NYC Administrative Code RS 13-1, Chapter 2 HVAC SYSTEMS
2–1 General Requirements—Equipment.
2–1.1 Equipment shall be arranged to afford access for inspection maintenance, and repair.
2–1.2 Equipment shall be selected and installed based on its proper application with respect to the manufacturer's installation instructions and listing, as applicable.
2–1.3 Equipment shall be guarded for personnel protection and against intake of foreign matter into the system.
2–1.4 Electrical wiring and equipment shall be installed in accordance with NYC Electrical Code.
2–1.5 Equipment Location—See §3–1
2–2 System Components.
2–2.1 Outside Air Intakes and Exhaust.
2–2.1.1 Outside air intakes shall be located to avoid drawing in combustible material or flammable vapor and to minimize hazard from fires in other structures.
2.2.1.2 Outside air intakes shall be protected by screens of corrosion-resistant material not larger than one-half in. (12.7 mm) mesh.
2–2.1.3 An outdoor air intake opening with gross area of more than 144 square inches (.0929 m 2 ) shall be provided with fire dampers and smoke dampers, or combined fire and smoke dampers when such opening is located as follows:
(a) Less than 30 feet (9.145 m) above grade.
(b) Less than 30 feet (9.145 m) in any direction from any opening in another building.
(c) Less than 15 feet (4.570 m) from a lot line.
(d) Less than 50 feet (15.240 m) above and less than 50 feet (15.240 m) in any direction from a roof of combustible material or a building in which the exterior walls are constructed wholly or partly of wood.
Exception No. 1: Smoke dampers shall not be required for outdoor air intake openings installed in any construction required to have a fire resistance rating of less than two hours.
Exception No. 2: Smoke dampers shall not be required for outdoor air intake openings of systems greater than 15,000 cfm (7080L/s) which are provided with smoke dampers in accordance with 2–3.9.2 and arranged as to not introduce smoke into the building or space in which the equipment is located.
2–2.1.4 To minimize the hazard from fires and from noxious, toxic or obnoxious discharges to structures, any exhaust air discharge to the outside atmosphere shall terminate at or above the roof or setback roof of the building or in an exterior wall adjoining a street, yard or court. Exhaust air discharges shall be at least 10 feet (3.050 m) above the sidewalk or ground and shall terminate at least 10 feet (3.050 m) from any window in another building or from any window in a residential portion of the same building, or from any fire escape, exterior stair, or balcony. Exhaust system openings shall be provided with vanes or louvers constructed so as to direct the air away from windows, other openings, and pedestrians. Protection of openings in exterior walls shall be in accordance with Table 3-4 of the Building Code.
2–2.2. Air Cleaners and Air Filters.
2–2.2.1 Electrostatic air cleaners shall be accepted in accordance with RS 14–6, and shall be installed in conformance with the conditions of acceptance.
2–2.2.2 Approved air filters shall have either a Class 1 or Class 2 rating in accordance with RS 13–15.
2–2.2.3 Liquid adhesive coatings used on air filters shall have flash point not lower than 325°F (163°C) as determined by RS 14–13.
2–2.2.4 Where air filters are flushed with liquid adhesives, the system shall be arranged so that the air cleaner cannot be flushed while the fan is in operation.
2–2.2.5 Liquid adhesive tanks into which removable filters are dipped should preferably be located outside the building or in a separate fire resistive room and stored in accordance with NFiPA 30/96, Flammable and Combustible Liquids Code. Such tanks shall be of metal, equipped with tight-fitting covers and shall be kept tightly covered when not in actual use.
2–2.2.6 All air filters shall be kept free of excess dust and combustible material. Unit filters shall be renewed or cleaned when the resistance to air flow has increased to two times the original resistance or when the resistance has reached a value of recommended replacement by the manufacturer. A permanently installed draft gauge shall be provided for this purpose. Where the filters are of the automatic liquid adhesive type, sludge shall be removed from the liquid adhesive reservoir regularly.
2–2.3 Fans.
2–2.3.1 Installation—Fans shall be installed in accordance with applicable NFPA standards and manufacturer's instructions. Fans shall be suitable for the specific installation.
2–2.3.2 Access—Fans shall be located, arranged and installed to afford access for inspection and maintenance.
