NYC Administrative Code Title 28, Chapter 7 New York City Building Code, part 21 of 33

Section BC 2304 to Section BC 2307: 4 sections.

Section BC 2304. General Construction Requirements

Open this section

2304.1 General.

The provisions of this section apply to design methods specified in Section 2301.2.

2304.2 Size of structural members.

Computations to determine the required sizes of members shall be based on the net dimensions (actual sizes) and not nominal sizes.

2304.3 Wall framing.

The framing of exterior and interior walls shall be in accordance with the provisions specified in Section 2308 unless a specific design is furnished.

2304.3.1 Bottom plates.

Studs shall have full bearing on a 2-inch-thick (actual 1 1/2-inch, 38 mm) or larger plate or sill having a width at least equal to the width of the studs.

2304.3.2 Framing over openings.

Headers, double joists, trusses or other approved assemblies that are of adequate size to transfer loads to the vertical members shall be provided over window and door openings in load-bearing walls and partitions.

2304.3.3 Shrinkage.

Wood walls and bearing partitions shall not support more than two floors and a roof unless an analysis satisfactory to the commissioner shows that shrinkage of the wood framing will not have adverse effects on the structure or any plumbing, electrical or mechanical systems or other equipment installed therein due to excessive shrinkage or differential movements caused by shrinkage. The analysis shall also show that the roof drainage system and the foregoing systems or equipment will not be adversely affected or, as an alternate, such systems shall be designed to accommodate the differential shrinkage or movements.

2304.4 Floor and roof framing.

The framing of wood-joisted floors and wood-framed roofs shall be in accordance with the provisions specified in Section 2308 unless a specific design is furnished.

2304.4.1 Firecutting.

The ends of wood beams, joists and rafters resting on unreinforced masonry or plain concrete walls shall be firecut to a bevel of 3 inches (76 mm) in depth.

2304.5 Framing around flues and chimneys.

Combustible framing shall be a minimum of 2 inches (51 mm), but shall not be less than the distance specified in Sections 2111 and 2113 and the New York City Mechanical Code, from flues, chimneys and fireplaces, and 6 inches (152 mm) away from flue openings.

2304.6 Exterior wall sheathing.

Wall sheathing on the outside of exterior walls, including gables, and the connection of the sheathing to framing shall be designed in accordance with the general provisions of this code and shall be capable of resisting wind pressures in accordance with Section 1609.

2304.6.1 Wood structural panel sheathing.

Where wood structural panel sheathing is used as the exposed finish on the outside of exterior walls, it shall have an exterior exposure durability classification. Where wood structural panel sheathing is used elsewhere, but not as the exposed finish, it shall be of a type manufactured with exterior glue (Exposure 1 or Exterior). Wood structural panel sheathing, connections and framing spacing shall be in accordance with Table 2304.6.1 for the applicable wind speed and exposure category where used in enclosed buildings with a mean roof height not greater than 30 feet (9144 mm) and a topographic factor (K zt ) of 1.0.

Table 2304.6.1 Maximum Allowable Stress Design Wind Speed V asd Permitted for Wood Structural Panel Wall Sheathing Used to Resist Wind Pressures a, b, c

Minimum Nail Minimum Wood Structural Panel Span Rating Minimum Nominal Panel Thickness (inches) Maximum Wall Stud Spacing (inches) Panel Nail Spacing Maximum Allowable Stress Design Wind Speed, V asd d (mph) Size Penetration (inches) Edges (inches o.c.) Field (inches o.c.) Wind exposure category B C D 6d common (2.0" × 0.113") 1.5 24/0 3/8 16 6 12 110 90 85 24/16 7/16 16 6 12 110 100 90 6 150 125 110 8d common (2.5" × 0.131") 1.75 24/16 7/16 16 6 12 130 110 105 6 150 125 110 24 6 12 110 90 85 6 110 90 85

For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.447 m/s.

a. Panel strength axis shall be parallel or perpendicular to supports. Three-ply plywood sheathing with studs spaced more than 16 inches on center shall be applied with panel strength axis perpendicular to supports.

b. The table is based on wind pressures acting toward and away from building surfaces in accordance with Section 30.6 of ASCE 7. Lateral requirements shall be in accordance with Section 2305 or 2308.

c. Wood structural panels with span ratings of wall-16 or wall-24 shall be permitted as an alternative to panels with a 24/0 span rating. Plywood siding rated 16 on center or 24 on center shall be permitted as an alternative to panels with a 24/16 span rating. Wall-16 and plywood siding 16 on center shall be used with studs spaced not more than 16 inches on center.

d. V asd shall be determined in accordance with Section 1609.3.1.

2304.7 Interior paneling.

Softwood wood structural panels used for interior paneling shall conform to the provisions of Chapter 8 and shall be installed in accordance with Table 2304.10.1. Panels shall comply with DOC PS 1, DOC PS 2 or ANSI/APA PRP 210. Prefinished hardboard paneling shall meet the requirements of CPA/ANSI A135.5. Hardwood plywood shall conform to HPVA HP-1.

2304.8 Floor and roof sheathing.

Structural floor sheathing and structural roof sheathing shall comply with Sections 2304.8.1 and 2304.8.2, respectively.

Table 2304.8(1) Allowable Spans for Lumber Floor and Roof Sheathing

Span (inches) Minimum Net Thickness (inches) of Lumber Placed Perpendicular to supports Diagonally to supports Surfaced dry a Surfaced unseasoned Surfaced dry a Surfaced unseasoned Floors 24 3/4 25/32 3/4 25/32 16 5/8 11/16 5/8 11/16 Roofs 24 5/8 11/16 3/4 25/32

For SI: 1 inch = 25.4 mm.

a. Maximum 19-percent moisture content.

Table 2304.8(2) Sheathing Lumber, Minimum Grade Requirements: Board Grade

Solid Floor or Roof Sheathing Spaced Roof Sheathing Grading Rules Utility Standard NLGA, WCLIB, WWPA 4 common or utility 3 common or standard NLGA, WCLIB, WWPA, NSLB or NELMA No. 3 No. 2 SPIB Merchantable Construction common RIS

Table 2304.8(3) Allowable Spans and Loads for Wood Structural Panel Sheathing and Single-Floor Grades Continuous over Two or More Spans with Strength Axis Perpendicular to Supports a

Sheathing Grades Roof b Floor c Panel span rating roof / floor span Panel thickness (inches) Maximum span (inches) Load d (psf) Maximum span (inches) With edge support e Without edge support Total load Live load 16/0 3/8 16 16 40 30 0 20/0 3/8 20 20 40 30 0 24/0 3/8, 7/16, 1/2 24 20 f 40 30 0 24/16 7/16, 1/2 24 24 50 40 16 32/16 15/32, 1/2, 5/8 32 28 40 30 16 g 40/20 19/32, 5/8, 3/4, 7/8 40 32 40 30 20 g, h 48/24 23/32, 3/4, 7/8 48 36 45 35 24 54/32 7/8, 1 54 40 45 35 32 60/32 7/8, 1 1/8 60 48 45 35 32 Single Floor Grades Roof b Floor c Panel span rating Panel thickness (inches) Maximum span (inches) Load d (psf) Maximum span (inches) With edge support e Without edge support Total load Live load 16 o.c. 1/2, 19/32, 5/8 24 24 50 40 16 g 20 o.c. 19/32, 5/8, 3/4 32 32 40 30 20 g, h 24 o.c. 23/32, 3/4 48 36 35 25 24 32 o.c. 7/8, 1 48 40 50 40 32 48 o.c. 1 3/32, 1 1/8 60 48 50 40 48

For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kN/m 2 .

a. Applies to panels 24 inches or wider.

b. Uniform load deflection limitations 1/180 of span under live load plus dead load, 1/240 under live load only.

c. Panel edges shall have approved tongue-and-groove joints or shall be supported with blocking unless 1/4-inch minimum thickness underlayment or 1 1/2 inches of approved cellular or lightweight concrete is placed over the subfloor, or finish floor is 3/4-inch wood strip. Allowable uniform load based on deflection of 1/360 of span is 100 pounds per square foot except the span rating of 48 inches on center is based on a total load of 65 pounds per square foot.

d. Allowable load at maximum span.

e. Tongue-and-groove edges, panel edge clips (one midway between each support, except two equally spaced between supports 48 inches on center), lumber blocking or other. Only lumber blocking shall satisfy blocked diaphragm requirements.

f. For 1/2-inch panel, maximum span shall be 24 inches.

g. Span is permitted to be 24 inches on center where 3/4-inch wood strip flooring is installed at right angles to joist.

h. Span is permitted to be 24 inches on center for floors where 1 1/2 inches of cellular or lightweight concrete is applied over the panels.

Table 2304.8(4) Allowable Span for Wood Structural Panel Combination Subfloor-Underlayment (Single Floor), a (Panels Continuous Over Two or More Spans and Strength Axis Perpendicular to Supports)

Identification Maximum Spacing of Joists (inches) 16 20 24 32 48 Species group b Thickness (inches) 1 1/2 5/8 3/4 — — 2, 3 5/8 3/4 7/8 — — 4 3/4 7/8 1 — — Single floor span rating c 16 o.c. 20 o.c. 24 o.c. 32 o.c. 48 o.c.

