ANSI/NFiPA 96–1984—Standard for the Installation of Equipment for the Removal of Smoke and Grease-Laden Vapors from Commercial Cooking Equipment, as Modified.

MODIFICATIONS—The provisions of ANSI/NFiPA 96–1984 shall be subject to the following modifications. The chapter, section and paragraph numbers are from that standard.

Amend Section 1–3.1 as follows:

1–3.1 Commercial cooking equipment used in processes producing smoke or grease-laden vapors and fumes such as from ranges, deep fat fryers, grills, broilers, candy kettles, cruller furnaces and ovens shall be equipped with an independent exhaust system complying with the following:

(a) A hood complying with the requirements of Chapter 2, and

(b) A duct system complying with the requirements of Chapter 3, and

(c) Grease removal devices complying with the requirements of Chapter 4, and

(d) Fire extinguishing equipment complying with the requirements of Chapter 7.

Add Section 1–3.1.1:

1–3.1.1 Where restaurant type equipment is installed and is used only for warming, where no frying or grilling is done, and where no grease-laden vapors or fumes can be generated, compliance with reference standard RS 13–6 shall not be required, and the ductwork may be constructed as required in reference standard RS 13–2. Where restaurant type equipment is installed for periodic cooking use, for other than commercial only, in community rooms of multiple dwellings, firehouses and other low hazard occupancies, determined by the commissioner, automatic fire extinguishing systems shall not be required and the ductwork may be constructed as required in reference standard RS 13–1.

Replace Section 1–3.3 with the following:

1–3.3 Permits in accordance with Section 27-147 of the Administrative (Building) Code shall be required for the alteration, replacement, or relocation of any exhaust or extinguishing system or part thereof, or cooking equipment.

1–3.3.1 Upon the issuance of such permit, the Contractor shall install the system as described on the applications and plans, examined and approved by the Department of Buildings.

1–3.3.2 Upon completion, the work shall be subject to a performance test conducted by the installer and witnessed by a representative from the Fire Department for the purpose of determining the performance of the installed system in accordance with Section 27-4275 of the Administrative Code.

1–3.3.3 Any discrepancies between the system as installed and the approved plans which prevents certification, shall be brought to the attention of the Department of Buildings and the Applicant of Record.

Add the following sections:

3–2.9.1.1 If the building is less than 4 stories in height and of construction classification II–C, II–D and II–E, the enclosure wall shall have a fire resistance rating of not less than one-hour.

3–2.9.4 Branch ducts from other equipment in the same kitchen area, for which hoods and filters are not required, or from registers exhausting the kitchen space in general, may be connected to the main hood exhaust duct if the following requirements are complied with:

(a) A fusible link fire damper of the same gauge as the hood exhaust duct shall be added at the point of connection of the branch duct to the hood exhaust duct.

(b) If the branch connection is made to the portion of the ductwork that will contain the fire extinguishing medium, then the fire dampers required in above shall be arranged to close automatically upon the operation of the fire extinguishing system.

(c) The branch connection shall be made in either the top or sides of the main duct in a manner to prevent grease from flowing into the branch duct.

(d) The branch ducts shall be constructed of steel, aluminum, or copper of the gauges and weights required in reference standard RS 13–1; and they shall be insulated with one inch of magnesia or other material having equivalent insulative and fire resistance qualities.

(e) All registers in these branches shall have fusible link actuated dampers.

(f) When branch ductwork is to be used to exhaust vapors from dishwashers, pot sinks, or from other equipment of a commercial type from which moisture is emitted, copper, aluminum, or other corrosion resistant metals of the minimum gauges and weights required in reference standard RS 13–1 shall be used. Such ductwork shall be installed so that condensate cannot leak from it.

3–2.9.5 All hoods in a single room or kitchen and/or all hoods in separate rooms may be connected to the same system, provided all of the hoods are part of the same facilities and are located on the same floor and under the control of one owner or tenant.

3–2.10 Insulation.

3–2.10.1 A minimum insulation covering of two-inches of magnesium or calcium silicate block, attached with galvanized steel wire or construction equivalent in insulating and fire resistance qualities, shall be applied to all ducts inside of the building. The insulation shall be applied up to the outer face of the discharge from the building and shall also be applied to the housing of the exhaust fan when it is located inside of the building. Care shall be taken to insure that the insulation extends through the walls and roofs to separate the ducts from the building construction. Masonry or concrete ducts shall not require insulation.

Replace section 3–3.1 with the following:

3–3.1 Materials.—Ducts shall be constructed in accordance with Table 15–4 of Section 27-863 for low temperature chimneys.

Amend the following section:

3–5.1 In all buildings more than one (1) story in height and in one-story buildings where the roof or roof-ceiling assembly is required to have a fire resistance rating, the ducts shall be enclosed in a continuous enclosure extending from the ceiling above the hood, through any vertical spaces passing through other floors, or through the roof so as to maintain the integrity of the fire separations required by the applicable building code provisions. Horizontal ducts passing through fire walls or partitions shall be protected by an enclosure or thimble extending at least equal to the width of the duct. Where passing over exit corridors, the protection shall be for the entire length of the duct within the corridor. The enclosure shall conform to the following:

Amend the following section:

4–1.2.1.2 Grease filters shall be accepted for use with commercial cooking equipment.

Add the following section:

4–1.2.1.3 Grease filters shall comply with UL 1046–1979. Standard for Grease Filters for Exhaust Ducts.

5–1.3 Flexible connectors at fans shall be made of non-combustible material that has a mineral base and that cannot be penetrated by grease.