2–2.3.3 Exposed Inlets—Exposed fan inlets shall be protected with metal screens to prevent the entry of paper, trash, and similar foreign materials.
2–2.4 Air Cooling and Heating Equipment.
2–2.4.1 Installation—Heating and cooling equipment shall be installed in accordance with applicable NFPA standards and the manufacturer's instructions. The equipment shall be approved/accepted for the specific installation. (See 2–3.3.1.)
2–2.4.2 Appliances—Materials used in the manufacturing of fan coil units, self-contained air conditioning units, furnaces, heat pumps, humidifiers, and all similar appliances shall meet the requirements of 2–3.3.1 and 2–3.3.2. Acceptance by the MEA Division of the Department of Buildings shall be sufficient evidence of compliance with this requirement.
2–2.4.3 Mechanical Cooling—Mechanical refrigeration used with air duct systems shall be installed in accordance with recognized safety practices and RS 13–6.
2–2.4.4 Furnaces—Heating furnaces, combined with cooling units in the same air duct system shall be installed in accordance with RS 14–2, if gas fired, and RS 14–3 if oil fired.
2–2.4.5 Duct Heaters—Where electrical resistance or fuel burning heaters are installed in air ducts, the air duct coverings and their installation shall comply with the provisions of 2–3.5.3. The installation of electrical duct heaters shall comply with the Electrical Code of the City of New York.
2–3 Air Distribution.
2–3.1 Air Ducts.
2–3.1.1 Air ducts shall be permitted to be rigid or flexible and shall be constructed of materials that are reinforced and sealed to satisfy the requirements for the use of the air duct system, such as the supply air system, the return or exhaust air system, and the variable volume/pressure air system.
2–3.1.2 Air ducts shall be constructed of the following materials:
(a) Iron, steel, aluminum, copper, concrete, masonry, or clay tile.
(b) Class 0 or Class 1 rigid or flexible air ducts tested in accordance with UL 181/96, Standard for Safety Factory-Made Air Ducts and Air Connectors, and installed in conformance with the conditions of listing.
Exception No. 1: Class 0 or Class 1 rigid or flexible air duct shall not be used as a vertical air duct that is more than two stories in height.
Exception No. 2: Class 0 or Class 1 rigid or flexible air ducts shall not be used for air ducts containing air at temperatures in excess of 250°F (121°C).
(c) Where the temperature of the conveyed air does not exceed 125°F (52°C) in normal service, negative pressure exhaust or return air ducts shall be permitted to be constructed of gypsum board having a maximum flame spread index/rating of 25 without evidence of continued progressive combustion and a maximum smoke developed index/rating of 50.
Exception: The maximum conveyed air temperature of 125°F (52°C) shall not apply to gypsum board material used for emergency smoke exhaust air ducts.
(d) All air duct materials shall be suitable for continuous exposure to the temperature and humidity conditions of the environmental air in the air duct.
2–3.1.3 The materials, thickness, construction, and installation of ducts shall provide structural strength and durability in conformance with recognized good practice. Air ducts shall be considered to be in compliance with this requirement where constructed and installed in accordance with RS 14–22. Where no standard exists for the construction of air ducts, they shall be constructed to withstand both the positive and negative pressures of the system.
2–3.2 Air Connectors.
2–3.2.1 Air connectors are limited-use, flexible air ducts that shall be required to conform to the provisions for air ducts where they meet the following requirements:
(a) Air connectors shall conform to the requirements for Class 0 or Class 1 connectors when tested and approved in accordance with UL 181/96, Standard for Safety Factory-Made Air Ducts and Air Connectors.
(b) Class 0 or Class 1 air connectors shall not be used for ducts containing air at temperatures in excess of 250°F (121°C).
(c) Air connector runs shall not exceed 14 ft. (4.265 m) in length.
(d) Air connectors shall not pass through any wall, partition, or enclosure of a vertical shaft that is required to have a fire resistance rating of 1 hour or more.
(e) Air connectors shall not pass through floors.
2–3.2.2 Vibration isolation connectors in duct systems shall be made of an approved flame-retardant fabric or shall consist of sleeve joints with packing of approved material, each having a maximum flame spread index/rating of 25 and a maximum smoke developed index/rating of 50. The fabric shall have a maximum length of 10 in. (254 mm) in the direction of airflow.
2–3.3 Supplementary Materials for Air Distribution Systems.
