 933 Woven wire plaster base ASTM C 1032
Section BC 2508. Gypsum Construction
2508.1 General.
Gypsum board, gypsum panel products and gypsum plaster construction shall be of the materials listed in Tables 2506.2 and 2507.2. These materials shall be assembled and installed in compliance with the appropriate standards listed in Tables 2508.1 and 2511.1.1, and Chapter 35.
Table 2508.1 Installation of Gypsum Construction
Material Standard Gypsum board and gypsum panel products GA-216; ASTM C 840 Gypsum sheathing and gypsum panel products ASTM C 1280 Gypsum board (Interior) ASTM C 1396 Gypsum board (Exterior) ASTM C 1396 Gypsum veneer base ASTM C 844 Interior bathing and furring ASTM C 841 Steel framing for gypsum board and gypsum panel products ASTM C 754; C 1007
2508.2 Limitations.
Gypsum wallboard or gypsum plaster shall not be used in any exterior surface where such gypsum construction will be exposed directly to the weather. Gypsum wallboard shall not be used where there will be direct exposure to water or continuous high humidity conditions beyond the published recommendations of the manufacturer. Gypsum sheathing shall be installed on exterior surfaces in accordance with ASTM C 1280.
2508.2.1 Weather protection.
Gypsum wallboard, gypsum lath or gypsum plaster shall not be installed until weather protection for the installation is provided.
2508.3 Single-ply application.
Edges and ends of gypsum board and gypsum panel products shall occur on the framing members, except those edges and ends that are perpendicular to the framing members. Edges and ends of gypsum board and gypsum panel products shall be in moderate contact except in concealed spaces where fire-resistance-rated construction, shear resistance or diaphragm action is not required.
2508.3.1 Floating angles.
Fasteners at the top and bottom plates of vertical assemblies, or the edges and ends of horizontal assemblies perpendicular to supports, and at the wall line are permitted to be omitted except on shear resisting elements or fire-resistance-rated assemblies. Fasteners shall be applied in such a manner as not to fracture the face paper with the fastener head.
2508.4 Joint treatment.
Gypsum board and gypsum panel product fire-resistance-rated assemblies shall have joints and fasteners treated.
Exception: Joint and fastener treatment need not be provided where any of the following conditions occur:
1. Where the gypsum board or the gypsum panel product is to receive a decorative finish such as wood paneling, battens, acoustical finishes or any similar application that would be equivalent to joint treatment.
2. On single-layer systems where joints occur over wood framing members.
3. Square edge or tongue-and-groove edge gypsum board (V-edge), gypsum panel products, gypsum backing board or gypsum sheathing.
4. On multilayer systems where the joints of adjacent layers are offset.
5. Assemblies tested without joint treatment.
2508.5 Horizontal gypsum board or gypsum panel product diaphragm ceilings.
Gypsum board or gypsum panel products shall be permitted to be used on wood joists to create a horizontal diaphragm ceiling in accordance with Table 2508.5.
Table 2508.5 Shear Capacity for Horizontal Wood-Frame Gypsum Board Diaphragm Ceiling Assemblies
Material Thickness of Material (Minimum) (inches) Spacing of Framing Members (inches) Shear Value a, b (PLF of Ceiling) Minimum Fastener Size Gypsum board or gypsum panel product 1/2 16 o.c. 90 5d cooler or wallboard nail; 1 5/8-inch long; 0.086-inch shank; 15/64-inch head c Gypsum board or gypsum panel product 1/2 24 o.c. 70 5d cooler or wallboard nail; 1 5/8-inch long; 0.086-inch shank; 15/64-inch head c
For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.59 N/m.
a. Values are not cumulative with other horizontal diaphragm values and are for short-term wind or seismic loading. Values shall be reduced 25 percent for normal loading.
b. Values shall be reduced 50 percent in Seismic Design Categories D, E and F.
c. 1 1/4-inch, No. 6 Type S or W screws are permitted to be substituted for the listed nails.
2508.5.1 Diaphragm proportions.
The maximum allowable diaphragm proportions shall be 1 1/2:1 between shear resisting elements. Rotation or cantilever conditions shall not be permitted.
2508.5.2 Installation.
Gypsum board or gypsum panel products used in a horizontal diaphragm ceiling shall be installed perpendicular to ceiling framing members. End joints of adjacent courses of gypsum board shall not occur on the same joist.
2508.5.3 Blocking of perimeter edges.
Perimeter edges shall be blocked using a wood member not less than 2-inch by 6-inch (51 mm by 152 mm) nominal dimension. Blocking material shall be installed flat over the top plate of the wall to provide a nailing surface not less than 2 inches (51 mm) in width for the attachment of the gypsum board or gypsum panel product.
2508.5.4 Fasteners.
Fasteners used for the attachment of gypsum board or gypsum panel products to a horizontal diaphragm ceiling shall be as defined in Table 2508.5. Fasteners shall be spaced not more than 7 inches (178 mm) on center at all supports, including perimeter blocking, and not more than 3/8 inch (9.5 mm) from the edges and ends of the gypsum board or gypsum panel products.
2508.5.5 Lateral force restrictions.
Gypsum board or gypsum panel products shall not be used in diaphragm ceilings to resist lateral forces imposed by masonry or concrete construction.
Section BC 2509. Showers and Water Closets
2509.1 Wet areas.
Showers and public toilet walls shall conform to Section 1210.2.
2509.2 Base for tile.
Materials used as a base for wall tile in tub and shower areas and wall and ceiling panels in shower areas shall be of materials listed in Table 2509.2 and installed in accordance with the manufacturer's recommendations. Water-resistant gypsum backing board shall be used as a base for tile in water closet compartment walls when installed in accordance with GA-216 or ASTM C 840 and the manufacturer's recommendations. Regular gypsum wallboard is permitted under tile or wall panels in other wall and ceiling areas when installed in accordance with GA-216 or ASTM C 840.
Table 2509.2 Backerboard Materials
Material Standard Glass mat water-resistant gypsum backing panel ASTM C 1178 Discrete nonasbestos fiber cement interior substrate sheets ASTM C 1288 Nonasbestos fiber cement flat sheets ISO 8336, Category C Nonasbestos fiber-mat reinforced cementitious backer unit ASTM C 1325
2509.3 Limitations.
Water-resistant gypsum backing board shall not be used in the following locations:
1. Over a vapor retarder in shower or bathtub compartments.
2. Where there will be direct exposure to water or in areas subject to continuous high humidity.
Section BC 2510. Lathing and Furring for Cement Plaster (Stucco)
2510.1 General.
Exterior and interior cement plaster and lathing shall be done with the appropriate materials listed in Table 2507.2 and Chapter 35.
2510.2 Weather protection.
Materials shall be stored in such a manner as to protect them from the weather.
2510.3 Installation.
Installation of these materials shall be in compliance with ASTM C 926 and ASTM C 1063.
2510.4 Corrosion resistance.
Metal lath and lath attachments shall be of corrosion-resistant material.
2510.5 Backing.
Backing or a lath shall provide sufficient rigidity to permit plaster applications.
2510.5.1 Support of lath.
Where lath on vertical surfaces extends between rafters or other similar projecting members, solid backing shall be installed to provide support for lath and attachments.
2510.5.2 Use of gypsum backing board.
Gypsum backing for cement plaster shall be in accordance with Section 2510.5.2.1 or 2510.5.2.2.
2510.5.2.1 Use of gypsum board as a backing board.
Gypsum lath or gypsum wallboard shall not be used as a backing for cement plaster.
Exception: Gypsum lath or gypsum wallboard is permitted, with a weather-resistive barrier, as a backing for self-furred metal lath or self-furred wire fabric lath and cement plaster where either of the following conditions occur:
1. On horizontal supports of ceilings or roof soffits.
2. On interior walls.
2510.5.2.2 Gypsum sheathing backing.
Gypsum sheathing is permitted as a backing for metal or wire fabric lath and cement plaster on walls. A weather-resistive barrier shall be provided in accordance with Section 2510.6.
2510.5.3 Backing not required.
Wire backing is not required under expanded metal lath or paperbacked wire fabric lath.
2510.6 Weather-resistive barriers.
Water-resistive barriers shall be installed as required in Section 1404.2 and, where applied over wood-based sheathing, shall include a water-resistive barrier with a performance at least equivalent to two layers of water-resistive barrier complying with ASTM E 2556, Type I. The individual layers shall be installed independently such that each layer provides a separate continuous plane and any flashing (installed in accordance with Section 1405.4), has a means for draining water that enters the assembly to the exterior.
Exception: Where the water-resistive barrier that is applied over wood-based sheathing has a water resistance equal to or greater than that of a water-resistive barrier complying with ASTM E 2556, Type II and is separated from the stucco by an intervening, substantially nonwater-absorbing layer or drainage space.
2510.7 Preparation of masonry and concrete.
Surfaces shall be clean, free from efflorescence, sufficiently damp and rough for proper bond. If the surface is insufficiently rough, approved bonding agents or a portland cement dash bond coat mixed in proportions of not more than two parts volume of sand to one part volume of portland cement or plastic cement shall be applied. The dash bond coat shall be left undisturbed and shall be moist cured not less than 24 hours.
Section BC 2511. Interior Plaster
2511.1 General.
Plastering gypsum plaster or cement plaster shall not be less than three coats where applied over metal lath or wire fabric lath and not less than two coats where applied over other bases permitted by this chapter.
Exception: Gypsum veneer plaster and cement plaster specifically designed and approved for one-coat applications.
2511.1.1 Installation.
Installation of lathing and plaster materials shall conform to Table 2511.1.1 and Section 2507.
Table 2511.1.1 Installation of Plaster Construction
Material Standard Cement plaster ASTM C 926 Gypsum plaster ASTM C 842 Gypsum veneer plaster ASTM C 843 Interior lathing and furring (gypsum plaster) ASTM C 841 Lathing and furring (cement plaster) ASTM C 1063 Steel framing ASTM C 754; C 1007
2511.2 Limitations.
Plaster shall not be applied directly to fiber insulation board. Cement plaster shall not be applied directly to gypsum lath or gypsum plaster except as specified in Sections 2510.5.1 and 2510.5.2.
2511.3 Grounds.
Where installed, grounds shall ensure the minimum thickness of plaster as set forth in ASTM C 842 and ASTM C 926. Plaster thickness shall be measured from the face of lath and other bases.
2511.4 Interior masonry or concrete.
Condition of surfaces shall be as specified in Section 2510.7. Approved specially prepared gypsum plaster designed for application to concrete surfaces or approved acoustical plaster is permitted. The total thickness of base coat plaster applied to concrete ceilings shall be as set forth in ASTM C 842 or ASTM C 926. Should ceiling surfaces require more than the maximum thickness permitted in ASTM C 842 or ASTM C 926, metal lath or wire fabric lath shall be installed on such surfaces before plastering.
2511.5 Wet areas.
Showers and public toilet walls shall conform to Sections 1210.2 and 1210.3. When wood frame walls and partitions are covered on the interior with cement plaster or tile of similar material and are subject to water splash, the framing shall be protected with an approved moisture barrier.
Section BC 2512. Exterior Plaster
2512.1 General.
Plastering with cement plaster shall be not less than three coats when applied over metal lath or wire fabric lath or gypsum board backing as specified in Section 2510.5 and shall be not less than two coats when applied over masonry or concrete. If the plaster surface is to be completely covered by veneer or other facing material, or is completely concealed by another wall, plaster application need be only two coats, provided the total thickness is as set forth in ASTM C 926.
2512.1.1 On-grade floor slab.
On wood frame or steel stud construction with an on-grade concrete floor slab system, exterior plaster shall be applied in such a manner as to cover, but not to extend below, the lath and paper. The application of lath, paper and flashing or drip screeds shall comply with ASTM C 1063.
2512.1.2 Weep screeds.
A minimum 0.019-inch (0.48 mm) (No. 26 galvanized sheet gage), corrosion-resistant weep screed with a minimum vertical attachment flange of 3 1/2 inches (89 mm) shall be provided at or below the foundation plate line on exterior stud walls in accordance with ASTM C 926. The weep screed shall be placed a minimum of 4 inches (102 mm) above the earth or 2 inches (51 mm) above paved areas and be of a type that will allow trapped water to drain to the exterior of the building. The water-resistive barrier shall lap the attachment flange. The exterior lath shall cover and terminate on the attachment flange of the weep screed.
2512.2 Plasticity agents.
Only approved plasticity agents and approved amounts thereof shall be added to portland cement or blended cements. When plastic cement or masonry cement is used, no additional lime or plasticizers shall be added. Hydrated lime or the equivalent amount of lime putty used as a plasticizer is permitted to be added to cement plaster or cement and lime plaster in an amount not to exceed that set forth in ASTM C 926.
2512.3 Limitations.
Gypsum plaster shall not be used on exterior surfaces.
2512.4 Cement plaster.
Plaster coats shall be protected from freezing for a period of not less than 24 hours after set has occurred. Plaster shall be applied when the ambient temperature is higher than 40°F (4°C), unless provisions are made to keep cement plaster work above 40°F (4°C) during application and 48 hours thereafter.
2512.5 Second-coat application.
The second coat shall be brought out to proper thickness, rodded and floated sufficiently rough to provide adequate bond for the finish coat. The second coat shall have no variation greater than 1/4 inch (6.4 mm) in any direction under a 5-foot (1524 mm) straight edge.
2512.6 Curing and interval.
First and second coats of cement plaster shall be applied and moist cured as set forth in ASTM C 926 and Table 2512.6.
Table 2512.6 Cement Plasters
Coat Minimum Period Moist Curing Minimum Interval Between Coats First 48 hours a 48 hours b Second 48 hours 7 days c Finish — Note c
a. The first two coats shall be as required for the first coats of exterior plaster, except that the moist-curing time period between the first and second coats shall not be less than 24 hours. Moist curing shall not be required where job and weather conditions are favorable to the retention of moisture in the cement plaster for the required time period.
b. Twenty-four-hour minimum interval between coats of interior cement plaster. For alternate method of application, see Section 2512.8.
c. Finish coat plaster is permitted to be applied to interior cement base coats after a 48-hour period.
