NYC Administrative Code Title 28, Chapter 7 New York City Building Code, part 24 of 33
Section BC 3008 to Section BC 3301: 25 sections.
Section BC 3008. Occupant Evacuation Elevators
3008.1 General.
Where elevators are to be used for occupant self-evacuation during fires, all passenger elevators for general public use shall comply with Sections 3008.1 through 3008.10. Where other elevators are used for occupant self-evacuation, those elevators shall comply with these sections
3008.1.1 Additional exit stairway.
Where an additional means of egress is required in accordance with Section 403.5.2, an additional exit stairway shall not be required to be installed in buildings provided with occupant evacuation elevators complying with Section 3008.1.
3008.1.2 Fire safety and emergency action plans.
The building shall have an approved fire safety and emergency action plans in accordance with the applicable requirements of the New York City Fire Code. The fire safety and emergency action plans shall incorporate specific procedures for the occupants using evacuation elevators.
3008.1.3 Operation.
The occupant evacuation elevators shall be used for occupant self-evacuation in accordance with the occupant evacuation operation requirements as per ASME A17.1/CSA B44 as modified by Appendix K of this code and the building's fire safety and emergency action plans.
3008.2 Reserved.
3008.3 Automatic sprinkler system.
The building shall be protected throughout by an approved, electrically-supervised automatic sprinkler system in accordance with Section 903.3.1.1, except as otherwise permitted by Section 903.3.1.1.1 and as prohibited by Section 3008.3.1.
3008.3.1 Prohibited locations.
Automatic sprinklers shall not be installed in elevator machine rooms, machinery spaces, control rooms, control spaces and elevator hoistways of occupant evacuation elevators.
3008.3.2 Sprinkler system monitoring.
The sprinkler system shall have a sprinkler control valve supervisory switch and water flow initiating device provided for each floor that is monitored by the building's fire alarm system.
3008.4 Water protection.
An approved method to prevent water from infiltrating into the hoistway enclosure from the operation of the automatic sprinkler system outside the enclosed occupant evacuation elevator lobby shall be provided.
3008.5 Reserved.
3008.6 Hoistway enclosure protection.
Occupant evacuation elevator hoistways shall be located in shaft enclosures complying with Section 713.
3008.6.1 Structural integrity of hoistway enclosures.
Occupant evacuation elevator hoistway enclosures shall comply with Sections 403.2.3.1 through 403.2.3.4.
3008.7 Occupant evacuation elevator lobby.
The occupant evacuation elevators shall open into an elevator lobby in accordance with Sections 3008.7.1 through 3008.7.6. Egress is permitted through the elevator lobby in accordance with Item 1 of Section 1016.2.
3008.7.1 Access to Interior exit stairway or ramp.
The occupant evacuation elevator lobby shall have direct access from the enclosed elevator lobby to an interior exit stairway or ramp.
Exception: Access to an interior exit stairway or ramp shall be permitted to be through a protected path of travel protected with smoke partitions complying with Section 711. The protected path shall be separated from the enclosed elevator lobby through an opening protected by a smoke and draft control assembly in accordance with Section 716.5.3.
3008.7.2 Lobby enclosure.
The occupant evacuation elevator lobby shall be enclosed with a smoke barrier having a fire-resistance rating of not less than 1 hour, except that lobby doorways shall comply with Section 3008.7.3.
Exception: Enclosed occupant evacuation elevator lobbies are not required at the levels of exit discharge.
3008.7.3 Lobby doorways.
Other than doors to the hoistway, and elevator machine rooms, machinery spaces, control rooms, and control spaces within the lobby enclosure smoke barrier, each doorway to an occupant evacuation elevator lobby shall comply with the smoke and draft control assembly requirements of Section 716.5.3.1 with the UL 1784 test conducted without the artificial bottom seal. Such doorway shall not be required to have a fire-resistance rating.
3008.7.3.1 Vision panel.
A vision panel shall be installed in each door assembly protecting the lobby doorway. The vision panel shall consist of glazing and shall be located to furnish clear vision of the occupant evacuation elevator lobby.
3008.7.3.2 Door closing.
Each door assembly protecting the lobby doorway shall be automatic closing upon receipt of any fire alarm signal from the emergency voice/alarm communication system serving the building.
3008.7.4 Lobby size.
Each occupant evacuation elevator lobby shall have minimum floor area as follows:
1. The occupant evacuation elevator lobby floor area shall accommodate, at 3 square feet (0.28 m 2 ) per person, not less than 25 percent of the occupant load of the floor area served by the lobby.
2. The occupant evacuation elevator lobby floor area shall accommodate one wheelchair space of 30 inches by 48 inches (760 mm by 1220 mm) for each 50 persons, or portion thereof, of the occupant load of the floor area served by the lobby.
Exception: The size of lobbies serving multiple banks of elevators shall have the minimum floor area approved on an individual basis and shall be consistent with the building's fire safety and emergency action plans.
3008.7.5 Signage.
An approved sign indicating elevators are suitable for occupant self-evacuation shall be posted on all floors adjacent to each elevator call station serving occupant evacuation elevators.
3008.7.6 Two-way communication system.
A two-way communication system shall be provided in each occupant evacuation elevator lobby for the purpose of initiating communication with the fire command center or an alternate location approved by the Fire Department. The two-way communication system shall be designed and installed in accordance with Sections 1009.8.1 and 1009.8.2.
3008.8 Elevator system monitoring.
The occupant evacuation elevators shall be continuously monitored at the fire command center or a central control point approved by the Fire Department and arranged to display all of the following information:
1. Floor location of each elevator car.
2. Direction of travel of each elevator car.
3. Status of each elevator car with respect to whether it is occupied.
4. Status of normal power to the elevator equipment, elevator machinery and electrical apparatus cooling equipment where provided, elevator machine room, control room and control space ventilation and cooling equipment.
5. Status of emergency or standby power system that provides backup power to the elevator equipment, elevator machinery and electrical cooling equipment where provided, elevator machine room, control room and control space ventilation and cooling equipment.
6. Activation of any fire alarm initiating device in any elevator lobby, elevator machine room, machine space containing a motor controller or electric driving machine, control space, control room or elevator hoistway.
3008.8.1 Elevator recall.
The fire command center or an alternate location approved by the Fire Department shall be provided with the means to manually initiate a Phase I Emergency Recall of the occupant evacuation elevators in accordance with ASME A17.1/CSA B44 as modified by Appendix K of this code.
3008.9 Electrical power.
The following features serving each occupant evacuation elevator shall be supplied by both normal power and Type 60/Class 6/Level 1 standby power:
1. Elevator equipment.
2. Ventilation and cooling equipment for elevator machine rooms, control rooms, machinery and control spaces.
3. Elevator car lighting.
Exceptions:
1. Standby power relying on natural gas as a fuel source need not be Class 6.
2. Where Exception 2 of Section 403.5.2 is utilized, the standby power generating equipment need only be sized to satisfy the loads required to simultaneously operate those elevators identified in the timed egress analysis described in Exception 2.2.
3008.9.1 Protection of wiring or cables.
Wires or cables that are located outside of the elevator hoistway, machine room, control room and control space and that provide normal or standby power, control signals, communication with the car, lighting, heating, air conditioning, ventilation and fire-detecting systems to occupant evacuation elevators shall be protected by construction having a fire-resistance rating of not less than 2 hours, or shall be circuit integrity cable having a fire-resistance rating of not less than 2 hours, or shall be protected by a listed electrical circuit protective system having a fire-resistance rating of not less than 2 hours.
Exception: Wiring and cables to control signals are not required to be protected provided that wiring and cables do not serve Phase II emergency in-car operation.
3008.10 Emergency voice/alarm communication system.
The building shall be provided with an emergency voice/alarm communication system. The emergency voice/alarm communication system shall be accessible to the Fire Department. The system shall be provided in accordance with Section 907.5.2.2.
3008.10.1 Notification appliances.
Not fewer than one audible and one visible notification appliance shall be installed within each occupant evacuation elevator lobby.
3008.11 Hazardous material areas.
No building areas shall contain hazardous materials exceeding the maximum allowable quantities per control area as addressed in Section 414.2.
Section BC 3009. Service Equipment Certificates
3009.1 Required.
No service equipment shall be placed in operation until a service equipment certificate of compliance has been obtained in accordance with the provisions of this code.
3009.2 Posting of inspection certificate.
At the time a service equipment certificate of compliance is issued, an inspection certificate issued by the commissioner shall be posted. No such inspection certificate shall be issued for elevators that are not subject to periodic inspections pursuant to this code. The inspection certificate shall be in such form as the commissioner shall determine by rule and shall be posted in a frame with a transparent cover in the car of every passenger and freight elevator and on or near every escalator and moving walk and power operated scaffold.
3009.2.1 Alternate posting locations.
In lieu of posting the inspection certificate in those locations specified in this section, the inspection certificate may be kept in the on-site building manager's office. In such case, the building manager's office must be open during normal business hours. In addition, notice must be posted in each location listed in Section 3009.2 and kept in a frame with a transparent cover, or a plaque or on the car operating panel, with an indelible inscription, stating that the inspection certificate is located in the building manager's office and identifying the location of such office.
3009.3 Temporary use certificates.
The commissioner may issue temporary use certificates for any equipment or device regulated by this code, except power-operated scaffolds, provided that such partial use and operation may be made safely and without endangering public health, safety, and welfare and provided further that such temporary use certificate shall not be issued for a period of more than 30 calendar days, subject to renewal for additional 30-day periods at the discretion of the commissioner. Temporary use certificates for elevators shall also be conditioned upon compliance with the following:
1. The class of service to be permitted shall be designated on the temporary use certificate.
2. The hoistway shall be enclosed throughout in an enclosure complying with ASME A17.1/CSA B44 or with a temporary enclosure in accordance with the requirements for workers' elevators (temporary elevators) of the Industrial Code of the State of New York, No. 23.
3009.3.1 Posting of temporary use certificate.
The temporary use certificate shall be posted in a conspicuous location on, or adjacent to, the device covered by the certificate and shall state that the device has not been finally approved by the commissioner.
Section BC 3010. Elevator, Amusement, and Other Device Operators
3010.1 Elevator operators.
With the exception of automatic operation elevators, every passenger and freight elevator with a rise of more than one story shall be in the charge of a designated competent operator, who shall be at least 18 years old and selected with consideration of his or her abilities to perform his or her duties in a careful and competent manner. Such designated competent operator shall be instructed in the safe and proper operation of the equipment.
3010.2 Amusement device operators.
Operators of amusement devices shall meet the requirements of rules of the department.
3010.3 Other device operators.
Other devices regulated by this code shall, when deemed necessary by the commissioner to protect public safety, be in the charge of a designated competent operator conforming to such qualifications as the commissioner may prescribe, except that operators for workers' hoists shall be assigned as required by the applicable provisions of ANSI A10.4.
3010.4 Sanction for unlawful operation.
If the commissioner finds that any person engaged in operating an elevator, amusement, or other device is not competent to operate the elevator, amusement or other device, the owner, agent or lessee of such elevator, amusement, or other device shall, upon notice from the commissioner, discontinue the operation of such device by such operator.
Section BC 3011. Elevator Being Serviced, Repaired, Inspected or Tested
3011.1 Signage.
When an existing or new automatic passenger elevator in any building or structure is being serviced, repaired, inspected or tested by an elevator company, or elevator personnel, and there are no elevator personnel available to remain in the elevator car, "CAUTION" sign tapes shall be placed across the car door jamb. One strip of "CAUTION" sign tape shall be placed at a height of 18 inches (457 mm) above the car floor and another strip of "CAUTION" sign tape shall be placed at a height of 54 inches (1372 mm) above the car floor.
3011.1.1 Sign tape.
The "CAUTION" sign tape shall be 3 inches (76 mm) in width with the words "CAUTION - DO NOT ENTER" repeated every 6 inches (152 mm). The lettering shall be black on yellow background. The letters shall be at least 2 inches (51 mm) high. Caution tape may be replaced with OSHA approved elevator barricades.
3011.1.2 Elevator out of service.
When an elevator is out of service with the car door open at a landing prior to the elevator personnel arriving, Sections 3011.1 and 3011.1.1 shall apply.
Section BC 3012. Accidents
3012.1 Accidents.
The owner of any device regulated by this chapter shall promptly notify the commissioner of every accident involving injury to any person requiring the services of Emergency Medical Service (EMS) or damage to property or to apparatus exceeding $5,000 on, about, or in connection with such equipment, before commencing any repairs and shall afford the commissioner every facility for investigating such accident or damage. The commissioner shall make an investigation immediately thereafter, and shall prepare a full and complete report of such investigation. Such report shall give in detail all material facts and information available and the cause or causes as far as they can be determined. Such report shall be a public record. When an accident involves the failure or destruction of any part of the construction or operating mechanism of such equipment, no such equipment shall be used until it has been made safe, and re-inspected by the commissioner; and the commissioner may order the discontinuance of such equipment until a new service equipment certificate has been issued by him or her for its use. No part shall be removed from the premises of the damaged construction or operating mechanism until permission to do so has been granted by the commissioner.
Section BC 3013. Existing Installations
3013.1 General.
Existing installations shall be modified in accordance with Appendix K, Chapter K3.
Section BC 3014. Inspection and Testing
3014.1 Elevators and conveying systems.
Inspection and testing of elevators and conveying systems shall be in accordance with Appendix K, including Table N1. Refer to Chapter 3 of Title 28 of the Administrative Code for additional requirements.
3014.2 Amusement devices.
Inspection and testing of amusement devices shall comply with rules of the department. Refer to Chapter 3 of Title 28 of the Administrative Code for additional requirements. Installation of amusement devices shall be subject to the requirements for special and progress inspections.
Section BC 3101. General
3101.1 Scope.
The provisions of this chapter shall govern special building construction including membrane structures, temporary structures, pedestrian walkways and tunnels, automatic vehicular gates, awnings, canopies, sun control devices, marquees, signs, telecommunications towers and antennas, swimming pools and enclosures, sidewalk cafes, and fences.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2012/028.
Section BC 3102. Membrane Structures
3102.1 General.
The provisions of Sections 3102.1 through 3102.8 shall apply to air-supported structures, air-inflated structures, membrane-covered cable structures, membrane-covered frame structures and tents, and tensile membrane structures, collectively known as membrane structures.
3102.1.1 Certificates of Occupancy.
The duration of Certificates of Occupancy for air-inflated structures, air-supported structures, and tents shall be limited in accordance with the requirements of Chapter 1 of Title 28 of the Administrative Code.
3102.1.2 Temporary installations.
In addition to the requirements of Section 3102 of this code, temporary installations of air-supported structures, air-inflated structures, membrane-covered cable structures, tensile membrane structures, membrane-covered frame structures and tents, collectively known as membrane structures shall comply with the requirements of Article 111 of Chapter 1 of Title 28 of the Administrative Code.