7–1.3 Approved fixed pipe extinguishing equipment, in addition to approved filters or other approved means of grease extraction, shall be provided where any of the following conditions occur:

(a) Where the discharge of the exhaust system is located in a wall below the top floor of a building, such discharges shall be permitted only where the wall containing the discharge is constructed with an outer surface of non-combustible material, having a fire resistance rating of one-hour or more and where this non-combustible material extends 8 ft. horizontally on either side of the opening and projects to a height of 40 ft. above the opening.

(b) Where the length of duct from the most remote hood in the system to the discharge from the building is more than 20 feet.

(c) Where the total exhaust air from all hoods served by the system is more than 3,000 cfm.

7–2.2 The following minimum requirements shall apply for the particular type of extinguishing system:

7–2.2.1 Where steam is used: A continuous source of steam supply of at least 15 psi shall be provided. The pipe sizes of the main branch shall be at least 1 1/2 inch in diameter and to the last stream jet or nozzle shall be at least 3/4 inch in diameter. Such nozzles shall be standard 1/2 inch open sprinkler heads or equivalent in spray pattern and delivery. Nozzles shall be located throughout the entire run of duct up to the flue or riser duct and the confining damper shall be located at this point. The piping within the hood and ductwork shall be a minimum of ANSI Schedule 40 steel with 125 psi standard cast iron screwed fittings. The piping shall be arranged and/or dipped to remove all condensate on both sides of the automatic and manual control valves. A shut-off valve that is sealed open shall be located in the branch line before the control valve.

7–2.2.2 Where a fine water spray is used: All pipe and valve sizes shall conform to provisions for the installation of sprinklers in reference standard RS 17–5. The minimum static pressure at the highest nozzle shall be at least 30 psig. Also, 1/2 inch open wide pattern nozzles shall be installed throughout.

7–2.2.3 Where carbon dioxide is used: At least one 50 lb. cylinder of carbon dioxide shall be provided for each installation up to 400 cu. ft. of hood and duct volume. For every additional 400 cu. ft. or portion thereof, an additional 50 lb. cylinder shall be installed. A confining damper shall be installed in the duct not less than 25 feet down stream from the last uptake or inlet from the hood or equipment into the duct.

7–2.2.4 Where listed pre-engineered dry chemical and liquid agent is used: All pipe and fittings shall conform to the manufacturer's specifications and limitations as approved by a national recognized testing laboratory, and approved by the Board of Standards and Appeals. Confining dampers shall be installed in the duct work, as per section 3–2.9.4, only for branch ducts connected to the main grease exhaust duct and shall be automatically operated either by means of mechanical fusible links or electric thermostats connected and/or wired to the extinguishing system to effect simultaneous operation. Exhaust fans shall not be inter-wired with the extinguishing system. They shall continue operation during and after the extinguishing system's discharge.

Amend the following section:

7–3.1.2 Fixed pipe extinguishing systems in a single hazard fire section (see Section 1–2) shall be arranged for simultaneous automatic operation upon actuation of any one of the systems.

Exception: When the fixed pipe extinguishing system is an automatic sprinkler system.

7.3.2 Except as otherwise provided, the following additional requirements shall apply for all extinguishing systems:

7–3.2.1 Manual controls or manual releases shall be accessibly located whenever practical on a path of egress from the protected area and at least 10 feet but not more than 35 feet from the hood and shall be sealed closed with a light wire seal or easy break-glass control. Manual controls shall be of quick-opening lever type and shall be operated by a chain or insulated handle.

7–3.2.2 Signs shall be affixed to all hand valves, manual control, or manual releases indicating the purpose of these devices and designating their proper operating position for manual operation.

7–3.2.3 The duct system and any deep frying units shall be provided with an adequate number of nozzles to effectively extinguish a fire. As minimum requirements, one nozzle shall be installed at each inlet to the duct and one at each side of any required confining damper. The nozzle on the downstream side of any required confining damper shall have a capacity of at least 10 percent of the total capacity of the system. The distance between other nozzles throughout the duct shall not exceed 10 feet on centers, except as provided in 7–2.2.4, and thermal detecting units shall be located at all duct inlets.

7–3.2.4 The automatic releasing equipment and heat detecting units shall be approved.

7–3.3 Clear, concise and complete operating and cleaning instructions covering all components of the exhaust system shall be permanently posted outside the main entrance or other suitable entrance to the kitchen; and, a schematic drawing or sketch at least 8 1/2 inches by 11 inches in size, showing the origin, run and terminus of the grease duct shall be similarly posted.

Replace Sections 7–4.1 and 7–4.2 with the following:

7–4.1 Complete drawings of the system installation to include the hood(s), exhaust duct(s), and appliances along with the interface of the fire extinguishing system detectors, piping, nozzles, fuel shut-off devices, agent storage container(s), and manual actuation device(s) shall be submitted in accordance with the requirements of sub-article 116.0 of this Code.

7–4.2 Installation of systems shall be made only by persons properly trained and qualified to install the specific system being provided. The installer shall certify to the Fire Commissioner that the installation is in complete agreement with the terms of the listing and the manufacturer's instruction and approved design, and that the manufacturer has qualified the installer.

Replace Section 8–2.1 with the following:

8–2.1 An inspection, test and servicing of the automatic valve operation and the fire extinguishing system by properly trained and qualified persons, on behalf of the owner, shall be made at least every six months. A record of such tests shall be kept on the premises and shall be available for inspection by the Commissioner and the Fire Commissioner.

Add the following Section: 8–4 Filters.

8–4.1 Filters shall be serviced and replaced regularly by qualified employees of the owner or by a cleaning agency. A record indicating the name of the person or firm doing the servicing and the dates when filters were cleaned or replaced shall be available for inspection by the Commissioner. They shall be cleaned or replaced as frequently as necessary, but at least every three months and no exhaust system shall be operated while cooking is being carried on without the filters installed in place.