For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kN/m 2 .

a. Spans limited to value shown because of possible effects of concentrated loads. Allowable uniform loads based on deflection of 1/360 of span is 100 pounds per square foot except allowable total uniform load for 1 1/8-inch wood structural panels over joists spaced 48 inches on center is 65 pounds per square foot. Panel edges shall have approved tongue-and-groove joints or shall be supported with blocking, unless 1/4-inch minimum thickness underlayment or 1 1/2 inches of approved cellular or lightweight concrete is placed over the subfloor, or finish floor is 3/4-inch wood strip.

b. Applicable to all grades of sanded exterior-type plywood. See DOC PS 1 for plywood species groups.

c. Applicable to Underlayment grade, C-C (Plugged) plywood, and Single Floor grade wood structural panels.

Table 2304.8(5) Allowable Load (psf) for Wood Structural Panel Roof Sheathing Continuous over Two or More Spans and Strength Axis Parallel to Supports (Plywood Structural Panels Are Five-Ply, Five-Layer Unless Otherwise Noted) a

Panel Grade Thickness (inch) Maximum Span (inches) Load at Maximum Span (psf) Live Total Structural I sheathing 7/16 24 20 30 15/32 24 35 b 45 b 1/2 24 40 b 50 b 19/32, 5/8 24 70 80 23/32, 3/4 24 90 100 Sheathing, other grades covered in DOC PS 1 or DOC PS 2 7/16 16 40 50 15/32 24 20 25 1/2 24 25 30 19/32 24 40 b 50 b 5/8 24 45 b 55 b 23/32, 3/4 24 60 b 65 b

For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kN/m 2 .

a. Uniform load deflection limitations 1/180 of span under live load plus dead load, 1/240 under live load only. Edges shall be blocked with lumber or other approved type of edge supports.

b. For composite and four-ply plywood structural panel, load shall be reduced by 15 pounds per square foot.

2304.8.1 Structural floor sheathing.

Structural floor sheathing shall be designed in accordance with the general provisions of this code.

Floor sheathing conforming to the provisions of Table 2304.8(1), 2304.8(2), 2304.8(3) or 2304.8(4) shall be deemed to meet the requirements of this section.

2304.8.2 Structural roof sheathing.

Structural roof sheathing shall be designed in accordance with the general provisions of this code and the special provisions in this section.

Roof sheathing conforming to the provisions of Table 2304.8(1), 2304.8(2), 2304.8(3) or 2304.8(5) shall be deemed to meet the requirements of this section. Wood structural panel roof sheathing shall be of a type manufactured with exterior glue (Exposure 1 or Exterior).

2304.9 Lumber decking.

Lumber decking shall be designed and installed in accordance with the general provisions of this code and Sections 2304.9.1 through 2304.9.5.3.

2304.9.1 General.

Each piece of lumber decking shall be square-end trimmed. When random lengths are furnished, each piece shall be square-end trimmed across the face so that at least 90 percent of the pieces are within 0.5 degrees (0.00873 rad) of square. The ends of the pieces shall be permitted to be beveled up to 2 degrees (0.0349 rad) from the vertical with the exposed face of the piece slightly longer than the opposite face of the piece. Tongue-and-groove decking shall be installed with the tongues up on sloped or pitched roofs with pattern faces down.

2304.9.2 Layup patterns.

Lumber decking is permitted to be laid up following one of five standard patterns as defined in Sections 2304.9.2.1 through 2304.9.2.5. Other patterns are permitted to be used provided they are substantiated through engineering analysis.

2304.9.2.1 Simple span pattern.

All pieces shall be supported on their ends (i.e., by two supports).

2304.9.2.2 Two-span continuous pattern.

All pieces shall be supported by three supports, and all end joints shall occur in line on alternating supports. Supporting members shall be designed to accommodate the load redistribution caused by this pattern.

2304.9.2.3 Combination simple and two-span continuous pattern.

Courses in end spans shall be alternating simple-span pattern and two-span continuous pattern. End joints shall be staggered in adjacent courses and shall bear on supports.

2304.9.2.4 Cantilevered pieces intermixed pattern.

The decking shall extend across a minimum of three spans. Pieces in each starter course and every third course shall be simple span pattern. Pieces in other courses shall be cantilevered over the supports with end joints at alternating quarter or third points of the spans. Each piece shall bear on at least one support.

2304.9.2.5 Controlled random pattern.

The decking shall extend across a minimum of three spans. End joints of pieces within 6 inches (152 mm) of the end joints of the adjacent pieces in either direction shall be separated by at least two intervening courses. In the end bays, each piece shall bear on at least one support. Where an end joint occurs in an end bay, the next piece in the same course shall continue over the first inner support for at least 24 inches (610 mm). The details of the controlled random pattern shall be as specified for each decking material in Section 2304.9.3.3, 2304.9.4.3 or 2304.9.5.3.

Decking that cantilevers beyond a support for a horizontal distance greater than 18 inches (457 mm), 24 inches (610 mm) or 36 inches (914 mm) for 2-inch (51 mm), 3-inch (76 mm) and 4-inch (102 mm) nominal thickness decking, respectively, shall comply with the following:

1. The maximum cantilevered length shall be 30 percent of the length of the first adjacent interior span;

2. A structural fascia shall be fastened to each decking piece to maintain a continuous, straight line; and

3. There shall be no endjoints in the decking between the cantilevered end of the decking and the centerline of the first adjacent interior span.

2304.9.3 Mechanically laminated decking.

Mechanically laminated decking shall comply with Sections 2304.9.3.1 through 2304.9.3.3.

2304.9.3.1 General.

Mechanically laminated decking consists of square-edged dimension lumber laminations set on edge and mechanically fastened to the adjacent pieces and to the supports.

2304.9.3.2 Nailing and fastening to supports.

Nailing of adjacent laminations and fastening to supports shall conform to the requirements of Section 2304.9.3.2.1 through 2304.9.3.2.2.

2304.9.3.2.1 Two-inch mechanically laminated decking.

For mechanically laminated decking constructed with laminations of 2-inch (51 mm) nominal thickness, nailing and fastening to supports in accordance with Table 2304.9.3.2.1 shall be permitted. Other connections are permitted to be used provided they are reviewed and approved by the registered design professional of record, but shall be spaced at no more than 16 inches (406 mm) on center.

Table 2304.9.3.2.1 Fastening Schedule for Mechanically Laminated Decking Using Laminations of 2-Inch Nominal Thickness

Minimum Nail Size (Length X Diameter) Maximum Spacing Between Face Nails a, b, c (Inches) Number of Toenails Into Supports d Decking Supports £ 48 inches on center Decking Supports > 48 inches on center 4" x 0.192" 30 18 1 4" x 0.162" 24 14 2 4" x 0.148" 22 13 2 3 1/2" x 0.162" 20 12 2 3 1/2" x 0.148" 19 11 2 3 1/2" x 0.135" 17 10 2 3" x 0.148" 11 7 2 3" x 0.128" 9 5 2 2 3/4" x 0.148" 10 6 2 2 3/4" x 0.131" 9 6 3 2 3/4" x 0.120" 8 5 3

For SI: 1 inch = 25.4 mm

a. Nails shall be driven perpendicular to the lamination face, alternating between top and bottom edges.

b. Where nails penetrate through two laminations and into the third, they shall be staggered one-third of the spacing in adjacent laminations. Otherwise, nails shall be staggered one-half of the spacing in adjacent laminations.

c. Two side nails shall be installed at each end of butt-jointed pieces.

d. Where supports are 48 inches (1219 mm) on center or less, alternate laminations shall be toenailed to alternate supports; where supports are spaced more than 48 inches (1219 mm) on center, alternate laminations shall be toenailed to every support.

2304.9.3.2.2 Three- and four-inch mechanically laminated decking.

For mechanically laminated decking constructed with laminations of 3-inch (76 mm) and 4-inch (102 mm) thickness, the length of nails connecting laminations shall not be less than two and one-half times the net thickness of each lamination. Where decking supports are 48 inches (1219 mm) on center or less, side nails shall be installed not more than 30 inches (762 mm) on center alternating between top and bottom edges, and staggered one-third of the spacing in adjacent laminations. Where supports are spaced more than 48 inches (1219 mm) on center, side nails shall be installed not more than 18 inches (457 mm) on center alternating between top and bottom edges and staggered one-third of the spacing in adjacent laminations. Two side nails shall be installed at each end of butt-jointed pieces.

Laminations shall be toenailed to supports with 20d or larger common nails. Where the supports are 48 inches (1219 mm) on center or less, alternate laminations shall be toenailed to alternate supports; where supports are spaced more than 48 inches (1219 mm) on center, alternate laminations shall be toenailed to every support.

Other connections are permitted to be used provided they are reviewed and approved by the registered design professional of record, but shall be spaced at no more than 16 inches (406 mm) on center.