3102.2 Definitions.
The following terms are defined in Chapter 2:
AIR-INFLATED STRUCTURE.
AIR-SUPPORTED STRUCTURE.
Double skin.
Single skin.
CABLE-RESTRAINED, AIR-SUPPORTED STRUCTURE.
MEMBRANE-COVERED CABLE STRUCTURE.
MEMBRANE-COVERED FRAME STRUCTURE.
NONCOMBUSTIBLE MEMBRANE STRUCTURE.
TENSILE MEMBRANE STRUCTURE.
TENT.
3102.3 Type of construction.
Noncombustible membrane structures shall be classified as Type IIB construction. Noncombustible frame or cable-supported structures covered by an approved membrane in accordance with Section 3102.3.1 shall be classified as Type IIB construction. Heavy timber frame-supported structures covered by an approved membrane in accordance with Section 3102.3.1 shall be classified as Type IV construction. Other membrane structures shall be classified as Type V construction.
3102.3.1 Membrane and interior liner material.
Membranes and interior liners shall be either noncombustible as set forth in Section 703.5, or meet the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701 and the manufacturer's test protocol.
3102.4 Allowable floor areas.
The area of a membrane structure shall not exceed the limitations specified in Section 506.
3102.5 Maximum height.
Membrane structures shall not exceed one story nor shall such structures exceed the height limitations in feet specified in Section 504.3. Membrane structures may be erected above the roof of a building provided that such roof is of noncombustible construction required to have a fire-resistance rating.
Exception: Noncombustible membrane structures serving as roofs only.
3102.6 Mixed construction.
Membrane structures shall be permitted to be utilized as specified in this section as a portion of buildings of other types of construction. Height and area limits shall be as specified for the type of construction and occupancy of the building.
3102.6.1 Noncombustible membrane.
A noncombustible membrane shall be permitted for use as the roof or as a skylight of any building or atrium of a building of any type of construction provided such membrane is not less than 20 feet (6096 mm) above any floor, balcony or gallery, and meets the fire classification requirements of Section 1505 for roof assemblies.
3102.6.1.1 Membrane.
A membrane meeting the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701 shall be permitted to be used as the roof or as a skylight on buildings of Type IIB, III, IV and V construction, provided such membrane is not less than 20 feet (6096 mm) above any floor, balcony or gallery, and meets the fire classification requirements of Section 1505 for roof assemblies.
3102.7 Engineering design.
Membrane structures, except tensile membrane structures, shall be designed and constructed to sustain dead loads; loads due to tension or inflation; live loads including wind, snow or flood and seismic loads and in accordance with Chapter 16 and Appendix G.
3102.7.1 Lateral restraint.
For membrane-covered frame structures, the membrane shall not be considered to provide lateral restraint in the calculation of the capacities of the frame members.
3102.7.2 Design.
Tents, air-inflated structures, and air-supported structures shall be designed by either an alternate engineering design approved by the commissioner or as follows:
1. Tents. Tents shall be guyed, supported, and braced to withstand a wind pressure of 10 psf (478.8 Pa) of projected area of the tent. The poles and their supporting guys, stays, stakes, fastenings, etc., shall be of sufficient strength and attached so as to resist wind pressure of 20 psf (957.6 Pa) of projected area of the tent.
2. Air-inflated structures and air-supported structures.
2.1. Air-inflated structures and air-supported structures shall be anchored to the ground or supporting structure by either ballast or positive anchorage, sufficiently and evenly distributed, and adequate to resist the inflation lift load, the aerodynamic lift load, and the drag (shear) load due to wind impact. The latter factors shall be based on a fastest mile wind speed of 70 mph (112.65 km/hr), and an estimated stagnation of not less than 0.5 q for structures on grade whose height is equal to, or less than, the width of the structure. For greater heights, or for elevated structures, increased anchorage shall be provided, justified by analytical and/or experimental data subject to approval by the commissioner.
2.2. The skin of the structure shall be of such strength, and the joints so constructed, as to provide a minimum dead load strip tensile strength at 70°F (21°C) of four times the 70 mph (121.65 km/hr) design load (inflation and aerodynamic loading). The joints shall provide a dead load strip tensile strength of 160°F (71°C) of twice the 70 mph (121.65 km/hr) design load (i.e., a factor of safety of 4 and 2, respectively). In addition, the material shall provide a trapezoidal tear strength of not less than 15 percent of the maximum design tensile load. Material and joint strengths shall be so certified by the manufacturer, justified by analytical and/or experimental data.
3102.7.3 Tensile membrane structures.
The design and construction shall be in accordance with ASCE 55. The provisions of Sections 3102.1 through 3102.6 shall also apply.
3102.8 Inflation systems.
Air-supported structures and air-inflated structures shall be provided with primary and auxiliary inflation systems to meet the minimum requirements of Sections 3102.8.1 through 3102.8.3.
3102.8.1 Equipment requirements.
The primary inflation system shall consist of one or more blowers and shall include provisions for automatic control to maintain the required inflation pressures. Such system shall be so designed as to prevent overpressurization of the system.
3102.8.1.1 Auxiliary inflation system.
In addition to the primary inflation system, in structures exceeding 1,500 square feet (140 m 2 ) in area, an auxiliary inflation system shall be provided with sufficient capacity to maintain the inflation of the structure in case of primary system failure. The auxiliary inflation system shall operate automatically when there is a loss of internal pressure and when the primary blower system becomes inoperative. Initiation of auxiliary inflation system shall be indicated by an audible and visual alert at the entrance or a regularly attended location.
3102.8.1.2 Blower equipment.
Blower equipment shall meet all of the following requirements:
1. Blowers shall be powered by continuous-rated motors at the maximum power required for any flow condition as required by the structural design.
2. Blowers shall be provided with inlet screens, belt guards and other protective devices as required by the commissioner to provide protection from injury.
3. Blowers shall be housed within a weather-protecting structure.
4. Blowers shall be equipped with backdraft check dampers to minimize air loss when inoperative.
5. Blower inlets shall be located to provide protection from air contamination. The location of inlets shall be approved.
3102.8.2 Standby power.
Wherever an auxiliary inflation system is required, an approved standby power-generating system shall be provided. However, notwithstanding Section 2702.1, the standby power-generating system shall be equipped with a suitable means for automatically starting the generator set upon failure of the normal electrical service and for automatic transfer and operation of all of the required electrical functions at full power within 60 seconds of such service failure. Standby power shall be capable of operating independently for not less than 4 hours. Initiation of standby power shall be indicated by an audible and visual alert at the entrance or a regularly attended location.
3102.8.3 Support provisions.
A system capable of supporting the membrane in the event of deflation shall be provided for in air-supported structures and air-inflated structures having an occupant load of 50 or more or where covering a swimming pool regardless of occupant load. Such support system shall be capable of maintaining the membranes not less than 7 feet (2134 mm) above the floor, seating area or surface of the water. When air-supported structures or air-inflated structures are used as a roof on Type I or II construction buildings, such support system shall be capable of maintaining the membranes not less than 20 feet (6096 mm) above the floor or seating area.
3102.9 Separation.
No air-inflated structure, air-supported structure, or tent shall be erected closer than 20 feet (6096 mm) to any interior lot line nor closer than 30 feet (9144 mm) in any direction to an unprotected opening, required exterior stairway or corridor, or required exit door, on the same level or above the level of such structure. Such structure may abut another building on the same tax lot if the following conditions exist:
1. No unprotected openings or exits are located above or within 30 feet (9144 mm) of such structure.
2. No doors serving as a required exit are located between such structure and the abutted building.
3. The exterior wall of the abutted building meets the requirements of Section 705 for fire walls.
3102.10 Exits.
In addition to the requirements of Chapter 10, travel distance to an exit from any point within a tent, air-supported structure, or air-inflated structure shall not exceed 75 feet (22 860 mm).
3102.10.1 Exit openings from tents.
Exit openings from tents shall remain open unless covered by a flame-resistant curtain of a contrasting color to the tent. Such curtain shall be supported not less than 80 inches (2032 mm) above the floor level at the exit and, when open, no part of the curtain shall obstruct the exit.
3102.10.2 Exit openings from air-supported structures and air-inflated structures.
Exit doors in air-supported structures and air-inflated structures shall close automatically against normal operational pressures. Opening force at the edge of such doors shall not exceed 15 pounds (6.80 kg), with the structure at operational pressure. Exit doors shall be located in frames constructed such that they will remain operative and support the weight of the pressurized membrane structure in a state of total collapse.
Section BC 3103. Temporary Structures
3103.1 General.
The provisions of Sections 3103.1 through 3103.4 shall apply to temporary tents, grandstands, platforms, reviewing stands, outdoor bandstands, stages and similar miscellaneous structures erected for a period of 90 days or less. Such structures may be constructed of wood whether located inside or outside of the fire districts.
3103.1.1 Permit required.
Temporary structures shall not be erected, operated or maintained for any purpose without obtaining a permit from the department in accordance with Section 28-111.1.1 of the Administrative Code.
Exception: No permit shall be required for:
1. The erection and use of temporary tents of less than 400 gross square feet (37 m 2 ), for not more than 30 days.
2. The erection and use of temporary platforms, reviewing stands, outdoor bandstands, and similar miscellaneous structures that cover an area less than 120 square feet (11.16 m 2 ), including connecting areas or spaces with a common means of egress or entrance, for not more than 30 days.
3103.2 Construction documents.
A permit application and construction documents shall be submitted for each installation of a temporary structure. The construction documents shall include a site plan indicating the location of the temporary structure and information delineating the means of egress and the occupant load.
3103.3 Location.
Temporary structures shall be located in accordance with the requirements of Table 602 based on the fire-resistance rating of the exterior walls for the proposed type of construction.
3103.4 Means of egress.
Temporary structures shall conform to the means of egress requirements of Chapter 10 and shall have an exit access travel distance of 100 feet (30 480 mm) or less.
Section BC 3104. Pedestrian Walkways and Tunnels
3104.1 General.
This section shall apply to connections between buildings such as pedestrian walkways or tunnels, located at, above or below grade level, that are used as a means of travel by persons. The pedestrian walkway shall not contribute to the building area or the number of stories or height of connected buildings.
3104.1.1 Application.
Pedestrian walkways shall be designed and constructed in accordance with Sections 3104.2 through 3104.9. Tunnels shall be designed and constructed in accordance with Sections 3104.2 and 3104.10.
3104.2 Separate structures.
Buildings connected by pedestrian walkways or tunnels shall be considered to be separate structures.
Exceptions:
1. Buildings that are on the same tax lot and considered as portions of a single building in accordance with Section 503.1.2.
2. For purposes of calculating the number of Type B units required by Chapter 11, structurally connected buildings and buildings with multiple wings shall be considered one structure.
3104.3 Construction.
The pedestrian walkway shall be of a Construction Type that is at least equal to the higher type of the two buildings connected.
Exception: Exterior pedestrian walkways serving as a required exit shall be constructed of noncombustible materials and comply with the fire-resistance rating requirements as set forth in Chapter 7.
3104.4 Contents.
Only materials approved by the department shall be located in the pedestrian walkway. Decorations may be permitted in accordance with the New York City Fire Code.
3104.5 Connections of pedestrian walkways to buildings.
The connection of a pedestrian walkway to a building shall comply with Section 3104.5.1, 3104.5.2, 3104.5.3 or 3104.5.4.
Exception: Buildings that are on the same tax lot and considered as portions of a single building in accordance with Section 503.1.2.
3104.5.1 Fire barriers.
Pedestrian walkways shall be separated from the interior of the building by not less than 2-hour fire barriers constructed in accordance with Section 707 and Sections 3104.5.1.1 through 3104.5.1.3.
3104.5.1.1 Exterior walls.
Exterior walls of buildings connected to pedestrian walkways shall be 2-hour fire-resistance-rated. This protection shall extend not less than 10 feet (3048 mm) in every direction surrounding the perimeter of the pedestrian walkway.
3104.5.1.2 Openings in exterior walls of connected buildings.
Openings in exterior walls required to be fire-resistance-rated in accordance with Section 3104.5.1.1 shall be equipped with opening protectives providing a not less than 3/4-hour fire protection rating in accordance with Section 716.
3104.5.1.3 Supporting construction.
The fire barrier shall be supported by construction as required by Section 707.5.1.
3104.5.2 Alternative separation.
The wall separating the pedestrian walkway and the building shall comply with Section 3104.5.2.1 or 3104.5.2.2 where:
1. The distance between the connected buildings is more than 30 feet (9144 mm).
2. The pedestrian walkway and connected buildings are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, and the roof of the walkway is not more than 55 feet (16 764 mm) above grade connecting to the fifth, or lower, story above grade plane, of each building.
Exception: Pedestrian walkways accessory to open parking garages need not be equipped with an automatic sprinkler system.
3104.5.2.1 Passage of smoke.
The wall shall be capable of resisting the passage of smoke.
3104.5.2.2 Glass.
The wall shall be constructed of a tempered, wired or laminated glass wall and doors or glass separating the interior of the building from the pedestrian walkway. The glass shall be protected by an automatic sprinkler system in accordance with Section 903.3.1.1 that, when actuated, shall completely wet the entire surface of interior sides of the wall or glass. Obstructions shall not be installed between the sprinkler heads and the wall or glass. The glass shall be in a gasketed frame and installed in such a manner that the framing system will deflect without breaking (loading) the glass before the sprinkler operates.
3104.5.3 Open sides on walkway.
Where the distance between the connected buildings is more than 30 feet (9144 mm), the walls at the intersection of the pedestrian walkway and each building need not be fire-resistance-rated provided both sidewalls of the pedestrian walkway are not less than 50 percent open with the open area uniformly distributed to prevent the accumulation of smoke and toxic gases. The roof of the walkway shall be located not more than 40 feet (12 160 mm) above grade plane, and the walkway shall only be permitted to connect to the third or lower story of each building.
Exception: Where the pedestrian walkway is protected with a sprinkler system in accordance with Section 903.3.1.1, the roof of the walkway shall be located not more than 55 feet (16 764 mm) above grade plane and the walkway shall only be permitted to connect to the fifth or lower story of each building.
3104.5.4 Exterior walls greater than 2 hours.
Where exterior walls of connected buildings are required by Section 705 to have a fire-resistance rating greater than 2 hours, the walls at the intersection of the pedestrian walkway and each building need not be fire-resistance-rated provided:
1. The pedestrian walkway is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.
2. The roof of the walkway is not located more than 55 feet (16 764 mm) above grade plane and the walkway connects to the fifth, or lower, story above grade plane of each building.
3104.6 Public way.
Pedestrian walkways over a public way shall comply with Chapter 32.
