NYC Administrative Code RS 13-1, Chapter 1 GENERAL
1–1 Introduction.—An air duct system has the potential to convey smoke, hot gases, and flame from area to area and to supply air to aid combustion in the fire area. For these reasons, fire protection of an air duct system is essential to safety, to life and the protection of property. However, an air duct system's fire integrity also enables it to be used as part of a building's fire protection system. (See §1–4)
1–2 Scope.—This standard shall apply to all systems for the movement of environmental air in structures that are not otherwise exempted by § 27-777(b) of the Administrative Code.
1–3 Purpose.
1–3.1 This standard is intended to prescribe minimum requirements for safety to life and property from fire. These requirements are intended to:
(a) Restrict the spread of smoke through air duct systems within a building or into a building from the outside.
(b) Restrict the spread of fire through air duct systems from the area of fire origin whether located within the building or outside.
(c) Maintain the fire-resistive integrity of building components and elements such as floors, partitions, roofs, walls, and floor/roof-ceiling assemblies affected by the installation of air duct systems.
(d) Minimize ignition sources and combustibility of the elements of the air duct systems.
(e) Permit the air duct systems in a building to be used for the additional purpose of emergency smoke control.
1–3.2 Nothing in this standard is intended to prevent the use of new methods or devices, provided that sufficient technical data is submitted to the Department of Buildings to demonstrate that the proposed method or device is equivalent in quality, strength, durability, and safety to that prescribed by this standard.
1–3.3 The provisions of this standard are not intended to be applied retroactively. Where the system is being altered, extended, or renovated, the requirements of Article 4 of Subchapter 1 of Chapter 1 of Title 27 of the Administrative Code shall govern the applicability of this standard.
1–4 Maintenance.—The appropriate provisions of the Building Code shall apply.
1–5 Definitions.
Accepted—Means "Accepted" by the Materials and Equipment Acceptance Division of the Department of Buildings.
NOTE: The MEA Division is the "authority having jurisdiction" in use of materials, assemblies, forms, methods of construction, and service equipment subject to the acceptance requirements of Building Code §§ 27-131 and 27-135.
Air Cleaner—A device used to reduce or remove airborne solids from heating, ventilating and air conditioning systems by electrostatic means.
Air Distribution System—A continuous passageway for the transmission of air that, in addition to air ducts, shall be permitted to include air connectors, air duct fittings, dampers, plenums, fans, and accessory air handling equipment, but that does not include conditioned spaces.
Air Duct—A conduit for conveying air.
Air Duct Connector—A conduit for transferring air between an air duct or plenum and an air terminal unit or an air inlet or an air outlet. (For limitations on use of air connectors, see §2–3.2.1.)
Air Duct Covering—A material such as adhesive, insulation, banding, a coating(s), film, or a jacket used to cover the outside surface of an air duct, fan casing, or duct plenum.
Air Duct Lining—A material such as an adhesive, insulation, a coating(s), or film used to line the inside surface of an air duct, fan casing, or duct plenum.
Air Filters—A device used to reduce or remove airborne solids from heating, ventilating, and air conditioning systems by mechanical means.
(a) A Class 1 air filter is one which, when clean, does not contribute fuel when attacked by flame, and emits only negligible amounts of smoke when tested in accordance with RS 13–15.
(b) A Class 2 air filter is one which, when clean, burns moderately when attacked by flame or emits moderate amounts of smoke or both when tested in accordance with RS 13–15.
Air Inlet—Any opening through which air is removed from a space and returned to an air distribution system.
Air Outlet—Any opening through which air is delivered to a space from an air distribution system.
Air Terminal Unit—An appliance receiving, conditioning, and delivering air supplied through an air distribution system.
Air Transfer Opening—An opening designed to allow the movement of environmental air between two contiguous spaces.
Approved—See subchapter 2 of the Building Code for definition.
