NYC Administrative Code RS 13-1, Chapter 3 INTEGRATION OF A VENTILATION AND AIR CONDITIONING SYSTEM(S) WITH BUILDING CONSTRUCTION

This section has 1 picture (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read RS 13-1, Chapter 3 at American Legal Publishing.

3–1 Air-Handling Equipment Rooms.

3–1.1 General—Air-handling equipment rooms generally fall into three categories:

(a) Those used as air plenums (usually return air);

(b) Those with air ducts that open directly into a shaft; and

(c) Other air-handling unit rooms.

3–1.2 Air-Handling Equipment Rooms Used as Plenum Space—Air-handling unit rooms used as plenums for supply or return air shall comply with 2–3.10.4.

3–1.3 Air-Handling Equipment Rooms that Have Air Ducts that Open Directly into a Shaft—Air-handling equipment rooms, including the protection of openings, shall be separated from shafts by construction having a fire resistance rating not less than that required for the shaft by 3–3.4.

Exception: Fire-resistant separation shall not be required for air-handling equipment rooms that are enclosed by construction having a fire resistance rating not less than that required for the shaft.

3–1.4 Other Spaces Housing Air-Handling Units—Other spaces housing air-handling units shall meet the requirements of the building code.

3–2 Building Construction.

3–2.1 Air Duct Clearance—The clearance from metal air ducts to assemblies constructed of combustible materials, including plaster on wood lath, shall be not less than one-half in. (12.7 mm), or the combustible material shall be protected with minimum one-quarter in. (6.4 mm) firestopping material as per the Building Code. The integrity of the firestopping and smokestopping shall be maintained.

Exception: This clearance shall not apply to systems used solely for ventilation, air cooling, or air conditioning without heating.

3–2.2 Structural Members—The installation of air ducts, including the hangers, shall not reduce the fire resistance rating of structural members.

3–2.3 Where the installation of the hangers for the components of an air duct system penetrates an existing ceiling of a fire-resistive floor/roof-ceiling assembly and necessitates removal of a portion of that ceiling, the replacement material shall be identical to or approved as equivalent to that which was removed.

Exception: As an alternative to repairing the existing ceiling, a new ceiling shall be permitted to be installed below the air duct system, provided the fire resistance rating of the floor/roof-ceiling design is not reduced.

3–3 Penetrations—Protection of Openings—For examples of the application of the penetration protection requirements, see Figure 3–3.

3–3.1 Fire-Rated Walls and Partitions.

3–3.1.1 Approved fire dampers shall be provided where air ducts penetrate or terminate at openings in walls or partitions required to have a fire resistance rating pursuant to § 27-343 of the Administrative Code. In addition, approved fire dampers shall be provided in outdoor intake openings in accordance with §2–2.1.3. (See Figure 3–3.)

Exception: Fire dampers shall not be required where other openings through the wall are not required to be protected.

3–3.1.2 Approved fire dampers shall be provided in all air transfer openings in partitions required to have a fire resistance rating and in which other openings are required to be protected.

3–3.2 Floors Require to Have a Fire Resistance Rating—Where air ducts extend through only one floor and serve only two adjacent stories, the air ducts shall be enclosed (see 3–3.4.1) or fire dampers shall be installed at each point where the floor is penetrated.

Exception: Air ducts serving air conditioning terminal devices on the floor above, provided a fire test conducted in accordance with RS 5–2, determines that the fire resistance rating of the floor is maintained.

3–3.3 Floor/Roof-Ceiling Assemblies Having a Fire Resistance Rating—Where air ducts and openings for air ducts are used in a floor/roof-ceiling assembly required to have a fire resistance rating, all the materials and the construction of the assembly, including the air duct materials and the size and protection of the openings, shall conform with the design of the fire-resistive assembly, as tested in accordance with RS 5–2. (Where dampers are required, see 3–4.4.)

3–3.4 Shafts.

3–3.4.1 Enclosure of Ducts.

(a) Air ducts that pass through the floors of buildings requiring the protection of vertical openings shall be enclosed with partitions or walls constructed of materials as permitted by the Building Code, § 27-344.

Exception: Where an air duct penetrates only one floor and the air duct contains a fire damper located where the duct penetrates the floor, an air duct enclosure shall not be required.

(b) Ducts passing through two or more floors, or through a floor and a roof, and having a cross-sectional area of more than 2 square feet (0.1858 m 2 ) shall be encased in shafts of noncombustible construction having a minimum 2-hour fire resistance rating. Where the cross-sectional area is 2 square feet (0.1858 m 2 ) or less, such ducts may be fire protected with construction having a minimum fire resistance rating of 1 hour placed as close as possible to the duct in lieu of a shaft, with the space between the duct and the floor construction filled solidly with inert noncombustible material for the full depth of the floor construction. Exceptions and qualifications are as follows:

(1) The encasing of ducts shall not be required for ducts which are cut off from the main portion of the duct by approved fire dampers.