3104.7 Width.
The unobstructed width of pedestrian walkways shall be not less than 36 inches (914 mm). The total width shall be not greater than 30 feet (9144 mm).
3104.8 Egress.
Access shall be provided at all times to a pedestrian walkway that serves as a required exit. Doors satisfying the requirements of Chapter 10 shall enclose each end of such pedestrian walkway. The width of such pedestrian walkway shall be at least equal to the width of the doors opening onto such pedestrian walkway, but in no case less than 44 inches (1118 mm). The floor level at doors shall be the same as that of the connected building.
Exception: The floor level at doors of open pedestrian walkways shall be not less than 7 1/2 inches (191 mm) below the level of the door. Where the requirements of Chapter 11 are applicable, these differences in level shall be accommodated by means of ramps in compliance with the provisions of Chapter 11.
3104.9 Exit access travel.
The length of exit access travel shall be 200 feet (60 960 mm) or less.
Exceptions:
1. Exit access travel distance on a pedestrian walkway equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 shall be 250 feet (76 200 mm) or less.
2. Exit access travel distance on a pedestrian walkway constructed with both sides not less than 50 percent open shall be 300 feet (91 440 mm) or less.
3. Exit access travel distance on a pedestrian walkway constructed with both sides not less than 50 percent open, and equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, shall be 400 feet (122 m) or less.
3104.10 Tunneled walkway.
Separation between the tunneled walkway and the building to which it is connected shall be not less than 2-hour fire-resistant construction and openings therein shall be protected in accordance with Table 716.5.
Section BC 3105. Awnings, Canopies and Sun Control Devices
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2012/028.
3105.1 General.
Awnings, canopies, and sun control devices shall comply with the requirements of this section, the requirements of Chapter 32 for projections over public ways, and other applicable sections of this code.
Exception: Canopies projecting over public rights-of-way governed by Title 19 of the Administrative Code and rules of the New York City Department of Transportation.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2012/028.
3105.2 Definitions.
The following term is defined in Chapter 2:
RETRACTABLE AWNING.
SUN CONTROL DEVICE.
3105.3 Design and construction.
Awnings, canopies and sun control devices shall be designed and constructed to withstand wind or other lateral loads and live loads as required by Chapter 16 with due allowance for shape, open construction and similar features that relieve the pressures or loads. Structural members shall be protected to prevent deterioration. Awnings and canopies shall have frames of noncombustible material, covered with fabric that meets the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701 or has a flame spread index not greater than 25 when tested in accordance with ASTM E 84 or UL 723, or covered in plastic in accordance with Section 2605, sheet metal, or other equivalent material, and shall be either fixed, retractable, folding or collapsible. Sun control devices shall be constructed of noncombustible materials.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2012/028.
3105.4 Reserved.
Section BC 3106. Marquees
3106.1 General.
Marquees shall comply with this section and other applicable sections of this code. Marquees projecting beyond the street line shall also comply with the requirements of Chapter 32. Signs placed on marquees shall also comply with Section 3107.
3106.2 Thickness.
The maximum height or thickness of a marquee measured vertically from its lowest to its highest point shall not be limited.
Exception: Marquees projecting beyond the street line shall meet the height and thickness requirements of Chapter 32.
3106.3 Roof construction.
Where the roof or any part thereof is a skylight, the skylight shall comply with the requirements of Chapter 24. Every roof and skylight of a marquee shall be drained in accordance with the provisions of the New York City Plumbing Code.
3106.4 Location prohibited.
Every marquee shall be so located as not to interfere with the operation of any exterior standpipe, and such that the marquee does not obstruct the clear passage of stairways or exit discharge from the building or the installation or maintenance of street lighting.
3106.5 Construction.
A marquee shall be supported entirely from the building and constructed of noncombustible materials. Marquees shall be designed as required in Chapter 16. Structural members shall be protected to prevent deterioration.
Section BC 3107. Signs
3107.1 General.
Signs shall be designed, constructed and maintained in accordance with Appendix H.
Section BC 3108. Radio, Television, and Telecommunications Towers and Antennas
3108.1 General.
Subject to the provisions of Chapter 16 and the requirements of Chapter 15 governing the fire-resistance ratings of buildings for the support of roof structures, radio, television, and telecommunications towers and antennas shall be designed and constructed as herein provided. All such towers and antennas shall be collectively referred to as "towers" for the purposes of this section. Towers shall be designed and constructed in accordance with the provisions of TIA-222.
Exceptions:
1. Exceptions related to seismic design in Section 2.7.3 of TIA-222 shall not apply;
2. The specified values for seismic coefficients S s , S 1 and Site Factors F a and F v shall comply with Section 1613.3; and
3. The horizontal extent of Topographic Category 2, escarpments, shall be 16 times the height of the escarpment.
3108.2 Location and access.
Towers shall be located and equipped with step bolts and ladders so as to provide ready access for inspection purposes. Guy wires or other accessories shall not cross or encroach upon any street or other public space, or over above-ground electric utility lines, or encroach upon any privately owned property without written consent of the owner of the encroached-upon property, space or above-ground electric utility lines. Towers shall be equipped with climbing and working facilities in compliance with TIA-222. See applicable OSHA, FCC and EPA regulations relating to limitations on access to tower sites.
3108.3 Construction.
Towers shall be constructed of approved corrosion-resistant noncombustible material. The minimum type of construction of isolated radio towers not more than 100 feet (30 480 mm) in height shall be Type IIB.
3108.4 Loads.
Towers shall be designed to resist wind loads in accordance with TIA-222 and Chapter 16 of this code. The design criteria shall not be less stringent than required by Chapter 16. Consideration shall be given to conditions involving wind load on ice-covered sections.
3108.4.1 Dead load.
Towers shall be designed for the dead load plus ice load.
3108.4.2 Wind load.
Towers shall be provided with adequate foundations and anchorage designed to resist two times the calculated wind load.
3108.4.3 Earthquake load.
Towers shall be provided with adequate foundations and anchorage designed to resist two times the calculated earthquake load.
3108.5 Grounding.
Towers shall be permanently and effectively grounded in accordance with the New York City Electrical Code.
Section BC 3109. Swimming Pools, Swimming Pool Enclosures, and Safety Devices
3109.1 General.
Swimming pools, swimming pool enclosures, and swimming pool safety devices shall comply with the requirements of this section and other applicable sections of this code.
3109.2 Definitions.
The following terms are defined in Chapter 2:
BARRIER, TEMPORARY.
SWIMMING POOL.
SWIMMING POOL, PRIVATE.
SWIMMING POOL, PUBLIC.
3109.3 Pool safety and accessibility.
Public and private swimming pools shall comply with the requirements for safety and accessibility as provided in this section.
3109.3.1 Entrapment protection.
Entrapment protection shall be provided in compliance with this section.
3109.3.1.1 Suction entrapment avoidance.
Suction outlets shall be designed and installed in accordance with ANSI/APSP-7.
3109.3.2 Swimming Pool and Spa Alarms.
Swimming pool and spa alarms shall comply with Sections 3109.3.2.1 through 3109.3.2.4.
3109.3.2.1 Applicability.
All swimming pools and spas shall be equipped with an approved pool alarm. Pool alarms shall comply with ASTM F 2208 and shall be installed, used and maintained in accordance with the manufacturer's instructions and this section.
Exceptions:
1. A hot tub or spa equipped with a safety cover that complies with ASTM F 1346.
2. A swimming pool (other than a hot tub or spa) equipped with an automatic power safety cover that complies with ASTM F 1346.
3109.3.2.2 Multiple alarms.
A pool alarm must be capable of detecting entry into the water at any point on the surface of the swimming pool. If necessary to provide detection capability at every point on the surface of the swimming pool, more than one pool alarm shall be provided.
3109.3.2.3 Alarm activation.
Pool alarms shall activate upon detecting entry into the water and shall sound poolside and inside the building.
3109.3.2.4 Prohibited alarms.
The use of personal immersion alarms shall not be construed as compliance with this section.
3109.3.3 Water circulation, water treatment and drainage.
The supply, circulation, treatment, and drainage of water for swimming pools shall meet the requirements of the New York City Plumbing Code.
3109.3.4 Electrical precautions.
No overhead electrical conductors shall be installed within 15 feet (4572 mm) of any swimming pool. All metal fences, enclosures, or railings that might become electrically charged as a result of contact with broken overhead conductors or from any other cause near, or adjacent to, a swimming pool shall be grounded in accordance with the provisions of lightning protection in the New York City Electrical Code.
3109.3.5 Facilities for people with disabilities.
Facilities for people with physical disabilities shall be provided where required by Chapter 11 of this code.
3109.4 Public swimming pools.
Public swimming pools shall comply with the requirements for safety and accessibility as provided in Sections 3109.3 and 3109.4.
Exception: A swimming pool with a power safety cover or a spa with a safety cover complying with ASTM F 1346.
3109.4.1 Barrier height and clearances.
Public swimming pools shall be completely enclosed by a fence, wall, building, or other solid barrier, or any combination thereof, not less than 6 feet (1829 mm) in height. Openings in the enclosure and pedestrian access gates shall not permit the passage of a 4-inch-diameter (102 mm) sphere. The enclosure shall be equipped with self-closing and self-latching gates.
Exception: Enclosures shall be not less than 4 feet (1219 mm) in height when surrounding wading pools with water less than 24 inches (610 mm) in depth.
3109.4.2 Gates.
Gates shall comply with Sections 3109.4.2.1 through 3109.4.2.3.
3109.4.2.1 Self-closing; opening configuration.
All gates shall be self-closing. In addition, if the gate is a pedestrian access gate, the gate shall open outward, away from the pool.
3109.4.2.2 Self-latching; location of latch handle.
All gates shall be self-latching, with the latch handle located within the enclosure (i.e., on the pool side of the enclosure) and not less than 40 inches (1016 mm) above grade. If the latch handle is located less than 54 inches (1372 mm) from the bottom of the gate, the latch handle shall be located not less than 3 inches (76 mm) below the top of the gate, and neither the gate nor barrier shall have any opening greater than 0.5 inch (12.7 mm) within 18 inches (457 mm) of the latch handle.
3109.4.2.3 Locking.
All gates shall be securely locked with a key, combination or other child proof lock sufficient to prevent access to the swimming pool through such gate when the swimming pool is not in use or supervised.
3109.4.3 Other laws.
In addition to the requirements of this section, any other, more stringent requirements for the construction and design of swimming pool and barriers that may be provided for in Article 165 of the New York City Health Code, as administered by the New York City Department of Health and Mental Hygiene, shall also be applicable.
3109.5 Private swimming pools.
Private swimming pools shall comply with the requirements for safety and accessibility as provided in Section 3109.3 and this section.
Exception: An above-ground private swimming pool which has a maximum water depth of 4 feet (1219 mm) and an area not exceeding 500 square feet (46.45 m 2 ) that is accessory to an R-3 occupancy and is privately used for noncommercial purposes shall not be required to comply with Sections 3109.3.1, 3109.3.2, 3109.5.2, 3109.5.3 and 3109.5.4.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
3109.5.1 Barrier height and clearances.
The top of the barrier enclosing a private swimming pool shall be not less than 48 inches (1219 mm) above grade measured on the side of the barrier that faces away from the swimming pool. The vertical clearance between grade and the bottom of the barrier shall be not greater than 2 inches (51 mm) measured on the side of the barrier that faces away from the swimming pool. Where the top of the pool structure is above grade, the barrier is authorized to be erected at grade level or mounted on top of the pool structure, and the vertical clearance between the top of the pool structure and the bottom of the barrier shall be not greater than 4 inches (102 mm).
3109.5.1.1 Openings.
Openings in the barrier shall not allow passage of a 4-inch-diameter (102 mm) sphere.
3109.5.1.2 Solid barrier surfaces.
Solid barriers which do not have openings shall not contain indentations or protrusions except for normal construction tolerances and tooled masonry joints.
3109.5.1.3 Closely spaced horizontal members.
Where the barrier is composed of horizontal and vertical members and the distance between the tops of the horizontal members is less than 45 inches (1143 mm), the horizontal members shall be located on the swimming pool side of the fence. Spacing between vertical members shall be not greater than 1 3/4 inches (44 mm) in width. Where there are decorative cutouts within vertical members, spacing within the cutouts shall be not greater than 1 3/4 inches (44 mm) in width.
3109.5.1.4 Widely spaced horizontal members.
Where the barrier is composed of horizontal and vertical members and the distance between the tops of the horizontal members is 45 inches (1143 mm) or more, spacing between vertical members shall be not greater than 4 inches (102 mm). Where there are decorative cutouts within vertical members, spacing within the cutouts shall be not greater than 1 3/4 inches (44 mm) in width.
3109.5.1.5 Chain link dimensions.
Mesh size for chain link fences shall be be not greater than a 2 1/4-inch square (57 mm square) unless the fence is provided with slats fastened at the top or the bottom that reduce the openings to not more than 1 3/4 inches (44 mm).
3109.5.1.6 Diagonal members.
Where the barrier is composed of diagonal members, the opening formed by the diagonal members shall be not greater than 1 3/4 inches (44 mm).
3109.5.1.7 Gates.
Gates shall comply with of Sections 3109.5.1.1 through 3109.5.1.6 and Sections 3109.5.1.7.1 through 3109.5.1.7.3.
3109.5.1.7.1 Self-closing; opening configuration.
All gates shall be self-closing. In addition, if the gate is a pedestrian access gate, the gate shall open outward, away from the pool.
3109.5.1.7.2. Self-latching; location of latch handle.
All gates shall be self-latching, with the latch handle located within the enclosure (i.e., on the pool side of the enclosure) and not less than 40 inches (1016 mm) above grade. In addition, if the latch handle is located less than 54 inches (1372 mm) from the bottom of the gate, the latch handle shall be located not less than 3 inches (76 mm) below the top of the gate, and neither the gate nor barrier shall have any opening greater than 0.5 inch (12.7 mm) within 18 inches (457 mm) of the latch handle.
3109.5.1.7.3 Locking.
All gates shall be securely locked with a key, combination or other child proof lock sufficient to prevent access to the swimming pool through such gate when the swimming pool is not in use or supervised.
3109.5.1.8 Dwelling wall as a barrier.
Where a wall of a dwelling serves as part of the barrier, one of the following shall apply:
1. Doors with direct access to the pool through that wall shall be equipped with an alarm that produces an audible warning when the door and/or its screen, if present, are opened. The alarm shall be listed in accordance with UL 2017. The audible alarm shall activate within 7 seconds and sound continuously for a minimum of 30 seconds immediately after the door and/or its screen, if present, are opened and be capable of being heard throughout the house during normal household activities. The alarm shall automatically reset under all conditions. The alarm shall be equipped with a manual means, such as touchpad or switch, to temporarily deactivate the alarm for a single opening. Such deactivation shall last no more than 15 seconds. In dwellings not required to be accessible Type B units, the deactivation switch shall be located 54 inches (1372 mm) or more above the threshold of the door. In dwellings required to be accessible Type B units, the deactivation switch(es) shall be located at 48 inches (1219 mm) above the threshold of the door.