2–3.3.1 Supplementary materials such as duct coverings, duct linings, vapor retarder facings, adhesives, fasteners, tapes, and core materials added to air ducts, plenums, panels, and duct silencers used in duct systems shall have, in the form in which they are used, a maximum flame spread index/rating of 25 without evidence of continued progressive combustion and a maximum smoke developed index/rating of 50. Where air duct coverings and linings are to be applied with adhesives, they shall have a maximum flame spread index of 25 and a maximum smoke developed index of 50 when in the final dry state. (See 2–2.4.2.)
Closure systems for use with rigid air ducts tested in accordance with UL 181/96, Standard for Safety Factory-Made Air Ducts and Air Connectors, shall have been tested and listed in accordance with UL 181A/94, Standard for Safety Closure Systems for use with Rigid Air Ducts and Air Connectors, and used in accordance with the conditions of their listings.
Exception No. 1: This requirement shall not apply to air duct weatherproof coverings where they are located entirely outside of a building, do not penetrate a wall or roof, and do not create an exposure hazard.
Exception No. 2: Smoke detectors required by 4–4.2.
2–3.3.2 Air duct, panel, and plenum coverings and linings shall not flame, glow, smolder, or smoke when tested in accordance with similar test for pipe coverings, ASTM C 411/97, Standard Test Method for Hot-Surface Performance of High-Temperature Thermal Insulation, at the temperature to which they are exposed in service. In no case shall the test temperature be below 250°F (121°C).
2–3.3.3 Air duct coverings shall not extend through walls or floors that are required to be firestopped or required to have a fire resistance rating.
Exception: Where such coverings meet the requirements of 3–4.6.4.
2–3.3.4 Air duct linings shall be interrupted at fire dampers to prevent interference with the operation of devices.
2–3.3.5 Air duct coverings shall not be installed so as to conceal or prevent the use of any service opening.
2–3.3.6 Pipe insulation and coverings shall meet the requirements of 2–3.3.1 and 2–3.3.2 where installed in ducts, plenums, or concealed spaces used as part of the air distribution system.
2–3.4 Air Duct Access and Inspection.
2–3.4.1 A service opening shall be provided in air ducts adjacent to each fire damper, smoke damper, and smoke detector. The opening shall be large enough to permit maintenance and resetting of the device.
Access doors for fire dampers shall be located so that the spring catch and fusible links are accessible for purposes of inspection, resetting or repair. Where the size of the duct permits, the minimum size access door shall be 18 in. × 16 in. (457 mm × 406 mm). For dampers that are too large for an ordinary person's arms to reach from outside the duct to reset the damper and replace the fusible link, the minimum size for the access door shall be increased to 24 in. × 16 in. (610 mm × 406 mm) to allow the entrance of an individual.
Access doors shall be located as close as practicable to fire dampers and smoke dampers. If feasible, the underside of the duct shall be used rather than a side door.
Whenever spring-loaded dampers require the use of two arms (two persons, if necessary) for resetting, the access doors (one on each side of the partition, if necessary) shall be of sufficient size to allow two arms to enter the duct. Also refer to § 27-343 of the Building Code.
2–3.4.2 Service openings shall be identified with letters having a minimum height of one-half in. (12.7 mm) to indicate the location of the fire protection device(s) within.
2–3.4.3 Horizontal air ducts and plenums shall be provided with service openings (see 2–3.4.1) to facilitate the removal of accumulations of dust and combustible materials. Service openings shall be located at approximately 20 ft. (6.095 m) intervals along the air duct and at the base of each vertical riser.
Exception No. 1: Removable air outlet or air inlet devices of adequate size shall be permitted in lieu of service openings.
Exception No. 2: Service openings shall not be required in supply ducts where the supply air has previously passed through an air filter, an air cleaner, or a water spray.
Exception No. 3: Service openings shall not be required where all the following conditions exist:
(a) The occupancy has no process producing combustible material such as dust, lint, or greasy vapors. Such occupancies include banks, office buildings, churches, hotels, and health care facilities (but not kitchens, laundries, and manufacturing portions of such facilities).
(b) The air inlets are at least 7 ft. (2.135 m) above the floor or are protected by corrosion-resistant metal screens of at least 14 mesh (0.07 in.) (1.8 mm) that are installed at the inlets so that they cannot draw papers, refuse, or other combustible solids into the return air duct.