(2) Ducts which are located in one story and have all duct openings extending through a floor to the story next above or below may in lieu of such fire resistive enclosure be provided with approved fire dampers at each such point where the floor is pierced.

(3) Two or more ducts serving separate floors shall not be encased in the same fire resistive enclosure unless approved fire dampers are installed where each branch is taken from such encased ducts.

(4) A branch duct having a cross-sectional area of less than 20 square inches (12900 mm 2 ) which passes through one floor only and pierces the floor at one point only to supply air conditioning units in one story only is not required to be encased. Where a branch serves connectors which pierce the floor at more than one point, the portion of the duct below the floor shall be encased with not less than one-half inch (12.7 mm) of noncombustible insulating material such as metal lath and plaster or shall be enclosed with noncombustible material such as by locating above a noncombustible ceiling.

3–3.4.2 A fire-resistive enclosure used as an air duct shall conform with 3–3.4.1 and 2–3.1. Gypsum board systems shall be constructed in accordance with RS 5–1A or RS 5–1B, and the corners of such systems shall be constructed in accordance with details approved by the Board of Standards and Appeals under Calendar Number 354-76-SM or equivalent.

3–3.4.3 Shafts that constitute air ducts or that enclose air ducts used for the movement of environmental air shall not enclose:

(a) Exhaust ducts used for the removal of smoke and grease-laden vapors from cooking equipment;

(b) Ducts used for the removal of flammable vapors;

(c) Ducts used for moving, conveying, or transporting stock, vapor or dust;

(d) Ducts used for the removal of nonflammable corrosive fumes and vapors;

(e) Refuse and linen chutes; or

(f) Piping.

Exception: Noncombustible piping conveying water or other nonhazardous or nontoxic materials.

3–3.4.4 Fire dampers shall be installed at each direct or ducted opening into or out of enclosures required by 3–3.4.1.

Exception No. 1: Where an air duct system serving only one story is used only for exhaust of air to the outside and is contained within its own dedicated shaft.

Exception No. 2: Where branch ducts connect to enclosed exhaust risers meeting the requirements of 3–3.4.1 or 3–3.4.2 in which the airflow moves upward and steel subducts at least 22 in. (559 mm) in length are carried up inside the riser for each inlet and the riser is appropriately sized to accommodate the flow restriction created by the subduct. (See Figure 3–3.)

Exception No. 3: Where such openings are provided for ducts serving air terminal units and the ducts or duct connectors meet all of the following conditions. (See Figure 3–3.):

(a) They have a cross-sectional area of less than 20 sq. in. (12900 mm 2 );

(b) They meet the requirements specified in 2–3.1;

(c) They serve air terminal units which directly abut the shaft enclosure or have continuous architectural enclosures constructed the same as the air terminal unit; and

(d) They meet the requirements of 3–4.6.4.

3–3.5 Location of Smoke Dampers.

3–3.5.1 Smoke dampers shall be installed at or adjacent to the point where air ducts pass through required smoke barriers, partitions adjacent to spaces leading from elevators to a street or to the exterior of a building, and any construction required to have a rating of 2 hrs. or more, but in no case shall a smoke damper be installed more than 2 ft. (610 mm) from the barrier or after the first air duct inlet or outlet, whichever is closer to the smoke barrier.

Exception No. 1: Smoke dampers shall not be required on air systems other than where necessary for the proper function of that system where the system is designed specifically to:

(a) Function as an engineered smoke-control system, including the provision of continuous air movement with the air-handling system; or

(b) Provide air to other areas of the building during a fire emergency; or

(c) Provide pressure differentials during a fire emergency.

Exception No. 2: Smoke dampers shall not be required to be located within a prescribed distance of a fire rated enclosure where isolation smoke dampers are used in air-handling equipment. (See 2–3.9.2.)

Exception No. 3: Buildings classified in Occupancy Group J-2.

Exception No. 4: Smoke dampers shall not be required in ducts where the air continues to move and the air-handling system installed is arranged to prevent recirculation of exhaust or return air under fire emergency conditions.

3–3.5.2 Where penetration of a smoke barrier is required to be provided with a fire damper, a combination fire and smoke damper equipped and arranged to be both smoke responsive and heat responsive shall be permitted.