2. The swimming pool shall be equipped with a power safety cover which complies with ASTM F 1346.
3. The door providing access to the swimming pool from the dwelling shall open inward, away from the swimming pool, and shall be self-closing and have a self-latching device. The release mechanism of the self-latching device shall be located no less than 54 inches (1372 mm) from the bottom of the door. In dwellings required to be accessible Type B units, the release mechanism shall be located at 48 inches (1219 mm) above the threshold of the door.
3109.5.1.9 Pool structure as barrier.
Where an above-ground private swimming pool structure is used as a barrier or where the barrier is mounted on top of the pool structure, and the means of access is a ladder or steps, then the ladder or steps either shall be capable of being secured, locked or removed to prevent access, or the ladder or steps shall be surrounded by a barrier that meets the requirements of Sections 3109.5.1.1 through 3109.5.1.8. Where the ladder or steps are secured, locked or removed, any opening created shall not allow the passage of a 4-inch-diameter (102 mm) sphere.
3109.5.2 Indoor swimming pools.
Walls surrounding indoor private swimming pools shall not be required to comply with Section 3109.5.1.8.
3109.5.3 Prohibited locations.
Barriers shall be located so as to prohibit permanent structures, equipment or similar objects from being used to climb the barriers.
3109.5.4 Construction requirements.
Private swimming pools shall be constructed so as to be water tight and easily cleaned. They shall be built of nonabsorbent materials with smooth surfaces and shall be free of open cracks and open joints.
3109.5.4.1 Walls.
The walls of swimming pools shall be vertical for not less than the top 30 inches (762 mm) below the normal water level. The junctions between the side walls and the bottom shall be coved. A swimming pool overflow shall be provided meeting the requirements of the New York City Plumbing Code.
3109.5.4.2 Bottom slopes.
The bottom of the swimming pool shall slope downward toward the main drains. The slope in shallow areas with depths less than 5 feet (1524 mm) shall not exceed 1 unit vertical in 12 units horizontal (8-percent slope). In portions of the swimming pool with depth greater than 5 feet (1524 mm), the slope shall not be steeper than 1 unit vertical in 3 units horizontal (33-percent slope).
3109.5.4.3 Ladders.
There shall be a ladder or steps with handrails at the deep end and at the shallow end of every swimming pool. Ladders and steps shall have no-slip treads. All ladders shall be rigidly installed and shall be constructed of corrosion-resistant materials.
3109.5.4.4 Walkways.
Every swimming pool shall have a walkway not less than 5 feet (1524 mm) wide around its entire perimeter. The walkway shall have a nonslip surface and shall be constructed to drain away from the swimming pool.
3109.5.4.5 Handholds.
Every swimming pool shall be constructed so that either the overflow gutter, if provided, or the tops of the side walls afford a continuous handhold for bathers.
3109.5.4.6 Markings.
Permanent markings showing the depth of the shallow end, break points, diving depth and deep end shall be provided so as to be visible from both inside and outside the swimming pool.
3109.5.4.7 Diving boards and towers.
Diving towers shall be rigidly constructed and permanently anchored. The depth of the water below a diving board shall be not less than 102 inches (2591 mm) for a board 39 inches (991 mm) or less above the water. For a diving board more than 39 inches (991 mm) and not more than 118 inches (2997 mm) above the water, the depth of the water below the board shall be not less than 144 inches (3658 mm). For a diving board or platform more than 118 inches (2997 mm) above the water, the depth of the water below the board shall be not less than 192 inches (4877 mm). Indoor swimming pools shall provide not less than 144 inches (3658 mm) overhead clearance above all diving boards.
3109.6 Temporary barriers.
An outdoor swimming pool, including an in-ground, above ground or on-ground pool, hot tub or spa shall be surrounded by a temporary barrier during installation or construction. Such barrier shall remain in place until a permanent fence in compliance with Section 3109.4 is provided for public swimming pools, or a barrier in compliance with Section 3109.5 is provided for residential private pools.
Exceptions:
1. Above-ground or on-ground residential swimming pools where the pool structure is the barrier in compliance with Section 3109.
2. Spas or hot tubs with a safety cover which complies with ASTM F 1346, provided that such safety cover is in place during the period of installation or construction of such hot tub or spa. The temporary removal of a safety cover as required to facilitate the installation or construction of a hot tub or spa during periods when at least one person engaged in the installation or construction is present is permitted.
3109.6.1 Height.
The top of the temporary barrier shall be not less than 48 inches (1219) above grade measured on the side of the barrier which faces away from the swimming pool.
3109.6.2 Replacement by a permanent barrier.
A temporary barrier shall be replaced by a complying permanent barrier within either of the following periods:
1. 90 days of the date of issuance of the building permit for the installation or construction of the swimming pool; or
2. 90 days of the date of commencement of the installation or construction of the swimming pool.
3109.6.2.1 Replacement extension.
Subject to the approval of the code enforcement official, the time period for completion of the permanent barrier may be extended for good cause, including, but not limited to, adverse weather conditions delaying construction.
Section BC 3110. Automatic Vehicular Gates
3110.1 General.
Automatic vehicular gates shall comply with the requirements of Sections 3110.2 through 3110.4 and other applicable sections of this code.
3110.2 Definition.
The following term is defined in Chapter 2:
VEHICULAR GATE.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
3110.3 Vehicular gates intended for automation.
Vehicular gates intended for automation shall be designed, constructed and installed to comply with the Class of gate in accordance with the requirements of ASTM F 2200.
3110.3.1 Entrapment protection.
Defined Classes of gates shall be subject to the entrapment protection provisions per UL 325.
3110.4 Vehicular gate operators.
Vehicular gate operators, when provided, shall be listed in accordance with UL 325.
Section BC 3111. Sidewalk Cafes
3111.1 General.
Sidewalk cafes provided beyond the building line shall comply with the requirements of this section, the New York City Zoning Resolution, the Commissioners of the Department of Consumer and Worker Protection and Department of Transportation, and with the projection limitations of Chapter 32 of this code.
(Am. L.L. 2020/080, 8/28/2020, eff. 8/28/2020)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2020/080.
3111.2 Enclosures.
Enclosed sidewalk cafes shall be constructed of noncombustible material. The walls of such enclosures shall not extend more than 8 feet (2438 mm) above the sidewalk. Light transmitting plastic glazing complying with Section 2606 shall be permitted as glazing within such walls. Light-transmitting plastic skylight glazing complying with Section 2610 may be installed in the roofs of such enclosures.
3111.3 Awnings.
Awnings supported entirely from the building may be placed over unenclosed sidewalk cafes provided they are not less than 8 feet (2438 mm) clear above the sidewalk and within the limits specified by the Commissioner of the Department of Consumer and Worker Protection. Such awnings shall be in compliance with Section 3105 of this code.
(Am. L.L. 2020/080, 8/28/2020, eff. 8/28/2020)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2020/080.
3111.4 Obstructions prohibited.
No part of any awning, enclosure, fixture, equipment or removable platform of a sidewalk cafe shall be located:
1. Beneath a fire escape so as to obstruct operation of fire escape drop ladders or counter-balanced stairs;
2. So as to obstruct any exit from a building;
3. So as to obstruct any cellar access hatch or areaway;
4. So as to interfere with any vent or other mechanical ventilation outlet or inlet; or
5. So as to interfere with or obscure any standpipe connections, hydrant or associated signage in any way that would hinder its use by the fire department.
Exception: Upon special application, the commissioner may permit an easily removable, prominently designated platform, designed in accordance with Section 3111.5, to cover a cellar entrance or areaway that is not used as a required means of egress.
3111.5 Removable platforms.
Removable platforms of sidewalk cafes shall be constructed in accordance with the requirements of this section.
3111.5.1 Continuity.
Removable platforms shall be constructed to provide for a continuous unbroken and level floor without openings or cracks so as to prevent any material or liquid from falling through to the area beneath.
3111.5.2 Maintenance.
No papers, trash or other materials may be permitted to accumulate in the area beneath the floor of any removable platform.
3111.6 Accessibility.
Sidewalk cafes and access thereto shall comply with Chapter 11.
3111.7 Assembly seating.
Unless separated from seating inside the building by fire partitions complying with Section 713, the seating for enclosed sidewalk cafes shall be added to that inside the building in order to determine whether a place of assembly certificate of operation is required.
3111.8 Rules.
In addition to the requirements specified herein, the commissioner may promulgate such additional rules necessary to secure safety.
Section BC 3112. Fences
3112.1 Permitted heights.
Fences are permitted to be erected to a maximum height of 10 feet (3048 mm) above the ground.
Exceptions:
1. In residence districts, as established by the New York City Zoning Resolution, fences are permitted to be erected to a maximum height of 4 or 6 feet (1829 mm) above the ground, depending upon its location on the zoning lot.
2. Fences in residence districts used in conjunction with nonresidential buildings and public playgrounds, excluding buildings accessory to dwellings, are permitted to be erected to a maximum height of 15 feet (4572 mm) above the ground.
3. Higher fences may be permitted by the commissioner where required for the enclosure of public playgrounds, school yards, parks, and similar public facilities.
Section BC 3113. Photovoltaic Panels and Modules
3113.1 General.
Photovoltaic panels and modules shall comply with the requirements of this code, the New York City Electrical Code, the Zoning Resolution and the New York City Fire Code.
3113.1.1 Rooftop-mounted photovoltaic panels and modules.
Photovoltaic panels and modules installed on a roof or as an integral part of a roof assembly shall comply with the requirements of the New York City Fire Code and Chapter 15 of this code.
Section BC 3114. Large Wind Turbines
3114.1 General.
Large wind turbines shall be designed and constructed in accordance with this section.
3114.2 Definitions.
The following terms are defined in Chapter 2:
LARGE WIND TURBINE.
LARGE WIND TURBINE TOWER.
3114.3 Design standards.
A large wind turbine shall be designed in accordance with standards adopted by rules of the commissioner. Such standards shall include but need not be limited to standards relating to the design of large wind turbines that are developed by the American Wind Energy Association, the New York State Energy Research and Development Authority, the California Energy Commission, the European Wind Turbine Certification, the British Wind Energy Association, the International Electrotechnical Commission, the National Renewable Energy Laboratory, or the Underwriters Laboratory.
3114.4 Wind speed.
A large wind turbine shall be designed to withstand winds of up to and including 130 mph (58.1 m/s) or such higher wind load as may be specified in this code or the design standard for such turbine pursuant to Section 3114.3.
3114.5 Brakes and locks.
Where necessary for public safety, the commissioner may require that a large wind turbine shall be equipped with a redundant braking system and a passive lock, including aerodynamic overspeed controls and mechanical brakes.
3114.6 Visual appearance.
A large wind turbine shall be white, off-white, grey, or another non-obtrusive color specified by the commissioner.
3114.7 Access.
Access to a large wind turbine shall be limited as follows:
1. Access to electrical components of a large wind turbine shall be prevented by a lock.
2. A large wind turbine tower shall not be climbable, except by authorized personnel, up to a height of 10 feet (3048 mm) measured from the base of such tower.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
3114.8 Noise.
A large wind turbine shall be designed to comply with the sound level limit of Section 24-232.1 of the Administrative Code.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
3114.9 Shadow flicker.
The commissioner shall by rule establish shadow flicker limitations for large wind turbines for the purpose of limiting, to the extent practicable, such flicker on buildings adjacent to such turbines.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
3114.10 Signal interference.
The commissioner shall establish rules governing large wind turbines for purpose of minimizing, to the extent practicable, interference by such turbines with radio, telephone, television, cellular or other similar signals.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
3114.11 Setback.
No part of a large wind turbine or large wind turbine tower shall be located within a horizontal distance of a property line that is equal or less than one-half the height of such turbine, including such tower, measured from the base of such tower or, if there is no such tower, the base of such turbine.
Exception: A turbine or tower for which each owner of property adjacent to such property line has entered into a written agreement providing that such turbine or tower or a part thereof may be located closer to such property line than this section allows.
(L.L. 2019/098, 5/19/2019, eff. 11/15/2019; Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
Section BC 3115. Small Wind Turbines
3115.1 General.
In addition to other applicable requirements in this code, other law or rule, and established by the commissioner, small wind turbines shall be designed and constructed in accordance with this section.
3115.2 Definitions.
The following terms are defined in Chapter 2:
SMALL WIND TURBINE.
SMALL WIND TURBINE TOWER.
3115.3 Design standards.
A small wind turbine shall be designed in accordance with standards adopted by rules of the commissioner. Such standards shall include but need not be limited to standards relating to the design of small wind turbines that are developed by the American Wind Energy Association, the New York State Energy Research and Development Authority, the California Energy Commission, the Small Wind Certification Council, the British Wind Energy Association, the International Electrotechnical Commission, the National Renewable Energy Laboratory, or the Underwriters Laboratory.
3115.4 Wind speed.
A small wind turbine shall be designed to withstand winds of up to and including 130 mph (58.1 m/s) or such higher wind load as may be specified in this code or the design standard for such turbine pursuant to Section 3113.3.
3115.5 Brakes and locks.
Where deemed necessary by the commissioner, a small wind turbine shall be equipped with a redundant braking system and a passive lock, including aerodynamic overspeed controls and mechanical brakes.
3115.5.1 Locking before hurricane or strong wind conditions.
If a hurricane or strong wind conditions are expected, the commissioner may order that small turbines equipped with passive locks be stopped and locked.
3115.6 Visual appearance.
A small wind turbine shall be white, off-white, grey, or another non-obtrusive color specified by the commissioner.
3115.7 Lighting.
A small wind turbine shall not be artificially lighted.
Exception: Lighting that is required by this code or other applicable laws or rules, provided that such lighting is shielded in accordance with rules promulgated by the commissioner.
3115.8 Access.
Access to a small wind turbine shall be limited as follows:
1. Access to electrical components of a small wind turbine shall be prevented by a lock.
2. A small wind turbine tower shall not be climbable, except by authorized personnel, up to a height of 10 feet (3048 mm) measured from the base of such tower.
3115.9 Noise.
A small wind turbine shall be designed in accordance with applicable sections of the New York City Noise Control Code.
3115.10 Shadow flicker.
The commissioner shall by rule establish shadow flicker limitations for small wind turbines for the purpose of limiting, to the extent practicable, such flicker on buildings adjacent to such turbines.
3115.11 Signal interference.
The commissioner shall establish rules governing small wind turbines for purpose of minimizing, to the extent practicable, interference by such turbines with radio, telephone, television, cellular or other similar signals.