(c) The minimum design velocity in the return duct for the particular occupancy is 1,000 ft./min. (5.080 m/s).
2–3.4.4 Inspection windows shall be permitted in air ducts provided they are glazed with wired glass. However, service openings shall be provided as required in 2–3.4.1.
2–3.4.5 Openings in walls or ceilings shall be provided so that service openings in air ducts are accessible for maintenance and inspection needs.
2–3.4.6 Where a service opening is necessary in an air duct located above the ceiling of a floor/roof-ceiling assembly that has been tested and assigned a fire resistance rating in accordance with RS 5–2, access shall be provided in the ceiling and shall be designed and installed so that it does not reduce the fire resistance rating of the assembly.
2–3.5 Air Duct Integrity.
2–3.5.1 Air ducts shall be located where they are not subject to damage or rupture, or they shall be protected to maintain their integrity.
2–3.5.2 Where an air duct is located outdoors, the air duct, together with its covering or lining, shall be protected from harmful elements.
2–3.5.3 Air Duct at Heat Sources—Where electrical, fossil fuel, or solar energy collection heat sources are installed in air ducts, the installation shall avoid the creation of a fire hazard. Air ducts rated as Class 1 in accordance with UL 181/96, Standard for Safety Factory-Made Air Ducts and Air Connectors, air duct coverings, and linings shall be interrupted at the immediate area of operation of such heat sources in order to meet the clearances specified as a condition of the equipment listing.
Exception No. 1: Appliances listed for zero clearance from combustibles where installed in accordance with the conditions of their listings.
Exception No. 2: Insulation specifically suitable for the maximum temperature that reasonably can be anticipated on the duct surface shall be permitted to be installed at the immediate area of operation of such appliances.
2–3.6 Air Outlets.
2–3.6.1 General—Air supplied to any space shall not contain flammable vapors, flyings, or dust in quantities and concentrations that would introduce a hazardous condition.
2–3.6.2 Construction of Air Outlets—Air outlets shall be constructed of noncombustible material or a material that has a maximum smoke developed index/rating of 50 and a maximum flame spread index/rating of 25.
2–3.6.3 Location of Air Outlets.
(a) Air outlets shall be located at least 3 in. (76 mm) above the floor.
Exception: Where provisions have been made to prevent dirt and dust accumulations from entering the system.
(b) Where located less than 7 ft. (2.135 m) above the floor, outlet openings shall be protected by a grille or screen having openings through which a one-half in. (12.7 mm) sphere cannot pass.
(c) Grilles may be located in floors provided they are installed so that they may be removed for cleaning purposes and provided they are constructed as follows:
(1) Grilles up to 3 square feet (0.2787 m 2 ) in gross area shall be designed to support a concentrated live load of 250 lb. (1112 N) on any 4 square inches (2580 mm 2 ) of surface.
(2) Grilles over 3 square feet (0.2787 m 2 ) in gross area shall be designed to support the same loads as the floor in the area where used.
(3) If located where they may be walked upon, the opening in grilles shall reject a one-half inch (12.7 mm) sphere.
2–3.7 Air Inlets (Return or Exhaust or Return and Exhaust).
2–3.7.1 General—Air shall not be recirculated from any space in which flammable vapors, flyings, or dust is present in quantities and concentrations that would introduce a hazardous condition into the return air system.
2–3.7.2 Construction of Air Inlets—Air inlets shall be constructed of noncombustible material or a material that has a maximum flame spread index/rating of 25 and a maximum smoke developed index/rating of 50.
2–3.7.3 Location of Air Inlets.
(a) Air inlets shall be located at least 3 in. (76 mm) above the floor.
Exception: Where provisions have been made to prevent dirt and dust accumulations from entering the system.
(b) Where located less than 7 ft. (2.135 m) above the floor, inlet openings shall be protected by a grille or screens having openings through which a one-half in. (12.7 mm) sphere cannot pass.
(c) Grilles may be located in floors provided they are installed so that they may be removed for cleaning purposes and provided they are constructed as follows:
(1) Grilles up to 3 square feet (0.2787 m 2 ) in gross area shall be designed to support a concentrated live load of 250 lb. (1112 N) on any 4 square inches (2580 mm 2 ) of surface.
