NYC Administrative Code RS 17-5

ANSI/NFPA No. 72–1993—National Fire Alarm Code.

The provisions of NFPA 72–1993 with the exception of Chapter 2 shall apply subject to the following modifications. The section and paragraph numbers are from that standard.

Note: Chapter 2 of NFPA 72–1993 entitled "Household Fire Warning Equipment" shall not be part of this reference standard.

The requirement of NICET Certification as outlined under Section 7–1.2.3 shall be applicable beginning on January 14, 2006.

CHAPTER 1—FUNDAMENTALS OF FIRE ALARM SYSTEMS

Add the definition of Evacuation Zone between Evacuation Signal and Exit Plan in Section 1–4.

Evacuation Zone.—An evacuation zone is an area of a floor, an entire floor, several floors or the entire building that is always intended to be evacuated simultaneously.

Amend the following definitions:

Section 1–5.2.3—Delete exceptions No. 1 and No. 2.

Section 1–5.2.6—Delete sub-paragraph (c).

Section 1–5.2.8.4—Delete

Section 1–5.2.9.2(c)—Delete

Section 1–5.2.10—Delete in its entirety.

Section 1–5.2.11—Delete in its entirety.

Section 1–5.4.1—Delete

Section 1–5.4.2.1 is modified as follows:

Section 1–5.4.2.1 Coded Alarm Signal—A coded alarm signal shall consist of not less than [three] four complete rounds of the number transmitted, and each round shall consist of not less than three impulses.

Section 1–5.4.3—Delete in its entirety.

Section 1–5.4.7—Delete the exception.

Section 1–5.4.8—Delete and substitute the following:

Section 1–5.4.8 Alarm Signal (Silence).—A means of silencing the alarm notification appliances shall be located within a locked F.A. Control Cabinet. Such a means shall be permitted only if a visible zone alarm indication or equivalent has been provided, as specified in 1–5.7, and subsequent alarms on other initiating device circuits will cause the notification appliances to reactivate. A means that is left in the "off" position when there is no alarm shall operate an audible visible trouble signal until the means is restored to normal.

Section 1–5.4.10—Delete

Section 1–5.5.4—Delete

Section 1–5.6—Delete

Section 1–5.7.1.1—Delete the first paragraph up to . . . "in a fire situation."

Section 1–5.8.1—Delete "within 200 seconds" from the end of the paragraph. Also delete "Exception #10."

Section 1–5.8.4—Delete "exception #3."

Section 1–5.8.5.1—Delete the exception of Subsection (b).

Section 1–5.8.6.1—Delete exceptions #3 and #4.

Section 1–5.8.6.2—Delete

Section 1–5.8.6.3—Delete

Section 1–7—Delete in its entirety.

CHAPTER 3—PROTECTED PREMISES FIRE ALARM SYSTEMS

Section 3–2.1—Delete

Section 3–3—Delete subdivisions (h), (i) & (k)

Section 3–4.2—Delete exceptions #3 and #5

Section 3–5.2—Delete

Section 3–5.3—Delete

Section 3–7.2(a)—Delete the effective date of the requirements.

Section 3–8.1.2—Amended to read as follows:

Section 3–8.1.2—For fire alarm systems employing automatic fire detectors or waterflow detection devices, at least one fire alarm box shall be provided to initiate [a] the same fire alarm signal as required by automatic fire detectors or waterflow detection devices. This fire alarm box shall be located where required by the authority having jurisdiction.

Section 3–8.3—Delete

Section 3–8.6.2 shall modified to read as follows:

Section 3–8.6.2—A dry-pipe or preaction sprinkler system that is supplied with water by a connection beyond (downstream from) the alarm initiating device of a wet-pipe system shall be equipped with a separate waterflow alarm initiating pressure switch or other approved means to initiate a waterflow alarm.

Section 3–8.9.1—Modify to read as follows: The operation of an automatic fire suppression system installed within the protected premises shall be indicated as an alarm on the protected premises fire alarm system.

Section 3–8.10.1—Delete last paragraph starting from "all phases . . ."

Section 3–8.10.2—Delete

Section 3–8.14—Delete in its entirety.

Section 3–8.15.4—Modify second sentence to read as follows: The operation of the elevators shall be in accordance with [ANSI/ASME A17.1, Safety Code for Elevators and Escalators, Rules 211.3 through 211.8] RS 18–1. Delete the third sentence.