2512.7 Application to solid backings.
Where applied over gypsum backing as specified in Section 2510.5 or directly to unit masonry surfaces, the second coat is permitted to be applied as soon as the first coat has attained sufficient hardness.
2512.8 Alternate method of application.
The second coat is permitted to be applied as soon as the first coat has attained sufficiently rigidity to receive the second coat.
2512.8.1 Admixtures.
When using this method of application, calcium aluminate cement up to 15 percent of the weight of the portland cement is permitted to be added to the mix.
2512.8.2 Curing.
Curing of the first coat is permitted to be omitted and the second coat shall be cured as set forth in ASTM C 926 and Table 2512.6.
2512.9 Finish coats.
Cement plaster finish coats shall be applied over base coats that have been in place for the time periods set forth in ASTM C 926. The third or finish coat shall be applied with sufficient material and pressure to bond and to cover the brown coat and shall be of sufficient thickness to conceal the brown coat.
Section BC 2513. Exposed Aggregate Plaster
2513.1 General.
Exposed natural or integrally colored aggregate is permitted to be partially embedded in a natural or colored bedding coat of cement plaster or gypsum plaster, subject to the provisions of this section.
2513.2 Aggregate.
The aggregate shall be applied manually or mechanically and shall consist of marble chips, pebbles or similar durable, moderately hard (three or more on the Mohs hardness scale), nonreactive materials.
2513.3 Bedding coat proportions.
The bedding coat for interior or exterior surfaces shall be composed of one part portland cement and one part Type S lime; or one part blended cement and one part Type S lime; or masonry cement; or plastic cement and a maximum of three parts of graded white or natural sand by volume. The bedding coat for interior surfaces shall be composed of 100 pounds (45.4 kg) of neat gypsum plaster and a maximum of 200 pounds (90.8 kg) of graded white sand. A factory-prepared bedding coat for interior or exterior use is permitted. The bedding coat for exterior surfaces shall have a minimum compressive strength of 1,000 pounds per square inch (psi) (6895 kPa)
2513.4 Application.
The bedding coat is permitted to be applied directly over the first (scratch) coat of plaster, provided the ultimate overall thickness is a minimum of 7/8 inch (22 mm), including lath. Over concrete or masonry surfaces, the overall thickness shall be a minimum of 1/2 inch (12.7 mm).
2513.5 Bases.
Exposed aggregate plaster is permitted to be applied over concrete, masonry, cement plaster base coats or gypsum plaster base coats installed in accordance with Section 2511 or 2512.
2513.6 Preparation of masonry and concrete.
Masonry and concrete surfaces shall be prepared in accordance with the provisions of Section 2510.7.
2513.7 Curing of base coats.
Cement plaster base coats shall be cured in accordance with ASTM C 926. Cement plaster bedding coats shall retain sufficient moisture for hydration (hardening) for 24 hours minimum or, where necessary, shall be kept damp for 24 hours by light water spraying.
Section BC 2514. Reinforced Gypsum Concrete
2514.1 General.
Reinforced gypsum concrete shall comply with the requirements of ASTM C 317 and ASTM C 956.
2514.2 Minimum thickness.
The minimum thickness of reinforced gypsum concrete shall be 2 inches (51 mm) except the minimum required thickness shall be reduced to 1 1/2 inches (38 mm), provided the following conditions are satisfied:
1. The overall thickness, including the formboard, is not less than 2 inches (51 mm).
2. The clear span of the gypsum concrete between supports does not exceed 33 inches (838 mm).
3. Diaphragm action is not required.
4. The design live load does not exceed 40 pounds per square foot (psf) (1915 Pa).
2514.3 Limitations of use.
Reinforced gypsum concrete shall not be used where exposed directly to the weather or where subject to frequent or continuous wetting. Precast units shall be protected by coverings or coatings from the weather and from contact with moisture during shipment and during storage at the work site.
Section BC 2601. General
2601.1 Scope.
These provisions shall govern the materials, design, application, construction and installation of foam plastic, foam plastic insulation, plastic veneer, interior plastic finish and trim, light-transmitting plastics and plastic composites, including plastic lumber. See Chapter 14 for requirements for exterior wall finish and trim.
2601.2 Exterior wall coverings.
The use of plastics in exterior wall coverings is subject to the following limitations:
1. Exterior wall coverings containing plastics shall not be permitted on Type IV construction utilizing cross-laminated timber (CLT) or structural composite lumber (SCL) complying with Section 602.4.
2. Exterior wall coverings containing plastics shall not be permitted at exterior balconies and shall comply with Section 1406.3.
Exception: Combustible water-resistive barriers complying with Section 1403.5.1.
2601.2.1 Construction documents.
Construction documents for exterior wall coverings required to be tested to NFPA 285 by this chapter shall comply with the requirements of Section 1401.2.
Section BC 2602. Definitions
2602.1 General.
The following terms are defined in Chapter 2:
FIBER REINFORCED POLYMER.
FIBERGLASS REINFORCED POLYMER.
FOAM PLASTIC INSULATION.
LIGHT-DIFFUSING SYSTEM.
LIGHT-TRANSMITTING PLASTIC ROOF PANELS.
LIGHT-TRANSMITTING PLASTIC WALL PANELS.
PLASTIC, APPROVED.
PLASTIC COMPOSITE.
PLASTIC GLAZING.
PLASTIC LUMBER.
THERMOPLASTIC MATERIAL.
THERMOSETTING MATERIAL.
WOOD/PLASTIC COMPOSITE.
Section BC 2603. Foam Plastic Insulation
This section has 1 picture (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read Section BC 2603 at American Legal Publishing.
2603.1 General.
The provisions of this section shall govern the requirements and uses of foam plastic insulation in buildings and structures.
2603.2 Labeling and identification.
Packages and containers of foam plastic insulation and foam plastic insulation components delivered to the job site shall bear the label of an approved agency showing the manufacturer's name, product listing, product identification and information sufficient to determine that the end use will comply with the code requirements.
2603.3 Surface-burning characteristics.
Unless otherwise indicated in this section, foam plastic insulation and foam plastic cores of manufactured assemblies shall have a flame spread index of not more than 75 and a smoke-developed index of not more than 450 where tested in the maximum thickness intended for use in accordance with ASTM E 84 or UL 723. Loose fill-type foam plastic insulation shall be tested as board stock for the flame spread and smoke-developed indexes.
Exceptions:
1. Foam plastic interior trim shall comply with the flame spread and smoke-developed indexes as provided for in Section 2604.2.
2. In cold storage buildings, ice plants, food plants, food processing rooms and similar areas, foam plastic insulation where tested in a thickness of 4 inches (102 mm) shall be permitted in a thickness up to 10 inches (254 mm) where the building is equipped throughout with an automatic fire sprinkler system in accordance with Section 903.3.1.1. The approved automatic sprinkler system shall be provided in both the room and that part of the building in which the room is located.
3. Foam plastic insulation that is a part of a Class A, B or C roof-covering assembly shall be exempt from the flame spread requirements of this section provided the assembly with the foam plastic insulation satisfactorily passes NFPA 276 or UL 1256. The smoke-developed index shall not be limited for roof applications.
4. Foam plastic insulation greater than 4 inches (102 mm) in thickness shall have a maximum flame spread index of 75 and a smoke-developed index of 450 where tested at a minimum thickness of 4 inches (102 mm), provided the end use is approved in accordance with Section 2603.9 using the thickness and density intended for use.
5. Foam plastic interior signs in covered mall buildings shall not be required to comply with the flame spread and smoke-developed indexes of this section, provided the signs comply with Section 402.6.4.
2603.4 Thermal barrier.
Except as provided for in Sections 2603.4.1 and 2603.9, foam plastic shall be separated from the interior of a building by an approved thermal barrier of 1/2-inch (12.7 mm) gypsum wallboard or equivalent thermal barrier material that will limit the average temperature rise of the unexposed surface to not more than 250°F (120°C) after 15 minutes of fire exposure, complying with the standard time-temperature curve of ASTM E 119 or UL 263. The thermal barrier shall be installed in such a manner that it will remain in place for 15 minutes based on FM 4880, UL 1040, NFPA 286 or UL 1715. Combustible concealed spaces shall comply with Section 719 of this code.
Exception: Thermal barriers for exterior walls shall comply with Section 2603.5.2.
2603.4.1 Thermal barrier not required.
The thermal barrier specified in Section 2603.4 is not required under the conditions set forth in Sections 2603.4.1.1 through 2603.4.1.14.
2603.4.1.1 Masonry or concrete construction.
A thermal barrier is not required for foam plastic insulation installed in a masonry or concrete wall, floor or roof system where the foam plastic insulation is covered on each face by not less than 1 inch (25 mm) thickness of masonry or concrete.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2014/051.
2603.4.1.2 Cooler and freezer walls.
Foam plastic installed in a maximum thickness of 10 inches (254 mm) in cooler and freezer walls shall be permitted without thermal barrier, provided that the walls:
1. Have a flame spread index of 25 or less and a smoke-developed index of not more than 450, where tested in a minimum 4-inch (102 mm) thickness.
2. Have flash ignition and self-ignition temperatures of not less than 600°F and 800°F (316°C and 427°C), respectively.
3. Have a covering of not less than 0.032-inch (0.8 mm) aluminum or corrosion-resistant steel having a base metal thickness not less than 0.0160 inch (0.4 mm) at any point.
4. Be protected by an automatic sprinkler system in accordance with Section 903.3.1.1. Where the cooler or freezer is within a building, both the cooler or freezer and that part of the building in which it is located shall be sprinklered.
2603.4.1.3 Walk-in coolers.
In nonsprinklered buildings, foam plastic having a thickness that does not exceed 4 inches (102 mm) and a maximum flame spread index of 75 is permitted without thermal barrier in walk-in coolers or freezer units where the aggregate floor area does not exceed 400 square feet (37 m 2 ) and the foam plastic is covered by a metal facing not less than 0.032-inch-thick (0.81 mm) aluminum or corrosion-resistant steel having a minimum base metal thickness of 0.016 inch (0.41 mm). A thickness of up to 10 inches (254 mm) is permitted where protected by a thermal barrier.
2603.4.1.4 Exterior walls – one-story buildings.
For one-story buildings, foam plastic having a flame spread index of 25 or less, and a smoke-developed index of not more than 450, shall be permitted without thermal barriers in or on exterior walls in a thickness not more than 4 inches (102 mm) where the foam plastic is covered by a thickness of not less than 0.032-inch-thick (0.81 mm) aluminum or corrosion-resistant steel having a base metal thickness of 0.0160 inch (0.41 mm) and the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
2603.4.1.5 Roofing.
A thermal barrier is not required for foam plastic insulation that is a part of a Class A, B or C roof-covering assembly that is installed in accordance with the code and the manufacturer's instructions and is either constructed as described in Item 1 or tested as described in Item 2.
1. The roof assembly is separated from the interior of the building by wood structural panel sheathing not less than 0.47 inch (11.9 mm) in thickness bonded with exterior glue, with edges supported by blocking, tongue-and-groove joints or other approved type of edge support, or an equivalent material.
2. The assembly with the foam plastic insulation satisfactorily passes NFPA 276 or UL 1256.
2603.4.1.6 Attics and crawl spaces.
Within an attic or crawl space where entry is made only for service of utilities, foam plastic insulation shall be permitted without thermal barrier if protected against ignition by 1 1/2-inch-thick (38 mm) mineral fiber insulation; 1/4-inch-thick (6.4 mm) wood structural panel, particleboard or hardboard; 3/8-inch (9.5 mm) gypsum wallboard, corrosion-resistant steel having a base metal thickness of 0.016 inch (0.4 mm); 1 1/2-inch thick (38 mm) self-supported spray-applied cellulose insulation in attic spaces only or other approved material installed in such a manner that the foam plastic insulation is not exposed. The protective covering shall be consistent with the requirements for the type of construction.
2603.4.1.7 Doors not required to have a fire protection rating.
Where pivoted or side-hinged doors are permitted without a fire protection rating, foam plastic insulation, having a flame spread index of 75 or less and a smoke-developed index of not more than 450, shall be permitted as a core material without a thermal barrier where the door facing is of metal having a minimum thickness of 0.032-inch (0.8 mm) aluminum or steel having a base metal thickness of not less than 0.016 inch (0.4 mm) at any point.
2603.4.1.8 Exterior doors in buildings of Group R-2 or R-3.
In occupancies classified as Group R-2 or R-3, foam-filled exterior entrance doors to individual dwelling units that do not require a fire-resistance rating shall be permitted without a thermal barrier, provided that the doors are faced with aluminum, steel, fiberglass, wood or other approved materials.
2603.4.1.9 Garage doors.
Where garage doors are permitted without a fire-resistance rating and foam plastic is permitted as a core material, provided that the door facing shall be metal having a minimum thickness of 0.032-inch (0.8 mm) aluminum or 0.010-inch (0.25 mm) steel or the facing shall be minimum 0.125-inch-thick (3.2 mm) wood. Garage doors having facings other than those described above shall be tested in accordance with, and meet the acceptance criteria of DASMA 107.
2603.4.1.9.1 Garage doors in one- and two-family dwellings.
Garage doors using foam plastic insulation complying with Section 2603.3 in detached and attached garages associated with one- and two-family dwellings need not be provided with a thermal barrier.
2603.4.1.10 Siding backer board.
Foam plastic insulation of not more than 2,000 British thermal units per square foot (Btu/sq. ft.) (22.7 MJ/m 2 ) as determined by NFPA 259 shall be permitted as a siding backer board with a maximum thickness of 1/2-inch (12.7 mm) without a thermal barrier, provided it is separated from the interior of the building by not less than 2 inches (51 mm) of mineral fiber insulation or equivalent or where applied as insulation over existing wall construction.