(2) Grilles over 3 square feet (0.2787 m 2 ) in gross area shall be designed to support the same loads as the floor in the area where used.
(3) If located where they may be walked upon, the opening in grilles shall reject a one-half inch (12.7 mm) sphere.
2–3.8 Fire Dampers—Approved fire dampers shall be provided as required in Chapter 3 and installed in conformance with the conditions of their listings.
2–3.9 Smoke Dampers.
2–3.9.1 Approved smoke dampers shall be provided as required in Chapter 3 and installed in conformance with the conditions of their listings.
2–3.9.2 Smoke dampers shall be installed in systems with a capacity greater than 15,000 cfm (7079 L/s) to isolate the air-handling equipment, including filters, from the remainder of the system in order to restrict the circulation of smoke.
Exception No. 1: Where the air-handling unit is located on the floor that it serves and serves only that floor.
Exception No. 2: Where the air-handling unit is located on the roof and serves only the floor immediately below the roof.
Exception No. 3: Existing buildings using only Class 1 filters shall be exempt from this subdivision provided the control system is arranged to shut down the fresh air intake, return air, and exhaust air dampers, and fan shutdown and smoke detection are provided in accordance with §4–4.
2–3.10 Plenums.
2–3.10.1 Ceiling Cavity Plenum—The space between the top of the finished ceiling and the underside of the floor or roof above shall be permitted to be used to supply air to, or return or exhaust air from, or return and exhaust air from the occupied area provided that the following conditions are met:
(a) All materials exposed to the airflow shall be noncombustible or limited combustible and have a maximum smoke developed index/rating of 50.
Exception No. 1: The following materials shall be permitted in the ceiling cavity plenum where listed as having a maximum peak optical density of 0.5 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 5 ft. (1.525 m) or less when tested in accordance with the specified test method:
(a) Electrical wires and cables—Electrical wires and cables shall be installed in accordance with the NYC Electrical Code.
(b) Pneumatic tubing for control systems—UL 1820/94, Standard for Safety Fire Test of Pneumatic Tubing for Flame and Smoke Characteristics Only.
(c) Optical-fiber cables—Optical-fiber cables shall be installed in accordance with the NYC Electrical Code.
(d) Optical-fiber cable raceway Optical-fiber cable raceway shall be installed in accordance with the NYC Electrical Code.
(e) Fire alarm cables—Fire alarm cables shall be red, type FPLP, and be installed in accordance with Reference Standards RS 17-3, RS 17-3A, RS 17-3B, and RS 17-3C, and be tested and listed in accordance with the requirements of UL 1424/90, UL 910/95 and the City of New York, and shall be marked with the company name, type FPLP, size (AWG), minimum temperature rating 150°C (UL), Also Classified NYC CERT Fire Alarm Cable.
Exception No. 2: Smoke detectors.
Exception No. 3: Loudspeakers, loudspeaker assemblies, and their accessories shall be permitted in the ceiling cavity plenum where listed as having a maximum peak optical density of 0.5 or less, an average optical density of 0.15 or less, and a peak heat release rate of 100 kW or less when tested in accordance with UL 2043/92, Standard for Safety Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces.
(b) The integrity of the firestopping for penetrations shall be maintained.
(c) Light diffusers, other than those made of metal or glass, used in air-handling light fixtures shall be listed and marked "Fixture Light Diffusers for Air-Handling Fixtures."
(d) The temperature of air delivered to these plenums shall not exceed 250°F (121°C).
(e) Materials used in the construction of a ceiling plenum shall be suitable for continuous exposure to the temperature and humidity conditions of the environmental air in the plenum.
(f) Where the plenum is a part of a floor-ceiling or roof-ceiling assembly that has been tested or investigated and assigned a fire resistance rating of 1 hour or more, the assembly shall meet the requirements of 3-3.3.
(g) All portions of the ceiling cavity plenum shall be designed to withstand the maximum air pressure differential that may be developed.
2–3.10.2 Duct Distribution Plenum—A duct enclosure used for the multiple distribution or gathering of ducts or connectors shall be constructed of materials and methods specified in 2–3.1.
2–3.10.3 Apparatus Casing Plenum—A fabricated plenum and apparatus casing shall be permitted to be used for supply, return, or exhaust air service and shall be constructed of materials and methods specified in 2–3.1, and in accordance with the following:
(a) The casing and plenum construction standards, as per RS 14–22.