Section 3–8.15.4 (a)—Delete

Section 3–8.15.4 (b)—Delete

Section 3–8.16—Delete

Section 3–9.2.3 Modify to read as follows: When permitted by the authority having jurisdiction. Transfer of data over listed communication ports shall be an acceptable means of interfacing between the fire alarm control unit and fire safety function control devices.

Section 3–9.3.3—Delete and substitute the following:

Section 3–9.3.3—Connection between fire alarm systems and the HVAC system for the purpose of monitoring and control shall be arranged such that primary control (the control that all other controls are secondary or subservient to) capability rests with the fire alarm control unit(s) under all circumstances, and in addition, shall operate and be monitored in accordance with Reference Standards RS 13–1, RS 17 and the authority having jurisdiction.

Add Section 3–9.3.4 as follows:

Section 3–9.3.4—Those HVAC fans or fan systems which have been automatically shut-down by virtue of the activation of any fire alarm control unit or device shall be arranged and equipped not to automatically restart when the fire alarm control unit or device is reset. At least two manual means of restarting the fans or fan systems shall be required, such as manually resetting the fire alarm control unit or device and the manually resetting the fan or fan system controls.

Add Section 3–9.3.5 as follows:

Section 3–9.3.5—Fans or fan systems that were automatically shut down by the fire alarm control unit or device in Class `E', `J' and `C' systems shall be manually enabled to start by a means of overriding the fan shutdown through use of a city-wide standard key switch (#2642) located at the Fire Command Station. The actual start of the fan(s) shall be accomplished manually through HVAC controls at the Fire Command Station, or at the Mechanical Control Center or locally at the fan room(s).

Add Section 3–9.3.6 as follows:

Section 3–9.3.6—Smoke exhaust control means shall be enabled through the use of a city-wide standard key (#2462) located at the Fire Command Station or fire alarm control unit, or when neither is provided, in the entrance lobby of the building.

Section 3–10.4—Delete

Section 3–11—Delete in its entirety.

Section 3–12.3—Delete in its entirety.

Section 3–12.4.1—Delete the exception.

Section 3–12.4.2—Delete

Section 3–12.4.3.1—Delete

Section 3–12.4.3.2—Delete

Section 3–12.4.4—Delete

Section 3–12.4.5.1—Delete the third sentence starting from "The fire command station shall be permitted . . ."

Section 3–12.4.6.2—Delete

Section 3–12.4.6.3—Delete

Section 3–12.5.1—Delete

Section 3–12.6.6—Delete

Section 3–12.6.7—Delete

CHAPTER 4

Deleted in its entirety (this chapter is for fire alarm central offices, which falls under the Fire Department's jurisdiction).

CHAPTER 5—INITIATING DEVICES

Section 5–1.3.4—Delete "appropriate NFPA standard or" from the first sentence.

Section 5–1.3.5—Delete

Section 5–2.2—Delete "either by the appropriate NFPA standard or" from the sentence.

Section 5–3.2—Delete "either by the appropriate NFPA standard or" from the sentence.

Section 5–3.5.9—Add, "Where required by the authority having jurisdiction" at the beginning of the paragraph.

Section 5–3.6.2—Add, "Where required by the authority having jurisdiction" at the beginning of the paragraph.

Section 5–5.2—Delete "either by the appropriate NFPA standard or" from the paragraph.

Section 5–6.1—Delete "either by the appropriate NFPA standard or" from the second sentence.

Section 5–8.1—Substitute the words "approvals/acceptances" for "listings".

Add Section 5–8.2 to read as follows:

Section 5–8.2—Appropriate means may involve:

(a) Foam Systems: Flow of Water

(b) Pump Activation

(c) Differential Pressure Detector

(d) Halon: Pressure Detector

(e) Carbon Dioxide: Pressure Detector

In any case, an alarm that activates the extinguishing system may be initiated from the detection system.

Section 5–9.1.1—Change the second sentence to read as follows: "The operable part of each manual fire alarm box shall be 4 feet above finished floor level."

Section 5–9.1.2—Delete

Section 5–9.1.3—Change the number of repetitions produced from three to four.

Sections 5–9.2 to 5–9.2.11—Delete

Sections 5–9.2.12 to 5–9.2.12.6—Delete

Sections 5–9.2.13 to 5–9.2.14.2—Delete

Section 5–10.5—Delete and substitute the following:

Section 5–10.5—Room Temperature Supervisory Signal-Initiating.—When temperature supervisory devices are provided to indicate a low temperature condition, they shall indicate the decrease in room temperature to 40°F (4.4°C) and its restoration to above 40°F (4.4°C).