3115.12 Setback.
No part of a small wind turbine or small wind turbine tower shall be located within a horizontal distance of a property line that is equal or less than one-half the height of such turbine, including such tower, measured from the base of such tower or, if there is no such tower, the base of such turbine.
Exception: Turbines or towers for which each owner of property adjacent to such property line has entered into a written agreement providing that such turbine or tower or a part thereof may be located closer to such property line than this section allows.
(L.L. 2018/105, 5/26/2018, eff. 11/22/2018)
Section BC 3201. General
3201.1 Scope.
The provisions of this chapter shall govern the encroachment of structures into the public right-of-way.
3201.1.1 Encroachments removable.
All encroachments permitted beyond the street line by the provisions of this chapter shall be constructed so that they may be removed at any time without endangering the structural safety or fire safety of the building except that footings as permitted under Section 3202.1.1 of this code need not be removable.
3201.2 Measurement.
The projection of any structure or portion thereof shall be the distance measured horizontally from the lot line to the outermost point of the projection.
3201.3 Other laws.
The provisions of this chapter shall not be construed to permit the violation of other laws regulating the use and occupancy of public property.
3201.3.1 Restrictions on construction and projections on certain streets, parkways, boardwalks and beaches.
Notwithstanding the provisions of this chapter, it shall be unlawful to build, erect, or make areaways, steps or other encroachments or projections prohibited by Sections 19-131, 19-132, 19-135, 18-109, 18-112 and 18-113 of the Administrative Code.
3201.4 Drainage.
Drainage water collected from a roof, awning, canopy or marquee, other than canvas and flexible material, and condensate from mechanical equipment shall not flow over a public walking surface.
3201.5 Permission revocable.
Any permission, expressed or implied, permitting the construction of encroachments within the area of the street under the provisions of this chapter shall be revocable, except footings as permitted under Section 3202.1.1.
3201.6 Existing projections.
Any part of a building that projects beyond a street line on January 1, 1938 may be maintained as constructed until its removal is directed in accordance with applicable law.
3201.7 Alteration of existing encroachments.
Alterations to existing encroachments beyond the street line may be permitted in whole or in part, provided that such alterations conform with the requirements of this chapter.
3201.7.1 Fences, guards and railings.
Elements of existing fences, guards and railings shall not be increased in height, thickness, spacing or opacity.
Exceptions:
1. Fences, guards and railings that are required to comply with other requirements of this code, including Chapters 10 and 16.
2. Buildings or structures designated by the Landmarks Preservation Commission, where such fences, guards or railings are approved by the Landmarks Preservation Commission.
3201.8 Definitions.
The following terms are defined in Chapter 2:
AREAWAY.
CURB LINE.
FOOTING.
PROJECTING SIGN.
SIGN.
STREET.
STREET LINE.
VAULT.
3201.9 Department of Transportation approval.
Any encroachment into the public right-of-way that exceeds the limitation provided for in this chapter shall require the approval of the Department of Transportation.
Section BC 3202. Encroachments
3202.1 Encroachments below grade.
Encroachments below grade shall comply with Sections 3202.1.1 through 3202.1.6.
3202.1.1 Footings.
Exterior wall and column footings may be constructed to project beyond the street line not more than 12 inches (305 mm), provided that the top of the footing is not less than 8 feet (2438 mm) below the ground or sidewalk level. Foundation walls required to support permitted projections may be constructed to project not more than the permitted projection beyond the street line.
3202.1.1.1 Footings for temporary barriers or shields in flood hazard areas or shaded X-Zones.
In flood hazard areas or shaded X-Zones, continuous footings for the support and attachment of temporary, removable dry floodproofing barriers or shields may be constructed to project beyond the street line not more than 12 inches (305 mm) both at grade and below grade.
3202.1.2 Vaults.
Vaults may be permitted in accordance with the New York City Charter and Title 19 of the Administrative Code. Such vaults shall comply with the provisions of this code and other applicable laws and rules.
3202.1.3 Areaways.
Areaways shall be protected by grates, guards or other approved means, subject to approval by the Commissioner of the Department of Transportation.
3202.1.4 Tunnels between buildings.
Tunnels connecting buildings, and projecting beyond street lines, may be constructed subject to the approval of the Commissioner of the Department of Transportation. Such tunnels shall comply with the provisions of this code and other applicable laws and regulations.
3202.1.5 Sidewalk supports.
Exterior foundation walls are permitted to be constructed with a ledge that projects beyond the street line not more than 4 inches (102 mm) to support sidewalk construction, provided that:
1. the top of the ledge is not more than 8 inches (203 mm) below the ground or sidewalk level; and
2. bottom of the ledge is not more than 24 inches (610 mm) below the ground or sidewalk level.
3202.1.6 Insulation.
Insulation shall be permitted to encroach into the public right of way not more than 6 inches (152 mm) beyond the face of the structural element being insulated, in accordance with the following:
1. The insulation is necessary to comply with the New York City Energy Conservation Code; or
2. In existing buildings, the installation of the insulation will reduce greenhouse gas emissions, as demonstrated by achieving not less than a thirty percent reduction of the existing thermal envelope UA (the area-weighted average of assembly u-factors, as defined in the New York City Energy Conservation Code) as compared to the improved thermal envelope UA. For the purposes of calculating the reduction in the thermal envelope UA, the improved thermal envelope UA is the area-weighted average of the proposed opaque U-factor times the alteration area of the opaque wall assembly compared to the area-weighted average UA of the existing wall assembly. The UA calculation shall be performed using a method consistent with the New York City Energy Conservation Code.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
3202.2 Encroachments above grade.
Encroachments into the public right-of-way above grade shall be prohibited except as provided for in Sections 3202.2.1 through 3202.2.5.
3202.2.1 Encroachments subject to the area limitations.
Encroachments that are subject to area limitations are those elements listed in Sections 3202.2.1.1 through 3202.2.1.9, generally of an architectural character, that form an integral part of the building facade. The aggregate area of all such elements constructed to extend beyond the street line shall not exceed 10 square feet (0.93 m 2 ) within any 10 feet (3048 mm) by 10 feet (3048 mm) square area of wall. The area of any such projection shall be measured at that vertical plane, parallel to the wall, in which the area of the projection is greatest. This plane of measurement may be at the street line, the line of maximum projection or any point in between. For the purpose of measuring the projected area of a balcony, air spaces of less than 6 inches (152 mm) between closely spaced railing or guards elements shall contribute to the area of the projection.
Exceptions:
1. The aggregate area of all elements subject to area limitations that includes a balcony or associated railings and brackets shall not exceed 24 square feet (2.2 m 2 ) in any 240 square foot (22.3 m 2 ) area on a given story.
2. The aggregate area of elements on existing buildings or structures designated by the Landmarks Preservation Commission as landmarks or within historic districts shall not be limited provided that such elements are approved by the Landmarks Preservation Commission.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2012/028.
3202.2.1.1 Entrance details.
Entrance details, including steps and doors when fully open, may be constructed to project beyond the street line not more than 18 inches (457 mm). Entrance steps that project beyond the street line shall be guarded at each end by railings at least 3 feet (914 mm) high or by other members of the entrance detail providing equivalent protection.
3202.2.1.2 Architectural details.
Details such as cornices, eaves, bases, sills, headers, band course, opening frames, rustications, applied ornament or sculpture, grilles, windows when fully open, air conditioning units, and other similar elements may be constructed:
1. To project not more than 4 inches (102 mm) beyond the street line when less than 10 feet (3048 mm) above the ground or sidewalk level.
2. To project not more than 10 inches (254 mm) beyond the street line when more than 10 feet (3048 mm) above the ground or sidewalk level.
Exceptions:
1. Replacement or restoration of historical architectural details that are, or were:
1.1. Located more than 10 feet (3048 mm) above the sidewalk and that project more than 10 inches (254 mm), on existing buildings or structures designated by the Landmarks Preservation Commission, may be permitted provided they do not exceed the historic projections and provided that they are approved by the Landmarks Preservation Commission; or
1.2. Located 10 feet (3048 mm) or less above the sidewalk, and that project more than 4 inches (102 mm), on existing buildings or structures designated by the Landmarks Preservation Commission, may be permitted provided they do not exceed the historic projections and provided that they are approved by the Landmarks Preservation Commission, and further provided that if the projection exceeds 18 inches (457 mm), the applicant demonstrates to the Department of Transportation's satisfaction that the replacement or restoration will not adversely impact the use of the public right of way.
2. New architectural details on new or existing buildings, additions or structures subject to the jurisdiction of the Landmarks Preservation Commission, that are more than 10 feet (3048 mm) above the sidewalk and that project more than 10 inches (254 mm) and no more than 3 feet (914 mm), may be permitted provided that the Landmarks Preservation Commission finds that the proposed detail is appropriate to the historic character of the historic district or landmarked building, structure or site.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2012/028 and L.L. 2023/077.
3202.2.1.3 Balconies.
Balconies, including railings and supporting brackets, no parts of which are less than 10 feet (3048 mm) above the ground or sidewalk level, may be constructed to project not more than 2 feet 6 inches (762 mm) beyond the street line. When permitted by the provisions of this code, fire escapes that are part of a required exit may be constructed to project not more than 4 feet 6 inches (1372 mm) beyond the street line provided no part, including any movable ladder or stair, is lower than 10 feet (3048 mm) above the ground or sidewalk level when not in use.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2012/028.
3202.2.1.4 Marquees.
Marquees may be constructed to project beyond the street line provided that they comply with Section 3106 and Sections 3202.2.1.4.1 through 3202.2.1.4.5.
3202.2.1.4.1 Height.
Marquees shall receive structural support only from the building, and shall be at least 10 feet (3048 mm) above the ground level or sidewalk.
3202.2.1.4.2 Projection.
Marquees shall project no closer to the curb line than 2 feet (610 mm).
3202.2.1.4.3 Thickness.
Marquees shall be no thicker nor shall the fascia be higher than 3 feet (914 mm) when measured vertically from its lowest to its highest point.
3202.2.1.4.4 Dimensions.
Dimensions shall include all decoration, but shall exclude any tension supports suspending the marquee from the wall.
3202.2.1.4.5 Occupancy restrictions.
Marquees may be erected on:
1. Buildings of an essentially public nature including but not limited to the following:
1.1 Public buildings, including schools.
1.2. Theatres.
1.3. Hotels.
1.4. Terminals.
1.5. Large department stores.
1.6. Supermarkets.
1.7. Multiple dwellings.
1.8. Office buildings.
2. Warehouses or markets in one of the following established market areas:
2.1. Bronx.
2.1.1. Edgewater Road and Halleck Street between Lafayette Avenue and East Bay Avenue.
2.1.2. Lafayette Avenue between Edgewater Road and the Bronx River.
2.1.3. East Bay Avenue between Halleck Street and the Bronx River.
2.1.4. Hunt's Point Avenue between East Bay Avenue and the Bronx River.
2.1.5. Exterior Street between East 149th Street and East 157th Street.
2.1.6. Cromwell Avenue between East 150th Street and East 153rd Street.
2.1.7. East 150th Street between Exterior Street and River Avenue.
2.1.8. Westchester Avenue between St. Ann's Avenue and Bergen Avenue.
2.1.9. Brook Avenue between East 150th Street and East 156th Street.
2.1.10. Bergen Avenue between East 149th Street and East 156th Street.
2.1.11. East 152nd Street between Bergen Avenue and Brook Avenue.
2.1.12. East 153rd Street between Bergen Avenue and Brook Avenue.
2.2. Brooklyn.
2.2.1. North 6th Street between Berry Street and Wythe Avenue.
2.3. Manhattan.
2.3.1. John Street to Fulton Street between South Street and Front Street.
2.3.2. Fulton Street to Dover Street between South Street and Water Street.
2.3.3. South Street and Front Street between John Street and Dover Street.
2.3.4. Water Street between Fulton Street and Dover Street.
2.3.5. Horatio Street to West 14th Street between West Street and 9th Avenue.
2.3.6. West Street, Washington Street, Greenwich Street
2.3.7. 9th Avenue and 10th Avenue between Horatio Street and West 14th Street.
2.3.8. West 16th Street, north side, and West 17th Street, south side, between 10th Avenue and 11th Avenue.
2.3.9. West 24th Street to West 26th Street, south side, between 11th Avenue and 12th Avenue.
2.3.10. West 27th Street, north side, to West 28th Street between 11th Avenue and 12th Avenue.
2.3.11. 12th Avenue and St. Claire Place between 125th Street and 132nd Street.
2.3.12. 12th Avenue, west side, between 132nd Street and 133rd Street.
2.4. Queens.
2.4.1. 95th Avenue, north side, between Sutphin Boulevard and 148th Street.
3202.2.1.4.6 Change of occupancy.
When the occupancy or use of a building with a marquee is changed to an occupancy or use for which a projecting marquee is not permitted, the marquee shall be removed.
Exception: For buildings subject to the jurisdiction of the Landmarks Preservation Commission, Section 3202.2.1.4.6 shall not apply when the Landmarks Preservation Commission makes a determination that the removal of the marquee would be inappropriate to the architectural character of the building or historic district.
3202.2.1.4.7 Other agency approvals.
An applicant wishing to erect a marquee shall provide proof that the Commissioners of the Departments of Transportation, Consumer and Worker Protection, and Environmental Protection have not permitted the use of a space or structure on or under the sidewalk beneath the proposed marquee in such a manner that the construction of the proposed marquee shall interfere with the removal or repair of any such permitted use or structure.
(Am. L.L. 2020/080, 8/28/2020, eff. 8/28/2020)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2020/080.
3202.2.1.5 Light fixtures.
Light fixtures that are supported entirely from the building may be constructed to project not more than 2 feet (610 mm) beyond the street line, provided no part of the fixture is less than 8 feet (2438 mm) above the ground or sidewalk level.
3202.2.1.6 Flagpoles.
Flagpoles that are supported entirely from the building may be constructed to project not more than 18 feet (5486 mm) beyond the street line, but not closer than 2 feet (610 mm) to the curb line, provided that no part of the flagpole is less than 15 feet (4572 mm) above the ground or sidewalk level.
3202.2.1.7 Wall signs.
Wall signs may be constructed to project not more than 12 inches (305 mm) beyond the street line when conforming to the requirements of this code and Section H111 of Appendix H.
3202.2.1.8 Projecting signs.
All permitted projecting signs may be constructed to project not more than 10 feet (3048 mm) beyond the street line, but not closer to the curb line than 2 feet (610 mm), when conforming to the requirements of this code and Section H112 of Appendix H, and provided that no part of the sign is less than 10 feet (3048 mm) above the ground or sidewalk level.