Authority Having Jurisdiction—Means "The Commissioner of the Department of Buildings" or his designee.
Blower—A fan used to force air under pressure through an air duct system.
Ceiling Damper—A device installed to limit radiant heat transfer through an air outlet or air inlet opening in the ceiling of a floor/roof-ceiling assembly having not less than a 1-hour fire resistance rating. Such a device is described in the construction details for some tested floor/roof-ceiling assemblies.
Environmental Air—Air that is supplied, returned, recirculated, or exhausted from spaces for the purpose of modifying the existing atmosphere within the building.
Exhaust Air—Air removed from a space and not reused.
Exhaust System—An assembly of connected ducts, plenums, fittings, registers, grilles and hoods through which air is conducted from the space or spaces and exhausted to the outside atmosphere.
Fan—An assembly comprising blades or runners and a housing or casing that is either a blower or an exhaust fan.
Fire Damper—A device installed in an air distribution system that is designed to close automatically upon detection of heat, to interrupt migratory airflow, and to restrict the passage of flame. A combination fire and smoke damper meets the requirements of both.
Fire-Resistance Rating—See subchapter 2 of the Building Code for definition.
Flame Spread Rating—The measurement of the comparative rate of propagation of flame over the surface of a material as determined by a fire test made in accordance with a specified standard in subchapter five of the Building Code.
Limited Combustible Material—A building construction material not complying with the definition of noncombustible material, which, in the form in which it is used, has a potential heat value not exceeding 3500 Btu/lb (8141kj/kg) and complies with one of the following paragraphs (a) or (b). Materials subject to increase in combustibility or flame spread index/rating beyond the limits herein established through the effects of age, moisture, or other atmospheric condition shall be considered combustible.
(a) Materials having a structural base or noncombustible material, with a surfacing not exceeding a thickness of one-eighth in. (3.2 mm), that has a flame spread index/rating not greater than 50.
(b) Materials, in the form and thickness used, other than as described in (a), having neither a flame spread index/rating greater than 25 nor evidence of continued combustion, and of such composition that surfaces that would be exposed by cutting through the material on any plane would have neither a flame spread index/rating greater than 25 nor evidence of continued progressive combustion.
Listed—Equipment, materials or services included in a list published by an organization acceptable to the "authority having jurisdiction" and concerned with evaluation of products or services that maintains periodic inspection of production of listed equipment, materials or periodic evaluation of services, and whose listing states either that the equipment, material or service meets identified standards or has been tested and found suitable for use in a specified purpose.
NOTE: The means for identifying listed equipment may vary for each organization concerned with product evaluation, some of which do not recognize equipment as listed unless it is also labeled. The "authority having jurisdiction" should utilize the system employed by the listing organization to identify a listed product.
Noncombustible—See subchapter 2 of the Building Code for definition.
Plenum—An air compartment or chamber located in one story only to which one or more ducts are connected and which forms part of the air supply or return system and may be part of the building construction such as the concealed space above a ceiling. Any such air compartment or chamber in more than one contiguous story shall meet the requirements of §2–3.10.
Shall—Indicates a mandatory requirement.
Smoke—The airborne solid and liquid particulars and gases evolved when a material undergoes pyrolysis or combustion.
Smoke Barrier—See subchapter 2 of the Building Code for definition.
Smoke Control—A system that utilizes fans to produce pressure differences to manage smoke movement.
Smoke Damper—A device to resist the passage of smoke which:
(a) Is arranged to operate automatically, and
(b) Is controlled by a smoke detector, and
(c) When required shall be capable of being positioned manually from a remote command station.
A smoke damper may be a fire damper or a damper serving other functions, if its location lends itself to the multiple functions. A combination fire and smoke damper shall meet the requirements of both.
Smoke Detector—A device which senses visible or invisible particles of combustion.
Smoke Developed Rating—A smoke developed rating of a material refers to a number or classification of a material obtained according to RS 5–5.