2304.9.3.3 Controlled random pattern.

There shall be a minimum distance of 24 inches (610 mm) between end joints in adjacent courses. The pieces in the first and second courses shall bear on at least two supports with end joints in these two courses occurring on alternate supports. A maximum of seven intervening courses shall be permitted before this pattern is repeated.

2304.9.4 Two-inch sawn tongue-and-groove decking.

Two-inch (51 mm) sawn tongue-and-groove decking shall comply with Sections 2304.9.4.1 through 2304.9.4.3.

2304.9.4.1 General.

Two-inch (51 mm) decking shall have a maximum moisture content of 15 percent when machined and installed. Decking shall be machined with a single tongue-and-groove pattern. Each decking piece shall be nailed to each support.

2304.9.4.2 Nailing.

Each piece of decking shall be toenailed at each support with one 16d common nail through the tongue and face-nailed with one 16d common nail.

2304.9.4.3 Controlled random pattern.

There shall be a minimum distance of 24 inches (610 mm) between end joints in adjacent courses. The pieces in the first and second courses shall bear on at least two supports with end joints in these two courses occurring on alternate supports. A maximum of seven intervening courses shall be permitted before this pattern is repeated.

2304.9.5 Three- and four-inch sawn tongue-and-groove decking.

Three- and four-inch (76 mm and 102 mm) sawn tongue-and-groove decking shall comply with Sections 2304.9.5.1 through 2304.9.5.3.

2304.9.5.1 General.

Three-inch (76 mm) and four-inch (102 mm) decking shall have a maximum moisture content of 19 percent when machined and installed. Decking shall be machined with a double tongue-and-groove pattern. Decking pieces shall be interconnected and nailed to the supports.

2304.9.5.2 Nailing.

Each piece shall be toenailed at each support with one 40d common nail and face-nailed with one 60d common nail. Courses shall be spiked to each other with 8-inch (203 mm) spikes at maximum intervals of 30 inches (762 mm) through predrilled edge holes penetrating to a depth of approximately 4 inches (102 mm). One spike shall be installed at a distance not exceeding 10 inches (254 mm) from the end of each piece.

2304.9.5.3 Controlled random pattern.

There shall be a minimum distance of 48 inches (1219 mm) between end joints in adjacent courses. Pieces not bearing on a support are permitted to be located in interior bays provided the adjacent pieces in the same course continue over the support for at least 24 inches (610 mm). This condition shall not occur more than once in every six courses in each interior bay.

2304.9 Connectors and fasteners.

Connectors and fasteners shall comply with the applicable provisions of Sections 2304.10.1 through 2304.10.8.

2304.10.1 Fastener requirements.

Connections for wood members shall be designed in accordance with the appropriate methodology in Section 2301.2. The number and size of fasteners connecting wood members shall not be less than that set forth in Table 2304.10.1.

Table 2304.10.1 Fastening Schedule

Description of Building Elements Number and Type of Fastener Spacing and Location Roof 1. Blocking between ceiling joists, rafters or trusses to top plate or other framing below 3-8d common (2 1/2" × 0.131"); or 3-10d box (3" × 0.128"); or 3-3" × 0.131" nails; or 3-3" 14 gage staples, 7/16" crown Each end, toenail Blocking between rafters or truss not at the wall top plate, to rafter or truss 2-8d common (2 1/2" × 0.131") 2-3" × 0.131" nails 2-3" 14 gage staples Each end, toenail 2-16 d common (3 1/2" × 0.162") 3-3" × 0.131" nails 3-3" 14 gage staples End nail Flat blocking to truss and web filler 16d common (3 1/2" × 0.162") @ 6" o.c. 3" × 0.131" nails @ 6" o.c. 3" × 14 gage staples @ 6" o.c Face nail 2. Ceiling joists to top plate 3-8d common (2 1/2" × 0.131"); or 3-10d box (3" × 0.128"); or 3-3" × 0.131" nails; or 3-3" 14 gage staples, 7/16" crown Each joist, toenail 3. Ceiling joist not attached to parallel rafter, laps over partitions (no thrust) (see Section 2308.7.3.1, Table 2308.7.3.1) 3-16d common (3 1/2" × 0.162"); or 4-10d box (3" × 0.128"); or 4-3" × 0.131" nails; or 4-3" 14 gage staples, 7/16" crown Face nail 4. Ceiling joist attached to parallel rafter (heel joint) (see Section 2308.7.3.1, Table 2308.7.3.1) Per Table 2308.7.3.1 Face nail 5. Collar tie to rafter 3-10d common (3" × 0.148"); or 4-10d box (3" × 0.128"); or 4-3" × 0.131" nails; or 4-3" 14 gage staples, 7/16" crown Face nail 6. Rafter or roof truss to top plate (See Section 2308.7.5, Table 2308.7.5) 3-10 common (3" × 0.148"); or 3-16d box (3 1/2" × 0.135"); or 4-10d box (3" × 0.128"); or 4-3" × 0.131 nails; or 4-3" 14 gage staples, 7/16" crown Toenail c 7. Roof rafters to ridge valley or hip rafters; or roof rafter to 2-inch ridge beam 2-16d common (3 1/2" × 0.162"); or 3-10d box (3" × 0.128"); or 3-3" × 0.131" nails; or 3-3" 14 gage staples, 7/16" crown; or End nail 3-10d common (3" × 0.148"); or 4-16d box (3 1/2" × 0.135"); or 4-10d box (3" × 0.128"); or 4-3" × 0.131" nails; or 4-3" 14 gage staples, 7/16" crown Toenail Wall 8. Stud to stud (not at braced wall panels) 16d common (3 1/2" × 0.162"); 24" o.c. face nail 10d box (3" × 0.128"); or 3" × 0.131" nails; or 3-3" 14 gage staples, 7/16" crown 16" o.c. face nail 9. Stud to stud and abutting studs at intersecting wall corners (at braced wall panels) 16d common (3 1/2" × 0.162"); or 16" o.c. face nail 16d box (3 1/2" × 0.135"); or 12" o.c. face nail 3" × 0.131" nails; or 3-3" 14 gage staples, 7/16" crown 12" o.c. face nail 10. Built-up header (2" to 2" header) 16d common (3 1/2" × 0.162"); or 16" o.c. each edge, face nail 16d box (3 1/2" × 0.135") 12" o.c. each edge, face nail 11. Continuous header to stud 4-8d common (2 1/2" × 0.131"); or 4-10d box (3" × 0.128") Toenail 12. Top plate to top plate 16d common (3 1/2" × 0.162"); or 16" o.c. face nail 10d box (3" × 0.128"); or 3" × 0.131" nails; or 3" 14 gage staples, 7/16" crown 12" o.c. face nail 13. Top plate to top plate, at end joints 8-16d common (3 1/2" × 0.162"); or 12-10d box (3" × 0.128"); or 12-3" × 0.131" nails; or 12-3" 14 gage staples, 7/16" crown Each side of end joint, face nail (minimum 24" lap splice length each side of end joint) 14. Bottom plate to joist, rim joist, band joist or blocking (not at braced wall panels) 16d common (3 1/2" × 0.162"); or 16" o.c. face nail 16d box (3 1/2" × 0.135"); or 3" × 0.131" nails; or 3" 14 gage staples, 7/16" crown 12" o.c. face nail 15. Bottom plate to joist, rim joist, band joist or blocking at braced wall panels 2-16d common (3 1/2" × 0.162"); or 3-16d box (3 1/2" × 0.135"); or 4-3" × 0.131" nails; or 4-3" 14 gage staples, 7/16" crown 16" o.c. face nail 16. Stud to top or bottom plate 4-8d common (2 1/2" × 0.131"); or 4-10d box (3" × 0.128"); or 4-3" × 0.131" nails; or 4-3" 14 gage staples, 7/16" crown; or Toenail 2-16d common (3 1/2" × 0.162"); or 3-10d box (3" × 0.128"); or 3-3" × 0.131" nails; or 3-3" 14 gage staples, 7/16" crown End nail 17. Top plates, laps at corners and intersections 2-16d common (3 1/2" × 0.162"); or 3-10d box (3" × 0.128"); or 3-3" × 0.131" nails; or 3-3" 14 gage staples, 7/16" crown Face nail 18. 1" brace to each stud and plate 2-8d common (2 1/2" × 0.131"); or 2-10d box (3" × 0.128"); or 2-3" × 0.131" nails; or 2-3" 14 gage staples, 7/16" crown Face nail 19. 1" × 6" sheathing to each bearing 2-8d common (2 1/2" × 0.131"); or 2-10d box (3" × 0.128") Face nail 20. 1" × 8" and wider sheathing to each bearing 3-8d common (2 1/2" × 0.131"); or 3-10d box (3" × 0.128") Face nail Floor 21. Joist to sill, top plate, or girder 3-8d common (2 1/2" × 0.131"); or 3-10d box (3" × 0.128"); or 3-3" × 0.131" nails; or 3-3" 14 gage staples, 7/16" crown Toenail 22. Rim joist, band joist, or blocking to top plate, sill or other framing below 8d common (2 1/2" × 0.131"); or 10d box (3" × 0.128"); or 3" × 0.131" nails; or 3" 14 gage staples, 7/16" crown 6" o.c., toenail 23. 1" × 6" subfloor or less to each joist 2-8d common (2 1/2" × 0.131"); or 2-10d box (3" × 0.128") Face nail 24. 2" subfloor to joist or girder 2-16d common (3 1/2" × 0.162") Face nail 25. 2" planks (plank & beam – floor & roof) 2-16d common (3 1/2" × 0.162") Each bearing, face nail 26. Built-up girders and beams, 2" lumber layers 20d common (4" × 0.192") 32" o.c., face nail at top and bottom staggered on opposite sides 10d box (3" × 0.128"); or 3" × 0.131" nails; or 3" 14 gage staples, 7/16" crown 24" o.c. face nail at top and bottom staggered on opposite sides And: 2-20d common (4" × 0.192"); or 3-10d box (3" × 0.128"); or 3-3" × 0.131" nails; or 3-3" 14 gage staples, 7/16" crown Ends and at each splice, face nail 27. Ledger strip supporting joists or rafters 3-16d common (3 1/2" × 0.162"); or 4-10d box (3" × 0.128"); or 4-3" × 0.131" nails; or 4-3" 14 gage staples, 7/16" crown Each joist or rafter, face nail 28. Joist to band joist or rim joist 3-16d common (3 1/2" × 0.162"); or 4-10d box (3" × 0.128"); or 4-3" × 0.131" nails; or 4-3" 14 gage staples, 7/16" crown End nail 29. Bridging or blocking to joist, rafter or truss 2-8d common (2 1/2" × 0.131"); or 2-10d box (3" × 0.128"); or 2-3" × 0.131" nails; or 2-3" 14 gage staples, 7/16" crown Each end, toenail Wood structural panels (WSP), subfloor, roof and interior wall sheathing to framing and particleboard wall sheathing to framing a Edges (inches) Intermediate supports (inches) 30. 3/8" – 1/2" 6d common or deformed (2" × 0.113") (subfloor and wall) 6 12 8d common or deformed (2 1/2" × 0.113") (roof) or RSRS-01 (2 3/8" x 0.113") nail (roof) d 6 12 2 3/8" × 0.113" nail (subfloor and wall) 6 12 1 3/4" 16 gage staple, 7/16" crown (subfloor and wall) 4 8 2 3/8" × 0.113" nail (roof) 4 8 1 3/4" 16 gage staple, 7/16" crown (roof) 3 6 31. 19/32" – 3/4" 8d common (2 1/2" × 0.131"); or 6d deformed (2" × 0.113") (subfloor and wall) 6 12 8d common or deformed (2 1/2 " × 0.131 " ) or RSRS-01 (2 3/8 " × 0.113 " nail (roof ) d 6 12 2 3/8" × 0.113" nail; or 2" 16 gage staple, 7/16" crown 4 8 32. 7/8" – 1 1/4" 10d common (3" × 0.148"); or 8d deformed (2 1/2" × 0.131") 6 12 Other exterior wall sheathing 33. 1/2" fiberboard sheathing b 1 1/2" galvanized roofing nail (7/16" head diameter); or 1 1/4" 16 gage staple with 7/16" or 1" crown 3 6 34. 25/32" fiberboard sheathing b 1 3/4" galvanized roofing nail (7/16" diameter head); or 1 1/2" 16 gage staple with 7/16" or 1" crown 3 6 Wood structural panels, combination subfloor underlayment to framing 35. 3/4" and less 8d common (2 1/2" × 0.131"); or 6d deformed (2" × 0.113") 6 12 36. 7/8" – 1" 8d common (2 1/2" × 0.131"); or 8d deformed (2 1/2" × 0.131") 6 12 37. 1 1/8" – 1 1/4" 10d common (3" × 0.148"); or 8d deformed (2 1/2" × 0.131") 6 12 Panel siding to framing 38. 1/2" or less 6d corrosion-resistant siding (1 7/8" × 0.106"); or 6d corrosion-resistant casing (2" × 0.099") 6 12 39. 5/8" 8d corrosion-resistant siding (2 3/8" × 0.128"); or 8d corrosion-resistant casing (2 1/2" × 0.113") 6 12 Interior paneling 40. 1/4" 4d casing (1 1/2" × 0.080"); or 4d finish (1 1/2" × 0.072") 6 12 41. 3/8" 6d casing (2" × 0.099"); or 6d finish (Panel supports at 24 inches) 6 12

