NYC Administrative Code RS 13-2 EXHAUST SYSTEMS FOR COOKING SPACES
1. CONSTRUCTION.—Exhaust systems for cooking spaces shall be separate systems that may exhaust a number of such spaces. The ductwork shall be constructed as required by reference standards RS 13–1, with the following modifications:
(a) Ducts shall be of galvanized steel and the minimum gauge shall be as follows:
(1) In all buildings other than those classified as residential occupancy, a minimum of no. 16 galvanized sheet gauge shall be used.
(2) In residential occupancies other than one- and two-family dwellings a minimum of no. 18 galvanized sheet gauge shall be used.
(3) In one- and two-family dwellings the gauges shall be as required in reference standard RS 13–4 for supply ductwork.
(b) Where branch ductwork is to be used to exhaust vapors from dishwashers, pot sinks, or other similar equipment of a commercial type from which moisture is emitted, copper or aluminum of the minimum gauges and weights required in reference standard RS 13–1, or other equivalent moisture and corrosion resistant metals, shall be used. Such ductwork shall be installed so that condensate cannot leak from it.
(c) Sub-ducts, as described in reference standard RS 13–1, shall not be permitted in lieu of fire dampers.