Exceptions: Permanent projecting signs are prohibited on buildings in the areas indicated below:
1. Borough of Manhattan.
1.1. Projecting signs. No permanent projecting sign shall be erected on any building on:
1.1.1. 5th Avenue between Washington Square north and 110th Street;
1.1.2. 34th Street between Park Avenue and 7th Avenue;
1.1.3. Madison Avenue between 23rd Street and 96th Street;
1.1.4. 57th Street between Lexington Avenue and Broadway;
1.1.5. Vanderbilt Avenue between 42nd Street and 47th Street;
1.1.6. Park Avenue between 32nd Street and 40th Street;
1.1.7. Park Avenue between 45th Street and 96th Street;
1.1.8. 33rd Street between Lexington Avenue and 5th Avenue;
1.1.9. 35th through 41st Streets between Lexington Avenue and 5th Avenue;
1.1.10. 43rd through 56th Streets between Lexington Avenue and 5th Avenue;
1.1.11. 58th Street between Lexington Avenue and 5th Avenue;
1.1.12. 60th Street between Lexington Avenue and 5th Avenue;
1.1.13. Nassau Street between Wall Street and Frankfort Street; or
1.1.14. John Street between Broadway and William Street.
1.2. Illuminated projecting signs. No permanent illuminated projecting sign shall be erected on any building on:
1.2.1. 72nd Street between Central Park West and River Drive.
2. Borough of Brooklyn.
2.1. Projecting signs. No permanent projecting sign shall be erected on any building on:
2.1.1. Fulton Street between Flatbush Avenue and Joralemon Street and Willoughby Street.
2.2. Illuminated projecting signs. No permanent illuminated projecting sign shall be erected on any building on:
2.2.1. Fulton Street between Flatbush Avenue and Prospect Street and Henry Street;
2.2.2. Washington Street between Myrtle Avenue and Prospect Street;
2.2.3. Court Street between Fulton Street and Livingston Street;
2.2.4. Pierrepont Street between Fulton Street and Clinton Street;
2.2.5. Montague Street between Court Street and Clinton Street;
2.2.6. Remsen Street between Court Street and Clinton Street; or
2.2.7. Joralemon Street between Court Street and Clinton Street.
3202.2.1.9 Sun control devices.
Sun control devices constructed in accordance with Section 3105 and supported entirely from the building may project beyond the street line not more than 2 feet 6 inches (762 mm), provided that no part of the sun control device is less than 8 feet (2438 mm) above the ground or sidewalk level. Any portion of a sun control device that is located over a sidewalk vault and is more than 10 inches (254 mm) beyond the street line and less than 40 feet (12 192 mm) above the ground or sidewalk shall be removable or retractable to less than 10 inches (254 mm) beyond the street line.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2012/028 and L.L. 2023/077.
3202.2.2 Encroachments not subject to area limitations.
3202.2.2.1 Ramps.
When a building erected prior to December 6, 1969 is altered to provide access to individuals who use wheelchairs, ramps constructed to provide such access may, with the approval of the commissioner, project beyond the street line for a distance of not more than 44 inches (1118 mm). Ramps shall comply with the applicable provisions of Chapter 11.
3202.2.2.2 Bridges between buildings.
Bridges connecting buildings, and projecting beyond street lines may be permitted in accordance with applicable law. Such bridges shall be of a construction class that is at least equal to the higher class of the two buildings connected, and shall otherwise comply with the provisions of this code and other applicable laws and rules.
3202.2.2.3 Flood shield supports.
In flood hazard areas or shaded X-Zones, permanent attachments to building facades necessary for the support and attachment of temporary, removable dry floodproofing barriers or shields may be constructed to project beyond the street line for a distance of not more than 6 inches (152 mm).
3202.2.2.4 Curb cuts.
The lowering of any curb or the change of grade of any sidewalk for the purpose of providing a driveway across such curb or sidewalk shall be constructed in accordance with the specifications prescribed in Section 406.10.
3202.2.2.4.1 Curb cut removal.
Vehicular access curb cuts that can no longer serve as vehicular access across a curb or sidewalk, including where an existing building served by such a curb cut is demolished, shall be removed and the curb and sidewalk shall be restored in accordance with standards of the Department of Transportation. The commissioner may order such removal and restoration. The commissioner shall limit the length of any curb cut for the purpose of providing a driveway across such curb or sidewalk, when in the opinion of the commissioner the actual use or intended use of such driveway would endanger the public. Where the vehicular use of such driveway, in the opinion of the commissioner is dangerous to the public, the commissioner shall order the owner to discontinue use of such driveway and restore the curb and sidewalk in accordance with standards of the Department of Transportation. Upon the failure of the owner to comply with any of the orders provided for in Section 3202.2.2.4, in such cases where the restoration of such curb cuts are needed to facilitate department of transportation work, the commissioner may inform the commissioner of transportation of such failure to comply and may request the cooperation of the commissioner of transportation acting under his or her authority pursuant to Section 2903(b)(7) of the New York City Charter in the enforcement of this section.
3202.2.3 Awnings.
Awnings constructed in accordance with Section 3105 and supported entirely from the building may project beyond the street line as follows:
3202.2.3.1 Store front awnings.
Store front awnings may project beyond the street line not more than 8 feet (2428 mm), provided no part of the awning is less than 8 feet (2438 mm) above the ground or sidewalk level, except for a flexible valance which may be not less than 7 feet (2134 mm) above the ground or sidewalk level, and provided that the awning box or cover does not project more than 12 inches (305 mm).
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
3202.2.3.2 Awnings over windows or doors.
Awnings over windows or doors may project beyond the street line not more than 5 feet (1524 mm), provided that no part of the awning is less than 8 feet (2438 mm) above the ground or sidewalk level.
3202.2.4 Fire department connections, caps or plugs.
Fire department connection swivels, caps and plugs including test headers shall be permitted to project beyond the street line as provided for in NFPA 14, as amended by Appendix Q of this code.
3202.2.5 Exterior wall covering systems for prior code buildings.
For prior code buildings, exterior insulation and associated cladding systems (i.e. rain screens, EIFS, etc.) that comply with Chapter 14 may be applied to the entire facade of a building and may project not more than 8 inches (203 mm) beyond the street line, in accordance with the following:
1. The exterior wall covering system is necessary to comply with the New York City Energy Conservation Code; or
2. In prior code buildings, the installation of the insulation will reduce greenhouse gas emissions, as demonstrated by achieving not less than a thirty percent reduction of the existing thermal envelope UA (the area-weighted average of assembly u-factors, as defined in the New York City Energy Conservation Code) as compared to the improved thermal envelope UA. For the purposes of calculating the reduction in the thermal envelope UA, the improved thermal envelope UA is the area-weighted average of the proposed opaque U-factor times the alteration area of the opaque wall assembly compared to the area-weighted average UA of the existing wall assembly. The UA calculation shall be performed using a method consistent with the New York City Energy Conservation Code.
Exceptions:
1. A veneer may be applied to the entire facade of a building erected before December 6, 1968, provided such veneer does not project more than 4 inches (102 mm) beyond the street line.
2. Exterior wall covering systems installed in accordance with this section on prior code buildings may project not more than 10 inches (254 mm) beyond the street, provided they are located more than 10 feet (3048 mm) above grade.
3. The department may approve the installation of exterior wall covering systems in accordance with this section that project more than 8 inches (203 mm) but not more than 12 inches (305 mm) beyond the street line provided they are substantiated with engineering calculations demonstrating need and practical difficulty, and provided that the applicant demonstrates to the Department of Transportation's satisfaction that the projection of the wall covering system will not adversely impact the use of the public right of way.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
3202.3 Temporary encroachments.
Encroachments of temporary nature shall comply with Sections 3202.3.1 through 3202.3.3.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
3202.3.1 Sidewalk cafes.
Enclosures for sidewalk cafes, where permitted by the Commissioner of the Department of Consumer Affairs pursuant to applicable law and constructed in compliance with Section 3111, may be constructed beyond the street line.
3202.3.2 Temporary storm enclosures.
Construction of temporary storm enclosures must comply with the requirements of this code, including the fire-resistance rating of the building to which it is appurtenant, and Chapter 11. Such enclosures may be permitted during the period between November 15 and the following April 15 and must be removed at the end of this period.
3202.3.2.1 Temporary storm enclosures for eating and drinking establishments.
Provided a minimum clear unobstructed sidewalk width of 5 feet is maintained, temporary storm enclosures for eating and drinking establishments with a projection of not more than 25 square feet (2.32 m 2 ) in area and door maneuvering clearances complying with Chapter 11, and related reference standards, including Section 404 (Doors and Doorways) of ICC A117.1, may be permitted.
3202.3.2.2 Temporary storm enclosures for other establishments.
Temporary storm enclosures projecting not more than 18 inches (457 mm) beyond the street line may be permitted at other establishments.
3202.3.3 Temporary flood shields, stairs and ramps in flood hazard areas and shaded X-Zones.
In flood hazard areas and shaded X-Zones, temporary flood shields, stairs and ramps shall comply with Sections G308.9 and G308.10 of Appendix G of the New York City Building Code and shall be permitted in accordance with plans approved by the department subject to the following conditions:
1. Such flood shields, stairs and ramps shall project no more than one foot (305 mm) beyond the street line.
2. Such flood shields, stairs and ramps shall be removed in a timely manner after a flood event.
Section BC 3301. General
This section has 5 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read Section BC 3301 at American Legal Publishing.
3301.1 Scope.
The provisions of this chapter shall govern the conduct of all construction or demolition operations with regard to the safety of the public and property. For regulations relating to the safety of persons employed in construction or demolition operations, OSHA standards shall apply.
3301.1.1 Responsibility for safety.
Nothing in this chapter shall be construed to relieve persons engaged in construction or demolition operations from complying with other applicable provisions of law, nor is it intended to alter or diminish any obligation otherwise imposed by law on any party engaged in a construction or demolition operation, including but not limited to the owner, construction manager, general contractor, subcontractors, material men, registered design professionals, or other party to engage in sound design and engineering, safe construction or demolition practices, including but not limited to debris removal, and to act in a reasonable and responsible manner to maintain a safe construction or demolition site.
3301.1.2 Fire code.
In addition to the requirements of this chapter, construction or demolition operations shall also be conducted in conformance with the New York City Fire Code.
3301.1.3 Manufacturer specifications.
See Section 3301.6.1.
3301.1.4 Sizes.
All sizes and dimensions prescribed in this chapter are minimum requirements, unless otherwise specified. Lumber sizes are nominal or commercial except where stated otherwise.
3301.2 Safety measures and safeguards.
Contractors, construction managers, and subcontractors engaged in construction or demolition operations shall institute and maintain all safety measures required by this chapter and provide all equipment or temporary construction installations necessary to safeguard the public and property affected by such contractor's operations.
3301.3 Site safety managers, coordinators and construction superintendents.
A site safety manager or site safety coordinator must be designated and present at the construction or demolition of a major building in accordance with Section 3310. A construction superintendent is required for the construction or demolition of buildings as identified in Section 3301.13.3.
3301.4 Inspection.
Structures, temporary construction installations, materials, operations, and equipment shall be inspected as required by this code, and records of such inspections shall be maintained as required by this code.
3301.4.1 Inspection of equipment where the code does not specifically require an inspection.
Where this code does not specifically require an inspection, any equipment, except hand tools, that would affect the safety of the public or property when operated shall be inspected by a competent person designated by the contractor using the equipment before the equipment is used at the site and on a periodic basis thereafter throughout the duration of the job. The results of the inspection shall be documented in an inspection checklist signed and dated by the competent person who performed the inspection.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
3301.5 Unsafe conditions.
Any structure, temporary construction installation, material, operation, or equipment found to be defective or unsafe, and posing a risk to the public or property, shall be immediately secured and corrected, or removed from the site.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
3301.6 Manufacturer specifications, design, and capacity.
The permit holder, or where there is no permit holder, the contractor or other entity causing the work to be performed, shall ensure compliance with manufacturer specifications, design documents, and capacity restrictions in accordance with Sections 3301.6.1 through 3301.6.5 and other applicable sections of the code. Where there is a discrepancy between a manufacturer specification, design document, capacity restriction, or other applicable code section, the more stringent requirement shall apply.
3301.6.1 Manufacturer specifications.
During construction or demolition operations, structures, building systems or components, temporary construction installations, materials, and equipment shall be installed, removed, and utilized in accordance with the specifications of their manufacturer, where such specifications exist.
3301.6.2 Design requirements.
Whenever design is required by this chapter, the design shall be in accordance with the requirements of this code. This requirement does not alleviate any other design requirements imposed by law or the manufacturer.
3301.6.3 Designer.
Where design is required by this chapter, the design shall be executed by or under the supervision of a registered design professional, who shall cause his or her seal and signature to be affixed to such documents that may be required for the work
Exception: Where this chapter specifically indicates that the design may be executed by another individual.
3301.6.4 Capacity.
No structure, building system or component, temporary construction installation, material, or equipment, including any partially or fully completed element or section, shall be utilized in excess of its capacity.
3301.6.5 Design documents.
Whenever design is required by this chapter, the design shall be indicated in plans and specifications and other written, graphic and pictorial documents that are prepared or assembled for describing the design, location, physical characteristics, and other elements of the project. Design documents shall be complete and of sufficient clarity to indicate the location and entire nature and extent of the work proposed, and shall show in detail that the work conforms to the provisions of this code and other applicable laws and rules.
3301.7 Documents to be maintained on site.
Where this chapter requires documents, including but not limited to construction documents, submittal documents, shop drawings, inspection reports, logs, checklists, meeting records, pre-construction surveys, designation letters, site safety plans, fire safety and evacuation plans, tenant protection plans, occupant protection plans, or monitoring plans, copies of such documents shall be maintained at the site for the duration of the job and made available to the commissioner upon request. Copies of required construction documents or other design drawings shall also be maintained by the permit holder and the designer. Copies of required inspection records, including but not limited to reports, logs, or checklists, shall also be maintained by the permit holder and the entity that performed the inspection. Copies of required plans shall also be maintained by the permit holder and the entity that developed the plan. Copies of all other documents required by this chapter shall also be maintained by the permit holder.
3301.7.1 Other obligations.
Where this chapter requires documents to be maintained by another specified entity, such documents shall be maintained by such specified entity.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
3301.7.2 Manufacturer specifications.
Where compliance with manufacturer specifications is required by this chapter, copies of such manufacturer specifications shall be available at the site and made available to the commissioner upon request. Manufacturer specifications that can be readily downloaded from the manufacturer's website or that are stored in an electronic format acceptable to the commissioner shall satisfy the requirements of this section. A serial number, make and model number, or other similar identification shall be maintained in a legible condition on the item for which the manufacturer specification is required such that the identification can be used to match the item to the manufacturer specification.