Section 5–11.4.2—Delete "NFPA 90A, Standard for the installation of Air Conditioning and Ventilating Systems" and substitute with "Reference Standard RS 13–1."

Section 5–11.5.2.1—Delete "other NFPA standards" and substitute with "Reference Standard RS 13–1."

Figure 5–11.7.4.1.1.(D) to read "One detector mounted on the higher side"

CHAPTER 6—NOTIFICATION APPLIANCES FOR FIRE ALARM SYSTEMS

Section 6–3.7—Amend to read as follows:

Section 6–3.7—Location of Audible Signal Appliances. Where ceiling heights permit, wall mounted appliances shall have their [tops] centerline at heights above the finished floors of [not less than 90 in. (2.30 m)] 8 ft. (2.45 m) and [below the finished ceilings of not less than 6 in. (0.15 m)] where ceiling heights prevent installation at this height installation shall be not greater than 6 in. (0.15 m) below. This shall not preclude ceiling-mounted or recessed appliances.

Exception: Combination audible/visible appliances.

Section 6–4.2—Delete

Section 6–4.4 is modified to read as follows:

Section 6–4.4 Appliance Location.—Wall-mounted appliances shall have their bottoms at heights above the finished floor of no less than 80 in. (2-m) nor less than 6 in. (13.5 cm) below the ceiling, whichever is lower. [and no greater than 96 in. (2.4 m.)] Ceiling-mounted appliances [shall] may be installed [per Table 6–4.4.1(b)].

Exception: Appliances installed in sleeping areas shall comply with 6–4.4.3.

Figure 6–4.4.1—Delete

Section 6–4.4.1.1 is modified to read as follows:

Section 6–4.4.1.1—Spacing shall be in accordance with [Figure 6-4.4.1 and] Table[s] 6–4.4.1(a) [and (b)]. A maximum separation between appliances shall not exceed 100-ft. (30 m). Visible notification appliances shall be installed in accordance with Table 6–4.4.1 (a), using one of the following:

(a) A single visible notification appliance, or

(b) Two visible notification appliances located on opposite walls, or

(c) In rooms 80 ft. by 80 ft. or greater, where there are more than two appliances in any field of view, they shall be spaced a minimum of 55 ft. from each other, or

(d) More than two visible notification appliances that flash in synchronization.

Section 6–4.4.2.1 is modified to read as follows:

Table 6–4.4.2 applies to corridors not exceeding 20 ft. (6.1 m) wide. For corridors greater than 20 ft. (6.1 m) wide, refer to [Figure 6-4.4.1 and] Table[s] 6–4.4.1(a) [and (b)]. In a corridor application, visible appliances shall be UL 1971 rated not less than 15 cd, and shall have an on-axis intensity of not less than 75 cd.

Table 6–4.4.1 (a) is modified as follows:

TABLE 6–4.4.1(a) Room Spacing Allocation for Wall-Mounted Visible Appliances

Minimum Required Light Output, Candela (cd) (Effective Intensity) (see note below) Maximum Room Size One Light Per Room (cd) Two Lights per Room (Located on Opposite Walls) (cd) Four Lights per Room—One Light per Wall (cd) 20' × 20' 15 N/A N/A 30' × 30' 30 15 N/A 40' × 40' 60 30 [15] N/A 45' × 45' 75 60 N/A 50' × 50' 95 60 [30] N/A 55' × 55' 110 75 N/A 60' × 60' 135 95 [30] N/A 70' × 70' 185 110 [60] N/A 80' × 80' 240 140 60 90' × 90' 305 180 95 100' × 100' 325 240 95 110' × 110' 455 240 135 120' × 120' 540 305 160 130' × 130' 635 375 185

Note: Candela (cd) ratings, as indicated, as based on UL 1971 listings. On-axis ratings shall in no case be less than 75 cd.

Table 6.4.4.1(b)—Delete

Section 6–6—Delete

Section 6–6.1—Delete

Section 6–6.2—Delete

Section 6–8—Delete in its entirety.

Section 6–9—Delete in its entirety.

CHAPTER 7

Section 7–1.1.1 is modified to read as follows:

Section 7–1.1.1—Inspection, testing and maintenance programs shall satisfy the requirements of [this code] the Fire Commissioner, the New York City Building Code and the equipment manufacturer's instructions.

Section 7–1.2—Delete the second sentence starting from "Delegation."