For SI: 1 inch = 25.4 mm.

a. Nails spaced at 6 inches at intermediate supports where spans are 48 inches or more. For nailing of wood structural panel and particleboard diaphragms and shear walls, refer to Section 2305. Nails for wall sheathing are permitted to be common, box or casing.

b. Spacing shall be 6 inches on center on the edges and 12 inches on center at intermediate supports for nonstructural applications. Panel supports at 16 inches (20 inches if strength axis in the long direction of the panel, unless otherwise marked).

c. Where a rafter is fastened to an adjacent parallel ceiling joist in accordance with this schedule and the ceiling joist is fastened to the top plate in accordance with this schedule, the number of toenails in the rafter shall be permitted to be reduced by one nail.

d. RSRS-01 is a Roof Sheathing Ring Shank nail meeting the specifications of ATSM F 1667.

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

2304.10.2 Sheathing fasteners.

Sheathing nails or other approved sheathing connectors shall be driven so that their head or crown is flush with the surface of the sheathing.

2304.10.3 Joist hangers and framing anchors.

Connections depending on joist hangers or framing anchors, ties and other mechanical fastenings not otherwise covered are permitted where approved. The vertical load-bearing capacity, torsional moment capacity and deflection characteristics of joist hangers shall be determined in accordance with ASTM D 7147.

2304.10.4 Other fasteners.

Clips, staples, glues and other approved methods of fastening are permitted where approved.

2304.10.5 Fasteners and connectors in contact with preservative-treated and fire-retardant-treated wood.

Fasteners, including nuts and washers, and connectors in contact with preservative-treated and fire-retardant-treated wood shall be in accordance with Sections 2304.10.5.1 through 2304.10.5.4. The coating weights for zinc-coated fasteners shall be in accordance with ASTM A 153. Stainless steel driven fasteners shall be in accordance with the material requirements of ASTM F 1667.

2304.10.5.1 Fasteners and connectors for preservative-treated wood.

Fasteners, including nuts and washers, in contact with preservative-treated wood shall be of hot-dipped zinc-coated galvanized steel, stainless steel, silicon bronze or copper. Staples shall be of stainless steel. Fasteners other than nails, staples, timber rivets, wood screws and lag screws shall be permitted to be of mechanically deposited zinc-coated steel with coating weights in accordance with ASTM B 695, Class 55 minimum. Connectors that are used in exterior applications and in contact with preservative-treated wood shall have coating types and weights in accordance with the treated wood or connector manufacturer's recommendations. In the absence of manufacturer's recommendations, a minimum of ASTM A 653, Type G185 zinc-coated galvanized steel, or equivalent, shall be used.

Exception: Plain carbon steel fasteners, including nuts and washers, in SBX/DOT and zinc borate preservative-treated wood in an interior, dry environment shall be permitted.

2304.10.5.2 Fastenings for wood foundations.

Fastenings, including nuts and washers, for wood foundations shall be as required in AWC PWF

2304.10.5.3 Fasteners for fire-retardant-treated wood used in exterior applications or wet or damp locations.

Fasteners, including nuts and washers, for fire-retardant-treated wood used in exterior applications or wet or damp locations shall be of hot-dipped zinc-coated galvanized steel, stainless steel, silicon bronze or copper. Staples shall be of stainless steel. Fasteners other than nails, staples, timber rivets, wood screws and lag screws shall be permitted to be of mechanically deposited zinc-coated steel with coating weights in accordance with ASTM B 695, Class 55 minimum.

2304.10.5.4 Fasteners for fire-retardant-treated wood used in interior applications.

Fasteners, including nuts and washers, for fire-retardant-treated wood used in interior locations shall be in accordance with the manufacturer's recommendations. In the absence of manufacturer's recommendations, Section 2304.10.5.3 shall apply.

2304.10.6 Load path.

Where wall framing members are not continuous from the foundation sill to the roof, the members shall be secured to ensure a continuous load path. Where required, sheet metal clamps, ties or clips shall be formed of galvanized steel or other approved corrosion-resistant material not less than 0.0329-inch (0.836 mm) base metal thickness.

2304.10.7 Framing requirements.

Wood columns and posts shall be framed to provide full end bearing. Alternatively, column-and-post end connections shall be designed to resist the full compressive loads, neglecting end-bearing capacity. Column-and-post end connections shall be fastened to resist lateral and net induced uplift forces.

2304.10.8 Connection fire resistance rating.

Wood structural connections, including connectors, fasteners, and portions of wood members included in the connection design, shall be protected from fire exposure for the required fire resistance time. For connections in Type IV construction, the required fire resistance time shall be at minimum one hour or as required for the building element by Table 601 and Section 602.4. Fire resistance ratings for connections shall be determined by one of the following:

1. Testing in accordance with Section 703.2 where the connection is part of the fire resistance test.

2. Engineering analysis that demonstrates that the temperature rise at any portion of the connection is limited to an average temperature rise of 250°F (139°C), and a maximum temperature rise of 325°F (181°C), for a time corresponding to the required fire resistance rating of the structural element being connected. For the purposes of this analysis, the connection includes connectors, fasteners, and portions of wood members included in the structural design of the connection.