2603.4.1.11 Interior trim.
Foam plastic used as interior trim in accordance with Section 2604 shall be permitted without a thermal barrier.
2603.4.1.12 Interior signs.
Foam plastic used for interior signs in covered mall buildings in accordance with Section 402.6.4 of this code shall be permitted without a thermal barrier. Foam plastic signs that are not affixed to interior building surfaces shall comply with Chapter 8 of the New York City Fire Code.
2603.4.1.13 Type V construction.
Foam plastic spray applied to a sill plate, joist header and rim joist in Type V construction is permitted without a thermal barrier, subject to all of the following:
1. The maximum thickness of the foam plastic shall be 3 1/4 inches (82.6 mm).
2. The density of the foam plastic shall be in the range of 1.5 to 2.0 pcf (24 to 32 kg/m 3 ).
3. The foam plastic shall have a flame spread index of 25 or less and an accompanying smoke-developed index of 450 or less when tested in accordance with ASTM E 84 or UL 723.
2603.4.1.14 Floors.
The thermal barrier specified in Section 2603.4 is not required to be installed on the walking surface of a structural floor system that contains foam plastic insulation when the foam is covered by a minimum nominal 1/2-inch-thick (12.7 mm) wood structural panel or approved equivalent. The thermal barrier specified in Section 2603.4 is required on the underside of the structural floor system that contains foam plastic insulation when the underside of the structural floor system is exposed to the interior of the building.
Exception: Foam plastic used as part of an interior floor finish.
2603.5 Exterior walls of buildings of any height.
Exterior walls of buildings of Type I, II, III or IV construction of any height shall comply with 2603.5.1 through 2603.5.7. Exterior walls of cold storage buildings required to be constructed of noncombustible materials, where the building is more than one story in height, shall comply with the provisions of Sections 2603.5.1 through 2603.5.7. Exterior walls of buildings of Type V construction shall comply with Sections 2603.2, 2603.3 and 2603.4.
2603.5.1 Fire-resistance-rated walls.
Where the wall is required to have a fire-resistance rating, data based on tests conducted in accordance with ASTM E 119 or UL 263 shall be provided to substantiate that the fire-resistance rating is maintained.
2603.5.2 Thermal barrier.
Any foam plastic insulation shall be separated from the building interior by a thermal barrier meeting the following provisions, unless special approval is obtained on the basis of Section 2603.9. For exterior walls, foam plastic shall be separated from the interior of a building by an approved thermal barrier of 5/8-inch (15.9 mm) Type X gypsum wallboard or equivalent thermal barrier material that will limit the average temperature rise of the unexposed surface to not more than 250°F (120°C) after 20 minutes of fire exposure, complying with the standard time-temperature curve of ASTM E 119 or UL 263. The thermal barrier shall be installed in accordance with criteria established by testing performed in accordance with FM 4880, UL 1040, NFPA 286 or UL 1715, where the thermal barrier shall remain in place for 20 minutes. Combustible concealed spaces shall comply with Section 718 of this code.
Exception: One-story buildings complying with Section 2603.4.1.4.
2603.5.3 Potential heat.
The potential heat of foam plastic insulation in any portion of the wall or panel shall not exceed the potential heat expressed in Btu per square foot (mJ/m 2 ) of the foam plastic insulation contained in the wall assembly tested in accordance with Section 2603.5.5. The potential heat of the foam plastic insulation shall be determined by tests conducted in accordance with NFPA 259 and the results shall be expressed in Btu per square foot (mJ/m 2 ).
Exception: One-story buildings complying with Section 2603.4.1.4.
2603.5.4 Flame spread and smoke-developed indexes.
Foam plastic insulation, exterior coatings and facings shall be tested separately in the thickness intended for use, but not to exceed 4 inches (102 mm), and shall each have a flame spread index of 25 or less and a smoke-developed index of 450 or less as determined in accordance with ASTM E 84 or UL 723.
Exception: Prefabricated or factory-manufactured panels having minimum 0.020-inch (0.51 mm) aluminum facings and a total thickness of 1/4-inch (6.4 mm) or less are permitted to be tested as an assembly where the foam plastic core is not exposed in the course of construction.
2603.5.5 Vertical and lateral fire propagation.
The exterior wall assembly shall be tested in accordance with and comply with the acceptance criteria of NFPA 285. NFPA 285 design documentation of the tested exterior wall assembly shall be included on the submitted construction documents complying with Section 2601.2.1.
Exceptions:
1. One-story buildings complying with Section 2603.4.1.4.
2. Wall assemblies where the foam plastic insulation is covered on each face by not less than 1 inch (25 mm) thickness of masonry or concrete and meeting one of the following:
2.1. There is no airspace between the insulation and the concrete or masonry.
2.2. The insulation has a flame spread index of not more than 25 as determined in accordance with ASTM E 84 or UL 723 and the maximum airspace between the insulation and the concrete or masonry is not more than 1 inch (25 mm).
2603.5.5.1 Fireblocking.
Exterior wall coverings containing foam plastic insulation shall be fireblocked in accordance with Section 718.2.6.1.
2603.5.6 Label required.
The edge or face of each piece, package or container of foam plastic insulation shall bear the label of an approved agency. The label shall contain the manufacturer's or distributor's identification, model number, serial number or definitive information describing the product or materials' performance characteristics and approved agency's identification.
2603.5.7 Ignition.
Exterior walls shall not exhibit sustained flaming where tested in accordance with NFPA 268. Where a material is intended to be installed in more than one thickness, tests of the minimum and maximum thickness intended for use shall be performed.
Exception: Assemblies protected on the outside with one of the following:
1. A thermal barrier complying with Section 2603.5.2.
2. A minimum 1-inch (25 mm) thickness of concrete or masonry.
3. Glass-fiber-reinforced concrete panels of a minimum thickness of 3/8-inch (9.5 mm).
4. Metal-faced panels having minimum 0.019-inch-thick (0.48 mm) aluminum or 0.016-inch thick (0.41 mm) corrosion-resistant steel outer facings.
5. A minimum 7/8-inch (22.2 mm) thickness of stucco complying with Section 2510.
6. A minimum 1/4-inch (6.4 mm) thickness of fiber-cement lap, panel or shingle siding complying with Sections 1405.16 and 1405.16.1 or 1405.16.2.
2603.5.8 Special inspection.
Foam plastic insulation in exterior wall coverings shall be subject to special inspection in accordance with Chapter 17.
2603.6 Roofing assembly.
Foam plastic insulation meeting the requirements of Sections 2603.2, 2603.3 and 2603.4 shall be permitted as part of a roof-covering assembly, provided the assembly with the foam plastic insulation is a Class A, B or C roofing assembly where tested in accordance with ASTM E 108 or UL 790.
2603.7 Foam plastic insulation used as interior finish or interior trim in plenums.
Foam plastic insulation used as interior wall or ceiling finish or as interior trim in plenums shall exhibit a flame spread index of 75 or less and a smoke-developed index of 450 or less when tested in accordance with ASTM E 84 or UL 723 and shall comply with one or more of Sections 2603.7.1, 2603.7.2 and 2607.3.
2603.7.1 Separation required.
The foam plastic insulation shall be separated from the plenum by a thermal barrier complying with Section 2603.4 and shall exhibit a flame spread index of 75 or less and a smoke-developed index of 450 or less when tested in accordance with ASTM E 84 or UL 723 at the thickness and density intended for use.
2603.7.2 Approval.
The foam plastic insulation shall exhibit a flame spread index of 25 or less and a smoke-developed index of 50 or less when tested in accordance with ASTM E 84 or UL 723 at the thickness and density intended for use and shall meet the acceptance criteria of Section 803.1.2 when tested in accordance with NFPA 286. The foam plastic insulation shall be approved based on tests conducted in accordance with Section 2603.9.
2603.7.3 Covering.
The foam plastic insulation shall be covered by corrosion-resistant steel having a base metal thickness of not less than 0.0160 inch (0.4 mm) and shall exhibit a flame spread index of 75 or less and a smoke-developed index of 450 or less when tested in accordance with ASTM E 84 or UL 723 at the thickness and density intended for use.
2603.8 Protection against termites.
In areas where the probability of termite infestation is very heavy in accordance with Figure 2603.8, extruded and expanded polystyrene, polyisocyanurate and other foam plastics shall not be installed on the exterior face or under interior or exterior foundation walls or slab foundations located below grade. The clearance between foam plastics installed above grade and exposed earth shall be not less than 6 inches (152 mm).
Exceptions:
1. Buildings where the structural members of walls, floors, ceilings and roofs are entirely of noncombustible materials or preservative-treated wood;
2. An approved method of protecting the foam plastic and structure from subterranean termite damage is provided; or
3. On the interior side of basement and cellar walls.
Figure 2603.8 Termite Infestation Probability Map
2603.9 Special approval.
Foam plastic shall not be required to comply with the requirements of Sections 2603.4 or 2603.6 where specifically approved by the department based on large-scale tests such as, but not limited to, NFPA 286 (with the acceptance criteria of Section 803.1.2.1 of this code), FM 4880, UL 1040 or UL 1715. Such testing shall be related to the actual end-use configuration and be performed on the finished manufactured foam plastic assembly in the maximum thickness intended for use. Foam plastics that are used as interior finish on the basis of special tests shall also conform to the flame spread and smoke-developed index requirements of Chapter 8. Assemblies tested shall include seams, joints and other typical details used in the installation of the assembly and shall be tested in the manner intended for use.
2603.10 Wind resistance.
Foam plastic insulation complying with ASTM C 578 and ASTM C 1289 and used as exterior wall sheathing on framed wall assemblies shall comply with ANSI/FS 100 for wind pressure resistance and withstand the loads indicated in Chapter 16 of this code.
2603.11 Cladding attachment over foam sheathing to masonry or concrete wall construction.
Cladding shall be specified and installed in accordance with Chapter 14 and the cladding manufacturer's installation instructions or an approved design. Foam sheathing shall be attached to masonry or concrete construction in accordance with the insulation manufacturer's installation instructions or an approved design. Furring and furring attachments through foam sheathing shall be designed to resist design loads determined in accordance with Chapter 16, including support of cladding weight as applicable. Fasteners used to attach cladding or furring through foam sheathing to masonry or concrete substrates shall be approved for application into masonry or concrete material and shall be installed in accordance with the fastener manufacturer's installation instructions.
Exceptions:
1. Where the cladding manufacturer has provided approved installation instructions for application over foam sheathing and connection to a masonry or concrete substrate, those requirements shall apply.
2. For exterior insulation and finish systems, refer to Section 1408.
3. For anchored masonry or stone veneer installed over foam sheathing, refer to Section 1405.
2603.12 Cladding attachment over foam sheathing to cold-formed steel framing.
Cladding shall be specified and installed in accordance with Chapter 14 and the cladding manufacturer's approved installation instructions, including any limitations for use over foam plastic sheathing, or an approved design. Where used, furring and furring attachments shall be designed to resist design loads determined in accordance with Chapter 16. In addition, the cladding or furring attachments through foam sheathing to framing shall meet or exceed the minimum fastening requirements of Sections 2603.12.1 and 2603.12.2, or an approved design for support of cladding weight.
Exceptions:
1. Where the cladding manufacturer has provided approved installation instructions for application over foam sheathing, those requirements shall apply.
2. For exterior insulation and finish systems, refer to Section 1408.
3. For anchored masonry or stone veneer installed over foam sheathing, refer to Section 1405.
2603.12.1 Direct attachment.
Where cladding is installed directly over foam sheathing without the use of furring, cladding minimum fastening requirements to support the cladding weight shall be as specified in Table 2603.12.1.
Table 2603.12.1 Cladding Minimum Fastening Requirements for Direct Attachment over Foam Plastic Sheathing to Support Cladding Weight a
Cladding Fastener Through Foam Sheathing Into: Cladding Fastener Type and Minimum Size b Cladding Fastener Vertical Spacing (inches) Maximum Thickness of Foam Sheathing c (inches) 16 2 o.c. fastener horizontal spacing 24 2 o.c. fastener horizontal spacing Cladding weight Cladding weight 3 psf 11 psf 25 psf 3 psf 11 psf 25 psf Steel framing (minimum penetration of steel thickness plus 3 threads) #8 screw into 33 mil steel or thicker 6 3 3 1.5 3 2 DR 8 3 2 0.5 3 1.5 DR 12 3 1.5 DR 3 0.75 DR #10 screw into 33 mil steel 6 4 3 2 4 3 0.5 8 4 3 1 4 2 DR 12 4 2 DR 3 1 DR #10 screw into 43 mil steel or thicker 6 4 4 3 4 4 2 8 4 4 2 4 3 1.5 12 4 3 1.5 4 3 DR
For SI: 1 inch = 25.4 mm; 1 pound per square foot (psf) = 0.0479 kPa, 1 pound per square inch = 0.00689 MPa.
DR = design required; o.c. = on center.
a. Steel framing shall be minimum 33 ksi steel for 33 mil and 43 mil steel and 50 ksi steel for 54 mil steel or thicker.
b. Screws shall comply with the requirements of AISI S240.
c. Foam sheathing shall have a minimum compressive strength of 15 pounds per square inch in accordance with ASTM C 578 or ASTM C 1289.
2603.12.2 Furred cladding attachment.
Where steel or wood furring is used to attach cladding over foam sheathing, furring minimum fastening requirements to support the cladding weight shall be as specified in Table 2603.12.2. Where placed horizontally, wood furring shall be preservative-treated wood in accordance with Section 2303.1.9 or naturally durable wood and fasteners shall be corrosion resistant in accordance Section 2304.10.5. Steel furring shall have a minimum G60 galvanized coating.