Section 7–1.2.1—Delete

Section 7–1.2.2—Delete and enact three new sections as follows:

Section 7–1.2.2—Personnel shall be qualified and experienced in the inspection and testing of fire alarm systems and shall meet the following requirements:

(a) Certified by the Buildings and/or Fire Commissioners, or

(b) Trained and qualified personnel of a NYC licensed electrical contracting firm, or

(c) Personnel with National Institute for Certification in Engineering Technologies (NICET) Certification of Level II in fire alarm technology, or

(d) Trained and qualified personnel of firm listed by a national testing laboratory for servicing of fire alarm systems.

Section 7–1.2.3—Personnel shall be qualified and experienced in the maintenance of fire alarm systems and shall meet the following requirements:

(a) Factory trained and certified, or

(b) Trained and qualified personnel of NYC licensed electrical contracting firm, or

(c) Trained and qualified personnel of firm listed by a national testing laboratory for servicing of fire alarm systems.

(d) Service personnel employed pursuant to (a), (b), and (c) above shall either have a valid NICET Certification of Level II in fire alarm technology or work under the direct supervision of a person having such certification.

Exception: The following are exempt from the above requirements:

(1) Person(s) exclusively performing smoke detector cleaning, having a Certificate of Fitness from the Fire Department and working under the supervision of, or employed by a person(s) having NICET Level II certification.

(2) Person(s) exclusively performing maintenance of fire alarm systems installed and approved prior to 1987, and working under the supervision of, or employed by a person(s) having NICET Level II certification.

(e) If during the course of maintenance either:

(1) total system replacement, or

(2) wiring repair, or

(3) replacement of wiring is (are) indicated, such repair(s) or replacement(s) shall be performed by a person holding a license or a special license in accordance with the provisions of the NYC Electrical Code.

Section 7–1.4 is modified to read as follows:

Section 7–1.4—Prior to system maintenance or testing, [the system certificate and the] all information regarding the system and . . . to the service personnel.

Section 7–1.5.1—Delete and substitute the following:

Section 7–1.5.1—The special hazard system and main building system shall be tested concurrently.

Section 7–1.6—Amend the last sentence to read as follows:

In addition, except for Class "E", "J" and "C" systems, 10 percent of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, shall also be tested and proper system operation verified.

Section 7–2.1—Delete

Section 7–2.2—Delete and substitute the following:

Section 7–2.2—Testing, which involves the disconnection of circuits of 50 volts or more with the exception of audio circuits up to 75 volts, shall be performed in accordance with the New York City Electrical Code by licensed electrical contracting firms meeting the requirements of Sections 7–1.2.3 and 7–1.2.3.1.

Sections 7–3.1 to 7–3.1.2—Delete

Section 7–3.2 shall be deleted and substitute the following:

Section 7–3.2 Testing—Testing shall be performed in accordance with the requirements of the Fire Prevention Code.

Sections 7–3.2.1 to 7–3.4—Delete

Section 7–4.1 shall be deleted and substitute the following:

Section 7–4.1—Fire alarm system equipment shall be periodically maintained in accordance with manufacturers' instructions and the Fire Prevention Code.

Sections 7–4.2 to 7–4.4—Delete

Sections 7–4.4.1 to 7–4.4.3.2—Delete

Section 7–5.1—Delete

Sections 7–5.3 to 7–5.4—Delete

CHAPTER 8—REFERENCED PUBLICATIONS

Delete in its entirety.

APPENDIX A—EXPLANATORY MATERIAL

This appendix is not part of Reference Standard RS 17–5, but is included for information purposes only with the exception of the following:

Section A–6–4.4.1—Delete in its entirety and substitute the following:

Section A–6–4.4.1—A design which delivers 0.0375 lumens per sq. ft. effective intensity to all occupied spaces where visible notification is required, is considered to meet minimum light intensity requirements of this section. The field of view is based on the focusing capability of the human eye, specified as 120 degrees in the IES Handbook. The apex of this angle is the viewer's eye. In order to ensure compliance with the requirements of §6–4.4.1, it has been accepted that this angle be increased to approximately 135 degrees.

Figure A–6–4.4.1 (a)—Delete

Figure A–6.4.4.1 (b)—Delete

Figure A–6.4.4.1 (c)—Delete

Figure A–6.4.4.1 (d)—Delete

Figure A–6.4.4.2—Delete

APPENDIX B—ENGINEERING GUIDE FOR AUTOMATIC FIRE DETECTOR SPACING

This appendix is not part of Reference Standard RS 17-5, but is included for information purposes only.