2304.11 Heavy timber construction.

Where a structure, portion thereof or individual structural elements are required by other provisions of this code to be of heavy timber, the building elements therein shall comply with the applicable provisions of Sections 2304.11.1 through 2304.11.4. Minimum dimensions of heavy timber shall comply with the applicable requirements in Table 2304.11 based on roofs or floors supported and the configuration of each structural element, or the applicable requirements in Sections 2304.11.2 through 2304.11.4. Lumber decking shall be in accordance with Section 2304.9.

Table 2304.11 Minimum Dimensions of Heavy Timber Structural Members

Supporting Heavy Timber Structural Elements Minimum Nominal Solid Sawn Size Minimum Glued Laminated Net Size Minimum Structural Composite Lumber Net Size Width, Inch Depth, Inch Width, Inch Depth, Inch Width, Inch Depth, Inch Floor loads only or combined floor and roof loads Columns; Framed sawn or glued-laminated timber arches that spring from the floor line; Framed timber trusses 8 8 6 3/4 8 1/4 7 7 1/2 Roof loads only Wood beams and girders 6 10 5 10 1/2 5 1/4 9 1/2 Columns (roof and ceiling loads); Lower half of: wood-frame or glued-laminated arches that spring from the floor line or from grade 6 8 5 8 1/4 5 1/4 7 1/2 Upper half of: wood-frame or glued-laminated arches that spring from the floor line or from grade 6 6 5 6 5 1/4 5 1/2 Framed timber trusses and other roof framing a ; Framed or glued-laminated arches that spring from the top of walls or wall abutments 4 b 6 3 b 3 1/2 b 5 1/2

For SI: 1 inch = 25.4 mm.

a. Spaced members shall be permitted to be composed of two or more pieces not less than 3 inches nominal in thickness where blocked solidly throughout their intervening spaces or where spaces are tightly closed by a continuous wood cover plate of note less than 2 inches nominal in thickness secured to the underside of the members. Splice plates shall be not less than 3 inches nominal in thickness.

b. Where protected by approved automatic sprinklers under the roof deck, framing members shall be not less than 3 inches nominal in width.

2304.11.1 Details of heavy timber structural members.

Heavy timber structural members shall be detailed and constructed in accordance with Sections 2304.11.1 through 2304.11.1.4.

2304.11.1.1 Columns.

Minimum dimensions of columns shall be in accordance with Table 2304.11. Columns shall be continuous or superimposed throughout all stories and connected in an approved manner. Girders and beams at column connections shall be closely fitted around columns and adjoining ends shall be cross tied to each other, or intertied by caps or ties, to transfer horizontal loads across joints. Wood bolsters shall not be placed on tops of columns unless the columns support roof loads only. Where traditional heavy timber detailing is used, connections shall be by means of reinforced concrete or metal caps with brackets, by properly designed steel or iron caps, with pintles and base plates, by timber splice plates affixed to the columns by metal connectors housed within the contact faces, or by other approved methods.

2304.11.1.2 Floor framing.

Minimum dimensions of floor framing shall be in accordance with Table 2304.11. Approved wall plate boxes or hangers shall be provided where wood beams, girders or trusses rest on masonry or concrete walls. Where intermediate beams are used to support a floor, they shall rest on top of girders, or shall be supported by an approved metal hanger into which the ends of the beams shall be closely fitted. Where traditional heavy timber detailing is used, these connections shall be permitted to be supported by ledgers or blocks securely fastened to the sides of the girders.

2304.11.1.3 Roof framing.

Minimum dimensions of roof framing shall be in accordance with Table 2304.11. Every roof girder and not less than every alternate roof beam shall be anchored to its supporting member to resist forces as required in Chapter 16.

2304.11.1.4 Cross-laminated timber.

Cross-laminated timber shall be used only when engineered by a registered design professional. The design shall take into account the effects of openings cut into the panels. Cross-laminated timber shall not be used as individual columns or beams.

2304.11.2 Partitions and walls.

Partitions and walls shall comply with Section 2304.11.2.1 or 2304.11.2.2.

2304.11.2.1 Exterior walls.

Exterior walls shall be of noncombustible materials or other materials as permitted by Section 602.4.

2304.11.2.2 Interior walls and partitions.

Interior walls and partitions shall be of solid wood construction formed by not less than two layers of 1-inch (25 mm) matched boards or laminated construction 4 inches (102 mm) thick, or of 1-hour fire-resistance-rated construction.

2304.11.3 Floors.

Floors shall be without concealed spaces. Wood floors shall be constructed in accordance with Section 2304.11.3.1 or 2304.11.3.2.

2304.11.3.1 Cross-laminated timber floors.

Cross-laminated timber shall be not less than 4 inches (102 mm) in actual thickness. Cross-laminated timber shall be continuous from support to support and mechanically fastened to one another. Cross-laminated timber shall be permitted to be connected to walls without a shrinkage gap providing swelling or shrinking is considered in the design. Corbelling of masonry walls under the floor shall be permitted to be used.

2304.11.3.2 Sawn or glued-laminated plank floors.

Sawn or glued-laminated plank floors shall be one of the following:

1. Sawn or glued-laminated planks, splined or tongue-and-groove, of not less than 3 inches (76 mm) nominal in thickness covered with 1-inch (25 mm) nominal dimension tongue-and-groove flooring, laid crosswise or diagonally, 15/32-inch (12 mm) wood structural panel or 1/2-inch (12.7 mm) particleboard.

2. Planks not less than 4 inches (102 mm) nominal in width set on edge close together and well spiked and covered with 1-inch (25 mm) nominal dimension flooring or 15/32-inch (12 mm) wood structural panel or 1/2-inch (12.7 mm) particleboard.

The lumber shall be laid so that continuous lines of joints will occur only at points of support. Floors shall not extend closer than 1/2 inch (12.7 mm) to walls. Such 1/2-inch (12.7 mm) space shall be covered by a molding fastened to the wall and so arranged that it will not obstruct the swelling or shrinkage movements of the floor. Corbelling of masonry walls under the floor shall be permitted to be used in place of molding.

2304.11.4 Roof decks.

Roofs shall be without concealed spaces and roof decks shall be constructed in accordance with Section 2304.11.4.1 or 2304.11.4.2. Other types of decking shall be an alternative that provides equivalent fire resistance and structural properties. Where supported by a wall, roof decks shall be anchored to walls to resist forces determined in accordance with Chapter 16. Such anchors shall consist of steel bolts, lags, screws or approved hardware of sufficient strength to resist prescribed forces.

2304.11.4.1 Cross-laminated timber roofs.

Cross-laminated timber roofs shall be not less than 3 inches (76 mm) nominal in thickness and shall be continuous from support to support and mechanically fastened to one another.

2304.11.4.2 Sawn, wood structural panel, or glued-laminated plank roofs.

Sawn, wood structural panel, or glued-laminated plank roofs shall be one of the following:

1. Sawn or glued laminated, splined or tongue-and-groove plank, not less than 2 inches (51 mm) nominal in thickness.

2. 1 1/8-inch-thick (32 mm) wood structural panel (exterior glue).

3. Planks not less than 3 inches (76 mm) nominal in width, set on edge close together and laid as required for floors.

2304.12 Protection against decay and termites.

Wood shall be protected from decay and termites in accordance with the applicable provisions of Sections 2304.12.1 through 2304.12.8.

2304.12.1 Locations requiring water-borne preservatives or naturally durable wood.

Wood used above ground in the locations specified in Sections 2304.12.1.1 through 2304.12.1.5, 2304.12.3 and 2304.12.5 shall be naturally durable wood or preservative-treated wood using water-borne preservatives, in accordance with AWPA U1 for above-ground use.

2304.12.1.1 Joists, girders and subfloor.

Wood joists or wood structural floors that are closer than 18 inches (457 mm) or wood girders that are closer than 12 inches (305 mm) to the exposed ground in crawl spaces or unexcavated areas located within the perimeter of the building foundation shall be of naturally durable or preservative-treated wood.

2304.12.1.2 Wood supported by exterior foundation walls.

Wood framing members, including wood sheathing, that are in contact with exterior foundation walls and are less than 8 inches (203 mm) from exposed earth shall be of naturally durable or preservative-treated wood.

2304.12.1.3 Exterior walls below grade.

Wood framing members and furring strips in direct contact with the interior of exterior masonry or concrete walls below grade shall be of naturally durable or preservative-treated wood.

2304.12.1.4 Sleepers and sills.

Sleepers and sills on a concrete or masonry slab that is in direct contact with earth shall be of naturally durable or preservative-treated wood.

