ANSI/NFiPA No. 90B 1996, as modified—Standard for the Installation of Warm Air Heating and Air Conditioning Systems.

The provisions of ANSI/NFiPA No. 90B-96 together with the modifications thereto shall constitute Reference Standards RS 13–4 and RS 14–1.

The appendices to ANSI/NFiPA No. 90B-96 are not part of this Reference Standard. These are for informational purposes only.

Wherever reference is made to the "National Electrical Code" it shall be changed to read "Electrical Code of the City of New York."

The New York State Energy Conservation Construction Code also regulates the design and construction of heating, ventilating, and air conditioning systems in New York City.

STANDARD FOR THE INSTALLATION OF WARM AIR HEATING AND AIR CONDITIONING SYSTEMS

ANSI/NFiPA No. 90B—1996, AS MODIFIED

CONTENTS

1–1 Scope 1–2 Purpose 1–3 Definitions 2–1 Supply Systems 2–2 Return Systems 2–3 Common Requirements 3–1 Clearances to Combustible Material 3–2 Firestopping 4–1 Equipment 4–2 Electric Wiring and Equipment 4–3 Controls

Index—Refer to NFPA 90B/96

Chapter 1—General

1–1 Scope—This standard shall apply to all systems for the movement of environmental air in structures that are otherwise exempted by § 27-777(b) of the Administrative Code, or whose heating systems are subject to § 27-812 of the Administrative Code.

1–1.1 The provisions of this standard are not intended to be applied retroactively. Where the system is being altered, extended, or renovated, the requirements of Article 4 of Subchapter 1 of Chapter 1 of Title 27 of the Administrative Code shall govern the applicability of this standard. (Added City Record Apr. 4, 2002 §4, eff. May 4, 2002.)

. . . . . . . . . .

1–3 Definitions.

Accepted. Means "Accepted" by the Materials and Equipment Acceptance Division of the Department of Buildings.

NOTE: The MEA Division is the "authority having jurisdiction" in use of materials, assemblies, forms, methods of construction, and service equipment subject to the acceptance requirements of Building Code §§ 27-131 and 27-135.

Air Filter.

(a) A Class 1 air filter is one which, when clean, does not contribute fuel when attacked by flame, and emits only negligible amounts of smoke when tested in accordance with RS 13–15.

(b) A Class 2 air filter is one which, when clean, burns moderately when attacked by flame or emits moderate amounts of smoke or both when tested in accordance with RS 13–15.

Approved. See subchapter 2 of the Building Code for definition.

Authority Having Jurisdiction. The Commissioner of the Department of Buildings or his designee.

. . . . . . . . . .

Listed. Equipment, materials or services included in a list published by an organization acceptable to the "authority having jurisdiction" and concerned with evaluation of products or services that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states either that the equipment, material or service meets identified standards or has been tested and found suitable for use in a specified purpose.

NOTE: The means for identifying listed equipment may vary for each organization concerned with product evaluation, some of which do not recognize equipment as listed unless it is also labeled. The "authority having jurisdiction" should utilize the system employed by the listing organization to identify a listed product.

Noncombustible Material. See subchapter 2 of the Building Code for definition.

Chapter 2 System Components

. . . . . . . . . .

2–1.1.1 Supply ducts shall be:

(a) Class 0 or Class 1 rigid or flexible air ducts tested in accordance with UL 181/96, Standard for Safety Factory-Made Air Ducts and Air Connectors; or

(b) Of sheet metal having a nominal thickness as shown in Table 2–1.1.1.

Exception No. 1: Supply ducts that are completely encased in not less than 2 in. (51 mm) of concrete in a floor slab shall not be required to meet the requirements of 2–1.1.1, except within 2 ft. (0.61 m) of the furnace supply plenum and within 2 ft. (0.61 m) of a vertical connection to a riser or register.

Exception No. 2: Supply ducts for a separate air cooling system, not interconnected to any warm air heating system, serving a single-family dwelling shall not be required to meet the requirements of 2–1.1.1, provided that they are not closer than 2 ft. (0.61 m) to any furnace or its supply plenum, boiler, or other heat-producing appliances and that they comply with 2–2.1.1, 2–2.1.3, 2–2.2, 2–2.3, and 2–2.4 as specified for return ducts.

Exception No. 3: Vibration isolation connectors in duct systems shall be made of approved flame-retardant fabric or shall consist of sleeve joints with packing of approved noncombustible material. The fabric shall not exceed 10 in. (254 mm) in length in the direction of airflow.

Exception No. 4: A Class 0 or Class 1 rigid or flexible air duct shall not be used as a vertical air duct that is more than two stories in height.

Exception No. 5: A Class 0 or Class 1 rigid or flexible air duct shall not be used in an air duct containing air at a temperature in excess of 250°F (121°C).

2–1.1.2 Supply ducts shall be installed in conformance with:

(a) The conditions of their listing;

(b) RS 14–22.

2–1.2 Air Connectors—Air connectors are limited-use, flexible air ducts that shall not be required to conform to the requirements for air ducts, provided they conform to the following provisions:

(a) Air connectors shall conform to the requirements for Class 0 or Class 1 connectors when tested in accordance with UL 181/96, Standard for Safety Factory-Made Air Ducts and Air Connectors.

(b) Class 0 or Class 1 air connectors shall not be used in ducts containing air at temperatures in excess of 250°F (121°C).

(c) An air connector run shall not exceed 14 ft. (4.3 m) in length.

(d) Air connectors shall not pass through any wall, partition, or enclosure of a vertical shaft that is required to have a fire resistance rating of 1 hour or more.

(e) Air connectors shall not pass through floors.