Table 2603.12.2 Furring Minimum Fastening Requirements for Application over Foam Plastic Sheathing to Support Cladding Weight a
Furring Material Framing Member Fastener Type and Minimum Size b Minimum Penetration into Wall Framing (inches) Fastener Spacing in Furring (inches) Maximum Thickness of Foam Sheathing 4* (inches) 16 2 o.c. furring e 24 2 o.c. furring e Cladding weight Cladding weight 3 psf 11 psf 25 psf 3 psf 11 psf 25 psf Minimum 33 mil steel furring or minimum 1x wood furring c 33 mil steel stud #8 screw Steel thickness plus 3 threads 12 3 1.5 DR 3 0.5 DR 16 3 1 DR 2 DR DR 24 2 DR DR 2 DR DR #10 screw Steel thickness plus 3 threads 12 4 2 DR 4 1 DR 16 4 1.5 DR 3 DR DR 24 3 DR DR 2 DR DR 43 mil or thicker steel stud #8 screw Steel thickness plus 3 threads 12 3 1.5 DR 3 0.5 DR 16 3 1 DR 2 DR DR 24 2 DR DR 2 DR DR #10 screw Steel thickness plus 3 threads 12 4 3 1.5 4 3 DR 16 4 3 0.5 4 2 DR 24 4 2 DR 4 0.5 DR
For SI: 1 inch = 25.4 mm; 1 pound per square foot (psf) = 0.0479 kPa, 1 pound per square inch = 0.00689 MPa.
DR = design required; o.c. = on center.
a. Wood furring shall be Spruce-Pine fir or any softwood species with a specific gravity of 0.42 or greater. Steel furring shall be minimum 33 ksi steel. Steel studs shall be minimum 33 ksi steel for 33 mil and 43 mil thickness and 50 ksi steel for 54 mil steel or thicker.
b. Screws shall comply with the requirements of AISI S240.
c. Where the required cladding fastener penetration into wood material exceeds 3/4 inch and is not more than 1 1/2 inches, a minimum 2-inch nominal wood furring shall be used or an approved design.
d. Foam sheathing shall have a minimum compressive strength of 15 pounds per square inch in accordance with ASTM C 578 or ASTM C 1289.
e. Furring shall be spaced not more than 24 inches on center, in a vertical or horizontal orientation. In a vertical orientation, furring shall be located over wall studs and attached with the required fastener spacing. In a horizontal orientation, the indicated 8-inch and 12-inch fastener spacing in furring shall be achieved by use of two fasteners into studs at 16 inches and 24 inches on center, respectively.
* Editor's note: As set forth in L.L. 2021/126; correct footnote should likely be d.
Section BC 2604. Interior Finish and Trim
2604.1 General.
Plastic materials installed as interior finish or trim shall comply with Chapter 8. Foam plastics shall only be installed as interior finish where approved in accordance with the special provisions of Section 2603.9. Foam plastics that are used as interior finish shall also meet the flame and smoke-developed spread index requirements for interior finish in accordance with Chapter 8. Foam plastics installed as interior trim shall comply with Section 2604.2.
2604.2 Foam plastic interior trim.
Foam plastic used as interior trim shall comply with Sections 2604.2.1 through 2604.2.4.
2604.2.1 Density.
The minimum density of the interior trim shall be 20 pcf (320 kg/m 3 ).
2604.2.2 Thickness.
The maximum thickness of the interior trim shall be 1/2-inch (12.7 mm) and the maximum width shall be 8 inches (204 mm).
2604.2.3 Area limitation.
The interior trim shall not constitute more than 10 percent of the specific wall or ceiling area to which it is attached.
2604.2.4 Flame spread.
The flame spread index shall not exceed 75 where tested in accordance with ASTM E 84 or UL 723. The smoke-developed index shall not be limited.
Exception: When the interior trim material has been tested as an interior finish in accordance with NFPA 286 and complies with the acceptance criteria in Section 803.1.2.1 of this code, it shall not be required to be tested for flame spread index in accordance with ASTM E 84 or UL 723.
Section BC 2605. Plastic Veneer
2605.1 Interior use.
Where used within a building, plastic veneer shall comply with the interior finish requirements of Chapter 8.
2605.2 Exterior use.
Exterior plastic veneer, other than plastic siding, shall be permitted to be installed on the exterior walls of buildings of any type of construction in accordance with all of the following requirements:
1. Plastic veneer shall comply with Section 2606.4.
2. Plastic veneer shall not be attached to any exterior wall to a height greater than 50 feet (15 240 mm) above grade.
3. Sections of plastic veneer shall not exceed 300 square feet (27.9 m 2 ) in area and shall be separated by not less than 4 feet (1219 mm) vertically.
4. Fireblocking complying with Section 718.2.6.1 shall be installed.
Exception: The area and separation requirements and the smoke-density limitation are not applicable to plastic veneer applied to buildings constructed of Type VB construction, provided the walls are not required to have a fire-resistance rating.
2605.3 Plastic siding.
Polypropylene siding and vinyl siding shall comply with the requirements of Sections 1404 and 1405.
2605.4 Special inspection.
Plastic veneers shall be subject to special inspection in accordance with Chapter 17.
Section BC 2606. Light-Transmitting Plastics
2606.1 General.
The provisions of this section and Sections 2607 through 2611 shall govern the quality and methods of application of light-transmitting plastics for use as light-transmitting materials in buildings and structures. Foam plastics shall comply with Section 2603. Light-transmitting plastic materials that meet the other code requirements for walls and roofs shall be permitted to be used in accordance with the other applicable chapters of the code.
2606.2 Approval for use.
Sufficient technical data shall be submitted to substantiate the proposed use of any light-transmitting material, as approved by the department and subject to the requirements of this section.
2606.3 Identification.
Each unit or package of light-transmitting plastic shall be identified with a mark or decal satisfactory to the commissioner, which includes identification as to the material classification.
2606.4 Specifications.
Light-transmitting plastics, including thermoplastic, thermosetting or reinforced thermosetting plastic material, shall have a self-ignition temperature of 650°F (343°C) or greater where tested in accordance with ASTM D 1929; a smoke-developed index not greater than 450 where tested in the manner intended for use in accordance with ASTM E 84 or UL 723, or a maximum average smoke density rating not greater than 75 where tested in the thickness intended for use in accordance with ASTM D 2843 and shall conform to one of the following combustibility classifications:
Class CC1: Plastic materials that have a burning extent of 1 inch (25 mm) or less where tested at a nominal thickness of 0.060 inch (1.5 mm), or in the thickness intended for use, in accordance with ASTM D 635.
Class CC2: Plastic materials that have a burning rate of 2 1/2-inches per minute (1.06 mm/s) or less where tested at a nominal thickness of 0.060 inch (1.5 mm), or in the thickness intended for use, in accordance with ASTM D 635.
2606.5 Structural requirements.
Light-transmitting plastic materials in their assembly shall be of adequate strength and durability to withstand the loads indicated in Chapter 16. Technical data shall be submitted to establish stresses, maximum unsupported spans and such other information for the various thicknesses and forms used as deemed necessary by the department.
2606.6 Fastening.
Fastening shall be adequate to withstand the loads in Chapter 16. Proper allowance shall be made for expansion and contraction of light-transmitting plastic materials in accordance with accepted data on the coefficient of expansion of the material and other material in conjunction with which it is employed.
2606.7 Light-diffusing systems.
Light-diffusing systems shall comply with Sections 2606.7.1 through 2606.7.5. Light-diffusing systems shall not be installed in the following occupancies and locations:
1. Any room in which the net floor area per occupant is 20 square feet (1.86 m 2 ) or less, or any room leading there from through which it is necessary for occupants to pass in order to reach the only exit.
2. Group I-2.
3. Group I-3.
4. Interior exit stairways, ramps and exit passageways.
2606.7.1 Support.
Light-transmitting plastic diffusers shall be supported directly or indirectly from ceiling or roof construction by use of noncombustible hangers. Hangers shall be not less than No. 12 steel-wire gage (0.106 inch) galvanized wire or equivalent.
Exception: Light-transmitting plastic diffusers used in suspended acoustical ceiling systems shall conform with the support requirements as set forth in Section 808.1.
2606.7.2 Installation.
Light-transmitting plastic diffusers shall comply with Chapter 8 unless the light-transmitting plastic diffusers will fall from the mountings before igniting, at an ambient temperature of not less than 200°F (111°C) below the ignition temperature of the panels. The panels shall remain in place at an ambient room temperature of 175°F (79°C) for a period of not less than 15 minutes.
2606.7.3 Size limitations.
Individual panels or units shall not exceed 10 feet (3048 mm) in length nor 30 square feet (2.79 m 2 ) in area.
2606.7.4 Fire suppression system.
In buildings that are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, plastic light-diffusing systems shall be protected both above and below unless the sprinkler system has been specifically approved for installation only above the light-diffusing system. Areas of light-diffusing systems that are protected in accordance with this section shall not be limited.
2606.7.5 Electrical luminaires.
Light-transmitting plastic panels and light-diffuser panels that are installed in approved electrical luminaires shall comply with the requirements of Chapter 8 unless the light-transmitting plastic panels conform to the requirements of Section 2606.7.2.
2606.8 Partitions.
Light-transmitting plastics used in or as partitions shall comply with the requirements of Chapters 6 and 8.
2606.9 Bathroom accessories.
Light-transmitting plastics shall be permitted as glazing in shower stalls, shower doors, bathtub enclosures and similar accessory units. Safety glazing shall be provided in accordance with Chapter 24.
2606.10 Awnings, patio covers and similar structures.
Awnings constructed of light-transmitting plastics shall be constructed in accordance with provisions specified in Section 3105 and Chapter 32 for projections. Patio covers constructed of light-transmitting plastics shall comply with Section 2606. Light-transmitting plastics used in canopies at motor fuel-dispensing facilities shall comply with Section 2606, except as modified by Section 406.7.2.
2606.11 Greenhouses.
Light-transmitting plastics shall be permitted in lieu of plain glass in greenhouses.
2606.12 Solar collectors.
Light-transmitting plastic covers on solar collectors having noncombustible sides and bottoms shall be permitted on buildings not over three stories above grade plane or 9,000 square feet (836.1 m 2 ) in total floor area, provided the light-transmitting plastic cover does not exceed 33.33 percent of the roof area for CC1 materials or 25 percent of the roof area for CC2 materials.
Exception: Light-transmitting plastic covers having a thickness of 0.010 inch (0.3 mm) or less shall be permitted to be of any plastic material provided the area of the solar collectors does not exceed 33.33 percent of the roof area.
Section BC 2607. Light-Transmitting Plastic Wall Panels
2607.1 General.
Light-transmitting plastics shall be permitted to be used as wall panels in exterior walls, provided that the walls are not required to have a fire-resistance rating and the installation conforms to the requirements of this section. Such panels shall be erected and anchored on a foundation, waterproofed or otherwise protected from moisture absorption and sealed with a coat of mastic or other approved waterproof coating. Light-transmitting plastic wall panels shall comply with Section 2606.
Exception: Light-transmitting plastics shall not be used as wall panels in exterior walls in occupancies in Groups A-l, A-2, H, I-2 and I-3.
2607.2 Installation.
Exterior wall panels installed as provided for herein shall not alter the type of construction classification of the building.
2607.3 Height limitation.
Light-transmitting plastics shall not be installed more than 75 feet (22 860 mm) above grade plane, except as allowed by Section 2607.5.
2607.4 Area limitation and separation.
The maximum area of a single wall panel and minimum vertical and horizontal separation requirements for exterior light-transmitting plastic wall panels shall be as provided for in Table 2607.4. The maximum percentage of wall area of any story in light-transmitting plastic wall panels shall not exceed that indicated in Table 2607.4 or the percentage of unprotected openings permitted by Section 705.8, whichever is smaller.
Exceptions:
1. In structures provided with approved flame barriers extending 30 inches (760 mm) beyond the exterior wall in the plane of the floor, a vertical separation is not required at the floor except that provided by the vertical thickness of the flame barrier projection.
2. Veneers of approved weather-resistant light-transmitting plastics used as exterior siding in buildings of Type V construction in compliance with Section 1406.
3. The area of light-transmitting plastic wall panels in exterior walls of greenhouses shall be exempt from the area limitations of Table 2607.4 but shall be limited as required for unprotected openings in accordance with Section 705.8.
Table 2607.4 Area Limitation and Separation Requirements for Light-Transmitting Plastic Wall Panels a
Fire Separation Distance (feet) Class of Plastic Maximum Percentage Area of Exterior Wall in Plastic Wall Panels Maximum Single Area of Plastic Wall Panels (square feet) Minimum Separation of Plastic Wall Panels (feet) Vertical Horizontal Less than 6 — Not Permitted Not Permitted — — 6 or more but less than 11 CC1 10 50 8 4 CC2 Not Permitted Not Permitted — — 11 or more but less than or equal to 30 CC1 25 90 6 4 CC2 15 70 8 4 Over 30 CC1 50 Not Limited 3 b 0 CC2 50 100 6 b 3
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m 2 .
a. For combinations of plastic glazing and plastic wall panel areas permitted, see Section 2607.6.
b. For reductions in vertical separation allowed, see Section 2607.4.
2607.5 Automatic sprinkler system.
Where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, the maximum percentage area of exterior wall in any story in light-transmitting plastic wall panels and the maximum square footage of a single area given in Table 2607.4 shall be increased 100 percent, but the area of light-transmitting plastic wall panels shall not exceed 50 percent of the wall area in any story, or the area permitted by Section 705.8 for unprotected openings, whichever is smaller. These installations shall be exempt from height limitations.
2607.6 Combinations of glazing and wall panels.
Combinations of light-transmitting plastic glazing and light-transmitting plastic wall panels shall be subject to the area, height and percentage limitations and the separation requirements applicable to the class of light-transmitting plastic as prescribed for light-transmitting plastic wall panel installations.