2304.12.1.5 Wood siding.

Clearance between wood siding and earth on the exterior of a building shall not be less than 8 inches (203 mm) or less than 2 inches (51 mm) vertical from covered concrete steps, porch slabs, patio slabs and similar horizontal surfaces exposed to the weather except where siding, sheathing and wall framing are of naturally durable or preservative-treated wood.

2304.12.2 Other locations.

Wood used in the locations specified in Sections 2304.12.2.1 through 2304.12.2.5 shall be naturally durable wood or preservative-treated wood in accordance with AWPA U1. Preservative-treated wood used in interior locations shall be protected with two coats of urethane, shellac, latex epoxy or varnish unless water-borne preservatives are used. Prior to application of the protective finish, the wood shall be dried in accordance with the manufacturer's recommendations.

2304.12.2.1 Girder ends.

The ends of wood girders entering exterior masonry or concrete walls shall be provided with a 1/2-inch (12.7 mm) airspace on top, sides and end, unless naturally durable or preservative-treated wood is used.

2304.12.2.2 Posts or columns.

Posts or columns supporting permanent structures and supported by a concrete or masonry slab or footing that is in direct contact with the earth shall be of naturally durable or preservative-treated wood.

Exception: Posts or columns that meet all of the following:

1. Are not exposed to the weather, or are protected by a roof, eave, overhang, or other covering if exposed to the weather.

2. Are supported by concrete piers or metal pedestals projected not less than 1 inch (25 mm) above the slab or deck and are separated from the concrete pier by an impervious moisture barrier.

3. Are located not less than 8 inches (203 mm) above exposed earth.

2304.12.2.3 Supporting member for permanent appurtenances.

Naturally durable or preservative-treated wood shall be utilized for those portions of wood members that form the structural supports of buildings, balconies, porches or similar permanent building appurtenances where such members are exposed to the weather without adequate protection from a roof, eave, overhang or other covering to prevent moisture or water accumulation on the surface or at joints between members.

2304.12.2.4 Laminated timbers.

The portions of glued-laminated timbers that form the structural supports of a building or other structure and are exposed to weather and not fully protected from moisture by a roof, eave or similar covering shall be pressure treated with preservative or be manufactured from naturally durable or preservative-treated wood.

2304.12.2.5 Supporting members for permeable floors and roofs.

Wood structural members that support moisture-permeable floors or roofs that are exposed to the weather, such as concrete or masonry slabs, shall be of naturally durable or preservative-treated wood unless separated from such floors or roofs by an impervious moisture barrier. The impervious moisture barrier system protecting the structure supporting floors shall provide positive drainage of water that infiltrates the moisture-permeable floor topping.

2304.12.2.6 Ventilation beneath balcony or elevated walking surfaces.

Enclosed framing in exterior balconies and elevated walking surfaces that are exposed to rain, snow or drainage from irrigation shall be provided with openings that provide a net free cross-ventilation area not less than 1/150 of the area of each separate space.

2304.12.3 Wood in contact with the ground or fresh water.

Wood used in contact with exposed earth shall be naturally durable for both decay and termite resistance or preservative treated in accordance with AWPA U1 for soil or fresh water use.

Exception: Untreated wood is permitted where such wood is continuously and entirely below the ground-water level or submerged in fresh water.

2304.12.3.1 Posts or columns.

Posts and columns that are supporting permanent structures and embedded in concrete that is exposed to the weather or in direct contact with the earth shall be of preservative-treated wood.

2304.12.4 Termite protection.

In geographical areas where hazard of termite damage is known to be very heavy, wood floor framing in the locations specified in Section 2304.12.1 and 2304.12.2 and exposed framing of exterior decks or balconies shall be of naturally durable species (termite resistant) or preservative treated in accordance with AWPA U1 for the species, product preservative and end use or provided with approved methods of termite protection.

2304.12.5 Wood used in retaining walls and cribs.

Wood installed in retaining or crib walls shall be preservative treated in accordance with AWPA U1 for soil and fresh water use.

2304.12.6 Attic ventilation.

For attic ventilation, see Section 1203.2.

2304.12.7 Under-floor ventilation (crawl space).

For under-floor ventilation (crawl space), see Section 1203.4.

2304.12.8 Debris.

All loose wood and debris and all wood forms shall be removed from spaces under the building. All stump and roots shall be grubbed to a minimum depth of 12 inches (305 mm).

2304.13 Long-term loading.

Wood members supporting concrete, masonry or similar materials shall be checked for the effects of long-term loading using the provisions of the ANSI/AWC NDS. The total deflection, including the effects of long-term loading, shall be limited in accordance with Section 1604.3.1 for these supported materials.

Exception: Horizontal wood members supporting masonry or concrete nonstructural floor or roof surfacing not more than 4 inches (102 mm) thick need not be checked for long-term loading.

Section BC 2305. General Design Requirements for Lateral Force-Resisting Systems

Open this section

This section has 4 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read Section BC 2305 at American Legal Publishing.

2305.1 General.

Structures using wood-frame shear walls or wood-frame diaphragms to resist wind, seismic or other lateral loads shall be designed and constructed in accordance with AWC SDPWS and the applicable provisions of Sections 2305, 2306 and 2307.

2305.1.1 Openings in shear panels.

Openings in shear panels that materially affect their strength shall be detailed on the plans and shall have their edges adequately reinforced to transfer all shearing stresses.

2305.2 Diaphragm deflection.

The deflection of wood-frame diaphragms shall be determined in accordance with AWC SDPWS. The deflection (D dia ) of a blocked wood structural panel diaphragm uniformly fastened throughout with staples is permitted to be calculated in accordance with Equation 23-1. If not uniformly fastened, the constant 0.188 (For SI: 1/1627) in the third term shall be modified by an approved method.

(Equation 23-1)

where:

A = Area of chord cross section, in square inches (mm 2 ).

E = Modulus of elasticity of diaphragm chords, in pounds per square inch (N/mm 2 ).

e n = Staple slip, in inches (mm) (See Table 2305.2(1)).

Gt = Panel rigidity through the thickness, in pounds per inch (N/mm) of panel width of or depth (See Table 2305.2(2)).

L = Diaphragm length (dimension perpendicular to the direction of the applied load), in feet (mm).

v = Induced unit shear in pounds per linear foot (plf) (N/mm).

W = Diaphragm width (in the direction of applied force, in feet (mm)).

x = Distance from chord splice to nearest support, in feet (mm).

D c = Diaphragm chord splice slip at the induced unit shear, in inches (mm).

D dia = Maximum mid-span diaphragm deflection determined by elastic analysis, in inches (mm).

Table 2305.2(1) e n Values (inches) for Use in Calculating Diaphragm and Shear Wall Deflection Due to Fastener Slip (Structural I) a, c

Load Per Fastener b (pounds) Fastener Designations 14-Ga staple × 2 inches long 60 0.011 80 0.018 100 0.028 120 0.04 140 0.053 160 0.068

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 4.448 N.

a. Increase e n values 20 percent for plywood grades other than Structural I.

b. Load per fastener = maximum shear per foot divided by the member of fasteners per foot at interior panel edges.

c. Decrease e n values 50 percent for seasoned lumber (moisture contest < 19 percents.

Table 2305.2(2) Values of Gt for Use in Calculating Deflection of Wood Structural Panel Shear Walls and Diaphragms

Panel Type Span Rating Values of Gt (lb/in. panel depth or width) Structural Sheathing Structural I Plywood Plywood 3-ply 4-ply 5-ply a OSB 3-ply 4-ply 5-ply a OSB Sheathing 24/0 25,000 32,500 37,500 77,500 32,500 42,500 41,500 77,500 24/16 27,000 35,000 40,500 83,500 35,000 45,500 44,500 83,500 32/16 27,000 35,000 40,500 83,500 35,000 45,500 44,500 83,500 40/20 28,500 37,000 43,000 88,500 37,000 48,000 47,500 88,500 48/24 31,000 40,500 46,500 96,000 40,500 52,500 51,000 96,000 Single Floor 16 o.c. 27,000 35,000 40,500 83,500 35,000 45,500 44,500 83,500 20 o.c. 28,000 36,500 42,000 87,000 36,500 47,500 46,000 87,000 24 o.c. 30,000 39,000 45,000 93,000 39,000 50,500 49,500 93,000 32 o.c. 36,000 47,000 54,000 110,000 47,000 61,000 59,500 110,000 48 o.c. 50,500 65,500 76,000 155,000 65,500 85,000 83,500 155,000

Structural Sheathing Structural I Thickness (in.) A-A, A-C Marine All Other Grades A-A, A-C Marine All Other Grades Sanded Plywood 1/4 24,000 31,000 24,000 31,000 31,000 31,000 11/32 25,500 33,000 25,500 33,000 33,000 33,000 3/8 26,000 34,000 26,000 34,000 34,000 34,000 15/32 38,000 49,500 38,000 49,500 49,500 49,500 1/2 38,500 50,000 38,500 50,000 50,000 50,000 19/32 49,000 63,500 49,000 63,500 63,500 63,500 5/8 49,500 64,500 49,500 64,500 64,500 64,500 23/32 50,500 65,500 50,500 65,500 65,500 65,500 3/4 51,000 66,500 51,000 66,500 66,500 66,500 7/8 52,500 68,500 52,500 68,500 68,500 68,500 1 73,500 95,500 73,500 95,500 95,500 95,500 1 1/8 75,000 97,500 75,000 97,500 97,500 97,500

For SI: 1 inch = 25.4 mm, 1 pound/inch = 0.1751 N/mm.

a. 5-ply applies to plywood with five or more layers; for five-ply plywood with three layers, use values for four ply.