Exception: Where this chapter specifically requires that the manufacturer specifications for a specific item be physically maintained at the site, downloadable or electronically formatted manufacturer specifications will not satisfy the accessibility and availability requirements of this section.
3301.8 Incidents and damage to adjoining property.
The department shall be notified immediately by the permit holder, or a duly authorized representative, of any incident at a construction or demolition site, or of any damage to adjoining property caused by construction or demolition activity at the site. Where required by Section 3301.13.11 or Section 3310.8.2.1, incidents or damage to adjoining property shall instead be reported by the construction superintendent or the site safety manager or coordinator.
3301.8.1 Additional notifications.
Nothing in this section shall diminish or relieve other notification requirements imposed by this chapter, including but not limited to, notifications by the site safety manager, site safety coordinator, concrete safety manager, or hoisting machine operator.
3301.8.2 Use and tampering prohibited.
Following an incident, no person shall permit any of the following without the permission of the commissioner, or without a lawful order from the New York city police or fire department:
1. Use or operation of any equipment or structure damaged or involved in the incident; or
2. Removal or alteration of any equipment, structure, material, or evidence related to the incident.
Exception: Immediate emergency procedures taken to secure structures, temporary construction installations, operations, or equipment that pose a continued imminent danger or to facilitate assistance for persons who are trapped or who have sustained bodily injury.
3301.9 Signs at a construction or demolition site.
Signs shall be posted at a construction or demolition site in accordance with Sections 3301.9.1 through 3301.9.8. It is the responsibility of the permit holder for the underlying construction or demolition work, or where there are no active permits, the building owner, to ensure such signs are posted and maintained at the site in accordance with Sections 3301.9.1 through 3301.9.8, and to ensure that such signs are updated in a timely fashion to reflect any revised information.
3301.9.1 Fence project information panel.
Where a site is enclosed with a fence in accordance with Section 3307.7, a project information panel meeting the requirements of Sections 3301.9.1.1 through 3301.9.1.6 shall be posted. Required project information panels shall be in place throughout the duration that the fence remains at the site.
Exception: Project information panels at government-owned sites or at sites with government funding may be modified in accordance with department rule.
3301.9.1.1 Project information panel content.
Project information panels shall contain the following information:
1. A rendering, elevation drawing, or zoning diagram of the building exterior that does not contain logos or commercially recognizable symbols;
2. A title line stating "Work in Progress:" and specifying the intended type(s) of zoning use(s) (e.g. Residential, Commercial, Manufacturing, Retail, Office, Hospital, School);
3. Anticipated project completion date;
4. The corporate name, address, and telephone number of the owner of the property;
5. Website address or phone number to contact for project information;
6. The corporate name and telephone number of the general contractor, or for a demolition site, the demolition contractor;
7. The statement, in both English and Spanish, "TO ANONYMOUSLY REPORT UNSAFE CONDITIONS AT THIS WORK SITE, CALL 311."; and
8. A copy of the primary project permit, with accompanying text "To see other permits issued on this property, visit: www.nyc.gov/buildings." The permit shall be laminated or encased in a plastic covering to protect it from the elements or shall be printed directly onto the project information panel.
Exception: A rendering, elevation drawing, or zoning diagram of the building exterior is not required for demolition projects.
3301.9.1.2 Posting of project information panels.
A project information panel shall be posted on the fence on each perimeter fronting a public thoroughfare. Where such perimeter is more than 150 feet (45 720 mm) in length, a project information panel shall be posted at each corner. Such panels shall be posted on the fence at a height of 4 feet (1219 mm) above the ground, with such distance measured from the ground to the bottom edge of the panel.
3301.9.1.3 Project information panel material.
Project information panels shall be constructed out of a durable and weatherproof material such as vinyl, plastic, or aluminum, and such material shall be flame retardant in accordance with NFPA 701 or listed under UL 214.
3301.9.1.4 Project information panel specifications.
Project information panels shall be 6 feet (1829 mm) wide and 4 feet (1219 mm) high, with the content required by Section 3301.9.1.1 arranged in accordance with Figures 3301.9.1.4(1) and 3301.9.1.4(2). The content required by Section 3301.9.1.1, items number 2 through 7 shall be written in the Calibri font or similar sans serif font style, with letters a minimum of 1 inch (25 mm) high, as measured by the upper case character. Such letters shall be white, on a blue background, with such blue color of a shade matching Pantone 296M, RGB 15, 43, 84, or CMYK 100, 88, 38, 35.
Exceptions:
1. The dimensions for a project information panel posted in conjunction with a demolition project shall be 2 feet 4 inches (711 mm) wide and 4 feet (1219 mm) high, in accordance with Figure 3301.9.1.4(1).
2. For construction sites with a street frontage less than 60 feet (18 288 mm), the dimensions for a project information panel, other than that posted in conjunction with a demolition project, shall be 55 inches (1397 mm) wide and 36.5 inches (927 mm) high, in accordance with Figure 3301.9.1.4(3).
Figure 3301.9.1.4(1) Fence Project Information Panel Text Detail For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
Figure 3301.9.1.4(2) Fence Project Information Panel Layout For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
Figure 3301.9.1.4(3) Fence Project Information Panel Layout for Small Lots For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
3301.9.1.5 Updating content.
When content required by Section 3301.9.1.1 changes, the project information panel shall be updated.
3301.9.1.6 Maintenance of project information panels.
Project information panels shall be maintained so that the panel remains legible, securely attached, and free of sharp edges, protruding nails, or similar hazards. Content required by Section 3301.9.1.1 shall not be obscured by panel attachments, including but not limited to grommets or grommet holes.
3301.9.2 Sidewalk shed parapet information panel.
Where a sidewalk shed is installed, a sidewalk shed parapet information panel meeting the requirements of Sections 3301.9.2.1 through 3301.9.2.6 shall be posted. Required sidewalk shed parapet information panels shall be in place throughout the duration that the sidewalk shed remains at the site.
3301.9.2.1 Sidewalk shed parapet information panel content.
Sidewalk shed parapet information panels shall contain the following information and be arranged in accordance with Figure 3301.9.2.1:
1. The street, address of the site;
2. Name (which may incorporate a logo) of the contractor responsible for the site or where there is no contractor, the name (which may incorporate a logo) of the owner of the site; and
3. The statement "For more information, visit www.nyc.gov/buildings."
Figure 3301.9.2.1 Sidewalk Shed Parapet Information Panel Layout
3301.9.2.2 Posting of sidewalk shed parapet information panels.
Sidewalk shed parapet information panels shall be posted on the parapet that runs along the long axis of the sidewalk shed. Where a sidewalk shed extends along multiple street frontages, not including incidental extensions at a street corner, a parapet information panel shall be posted along each long axis. Such sidewalk shed parapet information panel:
1. Shall not be posted above or below the level of the parapet; and
2. Shall be posted, as viewed from the perspective of an individual on the sidewalk opposite the long axis of the sidewalk shed and facing the sidewalk shed, in a location that is at least 3 feet (914 mm) but no more than 6 feet (1218 mm) to the right of the left edge of the sidewalk shed parapet, or where the sidewalk shed parapet extends beyond the projection of the property line, in a location that is at least 3 feet (914 mm) but no more than 6 feet (1218 mm) to the right of the projection of the property line through the left side of the sidewalk shed; or
3. Where a project information panel in accordance with Section 3301.9.1 is posted on the fence, the horizontal center of the sidewalk shed parapet information panel shall be in line with a vertical plane drawn through the horizontal center of the project information panel on the fence in accordance with Figure 3301.9.2.2.
Figure 3301.9.2.2 Panel Posting Elevation Diagram
3301.9.2.3 Sidewalk shed parapet information panel material.
Sidewalk shed parapet information panels shall be constructed out of a durable and weatherproof material such as vinyl, plastic, or aluminum, and such material shall be flame retardant in accordance with NFPA 701 or listed under UL 214.
3301.9.2.4 Sidewalk shed parapet information panel specifications.
Sidewalk shed parapet information panels shall be 3 feet (914 mm) high and 6 feet (1829 mm) wide, with the content required by Section 3301.9.2.1 arranged in accordance with Figure 3301.9.2.1. The sign shall have a white background. The content required by Section 3301.9.2.1 must be written in Calibri font or similar sans serif font style, and such letters shall be blue, with such blue color a shade matching Pantone 296, or RGB 15, 43, 84, or CMYK 100, 88, 38, 35.
3301.9.2.5 Updating content.
When content required by Section 3301.9.2.1 changes, the sidewalk shed parapet information panel shall be updated.
3301.9.2.6 Maintenance of sidewalk shed parapet information panels.
Sidewalk shed parapet information panels shall be maintained so that the panel remains legible, securely attached, and free of sharp edges, protruding nails, or similar hazards. Content required by Section 3301.9.2.1 shall not be obscured by sign attachments, including but not limited to grommets or grommet holes.
3301.9.3 Reserved.
3301.9.4 Reserved.
3301.9.5 Other temporary signs required by law.
Other temporary signs required by law to be displayed at a construction or demolition site shall be posted within the site, readily visible to workers, and shall not be posted in any location readily visible to the public unless otherwise required by law.
3301.9.6 Obscured lawful signs.
When a protective structure constructed in accordance with Section 3307 obscures from view a lawful and existing sign, a temporary sign may be posted on such protective structure. The temporary sign shall comply with the following requirements:
1. The temporary sign shall be securely fastened to the protective structure at a location directly in front of such business storefront;
2. The temporary sign shall be limited to a maximum height of 4 feet (1219 mm) and shall not exceed the square footage of the obscured lawful sign;
3. The temporary sign shall not project from the side or face of the protective structure;
4. When affixed to a sidewalk shed, the temporary sign shall not extend above or below the sidewalk shed parapet;
5. The temporary sign shall not be hung under the deck of a sidewalk shed or protective structure; and
6. Except where the sidewalk shed obscures a lawful projecting sign, the temporary sign shall not be placed on the end of a sidewalk shed that is perpendicular to the building.
3301.9.7 Other signs prohibited.
Except as specified by Sections 3301.9.1 through 3301.9.6 or as otherwise authorized by law, no sign, information, pictorial representation, or any business or advertising message shall be posted on any construction or demolition equipment or temporary construction installation, including but not limited to, protective structures.
3301.9.8 Illuminated signs prohibited.
No illuminated business or advertising sign shall be permitted on any construction or demolition equipment or temporary construction installation, including but not limited to, protective structures.
3301.10 Reserved.
3301.11 Site safety orientation and refresher.
Each permit holder at a site that requires a site safety manager, site safety coordinator, or construction superintendent shall ensure tat each construction or demolition worker employed or otherwise engaged at such site by the permit holder or performing subcontracted work for or on behalf of such permit holder receives a site safety orientation and refresher in accordance with the requirements of Sections 3301.11.1 through 3301.11.5.
(L.L. 2017/206, 11/17/2017, eff. 5/16/2018)
3301.11.1 Site safety orientation.
Each worker employed or otherwise engaged at such site by the permit holder or performing subcontracted work for or on behalf of such permit holder shall receive a site safety orientation before such worker commences any construction or demolition work at such site.
(L.L. 2017/206, 11/17/2017, eff. 5/16/2018)
3301.11.2 Site safety refresher.
Each worker employed or otherwise engaged at such site by the permit holder or performing subcontracted work for or on behalf of such permit holder shall receive a site safety refresher if such worker (i) has performed construction or demolition work at such site for one year or more and (ii) one year or more has elapsed since such worker received a site safety orientation or refresher with respect to such site.
(L.L. 2017/206, 11/17/2017, eff. 5/16/2018)
3301.11.3 Site safety orientation and refresher to be conducted by qualified person.
Site safety orientations and refreshers required by this section shall be conducted by a qualified person designated by the permit holder. Such qualified person shall have the ability to communicate with each worker who takes part in such orientation or refresher.
(L.L. 2017/206, 11/17/2017, eff. 5/16/2018)
3301.11.4 Site safety orientation and refresher content.
Site safety orientations and refreshers required by this section shall include a review of safety procedures at such site and any hazardous activities to be performed at such site. In addition, information pertaining to the site safety training required by Section 3321 shall be made available to each worker in the designated citywide languages, as such term is defined in Section 23-1101 of the Administrative Code, and any other language as may be required by rule of the department, in a form and manner established by the department.
(L.L. 2017/206, 11/17/2017, eff. 5/16/2018; Am. L.L. 2020/010, 12/27/2019, eff. 1/26/2020)
3301.11.5 Records.
A record of all orientations conducted for the site shall be maintained by the permit holder and kept at the site. Such record shall include for each such orientation or refresher:
1. The date and time of such orientation or refresher;
2. The name, title and company affiliations of each worker who participated; and
3. The name, title and company affiliation of the qualified person who conducted such orientation or refresher, along with such person's signature.
(L.L. 2017/206, 11/17/2017, eff. 5/16/2018)
3301.12 Pre-shift safety meetings.
Each permit holder at a site that requires a site safety manager, site safety coordinator, or construction superintendent shall ensure that each construction or demolition worker employed or otherwise engaged at such site by the permit holder or performing subcontracted work for or on behalf of such permit holder takes part in a safety meeting at the beginning of such worker's shift, but before such worker commences any construction or demolition work in such shift, in accordance with the requirements of Sections 3301.12.1 through 3301.12.3.
Exception: Where other sections of this code or rules promulgated thereunder specify pre-task or pre-shift meetings for specific types of work, those requirements shall instead apply.
(L.L. 2017/204, 11/17/2017, eff. 5/16/2018)
3301.12.1 Pre-shift safety meeting to be conducted by a competent person.
Pre-shift safety meetings shall be conducted at the beginning of each worker's shift, but before such worker commences any construction or demolition work in such shift, by a competent person designated by the permit holder, or where so authorized by the permit holder, by a competent person designated by the subcontractor. Such competent person shall have the ability to communicate with each worker who takes part in such meeting.
(L.L. 2017/204, 11/17/2017, eff. 5/16/2018)
3301.12.2 Pre-shift safety meeting content.
The pre-shift safety meeting shall include a review of activities and tasks to be performed during the shift, including specific safety concerns or risks associated with fulfilling such work.
(L.L. 2017/204, 11/17/2017, eff. 5/16/2018)
3301.12.3 Records.
The permit holder shall maintain, for each worker, a record of one pre-shift safety meeting per week. Such record shall include for each such meeting:
1. The date and time of each such meeting;
2. The name, title and company affiliation of each worker who participated; and
3. The name, title and company affiliation of the competent person who conducted such meeting, along with such person's signature.
(L.L. 2017/204, 11/17/2017, eff. 5/16/2018)
3301.13 Scope.
This section sets forth requirements for construction superintendents at certain construction or demolition sites.
