NYC Administrative Code Section BC 2305 General Design Requirements for Lateral Force-Resisting Systems

This section has 4 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read Section BC 2305 at American Legal Publishing.

2305.1 General.

Structures using wood-frame shear walls or wood-frame diaphragms to resist wind, seismic or other lateral loads shall be designed and constructed in accordance with AWC SDPWS and the applicable provisions of Sections 2305, 2306 and 2307.

2305.1.1 Openings in shear panels.

Openings in shear panels that materially affect their strength shall be detailed on the plans and shall have their edges adequately reinforced to transfer all shearing stresses.

2305.2 Diaphragm deflection.

The deflection of wood-frame diaphragms shall be determined in accordance with AWC SDPWS. The deflection (D dia ) of a blocked wood structural panel diaphragm uniformly fastened throughout with staples is permitted to be calculated in accordance with Equation 23-1. If not uniformly fastened, the constant 0.188 (For SI: 1/1627) in the third term shall be modified by an approved method.

(Equation 23-1)

where:

A = Area of chord cross section, in square inches (mm 2 ).

E = Modulus of elasticity of diaphragm chords, in pounds per square inch (N/mm 2 ).

e n = Staple slip, in inches (mm) (See Table 2305.2(1)).

Gt = Panel rigidity through the thickness, in pounds per inch (N/mm) of panel width of or depth (See Table 2305.2(2)).

L = Diaphragm length (dimension perpendicular to the direction of the applied load), in feet (mm).

v = Induced unit shear in pounds per linear foot (plf) (N/mm).

W = Diaphragm width (in the direction of applied force, in feet (mm)).

x = Distance from chord splice to nearest support, in feet (mm).

D c = Diaphragm chord splice slip at the induced unit shear, in inches (mm).

D dia = Maximum mid-span diaphragm deflection determined by elastic analysis, in inches (mm).

Table 2305.2(1) e n Values (inches) for Use in Calculating Diaphragm and Shear Wall Deflection Due to Fastener Slip (Structural I) a, c

Load Per Fastener b (pounds) Fastener Designations 14-Ga staple × 2 inches long 60 0.011 80 0.018 100 0.028 120 0.04 140 0.053 160 0.068

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 4.448 N.

a. Increase e n values 20 percent for plywood grades other than Structural I.

b. Load per fastener = maximum shear per foot divided by the member of fasteners per foot at interior panel edges.

c. Decrease e n values 50 percent for seasoned lumber (moisture contest < 19 percents.

Table 2305.2(2) Values of Gt for Use in Calculating Deflection of Wood Structural Panel Shear Walls and Diaphragms

Panel Type Span Rating Values of Gt (lb/in. panel depth or width) Structural Sheathing Structural I Plywood Plywood 3-ply 4-ply 5-ply a OSB 3-ply 4-ply 5-ply a OSB Sheathing 24/0 25,000 32,500 37,500 77,500 32,500 42,500 41,500 77,500 24/16 27,000 35,000 40,500 83,500 35,000 45,500 44,500 83,500 32/16 27,000 35,000 40,500 83,500 35,000 45,500 44,500 83,500 40/20 28,500 37,000 43,000 88,500 37,000 48,000 47,500 88,500 48/24 31,000 40,500 46,500 96,000 40,500 52,500 51,000 96,000 Single Floor 16 o.c. 27,000 35,000 40,500 83,500 35,000 45,500 44,500 83,500 20 o.c. 28,000 36,500 42,000 87,000 36,500 47,500 46,000 87,000 24 o.c. 30,000 39,000 45,000 93,000 39,000 50,500 49,500 93,000 32 o.c. 36,000 47,000 54,000 110,000 47,000 61,000 59,500 110,000 48 o.c. 50,500 65,500 76,000 155,000 65,500 85,000 83,500 155,000

Structural Sheathing Structural I Thickness (in.) A-A, A-C Marine All Other Grades A-A, A-C Marine All Other Grades Sanded Plywood 1/4 24,000 31,000 24,000 31,000 31,000 31,000 11/32 25,500 33,000 25,500 33,000 33,000 33,000 3/8 26,000 34,000 26,000 34,000 34,000 34,000 15/32 38,000 49,500 38,000 49,500 49,500 49,500 1/2 38,500 50,000 38,500 50,000 50,000 50,000 19/32 49,000 63,500 49,000 63,500 63,500 63,500 5/8 49,500 64,500 49,500 64,500 64,500 64,500 23/32 50,500 65,500 50,500 65,500 65,500 65,500 3/4 51,000 66,500 51,000 66,500 66,500 66,500 7/8 52,500 68,500 52,500 68,500 68,500 68,500 1 73,500 95,500 73,500 95,500 95,500 95,500 1 1/8 75,000 97,500 75,000 97,500 97,500 97,500

For SI: 1 inch = 25.4 mm, 1 pound/inch = 0.1751 N/mm.

a. 5-ply applies to plywood with five or more layers; for five-ply plywood with three layers, use values for four ply.

2305.3 Shear wall deflection.

The deflection of wood-frame shear walls shall be determined in accordance with AWC SDPWS. The deflection (D sw ) of a blocked wood structural panel shear wall uniformly fastened throughout with staples is permitted to be calculated in accordance with Equation 23-2.

(Equation 23-2)

where:

A = Area of end-post cross section in square inches (mm 2 ).

b Shear wall length, in feet (mm).

d a = Total vertical elongation of wall anchorage system (including fastener slip, device elongation, rod elongation) at the induced unit shear in the shear wall (v).

E = Modulus of elasticity of end posts, in pounds per square inch (N/mm 2 ).

e n = Staple slip, in inches (mm) (See Table 2305.2(1)).

Gt = Panel rigidity through the thickness, in pounds per inch (N/mm) of panel width or depth (See Table 2305.2(2)).

h = Shear wall height, in feet (mm).

v = Induced unit shear, in pounds per linear foot (plf) (N/mm).

D sw = Maximum shear wall deflection determined by elastic analysis, in inches (mm).