3–3.5.3 The above requirements are applicable to new buildings and existing buildings where new fire rated partitions are erected or where existing ducts are being modified or reconfigured in such a way as to require the installation of smoke and/or fire dampers.

3–4 Fire Dampers, Smoke Dampers, and Ceiling Dampers.

3–4.1 Fire dampers used for the protection of openings in walls, partitions, or floors with fire resistance ratings of less than 3 hours shall have a one and one-half hour fire protection rating in accordance with UL 555/99, Standard for Safety Fire Dampers.

3–4.2 Fire dampers used for the protection of openings in walls, partitions, or floors having a fire resistance rating of 3 hours or more shall have a 3-hour fire protection rating in accordance with UL 555/99, Standard for Safety Fire Dampers.

3–4.3 Smoke dampers used for the protection of openings in smoke barriers or in engineered smoke-control systems shall be classified in accordance with UL 555S/99, Standard for Safety Leakage Rated Dampers for Use in Smoke Control Systems.

3–4.4 Ceiling dampers or other methods of protecting openings in rated floor/roof-ceiling assemblies shall comply with the construction details of the tested floor/roof-ceiling assembly or with listed ceiling air diffusers, or with listed ceiling dampers. Ceiling dampers shall be tested in accordance with UL 555C/96, Standard for Safety Ceiling Dampers.

3–4.5 Damper Closure.

3–4.5.1 All fire dampers and ceiling dampers shall close automatically, and they shall remain closed upon the operation of a listed fusible link or other approved heat-actuated device located where readily affected by an abnormal rise of temperature in the air duct.

3–4.5.2 Fusible links shall have a temperature rating approximately 50°F (28°C) above the maximum temperature that normally is encountered when the system is in operation or shut down, but not less than 160°F (71°C).

Exception: Where combination fire/smoke dampers are located within air ducts that are part of an engineered smoke-control system, fusible links or other approved heat-responsive devices shall have a temperature rating approximately 50°F (28°C) above the maximum smoke-control system designed operating temperature, but shall not exceed the UL 555S/99, Standard for Safety Leakage Rated Dampers for Use in Smoke Control Systems degradation test temperature rating of the combination fire/smoke damper or a maximum of 350°F (177°C).

3–4.5.3 A provision for remote opening of combination fire and smoke dampers, where necessary for smoke removal, shall be permitted. Such dampers shall have provisions that allow them to reclose automatically upon reaching the damper's maximum degradation test temperature in accordance with UL 555S/99, Standard for Safety Leakage Rated Dampers for Use in Smoke Control Systems.

3–4.5.4 Dampers shall close against the maximum calculated airflow of that portion of the air duct system in which they are installed. Fire dampers shall be tested in accordance with UL 555/99, Standard for Safety Fire Dampers. Smoke dampers shall be tested in accordance with UL 555S/99, Standard for Safety Leakage Rated Dampers for Use in Smoke Control Systems.

Exception: Where provisions for fan or airflow shutdown are provided.

3–4.6 Installation. (See 2–3.4 for access.)

3–4.6.1 The locations and mounting arrangement of all fire dampers, smoke dampers, ceiling dampers, and fire protection means of a similar nature required by this standard shall be shown on the mechanical plans pursuant to § 27-157(c) or § 27-162 of the Building Code.

3–4.6.2 Fire dampers (including their sleeves), smoke dampers, and ceiling dampers shall be installed in accordance with the conditions of their listings and the manufacturer's installation instructions.

3–4.6.3 The thickness of sleeves for fire dampers shall not be less than that associated with the conditions of rating required by § 3–4.

Exception: Where UL 555/99, Standard for Safety Fire Dampers, permits sleeve thickness to be the same as that of the duct gauge, such thickness shall not be less than that specified in Table 3–4.6.3.

Table 3–4.6.3

Minimum Sleeve Thickness Permitted in Accordance

with UL 555/99

(See 3–4.6.3, Exception.)

Air Duct Diameter or Maximum Width Minimum Sleeve Thickness (in.) (mm) (in.) (ga.) 12 or less 305 0.018 26 13–30 330–762 0.024 24 31–54 787–1370 0.030 22 55–84 1395–2135 0.036 20 85 or more 2160 0.047 18

3–4.6.4 Patching, Filling and Repairing—Where air ducts pass through walls, floors or partitions required to have a fire resistance rating and where fire dampers are not required, the opening in the construction around the air duct shall not exceed a 1-in. (25.4 mm) average clearance on all sides and shall be firestopped in accordance with the Building Code.

Exception: Where fire dampers are installed, proper clearance for expansion shall be maintained. (See 3–4.6.)