NYC Administrative Code SECTION 10 – PRESSURE-RELIEF PROTECTION
10.4.8 Delete the entire paragraph and substitute the following: "Discharge or pressure relief devices and fusible plugs on all systems containing more than 6 lbs. of group 2 or group 3 refrigerants shall be to the outside of the building. On systems containing more than 100 lbs. of group 1 refrigerants, discharge of pressure relief devices and fusible plugs shall be to the outside of the building. Discharge of group 1 refrigerants to the outside of the building shall be at least 12 ft. above the grade level and the discharge outlets shall be turned downward. Discharge of systems employing group 2 refrigerants shall be acceptable to the commissioner. Discharge of group 3 refrigerants shall be acceptable to the commissioner and the fire commissioner."