NYC Administrative Code RS 13-1, Chapter 4 CONTROLS
4–1 Wiring—The installation of electrical wiring and equipment associated with the operation and control of air conditioning and ventilating systems shall be in accordance with the Electrical Code of the City of New York.
4–2 Manual Control—Each air distribution system shall be provided with not less than one manually operable means to stop the operation of the supply, return, and exhaust fan(s) in an emergency. The means of manual operation shall be located at an approved location.
4–2.1 Any building classified in Occupancy Group E, 75 feet (22.840 m) or more in height, and any existing office building 100 feet (30.450 m) or more in height where a system serves floors other than the floor on which the equipment is located, in addition to the controls required by this chapter, shall be provided with:
(a) Manual controls for operating individually each air supply and each exhaust or return fan in the system located as follows:
(1) At the Fire Command Station (or in a mechanical control center in existing buildings only), and
(2) In the room containing the affected air handling fans.
(b) Manual controls for operating individually or in groups each remote control reversible fire shutter, when such shutters are provided in accordance with the provisions of § 27-972 of the Administrative Code, or each smoke damper provided in accordance with the provisions of § 27-777.1(b) of the Administrative Code, shall be located at the Fire Command Station (or in a mechanical control center in existing buildings only).
4–2.2 Manual Restart of Fans After Reset of an Automatic Fire Detecting Device or Fire Alarm System—Fans or fan systems which have been automatically shut down on activation of an automatic fire detecting device or fire alarm system shall be arranged and equipped not to automatically restart when either the automatic fire detecting device or fire alarm system is reset. The manual means of restarting the fans or fan system shall function independently from the manual resetting of either the automatic fire detecting device or fire alarm system.
4–3 Smoke Dampers.
4–3.1 Smoke dampers shall be activated by an automatic smoke and/or alarm initiating device. Smoke dampers that are part of an engineered smoke control system shall be capable of being positioned manually from a command station. Such positioning devices shall be provided, for supply and return/exhaust dampers, grouped by floor and by type (i.e. supply or return/exhaust). Damper switch positions shall indicate whether the related dampers are commanded to be either open or closed.
Smoke damper positioning switches shall be located at the Fire Command Station, or in a mechanical control center in buildings without a Fire Command Station.
Refer to § 27-777.1(b) of the Building Code for additional requirements.
4–3.2 Smoke dampers installed to isolate the air-handling system in accordance with 2–3.9.2 shall be arranged to close automatically when the system is not in operation.
4–3.3 Smoke dampers installed in smoke barriers shall be permitted to remain open during fan shutdown, provided their associated controlling damper actuators and smoke detectors remain operational.
4–4 Smoke Detection for Automatic Control.
4–4.1 Location—Smoke detectors listed for use in air distribution systems shall be located:
(a) Downstream of the air filters and ahead of any branch connections in air supply systems having a capacity greater than 2000 cfm (944 L/s).
(b) At each story in buildings classified in Occupancy Group E, 75 ft. (22.838 m) or more in height, and in existing office buildings 100 ft. (30.450 m) or more in height prior to the connection to a return air shaft in air return systems having a capacity greater than 15,000 cfm (7080 L/s) and serving more than one story except that in an existing office building 100 feet (30.450 m) or more in height where compliance would cause practical difficulty or undue hardship, the Commissioner may approve other locations for such devices fulfilling the intent of the requirement.
(c) In the return air stream, prior to exhausting from the building and prior to any recirculation or fresh air inlet connection in air return systems having a capacity equal to or greater than 15,000 cfm (7080 L/s) arranged to either automatically exhaust the smoke laden return air or to stop the fan.
Exception No. 1: Return system smoke detectors shall not be required where the entire space served by the air distribution system is protected by a system of area smoke detectors.
Exception No. 2: Fan units whose sole function is to remove air from the inside of the building to the outside of the building.
Exception No. 3: Systems meeting the criteria for Exceptions Nos. 1 or 2 in §2–3.9.2.
Exception No. 4: Smoke detectors provided in accordance with (b) above shall fulfill the requirement of (c) above.
4–4.2 Function—Smoke detectors provided as required by 4–4.1 shall automatically stop their respective fan(s) upon detecting the presence of smoke.
Exception: Where the return air fan is functioning as part of an engineered smoke-control system and a different mode is required.
4–4.3 Installation.
4–4.3.1 In addition to the requirements of 4–4.2, where an approved protective signaling system is installed in a building, the smoke detectors required by the provisions of §§4–3 and 4–4 shall be connected to the protective signaling system in accordance with the requirements of the Building Code, so that the activation of any air distribution system smoke detector causes a supervisory signal to be indicated at a constantly attended location or causes an alarm signal.
4–4.3.2 Where smoke detectors required by §4–4 are installed in a building not equipped with an approved protective signaling system as specified by 4–4.3.1:
(a) The smoke detector activation required by §4–4 shall cause a visual and an audible signal in a normally occupied area; and
(b) Smoke detector trouble conditions shall be indicated visually or audibly in a normally occupied area and shall be identified as air duct detector trouble.
4–4.3.3 Smoke detectors powered separately from the signaling system for the sole function of stopping fans shall not require standby power.
4–4.3.4 When any building or floor is provided with an air system utilizing recirculated air and is protected by an automatic sprinkler system or an automatic fire alarm system, provision shall be made to automatically stop the fans serving the affected area when the sprinkler system or fire alarm system operates. Where both sprinkler systems and fire alarm systems are installed in the area, it shall be required to have only one of these systems arranged to stop the fans.
Exception No. 1: Activation of a manual pull station shall not be required to automatically stop the fans.
Exception No. 2: Systems having a capacity of 2,000 cfm or less or serving not more than one floor.