2305.3 Shear wall deflection.

The deflection of wood-frame shear walls shall be determined in accordance with AWC SDPWS. The deflection (D sw ) of a blocked wood structural panel shear wall uniformly fastened throughout with staples is permitted to be calculated in accordance with Equation 23-2.

(Equation 23-2)

where:

A = Area of end-post cross section in square inches (mm 2 ).

b Shear wall length, in feet (mm).

d a = Total vertical elongation of wall anchorage system (including fastener slip, device elongation, rod elongation) at the induced unit shear in the shear wall (v).

E = Modulus of elasticity of end posts, in pounds per square inch (N/mm 2 ).

e n = Staple slip, in inches (mm) (See Table 2305.2(1)).

Gt = Panel rigidity through the thickness, in pounds per inch (N/mm) of panel width or depth (See Table 2305.2(2)).

h = Shear wall height, in feet (mm).

v = Induced unit shear, in pounds per linear foot (plf) (N/mm).

D sw = Maximum shear wall deflection determined by elastic analysis, in inches (mm).

Section BC 2306. Allowable Stress Design

Open this section

This section has 16 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read Section BC 2306 at American Legal Publishing.

2306.1 Allowable stress design.

The design and construction of wood elements in structures using allowable design methods shall be in accordance with the following applicable standards:

American Wood Council.

ANSI/AWC NDS National Design Specification for Wood Construction

ANSI/AWC SDPWS Special Design Provisions for Wind and Seismic

American Society of Agricultural and Biological Engineers.

ASABE EP 484.3 Diaphragm Design of Metal-clad, Wood-frame Rectangular Buildings

ASABE EP 486.2 Shallow Post Foundation Design

ASABE EP 559.1 Design Requirements and Bending Properties for Mechanically Laminated Wood Assemblies

APA – The Engineered Wood Association.

ANSI 117 Standard Specifications for Structural Glued Laminated Timber of Softwood Species

ANSI A190.1 Structural Glued Laminated Timber

Panel Design Specification

Plywood Design Specification Supplement 1 - Design & Fabrication of Plywood Curved Panel

Plywood Design Specification Supplement 2 - Design & Fabrication of Glued Plywood-lumber Beams

Plywood Design Specification Supplement 3 - Design & Fabrication of Plywood Stressed-skin Panels

Plywood Design Specification Supplement 4 - Design & Fabrication of Plywood Sandwich Panels

Plywood Design Specification Supplement 5 - Design & Fabrication of All-plywood Beams

APA T300 Glulam Connection Details

APA S560 Field Notching and Drilling of Glued Laminated Timber Beams

APA S475 Glued Laminated Beam Design Tables

APA X440 Product and Application Guide: Glulam

APA R540 Builders Tips: Proper Storage and Handling of Glulam Beams

Truss Plate Institute, Inc.

TPI 1 National Design Standard for Metal Plate Connected Wood Truss Construction

West Coast Lumber Inspection Bureau

AITC 104 Typical Construction Details

AITC 110 Standard Appearance Grades for Structural Glued Laminated Timber

AITC 113 Standard for Dimensions of Structural Glued Laminated Timber

AITC 119 Standard Specifications for Structural Glued Laminated Timber of Hardwood Species

AITC 200 Inspection Manual

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

2306.1.1 Joists and rafters.

The design of rafter spans is permitted to be in accordance with the AWC STJR.

2306.1.2 Plank and beam flooring.

The design of plank and beam flooring is permitted to be in accordance with the AWC Wood Construction Data No. 4.

2306.1.3 Treated wood stress adjustments.

The allowable unit stresses for preservative-treated wood shall be adjusted for treatment in accordance with the ANSI/AWC NDS.

The allowable unit stresses for fire-retardant-treated wood, including fastener values, shall be developed from an approved method of investigation that considers the effects of anticipated temperature and humidity to which the fire-retardant-treated wood will be subjected, the type of treatment and the redrying process. Other adjustments are applicable except that the impact load duration shall not apply.

2306.1.4 Lumber decking.

The capacity of lumber decking arranged according to the patterns described in Section 2304.9.2 shall be the lesser of the capacities determined for flexure and deflection according to the formulas in Table 2306.1.4.

Table 2306.1.4 Allowable Loads for Lumber Decking

Pattern Allowable Area Load a, b Flexure Deflection Simple span Two-span continuous Combination simple- and two-span continuous Cantilevered pieces intermixed Controlled random layup Mechanically laminated decking 2-inch decking 3-inch and 4-inch decking

For SI: 1 inch = 25.4 mm.

a. s b = Allowable total uniform load limited by bending.

s D = Allowable total uniform load limited by deflection.

b. d = Actual decking thickness.

L = Span of decking.

F' b = Allowable bending stress adjusted by applicable factors.

E' = Modulus of elasticity adjusted by applicable factors.

2306.2 Wood-frame diaphragms.

Wood-frame diaphragms shall be designed and constructed in accordance with AWC SDPWS. Where panels are fastened to framing members with staples, requirements and limitations of AWC SDPWS shall be met and the allowable shear values set forth in Table 2306.2(1) or 2306.2(2) shall be permitted. The allowable shear values in Tables 2306.2(1) and 2306.2(2) are permitted to be increased 40 percent for wind design.

Table 2306.2(1) Allowable Shear Values (Pounds per Foot) for Wood Structural Panel Diaphragms Utilizing Staples with Framing of Douglas Fir-Larch, or Southern Pine a for Wind or Seismic Loading f

Panel Grade Staple Length and Gaged Minimum Fastener Penetration in Framing (inches) Minimum Nominal Panel Thickness (inch) Minimum Nominal Width of Framing Members at Adjoining Panel Edges and Boundaries e (inches) Blocked Diaphragms Unblocked Diaphragms Fastener spacing (inches) at diaphragm boundaries (all cases) at continuous panel edges parallel to load (Cases 3,4), and at all panel edges (Cases 5,6) b Fasteners spaced 6 max. at supported edges b 6 4 2 1/2 c 2 c Case 1 (No unblocked edges or continuous joints parallel to load) All other configurations (Cases 2, 3, 4, 5 and 6) Fastener spacing (inches) at other panel edges (Cases 1, 2, 3 and 4) b 6 6 4 3 Structural I grades 1 1/2 16 Gage 1 3/8 2 175 235 350 400 155 115 3 200 265 395 450 175 130 15/32 2 175 235 350 400 155 120 3 200 265 395 450 175 130 Sheathing, single floor and other grades covered in DOC PS 1 and PS 2 1 1/2 16 Gage 1 3/8 2 160 210 315 360 140 105 3 180 235 355 400 160 120 7/16 2 165 225 335 380 150 110 3 190 250 375 435 165 125 15/32 2 160 210 315 360 140 105 3 180 235 355 405 160 120 19/32 2 175 235 350 400 155 115 3 200 265 395 450 175 130

For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.5939 N/m.

a. For framing of other species: (1) Find specific gravity for species of lumber in ANSI/AWC NDS. (2) For staples, find shear value from table above for Structural I panels (regardless of actual grade) and multiply value by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species.

b. Space fasteners maximum 12 inches on center along intermediate framing members (6 inches on center where supports are spaced 48 inches on center).

c. Framing at adjoining panel edges shall be 3 inches nominal or wider.

d. Staples shall have a minimum crown width of 7/16 inch and shall be installed with their crowns parallel to the long dimension of the framing members.

e. The minimum nominal width of framing members not located at boundaries or adjoining panel edges shall be 2 inches.

f. For shear loads of normal or permanent load duration as defined by the ANSI/AWC NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively.