Section BC 2608. Light-Transmitting Plastic Glazing
2608.1 Buildings of Type VB construction.
Openings in the exterior walls of buildings of Type VB construction, where not required to be protected by Section 705, shall be permitted to be glazed or equipped with light-transmitting plastic. Light-transmitting plastic glazing shall comply with Section 2606.
2608.2 Buildings of other types of construction.
Openings in the exterior walls of buildings of types of construction other than Type VB, where not required to be protected by Section 705, shall be permitted to be glazed or equipped with light-transmitting plastic in accordance with Section 2606 and all of the following:
1. The aggregate area of light-transmitting plastic glazing shall not exceed 25 percent of the area of any wall face of the story in which it is installed. The area of a single pane of glazing installed above the first story above grade plane shall not exceed 16 square feet (1.5 m 2 ) and the vertical dimension of a single pane shall not exceed 4 feet (1219 mm).
Exception: Where an automatic sprinkler system is provided throughout in accordance with Section 903.3.1.1, the area of allowable glazing shall be increased to not more than 50 percent of the wall face of the story in which it is installed with no limit on the maximum dimension or area of a single pane of glazing.
2. Approved flame barriers extending 30 inches (762 mm) beyond the exterior wall in the plane of the floor, or approved vertical panels not less than 4 feet (1219 mm) in height, shall be installed between glazed units located in adjacent stories.
Exception: Approved vertical panels not less than 3 feet (914 mm) in height or flame barriers extending 30 inches (762 mm) beyond the exterior wall shall be installed between glazed units located in adjacent stories in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
3. Light-transmitting plastics shall not be installed more than 75 feet (22 860 mm) above grade level.
Exception: Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
Section BC 2609. Light-Transmitting Plastic Roof Panels
2609.1 General.
Light-transmitting plastic roof panels shall comply with this section and Section 2606. Light-transmitting plastic roof panels shall not be installed in Groups H, I-2 and I-3. In all other groups, light-transmitting plastic roof panels shall comply with any one of the following conditions:
1. The building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
2. The roof construction is not required to have a fire-resistance rating by Table 601.
3. The roof panels meet the requirements for roof coverings in accordance with Chapter 15.
2609.2 Separation.
Individual roof panels shall be separated from each other by a distance of not less than 4 feet (1219 mm) measured in a horizontal plane.
Exceptions:
1. The separation between roof panels is not required in a building equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
2. The separation between roof panels is not required in low-hazard occupancy buildings complying with the conditions of Section 2609.4, Exception 2 or 3.
2609.3 Location.
Where exterior wall openings are required to be protected by Section 705.8, a roof panel shall not be installed within 6 feet (1829 mm) of such exterior wall.
2609.4 Area limitations.
Roof panels shall be limited in area and the aggregate area of panels shall be limited by a percentage of the floor area of the room or space sheltered in accordance with Table 2609.4.
Exceptions:
1. The area limitations of Table 2609.4 shall be permitted to be increased by 100 percent in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
2. Low-hazard occupancy buildings, such as swimming pool shelters, shall be exempt from the area limitations of Table 2609.4, provided that the buildings do not exceed 5,000 square feet (465 m 2 ) in area and have a minimum fire separation distance of 10 feet (3048 mm).
3. Greenhouses that are occupied for growing plants on a production or research basis, without public access, shall be exempt from the area limitations of Table 2609.4 provided they have a minimum fire separation distance of 4 feet (1220 mm).
4. Roof coverings over terraces and patios in Group R-3 occupancies shall be exempt from the area limitations of Table 2609.4.
Table 2609.4 Area Limitations for Light-Transmitting Plastic Roof Panels
Class of Plastic Maximum Area of Individual Roof Panels (square feet) Maximum Aggregate Area of Roof Panels (percent of floor area) CC1 300 30 CC2 100 25
For SI: 1 square foot = 0.0929 m 2 .
Section BC 2610. Light-Transmitting Plastic Skylight Glazing
2610.1 Light-transmitting plastic glazing of skylight assemblies.
Skylight assemblies glazed with light-transmitting plastic shall conform to the provisions of this section and Section 2606. Unit skylights glazed with light-transmitting plastic shall comply with Section 2405.5.
Exception: Skylights in which the light-transmitting plastic conforms to the required roof-covering class in accordance with Section 1505.
2610.2 Mounting.
The light-transmitting plastic shall be mounted above the plane of the roof on a curb constructed in accordance with the requirements for the type of construction classification, but not less than 4 inches (102 mm) above the plane of the roof. Edges of the light-transmitting plastic skylights or domes shall be protected by metal or other approved noncombustible material, or the light-transmitting plastic dome or skylight shall be shown to be able to resist ignition where exposed at the edge to a flame from a Class B brand as described in ASTM E 108 or UL 790. The Class B brand test shall be conducted on a skylight that is elevated to a height as specified in the manufacturer's instructions, but not less than 4 inches (102 mm).
Exceptions:
1. Curbs shall not be required for skylights used on roofs having a minimum slope of three units vertical in 12 units horizontal (25-percent slope) in occupancies in Group R-3 and on buildings with a nonclassified roof covering.
2. The metal or noncombustible edge material is not required where nonclassified roof coverings are permitted.
2610.3 Slope.
Flat or corrugated light-transmitting plastic skylights shall slope not less than four units vertical in 12 units horizontal (4:12). Dome-shaped skylights shall rise above the mounting flange a minimum distance equal to 10 percent of the maximum width of the dome but not less than 3 inches (76 mm).
Exception: Skylights that pass the Class B Burning Brand Test specified in ASTM E 108 or UL 790 shall have no minimum slope requirement.
2610.4 Maximum area of skylights.
Each skylight shall have a maximum area within the curb of 100 square feet (9.3 m 2 ).
Exception: The area limitation shall not apply where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or the building is equipped with smoke and heat vents in accordance with Section 910.
2610.5 Aggregate area of skylights.
The aggregate area of skylights shall not exceed 33 1/3 percent of the floor area of the room or space sheltered by the roof in which such skylights are installed where Class CC1 materials are utilized, and 25 percent where Class CC2 materials are utilized.
Exception: The aggregate area limitations of light-transmitting plastic skylights shall be increased 100 percent beyond the limitations set forth in this section where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or the building is equipped with smoke and heat vents in accordance with Section 910.
2610.6 Separation.
Skylights shall be separated from each other by a distance of not less than 4 feet (1219 mm) measured in a horizontal plane.
Exceptions:
1. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
2. In Group R-3, multiple skylights located above the same room or space with a combined area not exceeding the limits set forth in Section 2610.4.
2610.7 Location.
Where exterior wall openings are required to be protected in accordance with Section 705, a skylight shall not be installed within 6 feet (1829 mm) of such exterior wall.
2610.8 Combinations of roof panels and skylights.
Combinations of light-transmitting plastic roof panels and skylights shall be subject to the area and percentage limitations and separation requirements of Section 2609 applicable to roof panel installations.
Section BC 2611. Light-Transmitting Plastic Interior Signs
2611.1 General.
Light-transmitting plastic interior wall signs shall be limited as specified in Sections 2611.2 through 2611.4. Light-transmitting plastic interior wall signs in covered and open mall buildings shall comply with Section 402.6.4. Light-transmitting plastic interior signs shall also comply with Section 2606.
2611.2 Aggregate area.
The sign shall not exceed 20 percent of the wall area.
2611.3 Maximum area.
The sign shall not exceed 24 square feet (2.2 m 2 ).
2611.4 Encasement.
Edges and backs of the sign shall be fully encased in metal.
Section BC 2612. Plastic Composites
2612.1 General.
Plastic composites shall consist of either wood/plastic composites or plastic lumber. Plastic composites shall comply with the provisions of this code and with the additional requirements of Section 2612.
2612.2 Labeling and identification.
Packages and containers of plastic composites used in exterior applications shall bear a label showing the manufacturer's name, product identification and information sufficient to determine that the end use will comply with code requirements.
2612.2.1 Performance levels.
The label for plastic composites used in exterior applications as deck boards, stair treads, handrails and guards shall indicate the required performance levels and demonstrate compliance with the provisions of ASTM D 7032.
2612.2.2 Loading.
The label for plastic composites used in exterior applications as deck boards, stair treads, handrails and guards shall indicate the type and magnitude of the load determined in accordance with ASTM D 7032.
2612.3 Flame spread index.
Plastic composites shall exhibit a flame spread index not exceeding 200 when tested in accordance with ASTM E 84 or UL 723 with the test specimen remaining in place during the test.
Exception: Materials determined to be noncombustible in accordance with Section 703.5.
2612.4 Termite and decay resistance.
Plastic composites containing wood, cellulosic or any other biodegradable materials shall be termite and decay resistant as determined in accordance with ASTM D 7032.
2612.5 Construction requirements.
Plastic composites shall be permitted to be used as exterior deck boards, stair treads, handrails and guards in buildings of Type VB construction.
2612.5.1 Span rating.
Plastic composites used as exterior deck boards shall have a span rating determined in accordance with ASTM D 7032.
2612.6 Plastic composite decking, handrails and guards.
Plastic composite decking, handrails and guards shall be installed in accordance with this code and the manufacturer's instructions.
Section BC 2613. Fiber-Reinforced Polymer
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
2613.1 General.
The provisions of this section shall govern the requirements and uses of fiber-reinforced polymer in and on buildings and structures.
2613.2 Labeling and identification.
Packages and containers of fiber-reinforced polymer and their components delivered to the job site shall bear the label of an approved agency showing the manufacturer's name, product listing, product identification and information sufficient to determine that the end use will comply with the code requirements.
2613.3 Interior finishes.
Fiber-reinforced polymer used as interior finishes, decorative materials or trim shall comply with Chapter 8.
2613.3.1 Foam plastic cores.
Fiber-reinforced polymer used as interior finish and which contains foam plastic cores shall comply with Chapter 8 and this chapter.
2613.4 Light-transmitting materials.
Fiber-reinforced polymer used as light-transmitting materials shall comply with Sections 2606 through 2611 as required for the specific application.
2613.5 Exterior use.
Fiber-reinforced polymer shall be permitted to be installed on the exterior walls of buildings of any type of construction when such polymers meet the requirements of Section 2603.5. Fireblocking shall be installed in accordance with Section 718.
Exceptions:
1. Compliance with Section 2603.5 is not required when all of the following conditions are met:
1.1. The fiber-reinforced polymer shall not exceed an aggregate total of 20 percent of the area of the specific wall to which it is attached, and no single architectural element shall exceed 10 percent of the area of the specific wall to which it is attached, and no contiguous set of architectural elements shall exceed 10 percent of the area of the specific wall to which they are attached.
1.2. The fiber-reinforced polymer shall have a flame spread index of 25 or less. The flame spread index requirement shall not be required for coatings or paints having a thickness of less than 0.036 inch (0.9 mm) that are applied directly to the surface of the fiber-reinforced polymer.
1.3. Fireblocking complying with Section 718.2.6 shall be installed.
1.4. The fiber-reinforced polymer shall be installed directly to a noncombustible substrate or be separated from the exterior wall by one of the following materials: corrosion-resistant steel having a minimum base metal thickness of 0.016 inch (0.41 mm) at any point, aluminum having a minimum thickness of 0.019 inch (0.5 mm) or other approved noncombustible material.
2. Compliance with Section 2603.5 is not required when the fiber-reinforced polymer is installed on buildings that are 40 feet (12 190 mm) or less above grade when all of the following conditions are met:
2.1. The fiber-reinforced polymer shall meet the requirements of Section 1406.2.
2.2. Where the fire separation distance is 5 feet (1524 mm) or less, the area of the fiber-reinforced polymer shall not exceed 10 percent of the wall area. Where the fire separation distance is greater than 5 feet (1524 mm), there shall be no limit on the area of the exterior wall coverage using fiber-reinforced polymer.
2.3. The fiber-reinforced polymer shall have a flame spread index of 200 or less. The flame spread index requirements do not apply to coatings or paints having a thickness of less than 0.036 inch (0.9 mm) that are applied directly to the surface of the fiber-reinforced polymer.
2.4. Fireblocking complying with Section 718.2.6 shall be installed.
Section BC 2614. Reflective Plastic Core Insulation
2614.1 General.
The provisions of this section shall govern the requirements and uses of reflective plastic core insulation in buildings and structures. Reflective plastic core insulation shall comply with the requirements of Section 2614.2 and of one of the following: Section 2614.3 or 2614.4.
2614.2 Identification.
Packages and containers of reflective plastic core insulation delivered to the job site shall show the manufacturer's or supplier's name, product identification and information sufficient to determine that the end use will comply with the code requirements.
2614.3 Surface-burning characteristics.
Reflective plastic core insulation shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 450 when tested in accordance with ASTM E 84 or UL 723. The reflective plastic core insulation shall be tested at the maximum thickness intended for use. Test specimen preparation and mounting shall be in accordance with ASTM E 2599.
2614.4 Room corner test heat release.
Reflective plastic core insulation shall comply with the acceptance criteria of Section 803.1.2.1 of this code when tested in accordance with NFPA 286 or UL 1715 in the manner intended for use and at the maximum thickness intended for use.
Section BC 2701. General
2701.1 Scope.
This chapter governs the electrical components, equipment and systems used in buildings and structures covered by this code. Electrical components, equipment and systems shall be designed and constructed in accordance with the provisions of the New York City Electrical Code.
Section BC 2702. Emergency and Standby Power Systems
2702.1 Installation.
Emergency power systems and standby power systems shall be installed in accordance with the New York City Electrical Code, NFPA 110 and NFPA 111.
2702.1.1 Fuel supply.
Systems relying on fuel supplies shall have an on-premises fuel supply sufficient for not less than 6-hour full-demand operation of the system. However, natural gas from the public utility street main shall be permitted as the sole fuel supply for (i) emergency power systems serving Group R-2 occupancies, (ii) emergency power systems where permitted by Appendix G of this code, and (iii) standby power systems, provided that an outside gas cut-off valve separate from other gas services is installed in accordance with Section E.6 of Appendix E of the New York City Fuel Gas Code.