(f) Air connectors shall be installed in conformance with the conditions of their approval.

. . . . . . . . . .

2–3.1.2 Duct coverings and linings shall not flame, glow, smolder, or smoke when tested in accordance with ASTM C 411/97, Standard Test Method for Hot-Surface Performance of High-Temperature Thermal Insulation, at the temperature to which it is exposed in service. In no case shall the test temperature be below 250°F (121°C).

2–3.2 Joints—Joints and seams shall be fastened securely and made substantially airtight. Slip joints shall have a lap of at least 1 in. (25.4 mm) and shall be fastened individually (see Figure 2–3.2). Tape shall be permitted to be used for sealing joints but, where exposed to the air in the system, it shall not be more combustible than fabric complying with RS 7–3.

Closure systems for use with rigid air ducts tested in accordance with UL 181/96, Standard for Safety Factory-Made Air Ducts and Air Connectors, shall have been tested and listed in accordance with UL 181A/94, Standard for Safety Closure Systems for Use with Rigid Air Ducts and Air Connectors, and used in conformance with the conditions of the listing.

. . . . . . . . . .

2–3.5.1 Registers shall be constructed of metal or shall conform with the following:

(a) Registers shall be made of a material classified as 94 HB when tested as described in UL 94/96, Standard for Safety Test for Flammability of Plastic Materials for Parts in Devices and Appliances.

(b) Floor registers shall resist, without structural failure, a 200-lb (90.7-kg) concentrated load on a 2-in. (51-mm) diameter disc applied to the most critical area of the exposed face of the register. For this test, the register shall be at a temperature not less than 165°F (74°C) and shall be supported in accordance with the manufacturer's instructions.

. . . . . . . . . .

2–3.5.3 Fittings connecting the registers to the duct system shall be constructed of metal or material that complies with the requirements of Class 0, Class 1, or Class 2 ducts in UL 181/96, Standard for Safety Factory-Made Air Ducts and Air Connectors.

. . . . . . . . . .

4–1.1.3 Construction.

(a) Where the warm air supply is from a warm air furnace, heating panels shall be enclosed on all sides with material that is wholly noncombustible or that possesses a flame spread classification of not over 25 as determined in accordance with RS 5–5. This enclosing material shall be attached securely to the building structure; joints and seams shall be substantially airtight. Braces and hangers inside the chamber shall be noncombustible.

(b) Where the warm air supply is from a steam or hot water heat exchanger, heating panels shall either comply with 4–1.1.3(a) or shall be enclosed on all sides with material not more flammable than 1-in. (25.4-mm) (nominal) wood boards. This enclosing material shall be attached securely to the building structure; joints and seams shall be substantially airtight. No single vertical heating panel shall serve more than one story.

. . . . . . . . . .

4–1.3.1 Air filters shall have either a Class 1 or Class 2 rating in accordance with RS 13–15.

. . . . . . . . . .

4–1.3.3 Liquid adhesive coatings used on filters shall have a flash point not less than 325°F (163°C) in accordance with RS 14–13.

4–1.3.4 All air filters shall be kept free of excess dust and combustible material. Unit filters shall be renewed or cleaned when the resistance to airflow has increased to two times the original resistance or when the resistance has reached a value of recommended replacement by the manufacturer. A permanently installed draft gauge shall be provided for this purpose. Where the filters are of the automatic liquid adhesive type, sludge shall be removed from the liquid adhesive reservoir regularly.

4–1.4 Air-Cooling Equipment—Mechanical refrigeration used with air duct systems shall be installed in accordance with RS 13–6.

. . . . . . . . . .

4–2 Electric Wiring and Equipment—Electric wiring and equipment shall be adequate for safe operation and shall be installed in accordance with the New York City Electrical Code. In addition, a disconnecting means shall be installed within sight and easy reach in the ungrounded leads of each power circuit to electrically operated components that are in unprotected locations and in other locations not readily accessible for service.

. . . . . . . . . .

4–3.2 Fan Control for Stoker-Fired Furnaces—Where a warm air furnace equipped with a fan to circulate the air is stoker-fired, it also shall be equipped with an automatic overrun control to start the fan when the air in the furnace bonnet or at the beginning of the main supply duct at a point not affected by radiated heat reaches a temperature not higher than 200°F (93°C) after the stoker and fan (in its normal operation) have been shut down as a result of a satisfied thermostat. If a manual disconnect is installed in the air circulating fan electrical circuit, it shall be installed to deenergize both the fan and the stoker simultaneously. Solid fuel may be used only as permitted by Local Law 93/85.

. . . . . . . . . .

4–3.4 Thermostatically Controlled, Hand-Fired, Solid-Fuel Burning Furnaces. Hand-fired, solid-fuel burning furnaces on which the furnace draft is controlled by a thermostat shall be equipped with the following:

(a) A fail-safe 250°F (121°C) limit control installed not more than 10 in. (254 mm) above the top surface of the heat exchanger in a supply plenum that extends at least 12 in. (305 mm) above the top surface of the heat exchanger; and

(b) A barometric draft control operated by draft intensity and permanently set to limit the draft to a maximum intensity of 0.13 in. (32.4 Pa) of water gauge. A fail-safe limit control is a limit control that automatically checks the furnace in the event of power failure or shutoff or that automatically checks the furnace when a temperature of 250°F (121°C) is reached, whether or not power is available.

(c) Solid fuel may be used only as permitted by Local Law 93/85

4–3.5 Air-Circulating Fan Controls. Where a hand-fired, solid-fuel burning furnace is equipped with a fan to circulate the air, it shall be equipped with fan controls as required for stoker-fired furnaces by 4–3.2. Solid fuel may be used only as permitted by Local Law 93/85.