NYC Administrative Code SECTION 13 – INSTRUCTIONS
13.1 Delete the entire paragraph and substitute: "Signs. Each refrigerating system erected on the premises shall be provided with a legible permanent sign in a prominent location, securely attached and readily accessible, indicating the name and address of the installer, the horsepower of the prime mover or compressor or the equivalent thereof in kilowatts, the kind and number of pounds of refrigerant required in the system for normal operation, and the refrigerant leakage field-test pressure applied."
13.7 Add to the last sentence in this paragraph: "and in no case more than 75 per cent of the container's capacity."
13.11 Add paragraph (d) as follows: "Where such systems are installed in machinery rooms, the instructions shall state that, in case of emergency or refrigerant leakage, the machinery room shall be vacated promptly, the system shut down by means of the required remote controls located outside the machinery room, and the room ventilated."