2702.1.2 Stationary generators.
Stationary emergency and standby power generators required by this code shall be listed in accordance with UL 2200
2702.1.2.1 Prohibited location.
Emergency and standby power generators shall not be located in the same room as the main or primary electrical service equipment. Distribution associated with emergency and standby power systems shall not pass through the room containing the main or primary electrical service equipment.
2702.1.2.2 Enclosure.
Emergency and standby generators within a building shall be located within a dedicated room separated by not less than 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 712, or both.
2702.1.2.2.1 Generator room contents.
Equipment and fuel tanks located within the emergency generator room shall be limited to equipment and fuel tanks associated with the emergency and standby power systems. Piping within the room shall be limited to sprinkler piping.
Exceptions:
1. Uninterrupted conduits not associated with the emergency and standby power system may pass through the emergency generator room.
2. Piping associated with generator cooling systems may be located within the emergency generator room.
2702.1.2.3 Multiple generators.
Multiple generators supplying emergency power system loads only, or supplying emergency power system equipment in combination with optional standby power loads as a common system may be located in the same room. Such generators may also share a common room, fuel supply and other common equipment and systems.
2702.1.3 Capacity.
The emergency and standby power systems shall have capacity and ratings that supply all equipment required to be operational at the same time.
2702.1.4 Protection of fire pumps.
Where electrically powered fire pumps are connected to the emergency power system, overcurrent protection and feeder conductors shall be provided in accordance with the New York City Electrical Code. Automatic transfer switches shall be located in the same room as the fire pump as an integral part of the pump controller.
2702.1.5 Special inspection.
The installation of a required emergency or standby power system shall be subject to special inspection in accordance with Section 1705.
2702.1.6 Registration.
Fuel-burning equipment for an emergency or standby power system shall be registered with the Department of Environmental Protection in accordance with the requirements of Section 24-109 of the Administrative Code.
2702.1.7 Automatic transfer devices and power system feeders.
Automatic transfer devices, emergency generators and emergency or standby power system feeders shall comply with Sections 2702.1.7.1 through 2702.1.7.2.1.
2702.1.7.1 Prohibited location.
All automatic transfer devices and power system feeders that serve emergency and required standby power system equipment shall not be located in the same room as the emergency power system equipment or the main or primary electrical service equipment. Where emergency and standby transfer devices are installed in accordance with Articles 700 and 701 of the New York City Electrical Code, automatic transfer devices for optional standby power systems shall not be installed in the same room.
2702.1.7.2 Enclosure.
Any automatic transfer device that is not located at the load shall be located within a dedicated room separated by not less than 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 712, or both.
2702.1.7.2.1 Automatic transfer device room.
Equipment located within the automatic transfer device room shall be limited to equipment associated with the emergency or standby power systems. Piping within the room shall be limited to sprinkler piping.
2702.2 Where required.
Emergency and standby power systems shall be provided where required by this section.
2702.2.1 Group A occupancies.
Emergency power shall be provided for voice/alarm communication systems in Group A occupancies in accordance with Section 907.5.2.2.5.
2702.2.1.1 Prior code buildings.
In prior code buildings, where a stationary generator is not otherwise required, the power source for emergency power to the voice/alarm communication system may be served by a gas generator or an uninterruptable power source (UPS) in accordance with the New York City Electrical Code.
2702.2.2 Smoke control systems.
Standby power shall be provided for smoke control systems in accordance with Section 909.11.
2702.2.3 Exit signs.
Emergency power shall be provided for exit signs in accordance with Section 1013.6.3.
2702.2.4 Means of egress illumination.
Emergency power shall be provided for means of egress illumination in accordance with Section 1008.3.
2702.2.5 Accessible means of egress elevators.
Standby power shall be provided for elevators that are part of an accessible means of egress in accordance with Section 1009.4.
2702.2.6 Horizontal sliding doors.
Standby power shall be provided for horizontal sliding doors in accordance with Section 1010.1.4.3.
2702.2.7 Semiconductor fabrication facilities.
Emergency power shall be provided for semiconductor fabrication facilities in accordance with Section 415.11.10.
2702.2.8 Membrane structures.
Standby power shall be provided for auxiliary inflation systems in accordance with Section 3102.8.2. Emergency power shall be provided for exit signs in tents and membrane structures.
2702.2.9 Hazardous materials.
Emergency or standby power shall be provided in occupancies with hazardous materials in accordance with the New York City Fire Code and Section 414.5.2 of this code.
2702.2.10 Highly toxic and toxic materials.
Emergency power shall be provided for occupancies with highly toxic or toxic materials in accordance with the New York City Fire Code.
2702.2.11 Organic peroxides.
Emergency or standby power shall be provided for occupancies with organic peroxides in accordance with the New York City Fire Code.
2702.2.12 Pyrophoric materials.
Emergency power shall be provided for occupancies with silane gas in accordance with the New York City Fire Code.
2702.2.13 Covered and open mall buildings.
Emergency power shall be provided for voice/alarm communication systems in covered and open mall buildings in accordance with Section 402.7.4.
2702.2.14 High-rise buildings.
Emergency and standby power shall be provided in high-rise buildings in accordance with Section 403.4.8.
2702.2.15 Underground buildings.
Emergency and standby power shall be provided in underground buildings in accordance with Section 405.8.
2702.2.16 Group I-3 occupancies.
Emergency power shall be provided for doors in Group I-3 occupancies in accordance with Section 408.4.2.
2702.2.17 Elevators.
Standby power for elevators, including elevators provided to accommodate ambulance stretchers pursuant to Section 3002.4, shall be provided as set forth in Section 3003.1.
2702.2.18 Airport traffic control towers.
Standby power shall be provided in airport traffic control towers in accordance with Section 412.3.9.
2702.2.19 Smokeproof enclosures and pressurized elevator shafts.
Standby power shall be provided for smokeproof enclosures as required by Section 909.20.6.2 and for pressurized elevator shafts provided in accordance with Section 3006.1.
2702.2.20 Occupancy Groups B, E and R-1.
Emergency and standby power system shall be required throughout those Group B, E and R- 1 occupancies specified in this section:
1. Group B occupancies with occupied floor less than 75 feet (22 860 mm) above the lowest level of fire department vehicle access having a gross floor area over 15,000 square feet (1393.6 m 2 ) on each floor, or having a total gross floor area of 100,000 square feet (9290.3 m 2 ) or more.
2. Group E occupancies with occupied floor less than 75 feet (22 860 mm) above the lowest level of fire department vehicle access having a gross floor area over 15,000 square feet (1393.6 m 2 ) on each floor, or having a total gross floor area of 100,000 square feet (9290.3 m 2 ) or more.
3. All Group R-1 occupancies.
2702.2.20.1 Equipment requiring emergency power system.
With respect to such Occupancy Groups B, E and R- 1, the following equipment, where such equipment is required by this code, shall be provided with an emergency power system:
1. Exit signs and means of egress illumination required by Chapter 10;
2. Elevator car lighting;
3. Emergency voice/alarm communications systems, including Fire Department in-building Auxiliary Radio Communication systems (ARCs) provided where required or installed voluntarily in accordance with Section 916;
4. Automatic fire detection systems;
5. Fire alarm systems; and
6. Electrically powered fire pumps, including manual fire pumps, automatic fire pumps and sprinkler booster pumps.
2702.2.20.2 Equipment requiring standby power system.
With respect to such Occupancy Groups B, E and R-1, the following equipment, where such equipment is required by this code, shall be provided with a standby power system:
1. Ventilating systems used for smoke venting or control;
2. Stair pressurization;
3. At least three elevators in a building at one time with manual transfer to other elevators as required by Section 3003; and
4. Power and lighting for the fire command center required by Section 403.4.6.
2702.2.21 Continuously operating HVAC systems.
Standby power systems shall be provided for fans or fan systems being designed in accordance with Section 607.5 of the New York City Mechanical Code and Section 717 of this code.
2702.2.22 Gas detection systems.
Emergency power systems shall be provided for gas detection systems in accordance with Section 918.5.
2702.3 Maintenance.
Emergency and standby power systems shall be maintained and tested in accordance with the New York City Fire Code and New York City Electrical Code.
2702.4 Required loads for optional standby power systems.
In addition to any other loads, optional standby power systems shall be capable of providing power to the following standby and emergency power loads upon failure of the normal power supply:
1. Emergency lighting;
2. Fire alarm systems; and
3. Elevators as follows:
3.1. For Groups R-2 occupancies in buildings greater than 125 feet (38 100 mm) in height, at least one elevator serving all floors, or one elevator per bank where different banks serve different portions of the building; or
3.2. For all other buildings having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access, at least one elevator that serves all floors.
Exception: Backup power systems that provide backup power for non-accessory public telecommunications equipment, such as rooftop telecommunications antennas, cooling equipment, routers, etc., need not provide power to the standby and emergency power loads listed in this section.
2702.4.1 Additional optional standby power systems.
Where a functioning emergency power system or required standby power system is in place and provides power to all required emergency or required standby power loads, any additional optional standby power system need not supply power to such emergency or required standby power loads.
2702.4.2 Compliance with NFPA 110 and UL 2200.
Where an optional standby power system is required to supply emergency or required standby power loads, such power system shall comply with the UL 2200 listing and NFPA 110.
2702.4.3 Special inspection.
Where an optional standby power system is required to supply emergency or required standby power loads, such power system shall be subject to special inspection in accordance with Section 1704.31 and the rules of the department.
Section BC 2801. General
2801.1 Scope.
Mechanical appliances, equipment and systems shall be constructed, installed and maintained in accordance with the New York City Mechanical Code and the New York City Fuel Gas Code. Masonry chimneys, fireplaces and barbecues shall comply with the New York City Mechanical Code and Chapter 21 of this code.
Section BC 2901. General
2901.1 Scope.
The New York City Plumbing Code shall govern the construction, erection, installation, alteration, repairs, relocation, replacement, addition to, use or maintenance of plumbing equipment and systems. Toilet and bathing rooms shall be constructed in accordance with Section 1210.
Section BC 3001. General
3001.1 Scope.
This chapter establishes the minimum safety requirements for, and governs the design, construction, installation, alteration, maintenance, inspection, test and operation of, elevators, dumbwaiters, escalators, moving walks, industrial lifts and loading ramps, mechanical parking equipment, console or stage lifts, power operated scaffolds, amusement devices, platform lifts, and special hoisting and conveying equipment. This chapter and all the provisions of this code for new installations shall also apply to elevators in existing buildings moved to new hoistways. High-rise buildings elevators shall also conform to the provisions of Section 403 of this code.
Exception: Personnel and material hoists used for construction operations subject to the requirements of Chapter 33.
3001.2 Referenced standards.
Except as otherwise provided for in this code, the design, construction, installation, alteration, repair and maintenance of elevators and conveying systems and their components shall conform to ASME A17.1/CSA B44 as modified by Appendix K, Chapter K1, ASME A17.2, ASME A17.3 as modified by Appendix K, Chapter K3, ASME A17.5, ASME A17.6, ASME A17.7/CSA B44.7, ASME A18.1, ASME A90.1, ASME B20.1 as modified by Appendix K, Chapter K2, ANSI A10.4, ANSI E1.46, BSR 1.42, ANSI/ICC A117.1, and ASCE 24 for construction in flood hazard areas established in Appendix G. Where this code makes reference to the nationally recognized standards ASME A17.1/CSA B44, ASME A17.3, and ASME B20.1, such standard(s) shall be as modified for New York City in accordance with Appendix K of this code.
3001.3 Accessibility.
The following elevators and lifts shall conform to ICC A117.1:
1. Passenger elevators, including destination-oriented elevators, required to be accessible by Chapter 11;
2. Limited-Use/Limited-Application (LULA) elevators permitted to be installed on an accessible route pursuant to Section 1109.7.1;
3. Platform lifts permitted to be installed on an accessible route pursuant to Section 1109.8;
4. Private residence elevators serving within an individual dwelling unit in Occupancy Groups R-2 and R-3 occupancies on an accessible route; and
5. Elevators provided in accordance with Sections 3002.4.3.2 and 3002.4.3.3.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
3001.4 Change in use.
A change in use of an elevator from freight to passenger, passenger to freight, or from one freight class to another freight class shall comply with Section 8.7 of ASME A17.1/CSA B44.
3001.5 Piping or ductwork.
No piping or ductwork, except as permitted by ASME A17.1/CSA B44, Section 2.8, shall be permitted within hoistway or elevator enclosures except:
1. As required for the elevator installation; and
2. Low voltage wiring less than 50 volts required for fire alarm systems required by this code.
3001.6 Elevator mirrors.
A mirror shall be installed in each self-service passenger elevator in multiple dwellings. Such mirror shall be affixed and maintained in a manner sufficient to enable persons entering such elevator to view the inside thereof prior to entry to determine whether any person is in the elevator.
3001.7 Car switch operation.
Elevators with car switch operation (manual operation) shall be provided with a signal system by means of which signals can be given from any landing whenever the elevator is desired at that landing.
3001.8 Prohibited devices.
The following devices shall be prohibited:
3001.8.1 Manlifts.
The installation of manlifts is prohibited.
3001.8.2 Sidewalk elevators.
The installation of sidewalk elevators located outside the street line is prohibited
3001.9 Approved equipment.
All equipment listed in ASME A17.1/CSA B44, Section 8.3 as modified by New York City Building Code, Appendix K, Chapter K1, shall be listed by an approved agency in accordance with Section 28-113.2.3 of the Administrative Code, Section 8.3.1 of ASME A17.1/CSA B44, and the rules of the department, and shall be approved by the commissioner.