3301.13.1 Site safety plan.
For jobs that require the designation of a primary construction superintendent pursuant to Section 3301.13.3, a site safety plan that meets the applicable requirements of Article 110 of Chapter 1 of Title 28 of the Administrative Code shall be kept on site and made available to the department upon request. Prior to the commencement of work, the permit holder must submit a statement to the department attesting that the site safety plan meets the requirements of Article 110 of Chapter 1 of Title 28 of the Administrative Code and coordinates with the scope of work intended.
Exception: For a major building subject to the provisions of Section 3310, the site safety plan requirements of Section 3310.3 shall apply.
(Am. L.L. 2021/149, 12/11/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/149.
3301.13.2 Definitions.
For the purposes of this section, the following terms shall have the following meanings:
Approved documents. For the purpose of this section, approved documents include construction documents as defined by this code, and any and all documents that set forth the location and entire nature and extent of the work proposed with sufficient clarity and detail to show that the proposed work conforms to the provisions of this code and other applicable laws and rules. In addition to construction documents, such documents include, but are not limited to, site safety plans, tenant or occupant protection plans, shop drawings, specifications, manufacturer's instructions and standards that have been accepted by the design professional of record or such other design professional retained by the owner for this purpose.
Job. A design and construction/demolition undertaking consisting of work at one building or structure, as well as related site improvements and work on accessory structures. A job may consist of one or more plan/work applications, and may result in the issuance of one or more permits.
Permit holder. The individual who receives the primary department-issued permit for the job.
(Am. L.L. 2021/149, 12/11/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/149.
3301.13.3 Designation of primary construction superintendent.
The permit holder shall designate a primary construction superintendent, who shall carry out all duties and responsibilities assigned to the construction superintendent by this chapter and rules promulgated by the commissioner, and notify the department of such designation prior to the commencement of work, for the following types of jobs:
1. The construction of a new building;
2. The full demolition of an existing building;
3. An alteration to an existing building that involves one or more of the following:
3.1 A vertical enlargement;
3.2 A horizontal enlargement;
3.3 The alteration or demolition of more than 50 percent of the gross floor area of the building during the course of work over any 12-month period;
3.4 The removal of one or more floors during the course of work over any 12-month period;
3.5 Work that requires a special inspection for underpinning; or
3.6 Work that requires a special inspection for the protection of sides of excavations; or
4. Other jobs that pose an enhanced risk to the public and property, as determined by the commissioner.
Exception: A construction superintendent is not required for work that solely involves a 1-, 2-, or 3-family building, or an accessory use to such building, provided the permit holder for such work is registered as a general contractor in accordance with Article 418 of Chapter 4 of Title 28 of the Administrative Code.
(Am. L.L. 2021/149, 12/11/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/149.
3301.13.4 Change of designation.
The permit holder must immediately notify the department of any permanent change to the primary construction superintendent.
3301.13.5 Alternate construction superintendent.
In the event the primary construction superintendent is temporarily unable to perform their duties, an alternate construction superintendent, designated by the permit holder, must act in place of the primary construction superintendent and carry out all duties and responsibilities assigned to the construction superintendent by this chapter and rules promulgated by the commissioner. In the event that an alternate construction superintendent will be acting in place of the primary construction superintendent for a period longer than two consecutive weeks, the permit holder must notify the department of such circumstance.
3301.13.6 Limitations on the designation of primary or alternate construction superintendents.
An individual may only be designated as a primary or alternate construction superintendent for that number of jobs for which he or she can adequately perform all required duties. No individual may be designated as the primary construction superintendent on more than ten jobs.
Exceptions:
1. If one of the jobs for which the construction superintendent is designated as a primary construction superintendent is on a building that meets the definition of a major building, the individual may only be designated as the primary construction superintendent for that job and may not serve as the primary construction superintendent for any other job.
2. Notwithstanding Exception 1, beginning on June 1, 2022, no individual may be designated as the primary construction superintendent for more than five jobs.
3. Notwithstanding Exception 1, beginning on January 1, 2024 or a later date established by the department, provided that such date is not later than January 1, 2025, no individual may be designated as the primary construction superintendent for more than three jobs.
4. Notwithstanding Exception 1, beginning on January 1, 2026 or a later date established by the department, provided that such date is not later than January 1, 2027, no individual may be designated as the primary construction superintendent for more than one job.
5. A construction superintendent designated as the primary construction superintendent at a job site may serve as a non-primary construction superintendent at another job site, provided there is no work requiring the presence of such individual occurring at the job site for which the individual has been designated as the primary construction superintendent.
6. Subject to the approval of the commissioner, a construction superintendent may serve as the primary construction superintendent for multiple non-major building jobs located on the same lot or on contiguous lots.
(Am. L.L. 2021/149, 12/11/2021, eff. 1/1/2022; Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/149 and L.L. 2023/077
3301.13.7 Duties of construction superintendents.
The duties of a construction superintendent shall include:
1. Acting in a reasonable and responsible manner to maintain a safe job site and ensure compliance with this chapter and any rules promulgated thereunder at each job site for which the construction superintendent is responsible;
2. To the extent that a registered design professional or special inspection agency is not responsible, the construction superintendent must ensure compliance with the approved documents at each job site for which the construction superintendent is responsible;
3. Fulfilling the duties of a superintendent of construction assigned by Chapter 1 of Title 28 of the Administrative Code at each job site for which the construction superintendent is responsible; and
4. Visiting each job site for which the construction superintendent is responsible each day when active work is occurring; or, beginning January 1, 2026 or a later date established by the department, provided that such date is not later than January 1, 2027, where Section 3301.13.6 requires the construction superintendent to be dedicated to one job, being present at the job site for which the construction superintendent is responsible during all times when active work is occurring.
Exception: The construction superintendent is not required to be present at the site during the following activities, provided no other work is in progress:
1. Surveying that does not involve the disturbance of material, structure, or earth;
2. Use of a hoist exterior to the building to transport personnel only;
3. Use of a hoist that is fully enclosed within the perimeter of the building to transport personnel or material;
4. Work limited to finish troweling of concrete floors;
5. Work limited to providing the site with temporary heat, light, or water;
6. Truck deliveries to the site, provided the delivery occurs within the site while the gate is closed and flagpersons are provided to direct traffic while the truck is entering and exiting the site;
7. Painting; or
8. Landscaping that does not involve the disturbance of material, structure, or earth.
(Am. L.L. 2021/149, 12/11/2021, eff. 1/1/2022; Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/149 and L.L. 2023/077
3301.13.8 Inspection by the construction superintendent.
Each time the construction superintendent visits a job site for which he or she is responsible, the construction superintendent must inspect all areas and floors where construction or demolition work, and ancillary activity, is occurring, and:
1. Verify work is being conducted in accordance with sound construction/demolition practices;
2. Verify compliance with the approved documents; and
3. Verify compliance with this chapter and any rules promulgated thereunder.
Exception: Where a site safety manager or coordinator has been designated for the job in accordance with Section 3310, the construction superintendent does not need to perform the inspections required by this section. Site safety inspections shall be performed by the site safety manager or coordinator in accordance with Section 3310.
(Am. L.L. 2021/149, 12/11/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/149.
3301.13.9 Correcting unsafe conditions.
In the event the construction superintendent discovers work or conditions at a job site for which he or she is responsible that are not being conducted in accordance with sound construction/demolition practices, not in compliance with approved documents, or not in compliance with this chapter and any rules promulgated thereunder, the construction superintendent must take all appropriate action to correct the unsafe work or condition, including but not limited to immediately notifying the person or persons responsible for creating the unsafe work or condition, and ordering the person or persons to correct the unsafe work or condition, to cease operations, or to leave the job site. Where unsafe work or an unsafe condition relates to an item which a registered design professional or special inspection agency is responsible for implementing or verifying, the construction superintendent must also notify the responsible registered design professional or special inspection agency of the unsafe work or condition. All such unsafe conditions, work, notices, orders, and corrective action must be recorded in the log required by Section 3301.13.13.
(Am. L.L. 2021/149, 12/11/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/149.
3301.13.10 Notification of conditions to the department.
The construction superintendent must immediately notify the department, when he or she discovers, at any job site for which the construction superintendent is responsible, any of the conditions listed in Section 3310.8.2.1. Notification to the department does not relieve the construction superintendent of their obligations under Section 3301.13.9.
Exception: Where a site safety manager or coordinator has been designated for the job in accordance with Section 3310, the construction superintendent does not need to provide the notification required by this section. Notifications shall be made by the site safety manager or coordinator in accordance with Section 3310.
(Am. L.L. 2021/149, 12/11/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/149.
3301.13.11 Reporting of incidents and damage to adjoining property.
The construction superintendent must immediately notify the department of any incident at any job site for which the construction superintendent is responsible, or any damage to adjoining property caused by construction or demolition activity at the job site.
Exception: Where a site safety manager or coordinator has been designated for the job in accordance with Section 3310, the construction superintendent does not need to provide the notification required by this section. Notifications shall be made by the site safety manager or coordinator in accordance with Section 3310.
(Am. L.L. 2021/149, 12/11/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/149.
3301.13.12 Competent person.
The construction superintendent must designate a competent person for each job site for which the construction superintendent is responsible and ensure such competent person is present at the designated job site at all times active work occurs when the construction superintendent is not at the site. The designation of a competent person does not alter or diminish any obligation imposed upon the construction superintendent. The competent person must carry out orders issued by the construction superintendent; be able to identify unsanitary, hazardous or dangerous conditions; take prompt corrective measures to eliminate such conditions; immediately report to the construction superintendent incidents at the job site or any damage to adjoining property caused by construction or demolition activity at the job site; and be able to effectively communicate workplace instructions and safety directions to all workers at the site.
Exception: Beginning January 1, 2026 or a later date established by the department, provided that such date is not later than January 1, 2027, where Section 3301.13.6 requires the construction superintendent to be dedicated to one job, the designation of a competent person is not authorized. In the event the primary construction superintendent cannot be present at the job site while active work is occurring, an alternate construction superintendent shall act on behalf of the primary construction superintendent in accordance with Section 3301.13.5.
(Am. L.L. 2021/149, 12/11/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/149.
3301.13.13 Log.
The construction superintendent must maintain a log at each job site for which the construction superintendent is responsible. Such log must be made available to the commissioner upon request. The construction superintendent must complete such log prior to departing the job site, or, where the job occurs on a building that meets the definition of a major building, by the end of the day. Each day's log entry must be signed and dated by the construction superintendent. Such log must contain, at a minimum, the following information:
1. The presence of the construction superintendent at the job site as evidenced by their printed name and signature and a notation indicating the times of arrival at, and departure from the site, which must be recorded immediately after arriving at the site and immediately prior to leaving the site, respectively;
2. The general progress of work at the job site, including a summary of that day's work activity;
3. The construction superintendent's activities at the job site, including areas and floors inspected;
4. Any unsafe condition(s) observed pursuant to Section 3301.13.9, and the time and location of such unsafe condition(s);
5. Orders and notice given by the construction superintendent pursuant to Section 3301.13.9, including the names of individuals issued orders or notices, any refusals to comply with orders or respond to notices given, follow up action taken by the construction superintendent, and where the condition giving rise to the order or notice is corrected, the nature of the correction;
6. Any violations, stop work orders, or summonses issued by the department, including date issued and date listed or dismissed;
7. Any incidents or damage to adjoining property caused by construction or demolition activity at the site;
8. The name of the competent person designated in accordance with Section 3301.13.12, along with an accompanying signature of the competent person. If the construction superintendent assigns a new competent person, the date and time of this change, along with the name of the new competent person, must be recorded, accompanied by the signature of the new competent person. If the construction superintendent is not at the job site when this occurs, the new competent person must instead make the log entry, which the construction superintendent must sign and date upon his or her next visit to the job site;
9. All construction superintendent personnel changes, accompanied by the signature of the new construction superintendent. Construction superintendent personnel changes include, but are not limited to: a change to the primary construction superintendent; an alternate construction superintendent acting in the place of the primary construction superintendent; or a new alternate construction superintendent taking over for the previous alternate construction superintendent; and
10. A record of the weekly safety meeting required by Section 3301.13.19, including date and time of meeting, summary of issues discussed, and the names and affiliation of those who attended.
(Am. L.L. 2021/149, 12/11/2021, eff. 1/1/2022; Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/149 and L.L. 2023/077
3301.13.14 Reserved.
3301.13.15 Reserved.
3301.13.16 Obligation of others.
Nothing in this section is intended to alter or diminish any obligation otherwise imposed by law on others, including but not limited to, the owner, permit holder, construction manager, general contractor, contractor, materialman, architect, engineer, land surveyor, site safety manager, site safety coordinator, concrete safety manager, or other party involved in a construction project to engage in sound engineering, design, and construction practices, and to act in a reasonable and responsible manner to maintain a safe job site.
3301.13.17 Licensing of construction superintendents.
No person shall perform the duties and responsibilities of a construction superintendent, including but not limited to serving as a primary construction superintendent or as an alternate construction superintendent, unless such person is licensed as a construction superintendent in accordance with Article 428 of Title 28 of the Administrative Code.*
* Editor's note: Correct reference should be Article 428 of Chapter 4 of Title 28 of the Administrative Code.
3301.13.18 Release of the construction superintendent.
The department may release the construction superintendent from the job when the construction superintendent demonstrates, to the satisfaction of the commissioner, that the job is substantially complete.
3301.13.19 Weekly safety meeting.
The construction superintendent shall, for each job site for which the construction superintendent is responsible, lead a safety meeting with the designated representative of the general contractor, construction manager, and each subcontractor to ascertain that all contractors and subcontractors are complying with the applicable provisions of this chapter, the site safety plan, and the tenant or occupant protection plan. Where a site safety manager or coordinator has been designated for the job in accordance with Section 3310, the site safety manager or coordinator shall also attend the meeting. Such meeting shall occur at least once a week while active work is occurring.
(L.L. 2021/149, 12/11/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/149.
3301.14 Contractor shall inform personnel.
General contractors and subcontractors shall state to their directly employed personnel at the construction or demolition site, prior to such directly employed person commencing work at the site, that they are to follow all safety regulations at all times and that they are required to obey and implement all orders and directives issued by the general contractor/subcontractor, the general contractor's/subcontractor's designee, the construction superintendent, and the worker's direct supervisor relating to safety requirements. Where a site safety manager or coordinator is required, the general contractor or subcontractor shall also state to their directly employed personnel at the site, prior to such directly employed person commencing work at the site, that the site safety manager or coordinator is responsible for monitoring compliance with laws and rules governing site safety; and shall inform their supervisory personnel at the site, prior to such supervisor commencing work at the site, of the name and responsibilities of the site safety manager or coordinator.
(Am. L.L. 2017/081, 5/10/2017, eff. 11/6/2017; Am. L.L. 2017/204, 11/17/2017, eff. 5/16/2018; Am. L.L. 2017/206, 11/17/2017, eff. 5/16/2018)