Table 2306.2(2) Allowable Shear Values (pounds per foot) for Wood Structural Panel Blocked Diaphragms Utilizing Multiple Rows of Staples (High-Load Diaphragms) with Framing of Douglas Fir-Larch or Southern Pine a for Wind or Seismic Loading b, g, h

Panel Grade Staple Gage f Minimum Fastener Penetration in Framing (inches) Minimum Nominal Panel Thickness (inch) Minimum Nominal Width of Framing Members at Adjoining Panel Edges and Boundaries e Lines of Fasteners Blocked Diaphragms Cases 1 and 2 d Fastener Spacing Per Line at Boundaries (inches) 4 2 1/2 2 Fastener Spacing Per Line at Other Panel Edges (inches) 6 4 4 3 3 2 Structural I grades 14 Gage Staples 2 15/32 3 2 600 600 860 960 1,060 1,200 4 3 860 900 1,160 1,295 1,295 1,400 19/32 3 2 600 600 875 960 1,075 1,200 4 3 875 900 1,175 1,440 1,475 1,795 Sheathing, single floor and other grades covered in DOC PS 1 and PS 2 14 Gage Staples 2 15/32 3 2 540 540 735 865 915 1,080 4 3 735 810 1,005 1,105 1,105 1,195 19/32 3 2 600 600 865 960 1,065 1,200 4 3 865 900 1,130 1,430 1,370 1,485 23/32 4 3 865 900 1,130 1,490 1,430 1,545

For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.5939 N/m.

a. For framing of other species: (1) Find specific gravity for species of framing lumber in ANSI/AWC NDS. (2) For staples, find shear value from table above for Structural I panels (regardless of actual grade) and multiply value by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species.

b. Fastening along intermediate framing members: Space fasteners not greater than 12 inches on center, except 6 inches on center for spans greater than 32 inches.

c. Panels conforming to PS 1 or PS 2.

d. This table gives shear values for Cases 1 and 2 as shown in Table 2306.2(1). The values shown are applicable to Cases 3, 4, 5 and 6 as shown in Table 2306.2(1), providing fasteners at all continuous panel edges are spaced in accordance with the boundary fastener spacing.

e. The minimum nominal depth of framing members shall be 3 inches nominal. The minimum nominal width of framing members not located at boundaries or adjoining panel edges shall be 2 inches.

f. Staples shall have a minimum crown width of 7/16 inch, and shall be installed with their crowns parallel to the long dimension of the framing members.

g. High-load diaphragms shall be subject to special inspection in accordance with Section 1705.5.1.

h. For shear loads of normal or permanent load duration as defined by the ANSI/AWC NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively.

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

2306.2.1 Gypsum board diaphragm ceilings.

Gypsum board diaphragm ceilings shall be in accordance with Section 2508.5.

2306.3 Wood-frame shear walls.

Wood-frame shear walls shall be designed and constructed in accordance with AWC SDPWS. Where panels are fastened to framing members with staples, requirements and limitations of AWC SDPWS shall be met and the allowable shear values set forth in Table 2306.3(1), 2306.3(2) or 2306.3(3) shall be permitted. The allowable shear values in Tables 2306.3(1) and 2306.3(2) are permitted to be increased 40 percent for wind design. Panels complying with ANSI/APA PRP-210 shall be permitted to use design values for Plywood Siding in the AWC SDPWS.

Table 2306.3(1) Allowable Shear Values (pounds per foot) for Wood Structural Panel Shear Walls Utilizing Staples with Framing of Douglas Fir-Larch or Southern Pine a for Wind or Seismic Loading b, f, g, i

Panel Grade Minimum Nominal Panel Thickness (inch) Minimum Fastener Penetration in Framing (inches) Panels Applied Direct to Framing Panels Applied over 1/2" or 5/8" Gypsum Sheathing Staple length and gage (inches) h Fastener spacing at panel edges (inches) Staple length and gage (inches) h Fastener spacing at panel edges (inches) 6 4 3 2 d 6 4 3 2 d Structural I grades 3/8 1 1 1/2 16 Gage 155 235 315 400 2 16 Gage 155 235 310 400 7/16 170 260 345 440 155 235 310 400 15/32 185 280 375 475 155 235 300 400 Sheathing, plywood siding e except Group 5 Species 5/16 c or 1/4 c 1 1 1/2 16 Gage 145 220 295 375 2 16 Gage 110 165 220 285 3/8 140 210 280 360 140 210 280 360 7/16 155 230 310 395 140 210 280 360 15/32 170 255 335 430 140 210 280 360 19/32 1 3/4 16 Gage 185 280 375 475 – – – – –

For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.5939 N/m.

a. For framing of other species: (1) Find specific gravity for species of lumber in ANSI/AWC NDS. (2) For staples, find shear value from table above for Structural I panels (regardless of actual grade) and multiply value by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species.

b. Panel edges backed with 2-inch nominal or wider framing. Install panels either horizontally or vertically. Space fasteners maximum 6 inches on center along intermediate framing members for 3/8-inch and 7/16-inch panels installed on studs spaced 24 inches on center. For other conditions and panel thickness, space fasteners maximum 12 inches on center on intermediate supports.

c. 3/8-inch panel thickness or siding with a span rating of 16 inches on center is the minimum recommended where applied directly to framing as exterior siding. For grooved panel siding, the nominal panel thickness is the thickness of the panel measured at the point of fastening.

d. Framing at adjoining panel edges shall be 3 inches nominal or wider.

e. Values apply to all-veneer plywood. Thickness at point of fastening on panel edges governs shear values.

f. Where panels are applied on both faces of a wall and fastener spacing is less than 6 inches on center on either side, panel joints shall be offset to fall on different framing members, or framing shall be 3 inches nominal or thicker at adjoining panel edges.

g. In Seismic Design Category D where shear design values exceed 350 pounds per linear foot, all framing members receiving edge fastening from abutting panels shall be not less than a single 3-inch nominal member, or two 2-inch nominal members fastened together in accordance with Section 2306.1 to transfer the design shear value between framing members. Wood structural panel joint and sill plate nailing shall be staggered at all panel edges. See AWC SDPWS for sill plate size and anchorage requirements.

h. Staples shall have a minimum crown width of 7/16-inch and shall be installed with their crowns parallel to the long dimension of the framing members.

i. For shear loads of normal or permanent load duration as defined by the ANSI/AWC NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively.

Table 2306.3(2) Allowable Shear Values (Plf) for Wind or Seismic Loading on Shear Walls of Fiberboard Sheathing Board Construction Utilizing Staples for Type V Construction Only a, b, c, d, e

Thickness and Grade (inches) Staple Gage and Dimensions Allowable Shear Value (pounds per linear foot) Staple Spacing at Panel Edges (inches) a 4 3 2 1/2" or 25/32" Structural No. 16 gage galvanized staple, 7/16 inch crown 1 3/4 inch long 150 200 225 No. 16 gage galvanized staple, 1 inch crown 1 3/4 inch long 220 290 325

For SI: 1 inch = 25.4 mm, 1 pound per linear foot = 14.5939 N/m.

a. Fiberboard sheathing shall not be used to brace concrete or masonry walls.

b. Panel edges shall be backed with 2-inch or wider framing of Douglas Fir-larch or Southern Pine. For framing of other species: (1) Find specific gravity for species of framing lumber in ANSI/AWC NDS. (2) For staples, multiply the shear value from the table above by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species.

c. Values shown are for fiberboard sheathing on one side only with long panel dimension either parallel or perpendicular to studs.

d. Fastener shall be spaced 6 inches on center along intermediate framing members.

e. Values are not permitted in Seismic Design Category D.

Table 2306.3(3) Allowable Shear Values for Wind or Seismic Forces for Shear Walls of Lath and Plaster or Gypsum Board Wood Framed Wall Assemblies Utilizing Staples

Type of Material Thickness of Material Wall Construction Staple Spacing b Maximum (inches) Shear Value a, c (plf) Minimum Staple Size f, g 1. Expanded metal or woven wire lath and portland cement plaster 7/8" Unblocked 6 180 No. 16 gage galv. staple, 7/8" legs 2. Gypsum lath, plain or perforated 3/8" lath and 1/2" plaster Unblocked 5 100 No. 16 gage galv. staple, 1 1/8" long 3. Gypsum sheeting 1/2" × 2' × 8' Unblocked 4 75 No. 16 gage galv. staple, 1 3/4" long 1/2" × 4' Blocked d 4 175 Unblocked 7 100 4. Gypsum board, gypsum veneer base or water-resistant gypsum backing board 1/2" Unblocked d 7 75 No. 16 gage galv. staple, 1 1/2" long Unblocked d 4 110 Unblocked 7 100 Unblocked 4 125 Blocked e 7 125 Blocked e 4 150 5/8" Unblocked d 7 115 No. 16 gage galv. staple, 1 1/2" legs, 1 5/8" long 4 145 Blocked e 7 145 4 175 Blocked e Two-ply Base ply: 9 Face ply: 7 250 No. 16 gage galv. staple, 1 5/8" long No. 15 gage galv. staple, 2 1/4" long

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per foot = 14.5939 N/m.

a. These shear walls shall not be used to resist loads imposed by masonry or concrete walls (see AWC SDPWS). Values shown are for short-term loading due to wind or seismic loading. Walls resisting seismic loads shall be subject to the limitations in Section 12.2.1 of ASCE 7. Values shown shall be reduced 25 percent for normal loading.

b. Applies to fastening at studs, top and bottom plates and blocking.

c. Except as noted, shear values are based on a maximum framing spacing of 16 inches on center.

d. Maximum framing spacing of 24 inches on center.

\e. All edges are blocked, and edge fastening is provided at all supports and all panel edges.

f. Staples shall have a minimum crown width of 7/16 inch, measured outside the legs, and shall be installed with their crowns parallel to the long dimension of the framing members.

g. Staples for the attachment of gypsum lath and woven-wire lath shall have a minimum crown width of 3/4 inch, measured outside the legs.

Section BC 2307. Load and Resistance Factor Design

Open this section

2307.1 Load and resistance factor design.

The design and construction of wood elements and structures using load and resistance factor design shall be in accordance with ANSI/AWC NDS and AWC SDPWS.