(b) Paragraph 2–3.3 for all air duct coverings, duct lining acoustical liner/cells, and miscellaneous materials.
2–3.10.4 Air-Handling Unit Room Plenum.
(a) Individual rooms containing an air-handling unit(s) gather return air from various sources and combine the return air within the room for returning to the air-handling unit. Duct covering, duct lining, acoustical liner/cells, and miscellaneous materials shall comply with 2–3.3.
(b) Air-handling unit room plenums shall not be used for storage or occupied other than during equipment servicing.
2–3.10.5 Raised Floor Plenum—The space between the top of the finished floor and the underside of a raised floor shall be permitted to be used to supply air to, or return exhaust air from, or return and exhaust air from the occupied area, provided that the following conditions are met:
(a) All materials exposed to the airflow shall be noncombustible or limited combustible and shall have a maximum smoke developed index/rating of 50.
Exception No. 1: The following materials shall be permitted in the raised floor plenum where listed as having a maximum peak optical density of 0.5 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 5 ft. (1.525 m) or less when tested in accordance with the specified test method:
(a) Electrical wires and cables—Electrical wires and cables shall be installed in accordance with the NYC Electrical Code.
(b) Pneumatic tubing for control systems—UL 1820/94, Standard for Safety Fire Test of Pneumatic Tubing for Flame and Smoke Characteristics Only.
(c) Optical-fiber cables—Optical-fiber cables shall be installed in accordance with the NYC Electrical Code.
(d) Optical-fiber cable raceway—Optical-fiber cable raceway shall be installed in accordance with the NYC Electrical Code.
(e) Fire alarm cables—Fire alarm cables shall be red, type FPLP, and be installed in accordance with Reference Standards RS 17–3, RS 17–3A, RS 17–3B, and RS 17–3C, and tested and listed in accordance with the requirements of UL 1424/90, UL 910/95 and the City of New York, and shall be marked with the company name, type FPLP, size (AWG), minimum temperature rating 150°C (UL), Also Classified NYC CERT Fire Alarm Cable.
Exception No. 2: Raised floors, intermachine cables, electrical wires, listed plenum optical-fiber cable raceways, and optical-fiber cables in computer/data processing rooms where these rooms are designed and installed in accordance with NFPA 75/95, Standard for the Protection of Electronic Computer/Data Processing Equipment.
Exception No. 3: Smoke detectors.
(b) The integrity of the firestopping for penetrations shall be maintained.
(c) The temperature of air delivered to these plenums shall not exceed 250°F (121°C).
(d) Materials used in the construction of a raised floor plenum shall be suitable for continuous exposure to the temperature and humidity conditions of the environmental air in the plenum.
2–3.11 Corridor Air Systems.
2–3.11.1 Egress Corridors—Except in fully sprinklered office buildings, public corridors shall not be used as a portion of direct supply, return, or exhaust air system serving adjoining areas. Air transfer because of pressure differential in health care occupancies from corridors is permitted. An air transfer opening(s) shall not be permitted in walls or in doors separating egress corridors from adjoining areas.
Exception No. 1: Toilet rooms, bathrooms, shower rooms, sink closets, and similar auxiliary spaces opening directly onto the egress corridor.
Exception No. 2: Where door clearances do not exceed those specified for fire doors in RS 5–8, air transfer caused by pressure differentials shall be permitted.
Exception No. 3: Use of egress corridors as part of an engineered smoke-control system.
Exception No. 4: In detention and correctional occupancies with corridor separations of open construction (e.g., grating doors or grating partitions).
Exception No. 5: In existing buildings classified in Occupancy Group J-1 ventilation may be provided in accordance with § 27-777.2(a) of the Administrative Code.
Exception No. 6: In institutions as classified in article 10 of subchapter 3 of the Administrative Code provided the system(s) serving the corridor have smoke detectors located as required in §4–4.1 of this Reference Standard that will shut down fans upon activation.
2–3.11.2 Exits—Exit passageways, stairs, ramps, and other exits shall not be used as a part of a supply, return, or exhaust air system serving other areas of the building.
2–3.12 Smoke Control—Where a smoke-control or exhaust system is required, it shall conform to the requirements of the building code.