NYC Administrative Code SECTION 11 – INSTALLATION REQUIREMENTS
11.9 Delete this paragraph and substitute the following: "When compressors or self contained unit systems are housed in a machinery space, other than in a machinery room or a plenum, the space shall be ventilated in accordance with the requirements of table 7."
11.13.4 After the last sentence add the following: "Exhaust registers or outlets capable of exhausting the amount required by table 7 shall be located near the floor unless a lighter than air refrigerant is used; when a lighter than air refrigerant is used, the exhaust registers or outlets shall be located near the ceiling. Emergency remote controls, properly labeled and in an accessible location outside the machinery room shall be provided to start and stop the fans."
Add the following paragraph: "11.13.51 Emergency remote controls, properly labeled and in an accessible location outside the machinery room shall be provided to stop the compressors."
Add the following paragraph:
"11.14 All insulation including finishes, coverings, vapor barriers, and adhesives used with refrigeration systems shall have a maximum flame spread rating of 25 without evidence of continued progressive combustion and with a maximum smoke developed rating of 50. If applied with adhesives the insulation may be tested as applied with adhesives; or the adhesives used shall have a maximum flame spread rating of 25 and a maximum smoke developed rating of 50. Tests shall be performed in accordance with ASTME 84–61."
11.12.2 After the words "main exit hallways" insert the words "or stairways." Delete the last part of the last sentence in the paragraph starting with the words "if there are no joints, etc.,", and substitute "if the section in the hallway is contained in a rigid metal pipe and is labeled in accordance with the provisions of paragraph 13.2."