ANSI/NFiPA No. 74–1989—Standard for the Installation, Maintenance and Use of Household Fire Warning Equipment, as Modified. The following Sections of this standard are modified to read as follows:
1–1 Scope. Covers the requirements for the proper selection, installation, operation and maintenance of fire warning equipment for use within dwelling units or rooming units.
1.2.6 The installation of wiring and equipment shall be in accordance with the New York City Electrical Code.
2–1.1.1 Smoke detectors shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms in dwelling units, in Occupancy Groups J-2 and J-3, and in Basements and Basement Recreation Rooms in Occupancy Group J-3.
Smoke detectors shall be installed within the sleeping area of hotel or motel units, rooming units or studio dwelling units in Occupancy Group J-1.
4–5.5 Each smoke detector shall have an integral test means to permit the occupant to check that it is operational. A continuous power display indicator light is recommended.
4–2.1.4 A smoke detector installed to protect a sleeping area in accordance with 2–1.1.1, shall be located outside the bedroom but in the immediate vicinity of the sleeping area, except as set forth for rooming units.
5–2.1.6 Smoke detectors shall be located on or near the ceiling, and within fifteen feet of all rooms used for sleeping purposes in J-2 or J-3 occupancies. In all dwelling units, with multiple levels, when any level has only one means of egress, the dwelling unit shall be provided with smoke detectors on all levels.
5–2.1.6.1 If ceiling mounted, the closest edge of the detector shall be a minimum of four inches from any wall.
5–2.1.6.2 If wall mounted, the closest edge of the detector shall be a minimum of four inches and a maximum of twelve inches from the ceiling.