3001.10 Construction documents.
Applications for elevator, escalator, moving walkway and stairway, dumbwaiter, and similar equipment shall contain construction documents that include the following:
1. The location of all machinery, switchboards, junction boxes, and reaction points, with loads indicated;
2. The details of all hoistway conditions including bracket spacing;
3. The estimated maximum vertical forces on the guide rails on application of the safety device;
4. In the case of freight elevators for class B or C loading, the horizontal forces on the guide-rail faces during loading and unloading; and the estimated maximum horizontal forces in a postwise direction on the guide-rail faces on application of the safety device;
5. The size and weight per foot of any rail reinforcements where provided;
6. Compliance with the accessibility features of this code;
7. The details of capability of the withstanding forces (impact) on door entrance assembly and retaining devices;
8. The withstanding hourly fire rating of the hoistway and the hoistway door assembly;
9. The impact loads imposed on machinery and sheave beams, supports and floors or foundations;
10. The impact load on buffer supports due to buffer engagement at the maximum permissible speed and load;
11. Where compensation tie down is applied, the load on the compensation tie down supports; and
12. The total static and dynamic loads from the governor, buffer and tension system.
3001.11 Special provisions for prior code buildings.
Prior code buildings shall be permitted to comply with Section 3001.11.1.
3001.11.1 Existing shafts.
Elevators cabs installed in existing shafts shall be permitted to be smaller than that required by this chapter where necessary to fit in the existing shaft.
Exception: An existing elevator shaft shall be enlarged or a new elevator shaft shall be constructed to accommodate an elevator cab in compliance with Chapter 11 where the entire building is required to be accessible pursuant to either Item 1 of Section 1101.3.1, or Section 1101.3.2.
Section BC 3002. Hoistway Enclosures
3002.1 Hoistway enclosure protection.
Elevator, dumbwaiter and other hoistway enclosures shall be shaft enclosures complying with Section 713.
3002.1.1 Definitions.
The following terms are defined in Chapter 2:
HOISTWAY.
ZERO CLEARANCE VESTIBULE.
3002.1.2 Opening protectives.
Openings in hoistway enclosures shall be protected as required in Chapter 7.
Exception: The elevator car doors and the associated hoistway enclosure doors at the floor level designated for recall in accordance with Section 3003.2 shall be permitted to remain open during Phase I Emergency Recall Operation in accordance with ASME A17.1/CSA B44, as modified by Appendix K, Chapter K1.
3002.1.3 Hardware.
Hardware on opening protectives shall be of an approved type installed as tested, except that approved interlocks, mechanical locks and electric contacts, door and gate electric contacts and door-operating mechanisms shall be exempt from the fire test requirements.
3002.2 Number of elevator cars in a hoistway.
1. Where four or more elevator cars serve all or the same portion of a building, the elevators shall be located in not fewer than two separate hoistways.
2. Where five or more elevators serve the same portion of a building, not more than four elevator cars shall be located in any single hoistway enclosure.
3. Elevators that service different rises shall be located in separate hoistways.
3002.3 Emergency signs.
A sign shall be posted and maintained on every floor at the elevator landing. The sign shall read "IN FIRE EMERGENCY, DO NOT USE ELEVATOR. USE THE EXIT STAIRS." The lettering shall be at least 1/2 inch (13 mm) block letters in red with white background or as otherwise approved by the commissioner. Such lettering shall be properly spaced to provide good legibility. The sign shall also contain a diagram showing the location where it is posted and the location and letter identification of the stairs on the floor. The sign shall be at least 10 inches by 12 inches (255 mm by 305 mm), located directly above a call button and securely attached to the wall or partition. The top of such sign shall not be more than 6 feet (1829 mm) above the floor level. The diagram on such sign may be omitted provided that signs containing such diagram are posted in conspicuous places on the respective floor. In such case, the sign at the elevator landing shall be at least 2 1/2 inches by 10 inches (64 mm by 254 mm) and the diagram signs shall be at least 8 inches by 12 inches (203 mm by 305 mm).
3002.3.1 Stair and elevator identification signs.
Each stair and each bank of elevators shall be identified by an alphabetic letter. A sign indicating the letter of identification for the elevator bank shall be posted and maintained at each elevator landing directly above or as part of the sign specified in Section 3002.3. The stair identification sign shall be posted and maintained on the occupancy side of the stair door. The letter on the sign shall be at least 3 inches (76 mm) high, of bold type and of contrasting color from the background. Such signs shall be securely attached.
Exceptions:
1. The emergency sign shall not be required for elevators that are part of an accessible means of egress complying with Section 1009.4.
2. The emergency sign shall not be required for elevators that are used for occupant self-evacuation in accordance with Section 3008.
3002.4 Elevator required.
In buildings five stories in height or more and buildings with four or more stories below grade plane, at least one elevator shall provide access to all floors.
3002.4.1 Standby power required for elevators.
Emergency power shall be provided to elevators in the following categories:
1. Elevator(s) in high-rise buildings covered by Section 403.1, other than Group R-2 occupancies, as required by Section 403.4.8.4.1;
2. Elevator(s) in high-rise buildings in Group R-2 occupancies more than 125 feet (38 100 mm) in height, as required by Section 403.4.8.4.2;
3. Elevator(s) in underground buildings, as required by Section 405.8;
4. Elevator(s) in Groups B, E, and R-1 occupancies that are subject to Section 2702.2.20; and
5. Elevator(s) serving as accessible means of egress pursuant to Section 1009.4.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2014/051.
3002.4.2 Elevator car to accommodate ambulance stretcher.
Where elevators are provided in buildings five or more stories above, or four or more stories below grade plane, or underground buildings as described in Section 405.1, not fewer than one elevator subject to Section 3003.3 shall be provided with an elevator car of such a size and arrangement to accommodate an ambulance stretcher 24 inches by 84 inches (610 mm by 2134 mm), with not less than 5 inch (127 mm) radius corners, in the horizontal, open position and shall be identified by the international symbol for emergency medical services (star of life). The symbol shall be not less than 3 inches (76 mm) in height and shall be placed on both jambs of the hoistway entrances on each floor. Standby power shall be required for such an elevator if it serves a building subject to Section 3002.4.1.
Exceptions:
1. An elevator serving not more than one individual dwelling unit in a building pursuant to Section 3002.4.3.1 or 3002.4.3.2.
2. Limited-Use/Limited-Application (LULA) elevators (25 feet maximum rise).
3002.4.3 Elevator serving individual dwelling unit.
Elevators provided in individual dwelling units in buildings in Occupancy Groups R-2 and R-3 shall comply with Section 3002.4.3.1 through 3002.4.3.3, as applicable.
3002.4.3.1 Maximum rise of 60 feet (18 288 mm).
A private residence elevator with 60 feet (18 288 mm) of maximum rise shall be permitted to serve within an individual dwelling unit provided the elevator car is in compliance with ASME A17.1/CSA B44, and Section 3001.3 of this code.
3002.4.3.2 Rise of over 60 feet (18 288 mm) but not more than 75 feet (22 860 mm).
An elevator with 60 feet (18 288 mm) but not more than 75 feet (22 860 mm) of maximum rise shall be permitted to serve within an individual dwelling unit provided the elevator car is in compliance with Parts 2 or 3 of ASME A17.1/CSA B44 and Section 3001.3 of this code even if it does not serve on an accessible route within the dwelling unit.
3002.4.3.3 Maximum rise of more than 75 feet (22 860 mm).
A passenger elevator shall be required to serve within an individual dwelling unit where the maximum rise is over 75 feet (22 860 mm). Such elevator shall comply with ASME A17.1/CSA B44, and Sections 3001.3 and 3002.4.2 of this code even if it does not serve on an accessible route within the dwelling unit.
3002.5 Emergency doors.
Where an elevator is installed in a single blind hoistway or on the outside of a building, there shall be installed in the blind portion of the hoistway or blank face of the building, an emergency door in accordance with ASME A17.1/CSA B44.
3002.6 Prohibited doors.
Doors, other than hoistway doors and the elevator car door, shall be prohibited at the point of egress from an elevator car unless such doors are readily openable from the car side without a key, tool, special knowledge or effort.
3002.7 Common enclosure with stairway.
Elevators shall not be in a common shaft enclosure with a stairway.
Exception: Elevators within open parking garages need not be separated from stairway enclosures.
3002.8 Glass in elevator enclosures.
Glass in elevator enclosures shall comply with ASME A17.1/CSA B44 and Section 2409.2 of this code.
3002.9 Plumbing and mechanical systems.
Plumbing and mechanical systems shall not be located in an elevator hoistway enclosure.
Exceptions:
1. Floor drains, sumps and sump pumps shall be permitted at the base of the hoistway enclosure provided they are indirectly connected to the plumbing system.
2. Sprinklers shall be permitted when otherwise required.
Section BC 3003. Emergency Operations
3003.1 Standby power.
In buildings and structures where standby power is required or furnished to operate an elevator, the operation shall be in accordance with Sections 3002.4.1 and 3003.1.1 through 3003.1.4.
3003.1.1 Manual transfer.
Standby power shall be manually transferable to all elevators in each bank.
3003.1.2 One elevator.
Where only one elevator is installed, the elevator shall automatically transfer to standby power within 60 seconds after failure of normal power.
3003.1.3 Two or more elevators.
Where two or more elevators are controlled by a common operating system, all elevators shall automatically transfer to standby power within 60 seconds after failure of normal power where the standby power source is of sufficient capacity to operate all elevators at the same time. Where the standby power source is not of sufficient capacity to operate all elevators at the same time, all elevators shall transfer to standby power in sequence, return to the designated landing and disconnect from the standby power source. For buildings with multiple banks of elevators, at least one elevator from each bank shall remain operable from the standby power source.
3003.1.4 Venting.
Where standby power is connected to elevators, the machine room ventilation or air conditioning shall be connected to the standby power source.
3003.2 Fire fighters' emergency operation.
Elevators shall be provided with Phase I emergency recall operation and Phase II emergency in-car operation where required by ASME A17.1/CSA B44 as modified by Appendix K.
3003.3 Elevator in readiness.
Requirements for elevator in readiness shall be as defined in Sections 3003.3.1 through 3003.3.2.
3003.3.1 Elevator in readiness for Fire Department emergency access.
Except as provided in Section 3003.3.2, in buildings five stories in height or more, underground buildings as described in Section 405.1, and high-rise buildings, at least one elevator shall be kept available for immediate use by the Fire Department during all hours of the night and day, including holidays, Saturdays and Sundays. The elevator in readiness shall serve all floors of the building. For buildings where a Fire Service Access Elevator (FSAE) is provided, the FSAE shall serve all floors of the building. There shall be available at all times a person competent to operate the elevator. However, an attendant shall not be required for buildings with occupied floors of 150 feet (45 720 mm) or less above the lowest level of the Fire Department vehicle access that have elevators with automatic or continuous pressure operation with keyed switches meeting the requirements of ASME A17.1/CSA B44 as modified by Appendix K so as to permit sole use of the elevators by the Fire Department.
3003.3.2 Number of Elevators.
A number of elevators shall be kept available at every floor for the sole use of the Fire Department as required by Section 3003.3.2.1 and Section 3003.3.2.2. This requirement shall apply to the following types of buildings:
1. High-rise buildings with occupancies classified in Groups A, B, E, I, F, H, M and S;
2. Buildings with Group B occupancies with a gross area of 200, 000 square feet (18 581 m 2 ); and
3. Buildings with a main use or dominant occupancy in Group R-1 or R-2.
Exception: In buildings that are five stories or more in height but are not one of the types of buildings described in Item 1 through 3 in Section 3003.3.2, at least one elevator car in such buildings shall be kept available for sole use by the Fire Department.
3003.3.2.1 Three or fewer elevators.
Where a floor is serviced by three or fewer elevator cars, every car shall be kept available for sole use by the Fire Department.
3003.3.2.2 More than three elevators.
Where a floor is serviced by more than three elevator cars, at least three elevator cars with a total rated load capacity of not less than 6,000 pounds (2722 kg) shall be kept available for sole use by the Fire Department. Such cars shall include not more than two cars that service all floors and at least one other car in another bank servicing that floor. If the total load capacity of all cars servicing the floor is less than 6,000 pounds (2722 kg), all such cars shall be kept available for sole use by the Fire Department.
3003.3.3 Operation and control.
Elevators that are kept for the sole use of the Fire Department and that have automatic or continuous pressure operation shall be controlled by keyed switches meeting the requirements of ASME A17.1/CSA B44.
3003.3.4 Other elevator cars.
In high rise buildings classified in occupancy groups A, B, E, F, H, I, M and S, in low-rise buildings classified in occupancy group B with a gross area of 200,000 square feet (18 581 m 2 ) or more and in buildings classified in occupancy group R-1 or R-2, all other automatically operated cars shall have manual operation capability.
Section BC 3004. Conveying Systems
3004.1 General.
Escalators, moving walks, conveyors, and amusement devices shall comply with the provisions of Sections 3004.2 through 3004.5 as applicable.
3004.2 Escalators and moving walks.
Escalators and moving walks shall be constructed of approved noncombustible and fire-retardant materials. This requirement shall not apply to electrical equipment, wiring, wheels, handrails and the use of 1/28-inch (0.9 mm) wood veneers on balustrades backed up with noncombustible materials.
3004.2.1 Enclosure.
Escalator floor openings shall be enclosed with shaft enclosures complying with Section 713.
3004.2.2 Escalators.
Where provided in below-grade transportation stations, escalators shall have a clear width of not less than 32 inches (813 mm).
Exception: The clear width is not required in existing facilities undergoing alterations.
3004.3 Conveyors.
Conveyors and conveying systems shall comply with ASME B20.1.
3004.3.1 Enclosure.
Conveyors and related equipment connecting successive floors or levels shall be enclosed with shaft enclosures complying with Section 713.
3004.3.2 Conveyor safeties.
Power-operated conveyors, belts and other material-moving devices shall be equipped with automatic limit switches that will shut off the power in an emergency and automatically stop all operation of the device.
3004.4 Reserved.
3004.5 Amusement devices.
Amusement devices shall comply with rules of the department.
Section BC 3005. Machinery Spaces, Machine Rooms, Control Spaces and Control Rooms
3005.1 Access.
An approved means of access shall be provided to elevator machine rooms, control rooms, control spaces and machinery spaces.
3005.2 Temperature control.
Elevator machine rooms, machinery spaces that contain the driving machine, and control rooms or spaces that contain the operation or motion controller for elevator operation shall be provided with an independent ventilation or air-conditioning system to protect against the overheating of the electrical equipment. The system shall be capable of maintaining temperatures within the range established for the elevator equipment.
3005.3 Pressurization.
The elevator machine room, control rooms or control space with openings into a pressurized elevator hoistway shall be pressurized upon activation of a heat or smoke detector located in the elevator machine room, control room or control space.
3005.4 Machine rooms, control rooms, machinery spaces, and control spaces.
Elevator machine rooms, control rooms, control spaces and machinery spaces shall be enclosed with fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. The fire-resistance rating shall be not less than the required rating of the hoistway enclosure served by the machinery. Openings in the fire barriers shall be protected with assemblies having a fire protection rating not less than that required for the hoistway enclosure doors.
Exception: For other than fire service access elevators and occupant evacuation elevators, where machine rooms, machinery spaces, control rooms and control spaces do not abut and have no openings to the hoistway enclosure they serve, the fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both, shall be permitted to be reduced to a 2-hour fire-resistance rating.
3005.5 Sprinklers and shunt trip.
Sprinklers are not permitted in elevator machine rooms, machine spaces, control rooms and control spaces. Where elevator hoistways are protected with automatic sprinklers, a means installed in accordance with Section 21.4 of NFPA 72 as modified by Appendix Q shall be provided, where required, to disconnect automatically the main line power supply to the affected elevator prior to the application of water. This means shall not be self-resetting. The activation of automatic sprinklers outside the hoistway, machine room, machinery space, control room or control space shall not disconnect the main line power supply.
3005.6 Plumbing systems.
Plumbing systems not related to elevator machinery shall not be located in elevator equipment rooms.
3005.7 Elevator machinery noise control in multiple dwellings.
Gear-driven machinery, gearless machinery, and motor generators located in an elevator machinery room or shaft on a roof, or on a floor other than a floor on grade, shall be supported on vibration isolator pads having a minimum thickness of 1/2 inch (12.7 mm).
Section BC 3006. Elevator Lobbies and Hoistway Opening Protection
3006.1 Elevator, dumbwaiter and other hoistways.
Elevator, dumbwaiter, and other hoistway enclosures shall be constructed in accordance with Section 713 and Chapter 30.
3006.1.1 Elevator lobby.
Except as provided by Sections 403.6.1 and 403.6.2, an enclosed elevator lobby shall be provided in high-rise buildings at the following locations:
1. Elevators opening onto a fire-resistance-rated corridor, in all occupancy groups.
2. Elevators serving Group B occupancies. Elevators that serve four or more stories that contain space classified in occupancy Group B, inclusive of any lobby or entrance level, shall provide elevator lobbies at every level served by such elevator.
The lobby enclosure shall separate the elevator shaft enclosure doors from each floor by smoke partitions. In addition to the requirements in Section 710 for smoke partitions, doors protecting openings in the elevator lobby enclosure walls shall also comply with Section 710.5.2.3 and penetrations of the elevator lobby enclosure by ducts and air transfer openings shall be protected in accordance with Section 710.8. Elevator lobbies shall have at least one means of egress complying with Chapter 10 and other provisions within this code. Access to an exit on any story through an elevator lobby shall be permitted provided that access to at least one other required exit does not require passing through the elevator lobby.
Exceptions:
1. Enclosed elevator lobbies are not required at the street floor, provided the entire street floor is equipped with an automatic sprinkler system in accordance with Section 903.3.1.1.
2. Elevators not required to be located in a shaft in accordance with Section 712 are not required to have enclosed elevator lobbies.
3. Enclosed elevator lobbies are not required where zero-clearance doors are provided at the hoistway opening in accordance with Section 3002.6. Such doors shall be tested in accordance with UL 1784 without an artificial bottom seal.
4. Enclosed elevator lobbies are not required on floors with less than 2,500 square feet (232 m 2 ), provided that the commissioner accepts an alternative design or construction method that accomplishes the purposes of this section, or provided that the commissioner determines that compliance with this section is impracticable in whole or in part, whereby the commissioner may authorize an exemption from the requirements of this section.
5. Enclosed elevator lobbies are not required on Group R-2 occupied floors.
6. Enclosed elevator lobbies are not required where the elevator hoistway is pressurized in accordance with Section 3006.1.2.
7. Enclosed elevator lobbies are not required where the elevator serves only open parking garages in accordance with Section 406.5.
3006.1.1.1 Areas of rescue assistance.
Areas of rescue assistance shall be provided as required in Section 1009.6.
3006.1.2 Enclosed elevator lobby.
Where elevator hoistway pressurization is provided in lieu of required enclosed elevator lobbies, the pressurization system shall comply with this section except as provided by Sections 403.6.1 and 403.6.2.
3006.1.2.1 Pressurization requirements.
Elevator hoistways shall be pressurized to maintain a minimum positive pressure of 0.10 inches of water (25 Pa) and a maximum positive pressure of 0.25 inches of water (67 Pa) with respect to adjacent occupied space on all floors. This pressure shall be measured at the midpoint of each hoistway door, with all elevator cars at the floor of recall and all hoistway doors on the floor of recall open and all other hoistway doors closed. The opening and closing of hoistway doors at each level must be demonstrated during this test. The supply air intake shall be from an outside, uncontaminated source located a minimum distance of 20 feet (6096 mm) from any air exhaust system or outlet.
3006.1.2.2 Rational analysis.
A rational analysis complying with Section 909.4 shall be submitted with the construction documents.
3006.1.2.3 Ducts for system.
Any duct system that is part of the pressurization system shall be protected with the same fire-resistance rating as required for the elevator shaft enclosure.
3006.1.2.4 Fan system.
The fan system provided for the pressurization system shall be as required by this section.
3006.1.2.4.1 Fire resistance.
When located within the building, the fan system that provides the pressurization shall be protected with the same fire-resistance rating required for the elevator shaft enclosure.
3006.1.2.4.2 Smoke detection.
The fan system shall be equipped with a smoke detector that will automatically shut down the fan system when smoke is detected within the system.
3006.1.2.4.3 Separate systems.
A separate fan system shall be used for each elevator hoistway.
3006.1.2.4.4 Fan capacity.
The supply fan shall either be adjustable with a capacity of at least 1,000 cfm (0.4719 m 3 /s) per door, or that specified by a registered design professional to meet the requirements of a designed pressurization system.
3006.1.2.5 Standby power.
The pressurization system shall be provided with standby power from the same source as other required emergency systems for the building.
3006.1.2.6 Activation of pressurization system.
The elevator pressurization system shall be activated upon activation of the building fire alarm system or upon activation of the elevator lobby smoke detectors. Where both a building fire alarm system and elevator lobby smoke detectors are present, each shall be independently capable of activating the pressurization system.
3006.1.2.7 Special inspection.
Special inspection for performance shall be required in accordance with Section 909.18.8. System acceptance shall be in accordance with Section 909.19.
3006.1.2.8 Marking and identification.
Detection and control systems shall be marked in accordance with Section 909.14.
3006.1.2.9 Control diagrams.
Control diagrams shall be provided in accordance with Section 909.15.
3006.1.2.10 Control panel.
A fire-fighter's smoke control panel complying with Section 909.16 shall be provided.
3006.1.2.11 System response time.
Hoistway pressurization systems shall comply with the requirements for smoke control system response time in Section 909.17.
Section BC 3007. Fire Service Access Elevator
This section has 1 picture (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read Section BC 3007 at American Legal Publishing.
3007.1 General.
Where required by Section 403.6.1, every floor of the building shall be served by a fire service access elevator complying with Sections 3007.1 through 3007.8. Except as modified in this section, the fire service access elevator shall be installed in accordance with this chapter and ASME A17.1/CSA B44 as modified by Appendix K, Chapter K1.
3007.2 Automatic sprinkler system.
The building shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, except as otherwise permitted by Section 903.3.1.1.1 and as prohibited by Section 3007.2.1.
3007.2.1 Prohibited locations.
Automatic sprinklers shall not be installed in elevator machine rooms, machinery spaces, control rooms, control spaces, and elevator hoistways of fire service access elevators.
3007.2.2 Sprinkler system monitoring.
The sprinkler system shall have a sprinkler control valve supervisory switch and water-flow-initiating device provided for each floor that is monitored by the building's fire alarm system.
3007.3 Water protection.
An approved method to prevent water from infiltrating into the hoistway enclosure from the operation of the automatic sprinkler system shall be provided:
1. Where an elevator lobby is provided in accordance with Section 3007.6, with respect to the automatic sprinkler system outside of the enclosed elevator lobby.
2. Where a corridor is provided in accordance with Section 3007.6, Exception 2, with respect to the automatic sprinkler system outside of the corridor and with respect to the automatic sprinklers inside the corridor that are beyond 10 feet of the entrance to the hoistway enclosure of the fire service access elevator.
3. Where neither an enclosed elevator lobby nor a corridor is provided in accordance with Section 3007.6, Exception 3, with respect to the automatic sprinklers that are located beyond 10 feet of the entrance to the hoistway enclosure of the fire service access elevator.
3007.4 Reserved.
3007.5 Hoistway enclosures.
The fire service access elevator hoistway shall be located in a shaft enclosure complying with Section 713.
3007.5.1 Structural integrity of hoistway enclosures.
The fire service access elevator hoistway enclosure shall comply with Sections 403.2.3.1 through 403.2.3.4.
3007.5.2 Hoistway lighting.
When fire-fighters' emergency operation is active, the entire height of the hoistway shall be illuminated at not less than 1 footcandle (11 lux) as measured from the top of the car of each fire service access elevator.
3007.6 Fire service access elevator lobby.
The fire service access elevator shall open into a fire service access elevator lobby in accordance with Sections 3007.6.1 through 3007.6.5. Egress is permitted through the elevator lobby in accordance with Item 1 of Section 1016.2.
Exceptions:
1. Where a fire service access elevator has two entrances onto a floor, the second entrance shall be permitted to open into an elevator lobby in accordance with Section 3006.1.1.
2. A fire service access elevator lobby shall not be required on stories where the elevator opens to a corridor enclosed with a fire barrier, provided all doors opening onto such corridor are smoke and draft controlled doors complying with Section 716.5.3.1 with the UL 1784 test conducted without the artificial bottom seal.
3. A fire service access elevator lobby shall not be required on stories that are less than 3,000 square feet (279 m 2 ) containing only Group R-2 occupancies.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
3007.6.1 Reserved.
3007.6.2 Lobby enclosure.
The fire service access elevator lobby shall be enclosed with a smoke barrier having a fire-resistance rating of not less than 1 hour, except that lobby doorways shall comply with Section 3007.6.3.
Exception: Enclosed fire service access elevator lobbies are not required at the levels of exit discharge.
3007.6.3 Lobby doorways.
Other than doors to the hoistway, elevator control room or elevator control space, each doorway to a fire service access elevator lobby shall be provided with a 3/4-hour fire door assembly complying with Section 716.5. The fire door assembly shall comply with the smoke and draft control door assembly requirements of Section 716.5.3.1 with the UL 1784 test conducted without the artificial bottom seal.
3007.6.4 Lobby size.
The enclosed fire service access elevator lobby shall be a not less than 120 square feet (11 m 2 ) in an area with a minimum dimension of 6 feet (1828 mm).
3007.6.5 Fire service access elevator symbol.
A pictorial symbol of a standardized design designating which elevators are fire service access elevators shall be installed on each side of the hoistway door frame on the portion of the frame at right angles to the fire service access elevator lobby. The fire service access elevator symbol shall be designed as shown in Figure 3007.6.5 and shall comply with the following:
1. The fire service access elevator symbol shall be not less than 3 inches (76 mm) in height.
2. The helmet shall contrast with the background, with either a light helmet on a dark background or a dark helmet on a light background.
3. The vertical center line of the fire service access elevator symbol shall be centered on the hoistway door frame. Each symbol shall be not less than 78 inches (1981 mm), and not more than 84 (2134 mm) inches above the finished floor at the threshold.
Figure 3007.6.5 Fire Service Access Elevator Symbol
3007.7 Elevator system monitoring.
The fire service access elevator shall be continuously monitored at the fire command center by a standard emergency service interface system meeting the requirements of NFPA 72 as modified by Appendix Q.
3007.8 Electrical power.
The following features serving each fire service access elevator shall be supplied by both normal power and Type 60/Class 6/Level 1 standby power:
1. Elevator equipment.
2. Elevator hoistway lighting.
3. Ventilation and cooling equipment for elevator machine rooms, control rooms, machine spaces and machinery/control spaces.
4. Elevator car lighting.
Exception: Standby power relying on natural gas as a fuel source need not be Class 6.
3007.8.1 Protection of wiring or cables.
Wires or cables that are located outside of the elevator hoistway and machine room and that provide normal or standby power, control signals, communication with the car, lighting, heating, air conditioning, ventilation and fire-detecting systems to fire service access elevators shall be protected by construction having a fire-resistance rating of not less than 2 hours, shall be a circuit integrity cable having a fire-resistance rating of not less than 2 hours, or shall be protected by a listed electrical protective system having a fire-resistance rating of not less than 2 hours.
Exception: Wiring and cables to control signals are not required to be protected provided that wiring and cables do not serve Phase II emergency in-car operations.